You are on page 1of 684

Anglo American Quellaveco S.A.

Digitally signed MQ15-08-TE-3340-FS0001


by Maria del
CPF Quellaveco Project Carmen, Andia Page 1 of 684
Merma
Date: 2022.11.20
13:07:52 -05'00'

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

This document has been revised as indicated below and described in the revision log on the next page. Please
destroy all previous revisions.

Revision Date Name and Signature Name and Signature of Reviewer / Pages
No. of the issuer (Contractor) Approver
(Contractor)
A 05-11-2021 Charles Helfer Cameron McGregor 138
B 16-11-2021 Charles Helfer Cameron McGregor 138
B1 24-05-2022 Charles Helfer Cameron McGregor 329
B2 29-08-2022 Charles Helfer Cameron McGregor 661
B3 11-10-2022 Charles Helfer Cameron McGregor 683
0 03-11-2022 Charles Helfer Cameron McGregor 683

APPROVERS SIGNATURE DATE

Engineering Manager

Area Manager

Project Manager Cameron McGregor 2022-11-04

Client: Francisco Araya

ISSUED FOR: Design x Construction Other:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 2 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Revision Log

Revision
Date Description

A 05-11-2021 Issued for Internal Review

B 16-11-2021 Issued for Client Review

B1 25-05-2022 Issued for Approval

B2 29-08-2022 Issued for Approval

B3 11-10-2022 Issued for Approval

0 03-11-2022 Issued As Approved

© 2019 Anglo American Quellaveco S.A. This document contains intellectual property of Anglo
American Quellaveco S.A. (“Anglo American”) and/or its affiliates and is subject to legal
restrictions as to its use. Recipients may not copy, distribute, disseminate, disclose or otherwise
use this document or the contents hereof except as is specifically authorized by Anglo American.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 3 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TABLE OF CONTENTS

1.0 INTRODUCTION ........................................................................................................................................ 28

2.0 PROCESS DESCRIPTION ....................................................................................................................... 28


2.1 Coarse Particle Feed Classification and Desliming (3340 – PLC – 101A) ................................... 30
2.2 Coarse Particle Separation (3340 – PLC – 101 B and C) .............................................................. 31
2.3 Coarse Particle Flotation (3340 – PLC – 101 B and C) ................................................................. 32
2.4 Concentrate Thickening (3340 – PLC – 101 A).............................................................................. 32
2.5 Concentrate Regrinding (3340 – PLC – 101 A).............................................................................. 33
2.6 Concentrate Return (3340 – PLC – 101 A)..................................................................................... 35
2.7 Reagents (3340 – PLC – 101 A) ....................................................................................................... 36
2.8 Utilities (Process and Fluidization Water) (3340 – PLC – 101 A) ................................................ 36
2.9 Utilities (Make-Up and Gland Seal Water) (3340 – PLC – 101 A) ............................................... 37
2.10 Utilities (Compressed Air) (3340 – PLC – 101 A) .......................................................................... 38
2.11 Global Start / Stop Sequence ........................................................................................................... 39

3.0 REFERENCES............................................................................................................................................ 42

4.0 DESCRIPTION OF CONTROL ................................................................................................................ 49


1.1 Objectives of Control........................................................................................................................ 49

5.0 STRUCTURE OF PLC SOFTWARE ....................................................................................................... 50

6.0 UNIDAD: CDCPF_DESLAMADO ........................................................................................................... 61


6.1 Sub Module 3340BX101 ................................................................................................................... 62
6.2 Engineering Module 2 - 3340XM100 .............................................................................................. 64
6.3 Engineering Module 2 – 3340PU101 ............................................................................................... 66
6.4 Engineering Module 2 – 3340PU102 ............................................................................................... 77
6.5 Engineering Module 2 – 3340PU174 ............................................................................................... 88
6.6 Engineering Module 1 – 3340Clasif001 .......................................................................................... 90
6.7 Engineering Module 2 – 3340CY101 ............................................................................................... 91
6.8 Engineering Module 2 – 3340CY102 ............................................................................................... 96

7.0 UNIDAD: SFCPF_ALIMFLUJOCRUZADO ......................................................................................... 101


7.1 Engineering Module– 3340PU185 ................................................................................................. 106
7.2 Engineering Module– 3340PU186 ................................................................................................. 115
7.3 Engineering Module – 3340DB103 ................................................................................................ 125
7.4 Engineering Module – 3340DB104 ................................................................................................ 127
7.5 Engineering Module – 3340PU198 ................................................................................................ 129

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 4 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.0 UNIDAD: SFCPF_SEPHFL1 .................................................................................................................. 132


8.1 Engineering Module 1 – 3340SepHF101 ....................................................................................... 133
8.2 Engineering Module 2 – 3340CF101 ............................................................................................. 136
8.3 Engineering Module 2 – 3340HF101 ............................................................................................. 142
8.4 Engineering Module 1 – 3340SepHF102 ....................................................................................... 152
8.5 Engineering Module 2 – 3340CF102 ............................................................................................. 154
8.6 Engineering Module 2 – 3340HF102 ............................................................................................. 159
8.7 Engineering Module 1 – 3340SepHF103 ....................................................................................... 169
8.8 Engineering Module 2 – 3340CF103 ............................................................................................. 171
8.9 Engineering Module 2 – 3340HF103 ............................................................................................. 176
8.10 Engineering Module 1 – 3340SepHF104 ....................................................................................... 186
8.11 Engineering Module 2 – 3340CF104 ............................................................................................. 188
8.12 Engineering Module 2 – 3340HF104 ............................................................................................. 193
8.13 Engineering Module 1 – 3340SepHF105 ....................................................................................... 203
8.14 Engineering Module 2 – 3340CF105 ............................................................................................. 205
8.15 Engineering Module 2 – 3340HF105 ............................................................................................. 210

9.0 UNIDAD: SFCPF_SEPHFL2 .................................................................................................................. 221


9.1 Engineering Module 1 – 3340SepHF106 ....................................................................................... 222
9.2 Engineering Module 2 – 3340CF106 ............................................................................................. 224
9.3 Engineering Module 2 – 3340HF106 ............................................................................................. 229
9.4 Engineering Module 1 – 3340SepHF107 ....................................................................................... 239
9.5 Engineering Module 2 – 3340CF107 ............................................................................................. 241
9.6 Engineering Module 2 – 3340HF107 ............................................................................................. 246
9.8 Engineering Module 1 – 3340SepHF108 ....................................................................................... 255
9.9 Engineering Module 2 – 3340CF108 ............................................................................................. 257
9.10 Engineering Module 2 – 3340HF108 ............................................................................................. 262
9.12 Engineering Module 1 – 3340SepHF109 ....................................................................................... 271
9.13 Engineering Module 2 – 3340CF109 ............................................................................................. 273
9.14 Engineering Module 2 – 3340HF109 ............................................................................................. 278
9.16 Engineering Module 1 – 3340SepHF110 ....................................................................................... 287
9.17 Engineering Module 2 – 3340CF110 ............................................................................................. 289
9.18 Engineering Module 2 – 3340HF110 ............................................................................................. 294

10.0 UNIDAD: CRCFP_RELAVES ................................................................................................................ 304


10.1 Engineering Module – 3340PU170 ................................................................................................ 309
10.2 Engineering Module– 3340PU197 ................................................................................................. 311

11.0 UNIDAD: RECPF_COLLECTOR3894 .................................................................................................. 317


11.1 Engineering Module– 3520PU179 ................................................................................................. 332

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 5 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

11.2 Engineering Module– 3350PU120_121 ......................................................................................... 335


11.3 Engineering Module 2 – 3350PU120 ............................................................................................. 337
11.4 Engineering Module 2 – 3350PU121 ............................................................................................. 340

12.0 UNIDAD: RECPF_COLLECTOR404 .................................................................................................... 345


12.1 Engineering Module– 3520PU182 ................................................................................................. 360
12.2 Engineering Module 2 – 3350PU160 ............................................................................................. 363
12.3 Engineering Module 2 – 3350PU161 ............................................................................................. 367

13.0 UNIDAD: RECPF_COLLECTORZ6 ...................................................................................................... 372


13.1 Engineering Module– 3520PU181 ................................................................................................. 387
13.2 Engineering Module 2 – 3350PU150 ............................................................................................. 390
13.3 Engineering Module 2 – 3350PU151 ............................................................................................. 394

14.0 UNIDAD: RECPF_COLLECTORDIESEL ............................................................................................ 399


14.1 Engineering Module– 3520PU180 ................................................................................................. 414
14.2 Engineering Module 2 – 3350PU130 ............................................................................................. 417
14.3 Engineering Module 2 – 3350PU131 ............................................................................................. 421

15.0 UNIDAD: RECPF_ALMESPUMANTE .................................................................................................. 426


15.1 Engineering Module– 3350PU178 ................................................................................................. 428
15.2 Engineering Module– 3350PU176_177 ......................................................................................... 430
15.3 Engineering Module 2 – 3350PU199 ............................................................................................. 433

16.0 UNIDAD: RECPF_ ESPUMANTE ......................................................................................................... 436


16.1 Engineering Module 2 – 3350PU140 ............................................................................................. 450
16.2 Engineering Module 2 – 3350PU141 ............................................................................................. 454

17.0 UNIDAD: FCPF_ALIMENTACION ........................................................................................................ 459


17.0 Engineering Module – 3520PU195 ................................................................................................ 460
17.1 Engineering Module – 3520PU196 ................................................................................................ 463
17.2 Engineering Module – 3340MX001 ............................................................................................... 467
17.3 Engineering Module – 3340MX002 ............................................................................................... 472
17.4 Engineering Module – 3340MX003 ............................................................................................... 476

18.0 UNIDAD: ECPF_ALIMENTACION ........................................................................................................ 482


18.0 Engineering Module – 3340BX109 ................................................................................................ 483
18.1 Engineering Module – 3340XV302_303A ..................................................................................... 485
18.2 Engineering Module – 3340XV302_303B ..................................................................................... 487
18.3 Engineering Module – 3340XV302_303C ..................................................................................... 490
18.4 Engineering Module 2 – 3340PU171 ............................................................................................. 493

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 6 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

19.0 UNIDAD: ECPF_3340TH101 ................................................................................................................. 497


19.1 Engineering Module 2 – 3340TH101UF ....................................................................................... 502
19.2 Engineering Module 2 – 3340TH101_RECIR .............................................................................. 511

20.0 UNIDAD: ECPF_3340TH102 ................................................................................................................. 515


20.1 Engineering Module 2 – 3340TH102UF ....................................................................................... 520
20.2 Engineering Module 2 – 3340TH102_RECIR .............................................................................. 529

21.0 UNIDAD: ECPF_3340TH103 ................................................................................................................. 533


21.1 Engineering Module 2 – 3340TH103UF ....................................................................................... 538
21.2 Engineering Module 2 – 3340TH103_RECIR .............................................................................. 547

22.0 UNIDAD: RMCPF_3340BX103.............................................................................................................. 551


22.1 Engineering Module– 3340PU106 ................................................................................................. 555
22.2 Engineering Module– 3340PU107 ................................................................................................. 564
22.3 Engineering Module – 3340CY110................................................................................................ 572
22.4 Engineering Module – 3340PU173 ................................................................................................ 577
22.5 Engineering Module – 3340PU175 ................................................................................................ 579

23.0 UNIDAD: RMCPF_ALIMENTACION .................................................................................................... 583

24.0 UNIDAD: RMCPF_3340MI101 ............................................................................................................... 586

25.0 UNIDAD: RMCPF_3340MI102 ............................................................................................................... 590

26.0 UNIDAD: CRCFP_RETORNOCONC ................................................................................................... 594


26.1 Engineering Module– 3340PU110 ................................................................................................. 600
26.2 Engineering Module– 3340PU190 ................................................................................................. 605
26.3 Engineering Module– 3340PU111 ................................................................................................. 611
26.4 Engineering Module– 3340PU191 ................................................................................................. 620

27.0 UNIDAD: SCPF_AGUAPROCESOS .................................................................................................... 627


27.1 Engineering Module– 3340PU112 ................................................................................................. 632
27.2 Engineering Module– 3340PU114 ................................................................................................. 636
27.3 Engineering Module– 3340PU115 ................................................................................................. 641
27.4 Engineering Module– 3340PU109 ................................................................................................. 644
27.5 Engineering Module– 3720PU007 ................................................................................................. 647
27.6 Engineering Module– 3720PU008 ................................................................................................. 652

28.0 UNIDAD: SCPF_AGUASELLO ............................................................................................................. 657


28.1 Engineering Module– 3340PU192 ................................................................................................. 660
28.2 Engineering Module– 3340PU193 ................................................................................................. 663

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 7 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

29.0 UNIDAD: SCPF_INSTAIR ...................................................................................................................... 668


29.0 Engineering Module– 3340CP101_103 ......................................................................................... 669
29.1 Engineering Module– 3340AR101................................................................................................. 672
29.2 Engineering Module– 3340AR102................................................................................................. 675
29.3 Engineering Module– 3340AR103................................................................................................. 678

30.0 APPENDIX – VENDOR CONTROL PHILOSOPHIES ....................................................................... 682

LIST OF TABLES
Table 1: Process Flowsheet Diagrams .............................................................................................................. 42
Table 2: Reference Piping and Instrumentation Diagrams .......................................................................... 44
Table 3: General Process Project Documents ................................................................................................ 44
Table 4: Reference Documents ...........................................................................................................................45
Table 5: Terminology ............................................................................................................................................. 47
Table 6: Equipment Abbreviations ..................................................................................................................... 48
Table 7: CPF Structural Hierarchy Summary .................................................................................................. 60
Table 8: List of Modules of Control for 3340BX101 ....................................................................................... 62
Table 9: List of Interlocks for CPF Flopper Gate ............................................................................................ 63
Table 10: List of Interlocks for Tails Launder Flopper Gate ........................................................................ 63
Table 11: Alarms and Process Setpoint 3340-BX-101 ................................................................................... 63
Table 12: List of Interlocks for 3340XM100 ...................................................................................................... 65
Table 13: Alarms and Process Setpoint 3340XM100 ..................................................................................... 65
Table 14: List of Unit Controls – 3340PU101 ................................................................................................... 69
Table 15: List of Interlocks for 3340-XV-001C ................................................................................................. 70
Table 16: List of Interlocks for 3340-XV-002A ................................................................................................. 70
Table 17: List of Interlocks for 3340-XV-002B ................................................................................................. 71
Table 18: List of Interlocks for 3340-XV-002C ................................................................................................. 71
Table 19: List of Interlocks for 3340 – PU - 101 .............................................................................................. 72
Table 20: List of Interlocks for 3340-XV-002D ................................................................................................. 73
Table 21: List of Interlocks for 3340-DX-009 .................................................................................................... 73
Table 22: List of Interlocks for 3340-XV-005 .................................................................................................... 74
Table 23: Alarms and Process Setpoint 3340PU101 ..................................................................................... 74
Table 24: Binary State Messages 3340PU101 ................................................................................................. 74
Table 25: Regulatory Control Loops for 3340-LIC-001 ..................................................................................75
Table 26: Regulatory Control Loops for 3340-FIC-001 ..................................................................................75
Table 27: Start Sequence 3340PU101 ................................................................................................................ 76
Table 28: Stop Sequence 3340PU101 ................................................................................................................ 77
Table 29: List of Unit Controls – 3340PU102 ................................................................................................... 80
Table 30: List of Interlocks for 3340-XV-001A ................................................................................................. 81
Table 31: List of Interlocks for 3340-XV-003A ................................................................................................. 81
Table 32: List of Interlocks for 3340-XV-003B ................................................................................................. 82
Table 33: List of Interlocks for 3340-XV-003C ................................................................................................. 82
Table 34: List of Interlocks for 3340 – PU - 102 .............................................................................................. 83
Table 35: List of Interlocks for 3340-XV-003D ................................................................................................. 84
Table 36: List of Interlocks for 3340-DX-009 .................................................................................................... 84
Table 37: List of Interlocks for 3340-XV-006 .................................................................................................... 85
Table 38: Alarms and Process Setpoint 3340PU102 ..................................................................................... 85

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 8 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 39: Binary State Messages 3340PU102 ................................................................................................. 85


Table 40: Regulatory Control Loops for 3340-FIC-001 ..................................................................................86
Table 41: Start Sequence 3340PU102 ................................................................................................................ 87
Table 42: Stop Sequence 3340PU102 ................................................................................................................ 88
Table 43: List of Unit Controls – 3340PU174 ................................................................................................... 88
Table 44: List of Interlocks for 3340-PU-174 .................................................................................................... 89
Table 45: Alarms and Process Setpoint 3340-PU-174 ................................................................................... 89
Table 46: Binary State Messages 3340PU174 ................................................................................................. 90
Table 47: List of Unit Controls – 3340CY101 ................................................................................................... 92
Table 48: List of Interlocks for 3340-XV-015 A though AD ........................................................................... 92
Table 49: List of Interlocks for 3340-XV-013 A ................................................................................................ 92
Table 50: Alarms and Process Setpoint 3340CY101 ..................................................................................... 93
Table 51: Binary State Messages for 3340CY101 ........................................................................................... 93
Table 52: Regulatory Control Loops for 3340-PIC-014 .................................................................................94
Table 53: List of Unit Controls – 3340CY102 ................................................................................................... 96
Table 54: List of Interlocks for 3340-XV-018 A though AD ........................................................................... 97
Table 55: List of Interlocks for 3340-XV-016 A ................................................................................................ 97
Table 56: Alarms and Process Setpoint 3340CY102 ..................................................................................... 98
Table 57: Binary State Messages for 3340CY102 ........................................................................................... 98
Table 58: Regulatory Control Loops for 3340-PIC-017 .................................................................................98
Table 59: List of Modules of Control for SFCPF_AlimFlujoCruzado ....................................................... 102
Table 60: List of Interlocks for 3340-LCV-032 ............................................................................................... 102
Table 61: List of Interlocks for 3340-XV-039 .................................................................................................. 103
Table 62: List of Interlocks for 3340 – AG – 101 – LU1HE1........................................................................ 104
Table 63: List of Interlocks for 3340 – AG – 101 ........................................................................................... 104
Table 64: Alarms and Process Setpoint 3340-TK-101 ................................................................................. 104
Table 65: Alarms and Process Setpoint 3340-AG-101 ................................................................................ 105
Table 66: Regulatory Control Loops for 3340 - TK – 101............................................................................ 105
Table 67: List of Unit Controls – 3340PU185 ................................................................................................. 108
Table 68: List of Interlocks for 3340-XV-021A ............................................................................................... 109
Table 69: List of Interlocks for 3340-XV-021B ............................................................................................... 109
Table 70: List of Interlocks for 3340-XV-021C ............................................................................................... 109
Table 71: List of Interlocks for 3340 – PU - 185 ............................................................................................ 111
Table 72: List of Interlocks for 3340-XV-021D ............................................................................................... 111
Table 73: List of Interlocks for 3340-DX-028 .................................................................................................. 112
Table 74: List of Interlocks for 3340-XV-024 .................................................................................................. 112
Table 75: Alarms and Process Setpoint 3340PU185 ................................................................................... 113
Table 76: Binary State Messages 3340PU185 ............................................................................................... 113
Table 77: Regulatory Control Loops for 3340-FIC-027 ................................................................................ 113
Table 78: Start Sequence 3340PU185 .............................................................................................................. 115
Table 79: Stop Sequence 3340PU185 .............................................................................................................. 115
Table 80: List of Unit Controls – 3340PU186 ................................................................................................. 118
Table 81: List of Interlocks for 3340-XV-022A ............................................................................................... 118
Table 82: List of Interlocks for 3340-XV-022B ............................................................................................... 119
Table 83: List of Interlocks for 3340-XV-022C ............................................................................................... 119
Table 84: List of Interlocks for 3340 – PU - 186 ............................................................................................ 120
Table 85: List of Interlocks for 3340-XV-022D ............................................................................................... 121
Table 86: List of Interlocks for 3340-DX-030 .................................................................................................. 121
Table 87: List of Interlocks for 3340-XV-025 .................................................................................................. 122

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 9 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 88: Alarms and Process Setpoint 3340PU186 ................................................................................... 122


Table 89: Binary State Messages 3340PU186 ............................................................................................... 122
Table 90: Regulatory Control Loops for 3340-FIC-029 ................................................................................ 123
Table 91: Start Sequence 3340PU186 .............................................................................................................. 124
Table 92: Stop Sequence 3340PU186 .............................................................................................................. 125
Table 93: List of Unit Controls – 3340DB103 ................................................................................................. 126
Table 94: Alarms and Process Setpoint 3340DB103 ................................................................................... 127
Table 95: List of Unit Controls – 3340DB104 ................................................................................................. 128
Table 96: Alarms and Process Setpoint 3340DB104 ................................................................................... 129
Table 97: List of Unit Controls – 3340PU198 ................................................................................................. 130
Table 98: List of Interlocks for 3340-PU-198 .................................................................................................. 130
Table 99: Alarms and Process Setpoint 3340-PU-198 ................................................................................. 130
Table 100: List of Modules of Control for 3340SepHF101 .......................................................................... 134
Table 101: List of Interlocks for 3340-XV-038A ............................................................................................. 135
Table 102: List of Modules of Control for 3340CF101 ................................................................................. 138
Table 103: List of Interlocks for 3340-XV-040A ............................................................................................. 138
Table 104: List of Interlocks for 3340-FV-101 ................................................................................................ 138
Table 105: List of Interlocks for 3340-LCV-102 ............................................................................................. 139
Table 106: List of Interlocks for 3340-XV-107 ................................................................................................ 139
Table 107: List of Interlocks for 3340-XV-108 ................................................................................................ 140
Table 108: Alarms and Process Setpoint 3340CF101 .................................................................................141
Table 109: Regulatory Control Loops for 3340CF101 ................................................................................ 141
Table 110: Start Sequence 3340CF101 ............................................................................................................ 142
Table 111: Stop Sequence 3340CF101 ............................................................................................................ 142
Table 112: List of Modules of Control for 3340HF101 ................................................................................. 144
Table 113: List of Interlocks for 3340-FV-201 ................................................................................................ 145
Table 114: List of Interlocks for 3340-FV-202 ................................................................................................ 145
Table 115: List of Interlocks for 3340-FV-203 ................................................................................................ 145
Table 116: List of Interlocks for 3340-FV-204A ............................................................................................. 146
Table 117: List of Interlocks for 3340-FV-204B ............................................................................................. 146
Table 118: List of Interlocks for 3340-XV-207 ................................................................................................ 147
Table 119: List of Interlocks for 3340-XV-205 ................................................................................................ 148
Table 120: List of Interlocks for 3340-XV-208 ................................................................................................ 149
Table 121: Alarms and Process Setpoint 3340HF101 .................................................................................150
Table 122: Regulatory Control Loops for 3340HF101 ................................................................................ 150
Table 123: Start Sequence 3340HF101 ............................................................................................................ 151
Table 124: Stop Sequence 3340HF101 ............................................................................................................ 152
Table 125: List of Modules of Control for 3340SepHF102 .......................................................................... 152
Table 126: List of Interlocks for 3340-XV-038B ............................................................................................. 153
Table 127: List of Modules of Control for 3340CF102 ................................................................................. 155
Table 128: List of Interlocks for 3340-XV-042A ............................................................................................. 155
Table 129: List of Interlocks for 3340-FV-111 ................................................................................................ 155
Table 130: List of Interlocks for 3340-LCV-112 ............................................................................................. 156
Table 131: List of Interlocks for 3340-XV-117 ................................................................................................ 156
Table 132: List of Interlocks for 3340-XV-118 ................................................................................................ 157
Table 133: Alarms and Process Setpoint 3340CF102 .................................................................................158
Table 134: Regulatory Control Loops for 3340CF102 ................................................................................ 158
Table 135: Start Sequence 3340CF102 ............................................................................................................ 159
Table 136: Stop Sequence 3340CF102 ............................................................................................................ 159

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 10 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 137: List of Modules of Control for 3340HF102 ................................................................................. 160


Table 138: List of Interlocks for 3340-FV-211 ................................................................................................ 161
Table 139: List of Interlocks for 3340-FV-212 ................................................................................................ 161
Table 140: List of Interlocks for 3340-FV-213 ................................................................................................ 162
Table 141: List of Interlocks for 3340-FV-214A ............................................................................................. 162
Table 142: List of Interlocks for 3340-FV-214B ............................................................................................. 163
Table 143: List of Interlocks for 3340-XV-217 ................................................................................................ 164
Table 144: List of Interlocks for 3340-XV-215 ................................................................................................ 164
Table 145: List of Interlocks for 3340-XV-218 ................................................................................................ 165
Table 146: Alarms and Process Setpoint 3340HF102 .................................................................................166
Table 147: Regulatory Control Loops for 3340HF102 ................................................................................ 167
Table 148: Start Sequence 3340HF102 ............................................................................................................ 168
Table 149: Stop Sequence 3340HF102 ............................................................................................................ 169
Table 150: List of Modules of Control for 3340SepHF103 .......................................................................... 169
Table 151: List of Interlocks for 3340-XV-038C ............................................................................................. 170
Table 152: List of Modules of Control for 3340CF103 ................................................................................. 172
Table 153: List of Interlocks for 3340-XV-044A ............................................................................................. 172
Table 154: List of Interlocks for 3340-FV-121 ................................................................................................ 172
Table 155: List of Interlocks for 3340-LCV-122 ............................................................................................. 173
Table 156: List of Interlocks for 3340-XV-127 ................................................................................................ 173
Table 157: List of Interlocks for 3340-XV-128 ................................................................................................ 174
Table 158: Alarms and Process Setpoint 3340CF103 .................................................................................175
Table 159: Regulatory Control Loops for 3340CF103 ................................................................................ 175
Table 160: Start Sequence 3340CF103 ............................................................................................................ 176
Table 161: Stop Sequence 3340CF103 ............................................................................................................ 176
Table 162: List of Modules of Control for 3340HF103 ................................................................................. 177
Table 163: List of Interlocks for 3340-FV-221 ................................................................................................ 178
Table 164: List of Interlocks for 3340-FV-222 ................................................................................................ 178
Table 165: List of Interlocks for 3340-FV-223 ................................................................................................ 179
Table 166: List of Interlocks for 3340-FV-224A ............................................................................................. 179
Table 167: List of Interlocks for 3340-FV-224B ............................................................................................. 180
Table 168: List of Interlocks for 3340-XV-227 ................................................................................................ 181
Table 169: List of Interlocks for 3340-XV-225 ................................................................................................ 181
Table 170: List of Interlocks for 3340-XV-228 ................................................................................................ 182
Table 171: Alarms and Process Setpoint 3340HF103 .................................................................................183
Table 172: Regulatory Control Loops for 3340HF103 ................................................................................ 184
Table 173: Start Sequence 3340HF103 ............................................................................................................ 185
Table 174: Stop Sequence 3340HF103 ............................................................................................................ 186
Table 175: List of Modules of Control for 3340SepHF104 .......................................................................... 186
Table 176: List of Interlocks for 3340-XV-038D ............................................................................................. 187
Table 177: List of Modules of Control for 3340CF104 ................................................................................. 189
Table 178: List of Interlocks for 3340-XV-046A ............................................................................................. 189
Table 179: List of Interlocks for 3340-FV-131 ................................................................................................ 189
Table 180: List of Interlocks for 3340-LCV-132 ............................................................................................. 190
Table 181: List of Interlocks for 3340-XV-137 ................................................................................................ 190
Table 182: List of Interlocks for 3340-XV-138 ................................................................................................ 191
Table 183: Alarms and Process Setpoint 3340CF104 .................................................................................192
Table 184: Regulatory Control Loops for 3340CF104 ................................................................................ 192
Table 185: Start Sequence 3340CF104 ............................................................................................................ 193

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 11 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 186: Stop Sequence 3340CF104 ............................................................................................................ 193


Table 187: List of Modules of Control for 3340HF104 ................................................................................. 194
Table 188: List of Interlocks for 3340-FV-231 ................................................................................................ 195
Table 189: List of Interlocks for 3340-FV-232 ................................................................................................ 195
Table 190: List of Interlocks for 3340-FV-233 ................................................................................................ 196
Table 191: List of Interlocks for 3340-FV-234A ............................................................................................. 196
Table 192: List of Interlocks for 3340-FV-234B ............................................................................................. 197
Table 193: List of Interlocks for 3340-XV-237 ................................................................................................ 198
Table 194: List of Interlocks for 3340-XV-235 ................................................................................................ 198
Table 195: List of Interlocks for 3340-XV-238 ................................................................................................ 199
Table 196: Alarms and Process Setpoint 3340HF104 .................................................................................200
Table 197: Regulatory Control Loops for 3340HF104 ................................................................................ 201
Table 198: Start Sequence 3340HF104 ............................................................................................................ 202
Table 199: Stop Sequence 3340HF104 ............................................................................................................ 203
Table 200: List of Modules of Control for 3340SepHF105 .......................................................................... 203
Table 201: List of Interlocks for 3340-XV-038E ............................................................................................. 204
Table 202: List of Modules of Control for 3340CF105 ................................................................................. 206
Table 203: List of Interlocks for 3340-XV-048A ............................................................................................. 206
Table 204: List of Interlocks for 3340-FV-141 ................................................................................................ 206
Table 205: List of Interlocks for 3340-LCV-142 ............................................................................................. 207
Table 206: List of Interlocks for 3340-XV-147 ................................................................................................ 207
Table 207: List of Interlocks for 3340-XV-148 ................................................................................................ 208
Table 208: Alarms and Process Setpoint 3340CF105 .................................................................................209
Table 209: Regulatory Control Loops for 3340CF105 ................................................................................ 209
Table 210: Start Sequence 3340CF105 ............................................................................................................ 210
Table 211: Stop Sequence 3340CF105 ............................................................................................................ 210
Table 212: List of Modules of Control for 3340HF105 ................................................................................. 211
Table 213: List of Interlocks for 3340-FV-241 ................................................................................................ 212
Table 214: List of Interlocks for 3340-FV-242 ................................................................................................ 212
Table 215: List of Interlocks for 3340-FV-243 ................................................................................................ 213
Table 216: List of Interlocks for 3340-FV-244A ............................................................................................. 213
Table 217: List of Interlocks for 3340-FV-244B ............................................................................................. 214
Table 218: List of Interlocks for 3340-XV-247 ................................................................................................ 215
Table 219: List of Interlocks for 3340-XV-245 ................................................................................................ 215
Table 220: List of Interlocks for 3340-XV-248 ................................................................................................ 216
Table 221: Alarms and Process Setpoint 3340HF105 .................................................................................217
Table 222: Regulatory Control Loops for 3340HF105 ................................................................................ 218
Table 223: Start Sequence 3340HF105 ............................................................................................................ 219
Table 224: Stop Sequence 3340HF105 ............................................................................................................ 220
Table 225: List of Modules of Control for 3340SepHF106 .......................................................................... 222
Table 226: List of Interlocks for 3340-XV-036A ............................................................................................. 223
Table 227: List of Modules of Control for 3340CF106 ................................................................................. 225
Table 228: List of Interlocks for 3340-XV-050A ............................................................................................. 225
Table 229: List of Interlocks for 3340-FV-151 ................................................................................................ 226
Table 230: List of Interlocks for 3340-LCV-152 ............................................................................................. 226
Table 231: List of Interlocks for 3340-XV-157 ................................................................................................ 227
Table 232: List of Interlocks for 3340-XV-158 ................................................................................................ 227
Table 233: Alarms and Process Setpoint 3340CF106 .................................................................................228
Table 234: Regulatory Control Loops for 3340CF106 ................................................................................ 228

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 12 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 235: Start Sequence 3340CF106 ............................................................................................................ 229


Table 236: Stop Sequence 3340CF106 ............................................................................................................ 229
Table 237: List of Modules of Control for 3340HF106 ................................................................................. 230
Table 238: List of Interlocks for 3340-FV-251 ................................................................................................ 231
Table 239: List of Interlocks for 3340-FV-252 ................................................................................................ 231
Table 240: List of Interlocks for 3340-FV-253 ................................................................................................ 232
Table 241: List of Interlocks for 3340-FV-254A ............................................................................................. 232
Table 242: List of Interlocks for 3340-FV-254B ............................................................................................. 233
Table 243: List of Interlocks for 3340-XV-257 ................................................................................................ 234
Table 244: List of Interlocks for 3340-XV-255 ................................................................................................ 234
Table 245: List of Interlocks for 3340-XV-258 ................................................................................................ 235
Table 246: Alarms and Process Setpoint 3340HF106 .................................................................................236
Table 247: Regulatory Control Loops for 3340HF106 ................................................................................ 237
Table 248: Start Sequence 3340HF106 ............................................................................................................ 238
Table 249: Stop Sequence 3340HF106 ............................................................................................................ 239
Table 250: List of Modules of Control for 3340SepHF107 .......................................................................... 239
Table 251: List of Interlocks for 3340-XV-036B ............................................................................................. 240
Table 252: List of Modules of Control for 3340CF107 ................................................................................. 242
Table 253: List of Interlocks for 3340-XV-052A ............................................................................................. 242
Table 254: List of Interlocks for 3340-FV-161 ................................................................................................ 242
Table 255: List of Interlocks for 3340-LCV-162 ............................................................................................. 243
Table 256: List of Interlocks for 3340-XV-167 ................................................................................................ 243
Table 257: List of Interlocks for 3340-XV-168 ................................................................................................ 244
Table 258: Alarms and Process Setpoint 3340CF107 .................................................................................245
Table 259: Regulatory Control Loops for 3340CF107 ................................................................................ 245
Table 260: Start Sequence 3340CF107 ............................................................................................................ 246
Table 261: Stop Sequence 3340CF107 ............................................................................................................ 246
Table 262: List of Modules of Control for 3340HF107 ................................................................................. 247
Table 263: List of Interlocks for 3340-FV-261 ................................................................................................ 248
Table 264: List of Interlocks for 3340-FV-262 ................................................................................................ 248
Table 265: List of Interlocks for 3340-FV-263 ................................................................................................ 248
Table 266: List of Interlocks for 3340-FV-264A ............................................................................................. 249
Table 267: List of Interlocks for 3340-FV-264B ............................................................................................. 249
Table 268: List of Interlocks for 3340-XV-267 ................................................................................................ 250
Table 269: List of Interlocks for 3340-XV-265 ................................................................................................ 251
Table 270: List of Interlocks for 3340-XV-268 ................................................................................................ 251
Table 271: Alarms and Process Setpoint 3340HF107 .................................................................................252
Table 272: Regulatory Control Loops for 3340HF107 ................................................................................ 253
Table 273: Start Sequence 3340HF107 ............................................................................................................ 254
Table 274: Stop Sequence 3340HF107 ............................................................................................................ 255
Table 275: List of Modules of Control for 3340SepHF108 .......................................................................... 255
Table 276: List of Interlocks for 3340-XV-036C ............................................................................................. 256
Table 277: List of Modules of Control for 3340CF108 ................................................................................. 258
Table 278: List of Interlocks for 3340-XV-054A ............................................................................................. 258
Table 279: List of Interlocks for 3340-FV-171 ................................................................................................ 258
Table 280: List of Interlocks for 3340-LCV-172 ............................................................................................. 259
Table 281: List of Interlocks for 3340-XV-177 ................................................................................................ 259
Table 282: List of Interlocks for 3340-XV-178 ................................................................................................ 260
Table 283: Alarms and Process Setpoint 3340CF108 .................................................................................261

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 13 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 284: Regulatory Control Loops for 3340CF108 ................................................................................ 261


Table 285: Start Sequence 3340CF108 ............................................................................................................ 262
Table 286: Stop Sequence 3340CF108 ............................................................................................................ 262
Table 287: List of Modules of Control for 3340HF108 ................................................................................. 263
Table 288: List of Interlocks for 3340-FV-271 ................................................................................................ 264
Table 289: List of Interlocks for 3340-FV-272 ................................................................................................ 264
Table 290: List of Interlocks for 3340-FV-273 ................................................................................................ 265
Table 291: List of Interlocks for 3340-FV-274A ............................................................................................. 265
Table 292: List of Interlocks for 3340-FV-274B ............................................................................................. 266
Table 293: List of Interlocks for 3340-XV-277 ................................................................................................ 267
Table 294: List of Interlocks for 3340-XV-275 ................................................................................................ 267
Table 295: List of Interlocks for 3340-XV-278 ................................................................................................ 268
Table 296: Alarms and Process Setpoint 3340HF108 .................................................................................269
Table 297: Regulatory Control Loops for 3340HF108 ................................................................................ 269
Table 298: Start Sequence 3340HF108 ............................................................................................................ 270
Table 299: Stop Sequence 3340HF108 ............................................................................................................ 271
Table 300: List of Modules of Control for 3340SepHF109 .......................................................................... 271
Table 301: List of Interlocks for 3340-XV-036D ............................................................................................. 272
Table 302: List of Modules of Control for 3340CF109 ................................................................................. 274
Table 303: List of Interlocks for 3340-XV-056A ............................................................................................. 274
Table 304: List of Interlocks for 3340-FV-181 ................................................................................................ 274
Table 305: List of Interlocks for 3340-LCV-182 ............................................................................................. 275
Table 306: List of Interlocks for 3340-XV-187 ................................................................................................ 275
Table 307: List of Interlocks for 3340-XV-188 ................................................................................................ 276
Table 308: Alarms and Process Setpoint 3340CF109 .................................................................................277
Table 309: Regulatory Control Loops for 3340CF109 ................................................................................ 277
Table 310: Start Sequence 3340CF109 ............................................................................................................ 278
Table 311: Stop Sequence 3340CF109 ............................................................................................................ 278
Table 312: List of Modules of Control for 3340HF109 ................................................................................. 279
Table 313: List of Interlocks for 3340-FV-281 ................................................................................................ 280
Table 314: List of Interlocks for 3340-FV-282 ................................................................................................ 280
Table 315: List of Interlocks for 3340-FV-283 ................................................................................................ 280
Table 316: List of Interlocks for 3340-FV-284A ............................................................................................. 281
Table 317: List of Interlocks for 3340-FV-284B ............................................................................................. 281
Table 318: List of Interlocks for 3340-XV-287 ................................................................................................ 282
Table 319: List of Interlocks for 3340-XV-285 ................................................................................................ 283
Table 320: List of Interlocks for 3340-XV-288 ................................................................................................ 283
Table 321: Alarms and Process Setpoint 3340HF109 .................................................................................284
Table 322: Regulatory Control Loops for 3340HF109 ................................................................................ 285
Table 323: Start Sequence 3340HF109 ............................................................................................................ 286
Table 324: Stop Sequence 3340HF109 ............................................................................................................ 287
Table 325: List of Modules of Control for 3340SepHF110 .......................................................................... 287
Table 326: List of Interlocks for 3340-XV-036E ............................................................................................. 288
Table 327: List of Modules of Control for 3340CF110 ................................................................................. 290
Table 328: List of Interlocks for 3340-XV-058A ............................................................................................. 290
Table 329: List of Interlocks for 3340-FV-191 ................................................................................................ 290
Table 330: List of Interlocks for 3340-LCV-192 ............................................................................................. 291
Table 331: List of Interlocks for 3340-XV-197 ................................................................................................ 291
Table 332: List of Interlocks for 3340-XV-198 ................................................................................................ 292

