Professional Documents
Culture Documents
KIOLDÁSI GÖRBE - Schneider - IEC
KIOLDÁSI GÖRBE - Schneider - IEC
Customizedtrippingcurve
PE0
Defined point by point using the SFT2841 setting and operating software tool, this
curve may be used to solve all special cases involving protection coordination or
revamping.
3
Customized tripping curve set using SFT2841 software.
IECcurves
Equation Curvetype Coefficient values
k a b
Standard inverse / A 0.14 0.02 2.97
k T
t d( I) = ---------------------- × --- Very inverse / B 13.5 1.50
--I--- – 1 b
a
Long time inverse / B 0 13.33
Is
Extremely inverse / C 0 0.808
Ultra inverse 315.2 2.5
RIcurve
Equation: 1 T
td ( I ) = -------------------------------------------------------- × -------------------
I –1 3 ,1706
0 ,339 – 0,236 -----
Is
IEEEcurves
Equation Curvetype Coefficient values
A B p b
Moderately inverse 0.010 0.023 0.02 0.241
A T Very inverse 3.922 0.098 0.138
td ( I ) = ------------------------ + B × ---
I p b Extremely inverse 5.64 0.0243 0.081
-Is
---
–
1
IEEEcurves
Equation Curvetype Coefficient values
A B C D E b
Inverse 0.208 0.863 0.800 -0.418 0.195 0.297
B D E T Very inverse 0.090 0.795 0.100 -1.288 7.958 0.165
td ( I ) = A + -------------------- + ----------------------- + ----------------------- x -----
---I- – C ---I-- – C
2
---I-- – C b
3 Extremely inverse 0.004 0.638 0.620 1.787 0.246 0.092
Is Is Is
0