Fire Case Relief Load Estimation For Unwetted Surface (Gas Full Vessel)

Reference: API Standard 520, DEP 80.45.10.10 (Pressure relief, emergency depressuring, flare and vent systems).

F'A' where A is the required orifice area in in 2, A' is exposed vessel area in ft2, P1 is
A= ------------ upstream releiving pressure in psia
P1^0.5

Adequate drainage and firefighthing Adequate drainage and firefighthing


equipment exist
q=21,000FA^(-0.18) equipment DO NOT exist
Q=34,500FA^0.82
Q=21,000FA^0.82

Relief valve tag number: 72PRV-320

Case: Fire

D: Diameter of vessel m 1.200


H: Height/length of vessel m 3.000
E: Vessel BTL above grade /Elevation (for horizontal arrangement) m 1.5
Type of vessel orientation (H=Horizontal, V=Vertical) V
Type of vessel head (E=2:1 Elliptical, H=Hemisphere,T=Torrispherical) E
M Molecular weight of gas 28.95
k: Ratio of specific heats 1.38
F: Environment factor (refer table 5, API 521) 1.00
-

Check of height (is higher than 8 m?) Within the fire height

H': Height of vessel within 8 m m 3.0000


A 1: Surface area of cylinder exposed to external fire m2 11.31
A 2: Surface area of head exposed to external fire m2 1.56
Av: Vessel surface area m2 12.87
Piping Area m2 0.00
Design Margin on Total Wetted Surface Area % 10.00
A': Total exposed surface area m2 14.16
ft2 152.39
Tw: Vessel wall temperature °
C 300
°
R 1031.69
T n: Normal operating gas temperature °
C 58
°
R 596.09
T1 : Relief temperature °
C 268.77
°
R 975.47
C: Constant based on ratio of specific heats (k) 354.02
(if k is unknown C=315 is used)
F': Factor "F" Insert K or U K
K=Known (Recommended minimum value,F' = 0.01) 0.0100
U=Unknown (Minimum unknown, F' = 0.045)

Pn: Normal pressure barg 7


Ps: Set pressure barg 10.00
A c: Permitted accumulation % 21
P1: Relief pressure (absolute) bara 13.1
psia 190

K d: Effective coefficient of discharge 0.9750


:0.975 when RV is installed with or without a rupture disk
:0.62 when RV is NOT installed and sizing is for a rupture disk

A: Required effective discharge area in2 0.11050


ft2 0.00077
cm2 0.71291

Required standard size 25E50 Orifice Area cm2 1.26

W: Relief load lb/hr 89


kg/hr 40.37
Note: Enter data for BLUE ones only; BLACK ones are calculated
0
0 25D49 0 0 0.71
0.71 25D50 0.71 25D50 0.71 1.26
1.26 25E50 1.26 25E50 1.26 1.98
1.98 40F50 1.98 40F50 1.98 3.25
3.25 50G80 5.06 50H80 3.25 5.06
5.06 50H80 11.86 80K100 5.06 8.3
8.3 50J80/80J100 18.41 100L150 8.3 11.86
11.86 80K100 41.16 100P150 11.86 18.41
18.41 100L150 71.23 150Q200 18.41 23.23
23.23 100M150 103.23 150R250 23.23 28
28 100N150 167.74 200T250 28 41.16
41.16 100P150 41.16 71.23
71.23 150Q200 71.23 103.23
103.23 150R250 103.23 167.4
167.4 200T250 167.4 Too High

@IF(H49<0.7,"25D50",@IF(H49<1.26,"25E50",@IF(H49<1.98,"40F50",@IF(H49<5.06,"50H80",@IF(
@IF(B50<0.71,0.71,@IF(B50<1.26,1.26,@IF(B50<1.98,1.98,@IF(B50<5.06,5.06,@IF(B50<11.86,11.86
IF(H49<5.06,"50H80",@IF(H49<11.86,"80K100",@IF(H49<18.41,"100L150",@IF(H49<41.16,"100P150",@IF(H49<71.23,"1
6,5.06,@IF(B50<11.86,11.86,@IF(B50<18.41,18.41,@IF(B50<41.16,41.16,@IF(B50<71.23,71.23,@IF(B50<103.23,103.23,@
50",@IF(H49<71.23,"150Q200",@IF(H49<103.23,"150R250",@IF(H49<167.7,"200T250",""))))))))))
(B50<103.23,103.23,@IF(B50<167.75,167.75,""))))))))))

You might also like