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 14 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 333: Alarms and Process Setpoint 3340CF110 .................................................................................293


Table 334: Regulatory Control Loops for 3340CF110 ................................................................................ 293
Table 335: Start Sequence 3340CF110 ............................................................................................................ 294
Table 336: Stop Sequence 3340CF110 ............................................................................................................ 294
Table 337: List of Modules of Control for 3340HF110 ................................................................................. 295
Table 338: List of Interlocks for 3340-FV-291 ................................................................................................ 296
Table 339: List of Interlocks for 3340-FV-292 ................................................................................................ 296
Table 340: List of Interlocks for 3340-FV-293 ................................................................................................ 296
Table 341: List of Interlocks for 3340-FV-294A ............................................................................................. 297
Table 342: List of Interlocks for 3340-FV-294B ............................................................................................. 297
Table 343: List of Interlocks for 3340-XV-297 ................................................................................................ 298
Table 344: List of Interlocks for 3340-XV-295 ................................................................................................ 299
Table 345: List of Interlocks for 3340-XV-298 ................................................................................................ 299
Table 346: Alarms and Process Setpoint 3340HF110 .................................................................................300
Table 347: Regulatory Control Loops for 3340HF110 ................................................................................ 301
Table 348: Start Sequence 3340HF110 ............................................................................................................ 302
Table 349: Stop Sequence 3340HF110 ............................................................................................................ 303
Table 350: List of Modules of Control for CRCFP_Relaves ....................................................................... 305
Table 351: List of Interlocks for 3340-XV-630A ............................................................................................. 305
Table 352: List of Interlocks for 3340-SA-103 ................................................................................................ 306
Table 353: List of Interlocks for 3340-XV-700 ................................................................................................ 306
Table 354: List of Interlocks for 3340-XV-701 ................................................................................................ 307
Table 355: List of Interlocks for 3340-XV-702 ................................................................................................ 308
Table 356: Alarms and Process Setpoint CRCFP_Relaves .......................................................................308
Table 357: Regulatory Control Loops for CRCFP_Relaves ....................................................................... 309
Table 358: List of Unit Controls – 3340PU170 ............................................................................................... 309
Table 359: List of Interlocks for 3340PU170 .................................................................................................. 310
Table 360: Alarms and Process Setpoint 3340PU170 ................................................................................. 310
Table 361: List of Unit Controls – 3340PU197 ............................................................................................... 312
Table 362: List of Interlocks for 3340-XV-632A ............................................................................................. 312
Table 363: List of Interlocks for 3340-XV-632B ............................................................................................. 313
Table 364: List of Interlocks for 3340-XV-632C ............................................................................................. 313
Table 365: List of Interlocks for 3340 – PU - 197 .......................................................................................... 314
Table 366: List of Interlocks for 3340-XV-633 ................................................................................................ 315
Table 367: Alarms and Process Setpoint 3340PU197 ................................................................................. 315
Table 368: Start Sequence 3340PU197 ........................................................................................................... 316
Table 369: Stop Sequence 3340PU197 ............................................................................................................ 316
Table 370: List of Modules of Control for RECPF_Collector3894 ............................................................ 319
Table 371: List of Interlocks for 3350-XV-120 ................................................................................................ 319
Table 372: List of Interlocks for 3350-XV-121 ................................................................................................ 320
Table 373: List of Interlocks for 3350-XV-122 ................................................................................................ 320
Table 374: List of Interlocks for 3350-XV-123 ................................................................................................ 321
Table 375: List of Interlocks for 3350-XV-124 ................................................................................................ 321
Table 376: List of Interlocks for 3350-XV-125 ................................................................................................ 322
Table 377: List of Interlocks for 3350-XV-126 ................................................................................................ 323
Table 378: List of Interlocks for 3350-XV-127 ................................................................................................ 323
Table 379: List of Interlocks for 3350-XV-128 ................................................................................................ 324
Table 380: List of Interlocks for 3350-XV-129 ................................................................................................ 324
Table 381: List of Interlocks for 3350-FCV-120 ............................................................................................. 325

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 15 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 382: List of Interlocks for 3350-FCV-121 ............................................................................................. 326


Table 383: List of Interlocks for 3350-FCV-122 ............................................................................................. 326
Table 384: List of Interlocks for 3350-FCV-123 ............................................................................................. 327
Table 385: List of Interlocks for 3350-FCV-124 ............................................................................................. 327
Table 386: List of Interlocks for 3350-FCV-125 ............................................................................................. 328
Table 387: List of Interlocks for 3350-FCV-126 ............................................................................................. 328
Table 388: List of Interlocks for 3350-FCV-127 ............................................................................................. 328
Table 389: List of Interlocks for 3350-FCV-128 ............................................................................................. 329
Table 390: List of Interlocks for 3350-FCV-129 ............................................................................................. 329
Table 391: Alarms and Process Setpoint RECPF_Collector3894............................................................. 330
Table 392: Regulatory Control Loops for RECPF_Collector3894 ............................................................ 330
Table 393: List of Modules of Control for 3520PU179 ................................................................................. 334
Table 394: List of Interlocks for 3520PU179 .................................................................................................. 334
Table 395: Alarms and Process Setpoint 3520PU179 ................................................................................. 334
Table 396: List of Modules of Control for 3350PU120 ................................................................................. 338
Table 397: List of Interlocks for 3350-XV-202A ............................................................................................. 338
Table 398: List of Interlocks for 3350-PU-120 ................................................................................................ 339
Table 399: List of Interlocks for 3350-XV-202B ............................................................................................. 339
Table 400: Start Sequence 3350PU120 ........................................................................................................... 340
Table 401: Stop Sequence 3350PU120 ............................................................................................................ 340
Table 402: List of Modules of Control for 3350PU121 ......................................................................................... 342
Table 403: List of Interlocks for 3350-XV-203A ............................................................................................. 342
Table 404: List of Interlocks for 3350-PU-121 ................................................................................................ 343
Table 405: List of Interlocks for 3350-XV-203B ............................................................................................. 343
Table 406: Start Sequence 3350PU121 ........................................................................................................... 344
Table 407: Stop Sequence 3350PU121 ............................................................................................................ 344
Table 408: List of Modules of Control for RECPF_Collector404 .............................................................. 347
Table 409: List of Interlocks for 3350-XV-160 ................................................................................................ 347
Table 410: List of Interlocks for 3350-XV-161 ................................................................................................ 348
Table 411: List of Interlocks for 3350-XV-162 ................................................................................................ 348
Table 412: List of Interlocks for 3350-XV-163 ................................................................................................ 349
Table 413: List of Interlocks for 3350-XV-164 ................................................................................................ 350
Table 414: List of Interlocks for 3350-XV-165 ................................................................................................ 350
Table 415: List of Interlocks for 3350-XV-166 ................................................................................................ 351
Table 416: List of Interlocks for 3350-XV-167 ................................................................................................ 351
Table 417: List of Interlocks for 3350-XV-168 ................................................................................................ 352
Table 418: List of Interlocks for 3350-XV-169 ................................................................................................ 352
Table 419: List of Interlocks for 3350-FCV-160 ............................................................................................. 353
Table 420: List of Interlocks for 3350-FCV-161 ............................................................................................. 354
Table 421: List of Interlocks for 3350-FCV-162 ............................................................................................. 354
Table 422: List of Interlocks for 3350-FCV-163 ............................................................................................. 355
Table 423: List of Interlocks for 3350-FCV-164 ............................................................................................. 355
Table 424: List of Interlocks for 3350-FCV-165 ............................................................................................. 355
Table 425: List of Interlocks for 3350-FCV-166 ............................................................................................. 356
Table 426: List of Interlocks for 3350-FCV-167 ............................................................................................. 356
Table 427: List of Interlocks for 3350-FCV-168 ............................................................................................. 357
Table 428: List of Interlocks for 3350-FCV-169 ............................................................................................. 357
Table 429: Alarms and Process Setpoint RECPF_Collector404 ............................................................... 358
Table 430: Regulatory Control Loops for RECPF_Collector404............................................................... 358

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 16 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 431: List of Modules of Control for 3520PU182 ................................................................................. 362


Table 432: List of Interlocks for 3520PU182 .................................................................................................. 362
Table 433: Alarms and Process Setpoint 3520PU182 ................................................................................. 362
Table 434: List of Modules of Control for 3350PU160 ................................................................................. 365
Table 435: List of Interlocks for 3350-XV-207A ............................................................................................. 365
Table 436: List of Interlocks for 3350-PU-160 ................................................................................................ 366
Table 437: List of Interlocks for 3350-XV-207B ............................................................................................. 366
Table 438: Start Sequence 3350PU160 ........................................................................................................... 367
Table 439: Stop Sequence 3350PU160 ............................................................................................................ 367
Table 440: List of Modules of Control for 3350PU161 ......................................................................................... 369
Table 441: List of Interlocks for 3350-XV-208A ............................................................................................. 369
Table 442: List of Interlocks for 3350-PU-161 ................................................................................................ 370
Table 443: List of Interlocks for 3350-XV-208B ............................................................................................. 370
Table 444: Start Sequence 3350PU161 ........................................................................................................... 371
Table 445: Stop Sequence 3350PU161 ............................................................................................................ 371
Table 446: List of Modules of Control for RECPF_CollectorZ6 ................................................................ 374
Table 447: List of Interlocks for 3350-XV-150 ................................................................................................ 375
Table 448: List of Interlocks for 3350-XV-151 ................................................................................................ 375
Table 449: List of Interlocks for 3350-XV-152 ................................................................................................ 376
Table 450: List of Interlocks for 3350-XV-153 ................................................................................................ 376
Table 451: List of Interlocks for 3350-XV-154 ................................................................................................ 377
Table 452: List of Interlocks for 3350-XV-155 ................................................................................................ 377
Table 453: List of Interlocks for 3350-XV-156 ................................................................................................ 378
Table 454: List of Interlocks for 3350-XV-157 ................................................................................................ 378
Table 455: List of Interlocks for 3350-XV-158 ................................................................................................ 379
Table 456: List of Interlocks for 3350-XV-159 ................................................................................................ 379
Table 457: List of Interlocks for 3350-FCV-150 ............................................................................................. 380
Table 458: List of Interlocks for 3350-FCV-151 ............................................................................................. 381
Table 459: List of Interlocks for 3350-FCV-152 ............................................................................................. 381
Table 460: List of Interlocks for 3350-FCV-153 ............................................................................................. 382
Table 461: List of Interlocks for 3350-FCV-154 ............................................................................................. 382
Table 462: List of Interlocks for 3350-FCV-155 ............................................................................................. 382
Table 463: List of Interlocks for 3350-FCV-156 ............................................................................................. 383
Table 464: List of Interlocks for 3350-FCV-157 ............................................................................................. 383
Table 465: List of Interlocks for 3350-FCV-158 ............................................................................................. 384
Table 466: List of Interlocks for 3350-FCV-159 ............................................................................................. 384
Table 467: List of Interlocks for 3350-ES-102 ................................................................................................ 384
Table 468: Alarms and Process Setpoint RECPF_CollectorZ6 ................................................................. 385
Table 469: Regulatory Control Loops for RECPF_CollectorZ6................................................................. 386
Table 470: List of Modules of Control for 3520PU181 ................................................................................. 389
Table 471: List of Interlocks for 3520PU181 .................................................................................................. 389
Table 472: Alarms and Process Setpoint 3520PU181 ................................................................................. 389
Table 473: List of Modules of Control for 3350PU150 ................................................................................. 392
Table 474: List of Interlocks for 3350-XV-212A ............................................................................................. 392
Table 475: List of Interlocks for 3350-PU-150 ................................................................................................ 393
Table 476: List of Interlocks for 3350-XV-212B ............................................................................................. 393
Table 477: Start Sequence 3350PU150 ........................................................................................................... 394
Table 478: Stop Sequence 3350PU150 ............................................................................................................ 394
Table 479: List of Modules of Control for 3350PU151 ................................................................................. 396

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 17 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 480: List of Interlocks for 3350-XV-213A ............................................................................................. 396


Table 481: List of Interlocks for 3350-PU-161 ................................................................................................ 397
Table 482: List of Interlocks for 3350-XV-213B ............................................................................................. 397
Table 483: Start Sequence 3350PU151 ........................................................................................................... 398
Table 484: Stop Sequence 3350PU151 ............................................................................................................ 398
Table 485: List of Modules of Control for RECPF_CollectorDIESEL ....................................................... 401
Table 486: List of Interlocks for 3350-XV-130 ................................................................................................ 401
Table 487: List of Interlocks for 3350-XV-131 ................................................................................................ 402
Table 488: List of Interlocks for 3350-XV-132 ................................................................................................ 403
Table 489: List of Interlocks for 3350-XV-133 ................................................................................................ 403
Table 490: List of Interlocks for 3350-XV-134 ................................................................................................ 404
Table 491: List of Interlocks for 3350-XV-135 ................................................................................................ 404
Table 492: List of Interlocks for 3350-XV-136 ................................................................................................ 405
Table 493: List of Interlocks for 3350-XV-137 ................................................................................................ 405
Table 494: List of Interlocks for 3350-XV-138 ................................................................................................ 406
Table 495: List of Interlocks for 3350-XV-139 ................................................................................................ 406
Table 496: List of Interlocks for 3350-FCV-130 ............................................................................................. 407
Table 497: List of Interlocks for 3350-FCV-131 ............................................................................................. 408
Table 498: List of Interlocks for 3350-FCV-132 ............................................................................................. 408
Table 499: List of Interlocks for 3350-FCV-133 ............................................................................................. 409
Table 500: List of Interlocks for 3350-FCV-134 ............................................................................................. 409
Table 501: List of Interlocks for 3350-FCV-135 ............................................................................................. 409
Table 502: List of Interlocks for 3350-FCV-136 ............................................................................................. 410
Table 503: List of Interlocks for 3350-FCV-137 ............................................................................................. 410
Table 504: List of Interlocks for 3350-FCV-138 ............................................................................................. 411
Table 505: List of Interlocks for 3350-FCV-139 ............................................................................................. 411
Table 506: Alarms and Process Setpoint RECPF_CollectorDIESEL ....................................................... 412
Table 507: Regulatory Control Loops for RECPF_CollectorDIESEL ....................................................... 412
Table 508: List of Modules of Control for 3520PU180 ................................................................................. 416
Table 509: List of Interlocks for 3520PU180 .................................................................................................. 416
Table 510: Alarms and Process Setpoint 3520PU180 ................................................................................. 416
Table 511: List of Modules of Control for 3350PU130 ................................................................................. 419
Table 512: List of Interlocks for 3350-XV-217A ............................................................................................. 419
Table 513: List of Interlocks for 3350-PU-130 ................................................................................................ 420
Table 514: List of Interlocks for 3350-XV-217B ............................................................................................. 420
Table 515: Start Sequence 3350PU130 ........................................................................................................... 421
Table 516: Stop Sequence 3350PU130 ............................................................................................................ 421
Table 517: List of Modules of Control for 3350PU131 ................................................................................. 423
Table 518: List of Interlocks for 3350-XV-218A ............................................................................................. 423
Table 519: List of Interlocks for 3350-PU-161 ................................................................................................ 424
Table 520: List of Interlocks for 3350-XV-218B ............................................................................................. 424
Table 521: Start Sequence 3350PU131 ........................................................................................................... 425
Table 522: Stop Sequence 3350PU131 ............................................................................................................ 425
Table 523: List of Modules of Control for RECPF_AlmEspumante ......................................................... 427
Table 524: Alarms and Process Setpoint RECPF_AlmEspumante .......................................................... 427
Table 525: List of Modules of Control for 3350PU178 ................................................................................. 428
Table 526: List of Interlocks for 3350 – PU – 178 ......................................................................................... 429
Table 527: List of Interlocks for 3350 – XV - 220...........................................................................................430
Table 528: Alarms and Process Setpoint 3350PU178 ................................................................................. 430

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 18 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 529: List of Modules of Control for 3350PU176_177 ........................................................................ 431


Table 530: List of Interlocks for 3350 – PU – 176 ......................................................................................... 432
Table 531: List of Interlocks for 3350 – PU - 177 .......................................................................................... 433
Table 532: Alarms and Process Setpoint 3350PU176_177 ........................................................................ 433
Table 533: List of Unit Controls – 3350PU199 ............................................................................................... 434
Table 534: List of Interlocks for 3350-PU-199 ................................................................................................ 434
Table 535: Alarms and Process Setpoint 3350PU199 ................................................................................. 434
Table 536: List of Modules of Control for RECPF_Espumante ................................................................. 438
Table 537: List of Interlocks for 3350-XV-140 ................................................................................................ 438
Table 538: List of Interlocks for 3350-XV-141 ................................................................................................ 439
Table 539: List of Interlocks for 3350-XV-142 ................................................................................................ 439
Table 540: List of Interlocks for 3350-XV-143 ................................................................................................ 440
Table 541: List of Interlocks for 3350-XV-144 ................................................................................................ 440
Table 542: List of Interlocks for 3350-XV-145 ................................................................................................ 441
Table 543: List of Interlocks for 3350-XV-146 ................................................................................................ 441
Table 544: List of Interlocks for 3350-XV-147 ................................................................................................ 442
Table 545: List of Interlocks for 3350-XV-148 ................................................................................................ 442
Table 546: List of Interlocks for 3350-XV-149 ................................................................................................ 443
Table 547: List of Interlocks for 3350-FCV-140 ............................................................................................. 443
Table 548: List of Interlocks for 3350-FCV-141 ............................................................................................. 444
Table 549: List of Interlocks for 3350-FCV-142 ............................................................................................. 444
Table 550: List of Interlocks for 3350-FCV-143 ............................................................................................. 445
Table 551: List of Interlocks for 3350-FCV-144 ............................................................................................. 445
Table 552: List of Interlocks for 3350-FCV-145 ............................................................................................. 445
Table 553: List of Interlocks for 3350-FCV-146 ............................................................................................. 446
Table 554: List of Interlocks for 3350-FCV-147 ............................................................................................. 446
Table 555: List of Interlocks for 3350-FCV-148 ............................................................................................. 447
Table 556: List of Interlocks for 3350-FCV-149 ............................................................................................. 447
Table 557: List of Interlocks for 3350-ES-101 ................................................................................................ 447
Table 558: Alarms and Process Setpoint RECPF_Espumante ................................................................. 448
Table 559: Regulatory Control Loops for RECPF_Espumante ................................................................. 449
Table 560: List of Modules of Control for 3350PU140 ................................................................................. 452
Table 561: List of Interlocks for 3350-XV-225A ............................................................................................. 452
Table 562: List of Interlocks for 3350-PU-140 ................................................................................................ 453
Table 563: List of Interlocks for 3350-XV-225B ............................................................................................. 453
Table 564: Start Sequence 3350PU140 ........................................................................................................... 454
Table 565: Stop Sequence 3350PU140 ............................................................................................................ 454
Table 566: List of Modules of Control for 3350PU141 ................................................................................. 455
Table 567: List of Interlocks for 3350-XV-226A ............................................................................................. 456
Table 568: List of Interlocks for 3350-PU-141 ................................................................................................ 456
Table 569: List of Interlocks for 3350-XV-226B ............................................................................................. 457
Table 570: Start Sequence 3350PU141 ........................................................................................................... 458
Table 571: Stop Sequence 3350PU141 ............................................................................................................ 458
Table 572: List of Modules of Control for 3520PU195 ................................................................................. 461
Table 573: List of Interlocks for 3520-XV-104A ............................................................................................. 461
Table 574: List of Interlocks for 3520-PU-195 ................................................................................................ 462
Table 575: List of Interlocks for 3520-XV-104B ............................................................................................. 462
Table 576: Start Sequence 3520PU195 ........................................................................................................... 463
Table 577: Stop Sequence 3520PU195 ............................................................................................................ 463

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 19 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 578: List of Modules of Control for 3520PU196 ................................................................................. 464


Table 579: List of Interlocks for 3520-XV-105A ............................................................................................. 465
Table 580: List of Interlocks for 3520-PU-196 ................................................................................................ 465
Table 581: List of Interlocks for 3520-XV-105B ............................................................................................. 466
Table 582: Start Sequence 3520PU196 ........................................................................................................... 467
Table 583: Stop Sequence 3520PU196 ............................................................................................................ 467
Table 584: List of Modules of Control for 3340MX001 ................................................................................ 468
Table 585: List of Interlocks for 3340-FCV-710 ............................................................................................. 469
Table 586: List of Interlocks for 3340-FCV-713 ............................................................................................. 470
Table 587: Alarms and Process Setpoints for 3340MX001 System ......................................................... 470
Table 588: Regulatory Control Loops for 3340MX001 System ................................................................. 470
Table 589: List of Modules of Control for 3340MX002 ................................................................................ 473
Table 590: List of Interlocks for 3340-FCV-711 ............................................................................................. 473
Table 591: List of Interlocks for 3340-FCV-714 ............................................................................................. 474
Table 592: Alarms and Process Setpoints for 3340MX002 System ......................................................... 474
Table 593: Regulatory Control Loops for 3340MX001 System ................................................................. 474
Table 594: List of Modules of Control for 3340MX003 ................................................................................ 477
Table 595: List of Interlocks for 3340-FCV-712 ............................................................................................. 478
Table 596: List of Interlocks for 3340-FCV-715 ............................................................................................. 479
Table 597: Alarms and Process Setpoints for 3340MX003 System ......................................................... 479
Table 598: Regulatory Control Loops for 3340MX001 System ................................................................. 479
Table 599: List of Modules of Control for 3340BX109 ................................................................................. 484
Table 600: List of Interlocks for 3340-XV-301A ............................................................................................. 484
Table 601: List of Modules of Control for 3340XV302_303A.............................................................................. 485
Table 602: List of Interlocks for 3340-XV-303A ............................................................................................. 486
Table 603: List of Interlocks for 3340-XV-302A ............................................................................................. 487
Table 604: List of Modules of Control for 3340XV302_303B ..................................................................... 488
Table 605: List of Interlocks for 3340-XV-303B ............................................................................................. 489
Table 606: List of Interlocks for 3340-XV-302B ............................................................................................. 490
Table 607: List of Modules of Control for 3340XV302_303C.............................................................................. 491
Table 608: List of Interlocks for 3340-XV-303C ............................................................................................. 492
Table 609: List of Interlocks for 3340-XV-302C ............................................................................................. 492
Table 610: List of Unit Controls – 3340PU171 ............................................................................................... 494
Table 611: List of Interlocks for 3340-PU-171 ................................................................................................ 495
Table 612: Alarms and Process Setpoint 3340-PU-171 ............................................................................... 495
Table 613: Binary State Messages 3340PU171 ............................................................................................. 495
Table 614: List of Modules of Control for ECPF_3340TH101 .................................................................... 498
Table 615: List of Interlocks for 3340-DCV305 .............................................................................................. 498
Table 616: List of Interlocks for 3340-XV-304 ................................................................................................ 499
Table 617: Alarms and Process Setpoint ECPF_3340TH101 ..................................................................... 499
Table 618: Settler Pressure Transmitter Solids Calculation Constants ................................................. 500
Table 619: Binary State Messages ECPF_3340TH101................................................................................. 501
Table 620: Start Sequence ECPF_3340TH101 ............................................................................................... 502
Table 621: Stop Sequence ECPF_3340TH101 ............................................................................................... 502
Table 622: List of Unit Controls – 3340TH101UF .......................................................................................... 504
Table 623: List of Interlocks for 3340-XV-351A ............................................................................................. 504
Table 624: List of Interlocks for 3340-XV-351B ............................................................................................. 505
Table 625: List of Interlocks for 3340-XV-351C ............................................................................................. 505
Table 626: List of Interlocks for 3340 – PU - 104 .......................................................................................... 506

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 20 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 627: List of Interlocks for 3340-DX-356 ................................................................................................ 507


Table 628: List of Interlocks for 3340-XV-353 ................................................................................................ 507
Table 629: Alarms and Process Setpoint 3340TH101UF ............................................................................ 507
Table 630: Binary State Messages 3340TH101UF ........................................................................................ 508
Table 631: Regulatory Control Loops for 3340TH101UF ............................................................................ 509
Table 632: Start Sequence 3340PU104 ........................................................................................................... 510
Table 633: Stop Sequence 3340PU104 ............................................................................................................ 510
Table 634: List of Unit Controls – 3340TH101_RECIR ................................................................................. 512
Table 635: List of Interlocks for 3340-XV-351E ............................................................................................. 512
Table 636: List of Interlocks for 3340-XV-351D ............................................................................................. 512
Table 637: List of Interlocks for 3340-XV-348 ................................................................................................ 513
Table 638: Regrind Feed Sequence ................................................................................................................. 514
Table 639: Thickener Recirculation Sequence .............................................................................................. 514
Table 640: List of Modules of Control for ECPF_3340TH102 .................................................................... 516
Table 641: List of Interlocks for 3340-DCV305 .............................................................................................. 516
Table 642: List of Interlocks for 3340-XV-306 ................................................................................................ 517
Table 643: Alarms and Process Setpoint ECPF_3340TH102 ..................................................................... 517
Table 644: Settler Pressure Transmitter Solids Calculation Constants ................................................. 518
Table 645: Binary State Messages ECPF_3340TH102................................................................................. 519
Table 646: Start Sequence ECPF_3340TH102 ............................................................................................... 520
Table 647: Stop Sequence ECPF_3340TH102 ............................................................................................... 520
Table 648: List of Unit Controls – 3340TH102UF .......................................................................................... 522
Table 649: List of Interlocks for 3340-XV-352A ............................................................................................. 522
Table 650: List of Interlocks for 3340-XV-352B ............................................................................................. 523
Table 651: List of Interlocks for 3340-XV-352C ............................................................................................. 523
Table 652: List of Interlocks for 3340 – PU - 105 .......................................................................................... 524
Table 653: List of Interlocks for 3340-DX-358 ................................................................................................ 525
Table 654: List of Interlocks for 3340-XV-354 ................................................................................................ 525
Table 655: Alarms and Process Setpoint 3340TH102UF ............................................................................ 525
Table 656: Binary State Messages 3340TH102UF ........................................................................................ 526
Table 657: Regulatory Control Loops for 3340TH102UF ............................................................................ 527
Table 658: Start Sequence 3340PU105 ........................................................................................................... 528
Table 659: Stop Sequence 3340PU105 ............................................................................................................ 528
Table 660: List of Unit Controls – 3340TH102_RECIR ................................................................................. 530
Table 661: List of Interlocks for 3340-XV-352E ............................................................................................. 530
Table 662: List of Interlocks for 3340-XV-352D ............................................................................................. 530
Table 663: List of Interlocks for 3340-XV-349 ................................................................................................ 531
Table 664: Regrind Feed Sequence ................................................................................................................. 532
Table 665: Thickener Recirculation Sequence .............................................................................................. 532
Table 666: List of Modules of Control for ECPF_3340TH103 .................................................................... 534
Table 667: List of Interlocks for 3340-DCV305 .............................................................................................. 534
Table 668: List of Interlocks for 3340-XV-308 ................................................................................................ 535
Table 669: Alarms and Process Setpoint ECPF_3340TH103 ..................................................................... 535
Table 670: Settler Pressure Transmitter Solids Calculation Constants ................................................. 536
Table 671: Binary State Messages ECPF_3340TH103................................................................................. 537
Table 672: Start Sequence ECPF_3340TH103 ............................................................................................... 538
Table 673: Stop Sequence ECPF_3340TH103 ............................................................................................... 538
Table 674: List of Unit Controls – 3340TH103UF .......................................................................................... 540
Table 675: List of Interlocks for 3340-XV-391A ............................................................................................. 540

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 21 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 676: List of Interlocks for 3340-XV-391B ............................................................................................. 541


Table 677: List of Interlocks for 3340-XV-391C ............................................................................................. 541
Table 678: List of Interlocks for 3340 – PU - 108 .......................................................................................... 542
Table 679: List of Interlocks for 3340-DX-394 ................................................................................................ 543
Table 680: List of Interlocks for 3340-XV-392 ................................................................................................ 543
Table 681: Alarms and Process Setpoint 3340TH103UF ............................................................................ 543
Table 682: Binary State Messages 3340TH103UF ........................................................................................ 544
Table 683: Regulatory Control Loops for 3340TH103UF ............................................................................ 545
Table 684: Start Sequence 3340PU108 ........................................................................................................... 546
Table 685: Stop Sequence 3340PU108 ............................................................................................................ 546
Table 686: List of Unit Controls – 3340TH103_RECIR ................................................................................. 548
Table 687: List of Interlocks for 3340-XV-391E ............................................................................................. 548
Table 688: List of Interlocks for 3340-XV-391D ............................................................................................. 548
Table 689: List of Interlocks for 3340-XV-350 ................................................................................................ 549
Table 690: Regrind Feed Sequence ................................................................................................................. 550
Table 691: Thickener Recirculation Sequence .............................................................................................. 550
Table 692: List of Modules of Control for RMCPF_3340BX103 ................................................................ 552
Table 693: List of Interlocks for 3340-LCV-600A .......................................................................................... 552
Table 694: List of Interlocks for 3340-SA-101 ................................................................................................ 553
Table 695: Alarms and Process Setpoint RMCPF_3340BX103 ................................................................. 553
Table 696: Regulatory Control Loops for RMCPF_3340BX103 ................................................................. 554
Table 697: List of Unit Controls – 3340PU106 ............................................................................................... 556
Table 698: List of Interlocks for 3340-XV-602A ............................................................................................. 557
Table 699: List of Interlocks for 3340-XV-602B ............................................................................................. 557
Table 700: List of Interlocks for 3340-XV-602C ............................................................................................. 558
Table 701: List of Interlocks for 3340 – PU - 106 .......................................................................................... 559
Table 702: List of Interlocks for 3340-XV-602D ............................................................................................. 559
Table 703: List of Interlocks for 3340-DX-607 ................................................................................................ 560
Table 704: List of Interlocks for 3340-XV-604 ................................................................................................ 560
Table 705: Alarms and Process Setpoint 3340PU106 ................................................................................. 561
Table 706: Binary State Messages 3340PU106 ............................................................................................. 561
Table 707: Regulatory Control Loops for 3340PU106 ................................................................................. 561
Table 708: Start Sequence 3340PU106 ........................................................................................................... 563
Table 709: Stop Sequence 3340PU106 ............................................................................................................ 564
Table 710: List of Unit Controls – 3340PU107 ............................................................................................... 566
Table 711: List of Interlocks for 3340-XV-603A ............................................................................................. 567
Table 712: List of Interlocks for 3340-XV-603B ............................................................................................. 567
Table 713: List of Interlocks for 3340-XV-603C ............................................................................................. 567
Table 714: List of Interlocks for 3340 – PU-107 ............................................................................................ 569
Table 715: List of Interlocks for 3340-XV-603D ............................................................................................. 569
Table 716: List of Interlocks for 3340-XV-605 ................................................................................................ 570
Table 717: Alarms and Process Setpoint 3340PU107 ................................................................................. 570
Table 718: Start Sequence 3340PU107 ........................................................................................................... 571
Table 719: Stop Sequence 3340PU107 ............................................................................................................ 572
Table 720: List of Unit Controls – 3340CY110 ............................................................................................... 574
Table 721: List of Interlocks for 3340-XV-365 A though N ......................................................................... 574
Table 722: Alarms and Process Setpoint 3340CY110 ................................................................................. 574
Table 723: Regulatory Control Loops for 3340-PIC-364 ............................................................................. 575
Table 724: List of Unit Controls – 3340PU173 ............................................................................................... 578

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 22 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 725: List of Interlocks for 3340-PU-173 ................................................................................................ 578


Table 726: Alarms and Process Setpoint 3340-PU-173 ............................................................................... 579
Table 727: List of Unit Controls – 3340PU175 ............................................................................................... 581
Table 728: List of Interlocks for 3340-PU-175 ................................................................................................ 581
Table 729: Alarms and Process Setpoint 3340-PU-175 ............................................................................... 581
Table 730: List of Modules of Control for RMCPF_Alimentacion............................................................. 584
Table 731: List of Interlocks for 3340-ZV-370 ................................................................................................ 584
Table 732: Alarms and Process Setpoint RMCPF_Alimentacion ............................................................. 585
Table 733: List of Modules of Control for RMCPF_3340MI101 .................................................................. 587
Table 734: List of Interlocks for 3340-MI-101 ................................................................................................. 588
Table 735: List of Interlocks for 3340-XV-367A ............................................................................................. 588
Table 736: Alarms and Process Setpoint RMCPF_3340MI101 .................................................................. 588
Table 737: List of Modules of Control for RMCPF_3340MI102 .................................................................. 591
Table 738: List of Interlocks for 3340-MI-102 ................................................................................................. 592
Table 739: List of Interlocks for 3340-XV-366A ............................................................................................. 592
Table 740: Alarms and Process Setpoint RMCPF_3340MI102 .................................................................. 592
Table 741: List of Modules of Control for CRCFP_RETORNOCONC ...................................................... 595
Table 742: List of Interlocks for 3340-LCV-611A .......................................................................................... 595
Table 743: List of Interlocks for 3340-DX-381 ................................................................................................ 596
Table 744: List of Interlocks for 3340-DX-383 ................................................................................................ 596
Table 745: Alarms and Process Setpoint CRCFP_RETORNOCONC ....................................................... 597
Table 746: Binary State Messages CRCFP_RETORNOCONC ................................................................... 597
Table 747: Regulatory Control Loops for CRCFP_RETORNOCONC ....................................................... 598
Table 748: List of Unit Controls – 3340PU110 ............................................................................................... 601
Table 749: List of Interlocks for 3340-XV-612A ............................................................................................. 601
Table 750: List of Interlocks for 3340-XV-612B ............................................................................................. 602
Table 751: List of Interlocks for 3340-XV-612C ............................................................................................. 602
Table 752: List of Interlocks for 3340 – PU - 110 .......................................................................................... 603
Table 753: List of Interlocks for 3340-XV-614 ................................................................................................ 603
Table 754: Alarms and Process Setpoint 3340PU110 ................................................................................. 604
Table 755: Start Sequence 3340PU106 ........................................................................................................... 604
Table 756: Stop Sequence 3340PU110 ............................................................................................................ 605
Table 757: List of Unit Controls – 3340PU190 ............................................................................................... 607
Table 758: List of Interlocks for 3340-XV-613A ............................................................................................. 607
Table 759: List of Interlocks for 3340-XV-613B ............................................................................................. 607
Table 760: List of Interlocks for 3340-XV-613C ............................................................................................. 608
Table 761: List of Interlocks for 3340 – PU - 190 .......................................................................................... 609
Table 762: List of Interlocks for 3340-XV-615 ................................................................................................ 609
Table 763: Alarms and Process Setpoint 3340PU190 ................................................................................. 609
Table 764: Start Sequence 3340PU106 ........................................................................................................... 610
Table 765: Stop Sequence 3340PU190 ............................................................................................................ 611
Table 766: List of Unit Controls – 3340PU111 ............................................................................................... 613
Table 767: List of Interlocks for 3340-XV-384A ............................................................................................. 613
Table 768: List of Interlocks for 3340-XV-384B ............................................................................................. 614
Table 769: List of Interlocks for 3340-XV-384C ............................................................................................. 614
Table 770: List of Interlocks for 3340 – PU – 111 ......................................................................................... 615
Table 771: List of Interlocks for 3340-XV-384D ............................................................................................. 615
Table 772: List of Interlocks for 3340 XV - 388A ........................................................................................... 616
Table 773: List of Interlocks for 3340-XV-389 ................................................................................................ 616

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 23 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 774: List of Interlocks for 3340 XV –386A ........................................................................................... 617


