C1400

Solar Collector Factsheet


RUG SC-F25/1
Model SC-F25/1
Type Flat plate collector
Manufacturer RUG Riello Urzadzenia Grzewcze S.A.
Address Ul. Sienna 39

PL-00-121 Warszawa
Telephone +48566571600
Fax +48566571657
Email info@beretta.pl
Internet www.beretta.pl
Test date 12.2008

 Performance test EN12975:2006


 Quality test EN12975:2006

Dimensions Technical data


Total length 2.047 m Minimum flowrate 18 l/h
Total width 1.187 m Nominal flowrate 75 l/h
2
Gross area 2.430 m Maximum flowrate 150 l/h
2
Aperture area 2.195 m Fluid content 1.6 l
2
Absorber area 2.161 m Maximum operating pressure 10 bar
Weight empty 40 kg Stagnation temperature 204 °C

Types of mounting Further information


 Construction for sloping roof  Units in different sizes available
 Integration into sloping roof  Glazing replaceable
 On flat roof with stand Hydraulic connection
 Facade Copper pipe, nominal diameter 22 mm

Construction
1 Cover rail
2 Frame
3 Glazing
4 Sealing profile
5 Absorber
6 Thermal insulation
7 Rear panel

SPF Testing, Institut für Solartechnik SPF, Hochschule für Technik Rapperswil HSR, CH-8640 Rapperswil, Switzerland
13.09.2011 / SCFv3.0en www.solarenergy.ch page 1/2
~
C1400
Peak Power per collector unit Wpeak Relative efficiency η
[kW] 2.0 Solar irradiance G=1000 W/m2 1.0 Solar irradiance G=800W/m2
1.8
1.6 0.8
1.4
1.2 0.6
1.0
0.8 0.4
0.6
0.4 0.2
0.2
0.0 0.0
0 20 40 60 80 Tm-T100
amb 0 0.02 0.04 0.06 0.08 T0.1
m
*

Peak Power Wpeak 1724 W Reference Gross Aperture Absorber


Thermal capacity* 5.6 kJ/K η0 0.710 0.786 0.798
Flowrate during test 140 l/h a1 [WK-1m-2] 3.80 4.20 4.27
-2 -2
Fluid for test Water-Glycol 33.3% a2 [WK m ] 0.0027 0.0030 0.0030
*) Specific thermal capacity C of the collector without fluid, determined according to 6.1.6.2 of EN12975-2:2006

Incident angle modifier IAM Pressure drop ∆p


1.2 [Pa] 3000

1.0 2500

0.8 2000

0.6 1500

0.4 1000

0.2 IAML=IAMT 500

0.0 0
0 10 20 30 40 50 60 70 80 θ
90 0 50 100 150 200 [l/h]
250

K1, transversal IAM at 50° 0.92 Pressure drop at nominal flowrate


K2, longitudinal IAM at 50° 0.92 ∆p = 631 Pa (T=20°C)

SPF Simulation of systems using Polysun


Short description of the system Surface demand** Solar yield**
Climate: Central Switzerland, orientation of the collectors: South, Number of collectors
Cold water 10°C, Hot water 50°

Domestic hot water: Fss* = 60%


Tank 450 l, collector inclination 45°, 5.25 m2
484 kWh/m2
Daily energy demand 10 kWh (4-6 persons) 2.4 collectors
Energy demand of the reference system 4200 kWh/year
Water pre-heating: Fss* = 25%
2 Tanks: 1500 l & 2500 l, collector inclination 30°, 67.2 m2
Domestic hot water consumption 10’000 l/day (200 persons) 715 kWh/m2
Daily heat losses (circulation and tanks) 60 kWh, 30.6 collectors
Energy demand of the reference system 191'700 kWh/year
Space heating system: Fss* = 25%
Combined storage1200 l, collector inclination 45°,
2
Daily energy demand 10 kWh (4-6 persons), Building 200 m , moderately 16.8 m2
321 kWh/m2
heavy construction, well insulated, Heating power demand 5.8 kW (ambient 7.7 collectors
temperature -8°C), Energy demand space heating 12140 kWh/year,
Energy demand of the reference system 16340 kWh/year

*) Fractional solar savings: Proportion of the final energy that, thanks to the solar system, can be saved compared to a reference system.
**) Surface demand and solar yield are given with respect to the aperture area.

SPF Testing, Institut für Solartechnik SPF, Hochschule für Technik Rapperswil HSR, CH-8640 Rapperswil, Switzerland
13.09.2011 / SCFv3.0en www.solarenergy.ch page 2/2