RXQ6-20AYM(W) / RXQ18-60AMYM(W) EDRMT341773D

Model Name (Combination Unit) RXQ38AMYM(W) RXQ40AMYM(W)


Model Name (Independent Unit) RXQ18AYM(W)+RXQ20AYM(W) RXQ20AYM(W)+RXQ20AYM(W)
Power supply 3 phase, 380-415/380 V, 50/60 Hz 3 phase, 380-415/380 V, 50/60 Hz
kcal/h 91,200 96,300
1 Cooling capacity Btu/h 362,000 382,000
kW 106 112
Casing color Ivory white (5Y7.5/1) (Metallic brown H3) Ivory white (5Y7.5/1) (Metallic brown H3)
Dimensions: (H×W×D) mm (1,657×1,240×765)+(1,657×1,240×765) (1,657×1,240×765)+(1,657×1,240×765)
Heat exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type

Compressor Motor output× kW (4.0×1)+(4.0×1)+(3.8×1)+(6.3×1) (3.8×1)+(6.3×1)+(3.8×1)+(6.3×1)


Number of units
Starting method Soft start Soft start
Type Propeller fan Propeller fan
Motor output kW (0.75×2)+(0.75×2) (0.75×2)+(0.75×2)
Fan
Airflow rate m³/min 257+297 297+297
Drive Direct drive Direct drive
Connecting Liquid pipe mm f19.1 C1220T (Brazing connection) f19.1 C1220T (Brazing connection)
pipes Gas pipe mm f41.3 C1220T (Brazing connection) f41.3 C1220T (Brazing connection)
Mass kg 260+285 (280+310 H3) 285+285 (310+310 H3)
2 Sound pressure level dB(A) 66 68
High pressure switch, Fan driver overload High pressure switch, Fan driver overload
Safety devices protector, Over current relay, Inverter overload protector, Over current relay, Inverter overload
protector protector
Capacity control % 4-100 3-100
Refrigerant name R410A R410A
Refrigerant Charge kg 8.4+11.8 11.8+11.8
Control Electronic expansion valve Electronic expansion valve
Refrigerator oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Installation manual, Operation manual,
Standard accessories Connection pipes, Clamps Connection pipes, Clamps
Specifications — —
Drawing No.
Sound level — —

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. kcal/h=kW×860
During actual operation, these values are normally somewhat higher as a result of ambient conditions and Btu/h=kW×3412
oil recovery mode.
When there is concern for noise the surrounding area such as residences, we recommend investigating
the installation location and taking soundproofing measures.
+3. Models with (W) are the outdoor units with anti-corrosion specifications. For details, refer to Anti-Corrosion
Model (W type) in Part 5 Guide Specifications.