Table 775: List of Interlocks for 3340 XV –386B ........................................................................................... 617
Table 776: List of Interlocks for 3340 XV –386C ........................................................................................... 618
Table 777: Alarms and Process Setpoint 3340PU111 ................................................................................. 618
Table 778: Start Sequence 3340PU111 ........................................................................................................... 619
Table 779: Stop Sequence 3340PU111 ............................................................................................................ 619
Table 780: List of Unit Controls – 3340PU191 ............................................................................................... 621
Table 781: List of Interlocks for 3340-XV-385A ............................................................................................. 621
Table 782: List of Interlocks for 3340-XV-385B ............................................................................................. 622
Table 783: List of Interlocks for 3340-XV-385C ............................................................................................. 622
Table 784: List of Interlocks for 3340 – PU – 191 ......................................................................................... 623
Table 785: List of Interlocks for 3340-XV-385D ............................................................................................. 623
Table 786: List of Interlocks for 3340 XV - 387A ........................................................................................... 624
Table 787: List of Interlocks for 3340-XV-390 ................................................................................................ 624
Table 788: Alarms and Process Setpoint 3340PU191 ................................................................................. 625
Table 789: Start Sequence 3340PU191 ........................................................................................................... 625
Table 790: Stop Sequence 3340PU191 ............................................................................................................ 626
Table 791: List of Modules of Control for CRCFP_RETORNOCONC ...................................................... 628
Table 792: List of Interlocks for 3340-XV-640A ............................................................................................. 629
Table 793: Alarms and Process Setpoint SCPF_AGUAPROCESOS ....................................................... 630
Table 794: Binary State Messages SCPF_AGUAPROCESOS ................................................................... 631
Table 795: List of Unit Controls – 3340PU112 ............................................................................................... 633
Table 796: List of Interlocks for 3340-PU-112 ................................................................................................ 633
Table 797: List of Interlocks for 3340-XV-644A ............................................................................................. 634
Table 798: Alarms and Process Setpoint 3340PU112 ................................................................................. 634
Table 799: Binary State Messages 3340PU112 ............................................................................................. 635
Table 800: Regulatory Control Loops for 3340PU112 ................................................................................. 635
Table 801: Start Sequence 3340PU112 ........................................................................................................... 636
Table 802: Stop Sequence 3340PU112 ............................................................................................................ 636
Table 803: List of Unit Controls – 3340PU114 ............................................................................................... 638
Table 804: List of Interlocks for 3340-PU-114 ................................................................................................ 638
Table 805: List of Interlocks for 3340-XV-645A ............................................................................................. 639
Table 806: Alarms and Process Setpoint 3340PU114 ................................................................................. 639
Table 807: Regulatory Control Loops for 3340PU114 ................................................................................. 639
Table 808: Start Sequence 3340PU114 ........................................................................................................... 640
Table 809: Stop Sequence 3340PU114 ............................................................................................................ 640
Table 810: List of Unit Controls – 3340PU115 ............................................................................................... 642
Table 811: List of Interlocks for 3340-PU-115 ................................................................................................ 642
Table 812: Alarms and Process Setpoint 3340PU115 ................................................................................. 643
Table 813: Binary State Messages 3340PU115 ............................................................................................. 643
Table 814: Regulatory Control Loops for 3340PU115 ................................................................................. 643
Table 815: Precedence of Opening for Flush Water Valves ...................................................................... 644
Table 816: List of Unit Controls – 3340PU109 ............................................................................................... 645
Table 817: List of Interlocks for 3340-PU-109 ................................................................................................ 646
Table 818: Alarms and Process Setpoint 3340PU109 ................................................................................. 646
Table 819: Binary State Messages 3340PU109 ............................................................................................. 647
Table 820: Regulatory Control Loops for 3340PU109 ................................................................................. 647
Table 821: List of Unit Controls – 3720PU007 ............................................................................................... 649
Table 822: List of Interlocks for 3720-PU-007 ................................................................................................ 649

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 24 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 823: List of Interlocks for 3720-XV-110 ................................................................................................ 650


Table 824: Alarms and Process Setpoint 3720PU007 ................................................................................. 650
Table 825: Binary State Messages 3720PU007 ............................................................................................. 650
Table 826: Regulatory Control Loops for 3720PU007 ................................................................................. 651
Table 827: Start Sequence 3720PU007 ........................................................................................................... 651
Table 828: Stop Sequence 3720PU007 ............................................................................................................ 652
Table 829: List of Unit Controls – 3720PU008 ............................................................................................... 654
Table 830: List of Interlocks for 3720-PU-008 ................................................................................................ 654
Table 831: List of Interlocks for 3720-XV-115A ............................................................................................. 655
Table 832: Alarms and Process Setpoint 3720PU008 ................................................................................. 655
Table 833: Regulatory Control Loops for 3720PU007 ................................................................................. 655
Table 834: Start Sequence 3720PU008 ........................................................................................................... 656
Table 835: Stop Sequence 3720PU008 ............................................................................................................ 656
Table 836: List of Modules of Control for SCPF_AGUASELLO ................................................................ 658
Table 837: List of Interlocks for 3340-XV-650 ................................................................................................ 658
Table 838: Alarms and Process Setpoint SCPF_AGUASELLO ................................................................ 658
Table 839: Binary State Messages SCPF_AGUASELLO ............................................................................ 659
Table 840: List of Unit Controls – 3340PU192 ............................................................................................... 660
Table 841: List of Interlocks for 3340-XV-654A ............................................................................................. 661
Table 842: List of Interlocks for 3340-PU-192 ................................................................................................ 662
Table 843: List of Interlocks for 3340-XV-654B ............................................................................................. 662
Table 844: Start Sequence 3340PU192 ........................................................................................................... 663
Table 845: Stop Sequence 3340PU192 ............................................................................................................ 663
Table 846: List of Unit Controls – 3340PU193 ............................................................................................... 664
Table 847: List of Interlocks for 3340-XV-655A ............................................................................................. 665
Table 848: List of Interlocks for 3340-PU-193 ................................................................................................ 665
Table 849: List of Interlocks for 3340-XV-655B ............................................................................................. 666
Table 850: Start Sequence 3340PU193 ........................................................................................................... 667
Table 851: Stop Sequence 3340PU193 ............................................................................................................ 667
Table 795: List of Unit Controls – 3340CP101_103 ...................................................................................... 670
Table 796: List of Interlocks for 3340-CP-101 ................................................................................................ 670
Table 796: List of Interlocks for 3340-CP-102 ................................................................................................ 671
Table 796: List of Interlocks for 3340-CP-103 ................................................................................................ 671
Table 798: Alarms and Process Setpoint 3340CP101_103 ........................................................................ 671
Table 800: Regulatory Control Loops for 3340CP101_103 ........................................................................ 672
Table 795: List of Unit Controls – 3340AR101 ............................................................................................... 673
Table 798: Alarms and Process Setpoint 3340AR101 ................................................................................. 674
Table 839: Binary State Messages 3340AR101 ............................................................................................. 674
Table 795: List of Unit Controls – 3340AR102 ............................................................................................... 676
Table 798: Alarms and Process Setpoint 3340AR102 ................................................................................. 677
Table 795: List of Unit Controls – 3340AR103 ............................................................................................... 679
Table 798: Alarms and Process Setpoint 3340AR103 ................................................................................. 680
Table 839: Binary State Messages 3340AR103 ............................................................................................. 680

LIST OF FIGURES
Figure 1: Blockflow Diagram ............................................................................................................................... 28
Figure 2: Simplified Process Flow Diagram of the CPF Plant ..................................................................... 30
Figure 3 CPF Global Start Sequence ................................................................................................................. 40

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 25 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 4: PLC Selection – Deslime and Crossflow Feed .............................................................................. 50


Figure 5: PLC Selection – Crossflow & Hydrofloat Separators B .............................................................. 51
Figure 6: PLC Selection – Crossflow & Hydrofloat Separators C .............................................................. 51
Figure 7: PLC Selection – Concentrate Thickening ....................................................................................... 52
Figure 8: PLC Selection – Regrind Milling ....................................................................................................... 53
Figure 9: PLC Selection – Concentrate Return and Tails Sampling .......................................................... 54
Figure 10: PLC Selection – Water Reticulation ............................................................................................... 55
Figure 11: PLC Selection – Frother Bulk Storage and Dosing .................................................................... 56
Figure 12: PLC Selection – Collector Dosing .................................................................................................. 57
Figure 13: PLC Selection – Compressed Air ................................................................................................... 58
Figure 14: Blockflow Control Diagram of the CDCPF_Deslamado System ............................................. 61
Figure 15: Blockflow Control Diagram of the 3340PU101 System ............................................................. 67
Figure 16: Blockflow Control Diagram of the 3340PU102 System ............................................................. 78
Figure 17: Blockflow Control Diagram of the 3340CY101 System ............................................................. 91
Figure 18: Blockflow Control Diagram of the 3340CY102 System ............................................................. 96
Figure 19: Blockflow Control Diagram of SFCPF_AlimFlujoCruzado System ...................................... 101
Figure 20: Blockflow Control Diagram of the 3340PU185 System ........................................................... 106
Figure 21: Blockflow Control Diagram of the 3340PU186 System ........................................................... 116
Figure 22: Blockflow Control Diagram of the 3340DB103 System........................................................... 126
Figure 23: Blockflow Control Diagram of the 3340DB104 System........................................................... 128
Figure 24: Blockflow Control Diagram of SFCPF_SEPHFL1 System ...................................................... 132
Figure 25: Blockflow Control Diagram of the 3340SepHF101 System .................................................... 134
Figure 26: Blockflow Control Diagram of the 3340HF101 System ........................................................... 137
Figure 27: Blockflow Control Diagram of the 3340HF101 System ........................................................... 143
Figure 28: Blockflow Control Diagram of SFCPF_SEPHFL2 System ...................................................... 222
Figure 29: Blockflow Control Diagram of CRCFP_Relaves System ........................................................ 304
Figure 30: Blockflow Control Diagram of the 3340PU197 System ........................................................... 311
Figure 31: Blockflow Control Diagram of RECPF_Collector3894 ............................................................ 317
Figure 32: Blockflow Control Diagram of the 3520PU179 System ........................................................... 333
Figure 33: Blockflow Control Diagram of the 3350PU120_121 System .................................................. 336
Figure 34: Blockflow Control Diagram of the 3350PU120 System ........................................................... 337
Figure 35: Blockflow Control Diagram of the 3350PU121 System ........................................................... 341
Figure 36: Blockflow Control Diagram of RECPF_Collector404............................................................... 345
Figure 37: Blockflow Control Diagram of the 3520PU182 System ........................................................... 361
Figure 38: Blockflow Control Diagram of the 3350PU160 System ........................................................... 364
Figure 39: Blockflow Control Diagram of the 3350PU161 System ........................................................... 368
Figure 40: Blockflow Control Diagram of RECPF_CollectorZ6................................................................. 373
Figure 41: Blockflow Control Diagram of the 3520PU181 System ........................................................... 388
Figure 42: Blockflow Control Diagram of the 3350PU150 System ........................................................... 391
Figure 43: Blockflow Control Diagram of the 3350PU151 System ........................................................... 395
Figure 44: Blockflow Control Diagram of RECPF_CollectorDIESEL ....................................................... 400
Figure 45: Blockflow Control Diagram of the 3520PU180 System ........................................................... 415
Figure 46: Blockflow Control Diagram of the 3350PU130 System ........................................................... 418
Figure 47: Blockflow Control Diagram of the 3350PU131 System ........................................................... 422
Figure 48: Blockflow Control Diagram of RECPF_AlmEspumante ......................................................... 426
Figure 49: Blockflow Control Diagram of the 3350PU178 System ........................................................... 428
Figure 50: Blockflow Control Diagram of the 3350PU176_177 System .................................................. 431
Figure 51: Blockflow Control Diagram of RECPF_Espumante ................................................................. 436
Figure 52: Blockflow Control Diagram of the 3350PU140 System ........................................................... 451

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 26 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 53: Blockflow Control Diagram of the 3350PU141 System ........................................................... 455
Figure 54: Blockflow Control Diagram of FCPF_Alimentacion System ................................................. 459
Figure 55: Blockflow Control Diagram of the 3520PU195 System ........................................................... 460
Figure 56: Blockflow Control Diagram of the 3520PU196 System ........................................................... 464
Figure 57: Blockflow Control Diagram of the 3340MX001 System ..........................................................468
Figure 58: Blockflow Control Diagram of the 3340MX002 System ..........................................................472
Figure 59: Blockflow Control Diagram of the 3340MX003 System ..........................................................477
Figure 60: Blockflow Control Diagram of ECPF_ALIMENTACION ........................................................... 482
Figure 61: Blockflow Control Diagram of the 3340BX109 System ........................................................... 483
Figure 62: Blockflow Control Diagram of the 3340XV302_303A System ............................................... 485
Figure 63: Blockflow Control Diagram of the 3340XV302_303B System ............................................... 488
Figure 64: Blockflow Control Diagram of the 3340XV302_303C System ............................................... 491
Figure 65: Blockflow Control Diagram of the 3340PU171 System ........................................................... 494
Figure 66: Blockflow Control Diagram of ECPF_3340TH101 .................................................................... 497
Figure 67: Blockflow Control Diagram of the 3340TH101UF System ...................................................... 503
Figure 68: Blockflow Control Diagram of the 3340TH101_RECIR System ............................................ 511
Figure 69: Blockflow Control Diagram of ECPF_3340TH102 .................................................................... 515
Figure 70: Blockflow Control Diagram of the 3340TH102UF System ...................................................... 521
Figure 71: Blockflow Control Diagram of the 3340TH102_RECIR System ............................................ 529
Figure 72: Blockflow Control Diagram of ECPF_3340TH103 .................................................................... 533
Figure 73: Blockflow Control Diagram of the 3340TH103UF System ...................................................... 539
Figure 74: Blockflow Control Diagram of the 3340TH103_RECIR System ............................................ 547
Figure 75: Blockflow Control Diagram of RMCPF_3340BX103 ................................................................. 551
Figure 76: Blockflow Control Diagram of the 3340PU106 System ........................................................... 555
Figure 77: Blockflow Control Diagram of the 3340PU107 System ........................................................... 565
Figure 78: Blockflow Control Diagram of the 3340CY110 System ........................................................... 573
Figure 79: Blockflow Control Diagram of the 3340PU173 System ........................................................... 577
Figure 80: Blockflow Control Diagram of the 3340PU175 System ........................................................... 580
Figure 81: Blockflow Control Diagram of RMCPF_Alimentacion ............................................................. 583
Figure 82: Blockflow Control Diagram of RMCPF_3340MI101 .................................................................. 586
Figure 83: Blockflow Control Diagram of RMCPF_3340MI102 .................................................................. 590
Figure 84: Blockflow Control Diagram of CRCFP_RETORNOCONC ....................................................... 594
Figure 85: Blockflow Control Diagram of the 3340PU110 System ........................................................... 600
Figure 86: Blockflow Control Diagram of the 3340PU190 System ........................................................... 606
Figure 87: Blockflow Control Diagram of the 3340PU111 System ........................................................... 612
Figure 88: Blockflow Control Diagram of the 3340PU191 System ........................................................... 620
Figure 89: Blockflow Control Diagram of SCPF_AGUAPROCESOS ....................................................... 627
Figure 90: Blockflow Control Diagram of the 3340PU112 System ........................................................... 632
Figure 91: Blockflow Control Diagram of the 3340PU114 System ........................................................... 637
Figure 92: Blockflow Control Diagram of the 3340PU115 System ........................................................... 641
Figure 93: Blockflow Control Diagram of the 3340PU109 System ........................................................... 645
Figure 94: Blockflow Control Diagram of the 3720PU007 System ........................................................... 648
Figure 95: Blockflow Control Diagram of the 3720PU008 System ........................................................... 653
Figure 96: Blockflow Control Diagram of SCPF_AGUASELLO ................................................................ 657
Figure 97: Blockflow Control Diagram of the 3340PU192 System ........................................................... 660
Figure 98: Blockflow Control Diagram of the 3340PU193 System ........................................................... 664
Figure 96: Blockflow Control Diagram of SCPF_InstAir .............................................................................668
Figure 90: Blockflow Control Diagram of the 3340CP101_103 System .................................................. 669
Figure 90: Blockflow Control Diagram of the 3340AR101 System........................................................... 673

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 27 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 90: Blockflow Control Diagram of the 3340AR102 System........................................................... 676


Figure 90: Blockflow Control Diagram of the 3340AR103 System........................................................... 679

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 28 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

1.0 INTRODUCTION

The scope of this document is to describe the discrete and regulatory control lines considered
for the Coarse Particle Flotation Plant (CPF), in the Quellaveco Project.
2.0 PROCESS DESCRIPTION

Anglo-American’s Quellaveco (AAQ) project is located in Peru, approximately 50 km to the east


of Moquegua, 236 km to the south-east of Arequipa and 1,200 km to the south-east of Lima, Peru.
The Papajuane concentrator plant will process 127,500 tpd of ore through primary crushing,
grinding, a collective Copper-Molybdenum (Cu-Mo) flotation process and a selective molybdenum
flotation process.
The Cu-Mo flotation process consists of a rougher flotation circuit followed by two sequential
cleaning stages and will produce a combined Cu-Mo concentrate. The rougher tailings produced
in the collective Cu-Mo flotation process contain valuable copper minerals within the coarser size
fractions which would otherwise be lost to final plant tailings. Conventional flotation preferentially
captures particles up to 150 µm, whereas, an important fraction of the valuable sulphides is
contained in the rougher tailings greater than 150 µm in size.
The Coarse Particle Flotation plant (CPF) will scavenge these coarser sulphide particles normally
lost to the rougher tailings stream. CPF is a technology designed to recover non-liberated valuable
minerals contained in coarser ground ores with an exposed valuable mineral surface area as low
as 1% - 2% of the total surface area and at particle sizes as high as 500 to 700 µm.

330- PC – 101 A, B and C

Coarse Particle
Flotation (CPF)

Flotacion
Molienda Relaves
Rougher

Flotacion
Remolienda Scavenger y
Primeira Limpieza

Espesamiento
Flotacion Columna
de Concentrado
(2da Limpieza)
Cu & Mo

Figure 1: Blockflow Diagram

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 29 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The scope of this document is the scope of the limits of the driver tags 334O-PC-1O1 A/B and C
identified in the figure above.

The CPF Plant for the Quellaveco project includes the following unit operations:

 Coarse Particle Classification and Desliming;

 Crossflow Separation

 Coarse Particle Flotation;

 Concentrate Thickening

 Concentrate Regrinding;

 Concentrate Return

 Reagents; and

 Utilities.

A high-level description of the process flow control requirements of the CPF plant is provided
below. Detailed specifications of each section are specified in subsequent sections of this
document.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 30 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

DRA Distributor
Rougher Flotation Tailings
Others Deslime Cyclone Two off
Cluster
3340 – LN – 103 (2)
CPF Plant Feed Launder
CPF Plant
Feed Box

Crossflow Separator
CrossFlow Feed (10)
Surge Tank Crossflow Feed
Pump
Deslime Feed Pump (2 + 0)
(2 + 0)
Feed Box Emergency
Overflow Chute
Emergency Overflow
Launder
Other
Regrind Cyclone Hydrofloat DRA
Cluster (1) (10)
Deep Cone Settlers
Ø 12m
(2+1)
Underflow
Distributor Tails Launder
Feed Box

Settler U/flow Pump (1 CPF Tails Launder Other


per Settler) DRA

Vertical Regrind Tails Thickening


Mills (2) Product Sampler
Fluidisation Overflow Box
Water Tanks 3710 – BX – 003
Regrind Cyclone Recovered Water
Tank (3) Fluidisation Water
Feed Pump Pump (2)
(1 + 1)
DRA Flush Water Pump
Low Pressure CPF (1)
Others
CPF Make-Up Water Reticulation
Water Pump Froth Suppression
(2) Pump (1) Bulk Rougher Flotation
Other
Hydrofloat Reground Concentrate
DRA
Concentrate Return
Collection Box 3310 – DB - 001
Concentrate Return
Concentrate Return Pump (1 + 1)
Pump (1 + 1)

Figure 2: Simplified Process Flow Diagram of the CPF Plant

2.1 Coarse Particle Feed Classification and Desliming (3340 – PLC – 101A)

The CPF feed is laundered from the Papajuane Concentrators’ rougher tailings slurry. The slurry
is gravitated down a concrete launder and discharged into Tailings Collection Box (3710 – BX –
003). The rougher tailings slurry is diverted by means of actuated flopper gate swingover system,
supplied by others, to gravitate down the CPF Plant Feed Launder (3340 – LN – 103). On
discharge from the concrete feed launder, the slurry velocity is attenuated and distributed by the
Plant Feed Break Box (3340 – BX – 100) into the Plant Feed Box (3340 – BX – 101).
Due to the large slurry volumes expected within the design, the Plant Feed Box may overflow for
a limited time while the flopper gates are closing. Slurry will overflow the pump box into the
Emergency Overflow Launder (3340 – LN – 104) and gravitate to the Tailings Collection Box
(3710 – BX – 003) supplied by others.
The slurry within the Plant Feed Box (3340 – BX – 101) is then pumped by two operating, variable
speed Deslime Cyclone Feed Pumps (3340 – PU – 101 / 102) to the two Deslime Cyclone
Clusters 1 & 2 (3340 – CY – 101 / 102). The level in the Plant Feed Box is measured by level
transmitter (3340-LIT-001) and controlled by varying the speed of the pumps.
The suction valves to the pumps are hydraulically actuated and are supplied with a hydraulic
power pack within a vendor package.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 31 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The Deslime Cyclone feed flowrate is measured (3340-FIT-008 / 010) and will not be allowed to
reduce below a minimum in order to prevent risks of pipeline sedimentation blockage. Slurry
density is also measured (3340-DIT-009 / 011) for mass balancing purposes.
The two Deslime Cyclone Clusters (3340 – CY – 101 / 102) receive the pumped slurry and provide
a size separation on the material. Cyclone feed pressure (3340-PIT-014A / 017A) is controlled by
varying the number of cyclone feed valves (3340-XV-015 / 018 A-AD) opened. If the cyclone feed
pressure is above the high setpoint limit for a specified time, another feed valve will open.
Conversely if the feed pressure is below the low setpoint limit for a specified time, a valve will
close.
2.2 Coarse Particle Separation (3340 – PLC – 101 B and C)

The Crossflow Feed Surge Tank (3340 – TK – 101) recombines the two deslime cyclone
underflow streams and provides a buffer surge capacity for the material while it is diluted before
being pumped at a controlled rate to the two Crossflow Distributors (3340 – DB – 103 / 104).
The level in the Crossflow Feed Surge Tank (3340-LIT-033) is controlled by adjusting the tanks
level control valve (3340-LCV-032) to a selected setpoint.
The Crossflow Feed Surge Tank Agitator (3340 – AG – 101) has a lubrication oil system for its
gearbox, with a drive-less lubrication oil pump powered from the rotating shaft that recirculates oil
through the gearbox. Should the oil temperature (3340-TS-034) reduce to a minimum value
specified by the vendor, the oil heater will switch on immediately. Unless the Surge Tank level is
Low Low, it is imperative that the agitator is never stopped while solids are contained within the
tank, even during plant shutdown events. The agitator will stop if the slurry level in the surge tank
(3340-LIT-033) reaches a Low Low limit. Prior to restarting the agitator, the operator shall confirm
its blades are free of any settled sediment.
Two Crossflow Feed Pumps (3340 – PU – 185 / 186) pump the re-pulped deslime cyclone
underflow to the Crossflow Distributors (3340 – DB – 103 / 104) at a controlled flowrate. The
individualised Crossflow Feed Pump slurry densities are measured by densitometer (3340-DIT-
028 and 030), while the flowrates are measured by flow transmitters (3340-FIT-027 / 029) and
compared to the two pumps individual setpoints.
Crossflow Separator feed slurry is pumped into two Crossflow Separator Distributors (3340 – DB
– 103 / 104) at a controlled rate. Each five-way distributor discharges slurry evenly to the available
Crossflow Separators (3340 – CF – 101 through 110). Should a Crossflow Separator / Hydrofloat
module not be available, it is isolated by closing the respective distributors discharge valve (3340-
XV-036 A – E and 3340-XV-038 A – E). Crossflow Feed Distributor pressure is measured (3340-
PIT-035A / 037A) and should it be below a low limit an alarm will be generated.
The Crossflow Separator (3340 – CF – 101 through 110) function is to elutriate out the ultrafine
material prior to discharging the coarsened slurry to the hydroflotation unit directly below.
Teeter water is injected into the separator via module isolation valve (3340-XV-040A) and teeter
water control valve (3340-FCV-101) which is controlled to a constant fluidised bed density as
measured by two pressure transmitters (3340-PIT-103A and 103B). The overall solids bed level

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 32 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

in the Crossflow Separator is measured by a level transmitter (3340-LIT-102 through 192) and
controlled by adjusting the opening of the underflow control valve (LCV – 102 through 192).
2.3 Coarse Particle Flotation (3340 – PLC – 101 B and C)

The Hydrofloat units (3340 – HF – 101 through 110) provide the coarse particle flotation
separation of the CPF plant. Air bubbles attach to material containing sulphide surfaces and are
carried to the overflow by the injected teeter water. Pre-aeration water and air are injected into
the units feed hopper at a controlled rate via control valves (3340-FCV-201 and 3340-FCV-202).
Teeter water and air are injected into the separator at a controlled rate via control valves (3340-
FCV-203 and 3340-FCV-204A/B). Teeter water flowrate is used to achieve a constant fluidised
bed density as measured by two pressure transmitters (3340-PIT-206A and 103B).
Three internal CPF Tails Launders (3340 – LN – 106 / 107 / 108) gravitate Hydrofloat rejects and
Crossflow Separator overflow to a Tails Launder Feed Box (3340 – BX – 110) where the slurry is
combined with Deslime Cyclone Overflow and laundered via an external final Tails Launder (3340
– LN – 105) the Tailings Collection Box (3710 – BX – 003) supplied by others.
The respective tails launder flush valves (3340-XV-700 / 701 / 702) can be opened by the control
room operator in order to prevent tails launder blockages while purging a Crossflow Separator or
Hydrofloat unit which is not in operation (i.e. does not have a Crossflow Separator overflow stream
to flush the solids).
A portion of the CPF final tails launder is bled to the Tails Return Pump box (3340 – BX – 135)
from where it is pumped to the Tails Sampler (3340 – SA – 103) and online analyser (3340 – AY
– 105) by means of a variable speed Tails Return Sample Pump (3340 – PU – 197). The Tails
Sampler (3340 – SA – 103) and Analyser (3340 – AY – 105) are contained within the same vendor
package item. The unit provides an online information of specific elemental analysis which
confirms to the operator the online real time estimate of the CPF tails grade. A physical sample
is also obtained from the sampler over a period of time, facilitating laboratory analysis and weekly
analyser calibration. The sampler and analyser are equipped with their own PLC controller. The
start / stop signal will be provided by either Crossflow Feed Pump (3340 – PU – 185 / 186) running
signals being healthy.
2.4 Concentrate Thickening (3340 – PLC – 101 A)

Hydrofloat concentrate is gravitated to the Thickener Feed Box (3340 – BX – 109) which reduces
slurry velocity prior to distributing it to the respective deep cone settlers (alternatively referred to
as thickeners) (3340 – TH – 101 / 102 / 103). Spray water is utilised as froth suppression water
(3340-XV-301A) within the box. All thickening area process water is supplied by a dedicated Froth
Suppression and Dilution Water Pump (3340 – PU – 109).
Although three deep cone settlers are installed, one can be utilised as a standby if required (i.e.
two operating). Under normal circumstances however, all three will operate to reduce up flow
velocity and maximise overflow water clarity. The Thickener Feed Valve (3340-XV-303A, 303B,
303C) isolates the individual thickener should it contain a high level of solids (3340-LIT-310 / 312
/ 314) or its underflow pump stop. Before re-opening the thickener feed valve, backflush water

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 33 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

must first be injected by opening a flush valve (3340-XV-302A, 302B, 302C) for a specified time,
prior to the feed valve opening to re-fluidise any solids build-up.
On gravitating into the individual Deep Cone Settler Thickener (3340 – TH – 101 / 102 / 103), the
slurry is distributed within the settlers centre well. Solids agglomerate with the controlled addition
of flocculant (see section below) and settle to the base of the settler, while water rises and is
discharged to the overflow into the Fluidisation Water Tanks (3340 – TK – 102, 103 and 104).
Froth suppression water (3340-XV-304 / 306 / 308) is sprayed around the respective centre wells’
and settler perimeters. Each settler has three pressure transmitters (3340-PIT-311A/B/C,
313A/B/C and 315A/B/C) located vertically above each other to assess the total solids above
each unit’s location. The three separate pressure transmitters are utilised to ensure that no
bridging is occurring on the outlet of each individual transmitter. Similarly, a separate ultrasonic
level transmitter (3340-LIT-310 / 312 / 314) provides an alternative measurement of the height of
the solids mud bed within the settler. Once settled at the base of the thickener, solids will quickly
compact to a high density and require re-fluidisation prior to being pumped from the thickener at
a controlled slurry density to the Regrind Mill circuit. For this to occur, dilution water is injected at
a controlled rate into the base of the thickener via a modulating control valve (3340-DCV-305 /
307 / 309).
A dedicated underflow pump (3340 – PU – 104, 105 and 108) is installed per settler. If this pump
is not running, the settler feed valve must close (3340-XV-303A, 303B, 303C). The thickener
underflow pump flow control loop setpoint is adjusted to achieve the following:
 While the slurry is recirculating in bypass mode (i.e. bypass valve is open), the underflow
pump flowrate setpoint will be reduced to the low limit value in order to minimise the
quantity of solids recirculated, flocculant usage and risks of solids overflowing to the
fluidisation water tanks.
 While the slurry is being pumped to the regrind mills, the flowrate setpoint will be controlled
by maintaining the pressure (i.e. quantity of solids held within the thickener) to the selected
setpoint as measured (3340-PIT-311C / 313C / 315C). The minimum slurry flowrate will
be limited to prevent pipeline sedimentation blockage. Should this minimum flowrate occur
for a specified time, the underflow pump discharge valves will open/close and redirect the
slurry back into the feed box for recirculation (i.e. bypass mode) until the solids level in the
thickener rises again to the specified setpoint value. While the slurry is being pumped to
the regrind mills, the maximum flowrate shall be limited by the regrind cyclone feed pump
maximum density limit (3340-DI-607).
By combining the flow transmitter and densitometer readings, a totalized mass flow to the regrind
mills will be calculated.
2.5 Concentrate Regrinding (3340 – PLC – 101 A)

Regrind cyclone underflow is combined with thickener underflow (i.e. mill new feed) in a Thickener
Underflow Collection Box (3340 – BX – 140) and discharged into the Underflow Distributor (3340
– DB – 105). The distributor allows for an adjustable, even split of the slurry to occur between the
two regrind mills. Under normal conditions, the splitter will be positioned manually by the control
room operator such that an even (50:50) split of slurry is effected. This can either be visually

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 34 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

assessed by an operator in the field or alternatively by comparing the power draw of the two mills.
Should one mill be offline, the distributor can be swung over by the control room operator to fully
discharge exclusively to the operating mill.
Two Regrind Mills (3340 – MI – 101 / 102) complete with lubrication system are a vendor package
item. During shutdown conditions, the mills are required to be operated until their product slurry
density drops below a specified value as defined in the vendor functional specification. While the
slurry is being purged from the mill, flush water is injected into the mill by opening the automated
flush water valve (3340-XV-366A / 367A). The opening and closing of these actuated valves
would be done at the request of the operator in the field. These valves are normally closed while
the mills operate.
The regrind mill product gravitates into the Regrind Cyclone Feed Pump Box (3340 – BX – 103)
where it is diluted with process water and pumped by a running / standby variable speed pump
(3340 – PU – 106 / 107) at a controlled density to the Regrind Cyclone Cluster (3340 – CY – 110).
The slurry level in the box is controlled to a selected setpoint by varying the percentage opening
of the sumps level control valve (3340-LCV-600A).
A running/standby pump arrangement is required to discharge the Regrind Mill product into the
Regrind Product Cyclone cluster at a controlled density.
The regrind cyclone feed flowrate setpoint is adjusted to achieve a final concentrate product return
slurry solids concentration to the Papajuane concentrator of 30%mass. If this concentrate return
density (3340-DIT-381 / 383) is too high, the regrind cyclone feed flowrate (3340-FIT-606) setpoint
will increase. This will speed up the variable speed regrind cyclone feed pump and vice versa. At
all times however, a minimum flowrate level shall be maintained in the regrind cyclone feed line
to prevent any risk of pipeline sedimentation blockage. Slurry density is also measured (3340-
DIT-607) for mass balancing purposes. Should this density rise above a maximum limit, the new
mill feed from the thickener underflow pumps will reduce .
The Regrind Mill Hydrocyclone cluster (3340 – CY – 110) receives the pumped milled slurry
product and effects a size separation on the material. Cyclone feed pressure (3340-PIT-364A) is
controlled by varying the number of cyclone feed valves (3340-XV-365 A-N) opened. If the
cyclone feed pressure is above the high setpoint limit for a specified time, another feed valve will
open. Conversely if the feed pressure is below the low setpoint limit for a specified time, a valve
will close.
The Product Sampler (3340 – SA – 101) and Analyser (3340 – AY – 101) are contained within
the same vendor package item. The unit provides an online information of specific elemental
analysis which confirms to the operator the online real time estimate of the CPF product grade. A
physical, metallurgical grade quality sample is also obtained from the sampler over a period of
time, facilitating laboratory analysis and weekly analyser calibration. The start / stop signal will be
provided by either Regrind Cyclone Feed Pump (3340 – PU – 106 / 107) running signals being
healthy.
A ball reload hopper (3340 – ZA – 101) is used to manually discharge balls into a sputnik skip
(3340 – ZA – 102). The actuator position is changed by the operator in the plant with a field switch.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 35 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The sputnik is then raised to the respective mill by an electric hoist (3340 – HT – 101) and then
manually discharged. All these functions are conducted by the operator in the field.
2.6 Concentrate Return (3340 – PLC – 101 A)

The CPF concentrate product gravitates into the Concentrate Return Collection Box (3340 – BX
– 106). The slurry level in the box is controlled by varying the speed of the concentrate return
pumps. A minimum line velocity must be maintained within the return pipeline and hence a level
control water valve (3340-LCV-611) will additionally be used to maintain the level of the sump
when it falls to the low level limit.
Two pumps in series are required to return the CPF concentrate to the Papajuane rougher
flotation circuit. A standby two-stage pump system is installed. Due to project space limitation, the
first and second stage pumps are in different areas of the CPF, thus requiring more complex
piping/flushing considerations.
The CPF concentrate slurry can discharge to three locations:
 Normal operation is to discharge concentrate to the Papajuane rougher flotation circuit
feed box (3310 – BX - 005). A two-stage pumping system is required for this to occur. The
first stage pump will operate at maximum (100% VFD, fixed) speed, while the second
stage pump speed will be adjusted to maintain a consistent Concentrate Return Collection
Box level (3340-LIT-611). A minimum flowrate limit will prevent the flowrate from reducing
to where pipeline sedimentation blockage could occur;
 CPF Tails launder. This will typically be utilised while purging the CPF during shutdown
occasions when the second stage pump system is stopped. In this case, the first stage
pump speed will be adjusted to maintain a consistent Concentrate Return Collection Box
level (3340-LIT-611). A minimum flowrate limit will prevent the flowrate from reducing to
where pipeline sedimentation blockage could occur;
 CPF Plant Feed Box. This will be utilised to operate the full CPF circuit, recycling product
back into the CPF feed, without affecting the operation of the Papajuane concentrator.
Proving all interlocks and process flow systems in this manor will be invaluable during
commissioning. Although the slurry will pass through the second stage pump, it will not be
required to provide additional energy to the slurry system. Consequently, the first stage
pump speed will be adjusted to maintain a consistent Concentrate Return Collection Box
level (3340-LIT-611) while the second stage will merely rotate/idle. A minimum flowrate
limit will prevent the flowrate from reducing to where pipeline sedimentation blockage
could occur.
Flowrate is measured in the two running/standby pipelines from the first stage pumps (3340-FIT-
380 or 3340-FIT-382) and should it reduce to a low limit, the pump speed will be increased to
ensure line velocities are maintained above low limits. Above this limit, the pump speed will be
adjusted to control the level in the concentrate return pump box (3340-BX-106). Slurry density is
also measured (3340-DIT-381 or 3340-DIT-383) and controlled to 30% mass solids density in
order not to dilute the Papajuane concentrators’ rougher feed. The density is controlled by varying

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 36 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

the flowrate setpoint of the regrind cyclone feed pumps (3340-FIC-606). However, the line
flowrate setpoint will have a low limitation to avoid pipeline sedimentation blockage risks.
2.7 Reagents (3340 – PLC – 101 A)

All collector reagent bulk make-up and dosing systems are similar. As such only one will be
described below. The bulk make-up for polypropylene frother is also similar but is a vendor
package item. All reagent day tank dosing systems are vendor packages.
The bulk reagent is pumped by a fixed speed pump to the Reagent Day Tanks (3350 – TK – 103
/ 104 / 105 / 108 / 110) which are batch filled. The Bulk Reagent Transfer Pump will start when
the respective Reagent Day Tank has a low limit (3350-LI-201A / 221A / 206A / 211A / 216A).
The reagent is then pump from the Reagent Day Tanks via a running/standby pump system and
the discharge pipe ring main pressure regulated by a pressure sustaining valve. The reagents are
dosed individually to the Crossflow Separators and Hydrofloats. The flowrate of each reagent is
based upon the calculated dry mass flow rate to the individual module. A reagent dosing control
loop will compare the calculated setpoint to the measured flowrate (3350-FIT-120 through 129,
130 through 139, 140 through 149, 160 through 169, 150 through 159) and adjust the position of
the dosing flow control valve (3350-FCV-120 through 129, 130 through 139, 140 through 149,
160 through 169, 150 through 159). No reagent may be added to the Hydrofloat if there is no
teeter water (3340-XV-040A is not open) or if its respective feed valve is closed (i.e. Crossflow
Underflow Valve 3340-XV-107). In such a case, the respective dosing isolation valve (3350-XV-
140 through 149) must close. No reagent may be added to the Crossflow Separator if there is no
teeter water (3340-XV-040A is not open) or if its respective feed valve is closed (3340-XV-036A
– E or 3340-XV-038A – E). In such a case, the respective collector dosing isolation valve must
close ((3350-XV-120 through 129, 130 through 139, 160 through 169, 150 through 159).
Two safety showers and eye wash stations are provided for at the reagent day tank area (3350 –
ES – 102) and bulk reagent storage area (3350 – ES – 101). The two showers are identical and
are vendor packages. All controls, alarms and interlocks specified in the vendor control philosophy
shall be followed.
2.8 Utilities (Process and Fluidization Water) (3340 – PLC – 101 A)

Three Fluidisation Water Tanks (3340 – TK – 102 / 103 / 104) are hydraulically connected in
parallel with each other and provide the storage capacity necessary for the CPF fluidisation, flush
and froth suppression water requirements. The tank levels are measured by individual level
transmitters (3340-LIT-643 / 648 & 649) respectively. Unless a tank is bypassed, they should
provide very similar readings. The tanks are filled with water via the CPF make-up water pumps
via an open/shut isolation valve (3340-XV-640A) and mechanical pressure sustaining valve
(3340-PCV-642). The make-up water valve will open on a Low level and close on a High Level.
Two variable speed Fluidisation Water Pumps (3340 – PU – 112 / 114) provide the fluidisation
water requirements for the Crossflow Separators and Hydrofloats via a common header pipe.
Each pump has sufficient capacity for six crossflow/hydrofloat modules. It is therefore very likely
that both pumps will always be required to run for the CPF to operate at full capacity. The
fluidisation water pressure is measured via pressure transmitter (3340-PIT-647) and controlled

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 37 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

by Proportional, Integral, Differential (PID) loop controller to achieve the required setpoint
pressure by varying the speeds of the pumps.
A variable speed Flush Water Pump (3340 – PU – 115) provides the CPF flush water
requirements. The flush water pressure is measured via pressure transmitter (3340-PIT-646) and
controlled by Proportional, Integral, Differential (PID) loop controller to achieve the required
setpoint pressure by varying the speed of the pump. The flush water pump provides hose down
water for the plant operations as well as hard-piped flush water to most slurry pump suctions and
other locations, including the tails launders. Flush water is introduced by opening the relevant
flush water valve before the pump or launder. To ensure the flush water pump capacity is not
exceeded while flushing multiple lines, not all flushing valves may be opened simultaneously.
Please refer to the relevant sections for flushing precedence and flushing time durations. Should
multiple valves require being opened simultaneously, the sequences with valves of lower
precedence shall hold until the priority sequences have completed.
A variable speed Froth Suppression and Dilution Water Pump (3340 – PU – 109) provides the
CPF deep cone settlers the water capacity for froth suppression as well as underflow density
control water addition. The water pressure is measured via pressure transmitter (3340-PIT-650)
and controlled by Proportional, Integral, Differential (PID) loop controller to achieve the required
setpoint pressure by varying the speed of the pump.
2.9 Utilities (Make-Up and Gland Seal Water) (3340 – PLC – 101 A)

CPF Process water is derived from the Papajuane concentrators Recovered Water Dam (3720-
TK -002) provided by others. Two CPF Make-Up Water Pumps 1 & 2 (3720 – PU – 007 & 008)
deliver water to the CPF at a controlled pressure measured by a pressure transmitter (3720-PIT-
116). Both pumps have variable speed drives, which will be adjusted via Proportional, Integral,
Differential (PID) loop controller to achieve the required setpoint pressure. For the CPF to operate
at full capacity, both pumps must run.
Clean gland seal water is gravity fed to the CPF via the Papajuane concentrators’ gland seal
water pipeline. Manual valves as well as an actuated valve (3340-XV-650) allows the gland seal
water to the CPF to be isolated if required. The feed pressure of the gland seal water offtake is
sufficient for most CPF applications and will be monitored via pressure transmitter (3340-PIT-
656). Should the pressure be Low, an alarm will be generated, and no pump start sequences will
be enabled. In the event of a Low Low pressure, feed to the CPF will be stopped and the pipelines
be allowed to purge themselves of solids to prevent chokes. Each individual slurry pump is
protected via a gland seal water flow switch which must be healthy for the pump to run (refer to
the relevant pump sections below). Some slurry pump duties within the CPF require a boosted
gland seal water pressure which is provided by the (running/standby) Gland Seal Water Booster
Pumps (3340 – PU – 192 / 193). The pumps suction and discharge are isolated by actuated
valves (3340-XV-654 / 655 A&B) which must be opened prior to the respective pump operating.
The boosted pressure of the gland seal water booster pump discharge will be monitored via
pressure transmitter (3340-PIT-659).

The CPF plant has two safety showers and eye wash stations located at the Reagent Day Tank
area and the Bulk Reagent Storage and Transfer area. These are independent of the CPF piped

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 38 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

water system and are manually filled periodically. The vendor functional specification for the
safety showers shall be utilized for their control and alarm monitoring.
2.10 Utilities (Compressed Air) (3340 – PLC – 101 A)

Compressed air for the CPF is supplied from three air compressors (3340-CP-101 / 102 / 103).
The compressors are stopped/started via vendor supplied controller which also controls their VFD
speeds to maintain the setpoint pressure of the instrument air (3340-PIT-675). Plant air pressure
(3340-PIT-672) and Front End instrument air (3340-PIT-677) are separately monitored and should
their readings differ significantly from that of the CPF instrument air, an alarm shall be generated.

The compressors discharge into a common pipe manifold which feeds the Plant Air Receiver
(3340 - AR – 101) that provides a buffer storage capacity for the CPF plant air requirements.
Water condensate which may accumulate at the base of the accumulator is periodically
discharged via a mechanical relief valve. The accumulator is also equipped with a safety pressure
relief valve to ensure the compressed air pressure does not exceed the line pressure rating of 10
bar.

Compressed air is then either directed to:

 The hydroflotation cells.

 CPF pneumatic air header. The pressure in this line is measured by a pressure
transmitter (3340-PIT-672) and should it drop a low level, an alarm shall be generated.

 Instrument air drier.

The instrument Air drier pre-filters (3340-FL-101 / 103) are in a running/standby configuration and
can be manually alternated by the filed operator. The desiccant air drier (3340 - DR – 101) reduces
the moisture content of the compressed air but can be manually bypassed under emergencies
during breakdown periods. Post-drier filters (3340-FL-102 / 104) remove final oil and dust
particles. They are in a running/standby configuration and can be manually alternated by the filed
operator.

Instrument Air is then piped into the Instrument Air Receiver (3340 - AR – 102) that provides a
buffer storage capacity for the CPF instrument air requirements. Water condensate which may
accumulate at the base of the accumulator is periodically discharged via a mechanical relief valve.
The accumulator is also equipped with a safety pressure relief valve to ensure the compressed
air pressure does not exceed the line pressure rating. Instrument air is then either directed to:

 The Front End Instrument Air Receiver (3340-AR-103). The pressure in this line is
measured by a pressure transmitter (3340-PIT-677).

 CPF instrument air header. The pressure in this line is measured by a pressure
transmitter (3340-PIT-675). No additional CPF plant equipment will be allowed to start

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 39 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

with a Low or Low Low air pressure alarm activated. At Low Low limits, certain equipment
(specified in later sections of this document) will stop within the process to allow the slurry
pipelines to purge themselves of solids and prevent plant choking. The pressure in the
instrument airline is controlled by varying the number and speed of the compressors.

2.11 Global Start / Stop Sequence

The following block diagram indicates the order of the CRP start up. This is a sequence to be
followed manually by the control room operator in starting up the CPF. The order of stopping the
CPF is directly opposite to that of the start sequence.

Set points and limits indicated in this Functional Specification document are indicative and should
be used to guide the reader to a better understanding of the plant. These will be confirmed on site
during commissioning.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 40 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Crossflow Agitator

Figure 3 CPF Global Start Sequence

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 41 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Notes:

1) The Crossflow Feed Surge Tank Agitator should never be stopped unless all solids have
been removed from the tank and/or the slurry level is below the minimum Low-Low
setpoint. Refer to the relevant section for more information.

2) The CPF can start without the Reagent Bulk Transfer system running provided there is
sufficient level in the respective reagent day tanks. Refer to the relevant section for more
information.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 42 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3.0 REFERENCES

The CPF Process Flow Diagrams are tabulated below in Table 1: Process Flowsheet Diagrams.

Process Flow Diagrams (PFD’s)


Area Number Drawing Number Drawing Title
0000 MQ14-08-DR-0000-FS1000 Overall Process Flow Diagram
3340 MQ14-08-DR-3340-FS1001 Coarse Particle Classification and Desliming
3340 MQ14-08-DR-3340-FS1002 Coarse Particle Separation and Flotation Line 1
3340 MQ14-08-DR-3340-FS1003 Coarse Particle Separation and Flotation Line 2
3340 MQ14-08-DR-3340-FS1004 Coarse Particle Regrinding
3340 MQ14-08-DR-3340-FS1005 Coarse Particle Flotation Utilities
3340 MQ14-08-DR-3340-FS1006 Concentrate and Tails Pumping
3340 MQ14-08-DR-3340-FS1007 Water Reticulation
3340 MQ14-08-DR-3340-FS1008 Deep Cone Settlers
3350 MQ14-08-DR-3350-FS1001 Coarse Particle Flotation Reagents 1
3350 MQ14-08-DR-3350-FS1002 Coarse Particle Flotation Reagents 2

Table 1: Process Flowsheet Diagrams

Controls and instruments described in this document can be found in the Piping and
Instrumentation Diagrams referred in Table 2: Reference Piping and Instrumentation Diagrams.

Piping and Instrumentation Diagrams (P&ID’s)


Associated Process Cell Coarse Particle Flotation (CPF) Plant

Drawing Number Drawing


MQ14 - 08 - DR - 0000 - PD1050 Equipment Symbology
MQ14 - 08 - DR - 0000 - PD1051 Equipment Symbology
MQ14 - 08 - DR - 0000 - PD1052 Index Page
MQ14 - 08 - DR - 3340 - PD1053 CPF Feed
MQ14 - 08 - DR - 3340 - PD1054 Deslime Cyclone Cluster 1
MQ14 - 08 - DR - 3340 - PD1055 Deslime Cyclone Cluster 2
MQ14 - 08 - DR - 3340 - PD1056 Crossflow Feed Tank
MQ14 - 08 - DR - 3340 - PD1057 Crossflow Distribution
MQ14 - 08 - DR - 3340 - PD1058 Crossflow Separator #1
MQ14 - 08 - DR - 3340 - PD1059 Crossflow Separator #2
MQ14 - 08 - DR - 3340 - PD1060 Crossflow Separator #3
MQ14 - 08 - DR - 3340 - PD1061 Crossflow Separator #4
MQ14 - 08 - DR - 3340 - PD1062 Crossflow Separator #5
MQ14 - 08 - DR - 3340 - PD1063 Crossflow Separator #6
MQ14 - 08 - DR - 3340 - PD1064 Crossflow Separator #7

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 43 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

MQ14 - 08 - DR - 3340 - PD1065 Crossflow Separator #8


MQ14 - 08 - DR - 3340 - PD1066 Crossflow Separator #9
MQ14 - 08 - DR - 3340 - PD1067 Crossflow Separator #10
MQ14 - 08 - DR - 3340 - PD1068 Hydrofloat #1
MQ14 - 08 - DR - 3340 - PD1069 Hydrofloat #2
MQ14 - 08 - DR - 3340 - PD1070 Hydrofloat #3
MQ14 - 08 - DR - 3340 - PD1071 Hydrofloat #4
MQ14 - 08 - DR - 3340 - PD1072 Hydrofloat #5
MQ14 - 08 - DR - 3340 - PD1073 Hydrofloat #6
MQ14 - 08 - DR - 3340 - PD1074 Hydrofloat #7
MQ14 - 08 - DR - 3340 - PD1075 Hydrofloat #8
MQ14 - 08 - DR - 3340 - PD1076 Hydrofloat #9
MQ14 - 08 - DR - 3340 - PD1077 Hydrofloat #10
MQ14 - 08 - DR - 3340 - PD1078 Thickener Feed Box
MQ14 - 08 - DR - 3340 - PD1079 Thickener Rakes and Hydraulics (Vendor)
MQ14 - 08 - DR - 3340 - PD1080 Thickener Underflow
MQ14 - 08 - DR - 3340 - PD1081 Regrind Hydrocyclone Cluster
MQ14 - 08 - DR - 3340 - PD1082 Vertical Regrind Mill 1 (Vendor)
MQ14 - 08 - DR - 3340 - PD1083 Vertical Regrind Mill 2 (Vendor)
MQ14 - 08 - DR - 3340 - PD1084 Regrind Cyclone Pumping
MQ14 - 08 - DR - 3340 - PD1085 Regrind Cyclone Pumps (Vendor)
MQ14 - 08 - DR - 3340 - PD1086 Product Pumping - First Stage
MQ14 - 08 - DR - 3340 - PD1087 Tails Launder
MQ14 - 08 - DR - 3340 - PD1088 Fluidization and Flush Water Pumps
MQ14 - 08 - DR - 3340 - PD1089 Process Water Pumping
MQ14 - 08 - DR - 3340 - PD1090 Gland Seal Water
MQ14 - 08 - DR - 3340 - PD1091 Reagent Collector 3894
MQ14 - 08 - DR - 3340 - PD1092 Reagent Collector 404
MQ14 - 08 - DR - 3340 - PD1093 Reagent Collector Z6
MQ14 - 08 - DR - 3340 - PD1094 Reagent Collector Diesel
MQ14 - 08 - DR - 3340 - PD1095 Reagent Polypropylene
MQ14 - 08 - DR - 3340 - PD1096 Compressed Air Generation
MQ14 - 08 - DR - 3340 - PD1097 Instrument Air Reticulation
MQ14 - 08 - DR - 3340 - PD1098 Plant Air Reticulation
MQ14 - 08 - DR - 3340 - PD1099 Deslime Cyclone Feed Pumps (Vendor)
MQ14 - 08 - DR - 3340 - PD1100 Crossflow Feed Pumps (Vendor)
MQ14 - 08 - DR - 3340 - PD1101 Hydrofloat Rejects Launders
MQ14 - 08 - DR - 3340 - PD1102 Product Pumping - Second Stage

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 44 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

MQ14 - 08 - DR - 3340 - PD1103 Hydraulic Valve Power Pack


MQ14 - 08 - DR - 3340 - PD1104 Froth Suppression and Flush Water Pumps
MQ14 - 08 - DR - 3340 - PD1105 Flocculant Dosing
MQ14 - 08 - DR - 3340 - PD1106 Hose Down Water Reticulation
MQ14 - 08 - DR - 3340 - PD1107 Reagent Day Tank - Collector 3894
MQ14 - 08 - DR - 3340 - PD1108 Reagent Day Tank - Collector 404
MQ14 - 08 - DR - 3340 - PD1109 Reagent Day Tank - Collector Z6
MQ14 - 08 - DR - 3340 - PD1110 Reagent Day Tank - Collector Diesel
MQ14 - 08 - DR - 3340 - PD1111 Reagent Day Tank - Polypropylene

Table 2: Reference Piping and Instrumentation Diagrams

The following general references to the CPF design should be referred to in reading this
document.

General Project Documents


Drawing Number Drawing Title
MQ14-08-ES-3340-FS0001 Coarse Particle Flotation Process Description
MQ14-08-3340-EL-ME0001 Mechanical Equipment List
MQ14-08-3340-LIT--IN0001 Instrument List

Table 3: General Process Project Documents

Documents referenced in this document are tabulated below in

Table 4: Reference Documents.

Vendor and Client Specification Documents


Drawing Number Drawing
AGS067 Software Design Specification
AGS068 Controller Configuration Specification
AGS069 Control Template Specification
MQ15-760-DR-3340-ME0002 Vendor compressor PID
MQ15-760-DR-3340-ME0004 Vendor drier PID
MQ15-760-TE-3340-IN0001 Vendor Profibus Communication Map to Compressors
MQ15-760-TE-3340-IN0002 Vendor Profibus Communication Map to Drier
MQ15-715-DC-3340-IN0101 Vendor Water Pump Control Philosophy
MQ15-51-DR-3340-EE0011 Vendor Regrind Mill Functional Specification
MQ15-718-TE-3340-IN0001 Vendor Regrind Cyclone Control Philosophy

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 45 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

MQ15-51-TE-3340-GA0601 Vendor Thickener Control Philosophy


MQ15-727-TE-3340-IN1001 Vendor Hydrofloat Control Philosophy
MQ15-727-TE-3340-IN1002 Vendor Crossflow Separator Control Philosophy
MQ15-718-TE-3340-IN0101 Vendor Weir Large Slurry Pump Control Philosophy
MQ15-722-DC-3340-IN0001 Vendor Agitator Control Philosophy
MQ15-700-OM-3340-IN0001 Vendor Deslime Cyclone Control Philosophy
MQ15-720-IOM-3340-ME0002 Vendor Sampler and Analyzer Control Philosophy
MQ15-775-DR-3340-IN0001-HSS Vendor Safety Shower P&ID
MQ15-775-IOM-3340-ME0001 Vendor Safety Shower Operating Manual
MQ15-780-PRC-3340-GA0001 Vendor Reagent Bulk Storage Control Philosophy
MQ15-781-DC-3340-IN0001 Vendor Reagent Dosing Control Philosophy

Table 4: Reference Documents

Terminology

Abbreviation Description
“!“ Not (negation)
AH High Alarm
AHH High-High Alarm
AL Low Alarm
ALL Low Low Alarm
3
m Cubic meter
APC Advance Process Control
CL Closed
CLN Closing
CM Control Module (ISA 88 or PCS7 CMT Tec I/O Group
CMT Typical module of control
CV Control Variable
Cmd Command
Debounce Time that an interlocking condition must be maintained to de-energize a
device (2 to 3 seconds)
Debounce Extendido Time that an interlocking condition must be maintained to de-energize a
device (5 to 10 seconds)
EM Equipment Module
Functional group of teams that carry out a finite number of minor
processing.
EPH Equipment Phase
Fail Equipment in Fail
FB Function Block

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 46 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

FC Function (PLC)
FC Function (PAA/COMOS)
FC Fail Close
FL Fail Last Position
FLT Fault
FO Fail Open
HMI Human Machine Interface
IL Interlock
INTERLOCK (Enclavamiento) It corresponds to an interlocking that will de-energize the equipment. The
interlocking will be released after the interlocking condition has been
exceeded, not requiring the condition to be reset. The computer remains
de-energized until a new command is given.
This kind of interlocking is used to protect the process from abnormal
conditions or actions; this is often triggered by process conditions that
were rectified as part of the plant's starting process or the normal
operation of a piece of equipment.
An example of this type of interlocking corresponds to the stopping of a
conveyor downstream, which stops the conveyor belt located upstream.

Interlock Primario Interlocks that relate to conditions that require the intervention of the
Operator before a normal operation can proceed. Primary interlocks often
refer to interlocks associated with the same equipment, and not to
interlocks associated with equipment located downstream. TYPE
PROTECT interlocks are always Primary interlocks.
Interlock Secundario Interlocks that do not require the intervention of the Operator before a
normal operation can proceed. Active Sequencing Interlocks will prevent a
piece of equipment from being energized, but even so, the equipment is
considered ready to receive commands from higher levels of control.
KL Keep Last
Maintains the last active position of the valve in case of loss of position
limit.
M (Maintenance Bypass) It corresponds to the action of "By Passer" an interlock at the request of
the maintenance start.
This type of By Pass expires automatically after the device has been
energized for a certain time with the By Pass of the active interlock. The
default time is 60 sec, but it can be activated for a longer time once
deactivated from the PCS Engineering Station. This type of By Pass can
be only activated by the maintenance staff with the due rights.

MV Manipulated Variable
OP Open
OPN Opening
P (Process Bypass) It corresponds to the action of "By Passer" an interlock at the request of
the process personnel of the plant.
This type of By Pass does not expire automatically, and can be activated
while the computer is energized.
This type of By Pass can be only activated by the process personnel with
the due rights.
PCS Process Control System (Siemens PCS7)
PERMIT (Permisivo) It corresponds to a condition that will prevent the energizing of the
equipment while it is stopped. This type of condition prevents a computer
from being energized, but has no effect on it once the command
(Start/Open, etc.) has been executed, that is, while the computer is
energized.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 47 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

In the Interlock tables, it corresponds to the condition that of being present,


or allows to depart.
PID Proportional Integral Derivative Controller
PLC Programmable Logic Controller
Process Cell Process Cell.
Logical grouping of equipment that includes teams working together to
produce one or more lots" of process.
PROTECT (Enclavamiento) It corresponds to an interlocking that will de-energize the equipment. This
type of interlocking will not be released after the interlocking condition has
been overcome. The release of this will be possible once the condition
has been overcome and the condition recognized (reset). Once the
condition is overcome and recognized, the equipment remains
deenergized until a new boot command is given.
This type of interlocking is used to protect the safety of people and
equipment (e.g. high temperature breaks, safety interlocks, etc.). This type
of interlocking, by default, cannot be enabled to be Bypassed
PV Process Value
P&ID Piping and Instrumentation Diagram
P/H Plant Hierarchy
RDY Ready
RUN Equipment Running
SEM Sub Equipment. Equipment or module dependent upon a higher module
SEQRDY Equipment Ready to Start in Sequence.
It is defined as a module that is available and ready for a higher control
layer to start it. This implies that the module is available, in Auto, and that
there are no primary interlocks active.
ReadyToStart Equipment Ready to Start in Sequence
It is defined as a module that is available and ready for operation
according to the program.
This implies that the module is available and in Auto, and that there are no
active interlocks.
SP Set Point
Unit Unit
Collection of modules of Equipment/modules of Control that together carry
out one or more major processing activities.
WATCHDOG Symmetrical pulse train of constant period (E.g.: 3 seconds with state "1"
logic, and 3 seconds with state "O" logic), sent by PCS to external
equipment with which you have communications link (transfer of
information).
PCS monitors return of pulse train vfa communications link, declaring
communications failure (Watchdog alarm), in case it is detected that pulse
does not vary for a period of time.

Table 5: Terminology

Equipment Abbreviations
Abbreviation Description
BH Bag House
CH Chute

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 48 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

CY Cyclone
CV Conveyor
FA Fan
FE Feeder
GSW Gland Seal Water
HE Heater
HY Hydraulic Unit
LV Low Voltage (0.48KV)
MO Motor
MV Medium Voltage (4.16 kV)
PU Pump
RV Rotary Valve
SPW Spray Water
TK Tank
VFD Variable Frequency Driver
XM Cooling Unit

Table 6: Equipment Abbreviations

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 49 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

4.0 DESCRIPTION OF CONTROL

1.1 Objectives of Control

The control objectives considered for this area correspond to maximizing the Cu concentrate recovery from
primary rougher copper tailings to maximize total concentrator metal recoveries. This will be achieved by:

- Maintaining a controlled flowrate and pressure to the deslime cyclone clusters

- Maintain a consistent controlled flowrate to the crossflow separators and a controlled fluidization
water injection to maximize the removal of ultrafines (-75µm) material while not displacing to tailings
coarse material containing recoverable grades

- Maintaining a controlled feed rate, fluidization water, compressed air and reagent addition to the
crossflow separators and hydrofloats in order to maximize coarse particle flotation efficiency

- Maintaining a controlled feed rate and concentrate regrind size of recovered concentrate material
prior to returning it at a controlled solids concentration back to the concentrators Cu rougher
flotation circuit.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 50 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

5.0 STRUCTURE OF PLC SOFTWARE

Three PLC’s are to be used for the control of the CPF plant The following colored process flow diagrams
provide a visual indication of the selected PLC delineation for the CPF plant.

Figure 4: PLC Selection – Deslime and Crossflow Feed

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 51 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 5: PLC Selection – Crossflow & Hydrofloat Separators B

Figure 6: PLC Selection – Crossflow & Hydrofloat Separators C

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 52 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 7: PLC Selection – Concentrate Thickening

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 53 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 8: PLC Selection – Regrind Milling

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 54 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 9: PLC Selection – Concentrate Return and Tails Sampling

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 55 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 10: PLC Selection – Water Reticulation

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 56 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 11: PLC Selection – Frother Bulk Storage and Dosing

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 57 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 12: PLC Selection – Collector Dosing

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 58 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 13: PLC Selection – Compressed Air

The structural hierarchy of the functional specification is tabulated below.

Unit EM1 EM2 DRA DRA DRA

Módulo de Módulo de
Unidad Código Descripción P&ID No
Equipo 1 Equipo 2
CDCPF_Deslamado 3340BX101 3340-BX-101 CPF Plant Feed Box MQ14-08-DR-3340-PD1053
CDCPF_Deslamado 3340BX101 3340PU101 3340-PU-101 Deslime Feed Pump 1 MQ14-08-DR-3340-PD1053
CDCPF_Deslamado 3340BX101 3340PU102 3340-PU-102 Deslime Feed Pump 2 MQ14-08-DR-3340-PD1053
CDCPF_Deslamado 3340BX101 3340PU174 3340-PU-174 Feed Area Sump Pump MQ14-08-DR-3340-PD1053
CDCPF_Deslamado 3340Clasif001 3340CY101 3340-CY-101 Deslime Cyclone Cluster 1 MQ14-08-DR-3340-PD1054
CDCPF_Deslamado 3340Clasif001 3340CY102 3340-CY-102 Deslime Cyclone Cluster 2 MQ14-08-DR-3340-PD1055
SFCPF_AlimFlujoCruzado 1 3340-TK-101 Crossflow Feed Surge Tank MQ14-08-DR-3340-PD1056
Crossflow Feed Surge Tank
SFCPF_AlimFlujoCruzado 1 3340-AG-101 Agitator MQ14-08-DR-3340-PD1056
SFCPF_AlimFlujoCruzado 3340DB103 3340-DB-103 Crossflow Distributor 1 MQ14-08-DR-3340-PD1056
SFCPF_AlimFlujoCruzado 3340DB104 3340-DB-104 Crossflow Distributor 2 MQ14-08-DR-3340-PD1100
SFCPF_AlimFlujoCruzado 3340PU185 3340-PU-185 Crossflow Feed Pump 1 MQ14-08-DR-3340-PD1100
SFCPF_AlimFlujoCruzado 3340PU186 3340-PU-186 Crossflow Feed Pump 2 MQ14-08-DR-3340-PD1100
SFCPF_AlimFlujoCruzado 3340PU198 3340-PU-198 Deslime Cyclone Spillage Pump MQ14-08-DR-3340-PD1057
SFCPF_SepHFL1 3340SepHFL101 3340CF101 3340-CF-101 Crossflow Separator 1 MQ14-08-DR-3340-PD1058
SFCPF_SepHFL1 3340SepHFL102 3340CF102 3340-CF-102 Crossflow Separator 2 MQ14-08-DR-3340-PD1059
SFCPF_SepHFL1 3340SepHFL103 3340CF103 3340-CF-103 Crossflow Separator 3 MQ14-08-DR-3340-PD1060
SFCPF_SepHFL1 3340SepHFL104 3340CF104 3340-CF-104 Crossflow Separator 4 MQ14-08-DR-3340-PD1061
SFCPF_SepHFL1 3340SepHFL105 3340CF105 3340-CF-105 Crossflow Separator 5 MQ14-08-DR-3340-PD1062
SFCPF_SepHFL2 3340SepHFL106 3340CF106 3340-CF-106 Crossflow Separator 6 MQ14-08-DR-3340-PD1063
SFCPF_SepHFL2 3340SepHFL107 3340CF107 3340-CF-107 Crossflow Separator 7 MQ14-08-DR-3340-PD1064
SFCPF_SepHFL2 3340SepHFL108 3340CF108 3340-CF-108 Crossflow Separator 8 MQ14-08-DR-3340-PD1065
SFCPF_SepHFL2 3340SepHFL109 3340CF109 3340-CF-109 Crossflow Separator 9 MQ14-08-DR-3340-PD1066
SFCPF_SepHFL2 3340SepHFL110 3340CF110 3340-CF-110 Crossflow Separator 10 MQ14-08-DR-3340-PD1067
SFCPF_SepHFL1 3340SepHFL101 3340HF101 3340-HF-101 Hydrofloat 1 MQ14-08-DR-3340-PD1068
SFCPF_SepHFL1 3340SepHFL102 3340HF102 3340-HF-102 Hydrofloat 2 MQ14-08-DR-3340-PD1069
SFCPF_SepHFL1 3340SepHFL103 3340HF103 3340-HF-103 Hydrofloat 3 MQ14-08-DR-3340-PD1070
SFCPF_SepHFL1 3340SepHFL104 3340HF104 3340-HF-104 Hydrofloat 4 MQ14-08-DR-3340-PD1071
SFCPF_SepHFL1 3340SepHFL105 3340HF105 3340-HF-105 Hydrofloat 5 MQ14-08-DR-3340-PD1072
SFCPF_SepHFL2 3340SepHFL106 3340HF106 3340-HF-106 Hydrofloat 6 MQ14-08-DR-3340-PD1073
SFCPF_SepHFL2 3340SepHFL107 3340HF107 3340-HF-107 Hydrofloat 7 MQ14-08-DR-3340-PD1074
SFCPF_SepHFL2 3340SepHFL108 3340HF108 3340-HF-108 Hydrofloat 8 MQ14-08-DR-3340-PD1075
SFCPF_SepHFL2 3340SepHFL109 3340HF109 3340-HF-109 Hydrofloat 9 MQ14-08-DR-3340-PD1076
SFCPF_SepHFL2 3340SepHFL110 3340HF110 3340-HF-110 Hydrofloat 10 MQ14-08-DR-3340-PD1077
ECPF_Alimentacion 3340BX109 3340-BX-109 Concentrate Thickener Feed Box MQ14-08-DR-3340-PD1078
ECPF_Alimentacion 3340PU171 3340-PU-171 Thickening Area Sump Pump MQ14-08-DR-3340-PD1078
ECPF_3340TH101 3340TH101UF 3340-PU-104 Thickener Underflow Pump 1 MQ14-08-DR-3340-PD1079
ECPF_3340TH102 3340TH102UF 3340-PU-105 Thickener Underflow Pump 2 MQ14-08-DR-3340-PD1079
ECPF_3340TH103 3340-TH-103 Deep Cone Settler 3 (Standby) MQ14-08-DR-3340-PD1079
ECPF_3340TH101 3340-TH-101 Deep Cone Settler 1 MQ14-08-DR-3340-PD1080
ECPF_3340TH102 3340-TH-102 Deep Cone Settler 2 MQ14-08-DR-3340-PD1080

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 59 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Thickener Underflow Pump 3


ECPF_3340TH103 3340TH103UF 3340-PU-108 (Standby) MQ14-08-DR-3340-PD1080
Regrind Mill Hydro Cyclone
RMCPF_3340BX103 3340CY110 3340-CY-110 Cluster MQ14-08-DR-3340-PD1081
Regrind
RMCPF_3340BX103 3340PU106_107 3340PU106 3340-PU-106 Hydrocyclone Feed Pump 1 MQ14-08-DR-3340-PD1086
RMCPF_Alimentacion 3340-DB-105 Underflow Distributor MQ14-08-DR-3340-PD1081
RMCPF_Alimentacion 3340-HT-101 Ball Loading Hoist MQ14-08-DR-3340-PD1081
RMCPF_Alimentacion 3340-ZA-101 Ball Loading Hopper MQ14-08-DR-3340-PD1081
MQ14-08-DR-3340-PD1082
RMCPF_3340MI101 3340MI101 3340-MI-101 REGRIND MILL No.1 MQ14-08-DR-3340-PD1081
MQ14-08-DR-3340-PD1083
RMCPF_3340MI102 3340MI102 3340-MI-102 REGRIND MILL No.2 MQ14-08-DR-3340-PD1081
Regrind
RMCPF_3340BX103 3340PU106_107 3340PU107 3340-PU-107 Hydrocyclone Feed Pump 2 MQ14-08-DR-3340-PD1085
RMCPF_3340BX103 3340PU173 3340-PU-173 Regrind Area Sump Pump MQ14-08-DR-3340-PD1085
Fluidisation Water Spillage
RMCPF_3340BX103 3340PU175 3340-PU-175 Pump MQ14-08-DR-3340-PD1085
RMCPF_3340BX103 3340-SA-101 Primary Product Sampler MQ14-08-DR-3340-PD1084
RMCPF_3340BX103 3340-AY-101 Primary Product Analyser MQ14-08-DR-3340-PD1084
RMCPF_3340BX103 3340-BX-103 Regrind Cyclone Feed Box MQ14-08-DR-3340-PD1084
CRCFP_RetornoConc 3340PU110_191 3340PU110 3340-PU-110 Concentrate Return Pump 1 MQ14-08-DR-3340-PD1086
CRCFP_RetornoConc 3340PU110_191 3340PU111 3340-PU-111 Concentrate Return Pump 2 MQ14-08-DR-3340-PD1086
Concentrate return Pump 3
CRCFP_RetornoConc 3340PU110_191 3340PU190 3340-PU-190 (Standby) MQ14-08-DR-3340-PD1102
CRCFP_RetornoConc 3340PU110_191 3340PU191 3340-PU-191 Concentrate Return Pump 4 MQ14-08-DR-3340-PD1102
Concentrate Return Collection B
CRCFP_RetornoConc 3340-BX-106 ox MQ14-08-DR-3340-PD1102
CRCFP_Relaves 3340-BX-135 Tails Return Pump Box MQ14-08-DR-3340-PD1087
CRCFP_Relaves 3340-SA-103 Tails Sampler and Analyser MQ14-08-DR-3340-PD1087
CRCFP_Relaves 3340PU197 3340-PU-197 Tails Return Pump 1 MQ14-08-DR-3340-PD1087
CRCFP_Relaves 3340PU170 3340-PU-170 CPF Sump Pump MQ14-08-DR-3340-PD1101
CRCFP_Relaves 3340-LN-106 Hydrofloat Rejects Launder 1 MQ14-08-DR-3340-PD1101
CRCFP_Relaves 3340-LN-107 Hydrofloat Rejects Launder 2 MQ14-08-DR-3340-PD1101
CRCFP_Relaves 3340-LN-108 Hydrofloat Rejects Launder 3 MQ14-08-DR-3340-PD1101
SCPF_InstAir 3340CP101_103 3340-CP-101 Air Compressor 1 MQ14-08-DR-3340-PD1096
SCPF_InstAir 3340CP101_103 3340-CP-102 Air Compressor 2 (Standby) MQ14-08-DR-3340-PD1096
SCPF_InstAir 3340CP101_103 3340-CP-103 Air Compressor 3 MQ14-08-DR-3340-PD1096
SCPF_InstAir 3340AR101 3340-AR-101 Plant Air Receiver MQ14-08-DR-3340-PD1096
SCPF_InstAir 3340AR102 3340-AR-102 Instrument Air Receiver MQ14-08-DR-3340-PD1096
Instrument Air Receiver (Feed
SCPF_InstAir 3340AR103 3340-AR-103 Area) MQ14-08-DR-3340-PD1096
3340-HT-102 CPF Maintenance Elevator MQ14-08-DR-3340-PD1096
Collector AP-3894 Transfer
RECPF_Colector3894 3520PU179 3520-PU-179 Pump MQ14-08-DR-3350-PD1091
RECPF_Colector404 3520PU182 3520-PU-182 Collector AP404 Transfer Pump MQ14-08-DR-3350-PD1092
Xanthate Z6 (SIPX) Transfer
RECPF_ColectorZ6 3520PU181 3520-PU-181 Pump MQ14-08-DR-3350-PD1093
RECPF_Diesel 3520PU180 3520-PU-180 Diesel Transfer Pump MQ14-08-DR-3350-PD1094
Polypropylene Glycol Frother
RECPF_AlmEspumante 3350PU176_177 3350-PU-176 Pump 1 MQ14-08-DR-3350-PD1095
Polypropylene Glycol Frother
RECPF_AlmEspumante 3350PU176_177 3350-PU-177 Pump 2 MQ14-08-DR-3350-PD1095
Polypropylene Glycol Frother
RECPF_AlmEspumante 3350PU178 3350-PU-178 Supply Pump MQ14-08-DR-3350-PD1095
RECPF_AlmEspumante 3350PU199 3350-PU-199 Bulk Reagent Spillage Pump MQ14-08-DR-3350-PD1095

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 60 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

RECPF_Colector3894 3350-TK-104 Collector AP-3894 Day Tank MQ14-08-DR-3350-PD1091


RECPF_Colector404 3350-TK-103 Collector AP404 Day Tank MQ14-08-DR-3350-PD1108
RECPF_ColectorZ6 3350-TK-108 Collector Z6 (SIPX) Day Tank MQ14-08-DR-3350-PD1109
RECPF_Diesel 3350-TK-105 Collector Diesel Day Tank MQ14-08-DR-3350-PD1110
3350-LSH- NIVEL ALTO EN TANQUE DIARIO
RECPF_Diesel 216B DE DIESEL MQ14-08-DR-3350-PD1110
RECPF_Espumante 3350-TK-106 Polypropylene Glycol Day Tank MQ14-08-DR-3350-PD1095
Polypropylene Glycol Frother
RECPF_AlmEspumante 3350-TK-110 Tank MQ14-08-DR-3350-PD1095
RECPF_Colector3894 3350PU120_121 3350PU120 3350-PU-120 AP-3894 Dosing Pump 1 MQ14-08-DR-3350-PD1107
RECPF_Colector404 3350PU160_161 3350PU160 3350-PU-160 AP-404 Dosing Pump 1 MQ14-08-DR-3350-PD1092
Xanthate Z6 (SIPX) Dosing Pump
RECPF_ColectorZ6 3350PU150_151 3350PU150 3350-PU-150 1 MQ14-08-DR-3350-PD1109
RECPF_Diesel 3350PU130_131 3350PU130 3350-PU-130 Diesel Dosing Pump 1 MQ14-08-DR-3350-PD1110
RECPF_Espumante 3350PU140_141 3350PU140 3350-PU-140 Polypropylene Dosing Pump 1 MQ14-08-DR-3350-PD1111
AP-3894 Dosing Pump 2
RECPF_Colector3894 3350PU120_121 3350PU121 3520-PU-121 (Standby) MQ14-08-DR-3350-PD1107
AP-404 Dosing Pump 2
RECPF_Colector404 3350PU160_161 3350PU161 3350-PU-161 (Standby) MQ14-08-DR-3350-PD1108
Xanthate Z6 (SIPX) Dosing Pump
RECPF_ColectorZ6 3350PU150_151 3350PU151 3350-PU-151 2 MQ14-08-DR-3350-PD1109
RECPF_Diesel 3350PU130_131 3350PU131 3350-PU-131 Diesel Dosing Pump 2 (Standby) MQ14-08-DR-3350-PD1110
Polypropylene Dosing Pump 2
RECPF_Espumante 3350PU140_141 3350PU141 3350-PU-141 (Standby) MQ14-08-DR-3350-PD1111
Reagent Bulk Offloading Safety
RECPF_Espumante 3350-ES-101 Shower and Eye Wash Station MQ14-08-DR-3340-PD1090
Reagent Day Tank Safety
RECPF_ColectorZ6 3350-ES-102 Shower And Eye Wash Station MQ14-08-DR-3340-PD1090
SCPF_AguaProcesos 3340-TK-102 Fluidization Water Tank 2 MQ14-08-DR-3340-PD1088
SCPF_AguaProcesos 3340-TK-103 Fluidization Water Tank 3 MQ14-08-DR-3340-PD1088
SCPF_AguaProcesos 3340-TK-104 Fluidization Water Tank 1 MQ14-08-DR-3340-PD1088
SCPF_AguaProcesos 3340PU112 3340-PU-112 Fluidization Water Pump 1 MQ14-08-DR-3340-PD1088
SCPF_AguaProcesos 3340PU114 3340-PU-114 Fluidization Water Pump 2 MQ14-08-DR-3340-PD1088
SCPF_AguaProcesos 3340PU115 3340-PU-115 Flush Water Pump MQ14-08-DR-3340-PD1104
Froth Suppression and Dilution
SCPF_AguaProcesos 3340PU109 3340-PU-109 Water Pump MQ14-08-DR-3340-PD1104
SCPF_AguaProcesos 3720PU007 3720-PU-007 Make-up Water Pump 1 MQ14-08-DR-3340-PD1089
SCPF_AguaProcesos 3720PU008 3720-PU-008 Make-up Water Pump 2 MQ14-08-DR-3340-PD1089
SCPF_AguaSello 3340PU192 3340-PU-192 Gland Seal Water Pump 1 MQ14-08-DR-3340-PD1090
Gland Seal Water Pump 2
SCPF_AguaSello 3340PU193 3340-PU-193 (Standby) MQ14-08-DR-3340-PD1090
FCPF_Alimentacion 3520PU195 3520-PU-195 Flocculant Dosing Pump 1 MQ14-08-DR-3340-PD1105
FCPF_Alimentacion 3520PU196 3520-PU-196 Flocculant Dosing Pump 2 MQ14-08-DR-3340-PD1105
3340-MX-
FCPF_Alimentacion 3340MX001 001 Flocculant Static Mixer 1 MQ14-08-DR-3340-PD1105
3340-MX-
FCPF_Alimentacion 3340MX002 002 Flocculant Static Mixer 2 MQ14-08-DR-3340-PD1105
3340-MX-
FCPF_Alimentacion 3340MX003 003 Flocculant Static Mixer 3 MQ14-08-DR-3340-PD1105

Table 7: CPF Structural Hierarchy Summary

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 61 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

6.0 UNIDAD: CDCPF_DESLAMADO

Refer to:
MQ14 - 08 - DR - 3340 - PD1053 CPF Feed
MQ14 - 08 - DR - 3340 - PD1054 Deslime Cyclone Cluster 1
MQ14 - 08 - DR - 3340 - PD1055 Deslime Cyclone Cluster 2
MQ14 - 08 - DR - 3340 - PD1099 Deslime Cyclone Feed Pumps
MQ14 - 08 - DR - 3340 - PD1103 Hydraulic Valves
MQ15-718-TE-3340-IN0101 Vendor Weir Large Slurry Pump Control Philosophy

A block flow control diagram is depicted below for the CDCPF_Deslamado system.
Flush Water

Rougher Tails 3340-XV-YYY Tails Launder


Launder (Fluor)

Flopper Gates
3340BX101 3340-XV-XXX
3340-XV-003B 3340-XV-002B
LC
3340001

Emergency Tails
Launder
LT

3340-XV-013
PC
3340-BX-101 SC
FI DI 3340014
3340002
3340008 3340009
Vendor Tails Launder
Package PT
3340-XV-002A M
3340-XV-001A FT DT
Vendor Package
3340-XV-015
A - AD
3340-PU-101
3340-CY-101
3340-XV-001C 3340-XV-002C Vendor
Package 3340-XV-002D FC
3340001

3340-XV-016
PC
SC
FI DI
3340005

3340017
3340003
FAL

FSL

3340010 3340011
Vendor Tails Box
Package
3340-XV-003A M
PT
FT DT
Vendor Package
3340-XV-017
3340-XV-005 A - AD
3340-PU-102
3340-XV-003C
FAL Vendor 3340-CY-102
3340-XV-006 3340006 Package 3340-XV-003D
Crossflow Surge
Tank
FSL

GSW
3340Clasif001

Figure 14: Blockflow Control Diagram of the CDCPF_Deslamado System

The above control unit is broken into two engineering modules and sub-modules:
- 3340BX101 where the feed slurry is received and pumped

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 62 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

o 3340XM100 Hydraulic Valve Power Pack


o 3340PU101 Deslime Pump 1
o 3340PU102 Deslime Pump 2
o 3340PU174 Feed Area Sump Pump
- 3340Clasif001 where the pumped slurry is deslimed in two deslime cyclone clusters
o 3340CY101 Deslime Cluster 1
o 3340CY102 Deslime Cluster 2

6.1 Sub Module 3340BX101

6.1.1 Modules of Control

There are no modules of control within the DRA scope for 3340BX101 which do not reside within
sub-engineering modules.
However, the flopper diversion gates supplied by others require certain controls for the CPF to
operate.

T1 Control Module
UN CDCPF_Deslamado EM 3340BX101 Sub EM

Tag Service
3340-XV-XXX CPF Feed Flopper Gate (others)
3340-XV-YYY Tails Launder Flopper Gate (others)
3340-LIT-001 CPF Plant Feed Box Level Transmitter

Table 8: List of Modules of Control for 3340BX101

6.1.2 List of Interlocks.

T2 Interlock
Tag 3340-XV-XXX Description CPF Feed Flopper Gate (others)
Sub
UN CDCPF_Deslamado EM 3340BX101
EM
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340 – PU – 101 If both Deslime Cyclone Feed Pumps


Delay time
3340 – PU – 102 3340 – PU – 101 × P
10s
Not running. AND

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 63 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340 – PU – 102

Have not run in for a time delay, then


close flopper gate
Refer to vendor and design functional specifications by others

Table 9: List of Interlocks for CPF Flopper Gate

T2 Interlock
Tag 3340-XV-YYY Description Tails Launder Flopper Gate (others)
Sub
UN CDCPF_Deslamado EM 3340BX101
EM
Interlock
Motor Type Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-XXX If CPF Feed Flopper Gate open then close Delay time
× P
Is open flopper gate 10s
3340-XV-XXX If CPF Feed Flopper Gate not open or Delay time
×
Is not open or closed closed, then open flopper gate 120s
Refer to vendor and design functional specifications by others

Table 10: List of Interlocks for Tails Launder Flopper Gate

Both flopper gates are not allowed to be open together.


One of the flopper gates must be open at all times to prevent spillage overflows.

6.1.3 Alarms and Process Setpoints – 3340BX101

T3 Alarms and Process Setpoints


UN CDCPF_Deslamado EM 3340BX101 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-LIT-001 CPF Plant Feed Box Level


0 - 100 % 95 30 5
Transmitter

Table 11: Alarms and Process Setpoint 3340-BX-101

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 64 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

6.1.4 Binary State Messages – 3340BX101

There are no binary state messages for this section 3340BX101


6.1.5 Regulatory Control Loops – 3340BX101

There are no regulatory control loops for this section 3340BX101


6.1.6 Advanced Control Loops – 3340BX101

There are no advanced control loops for this section 3340BX101

6.1.7 Description - CPF Plant Feed Box, Launders and Flopper Diversion

The CPF feed is derived from the Papajuane Concentrators’ rougher tailings slurry. The slurry is
gravitated down a concrete launder and discharged into Tailings Collection Box (3710 – BX –
003).
The rougher tailings slurry is diverted by means of actuated flopper gate swingover system,
supplied by others. Should the CPF be available to receive feed slurry, the flopper gates will be
opened, and slurry allowed to gravitate down the CPF Plant Feed Launder (3340 – LN – 103). On
discharge from the concrete feed launder, the slurry velocity is attenuated and distributed by the
Plant Feed Break Box (3340 – BX – 100) into the Plant Feed Box (3340 – BX – 101).
The flopper gates must immediately divert slurry away from the CPF Plant Feed Box if both
Deslime Cyclone Pumps (3340 – PU – 101 / 102) are not running. This will prevent solids from
accumulating at the base of the pump box which may block the pumps on re-start.
Due to the large slurry volumes expected within the design, the Plant Feed Box may overflow for
a limited time while the flopper gates are closing. Slurry will overflow the pump box into the
Emergency Overflow Launder (3340 – LN – 104) and gravitate to the Tailings Collection Box
(3710 – BX – 003) supplied by others.
The level in the Plant Feed Box is measured by level transmitter (3340-LIT-001) and controlled
by varying the speed of the pumps.

6.2 Engineering Module 2 - 3340XM100

6.2.1 Modules of Control – 3340XM100

T1 Control Module
UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340XM100

Tag Service
3340-XM-100 Deslime Pump Suction Valve Hydraulic Power Pack Pump
3340-XM-100 Deslime Pump Suction Valve Hydraulic Power Pack Heater

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 65 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PT-001A Power Pack Pressure transmitter


3340-TiT-001A Power Pack Temperature transmitter
3340-LIT-001A Power Pack Level transmitter
3340-HS-002A Local/Remote Switch
3340-ZL-001A Valve 1 Open Piston
3340-ZL-002A Valve 1 Close Piston
3340-ZL-003A Valve 2 Open Piston
3340-ZL-004A Valve 2 Close Piston

6.2.2 List of Interlocks – 3340-XM-100

T2 Interlock
Deslime Pump Suction Valve Hydraulic
Tag 3340-XM-100 Description
Power Pack Pump
Sub
UN CDCPF_Deslamado EM 3340BX101 3340XM100
EM
Fail Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to vendor and design functional specifications by others. Document number MQ14 - 08 - DR - 3340 - PD1103

Table 12: List of Interlocks for 3340XM100

6.2.3 Alarms and Process Setpoints – 3340XM100

T3 Alarms and Process Setpoints


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340XM100
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

Refer to vendor and design functional specifications by others. Document number MQ14 - 08 - DR - 3340 - PD1103

Table 13: Alarms and Process Setpoint 3340XM100

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 66 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

6.2.4 Binary State Messages – 3340XM100

There are no binary state messages for this section 3340XM100


6.2.5 Regulatory Control Loops – 3340XM100

There are no regulatory control loops for this section 3340XM100


6.2.6 Advanced Control Loops – 3340XM100

There are no advanced control loops for this section 3340XM100

6.2.7 Description – Deslime Pump Suction Valve Hydraulic Power Pack

The suction valves of the two Deslime Cyclone Feed Pumps are hydraulically driven via a
common hydraulic power pack. The power pack must be operating for the valves to open/close.
Reference should be made to the vendor control philosophy.
The power pack operation and control of the opening and closing of the suction valves is via a
local PLC. This communicates with the CPF’s PLC via Profinet S2.

6.3 Engineering Module 2 – 3340PU101

6.3.1 Description – 3340PU101

The following figure shows the elements that make up the 3340PU101 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 67 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Flush Water

3340-XV-003B 3340-XV-002B
LC
3340001

Emergency Tails
Launder
LT

3340-XV-013
PC
3340-BX-101 SC
FI DI 3340014
3340002
3340008 3340009
Tails Launder
PT
3340-XV-002A M
3340-XV-001A FT DT

3340-XV-015
A - AD
3340-PU-101
3340-CY-101
3340-XV-001C 3340-XV-002C
3340-XV-002D P-1224
FC
3340001

3340-XV-016
PC
SC
FI DI
3340005

3340017
3340003
FAL

FSL

3340010 3340011
Tails Box
3340-XV-003A M
PT
FT DT

3340-XV-017
3340-XV-005 A - AD
3340-PU-102
3340-XV-003C
FAL 3340-CY-102
3340-XV-006 3340006 3340-XV-003D
Crossflow Surge
Tank
FSL

GSW

Figure 15: Blockflow Control Diagram of the 3340PU101 System

The slurry within the Plant Feed Box (3340 – BX – 101) is then pumped by two operating, variable
speed Deslime Cyclone Feed Pumps (3340 – PU – 101 / 102) to the two Deslime Cyclone
Clusters 1 & 2 (3340 – CY – 101 / 102). The level in the Plant Feed Box is measured by level
transmitter (3340-LIT-001) and controlled by varying the speed of the pumps. Should the level
reach the low limit, the operating pumps flowrate setpoint will reduce to the minimum.
The suction valves to the pumps are hydraulically actuated and are supplied with a hydraulic
power pack within a vendor package (3340-XM-100).
The Deslime Cyclone Feed Pumps are a vendor package and all control loops, alarms and
interlocks specified in the vendor control philosophy document shall be applied.
The Deslime Cyclone feed flowrate is measured (3340-FIT-008 / 010) and shall not be allowed to
reduce below a minimum in order to prevent risks of pipeline sedimentation blockage.
Slurry density is also measured (3340-DIT-009 / 011) for mass balancing purposes. Its nuclear
source has an actuated shutter (3340-DX-009 / 011) for isolation.
By combining the flow transmitter and densitometer readings, a totalized mass flow in the deslime
cyclone feed pipeline will be calculated based upon the following formulae:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 68 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

𝑆𝐺
𝑇 = 𝑉𝑝 (𝑑𝑝 − 1) ×
𝑆𝐺 − 1
Where: T = Dry Solids Mass [tph]
Vp = Volumetric Flowrate [m3/hr] (3340-FIT-008 / 010)
Dp = Slurry density [t/m3] (3340-DIT-009 / 011)
SG = Solids Specific Gravity = 2.68 t/m3
Total dry mass feed to the CPF is the sum of the two pumps dry mass flowrates.
Solids mass pumped to the Deslime Cyclones will be totalized on an hour, shift, day and monthly
basis and will be visible to the control room operator.
This, together with the total crossflow feed mass flow rate calculation will provide input into the
calculation of the total mass rejection to the total deslime cyclone overflow.
Deslime Cyclone Mass Rejection [%] = {[ TCyclone Feed – TCrossflow Feed] / TCyclone Feed } × 100%
Where:
TCyclone Feed = Total Deslime Cyclone dry solids mass flow [tph]
TCrossflow Feed = Total Crossflow Feed dry solids mass flow [tph].
The mass rejection to overflow will be logged on an hour, shift, day and monthly basis and will be
visible to the control room operator.
6.3.2 Unit of Control Modules – 3340PU101

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU101

Tag Service
3340-XV-001C Flush valve, pre-suction 3340-BX-101
3340-PU-101-LU1FA1 Deslime Cyclone Feed Pump 1 Gearbox Cooling Fan
3340-PU-101-LU1HE1 Deslime Cyclone Feed Pump 1 Gearbox Oil Heater 1
3340-PU-101-LU1HE2 Deslime Cyclone Feed Pump 1 Gearbox Oil Heater 2
3340-PU-101-LU1HE3 Deslime Cyclone Feed Pump 1 Gearbox Oil Heater 3
3340-PU-101-LU1HE4 Deslime Cyclone Feed Pump 1 Gearbox Oil Heater 4
3340-PU-101-LU1HE5 Deslime Cyclone Feed Pump 1 Gearbox Oil Heater 5
3340-PU-101-LU1HE6 Deslime Cyclone Feed Pump 1 Gearbox Oil Heater 6
3340-PU-101-LU1PU1 Deslime Cyclone Feed Pump 1 Lube Oil Pump 1
3340-PU-101-LU1PU2 Deslime Cyclone Feed Pump 1 Lube Oil Pump 2
3340-PU-101-MO1FA1 Deslime Cyclone Feed Pump 1 Motor Fan 1

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 69 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PU-101-MO1FA2 Deslime Cyclone Feed Pump 1 Motor Fan 2


3340-PU-101-MO1FA3 Deslime Cyclone Feed Pump 1 Motor Fan 3
3340-PU-101-MO1FA4 Deslime Cyclone Feed Pump 1 Motor Fan 4
3340-PU-101-MO1HE1 Deslime Cyclone Feed Pump 1 Motor Space Heater
3340-DIT-009 Densitometer deslime cyclone cluster 3340-CY-101
3340-DX-009 Densitometer Nuclear source isolation, 3340-CY-101
3340-XV-002A Pump suction valve 3340-PU-101
3340-XV-002B Suction Flush water valve , 3340-PU-101
3340-XV-002C Suction Drain valve 3340-PU-101
3340-XV-002D Discharge drain valve 3340-PU-101
3340-FIT-008 Flowmeter to deslime cyclone cluster 3340-CY-101
3340-XV-005 Gland Water valve, 3340-PU-101
3340-FSL-005 Gland Seal Water Flow switch 3340-PU-101
3340-TSL-002D1 Temperature Switch Low, lubrication system 3340-PU-101
3340-TSH-002D2 Temperature Switch High, lubrication system 3340-PU-101
3340-LSL-002B Level Switch Low Flender unit 3340-PU-101
3340-PSL-002D1 Pressure Switch Low, lubrication system 3340-PU-101
3340-TT-002A2 Temperature Transmitter 3340-PU-101
3340-TT-002B3/4 Temperature Transmitter Flender unit 3340-PU-101
3340-TT-002A1 Temperature Transmitter 3340-PU-101
3340-VT-002B1/2/3 Vibration Transmitter Flender unit 3340-PU-101
3340-VT-002B4/5/6 Vibration Transmitter Flender unit 3340-PU-101
3340-TT-002B1/2 Temperature Transmitter Flender unit 3340-PU-101
3340-VT-002C1/2 Vibration Transmitter 3340-PU-101
3340-TSL-002D3 Temperature Switch Low, lubrication system 3340-PU-101
3340-FISL-002D1 Flow Switch Low, lubrication system 3340-PU-101
3340-TT-002B5/6 Temperature Transmitter, Flender unit 3340-PU-101
3340-VT-002C3/4 Vibration Transmitter 3340-PU-101
3340-TT-002B7 Temperature Transmitter Flender unit 3340-PU-101
3340-PSH-002D2 Pressure switch high, lubrication 3340-PU-101

Table 14: List of Unit Controls – 3340PU101

6.3.3 Interlocks – 3340PU101

T2 Interlock
Deslime Feed Pump 1 Pre-Suction Valve
Tag 3340-XV-001C Description
Flush Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 70 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

CDCPF_Deslama Sub
UN EM 3340BX101 3340PU101
do EM
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 15: List of Interlocks for 3340-XV-001C

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Tag 3340-XV-002A Description Deslime Feed Pump 1 Suction Valve
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU101
do EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-002C.OP Suction drain valve open


OR OR ×
3340-XV-002C.OPNG Suction drain valve opening
3340-PU-101.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-002A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-002A.OPNG)
Refer to vendor control philosophy of valve hydraulic power pack, 3340XM100. Document number MQ14 - 08 - DR - 3340 -
PD1103

Table 16: List of Interlocks for 3340-XV-002A

T2 Interlock
Tag 3340-XV-002B Description Deslime Feed Pump 1 Flush Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 71 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

CDCPF_Deslama Sub
UN EM 3340BX101 3340PU101
do EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 17: List of Interlocks for 3340-XV-002B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Deslime Feed Pump 1 Suction Drain
Tag 3340-XV-002C Description
Valve
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU101
do EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 18: List of Interlocks for 3340-XV-002C

T2 Interlock
Tag 3340 – PU - 101 Description Deslime Feed Pump 1
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU101
do EM
Interlock
Motor Type VFD (Multiple) Intlck_3340BB_SL_01
Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 72 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. Document number MQ15-718-TE-3340-IN0101


3340-XV-005 !OP ×
If gland seal water valve not open and
AND Note 1
3340-PU-101 is running
3340-PU-101.MO1.Run
3340-FSL-005.ACT Flow switch (3340-FSL-005) has a low ×
Time Delay
AND flow alarm for a time delay and 3340-PU-
300 seconds
3340-PU-101-MO1.Run 101 is running
Flow switch (3340-FSL-005) has a low
3340-FSL-005.ACT ×
flow alarm
3340-XV-002A CL ×
Suction valve (3340-XV-002A)
OR CLN Time Delay
Is closed or closing and 3340-PU-101 is
AND 10 seconds
running for a time delay
3340-PU-101-MO1.Run
3340-XV-002C OP OR Suction drain valve (3340-XV-002C) is × Debounce
OPN open or opening
× Time Delay
The level of the Plant Feed Pump Box
3340-LIT-001.LL 300 seconds
(3340-LIT-001) is Low Low
Note 2
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-002D OP OR Discharge drain valve (3340-XV-002D) is × Debounce
OPN open or opening
3340-CY- ×
101.V_OPEN_HLIM Number of deslime cyclones available <
(3340-XV-015 A thru 15
AD)
3340-FIT-008.LL AND ×
Slurry flowrate is Low Low and pump is Time Delay
3340-PU-101-
running 600 seconds
MO1.RUN
Instrument Air Pressure (3340-PIT-675) is × Time Delay
3340-PIT-675.LL
Low Low for a time delay 10 seconds
Either ×
3340-PIT-670.LL
3340-PIT-670
OR
OR
3340-PIT-671.LL Time Delay
3340-PIT-671
OR 60 seconds
OR
3340-PIT-678.LL
3340-PIT-678
is Low Low for a time delay
CPF Make-Up Water Pressure 3720-PIT- × Time Delay
3720-PIT-116.LL
116 is Low Low for a time delay 180 seconds
3340 – PU – Both Crossflow Feed Pumps ×
185.MO1.Run 3340 – PU – 185
Time Delay
AND AND
300 seconds
3340 – PU – 3340 – PU – 186
186.MO1.Run Have not run for a time delay

Table 19: List of Interlocks for 3340 – PU - 101

Note 1 On stopping 3340 – PU – 101, its gearbox lubrication system may continue to run. Refer
to vendor functional specification

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 73 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note 2 Pump 3340 – PU – 101 should only stop if it has a longer run time than 3340 – PU – 102

T2 Interlock
Deslime Feed Pump 1 Discharge Drain
Tag 3340-XV-002D Description
Valve
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU101
do EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 20: List of Interlocks for 3340-XV-002D

T2 Interlock
Deslime Feed Pump 1 Densitometer
Tag 3340-DX-009 Description
Nuclear Source Isolation Shutter
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU101
do EM
Interlock Intlck_OBTURADOR_DENSI
Motor Type
Type METRO_01
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-PU-101.!RUN If the pump is not working ×

Table 21: List of Interlocks for 3340-DX-009

T2 Interlock
Deslime Feed Pump 1 Gland Seal Water
Tag 3340-XV-005 Description
Valve
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU101
do EM
Fail Position:
Keep Last (KL) Interlock Intlck_VLV_gland seal water
Motor Type
Safe Position: Type O_01
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 74 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Delay time
3340-PU-101.!RUN If the pump is not working ×
5s

Table 22: List of Interlocks for 3340-XV-005

6.3.4 Alarms and Process Setpoints – 3340PU101

T3 Alarms and Process Setpoints


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU101
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Refer to vendor control philosophy for pump specific Alarms and Process Setpoints. MQ15-718-TE-3340-IN0101

3340-FIT-008 Deslime Cyclone Feed Pump


0 – 10 000 % 8 545 5 350 4 700
Flowmeter
3340-DIT-009 Deslime Cyclone Feed Pump
1.0 – 2.0 t/m3
densitometer
3340-FSL-005 Deslime Cyclone Feed Pump
0 - 18 m3/hr 9.78
Gland Seal Water Flow switch

Table 23: Alarms and Process Setpoint 3340PU101

The alarms associated with the Density transmitter, as well as the flow measurement should be
inhibited when pump 3340-PU-101 is not running.
6.3.5 Binary Messages – 3340PU101

T4 Binary State Messages


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU101
Tag Description OFF ON

3340-ZSC-009 LINE RADIOACTIVE SOURCE


× Note 2
CYCLONE 3340-CY-101 CLOSED
3340-ZSO-009 LINE RADIOACTIVE SOURCE
× Note 1
CYCLONE 3340-CY-101 OPEN

Table 24: Binary State Messages 3340PU101

Note:
1) Condition should alarm, if the valve is open 5 seconds after the pump 3340-PU-101 has
stopped.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 75 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

2) Condition should alarm, if the valve is closed, 5 seconds after the pump 3340-PU-101 is
running. If this condition occurs, calculation of the mass flowrate and average value % of
solids should not occur.
3) An alarm should be provided when a nuclear density meter reading (tag 3340-DIT-009)
provides a difference in measured value greater than 10%, under normal operating
conditions (both pumps operating). Alarm will not be triggered when only one pump is
operating, when the pump is under start-up conditions.
6.3.6 Regulatory Control Loops – 3340PU101

T5 Regulatory Control Loops


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU101
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 - 100 30 - 95 Expected
3340-LIC-001 CPF Plant Feed Box Level Controller
setpoint 60%

Table 25: Regulatory Control Loops for 3340-LIC-001

T5 Regulatory Control Loops


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU101
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
76 - 100 % m3/hr 0 - 10000 5350 – Expected
Deslime Cyclone Feed Flowrate
3340-FIC-001 8540 setpoint
Controller
m3/hr 6540m3/hr

Table 26: Regulatory Control Loops for 3340-FIC-001

Note 1: Controller will be disabled (tracking action), if pump is stopped

6.3.7 Advanced Control Loops – 3340PU101

Not applicable

6.3.8 Sequence Description – 3340PU101

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. The pump start sequence 3340-PU-101, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 76 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU101
Seq Command Tag Description Transition Min Monitor
Time Time
Suction drain Valve
3340-XV-002C 2 60
1. Close and Closed
3340-XV-002D seconds seconds
Discharge drain valve
Flush Water valve, pre-suction Open for 30 20 60
2. Open 3340-XV-001C
valve seconds seconds seconds
Flush Water valve, pre-suction 2 60
3. Close 3340-XV-001C Closed
valve seconds seconds
(Open &
Low Flow
2 60
4. Open 3340-XV-005 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
Open
Suction Valve.
and 2 220
5. Open 3340-XV-002B Refer to vendor functional
3340-XM- seconds seconds
specification.
100.RUN
3340-PU-101-LU1PU1
3340-PU-101-LU1PU2 Start Pump lubrication
10 120
6. Start 3340-PU-101-LU1HE1 sequences. Refer to vendor
seconds seconds
3340-PU-101-LU1HE2 functional specification.
3340-PU-101-LU1FA1
Start pump. Refer to vendor 10 60
7. Start 3340-PU-101.MO1 Working
functional specification. seconds seconds

Table 27: Start Sequence 3340PU101

Reference should be made to the hydraulic valve power pack (3340-XM-100) functional
specification for its start/stop sequence and monitoring requirements.
Reference should be made to the Deslime Cyclone Feed Pump (3340-PU-101) functional
specification for its start/stop sequence of the lubrication system and monitoring requirements.
(MQ15-718-TE-3340-IN0101).
The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-101 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-101-MO1 stopped
The pump stop sequence 3340-PU-101, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 77 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU101
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-101.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
Stop pump.
20 60
2. Stop 3340-PU-101.MO1 Refer to vendor functional Stopped
seconds seconds
specification
Suction Valve.
2 180
3. Close 3340-XV-002A Refer to vendor functional Closed
seconds seconds
specification
2 60
4. Open 3340-XV-002D Discharge Drain Valve Opened
seconds seconds
2 60
5. Open 3340-XV-002C Suction Drain valve Opened
seconds seconds
2 20
6. Close 3340-XV-005 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, pre-suction 20 60
7. Open 3340-XV-001C 30
valve seconds seconds
seconds
Flush Water valve, pre-suction 2 20
8. Close 3340-XV-001C Closed
valve seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-002B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-002B Closed
valve seconds seconds

Table 28: Stop Sequence 3340PU101

The Shutter of the Nuclear Density Meter (3340-DX-009) will open 5 seconds after the pump
3340-PU-101 is operational. The shutter will close when the pump stops.

6.4 Engineering Module 2 – 3340PU102

6.4.1 Description – 3340PU102

The following figure shows the elements that make up the 3340PU102 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 78 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Flush Water

3340-XV-003B 3340-XV-002B
LC
3340001

Emergency Tails
Launder
LT

3340-XV-013
PC
3340-BX-101 SC
FI DI 3340014
3340002
3340008 3340009
Tails Launder
PT
3340-XV-002A M
3340-XV-001A FT DT

3340-XV-015
A - AD
3340-PU-101
3340-CY-101
3340-XV-001C 3340-XV-002C
3340-XV-002D FC
3340001

3340-XV-016
PC
SC
FI DI
3340005

3340017
3340003
FAL

FSL

P-1272 3340010 3340011


Tails Box
3340-XV-003A M
PT
FT DT

3340-XV-017
3340-XV-005 A - AD
3340-PU-102
3340-XV-003C
FAL 3340-CY-102
3340-XV-006 3340006 3340-XV-003D
Crossflow Surge
Tank
FSL

GSW

Figure 16: Blockflow Control Diagram of the 3340PU102 System

The slurry within the Plant Feed Box (3340 – BX – 101) is pumped by two operating, variable
speed Deslime Cyclone Feed Pumps (3340 – PU – 101 / 102) to the two Deslime Cyclone
Clusters 1 & 2 (3340 – CY – 101 / 102). The level in the Plant Feed Box is measured by level
transmitter (3340-LIT-001) and controlled by varying the speed of the pumps. Should the level
reach the low limit, the operating pumps flowrate setpoint will reduce to the minimum.
The suction valves to the pumps are hydraulically actuated and are supplied with a hydraulic
power pack within a vendor package (3340-XM-100).
The Deslime Cyclone Feed Pumps are a vendor package and all control loops, alarms and
interlocks specified in the vendor control philosophy document shall be applied.
The Deslime Cyclone feed flowrate is measured (3340-FIT-008 / 010) and shall not be allowed to
reduce below a minimum in order to prevent risks of pipeline sedimentation blockage.
Slurry density is also measured (3340-DIT-009 / 011) for mass balancing purposes. Its nuclear
source has an actuated shutter (3340-DX-009 / 011) for isolation.
By combining the flow transmitter and densitometer readings, a totalized mass flow in the deslime
cyclone feed pipeline will be calculated based upon the following formulae:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 79 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

𝑆𝐺
𝑇 = 𝑉𝑝 (𝑑𝑝 − 1) ×
𝑆𝐺 − 1
Where: T = Dry Solids Mass [tph]
Vp = Volumetric Flowrate [m3/hr] (3340-FIT-008 / 010)
Dp = Slurry density [t/m3] (3340-DIT-009 / 011)
SG = Solids Specific Gravity = 2.68 t/m3
Total dry mass feed to the CPF is the sum of the two pumps dry mass flowrates.
Solids mass pumped to the Deslime Cyclones will be totalized on an hour, shift, day and monthly
basis and will be visible to the control room operator.
This, together with the total crossflow feed mass flow rate calculation will provide input into the
calculation of the total mass rejection to the total deslime cyclone overflow.
Deslime Cyclone Mass Rejection [%] = {[ TCyclone Feed – TCrossflow Feed] / TCyclone Feed } × 100%
Where:
TCyclone Feed = Total Deslime Cyclone dry solids mass flow [tph]
TCrossflow Feed = Total Crossflow Feed dry solids mass flow [tph].
The mass rejection to overflow will be logged on an hour, shift, day and monthly basis and will be
visible to the control room operator.
6.4.2 Unit of Control Modules – 3340PU102

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU102

Tag Service
3340-XV-001A Flush Water Valve, pre-suction valve 3340-BX-101
3340-PU-102-LU1FA1 Deslime Cyclone Feed Pump 2 Gearbox Cooling Fan
3340-PU-102-LU1HE1 Deslime Cyclone Feed Pump 2 Gearbox Oil Heater 1
3340-PU-102-LU1HE2 Deslime Cyclone Feed Pump 2 Gearbox Oil Heater 2
3340-PU-102-LU1HE3 Deslime Cyclone Feed Pump 2 Gearbox Oil Heater 3
3340-PU-102-LU1HE4 Deslime Cyclone Feed Pump 2 Gearbox Oil Heater 4
3340-PU-102-LU1HE5 Deslime Cyclone Feed Pump 2 Gearbox Oil Heater 5
3340-PU-102-LU1HE6 Deslime Cyclone Feed Pump 2 Gearbox Oil Heater 6
3340-PU-102-LU1PU1 Deslime Cyclone Feed Pump 2 Lube Oil Pump 1
3340-PU-102-LU1PU2 Deslime Cyclone Feed Pump 2 Lube Oil Pump 2
3340-PU-102-MO1FA1 Deslime Cyclone Feed Pump 2 Motor Fan 1

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 80 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PU-102-MO1FA2 Deslime Cyclone Feed Pump 2 Motor Fan 2


3340-PU-102-MO1FA3 Deslime Cyclone Feed Pump 2 Motor Fan 3
3340-PU-102-MO1FA4 Deslime Cyclone Feed Pump 2 Motor Fan 4
3340-PU-102-MO1HE1 Deslime Cyclone Feed Pump 2 Motor Space Heater
3340-DIT-011 Densitometer to 3340-CY-102
3340-DX-011 Densitometer nuclear source shutter to cyclones 3340-CY-102
3340-FSL-006 Gland Seal Flow switch 3340-PU-102
3340-XV-003A Suction valve pump 3340-PU-102
3340-XV-003B Suction Flush Valve of pump 3340-PU-102
3340-XV-003C Suction drain valve of pump 3340-PU-102
3340-XV-003D Discharge drain valve of pump 3340-PU-102
3340-FIT-010 Flowmeter of slurry to cyclones 3340-CY-102
3340-VT-003C1/2 Vibration Transmitter bearings pump 3340-PU-102
3340-TT-003B1/2 Temperature Transmitter bearings Flender unit 3340-PU-102
3340-TT-003A2 Temperature transmitter bearings pump 3340-PU-102
3340-TT-003B3/4 Temperature transmitter bearings Flender unit 3340-PU-102
3340-TT-003A1 Temperature Transmitter bearings pump 3340-PU-102
3340-VT-003B1/2/3 Vibration transmitter bearings Flender unit 3340-PU-102
3340-VT-003B4/5/6 Vibration transmitter bearings Flender unit 3340-PU-102
3340-TSL-003D1 Temperature Switch Low lubrication 3340-PU-102
3340-TSH-003D2 Temperature switch high lubrication 3340-PU-102
3340-LSL-003B Low level switch Flender unit 3340-PU-102
3340-PSL-003D1 Pressure switch low lubrication 3340-PU-102
3340-XV-006 Gland seal water valve for 3340-PU-102
3340-VT-003C3/4 Vibration transmitter bearings pump 3340-PU-102
3340-TT-003B5/6 Temperature transmitter bearings Flender unit 3340-PU-102
3340-TT-003B7 Temperature transmitter Flender unit 3340-PU-102
3340-PSH-003D2 Pressure switch high lubrication 3340-PU-102
3340-TSL-003D3 Temperature switch low lubrication 3340-PU-102
3340-FISL-003D1 Flow switch low lubrication 3340-PU-102

Table 29: List of Unit Controls – 3340PU102

6.4.3 Interlocks – 3340PU102

T2 Interlock
Deslime Feed Pump 2 Pre-Suction Valve
Tag 3340-XV-001A Description
Flush Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 81 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

CDCPF_Deslama Sub
UN EM 3340BX101 3340PU102
do EM
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 30: List of Interlocks for 3340-XV-001A

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Tag 3340-XV-003A Description Deslime Feed Pump 2 Suction Valve
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU102
do EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-003C.OP Suction drain valve open


OR OR ×
3340-XV-003C.OPNG Suction drain valve opening
3340-PU-102.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-003A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-003A.OPNG)
Refer to vendor control philosophy of valve hydraulic power pack, 3340XM100. Document number MQ14 - 08 - DR - 3340 -
PD1103

Table 31: List of Interlocks for 3340-XV-003A

T2 Interlock
Tag 3340-XV-003B Description Deslime Feed Pump 2 Flush Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 82 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

CDCPF_Deslama Sub
UN EM 3340BX101 3340PU102
do EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 32: List of Interlocks for 3340-XV-003B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Deslime Feed Pump 2 Suction Drain
Tag 3340-XV-003C Description
Valve
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU102
do EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 33: List of Interlocks for 3340-XV-003C

T2 Interlock
Tag 3340 – PU – 102 Description Deslime Feed Pump 2
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU102
do EM
Interlock
Motor Type VFD (Multiple) Intlck_3340BB_SL_01
Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 83 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. MQ15-718-TE-3340-IN0101


3340-XV-006 !OP ×
If gland seal water valve not open and
AND Note 1
3340-PU-102 is running
3340-PU-102.MO1.Run
3340-FSL-006.ACT Flow switch (3340-FSL-006) has a low ×
Time Delay
AND flow alarm for a time delay and 3340-PU-
300 seconds
3340-PU-102-MO1.Run 102 is running
Flow switch (3340-FSL-006) has a low
3340-FSL-006.ACT ×
flow alarm
3340-XV-003A CL ×
Suction valve (3340-XV-003A)
OR CLN Time Delay
Is closed or closing and 3340-PU-102 is
AND 10 seconds
running for a time delay
3340-PU-102-MO1.Run
3340-XV-003C OP OR Suction drain valve (3340-XV-003C) is × Debounce
OPN open or opening
× Time Delay
The level of the Plant Feed Pump Box
3340-LIT-001.LL 300 seconds
(3340-LIT-001) is Low Low
Note 2
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-003D OP OR Discharge drain valve (3340-XV-003D) is × Debounce
OPN open or opening
3340-CY- ×
102.V_OPEN_HLIM Number of deslime cyclones available <
(3340-XV-018 A thru 15
AD)
3340-FIT-010.LL AND ×
Slurry flowrate is Low Low and pump is Time Delay
3340-PU-102-
running 600 seconds
MO1.RUN
Instrument Air Pressure (3340-PIT-675) is × Time Delay
3340-PIT-675.LL
Low Low for a time delay 10 seconds
Either ×
3340-PIT-670.LL
3340-PIT-670
OR
OR
3340-PIT-671.LL Time Delay
3340-PIT-671
OR 60 seconds
OR
3340-PIT-678.LL
3340-PIT-678
is Low Low for a time delay
CPF Make-Up Water Pressure 3720-PIT- × Time Delay
3720-PIT-116.LL
116 is Low Low for a time delay 180 seconds
3340 – PU – Both Crossflow Feed Pumps ×
185.MO1.Run 3340 – PU – 185
AND Time Delay
AND
300 seconds
3340 – PU – 3340 – PU – 186
186.MO1.Run Have not run for a time delay

Table 34: List of Interlocks for 3340 – PU - 102

Note 1 On stopping 3340 – PU – 102, its gearbox lubrication system may continue to run. Refer
to vendor functional specification MQ15-718-TE-3340-IN0101

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 84 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note 2 Pump 3340 – PU – 102 should only stop if it has a longer run time than 3340 – PU – 101

T2 Interlock
Deslime Feed Pump 2 Discharge Drain
Tag 3340-XV-003D Description
Valve
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU102
do EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 35: List of Interlocks for 3340-XV-003D

T2 Interlock
Deslime Feed Pump 2 Densitometer
Tag 3340-DX-011 Description
Nuclear Source Isolation Shutter
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU102
do EM
Interlock Intlck_OBTURADOR_DENSI
Motor Type
Type METRO_01
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-PU-102.!RUN If the pump is not working ×

Table 36: List of Interlocks for 3340-DX-009

T2 Interlock
Deslime Feed Pump 2 Gland Seal Water
Tag 3340-XV-006 Description
Valve
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU102
do EM
Fail Position:
Keep Last (KL) Interlock Intlck_VLV_gland seal water
Motor Type
Safe Position: Type O_01
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 85 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-102.!RUN If the pump is not working ×

Table 37: List of Interlocks for 3340-XV-006

6.4.4 Alarms and Process Setpoints – 3340PU102

T3 Alarms and Process Setpoints


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU102
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Refer to vendor control philosophy for pump specific Alarms and Process Setpoints. MQ15-718-TE-3340-IN0101
3340-FIT-010 Deslime Cyclone Feed Pump
0 – 10 000 % 8 545 5 350 4 700
Flowmeter
3340-DIT-011 Deslime Cyclone Feed Pump
1.0 – 2.0 t/m3
densitometer
3340-FSL-006 Deslime Cyclone Feed Pump 0 - 18 m3/hr 9.78
Gland Seal Water Flow switch

Table 38: Alarms and Process Setpoint 3340PU102

The alarms associated with the Density transmitter, as well as the flow measurement should be
inhibited when pump 3340-PU-102 is not running.
6.4.5 Binary Messages – 3340PU102

T4 Binary State Messages


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU102
Tag Description OFF ON

3340-ZSC-011 LINE RADIOACTIVE SOURCE


× Note 2
CYCLONE 3340-CY-102 CLOSED
3340-ZSO-011 LINE RADIOACTIVE SOURCE
× Note 1
CYCLONE 3340-CY-102 OPEN

Table 39: Binary State Messages 3340PU102

Note:
1) Condition should alarm, if the valve is open 5 seconds after the pump 3340-PU-102 has
stopped.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 86 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

2) Condition should alarm, if the valve is closed, 5 seconds after the pump 3340-PU-102 is
running. If this condition occurs, calculation of the mass flowrate and average value % of
solids should not occur.
3) An alarm should be provided when a nuclear density meter reading (tag 3340-DIT-011)
provides a difference in measured value greater than 10%, under normal operating
conditions (both pumps operating). Alarm will not be triggered when only one pump is
operating, when the pump is under start-up conditions.
6.4.6 Regulatory Control Loops – 3340PU102

T5 Regulatory Control Loops


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU102
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
76 - 100 % m3/hr 0 - 100 5350 – Expected
Deslime Cyclone Feed Flowrate
3340-FIC-001 8540 setpoint
Controller
m3/hr 6540m3/hr

Table 40: Regulatory Control Loops for 3340-FIC-001

Note 1: Controller will be disabled (tracking action), if pump is stopped


6.4.7 Advanced Control Loops – 3340PU102

Not applicable

6.4.8 Sequence Description – 3340PU102

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. The pump start sequence 3340-PU-102, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 87 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU102
Seq Command Tag Description Transition Min Monitor
Time Time
Suction drain Valve
3340-XV-003C 2 60
1. Close and Closed
3340-XV-003D seconds seconds
Discharge drain valve
Flush Water valve, pre-suction Open for 30 20 60
2. Open 3340-XV-001A
valve seconds seconds seconds
Flush Water valve, pre-suction 2 60
3. Close 3340-XV-001A Closed
valve seconds seconds
(Open &
Low Flow
2 60
4. Open 3340-XV-006 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
Open
Suction Valve.
and 2 220
5. Open 3340-XV-003B Refer to vendor functional
3340-XM- seconds seconds
specification.
100.RUN
3340-PU-102-LU1PU1
3340-PU-102-LU1PU2 Start Pump lubrication
10 120
6. Start 3340-PU-102-LU1HE1 sequences. Refer to vendor
seconds seconds
3340-PU-102-LU1HE2 functional specification.
3340-PU-102-LU1FA1
Start pump. Refer to vendor 10 60
7. Start 3340-PU-102.MO1 Working
functional specification. seconds seconds

Table 41: Start Sequence 3340PU102

Reference should be made to the hydraulic valve power pack (3340-XM-100) functional
specification for its start/stop sequence and monitoring requirements.
Reference should be made to the Deslime Cyclone Feed Pump (3340-PU-102) functional
specification for its start/stop sequence of the lubrication system and monitoring requirements.
MQ15-718-TE-3340-IN0101
The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-102 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-102-MO1 stopped
The pump stop sequence 3340-PU-102, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 88 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU102
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-102.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
Stop pump.
20 60
2. Stop 3340-PU-102.MO1 Refer to vendor functional Stopped
seconds seconds
specification
Suction Valve.
2 180
3. Close 3340-XV-003A Refer to vendor functional Closed
seconds seconds
specification
2 60
4. Open 3340-XV-003D Discharge Drain Valve Opened
seconds seconds
2 60
5. Open 3340-XV-003C Suction Drain valve Opened
seconds seconds
2 20
6. Close 3340-XV-006 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, pre-suction 20 60
7. Open 3340-XV-001A 30
valve seconds seconds
seconds
Flush Water valve, pre-suction 2 20
8. Close 3340-XV-001A Closed
valve seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-003B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-003B Closed
valve seconds seconds

Table 42: Stop Sequence 3340PU102

The Shutter of the Nuclear Density Meter (3340-DX-011) will open 5 seconds after the pump
3340-PU-102 is operational. The shutter will close when the pump stops.

6.5 Engineering Module 2 – 3340PU174

6.5.1 Unit of Control Modules – 3340PU174

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU174

Tag Service
3340-TE-012 Bearing temperature switch
3340-LSH-012 Level Switch High – sump pump 3340-PU-174
3340-LSHH-012 Level Switch High High – deslime pump area

Table 43: List of Unit Controls – 3340PU174

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 89 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

6.5.2 Interlocks – 3340PU174

T2 Interlock
Tag 3340-PU-174 Description Feed Area Sump Pump
CDCPF_Deslama Sub
UN EM 3340BX101 3340PU174
do EM
Interlock
Motor Type M1 Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Delay 10
3340-LSH-012.ACT High level switch activated × seconds
Note 1

3340-TE-012.ACT High bearing temperature alarm ×

BLACKOUT Delay 5
Electrical BlackOut Activated ×
ELECTRICO.ACT seconds

Table 44: List of Interlocks for 3340-PU-174

Note 1: Pump to run 15 minutes after the high level has been removed.
6.5.3 Alarms and Process Setpoints – 3340PU174

T3 Alarms and Process Setpoints


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU174
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-LSH-012 Deslime Cyclone Spillage Pump


0 - 100 % 27%
High Switch Alarm
3340-LSHH- Deslime Cyclone Spillage Pump
012 0 - 100 % 85%
High High Switch Alarm

Table 45: Alarms and Process Setpoint 3340-PU-174

Note: Level switches setpoints set in field, not within PLC.


6.5.4 Binary Messages – 3340PU174

T4 Binary State Messages


UN CDCPF_Deslamado EM 3340BX101 Sub EM 3340PU174

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 90 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag Description OFF ON


3340-LSHH- CPF DESLIME PUMP BUND AREA
012 × Delay 5 seconds
HIGH HIGH SLURRY LEVEL

Table 46: Binary State Messages 3340PU174

6.5.5 Regulatory Control Loops – 3340PU174

Not applicable.
6.5.6 Advanced Control Loops – 3340PU174

Not applicable
6.5.7 Description – 3340PU174

Spillage in the Deslime Cyclone Feed Pump area will gravitate to the Feed Area Spillage Pump
(3340 – PU – 174). The pump will discharge by manual selection to either:
 The Emergency Tails Launder (3340 – LN - 104);
 Or, more commonly, to the CPF Plant Feed Box (3340 – BX - 101).
This equipment can operate in manual mode or automatic mode. In manual mode, the start and
stop by the PLC will depend on the start/stop command that the operator. The operation of the
pump in Automatic Mode will occur if:
- The pump will start automatically, if it is ready to Operate in Sequence, and if Sump level
switch is high.
- The sump pump will stop automatically 15 minutes after the level switch high has fallen
away. The time delay in stopping the pump allows the pump to continue to run while hose
down of the area is occurring.
An additional High High limit switch is included to alarm the operator that significant spillage is
occurring in the area requiring operator intervention.

6.6 Engineering Module 1 – 3340Clasif001

6.6.1 Description – 3340Clasif001

The two Deslime Cyclone Clusters (3340 – CY – 101 / 102) receives the pumped slurry and
effects a size separation on the material. Cyclone feed pressure (3340-PIT-014A / 017A) is
controlled by varying the number of cyclone feed valves (3340-XV-015 / 018 A-AD) opened. If the
cyclone feed pressure is above the high setpoint limit for a specified time, another feed valve will
open. Conversely if the feed pressure is below the low setpoint limit for a specified time, a valve
will close. The PLC will select which valve to open/close in preference of equalising operating
time, so that all cyclone equipment will over time have similar wear rates.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 91 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Flush dilution water is added (3340-XV-013A / 016A) on a continuous basis to the cyclone
underflow to initially dilute and flush the slurry into the Crossflow Feed Surge Tank below. This
valve must close if the respective Deslime Cyclone Feed Pump (3340 – PU – 101 / 102) stops
running.
On start-up of the Deslime Cyclone Feed pump, a minimum number of cyclone feed valves must
be open. After starting the number of cyclones utilised will be allowed to vary to maintain the
pressure setpoint.

6.7 Engineering Module 2 – 3340CY101

6.7.1 Description – 3340CY101

The following figure shows the elements that make up the 3340CY101 equipment module.
Flush Water

3340-XV-003B 3340-XV-002B
LC
3340001

Emergency Tails
Launder
LT

3340-XV-013
PC
3340-BX-101 SC
FI DI 3340014
3340002
P-1327 3340008 3340009
Tails Launder
PT
3340-XV-002A M
3340-XV-001A FT DT

3340-XV-015
A - AD
3340-PU-101
3340-CY-101
3340-XV-001C 3340-XV-002C
3340-XV-002D FC
3340001

3340-XV-016
PC
SC
FI DI
3340005

3340017
3340003
FAL

FSL

3340010 3340011
Tails Box
3340-XV-003A M
PT
FT DT

3340-XV-017
3340-XV-005 A - AD
3340-PU-102
3340-XV-003C
FAL 3340-CY-102
3340-XV-006 3340006 3340-XV-003D
Crossflow Surge
Tank
FSL

GSW

Figure 17: Blockflow Control Diagram of the 3340CY101 System

6.7.2 Unit of Control Modules – 3340CY101

T1 Control Module
UN CDCPF_Deslamado EM 3340Clasif001 Sub EM 3340CY101

Tag Service

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 92 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PIT-0014 Deslime Cyclone Cluster 1 pressure transmitter


3340-XV-0185 thru AD Deslime Cyclone Cluster 1 cyclone isolation valve A through AD (total 30 valves)
3340-XV-013A Deslime Cyclone Cluster 1 Underflow Dilution Isolation Valve

Table 47: List of Unit Controls – 3340CY101

6.7.3 Interlocks – 3340CY101

T2 Interlock
3340-XV-015 A Deslime Cyclone Cluster 1 Feed Valves
Tag Description
thru AD (30 in total)
CDCPF_Deslama 3340Clasif00 Sub
UN EM 3340CY101
do 1 EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

No Interlocks

Table 48: List of Interlocks for 3340-XV-015 A though AD

T2 Interlock
Deslime Cyclone Cluster 1 Underflow
Tag 3340-XV-013 A Description
Dilution Valve
CDCPF_Deslama 3340Clasif00 Sub
UN EM 3340CY101
do 1 EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

No Interlocks

Table 49: List of Interlocks for 3340-XV-013 A

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 93 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Operation Valve 3340-XV-013A must be linked to the operation of the pump 3340-PU-101, so that it opens
when starting the pump, and closes 300 seconds after the pump stops.

6.7.4 Alarms and Process Setpoints – 3340CY101

T3 Alarms and Process Setpoints


UN CDCPF_Deslamado EM 3340Clasif001 Sub EM 3340CY101
High Low
Tag Description Range Unit SP HYS High Low
High Low
3340-PIT- Deslime Cyclone Cluster 1 Feed
0014 0 - 1000 KPa 150 103 83
Pressure Transmitter

Table 50: Alarms and Process Setpoint 3340CY101

Note

1) Low pressure Cyclone cluster feed pressure alarms must be inhibited if the pump 3340-PU-101 is not
running.

6.7.5 Binary State Messages – 3340CY101

T4 Binary State Messages


CDCPF_Deslamad
UN EM 3340Clasif001 Sub EM 3340CY101
o
Tag Service OFF ON QC
3340-ZSO-014A Deslime Cyclone Cluster 1 underflow flush × Note 2
water
3340-ZSC-014A Deslime Cyclone Cluster 1 underflow flush × Note 1
water

Table 51: Binary State Messages for 3340CY101

Note

1) Condition must alarm, if valve is not open and pump 3340-PU-101 running for more than 10 seconds.

2) Condition must alarm, if valve is not closed and pump 3340-PU-101 running for more than 10 seconds.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 94 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

6.7.6 Regulatory Control Loops – 3340CY101

T5 Regulatory Control Loops


UN CDCPF_Deslamado EM 3340Clasif001 Sub EM 3340CY101
Tag Description Range Unit MV Unit Range Range Conditions MV
MV PV/SP PV SP
0 - 30 # cyclones KPa 80 - 3340PU101.!R
1201 un OR
Deslime Cyclone Cluster Pressure (3340PU101.R
3340-PIC-014
Controller UN &
APC_CY101-
ON

Table 52: Regulatory Control Loops for 3340-PIC-014

The control loop 3340-PIC-101, corresponds to a Rule-based Controller, the which will enter into
operations when the APC Controller that controls the operation of the Cyclone Battery is not operational.

Tabulated below are the rules for the operation of the intervening block.

ID Condition Action
1. 3340-PIT-014 > HTH Increase by one (1) N° Cyclones.
2. 3340-PIT-014 < LTH Decrease by one (1) N° Cyclones.
Where:

PV1: 3340-PIT-014

PV1.HTH = 103 KPa

PV1.LTH = 83KPa

Selection of the valves to open / close in the cluster based upon the longest open time.

The Intervening Block will be evaluated 1 time every 60 seconds, in order to update (increase or
decrease), the number of Cyclones required to achieve an adequate Classification of the mineral. The
Controller based on the Controller block, tag 3340-PIC-101, will work in conjunction with the Advanced
Control Loop 3340-UIC-101 described in the subsection "Advanced Control Loops", and “Description" of
the EM 3340CY101.

1
Expected setpoint 100KPa

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 95 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

6.7.7 Advanced Control Loops – 3340CY101

T5 Regulatory Control Loops


3340-UIC-014A/
Tag APC Type APC 10
APC-3340-PIC-014A
UN CDCPF_Deslamado EM 3340Clasif001 Sub EM 3340CY101
Tag Description Unit Variable Type Notes
Deslime Cyclone Cluster 1 KPa CV1
3340-PIT-014
Pressure Controller
Hydrocyclone Cluster – Control # MV1 Note 1
3340-KC-
Opening/Cyclone Closure cyclone
014.RSP
s

Note:

1) The 3340KC014 controller corresponds to the Opening and Closing Control block of Cyclones (CL30).
The cyclone cluster has thirty (30) cyclones in total, where fifteen (15) cyclones (LLIM1) will be the
minimum of devices that will be able to operate, while Twenty-four (24) cyclones (HLIM1), will be a
maximum of devices that can operate. On the other hand, six (6) Cyclones will be available in Stand
By condition, for replace any unit in case of failure. Block CL24 will be activated with the operating
status of the 3340-PU-101 pump.

6.7.8 Description – 3340CY101

The objective of the cyclone cluster 3340-CY-101 is to classify the mineral received by the CPF, in order
to differentiate it between mineral that contains a recoverable grade and the smaller size fractions that
can be discarded.

The coarse material, will be obtained through the spigot underflow of the cyclones, while the fines
material will overflow the cyclone and report to tailings. The cyclone cluster feed pressure is controlled by
opening or closing the isolation valve of each cyclone, opening a valve in case the pressure exceeds a
limit value, or closing a valve in case the pressure falls below the limit value defined for such purposes.

For this purpose, the control logic to be implemented is to use of the CL30 block of the AAPL library,
which is capable of commanding the opening or closing of up to 30 power valves of a cyclone battery,
depending on the value of the quantity of cyclones that are required. Before this Set Point of number of
cyclones required for operation, the CL30 block will keep the number of cyclones open required,
automatically replacing those cyclones that cannot continue operating (cyclones with problems with the
actuation of their insulation valve, or that have been moved to maintenance for repair).

For more details of the control scheme considered to control the cyclone cluster 3340-CY-101, see
document Anglo-American, AGS 69, "Process Control - Control Template Specification r1.2a”, sección
4.1, “Controller Configuration Template”, configuración “Controller Configuration Template for the Cyclone
Cluster APC controller”.

Annex B, "Regulatory Control Grinding", sheet 1, shows the control scheme regulatory considered, where
the use of the scheme described in this section is appreciated, applied to the Project.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 96 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

6.8 Engineering Module 2 – 3340CY102

6.8.1 Description – 3340CY102

The following figure shows the elements that make up the 3340CY102 equipment module.
Flush Water

3340-XV-003B 3340-XV-002B
LC
3340001

Emergency Tails
Launder
LT

3340-XV-013
PC
3340-BX-101 SC
FI DI 3340014
3340002
P-1327 3340008 3340009
Tails Launder
PT
3340-XV-002A M
3340-XV-001A FT DT

3340-XV-015
A - AD
3340-PU-101
3340-CY-101
3340-XV-001C 3340-XV-002C
3340-XV-002D FC
3340001

3340-XV-016
PC
SC
FI DI
3340005

3340017
3340003
FAL

FSL

3340010 3340011
Tails Box
3340-XV-003A M
PT
FT DT

3340-XV-017
3340-XV-005 A - AD
3340-PU-102
3340-XV-003C
FAL 3340-CY-102
3340-XV-006 3340006 3340-XV-003D
Crossflow Surge
Tank
FSL

GSW

Figure 18: Blockflow Control Diagram of the 3340CY102 System

6.8.2 Unit of Control Modules – 3340CY102

T1 Control Module
UN CDCPF_Deslamado EM 3340Clasif001 Sub EM 3340CY102

Tag Service
3340-PIT-0017 Deslime Cyclone Cluster 2 pressure transmitter
3340-XV-018 A thru AD Deslime Cyclone Cluster 2 cyclone isolation valve A through AD (total 30 valves)
3340-XV-016A Deslime Cyclone Cluster 2 Underflow Dilution Isolation Valve

Table 53: List of Unit Controls – 3340CY102

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 97 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

6.8.3 Interlocks – 3340CY102

T2 Interlock
3340-XV-018 A Deslime Cyclone Cluster 2 Feed Valves
Tag Description
thru AD (30 in total)
CDCPF_Deslama 3340Clasif00 Sub
UN EM 3340CY102
do 1 EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

No Interlocks

Table 54: List of Interlocks for 3340-XV-018 A though AD

T2 Interlock
Deslime Cyclone Cluster 1 Underflow
Tag 3340-XV-016 A Description
Dilution Valve
CDCPF_Deslama 3340Clasif00 Sub
UN EM 3340CY101
do 1 EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

No Interlocks

Table 55: List of Interlocks for 3340-XV-016 A

Operation Valve 3340-XV-016A must be linked to the operation of the pump 3340-PU-102, so that it opens
when starting the pump, and closes 300 seconds after the pump stops.

6.8.4 Alarms and Process Setpoints – 3340CY102

T3 Alarms and Process Setpoints

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 98 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

UN CDCPF_Deslamado EM 3340Clasif001 Sub EM 3340CY102


High Low
Tag Description Range Unit SP HYS High Low
High Low
3340-PIT- Deslime Cyclone Cluster 2 Feed
0017 0 - 1000 KPa 150 103 83
Pressure Transmitter

Table 56: Alarms and Process Setpoint 3340CY102

Note

1) Low pressure Cyclone cluster feed pressure alarms must be inhibited if the pump 3340-PU-102 is not
running.

6.8.5 Binary State Messages – 3340CY102

T4 Binary State Messages


CDCPF_Deslamad
UN EM 3340Clasif001 Sub EM 3340CY102
o
Tag Service OFF ON QC
3340-ZSO- Deslime Cyclone Cluster 2 underflow flush × Note 2
016A water
3340-ZSC- Deslime Cyclone Cluster 2 underflow flush × Note 1
016A water

Table 57: Binary State Messages for 3340CY102

Note

1) Condition must alarm, if valve is not open and pump 3340-PU-102 running for more than 10 seconds.

2) Condition must alarm, if valve is not closed and pump 3340-PU-102 running for more than 10 seconds.

6.8.6 Regulatory Control Loops – 3340CY102

T5 Regulatory Control Loops


UN CDCPF_Deslamado EM 3340Clasif001 Sub EM 3340CY102
Tag Description Range Unit MV Unit Range Range Conditions MV
MV PV/SP PV SP
0 - 30 # cyclones KPa 80 - 3340PU102.!R
1202 un OR
Deslime Cyclone Cluster Pressure (3340PU102.R
3340-PIC-017
Controller UN &
APC_CY102-
ON

Table 58: Regulatory Control Loops for 3340-PIC-017

2
Expected setpoint 100KPa

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 99 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The control loop 3340-PIC-017, corresponds to a Rule-based Controller, the which will enter into
operations when the APC Controller that controls the operation of the Cyclone Battery is not operational.

Tabulated below are the rules for the operation of the intervening block.

ID Condition Action
1. 3340-PIT-017 > HTH Increase by one (1) N° Cyclones.
2. 3340-PIT-017 < LTH Decrease by one (1) N° Cyclones.
Where:

PV1: 3340-PIT-017

PV1.HTH = 103 KPa

PV1.LTH = 83KPa

Selection of the valves to open / close in the cluster based upon the longest open time.

The Intervening Block will be evaluated 1 time every 60 seconds, in order to update (increase or
decrease), the number of Cyclones required to achieve an adequate Classification of the mineral. The
Controller based on the Controller block, tag 3340-PIC-101, will work in conjunction with the Advanced
Control Loop 3340-UIC-101 described in the subsection "Advanced Control Loops", and “Description" of
the EM 3340CY101.

6.8.7 Advanced Control Loops – 3340CY102

T5 Regulatory Control Loops


3340-UIC-014A/
Tag APC Type APC 10
APC-3340-PIC-017A
UN CDCPF_Deslamado EM 3340Clasif001 Sub EM 3340CY102
Tag Description Unit Variable Type Notes
Deslime Cyclone Cluster 2 KPa CV1
3340-PIT-017
Pressure Controller
Hydrocyclone Cluster – Control # MV1 Note 1
3340-KC-
Opening/Cyclone Closure cyclone
017.RSP
s

Note:

1) The 3340KC017 controller corresponds to the Opening and Closing Control block of Cyclones (CL30).
The cyclone cluster has thirty (30) cyclones in total, where fifteen (15) cyclones (LLIM1) will be the
minimum of devices that will be able to operate, while Twenty-four (24) cyclones (HLIM1), will be a
maximum of devices that can operate. On the other hand, six (6) Cyclones will be available in Stand
By condition, for replace any unit in case of failure. Block CL24 will be activated with the operating
status of the 3340-PU-102 pump.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 100 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

6.8.8 Description – 3340CY102

The objective of the cyclone cluster 3340-CY-102 is to classify the mineral received by the CPF, in order
to differentiate it between mineral that contains a recoverable grade and the smaller size fractions that
can be discarded.

The coarse material, will be obtained through the spigot underflow of the cyclones, while the fines
material will overflow the cyclone and report to tailings. The cyclone cluster feed pressure is controlled by
opening or closing the isolation valve of each cyclone, opening a valve in case the pressure exceeds a
limit value, or closing a valve in case the pressure falls below the limit value defined for such purposes.

For this purpose, the control logic to be implemented is to use of the CL30 block of the AAPL library,
which can command the opening or closing of up to 30 power valves of a cyclone battery, depending on
the value of the quantity of cyclones that are required. Before this Set Point of number of cyclones
required for operation, the CL30 block will keep the number of cyclones open required, automatically
replacing those cyclones that cannot continue operating (cyclones with problems with the actuation of
their insulation valve, or that have been moved to maintenance for repair).

For more details of the control scheme considered to control the cyclone cluster 3340-CY-102, see
document Anglo-American, AGS 69, "Process Control - Control Template Specification r1.2a”, sección
4.1, “Controller Configuration Template”, configuración “Controller Configuration Template for the Cyclone
Cluster APC controller”.

Annex B, "Regulatory Control Grinding", sheet 1, shows the control scheme regulatory considered, where
the use of the scheme described in this section is appreciated, applied to the Project.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 101 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

7.0 UNIDAD: SFCPF_ALIMFLUJOCRUZADO

Refer to:
MQ14 - 08 - DR - 3340 - PD1056 Crossflow Feed Tank
MQ15-718-TE-3340-IN0101 Vendor Weir Large Slurry Pump Control Philosophy
MQ15-722-DC-3340-IN0001 Vendor Agitator Control Philosophy

A block flow control diagram is depicted below for the SFCPF_AlimFlujoCruzado system.
Flush Water

LC
3340032
Make-Up Water

3340 – LCV - 032


Deslime Cyclone 3340PU185
U/Flow Combined

3340-XV- 021B

Vendor
Package
M
Tails Launder
FC
TS LT
3340027
3340-XV- 039
3340DB103 Crossflow 1
SC
FI DI
3340-XV- 038A
3340021
3340027 3340028
Crossflow 2
3340-TK-101 3340-XV- 021A PT 3340-XV- 038B
M
FT DT
3340-AG-101
Crossflow 3
3340-XV- 038C
3340-PU-185 P-1387
FAL
3340-XV- 021C Vendor Package 3340-DB-103 Crossflow 4
3340024 3340-XV- 021D 3340-XV- 038D
3340-XV- 024
FSL FC
3340029 Crossflow 5
3340-XV- 038E
SC
FI DI
3340022
3340029 3340030
3340-XV- 022B Crossflow 6
3340DB104
3340-XV- 036A
3340-XV- 022A M
FT DT

Crossflow 7
PT 3340-XV- 036B
3340-PU-186
3340-XV- 022C Crossflow 8
FAL Vendor Package
3340-XV- 025 3340025 3340-XV- 022D 3340-XV- 036C

FSL 3340-DB-104 Crossflow 9


GSW 3340-XV- 036D

3340PU186 P-1389
Crossflow 10
3340-XV- 036E

Figure 19: Blockflow Control Diagram of SFCPF_AlimFlujoCruzado System

The above control unit is broken into five engineering modules and no sub-modules:
- 3340PU185 (Crossflow Feed Pump 1)
- 3340PU186 (Crossflow Feed Pump 2)
- 3340DB103 (Crossflow Distributor 1)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 102 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

- 3340DB104 (Crossflow Distributor 2)


- 3340PU198 (Deslime Cyclone Spillage Pump)

7.0.1 Modules of Control SFCPF_AlimFlujoCruzado

The Surge Tank and Surge Tank Agitator require certain controls.

T1 Control Module
UN SFCPF_AlimFlujoCruzado EM Sub EM

Tag Service
3340-LIT-033 Level Indicator Transmitter
3340-LCV-032 Level Control Valve, tank 3340-TK-101
3340-XV-039 Flush water to tank 3340-TK-101
3340-AG-101-LU1HE1 Crossflow Feed Surge Tank Agitator Lubrication Oil Heater
3340-TS-034 Temperature Switch Agitator 3340-AG-101
3340-AG-101 Crossflow Feed Surge Tank Agitator

Table 59: List of Modules of Control for SFCPF_AlimFlujoCruzado

7.0.2 Interlocks – SFCPF_AlimFlujoCruzado

T2 Interlock
Tag 3340-LCV-032 Description Level Control Valve, tank 3340-TK-101
SFCPF_AlimFlujo Sub
UN EM
Cruzado EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 60: List of Interlocks for 3340-LCV-032

T2 Interlock
Tag 3340-XV-039 Description Flush water to tank 3340-TK-101

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 103 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

SFCPF_AlimFlujo Sub
UN EM
Cruzado EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
Crossflow Feed Tank level (3340-LIT-
3340-LIT-033 ≠ Low 033) is not Low Low
Low AND
AND Crossflow Feed Tank Agitator (3340 × P
3340 – AG – 101 not – AG – 101) is not running
running then
Flush Valve (3340-XV-039) must
open
IF
3340-LIT-033 = Low Crossflow Feed Tank level is Low for
AND a delay time after reducing both
3340-FIC-027 = crossflow feed pumps flow setpoints Delay time
× P
setpoint minimum to minimum 120s
3340-FIC-029 = then
setpoint minimum Flush Valve (3340-XV-039) must
open

Table 61: List of Interlocks for 3340-XV-039

T2 Interlock
3340-AG-101- Crossflow Feed Surge Tank Agitator Lube
Tag Description
LU1HE1 Heater
SFCPF_AlimFlujo Sub
UN EM
Cruzado EM
Interlock
Motor Type DOL Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Lube Oil Temperature (3340-TS-034)


is Low
3340-TS-034 = Low ×
Switch on Lube Oil Heater 3340 – AG
– 101 – LU1HE1
Lube Oil Temperature (3340-TS-034) Delay 10
3340-TS-034 ≠ Low ×
is not Low seconds

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 104 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Switch off Lube Oil Heater 3340 – AG


– 101 – LU1HE1
Vendor interlocks as specified in Agitator control philosophy. MQ15-722-DC-3340-IN0001

Table 62: List of Interlocks for 3340 – AG – 101 – LU1HE1

T2 Interlock
Tag 3340-AG-101 Description Crossflow Feed Surge Tank Agitator
SFCPF_AlimFlujo Sub
UN EM
Cruzado EM
Interlock
Motor Type DOL Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the Crossflow Feed Tank level


(3340-LIT-033) is Low Low for a Delay time
3340-LIT-033 ×
delay time, the agitator must be 5 seconds
stopped.
3340-TS-034 = Low If the agitator lubrication oil
AND temperature is Low and the agitator is
×
3340-AG-101 is not not running, the agitator may not be
running started.
Vendor interlocks as specified in Agitator control philosophy MQ15-722-DC-3340-IN0001

Table 63: List of Interlocks for 3340 – AG – 101

If the lubrication oil temperature is low while running, the agitator is not stopped.

7.0.3 Alarms and Process Setpoints – SFCPF_AlimFlujoCruzado

T3 Alarms and Process Setpoints


UN SFCPF_AlimFlujoCruzado EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-LIT-033 Crossflow Feed Surge Tank


0 - 100 % 95 30 13 3
Level Transmitter

Table 64: Alarms and Process Setpoint 3340-TK-101

3
Low Low level based on 1500mm slurry level above tank bottom

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 105 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T3 Alarms and Process Setpoints


UN SFCPF_AlimFlujoCruzado EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-TS-034 Agitator Lube Oil Temperature


Refer to vendor functional specification
Switch

Table 65: Alarms and Process Setpoint 3340-AG-101

7.0.4 Binary State Messages – SFCPF_AlimFlujoCruzado

There are no binary state messages for this section


7.0.5 Regulatory Control Loops – SFCPF_AlimFlujoCruzado

T5 Regulatory Control Loops


UN SFCPF_AlimFlujoCruzado EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 - 100 30 - 95 Expected
3340-LIC-033 Crossflow Feed Tank Level Controller
setpoint 50%

Table 66: Regulatory Control Loops for 3340 - TK – 101

The agitator lubrication oil temperature is controlled via a batch on-off process.
In the event that the temperature 3340-TS-034 is Low, the lubrication oil heater 3340-AG-101-
LU1HE1 switches on. The heater will switch off if the temperature is not Low. There is a 10 second
delay time to switch the heater on and off.
7.0.6 Advanced Control Loops – SFCPF_AlimFlujoCruzado

There are no advanced control loops for this section


7.0.7 Description – SFCPF_AlimFlujoCruzado

The Crossflow Feed Surge Tank (3340 – TK – 101) recombines the two deslime cyclone underflow streams
and provides a buffer surge capacity for the material while it is diluted before being pumped at a controlled
rate to the two Crossflow Distributors (3340 – DB – 103 / 104).
The level in the Crossflow Feed Surge Tank (3340-LIT-033) is controlled by adjusting the tanks level control
valve (3340-LCV-032) to a selected setpoint.
Flush water is also injected into the surge tank by opening the Flush Water valve (3340-XV-039) in the
following instances:
 Should the agitator (3340 – AG – 101) stop, flush water is added to aid the temporary fluidisation
of solids from the base of the tank. In such cases, the flush water valve should remain open even
if the tank overflows;
 Should the Surge Tank operate with a Low level limit for a specified time.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 106 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The Crossflow Feed Surge Tank Agitator (3340 – AG – 101) is a package item and all process control
loops, alarms and interlocks specified within the vendor control philosophy document shall be followed.
The agitator has a lubrication oil system for its gearbox, with a drive-less lubrication oil pump powered from
the rotating shaft that recirculates oil through the gearbox. Should the oil temperature (3340-TS-034) reduce
to a minimum value specified by the vendor, the oil heater will switch on immediately. Prior to starting the
agitator, the temperature cannot be on a Low level.
Unless the Surge Tank level is Low Low, it is imperative that the agitator is never stopped while solids are
contained within the tank, even during plant shutdown events. The agitator will stop if the slurry level in the
surge tank (3340-LIT-033) reaches a Low Low limit. Prior to restarting the agitator, the operator shall
confirm its blades are free of any settled sediment.

7.1 Engineering Module– 3340PU185

7.1.1 Description – 3340PU185

The following figure shows the elements that make up the 3340PU185 equipment module.
Flush Water

LC
3340032
Make-Up Water

3340 – LCV - 032


Deslime Cyclone 3340PU185
U/Flow Combined

3340-XV- 021B

Vendor
Package
M
Tails Launder
FC
TS LT
3340027
3340-XV- 039
Crossflow 1
SC
FI DI
3340-XV- 038A
3340021
3340027 3340028
Crossflow 2
3340-TK-101 3340-XV- 021A PT 3340-XV- 038B
M
FT DT
3340-AG-101
Crossflow 3
3340-XV- 038C
3340-PU-185
FAL
3340-XV- 021C Vendor Package 3340-DB-103 Crossflow 4
3340024 3340-XV- 021D 3340-XV- 038D
3340-XV- 024
FSL FC
3340029 Crossflow 5
3340-XV- 038E
SC
FI DI
3340022
3340029 3340030
3340-XV- 022B Crossflow 6
3340-XV- 036A
3340-XV- 022A M
FT DT

Crossflow 7
PT 3340-XV- 036B
3340-PU-186
3340-XV- 022C Crossflow 8
FAL Vendor Package
3340-XV- 025 3340025 3340-XV- 022D 3340-XV- 036C

FSL 3340-DB-104 Crossflow 9


GSW 3340-XV- 036D

Crossflow 10
3340-XV- 036E

Figure 20: Blockflow Control Diagram of the 3340PU185 System

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 107 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The Crossflow Feed Pump (3340 – PU – 185) pumps re-pulped deslime cyclone underflow to the Crossflow
Distributor (3340 – DB – 103) at a controlled flowrate.
The Crossflow Feed Pump slurry density is measured by densitometer (3340-DIT-028). Their nuclear
source is isolated by an actuated shutter gate (3340-DX-0028). The slurry flowrate is measured by flow
transmitter (3340-FIT-027) and compared to the pumps setpoint. The setpoint is calculated upon the total
number of open Crossflow Separator Feed Valves (3340-XV- 038A-E) on the distributor.
By combining the flow transmitter and densitometer readings, a totalized mass flow in the Crossflow
Separator feed pipeline will be calculated based upon the following formulae:
𝑆𝐺
𝑇 = 𝑉𝑝 (𝑑𝑝 − 1) ×
(𝑆𝐺 − 1
Where: T = Dry Solids Mass [tph]
Vp = Volumetric Flowrate [m3/hr] (3340-FIT-027)
Dp = Slurry density [t/m3] (3340-DIT-028).
SG = Solids Specific Gravity = 2.68 t/m3
Total dry mass feed to the Crossflow Separators is the sum of the two pumps dry mass flowrates summed
only when the respective pumps are running.
Solids mass pumped to the Crossflow Separators will be totalized on an hour, shift, day and monthly basis
and will be visible to the control room operator. This information forms the basis of the reagent and flocculant
dosage calculations.
The Crossflow Feed Pumps are a vendor package and all control loops, alarms and interlocks specified in
the vendor control philosophy document shall be applied.

7.1.2 Unit of Control Modules – 3340PU185

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SFCPF_AlimFlujoCruzado EM 3340PU185 Sub EM

Tag Service
3340-XV-021A Suction valve – pump 3340-PU-185
3340-XV-021B Suction Flush Water Valve - pump 3340-PU-185
3340-XV-021C Suction Drain Valve - pump 3340-PU-185
3340-XV-021D Discharge Drain valve - pump 3340-PU-185
3340-FSL-024 Gland Seal Water Flow switch
3340-XV-024 Gland Seal Water Valve - pump 3340-PU-185
3340-PU-185 Crossflow Feed Pump 1
3340-PU-185-MO1HE1 Crossflow Feed Pump 1 Motor Heater 1
3340-PU-185-MO1FA1 Crossflow Feed Pump 1 Motor Fan 1

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 108 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PU-185-MO1FA2 Crossflow Feed Pump 1 Motor Fan 2


3340-PU-185-LU1FA1 Crossflow Feed Pump 1 Gearbox Cooling Fan
3340-PU-185-LU1HE1 Crossflow Feed Pump 1 Gearbox Oil Heater 1
3340-PU-185-LU1HE2 Crossflow Feed Pump 1 Gearbox Oil Heater 2
3340-VT-021C1/2 VIBRATION TRANSMITTER 3340-PU-185
3340-VT-021C3/4 VIBRATION TRANSMITTER 3340-PU-185
3340-TT-021B1/2 TEMPERATURE TRANSMITTER 3340-PU-185
3340-TT-021A2 TEMPERATURE TRANSMITTER 3340-PU-185
3340-TT-021B3/4 TEMPERATURE TRANSMITTER 3340-PU-185
3340-TT-021A1 TEMPERATURE TRANSMITTER 3340-PU-185
3340-VT-021B1/2 VIBRATION TRANSMITTER 3340-PU-185
3340-VT-021B3/4 VIBRATION TRANSMITTER 3340-PU-185
3340-TT-021B5 TEMPERATURE TRANSMITTER 3340-PU-185
3340-LSL-021B LEVEL SWITCH LOW 3340-PU-185
3340-PSL-021B PRESSURE SWITCH LOW 3340-PU-185
3340-DIT-028 Slurry Densitometer to Distributor #1 3340-DB-103
3340-DX-028 Densitometer Nuclear Source Distributor #1 3340-DB-103
3340-FIT-027 Flow Transmitter to Distributor #1 3340-DB-103

Table 67: List of Unit Controls – 3340PU185

7.1.3 Interlocks – 3340PU185

T2 Interlock
Tag 3340-XV-021A Description Suction valve – pump 3340-PU-185
SFCPF_AlimFlujo Sub
UN EM 3340PU185
Cruzado EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-021C.OP Suction drain valve open


OR OR ×
3340-XV-021C.OPNG Suction drain valve opening
3340-PU-185.!RUN Pump Stopped
AND AND Time Delay
×
(3340-XV-021A.OP Suction Valve Open OR Opening 180 seconds
OR

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 109 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-021A.OPNG)

Table 68: List of Interlocks for 3340-XV-021A

T2 Interlock
Suction Flush Water Valve - pump 3340-PU-
Tag 3340-XV-021B Description
185
SFCPF_AlimFlujo Sub
UN EM 3340PU185
Cruzado EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 69: List of Interlocks for 3340-XV-021B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Suction Drain Water Valve - pump 3340-PU-
Tag 3340-XV-021C Description
185
SFCPF_AlimFlujo Sub
UN EM 3340PU185
Cruzado EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 70: List of Interlocks for 3340-XV-021C

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 110 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340 – PU – 185 Description Crossflow Feed Pump 1
SFCPF_AlimFlujo Sub
UN EM 3340PU185
Cruzado EM
Interlock
Motor Type VFD (Multiple) Intlck_3340BB_SL_01
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Vendor interlocks as specified in equipment control philosophy MQ15-718-TE-3340-IN0101

3340-XV-024 !OP ×
If gland seal water valve not open and
AND Note 1
3340-PU-185 is running
3340-PU-185.MO1.Run
3340-FSL-024.ACT Flow switch (3340-FSL-024) has a low ×
Time Delay
AND flow alarm for a time delay and 3340-PU-
300 seconds
3340-PU-185-MO1.Run 185 is running
Flow switch (3340-FSL-024) has a low
3340-FSL-024.ACT ×
flow alarm
3340-XV-021A CL ×
Suction valve (3340-XV-021A)
OR CLN Time Delay
Is closed or closing and 3340-PU-185 is
AND 10 seconds
running for a time delay
3340-PU-185-MO1.Run
3340-XV-021C OP OR Suction drain valve (3340-XV-021C) is × Debounce
OPN open or opening
× Time Delay
The level of the Crossflow Feed Surge
3340-LIT-033.LL 300 seconds
Tank (3340-LIT-033) is Low Low
Note 2
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-021D OP OR Discharge drain valve (3340-XV-021D) is × Debounce
OPN open or opening
3340-DB- ×
Number of Crossflow Feed Isolation
103.V_OPEN_HLIM
Valves available < 3
(3340-XV-038 A thru E)
3340-FIT-027.LL AND ×
Slurry flowrate is Low Low and pump is Time Delay
3340-PU-185-
running 600 seconds
MO1.RUN
Instrument Air Pressure (3340-PIT-675) is × Time Delay
3340-PIT-675.LL
Low Low for a time delay 10 seconds
Either ×
3340-PIT-670.LL
3340-PIT-670
OR
OR
3340-PIT-671.LL Time Delay
3340-PIT-671
OR 60 seconds
OR
3340-PIT-678.LL
3340-PIT-678
is Low Low for a time delay
CPF Make-Up Water Pressure 3720-PIT- × Time Delay
3720-PIT-116.LL
116 is Low Low for a time delay 180 seconds
Fluidisation Water pressure (3340-PIT- × Delay time
3340-PIT-647.LL
647) is low low for a delay time 60 seconds
Flush Water Pressure (3340-PIT-648) is × Delay time 5
3340-PIT-648.LL
not low low for a delay time minutes
3340-XV-303A CL All thickener feed valves are closed or × Delay time 3
OR CLN closing minutes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 111 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

AND (3340-XV-303A
3340-XV-303B CL AND
OR CLN 3340-XV-303B
AND AND
3340-XV-303C CL 3340-XV-303C)
OR CLN and 3340-PU-185 is running for a time
AND delay
3340-PU-185-MO1.Run
Gland seal water pressure (3340-PIT-656) × Delay time
3340-PIT-656.LL
is Low Low for a delay time 60 seconds
Boosted gland seal water pressure (3340- × Delay time
3340-PIT-659.LL
PIT-659) is Low Low for a delay time 60 seconds

Table 71: List of Interlocks for 3340 – PU - 185

Note 1 On stopping 3340 – PU – 185, its gearbox lubrication cooling and heating system
may continue to run. Refer to vendor functional specification
Note 2 Stop either 3340 – PU – 185 or 3340 – PU – 186
Depending which has:
a) The least number of Crossflow Feed valves (3340-XV-036A-E / 038A-E) open,
or if even
b) The longest pump run time

T2 Interlock
Crossflow Feed Pump 1 Discharge Drain
Tag 3340-XV-021D Description
Valve
SFCPF_AlimFlujo Sub
UN EM 3340PU185
Cruzado EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 72: List of Interlocks for 3340-XV-021D

T2 Interlock
Crossflow Feed Pump 1 Densitometer
Tag 3340-DX-028 Description
Nuclear Source Isolation Shutter

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 112 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

SFCPF_AlimFlujo Sub
UN EM 3340PU185
Cruzado EM
Interlock Intlck_OBTURADOR_DENSI
Motor Type
Type METRO_01

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the pump 3340 – PU – 185 is not


3340-PU-185.!RUN ×
running

Table 73: List of Interlocks for 3340-DX-028

T2 Interlock
Crossflow Feed Pump 1 Gland Seal Water
Tag 3340-XV-024 Description
Valve
SFCPF_AlimFlujo Sub
UN EM 3340PU185
Cruzado EM
Fail Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the pump 3340 – PU – 185 is not


3340-PU-185.!RUN ×
running

Table 74: List of Interlocks for 3340-XV-024

7.1.4 Alarms and Process Setpoints – 3340PU185

T3 Alarms and Process Setpoints


UN SFCPF_AlimFlujoCruzado EM 3340PU185 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Refer to vendor control philosophy for pump specific Alarms and Process Setpoints. MQ15-718-TE-3340-IN0101
3340-FIT-027 Crossflow Feed Pump Flowmeter 0 - 5000 m3/hr 3630 2550
3340-DIT-028 Crossflow Feed Pump
1.0 – 2.0 t/m3 1.34
densitometer
3340-FSL-024 Crossflow Feed Pump Gland
0 - 15 m3/hr 7.92
Seal Water Flow switch

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 113 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 75: Alarms and Process Setpoint 3340PU185

The alarms associated with the Density transmitter, as well as the flow measurement should be
inhibited when pump 3340-PU-185 is not running.
7.1.5 Binary Messages – 3340PU185

T4 Binary State Messages


UN SFCPF_AlimFlujoCruzado EM 3340PU185 Sub EM
Tag Description OFF ON

3340-ZSC-028 LINE RADIOACTIVE SOURCE


× Note 2
CYCLONE 3340-DB-103 CLOSED
3340-ZSO-028 LINE RADIOACTIVE SOURCE
× Note 1
CYCLONE 3340-DB-103 OPEN

Table 76: Binary State Messages 3340PU185

Note:
1) Condition should alarm, if the valve is open 5 seconds after the pump 3340-PU-185 has
stopped.
2) Condition should alarm, if the valve is closed, 5 seconds after the pump 3340-PU-185 is
running. If this condition occurs, calculation of the mass flowrate and average value % of
solids should not occur.
3) An alarm should be provided when a nuclear density meter reading (tag 3340-DIT-028)
provides a difference in measured value greater than 10%, under normal operating
conditions. Alarm will not be triggered when only one pump is operating, when the pump
is under start-up conditions.
7.1.6 Regulatory Control Loops – 3340PU185

T5 Regulatory Control Loops


UN SFCPF_AlimFlujoCruzado EM 3340PU185 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
77.5 - % m3/hr 0 - 5000 2575 - Expected
100 3603 setpoint
3340-FIC-027 Crossflow Feed Pump Flow controller m3/hr 2975m3/hr
Note 1
Note 2

Table 77: Regulatory Control Loops for 3340-FIC-027

If the Crossflow Feed Tank does not have any level warnings and all five Crossflow Separator Feed Isolation
valves per distributor are open, the flow rate setpoint is 2,975m3/hr (595m3/hr / crossflow).
If either of the following should occur, the flowrate setpoint may gradually increase until the condition is
removed or to a maximum of 3600m3/hr (720m3/hr / crossflow):
 The slurry density is above its high limit for 30 seconds; or

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 114 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

 The Crossflow Feed Tank level (3340-LIT-033) is High for 30 seconds.


Only if one or more Crossflow Separator Feed valves are closed, the maximum flowrate permissible per
Crossflow Separator shall allowed to increase to a maximum of 860m3/hr/separator. The pump flowrate
setpoint may not reduce below the minimum flowrate setting specified at 2575 m3/hr for the flow transmitter
to prevent line sedimentation blockages which will occur over time at less than 2550m3/hr. This means that
at least three feed valves on the respective distributor must be open, or else the Crossflow Feed Pump will
stop after a specified time.
Note 1 Setpoint without any upset conditions is 595m3/hr per Crossflow Separator available (i.e., feed
valve open).
Setpoint 720m3/hr/Crossflow (max 3600m3/hr) if Surge Tank level or slurry density is high
Setpoint 2880m3/hr (720m3/hr /crossflow) if four Crossflow Separators available.
If the Crossflow Feed Tank level (3340-LIT-033) is Low after the pump speed setpoints have been reduced
to a minimum rate of 2575 m3/hr, the flush water valve (3340-XV-039) shall be opened after a specified
time, If the level remains low for a further specified time, one Crossflow Feed pump with the longest
historical runtime shall stop.
Note 2: Controller will be disabled (tracking action), if pump is stopped

7.1.7 Advanced Control Loops – 3340PU185

Not applicable

7.1.8 Sequence Description – 3340PU185

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. The pump start sequence 3340-PU-185, shall follow the following steps:
TSQST Start Sequence Table
UN SFCPF_AlimFlujoCruzado EM 3340PU185 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Suction drain Valve
3340-XV-021C 2 60
1. Close and Closed
3340-XV-021D seconds seconds
Discharge drain valve
(Open &
Low Flow
2 60
2. Open 3340-XV-024 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
2 220
3. Open 3340-XV-021B Suction Valve. Open
seconds seconds
3340-PU-185-MO1HE1
3340-PU-185-MO1FA1
Start Pump lubrication
3340-PU-185-MO1FA2 10 120
4. Start sequences. Refer to vendor
3340-PU-185-LU1FA1 seconds seconds
functional specification.
3340-PU-185-LU1HE1
3340-PU-185-LU1HE2
Start pump. Refer to vendor 10 60
5. Start 3340-PU-185.MO1 Working
functional specification. seconds seconds

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 115 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 78: Start Sequence 3340PU185

Reference should be made to the Crossflow Feed Pump (3340-PU-185) functional specification
for its start/stop sequence of the lubrication system and monitoring requirements. MQ15-718-TE-
3340-IN0101
The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-185 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-185-MO1 stopped
The pump stop sequence 3340-PU-185, shall follow the following steps:
TSQST Stop Sequence Table
UN SFCPF_AlimFlujoCruzado EM 3340PU185 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-185.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
Stop pump.
20 60
2. Stop 3340-PU-185.MO1 Refer to vendor functional Stopped
seconds seconds
specification
2 180
3. Close 3340-XV-021A Suction Valve. Closed
seconds seconds
2 60
4. Open 3340-XV-021D Discharge Drain Valve Opened
seconds seconds
2 60
5. Open 3340-XV-021C Suction Drain valve Opened
seconds seconds
2 20
6. Close 3340-XV-024 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-021B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-021B Closed
valve seconds seconds

Table 79: Stop Sequence 3340PU185

The Shutter of the Nuclear Density Meter (3340-DX-028) will open 5 seconds after the pump
3340-PU-185 is operational. The shutter will close when the pump stops.

7.2 Engineering Module– 3340PU186

7.2.1 Description – 3340PU186

The following figure shows the elements that make up the 3340PU186 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 116 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Flush Water

LC
3340032
Make-Up Water

3340 – LCV - 032


Deslime Cyclone
U/Flow Combined

3340-XV- 021B

Vendor
Package
M
Tails Launder
FC
TS LT
3340027
3340-XV- 039
Crossflow 1
SC
FI DI
3340-XV- 038A
3340021
3340027 3340028
Crossflow 2
3340-TK-101 3340-XV- 021A PT 3340-XV- 038B
M
FT DT
3340-AG-101
Crossflow 3
3340-XV- 038C
3340-PU-185
FAL
3340-XV- 021C Vendor Package 3340-DB-103 Crossflow 4
3340024 3340-XV- 021D 3340-XV- 038D
3340-XV- 024
FSL FC
3340029 Crossflow 5
3340-XV- 038E
SC
FI DI
3340022
3340029 3340030
3340-XV- 022B Crossflow 6
3340-XV- 036A
3340-XV- 022A M
FT DT

Crossflow 7
PT 3340-XV- 036B
3340-PU-186
3340-XV- 022C Crossflow 8
FAL Vendor Package
3340-XV- 025 3340025 3340-XV- 022D 3340-XV- 036C

FSL 3340-DB-104 Crossflow 9


GSW 3340-XV- 036D
3340PU186
Crossflow 10
3340-XV- 036E

Figure 21: Blockflow Control Diagram of the 3340PU186 System

The Crossflow Feed Pump (3340 – PU – 186) pumps re-pulped deslime cyclone underflow to the Crossflow
Distributor (3340 – DB – 104) at a controlled flowrate.
The Crossflow Feed Pump slurry density is measured by densitometer (3340-DIT-030). Their nuclear
source is isolated by an actuated shutter gate (3340-DX-0030). The slurry flowrate is measured by flow
transmitter (3340-FIT-029) and compared to the pumps setpoint. The setpoint is calculated upon the total
number of open Crossflow Separator Feed Valves (3340-XV- 036A-E) on the distributor.
By combining the flow transmitter and densitometer readings, a totalized mass flow in the Crossflow
Separator feed pipeline will be calculated based upon the following formulae:
𝑆𝐺
𝑇 = 𝑉𝑝 (𝑑𝑝 − 1) ×
(𝑆𝐺 − 1
Where: T = Dry Solids Mass [tph]
Vp = Volumetric Flowrate [m3/hr] (3340-FIT-029)
Dp = Slurry density [t/m3] (3340-DIT-030).
SG = Solids Specific Gravity = 2.68 t/m3

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 117 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Total dry mass feed to the Crossflow Separators is the sum of the two pumps dry mass flowrates.
Solids mass pumped to the Crossflow Separators will be totalized on an hour, shift, day and monthly basis
and will be visible to the control room operator. This information forms the basis of the reagent and flocculant
dosage calculations.
The Crossflow Feed Pumps are a vendor package and all control loops, alarms and interlocks specified in
the vendor control philosophy document shall be applied.

7.2.2 Unit of Control Modules – 3340PU186

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SFCPF_AlimFlujoCruzado EM 3340PU185 Sub EM

Tag Service
3340-XV-022A Suction valve – pump 3340-PU-186
3340-XV-022B Suction Flush Water Valve - pump 3340-PU-186
3340-XV-022C Suction Drain Valve - pump 3340-PU-186
3340-XV-022D Discharge Drain valve - pump 3340-PU-186
3340-FSL-025 Gland Seal Water Flow switch
3340-XV-0245 Gland Seal Water Valve - pump 3340-PU-186
3340-PU-186 Crossflow Feed Pump 2
3340-PU-186-MO1HE1 Crossflow Feed Pump 2 Motor Heater 1
3340-PU-186-MO1FA1 Crossflow Feed Pump 2 Motor Fan 1
3340-PU-186-MO1FA2 Crossflow Feed Pump 2 Motor Fan 2
3340-PU-186-LU1FA1 Crossflow Feed Pump 2 Gearbox Cooling Fan
3340-PU-186-LU1HE1 Crossflow Feed Pump 2 Gearbox Oil Heater 1
3340-PU-186-LU1HE2 Crossflow Feed Pump 2 Gearbox Oil Heater 2
3340-VT-022C1/2 VIBRATION TRANSMITTER 3340-PU-186
3340-VT-022C3/4 VIBRATION TRANSMITTER 3340-PU-186
3340-TT-022B1/2 TEMPERATURE TRANSMITTER 3340-PU-186
3340-TT-022A2 TEMPERATURE TRANSMITTER 3340-PU-186
3340-TT-022B3/4 TEMPERATURE TRANSMITTER 3340-PU-186
3340-TT-022A1 TEMPERATURE TRANSMITTER 3340-PU-186
3340-VT-022B1/2 VIBRATION TRANSMITTER 3340-PU-186
3340-VT-022B3/4 VIBRATION TRANSMITTER 3340-PU-186
3340-TT-022B5 TEMPERATURE TRANSMITTER 3340-PU-186
3340-LSL-022B LEVEL SWITCH LOW 3340-PU-186
3340-PSL-022B PRESSURE SWITCH LOW 3340-PU-186

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 118 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-DIT-030 Slurry Densitometer to Distributor #1 3340-DB-104


3340-DX-030 Densitometer Nuclear Source Distributor #1 3340-DB-104
3340-FIT-028 Flow Transmitter to Distributor #1 3340-DB-104

Table 80: List of Unit Controls – 3340PU186

7.2.3 Interlocks – 3340PU186

T2 Interlock
Tag 3340-XV-022A Description Suction valve – pump 3340-PU-186
SFCPF_AlimFlujo Sub
UN EM 3340PU186
Cruzado EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-022C.OP Suction drain valve open


OR OR ×
3340-XV-022C.OPNG Suction drain valve opening
3340-PU-186.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-022A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-022A.OPNG)

Table 81: List of Interlocks for 3340-XV-022A

T2 Interlock
Suction Flush Water Valve - pump 3340-PU-
Tag 3340-XV-022B Description
186
SFCPF_AlimFlujo Sub
UN EM 3340PU186
Cruzado EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 119 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 82: List of Interlocks for 3340-XV-022B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Suction Drain Water Valve - pump 3340-PU-
Tag 3340-XV-022C Description
186
SFCPF_AlimFlujo Sub
UN EM 3340PU186
Cruzado EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 83: List of Interlocks for 3340-XV-022C

T2 Interlock
Tag 3340 – PU – 186 Description Crossflow Feed Pump 2
SFCPF_AlimFlujo Sub
UN EM 3340PU186
Cruzado EM
Interlock
Motor Type VFD (Multiple) Intlck_3340BB_SL_01
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Vendor interlocks as specified in equipment control philosophy MQ15-718-TE-3340-IN0101

3340-XV-025 !OP ×
If gland seal water valve not open and
AND Note 1
3340-PU-186 is running
3340-PU-186.MO1.Run
3340-FSL-025.ACT Flow switch (3340-FSL-025) has a low ×
Time Delay
AND flow alarm for a time delay and 3340-PU-
300 seconds
3340-PU-186-MO1.Run 186 is running
Flow switch (3340-FSL-025) has a low
3340-FSL-025.ACT ×
flow alarm

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 120 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-022A CL ×
Suction valve (3340-XV-022A)
OR CLN Time Delay
Is closed or closing and 3340-PU-186 is
AND 10 seconds
running for a time delay
3340-PU-186-MO1.Run
3340-XV-022C OP OR Suction drain valve (3340-XV-022C) is × Debounce
OPN open or opening
× Time Delay
The level of the Crossflow Feed Surge
3340-LIT-033.LL 300 seconds
Tank (3340-LIT-033) is Low Low
Note 2
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-022D OP OR Discharge drain valve (3340-XV-022D) is × Debounce
OPN open or opening
3340-DB- ×
Number of Crossflow Feed Isolation
104.V_OPEN_HLIM
Valves available < 3
(3340-XV-036 A thru E)
3340-FIT-029.LL AND ×
Slurry flowrate is Low Low and pump is Time Delay
3340-PU-186-
running 600 seconds
MO1.RUN
Instrument Air Pressure (3340-PIT-675) is × Time Delay
3340-PIT-675.LL
Low Low for a time delay 10 seconds
Either ×
3340-PIT-670.LL
3340-PIT-670
OR
OR
3340-PIT-671.LL Time Delay
3340-PIT-671
OR 60 seconds
OR
3340-PIT-678.LL
3340-PIT-678
is Low Low for a time delay
CPF Make-Up Water Pressure 3720-PIT- × Time Delay
3720-PIT-116.LL
116 is Low Low for a time delay 180 seconds
Fluidisation Water pressure (3340-PIT- × Delay time
3340-PIT-647.LL
647) is low low for a delay time 60 seconds
Flush Water Pressure (3340-PIT-648) is × Delay time 5
3340-PIT-648.LL
not low low for a delay time minutes
3340-XV-303A CL ×
All thickener feed valves are closed or
OR CLN
closing
AND
(3340-XV-303A
3340-XV-303B CL
AND
OR CLN Delay time 3
3340-XV-303B
AND minutes
AND
3340-XV-303C CL
3340-XV-303C)
OR CLN
and 3340-PU-185 is running for a time
AND
delay
3340-PU-185-MO1.Run
Gland seal water pressure (3340-PIT-656) × Delay time
3340-PIT-656.LL
is Low Low for a delay time 60 seconds
Boosted gland seal water pressure (3340- × Delay time
3340-PIT-659.LL
PIT-659) is Low Low for a delay time 60 seconds

Table 84: List of Interlocks for 3340 – PU - 186

Note 1 On stopping 3340 – PU – 186, its gearbox lubrication cooling and heating system may
continue to run. Refer to vendor functional specification

Note 2 Stop either 3340 – PU – 186 or 3340 – PU – 185


Depending which has:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 121 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

a) The least number of Crossflow Feed valves (3340-XV-036A-E / 038A-E) open,


or if even
b) The longest pump run time

T2 Interlock
Crossflow Feed Pump 2 Discharge Drain
Tag 3340-XV-021D Description
Valve
SFCPF_AlimFlujo Sub
UN EM 3340PU186
Cruzado EM
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 85: List of Interlocks for 3340-XV-022D

T2 Interlock
Crossflow Feed Pump 2 Densitometer
Tag 3340-DX-030 Description
Nuclear Source Isolation Shutter
SFCPF_AlimFlujo Sub
UN EM 3340PU186
Cruzado EM
Interlock Intlck_OBTURADOR_DENSI
Motor Type
Type METRO_01
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If the pump 3340 – PU – 186 is not


3340-PU-186.!RUN ×
running

Table 86: List of Interlocks for 3340-DX-030

T2 Interlock
Crossflow Feed Pump 2 Gland Seal Water
Tag 3340-XV-025 Description
Valve
SFCPF_AlimFlujo Sub
UN EM 3340PU186
Cruzado EM

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 122 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fail Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the pump 3340 – PU – 186 is not


3340-PU-186.!RUN ×
running

Table 87: List of Interlocks for 3340-XV-025

7.2.4 Alarms and Process Setpoints – 3340PU186

T3 Alarms and Process Setpoints


UN SFCPF_AlimFlujoCruzado EM 3340PU185 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Refer to vendor control philosophy for pump specific Alarms and Process Setpoints MQ15-718-TE-3340-IN0101
3340-FIT-029 Crossflow Feed Pump Flowmeter 0 - 5000 m3/hr 3630 2550
3340-DIT-030 Crossflow Feed Pump
1.0 – 2.0 t/m3 1.34
densitometer
3340-FSL-025 Crossflow Feed Pump Gland
0 - 15 m3/hr 7.92
Seal Water Flow switch

Table 88: Alarms and Process Setpoint 3340PU186

The alarms associated with the Density transmitter, as well as the flow measurement should be
inhibited when pump 3340-PU-186 is not running.
7.2.5 Binary Messages – 3340PU186

T4 Binary State Messages


UN SFCPF_AlimFlujoCruzado EM 3340PU186 Sub EM
Tag Description OFF ON

3340-ZSC-030 LINE RADIOACTIVE SOURCE


× Note 2
CYCLONE 3340-DB-104 CLOSED
3340-ZSO-030 LINE RADIOACTIVE SOURCE
× Note 1
CYCLONE 3340-DB-104 OPEN

Table 89: Binary State Messages 3340PU186

Note:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 123 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

1) Condition should alarm, if the valve is open 5 seconds after the pump 3340-PU-186 has
stopped.
2) Condition should alarm, if the valve is closed, 5 seconds after the pump 3340-PU-186 is
running. If this condition occurs, calculation of the mass flowrate and average value % of
solids should not occur.
3) An alarm should be provided when a nuclear density meter reading (tag 3340-DIT-030)
provides a difference in measured value greater than 10%, under normal operating
conditions. Alarm will not be triggered when only one pump is operating, when the pump
is under start-up conditions.
7.2.6 Regulatory Control Loops – 3340PU186

T5 Regulatory Control Loops


UN SFCPF_AlimFlujoCruzado EM 3340PU185 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
77.5 - % m3/hr 0 - 5000 2575 - Expected
100 3603 setpoint
3340-FIC-029 Crossflow Feed Pump Flow controller m3/hr 2975m3/hr
Note 1
Note 2

Table 90: Regulatory Control Loops for 3340-FIC-029

If the Crossflow Feed Tank does not have any level warnings and all five Crossflow Separator Feed Isolation
valves per distributor are open, the flow rate setpoint is 2,975m3/hr (595m3/hr / crossflow).
If either of the following should occur, the flowrate setpoint may gradually increase until the condition is
removed or to a maximum of 3600m3/hr (720m3/hr / crossflow):
 The slurry density is above its high limit for 30 seconds; or
 The Crossflow Feed Tank level (3340-LIT-033) is High for 30 seconds.
Only if one or more Crossflow Separator Feed valves are closed, the maximum flowrate permissible per
Crossflow Separator shall allowed to increase to a maximum of 860m3/hr/separator. The pump flowrate
setpoint may not reduce below the minimum flowrate setting specified at 2575 m3/hr for the flow transmitter
to prevent line sedimentation blockages which will occur over time at less than 2550m3/hr. This means that
at least three feed valves on the respective distributor must be open, or else the Crossflow Feed Pump will
stop after a specified time.
Note 1 Setpoint without any upset conditions is 595m3/hr per Crossflow Separator available (i.e., feed
valve open).
Setpoint 720m3/hr/Crossflow (max 3600m3/hr) if Surge Tank level or slurry density is high
Setpoint 2880m3/hr (720m3/hr /crossflow) if four Crossflow Separators available.
If the Crossflow Feed Tank level (3340-LIT-033) is Low after the pump speed setpoints have been reduced
to a minimum rate of 2575 m3/hr, the flush water valve (3340-XV-039) shall be opened after a specified
time, If the level remains low for a further specified time, one Crossflow Feed pump with the longest
historical runtime shall stop.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 124 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note 2: Controller will be disabled (tracking action), if pump is stopped

7.2.7 Advanced Control Loops – 3340PU186

Not applicable

7.2.8 Sequence Description – 3340PU186

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. The pump start sequence 3340-PU-186, shall follow the following steps:
TSQST Start Sequence Table
UN SFCPF_AlimFlujoCruzado EM 3340PU186 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Suction drain Valve
3340-XV-022C 2 60
1. Close and Closed
3340-XV-022D seconds seconds
Discharge drain valve
(Open &
Low Flow
2 60
2. Open 3340-XV-025 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
2 220
3. Open 3340-XV-022B Suction Valve. Open
seconds seconds
3340-PU-186-MO1HE1
3340-PU-186-MO1FA1
Start Pump lubrication
3340-PU-186-MO1FA2 10 120
4. Start sequences. Refer to vendor
3340-PU-186-LU1FA1 seconds seconds
functional specification.
3340-PU-186-LU1HE1
3340-PU-186-LU1HE2
Start pump. Refer to vendor 10 60
5. Start 3340-PU-186.MO1 Working
functional specification. seconds seconds

Table 91: Start Sequence 3340PU186

Reference should be made to the Crossflow Feed Pump (3340-PU-186) functional specification
for its start/stop sequence of the lubrication system and monitoring requirements. MQ15-718-TE-
3340-IN0101
The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-186 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-186-MO1 stopped
The pump stop sequence 3340-PU-186, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 125 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN SFCPF_AlimFlujoCruzado EM 3340PU186 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-186.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
Stop pump.
20 60
2. Stop 3340-PU-186.MO1 Refer to vendor functional Stopped
seconds seconds
specification
2 180
3. Close 3340-XV-022A Suction Valve. Closed
seconds seconds
2 60
4. Open 3340-XV-022D Discharge Drain Valve Opened
seconds seconds
2 60
5. Open 3340-XV-022C Suction Drain valve Opened
seconds seconds
2 20
6. Close 3340-XV-025 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-022B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-022B Closed
valve seconds seconds

Table 92: Stop Sequence 3340PU186

The Shutter of the Nuclear Density Meter (3340-DX-030) will open 5 seconds after the pump
3340-PU-186 is operational. The shutter will close when the pump stops.
7.3 Engineering Module – 3340DB103

7.3.1 Description – 3340DB103

The following figure shows the elements that make up the 3340DB103 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 126 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Flush Water

LC
3340032
Make-Up Water

3340 – LCV - 032


Deslime Cyclone
U/Flow Combined

3340-XV- 021B

Vendor
Package
M
Tails Launder
FC
TS LT
3340027
3340-XV- 039
Crossflow 1
SC
FI DI
3340-XV- 038A
3340021
3340027 3340028
Crossflow 2
3340-TK-101 3340-XV- 021A PT 3340-XV- 038B
M
FT DT
3340-AG-101
Crossflow 3
3340-XV- 038C
3340-PU-185
FAL
3340-XV- 021C Vendor Package 3340-DB-103 Crossflow 4
3340024 3340-XV- 021D 3340-XV- 038D
3340-XV- 024
FSL FC
3340029 3340DB103 Crossflow 5
3340-XV- 038E
SC
FI DI
3340022
3340029 3340030
3340-XV- 022B Crossflow 6
3340-XV- 036A
3340-XV- 022A M
FT DT

Crossflow 7
PT 3340-XV- 036B
3340-PU-186
3340-XV- 022C Crossflow 8
FAL Vendor Package
3340-XV- 025 3340025 3340-XV- 022D 3340-XV- 036C

FSL 3340-DB-104 Crossflow 9


GSW 3340-XV- 036D

Crossflow 10
3340-XV- 036E

Figure 22: Blockflow Control Diagram of the 3340DB103 System

7.3.2 Unit of Control Modules – 3340DB103

T1 Control Module
UN SFCPF_AlimFlujoCruzado EM 3340DB103 Sub EM

Tag Service
3340-PIT-037 Crossflow Feed Distributor 1 pressure transmitter

Table 93: List of Unit Controls – 3340DB103

7.3.3 Interlocks – 3340DB103

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 127 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

7.3.4 Alarms and Process Setpoints – 3340DB103

T3 Alarms and Process Setpoints


UN SFCPF_AlimFlujoCruzado EM 3340DB103 Sub EM
High Low
Tag Description Range Unit SP HYS High Low
High Low
0 – 1000
3340-PIT-037 Crossflow Feed Distributor 1
(Expected KPa 10
pressure transmitter
50)

Table 94: Alarms and Process Setpoint 3340DB103

Note

1) The feed pressure to the distributor is not controlled.

2) Low pressure distributor feed pressure alarms must be inhibited if the pump 3340-PU-185 is not running.

7.3.5 Binary State Messages – 3340DB103

Not applicable

7.3.6 Regulatory Control Loops – 3340DB103

Not applicable

7.3.7 Advanced Control Loops – 3340DB103

Not applicable

7.3.8 Description – 3340DB103

The objective of the crossflow feed distributor 3340-DB-103 is to distribute the slurry evenly to the
available crossflows separators in the cluster. Should the Crossflow Separator module be available, the
respective feed valve (3340-XV-0038 A – E) will open.

Distributor feed pressure is monitored, not controlled, and will alarm should it drop to a low limit.

7.4 Engineering Module – 3340DB104

7.4.1 Description – 3340DB104

The following figure shows the elements that make up the 3340DB104 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 128 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Flush Water

LC
3340032
Make-Up Water

3340 – LCV - 032


Deslime Cyclone
U/Flow Combined

3340-XV- 021B

Vendor
Package
M
Tails Launder
FC
TS LT
3340027
3340-XV- 039
Crossflow 1
SC
FI DI
3340-XV- 038A
3340021
3340027 3340028
Crossflow 2
3340-TK-101 3340-XV- 021A PT 3340-XV- 038B
M
FT DT
3340-AG-101
Crossflow 3
3340-XV- 038C
3340-PU-185
FAL
3340-XV- 021C Vendor Package 3340-DB-103 Crossflow 4
3340024 3340-XV- 021D 3340-XV- 038D
3340-XV- 024
FSL FC
3340029 Crossflow 5
3340-XV- 038E
SC
FI DI
3340022
3340029 3340030
3340-XV- 022B Crossflow 6
3340-XV- 036A
3340-XV- 022A M
FT DT

Crossflow 7
PT 3340-XV- 036B
3340-PU-186
3340-XV- 022C Crossflow 8
FAL Vendor Package
3340-XV- 025 3340025 3340-XV- 022D 3340-XV- 036C

FSL 3340-DB-104 Crossflow 9


GSW 3340-XV- 036D

Crossflow 10
3340DB104 3340-XV- 036E

Figure 23: Blockflow Control Diagram of the 3340DB104 System

7.4.2 Unit of Control Modules – 3340DB104

T1 Control Module
UN SFCPF_AlimFlujoCruzado EM 3340DB104 Sub EM

Tag Service
3340-PIT-035 Crossflow Feed Distributor 2 pressure transmitter

Table 95: List of Unit Controls – 3340DB104

7.4.3 Interlocks – 3340DB104

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 129 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

7.4.4 Alarms and Process Setpoints – 3340DB104

T3 Alarms and Process Setpoints


UN SFCPF_AlimFlujoCruzado EM 3340DB104 Sub EM
High Low
Tag Description Range Unit SP HYS High Low
High Low
0 – 1000
3340-PIT-035 Crossflow Feed Distributor 2
(Expected KPa 10
pressure transmitter
50)

Table 96: Alarms and Process Setpoint 3340DB104

Note

1) The feed pressure to the distributor is not controlled.

2) Low pressure distributor feed pressure alarms must be inhibited if the pump 3340-PU-186 is not running.

7.4.5 Binary State Messages – 3340DB104

Not applicable

7.4.6 Regulatory Control Loops – 3340DB104

Not applicable

7.4.7 Advanced Control Loops – 3340DB104

Not applicable

7.4.8 Description – 3340DB104

The objective of the crossflow feed distributor 3340-DB-104 is to distribute the slurry evenly to the
available crossflows separators in the cluster. Should the Crossflow Separator module be available, the
respective feed valve (3340-XV-0036 A – E) will open.

Distributor feed pressure is monitored, not controlled, and will alarm should it drop to a low limit.

7.5 Engineering Module – 3340PU198

7.5.1 Unit of Control Modules – 3340PU198

The following table shows the details of the Control Modules considered for this Equipment
Module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 130 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T1 Control Module
UN SFCPF_AlimFlujoCruzado EM 3340PU198 Sub EM

Tag Service
3340-TE-031 Bearing temperature switch
3340-LSH-031 Level Switch High – sump pump 3340-PU-198

Table 97: List of Unit Controls – 3340PU198

7.5.2 Interlocks – 3340PU198

T2 Interlock
Tag 3340-PU-198 Description Deslime Cyclone Spillage Pump
SFCPF_AlimFlujo Sub
UN EM 3340PU198
Cruzado EM
Interlock
Motor Type M1 Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Delay 10
3340-LSH-031.ACT High level switch activated × seconds
Note 1

3340-TE-031.ACT High bearing temperature alarm ×

BLACKOUT Delay 5
Electrical BlackOut Activated ×
ELECTRICO.ACT seconds

Table 98: List of Interlocks for 3340-PU-198

Note 1: Pump to run 15 minutes after the high level has been removed.
7.5.3 Alarms and Process Setpoints – 3340PU198

T3 Alarms and Process Setpoints


UN SFCPF_AlimFlujoCruzado EM 3340PU198 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-LSH-031 Deslime Cyclone Spillage Pump


0 - 100 % 27%
High Switch Alarm

Table 99: Alarms and Process Setpoint 3340-PU-198

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 131 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note: Level switches setpoints set in field, not within PLC.


7.5.4 Binary Messages – 3340PU198

Not applicable.
7.5.5 Regulatory Control Loops – 3340PU198

Not applicable.
7.5.6 Advanced Control Loops – 3340PU198

Not applicable
7.5.7 Description – 3340PU198

Spillage in the Crossflow Feed Pump area will gravitate to the Deslime Cyclone Spillage Pump
(3340 – PU – 198). The pump will discharge the slurry to the Tails Launder Feed Box (3340 – BX – 110)
or more normally to the Crossflow Feed Tank (3340 – TK – 101).
This equipment can operate in manual mode or automatic mode. In manual mode, the start and
stop by the PLC will depend on the start/stop command that the operator. The operation of the
pump in Automatic Mode will occur if:
- The pump will start automatically, if it is ready to Operate in Sequence, and if Sump level
switch is high.
- The sump pump will stop automatically 15 minutes after the level switch high has fallen
away. The time delay in stopping the pump allows the pump to continue to run while hose
down of the area is occurring.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 132 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.0 UNIDAD: SFCPF_SEPHFL1

Refer to:
MQ14 - 08 - DR - 3340 - PD1057 Crossflow Distribution
MQ14 - 08 - DR - 3340 - PD1058 Crossflow Separator #1
MQ14 - 08 - DR - 3340 - PD1059 Crossflow Separator #2
MQ14 - 08 - DR - 3340 - PD1060 Crossflow Separator #3
MQ14 - 08 - DR - 3340 - PD1061 Crossflow Separator #4
MQ14 - 08 - DR - 3340 - PD1062 Crossflow Separator #5
MQ14 - 08 - DR - 3340 - PD1068 Hydrofloat #1
MQ14 - 08 - DR - 3340 - PD1069 Hydrofloat #2
MQ14 - 08 - DR - 3340 - PD1070 Hydrofloat #3
MQ14 - 08 - DR - 3340 - PD1071 Hydrofloat #4
MQ14 - 08 - DR - 3340 - PD1072 Hydrofloat #5
MQ15-727-TE-3340-IN1001 Vendor Hydrofloat Control Philosophy
MQ15-727-TE-3340-IN1002 Vendor Crossflow Separator Control Philosophy

A block flow control diagram is depicted below for the SFCPF_SEPHFL1 system.

3340SepHFL101 3340SepHFL102 3340SepHFL103 3340SepHFL104 3340SepHFL105


3340-XV-038A 3340-XV-038B 3340-XV-038C 3340-XV-038D 3340-XV-038E

SFCPF_SepHFL1
Figure 24: Blockflow Control Diagram of SFCPF_SEPHFL1 System

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 133 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The above control unit is broken into five Engineering Module 1’s, each containing two sub Engineering
Module 2’s:
- 3340SepHFL101
o 3340CF101 (Crossflow Separator 1)
o 3340HF101 (Hydrofloat 1)
- 3340SepHFL102
o 3340CF102 (Crossflow Separator 2)
o 3340HF121 (Hydrofloat 2)
- 3340SepHFL103
o 3340CF103 (Crossflow Separator 3)
o 3340HF103 (Hydrofloat 3)
- 3340SepHFL104
o 3340CF104 (Crossflow Separator 4)
o 3340HF104 (Hydrofloat 4)
- 340SepHFL105
o 3340CF105 (Crossflow Separator 5)
o 3340HF105 (Hydrofloat 5)

8.1 Engineering Module 1 – 3340SepHF101

8.1.1 Description – 3340SepHF101

The following figure shows the elements that make up the 3340SepHF101 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 134 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Crossflow Feed
Solids
3340 – XV - 038 A LC
EM2 = 3340CF101
LT 3340102
FC
3340101
3340 – PT - 101A Tails Launder

PT
3340-PT – 103A
PT FT PT 3340-CF-101

PT
3340 - FCV -101 3340 - PT – 103B
Fluidization 3340 - PT –101C
Water

XV – 3340040A 3340 - XV-107 3340-XV-108

3340 - LCV -102


3340-BX-111
Collector
Reagents 1 - 4
Frother

FC
3340-PT – EM2 = 3340HF101
3340202 3340-PT –202C
202A 3340-PT –202D
PT FT PT PT
3340-PT – 201C

3340- FC
FCV -202 3340204B
PT

FT

3340-FCV
3340201

–204B LC
3340-FCV
FC

FT

3340205
-201

LT
FC
3340203
3340-PT – 3340-PT Concentrate
–204D Thickener
204C
3340-HF-101
3340-PT –

PT
PT

FT PT PT
PT

3340-PT – 206A
201A

3340-PT –
204A 3340-FCV - 204
PT

3340-PT – 206B
FC
3340101
Air 3340-PT –203C 3340-XV-207 3340 - XV- 208
PT FT PT
3340-LCV - 205
3340-PT –
203A 3340-FCV
-203
Frother

Figure 25: Blockflow Control Diagram of the 3340SepHF101 System

8.1.2 Modules of Control 3340SepHF101

The slurry feed to each Crossflow Separator is isolated via actuated valve.

T1 Control Module
UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM

Tag Service
3340-XV-038A Slurry Isolation Valve – Crossflow Separator 1

Table 100: List of Modules of Control for 3340SepHF101

8.1.3 Interlocks – 3340SepHF101

T2 Interlock
Slurry Isolation Valve – Crossflow
Tag 3340-XV-038A Description
Separator 1

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 135 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

SFCPF_ 3340SepH
UN EM1 EM2
SEPHFL1 F101
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to Crossflow Separator vendor Control Philosophy. MQ15-727-TE-3340-IN1002


Crossflow Separator has a high solids Delay time 5
3340-LIT-102.H ×
limit, the valve must close s
Crossflow Separator is not filled with water
Delay time 5
3340-PIT-103B.LL with 3340-PIT-103B on Low Low limit , the ×
s
valve must close
Crossflow Separator teeter water flowrate
Delay time 2
3340-FIT-101.L 3340-FIT-101 low limit exists for 2 ×
minutes
minutes, the valve must close
If only one thickener feed valve (3340-XV-
303 A – C) is closed. A maximum of seven
3340-XV-303A,
Crossflow Separator feed valves may be Delay time 5
3340-XV-303B ×
open. Close the remaining valves, with s
3340-XV-303C
preference for a 4+3 split between
distributors.
3340-XV-303A, If all thickener feed valves (3340-XV-303
Delay time 5
3340-XV-303B A – C) are closed, then the valve must ×
s
3340-XV-303C close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 101: List of Interlocks for 3340-XV-038A

8.1.4 Alarms and Process Setpoints – 3340SepHF101

There are no alarms or process setpoints for this section


8.1.5 Binary State Messages – 3340SepHF101

There are no binary state messages for this section


8.1.6 Regulatory Control Loops – 3340SepHF101

There are no regulatory control loops for this section


8.1.7 Advanced Control Loops – 3340SepHF101

There are no advanced control loops for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 136 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.1.8 Description – 3340SepHF101

Crossflow Separator feed slurry is pumped into a Crossflow Separator Distributor (3340 – DB –
103) at a controlled rate. The five-way distributor discharges slurry evenly to the available
Crossflow Separators (3340 – CF – 101 through 105). Should a Crossflow Separator / Hydrofloat
module not be available, it is isolated by closing the respective distributors discharge valve (3340
– XV - 036 A – E).
An individual Crossflow Feed Valve will close (3340 - XV –036 A – E) if the following is true:
 The solids level in the respective Crossflow Separator (3340 - LIT –102 through 152) has
reached a High limit;
 Water level in the Crossflow Separator (3340 - PIT –103B through 153B) is Low;
 The Crossflow Teeter Water flowrate (3340 - FIT – 101 through 151) has reached a low
limit for a specified time;
 All three thickener feed valves (3340 - XV – 303A, 303B, 303C) are closed.
Should only one Thickener Feed Valve be open (3340 - XV – 303A, 303B, 303C), a maximum of
seven crossflow feed valves may be open when considering both distributor 3340-DB103 and
3340-DB - 104. In this instance it is recommended that two valves from one distributor and one
from the other are closed so as not to reduce the crossflow feed pump flowrate below minimum
sedimentation levels.

8.2 Engineering Module 2 – 3340CF101

8.2.1 Description – 3340CF101

The following figure shows the elements that make up the 3340CF101 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 137 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Crossflow Feed
Solids
3340 – XV - 038 A LC
EM2 = 3340CF101
LT 3340102
FC
3340101
3340 – PT - 101A Tails Launder

PT
3340-PT – 103A
PT FT PT 3340-CF-101

PT
3340 - FCV -101 3340 - PT – 103B
Fluidization 3340 - PT –101C
Water

XV – 3340040A 3340 - XV-107 3340-XV-108

3340 - LCV -102


3340-BX-111
Collector
Reagents 1 - 4
Frother

FC
3340-PT – EM2 = 3340HF101
3340202 3340-PT –202C
202A 3340-PT –202D
PT FT PT PT
3340-PT – 201C

3340- FC
FCV -202 3340204B
PT

FT

3340-FCV
3340201

–204B LC
3340-FCV
FC

FT

3340205
-201

LT
FC
3340203
3340-PT – 3340-PT Concentrate
–204D Thickener
204C
3340-HF-101
3340-PT –

PT
PT

FT PT PT
PT

3340-PT – 206A
201A

3340-PT –
204A 3340-FCV - 204
PT

3340-PT – 206B
FC
3340101
Air 3340-PT –203C 3340-XV-207 3340 - XV- 208
PT FT PT
3340-LCV - 205
3340-PT –
203A 3340-FCV
-203
Frother

Figure 26: Blockflow Control Diagram of the 3340HF101 System

8.2.2 Modules of Control 3340CF101

T1 Control Module
UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340CF101

Tag Service
3340-XV-040A Fluidization water to 3340SepHF101
3340-FV-101 Crossflow Teeter Water flow control valve
3340-FIT-101 Crossflow Teeter Water flowmeter
3340-PIT-101A Crossflow Teeter Water feed pressure
3340-PIT-101C Crossflow Teeter Water delivered pressure
3340-LT-102 Crossflow Separator fluidized bed level transmitter
3340-PIT-103B Fluidized bed pressure transmitter – Upper
3340-PIT-103A Fluidized bed pressure transmitter – Lower
3340-LCV-102 Crossflow Separator Solids Level Control Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 138 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-107 Crossflow Separator underflow Isolation valve


3340-XV-108 Crossflow Separator drain valve

Table 102: List of Modules of Control for 3340CF101

8.2.3 Interlocks – 3340CF101

T2 Interlock
Crossflow Separator and Hydrofloat
Tag 3340-XV-040A Description
Fluidization Water Isolation Valve
3340SepH
UN SFCPF_SEPHFL1 EM Sub EM 3340CF101
F101
Fail Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Both Fluidisation Water Pump 1 (3340 –


3340 – PU – 112!RUN PU – 112)
AND AND ×
3340 – PU – 114!RUN Fluidisation Water Pump 2 (3340 – PU –
114) are not running

Table 103: List of Interlocks for 3340-XV-040A

T2 Interlock
Tag 3340-FV-101 Description Crossflow Teeter Water flow control valve

UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340CF101


Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 104: List of Interlocks for 3340-FV-101

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 139 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Crossflow Separator 1 U/Flow Control
Tag 3340-LCV-102 Description
Valve
UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340CF101
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If underflow Isolation valve is closed, close


3340-XV-107.CL ×
valve

Table 105: List of Interlocks for 3340-LCV-102

T2 Interlock
Crossflow Separator 1 U/Flow Isolation
Tag 3340-XV-107 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF101
1 F101
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If downstream hydrofloat is not filled with


3340-PIT-206B.LL water with 3340-PIT-206B on Low limit. ×
Then, the valve must close
If downstream Hydrofloat Fluidization
3340- FIT – 204A.L
Water flowrates (A and B) are both Low
AND ×
limit for 2 minutes. Then, the valve must
3340- FIT - 204B.L
close
If downstream hydrofloat has a High High
3340 – LIT – 205.HH solids level for 5 minutes, then the valve ×
must close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 106: List of Interlocks for 3340-XV-107

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 140 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3340-XV-108 Description Crossflow Separator 1 Drain Valve


SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF101
1 F101
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT-103B on
Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-101) Lower than the
Low limit setpoint.
AND
3340-XV-108 cannot
All feed valves to all upstream Crossflow ×
open
Separators on the tailings launder are
closed (3340-XV-0038B.CL and 3340-XV-
0036A.CL and 3340-XV-0036B.CL)
AND
The respective Tails Launder Flush Valve
(3340-XV-700.CL) is closed AND the
Flush water pump (3340 – PU – 115!RUN)
is not running.

Table 107: List of Interlocks for 3340-XV-108

8.2.4 Alarms and Process Setpoints – 3340CF101

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340CF101
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-101 Crossflow Teeter Water flowmeter Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
Crossflow Teeter Water feed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-101A pressure

Crossflow Teeter Water delivered Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-101C pressure

Crossflow Separator fluidized bed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-LT-102 level transmitter

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 141 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-103B transmitter – Upper
Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-103A transmitter – Lower

Table 108: Alarms and Process Setpoint 3340CF101

8.2.5 Binary State Messages – 3340CF101

There are no binary state messages for this section


8.2.6 Regulatory Control Loops – 3340CF101

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340CF101
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy. MQ15-727-TE-3340-IN1002

Table 109: Regulatory Control Loops for 3340CF101

Teeter/fluidisation water is injected into the separator via module isolation valve (3340 - XV –
040A) and teeter water control valve (3340 - FCV –101) which is controlled to a constant fluidised
bed density as measured by two pressure transmitters (3340 - PIT –103A and 103B). There is a
minimum limitation to which the fluidisation water flow can be reduced to.
The overall solids bed level in the Crossflow Separator is measured by a level transmitter (3340
- LIT –102 through 192) and controlled by adjusting the opening of the underflow control valve
(3340 - LCV – 102 through 192).

8.2.7 Advanced Control Loops – 3340CF101

There are no advanced control loops for this section.

8.2.8 Sequence Description – 3340CF101

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 142 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340CF101
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 040A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via Flow rate
2 60
2. Initiate 3340-FC-101 3340-FV-101. Refer to vendor above
seconds seconds
functional specification. minimum
for 10 Sec
2 120
3. Open 3340-XV-107 Underflow Isolation Valve. Open
seconds seconds
Underflow solids level control
3340-LC-103 loop via level control valve 2second 120
6. Initiate Open
3340-LCV-103. Refer to vendor s seconds
functional specification.

Table 110: Start Sequence 3340CF101

The crossflow separator shall follow the following steps during shutdown:
TSQST Stop Sequence Table
UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340CF101
Seq Command Tag Description Transition Min Monitor
Time Time
Stop underflow solids level
control loop via level control valve 2second 120
1. Close 3340-LC-103 Close
3340-LCV-103. Refer to vendor s seconds
functional specification.
2 120
2. Close 3340-XV-107 Underflow Isolation Valve. Close
seconds seconds
Stop Teeter water control loop via
Close 2 60
3. Close 3340-FC-101 3340-FV-101. Refer to vendor
seconds seconds
functional specification.
Close. Wait
for the
hydrofloat 2 60
4. 3340-XV- 040A Teeter water Isolation valve Close
system seconds seconds
3340HF101 to
shutdown first

Table 111: Stop Sequence 3340CF101

If the Crossflow Separator is to not operate for more than approximately two days, the equipment
must be manually drained of solids to prevent cementation within the unit.

8.3 Engineering Module 2 – 3340HF101

8.3.1 Description – 3340HF101

The following figure shows the elements that make up the 3340HF101 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 143 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Crossflow Feed
Solids
3340 – XV - 038 A LC
EM2 = 3340CF101
LT 3340102
FC
3340101
3340 – PT - 101A Tails Launder

PT
3340-PT – 103A
PT FT PT 3340-CF-101

PT
3340 - FCV -101 3340 - PT – 103B
Fluidization 3340 - PT –101C
Water

XV – 3340040A 3340 - XV-107 3340-XV-108

3340 - LCV -102


3340-BX-111
Collector
Reagents 1 - 4
Frother

FC
3340-PT – EM2 = 3340HF101
3340202 3340-PT –202C
202A 3340-PT –202D
PT FT PT PT
3340-PT – 201C

3340- FC
FCV -202 3340204B
PT

FT

3340-FCV
3340201

–204B LC
3340-FCV
FC

FT

3340205
-201

LT
FC
3340203
3340-PT – 3340-PT Concentrate
–204D Thickener
204C
3340-HF-101
3340-PT –

PT
PT

FT PT PT
PT

3340-PT – 206A
201A

3340-PT –
204A 3340-FCV - 204
PT

3340-PT – 206B
FC
3340101
Air 3340-PT –203C 3340-XV-207 3340 - XV- 208
PT FT PT
3340-LCV - 205
3340-PT –
203A 3340-FCV
-203
Frother

Figure 27: Blockflow Control Diagram of the 3340HF101 System

8.3.2 Modules of Control 3340HF101

T1 Control Module
UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340HF101

Tag Service
3340-PIT-201A Pre-Aeration Air Pressure Indicator Transmitter
3340-FIT-201 Pre-Aeration Air Flow Indicator Transmitter - Received
3340-FV-201 Hydrofloat Pre-Aeration Air Flow Control Valve
3340-PIT-201C Pre-Aeration Air Flow Indicator Transmitter - Delivered
3340-FV-202 Hydrofloat Pre-Aeration Water Flow Control Valve
3340-FIT-202 Hydrofloat Pre-Aeration Water Flow Meter
3340-PIT-202A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Received
3340-PIT-202D Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Delivered
3340-PIT-202C Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Bubble Generator Feed

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 144 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PIT-206B Fluidized Bed Pressure Transmitter – Upper


3340-PE-206B PRESSURE ELEMENT
3340-PE-206A PRESSURE ELEMENT
3340-PIT-206A Fluidized Bed Pressure Transmitter – Lower
3340-PIT-203A Air Pressure Indicator Transmitter - Received
3340-FIT-203 Air Flow Indicator Transmitter
3340-FV-203 Air Flow Control Valve
3340-PIT-203C Air Pressure Indicator Transmitter - Delivered
3340-FV-204A Fluidization Water Control Valve
3340-FIT-204A Fluidization Water flow indicator transmitter
3340-PIT-204A Fluidization Water Pressure indicator transmitter - Received
3340-FIT-204B Fluidization Water – bubble generator bypass - flow indicator transmitter
3340-FV-204B Fluidization Water – bubble generator bypass - flow control valve
3340-PIT-204C Fluidization Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-204D Fluidization Water Pressure Indicator Transmitter - Delivered
3340-LIT-205 Fluidized Bed Level Indicator Transmitter
3340-LCV-205 Fluidized Bed Level Control Valve
3340-ZE-205 POSITION ELEMENT
3340-XV-207 Underflow Isolation Valve
3340-XV-208 Underflow Drain Valve

Table 112: List of Modules of Control for 3340HF101

8.3.3 Interlocks – 3340HF101

T2 Interlock
Hydrofloat Pre-Aeration Air Flow Control
Tag 3340-FV-201 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF101
1 F101
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Upstream crossflow separator underflow


3340-XV-107.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-102.CL ×
control valve is closed, then close valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 145 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 113: List of Interlocks for 3340-FV-201

T2 Interlock
Hydrofloat Pre-Aeration Water Flow Control
Tag 3340-FV-202 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF101
1 F101
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 114: List of Interlocks for 3340-FV-202

T2 Interlock
Tag 3340-FV-203 Description Air Flow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF101
1 F101
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Upstream crossflow separator underflow


3340-XV-107.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-102.CL ×
control valve is closed, then close valve

Table 115: List of Interlocks for 3340-FV-203

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 146 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3340-FV-204A Description Fluidization Water Control Valve


SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF101
1 F101
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 116: List of Interlocks for 3340-FV-204A

T2 Interlock
Fluidization Water – bubble generator bypass
Tag 3340-FV-204B Description
- flow control valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF101
1 F101
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL) Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 117: List of Interlocks for 3340-FV-204B

T2 Interlock
Tag 3340-XV-207 Description Hydrofloat Underflow Isolation Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF101
1 F101
Fail Position: Interlock
Motor Type Interlock
Keep Last (KL) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 147 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow


Separator not overflowing.
In other words it must be filled with liquid
(3340-PIT-103B not on Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-101) greater than the
Low limit setpoint.

AND

No feed valves to any upstream Crossflow


Separators on the tailings launder are
open (3340-XV-0038B.!OPN or 3340-XV-
036A.!OPN or 3340-XV-0036B.!OPN)

AND
3340-XV-207 may not
×
open if
{The respective Tails Launder Flush Valve
(3340-XV-700.!OPN) is not open AND the
Flush water pump (3340 – PU – 115.!RN)
is not running}.

OR

Respective upstream Crossflow Separator


drain valves (3340-XV-118.OPN or 3340-
XV-158.OPN or 3340-XV-168.OPN) are
open

OR

Upstream Hydrofloat drain valve (3340-


XV-218.OPN or 3340-XV-258.OPN or
3340-XV-268.OPN) are open}
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 118: List of Interlocks for 3340-XV-207

The hydrofloat underflow discharge slurry must have dilution water assistance in order to be able to be
laundered down the respective tails launder without risk of blockage.

In order to avoid tails launder blockages, only one hydrofloat or crossflow separator may drain at a time
into a respective tails launder.

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be manually
drained of solids to prevent cementation within the unit.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 148 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-LCV-205 Description Hydrofloat Underflow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF101
1 F101
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If Hydrofloat Outlet Isolation valve is


3340-XV-207.CL ×
closed, then close valve

Table 119: List of Interlocks for 3340-XV-205

T2 Interlock
Tag 3340-XV-208 Description Hydrofloat Drain Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF101
1 F101
Fail Position
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT- 103B.L
not on Low limit)

AND

Respective Modules Crossflow Separator


has a low teeter water flowrate (3340-FIT-
3340-XV-208 may not
101.L lower than the Low limit). ×
open if
AND

All feed valves to the upstream Crossflow


Separators (3340-XV-0038B, 3340-XV-
0036A, 3340-XV-0036B) on the tailings
launder are closed

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 149 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

AND

The respective Tails Launder Flush Valve


(3340-XV-700.!OPN) is not open OR the
Flush water pump (3340 – PU – 115.!RN)
is not running.

OR

Any of the respective upstream Crossflow


Separator drain valves (3340-XV-
118.OPN or 3340-XV-158.OPN or 3340-
XV-168.OPN) open

Table 120: List of Interlocks for 3340-XV-208

8.3.4 Alarms and Process Setpoints – 3340HF101

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340HF101
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Pre-Aeration Air Pressure Indicator
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-201A Transmitter

Pre-Aeration Air Flow Indicator


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-FIT-201 Transmitter - Received

Pre-Aeration Air Flow Indicator


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-201C Transmitter - Delivered

Hydrofloat Pre-Aeration Water Flow


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-FIT-202 meter

Hydrofloat Pre-Aeration Water


Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-202A Received

Hydrofloat Pre-Aeration Water


Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-202D Bubble Generator Feed

Hydrofloat Pre-Aeration Water


Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-202C Delivered

Fluidized Bed Pressure Transmitter –


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-206B Upper

Fluidized Bed Pressure Transmitter –


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-206A Lower

Air Pressure Indicator Transmitter -


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-203A Received

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 150 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-FIT-203 Air Flow Indicator Transmitter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
Air Pressure Indicator Transmitter -
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-203C Delivered

3340-FIT-204A Fluidization Water flow meter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
Fluidization Water Pressure
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-204A indicator transmitter - Received

Fluidization Water – bubble


generator bypass - flow indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-FIT-204B transmitter

Fluidization Water Pressure


Indicator Transmitter - Bubble Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-204C Generator Feed

Fluidization Water Pressure


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-204D Indicator Transmitter - Delivered

Fluidized Bed Level Indicator


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-LIT-205 Transmitter

Table 121: Alarms and Process Setpoint 3340HF101

8.3.5 Binary State Messages – 3340HF101

There are no binary state messages for this section


8.3.6 Regulatory Control Loops – 3340HF101

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340HF101
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy

Table 122: Regulatory Control Loops for 3340HF101

Pre-aeration water and air are injected into the units feed hopper at a controlled rate via PID loop
controller and control valves (3340 - FCV –201 and 3340 - FCV – 202).
Fluidisation teeter water and air are injected into the hydrofloat at a controlled rate via PID loop
controller and control valves (3340 - FCV –203 and 3340 - FCV –204A/B). Teeter water flowrate
is used to achieve a controlled fluidised bed density as measured by two pressure transmitters
(3340 - PIT –206A and 206B).
The overall solids bed level in the Hydrofloat is measured by a level transmitter (3340 - LIT –205)
and controlled by adjusting the opening of the underflow control valve (3340 - LCV – 205).

8.3.7 Advanced Control Loops – 3340HF101

There are no advanced control loops for this section.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 151 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.3.8 Sequence Description – 3340HF101

The crossflow separator shall follow the following steps during start-up:
TSQST Start Sequence Table
UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340HF101
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 040A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via
3340-FC- 204A Flow rate
3340-FV-204A and 3340-FV- 2 60
2. Initiate And above
204B. Refer to vendor functional seconds seconds
3340-FC-204B minimum
specification.
for 10 Sec
Open &
Hydrofloat Pre-Aeration Water Flow rate
2 60
3. Initiate 3340-FC-202 Control above
seconds seconds
3340-FV-202. minimum
for 10 Sec
3340-XV-207 Open underflow Isolation Valve 2second 60
4. Open Open
3340-XV –207 s seconds
Initiate Hydrofloat Underflow
2second 60
5. Initiate 3340-LC-205 Valve Level Control Open
s seconds
3340-LV-205
(Open &
Flow rate
Pre-Aeration air control loop via 2 60
6. Initiate 3340-FC-201 above
3340-FV-201. seconds seconds
minimum
for 10 Sec
(Open &
Flow rate
Air control loop via 3340-FV- 2 60
7. Initiate 3340-FC-203 above
203. seconds seconds
minimum
for 10 Sec

Table 123: Start Sequence 3340HF101

The hydrofloat should be started before the upstream Crossflow Separator is started.
Frother reagent is only to be initiated once feed is added to the hydrofloat.

The hydrofloat shall follow the following steps during shutdown:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 152 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF101 Sub EM 3340HF101
Seq Command Tag Description Transition Min Monitor
Time Time
Stop Air control loop via 3340- 2 60
1. Close 3340-FV-203 Close
FC-203. seconds seconds
Stop Pre-Aeration air control loop 2 60
2. Close 3340-FV-201 Close
via 3340-FC-201. seconds seconds
Close Close Hydrofloat Underflow Valve
2second 60
3. 3340-LV-205 Level Control Close
s seconds
3340-LV-205
Close 3340-XV-207 Close underflow Isolation Valve 2second 60
4. Close
3340-XV –207 s seconds
Close Hydrofloat Pre-Aeration Water Close
2 60
5. 3340-FV-202 Control
seconds seconds
3340-FV-202.
Close 3340-FV- 204A Close
Teeter water control valve 3340- 2 60
6. And
FV-204A and 3340-FV-204B. seconds seconds
3340-FV-204B
Close Teeter water Isolation valve to Close
2 60
7. 3340-XV- 040A close if crossflow separator also
seconds seconds
stopped.

Table 124: Stop Sequence 3340HF101

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be
manually drained of solids to prevent cementation within the unit.

8.4 Engineering Module 1 – 3340SepHF102

8.4.1 Description – 3340SepHF102

8.4.2 Modules of Control 3340SepHF102

The slurry feed to each Crossflow Separator is isolated via actuated valve.

T1 Control Module
UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM

Tag Service
3340-XV-038B Slurry Isolation Valve – Crossflow Separator 2

Table 125: List of Modules of Control for 3340SepHF102

8.4.3 Interlocks – 3340SepHF102

T2 Interlock
Slurry Isolation Valve – Crossflow
Tag 3340-XV-038B Description
Separator 2
SFCPF_ 3340SepH
UN EM1 EM2
SEPHFL1 F102

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 153 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


Crossflow Separator has a high solids Delay time 5
3340-LIT-112.H ×
limit, the valve must close s
Crossflow Separator is not filled with water
Delay time 5
3340-PIT-113B.LL with 3340-PIT-113B on Low Low limit , the ×
s
valve must close
Crossflow Separator teeter water flowrate
Delay time 2
3340-FIT-111.L 3340-FIT-111 low limit exists for 2 ×
minutes
minutes, the valve must close
If only one thickener feed valve (3340-XV-
303 A – C) is closed. A maximum of seven
3340-XV-303A,
Crossflow Separator feed valves may be Delay time 5
3340-XV-303B ×
open. Close the remaining valves, with s
3340-XV-303C
preference for a 4+3 split between
distributors.
3340-XV-303A, If all thickener feed valves (3340-XV-303
Delay time 5
3340-XV-303B A – C) are closed, then the valve must ×
s
3340-XV-303C close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 126: List of Interlocks for 3340-XV-038B

8.4.4 Alarms and Process Setpoints – 3340SepHF102

There are no alarms or process setpoints for this section


8.4.5 Binary State Messages – 3340SepHF102

There are no binary state messages for this section


8.4.6 Regulatory Control Loops – 3340SepHF102

There are no regulatory control loops for this section


8.4.7 Advanced Control Loops – 3340SepHF102

There are no advanced control loops for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 154 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.4.8 Description – 3340SepHF102

Crossflow Separator feed slurry is pumped into a Crossflow Separator Distributor (3340 – DB –
103) at a controlled rate. The five-way distributor discharges slurry evenly to the available
Crossflow Separators (3340 – CF – 101 through 105). Should a Crossflow Separator / Hydrofloat
module not be available, it is isolated by closing the respective distributors discharge valve (3340
– XV - 036 A – E).
An individual Crossflow Feed Valve will close (3340 - XV –036 A – E) if the following is true:
 The solids level in the respective Crossflow Separator (3340 - LIT –102 through 152) has
reached a High limit;
 Water level in the Crossflow Separator (3340 - PIT –103B through 153B) is Low;
 The Crossflow Teeter Water flowrate (3340 - FIT – 101 through 151) has reached a low
limit for a specified time;
 All three thickener feed valves (3340 - XV – 303A, 303B, 303C) are closed.
Should only one Thickener Feed Valve be open (3340 - XV – 303A, 303B, 303C), a maximum of
seven crossflow feed valves may be open when considering both distributor 3340-DB103 and
3340-DB - 104. In this instance it is recommended that two valves from one distributor and one
from the other are closed so as not to reduce the crossflow feed pump flowrate below minimum
sedimentation levels.

8.5 Engineering Module 2 – 3340CF102

8.5.1 Description – 3340CF102

8.5.2 Modules of Control 3340CF102

T1 Control Module
UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340CF102

Tag Service
3340-XV-042A Fluidization water isolation to Crossflow-Hydrofloat
3340-FV-111 Crossflow Teeter Water Control Valve
3340-FIT-111 Crossflow Teeter Water flowmeter
3340-PIT-111A Crossflow Teeter Water feed pressure
3340-PIT-111C Crossflow Teeter Water delivered pressure
3340-LT-112 Crossflow Separator fluidized bed level transmitter
3340-PIT-113B Fluidized bed Pressure Transmitter - Upper
3340-PIT-113A Fluidized bed Pressure Transmitter - Lower
3340-LCV-112 Crossflow Separator Solids Level Control Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 155 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-117 Crossflow Separator underflow Isolation valve


3340-XV-118 Crossflow Separator drain valve

Table 127: List of Modules of Control for 3340CF102

8.5.3 Interlocks – 3340CF102

T2 Interlock
Crossflow Separator and Hydrofloat
Tag 3340-XV-042A Description
Fluidization Water Isolation Valve
3340SepH
UN SFCPF_SEPHFL1 EM Sub EM 3340CF102
F1012
Fail Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Both Fluidisation Water Pump 1 (3340 –


3340 – PU – 112!RUN PU – 112)
AND AND ×
3340 – PU – 114!RUN Fluidisation Water Pump 2 (3340 – PU –
114) are not running

Table 128: List of Interlocks for 3340-XV-042A

T2 Interlock
Tag 3340-FV-111 Description Crossflow Teeter Water flow control valve

UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340CF102


Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 129: List of Interlocks for 3340-FV-111

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 156 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-LCV-112 Description Crossflow Separator U/Flow Control Valve
UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340CF102
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If underflow Isolation valve is closed, close


3340-XV-117.CL ×
valve

Table 130: List of Interlocks for 3340-LCV-112

T2 Interlock
Crossflow Separator U/Flow Isolation
Tag 3340-XV-117 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF102
1 F102
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If downstream hydrofloat is not filled with


3340-PIT-216B.LL water with 3340-PIT-206B on Low Low ×
limit. Then, the valve must close
If downstream Hydrofloat Fluidization
3340- FIT – 214A.L
Water flowrates (A and B) are both Low
AND ×
limit for 2 minutes. Then, the valve must
3340- FIT - 214B.L
close
If downstream hydrofloat has a High High
3340 – LIT – 215.HH solids level for 5 minutes, then the valve ×
must close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 131: List of Interlocks for 3340-XV-117

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 157 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3340-XV-118 Description Crossflow Separator 1 Drain Valve


SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF102
1 F102
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT-113B on
Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-111) Lower than the
Low limit setpoint.
AND
3340-XV-118 cannot
All feed valves to all upstream Crossflow ×
open
Separators on the tailings launder are
closed (3340-XV-0035A.CL and 3340-XV-
0036B.CL)
AND
The respective Tails Launder Flush Valve
(3340-XV-700.CL) is closed AND the
Flush water pump (3340 – PU – 115!RUN)
is not running.

Table 132: List of Interlocks for 3340-XV-118

8.5.4 Alarms and Process Setpoints – 3340CF102

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340CF102
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-111 Crossflow Teeter Water flowmeter Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
Crossflow Teeter Water feed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-111A pressure

Crossflow Teeter Water delivered Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-111C pressure

Crossflow Separator fluidized bed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-LT-112 level transmitter

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 158 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-113B transmitter – Upper
Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-113A transmitter – Lower

Table 133: Alarms and Process Setpoint 3340CF102

8.5.5 Binary State Messages – 3340CF102

There are no binary state messages for this section


8.5.6 Regulatory Control Loops – 3340CF102

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340CF102
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1002

Table 134: Regulatory Control Loops for 3340CF102

Teeter/fluidisation water is injected into the separator via module isolation valve (3340 - XV –
042A) and teeter water control valve (3340 - FCV –111) which is controlled to a constant fluidised
bed density as measured by two pressure transmitters (3340 - PIT –113A and 113B). There is a
minimum limitation to which the fluidisation water flow can be reduced to.
The overall solids bed level in the Crossflow Separator is measured by a level transmitter (3340
- LIT –112) and controlled by adjusting the opening of the underflow control valve (3340 - LCV –
112).

8.5.7 Advanced Control Loops – 3340CF102

There are no advanced control loops for this section.

8.5.8 Sequence Description – 3340CF102

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 159 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340CF102
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 042A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via Flow rate
2 60
2. Initiate 3340-FC-111 3340-FV-111. Refer to vendor above
seconds seconds
functional specification. minimum
for 10 Sec
2 120
3. Open 3340-XV-117 Underflow Isolation Valve. Open
seconds seconds
Underflow solids level control
3340-LC-113 loop via level control valve 2second 120
6. Initiate Open
3340-LCV-113. Refer to vendor s seconds
functional specification.

Table 135: Start Sequence 3340CF102

The crossflow separator shall follow the following steps during shutdown:
TSQST Stop Sequence Table
UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340CF102
Seq Command Tag Description Transition Min Monitor
Time Time
Stop underflow solids level
control loop via level control valve 2second 120
1. Close 3340-LC-113 Close
3340-LCV-103. Refer to vendor s seconds
functional specification.
2 120
2. Close 3340-XV-117 Underflow Isolation Valve. Close
seconds seconds
Stop Teeter water control loop via
Close 2 60
3. Close 3340-FC-111 3340-FV-101. Refer to vendor
seconds seconds
functional specification.
Close. Wait
for the
hydrofloat 2 60
4. 3340-XV- 042A Teeter water Isolation valve Close
system seconds seconds
3340HF102 to
shutdown first

Table 136: Stop Sequence 3340CF102

If the Crossflow Separator is to not operate for more than approximately two days, the equipment
must be manually drained of solids to prevent cementation within the unit.

8.6 Engineering Module 2 – 3340HF102

8.6.1 Description – 3340HF102

8.6.2 Modules of Control 3340HF102

T1 Control Module

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 160 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340HF102

Tag Service
3340-PIT-211A Pre-Aeration Air Pressure Indicator Transmitter
3340-FIT-211 Pre-Aeration Air Flow Indicator Transmitter - Received
3340-FIT-213 Hydrofloat Pre-Aeration Air Flow Control Valve
3340-FV-213 Pre-Aeration Air Flow Indicator Transmitter - Delivered
3340-PIT-213C Hydrofloat Pre-Aeration Water Flow Control Valve
3340-FV-214A Hydrofloat Pre-Aeration Water Flow Meter
3340-FIT-214A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Received
3340-PIT-214A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Delivered
3340-FIT-214B Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-FV-214B Fluidized Bed Pressure Transmitter – Upper
3340-PIT-214C PRESSURE ELEMENT
3340-PIT-214D PRESSURE ELEMENT
3340-LIT-215 Fluidized Bed Pressure Transmitter – Lower
3340-FV-211 Air Pressure Indicator Transmitter - Received
3340-PIT-211C Air Flow Indicator Transmitter
3340-FV-212 Air Flow Control Valve
3340-FIT-212 Air Pressure Indicator Transmitter - Delivered
3340-PIT-212A Fluidization Water Control Valve
3340-PIT-212D Fluidization Water flow indicator transmitter
3340-PIT-212C Fluidization Water Pressure indicator transmitter - Received
3340-PIT-216B Fluidization Water – bubble generator bypass - flow indicator transmitter
3340-PE-216B Fluidization Water – bubble generator bypass - flow control valve
3340-PE-216A Fluidization Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-216A Fluidization Water Pressure Indicator Transmitter - Delivered
3340-PIT-213A Fluidized Bed Level Indicator Transmitter
3340-LCV-215 Fluidized Bed Level Control Valve
3340-ZE-215 POSITION ELEMENT
3340-XV-217 Underflow Isolation Valve
3340-XV-218 Underflow Drain Valve

Table 137: List of Modules of Control for 3340HF102

8.6.3 Interlocks – 3340HF102

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 161 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Hydrofloat Pre-Aeration Air Flow Control


Tag 3340-FV-211 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF102
1 F102
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-117.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-112.CL ×
control valve is closed, then close valve

Table 138: List of Interlocks for 3340-FV-211

T2 Interlock
Hydrofloat Pre-Aeration Water Flow Control
Tag 3340-FV-212 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF102
1 F102
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL) Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 139: List of Interlocks for 3340-FV-212

T2 Interlock
Tag 3340-FV-213 Description Air Flow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF102
1 F102
Fail Position: Fail Interlock
Motor Type Interlock
Closed (FC) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 162 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-117.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-112.CL ×
control valve is closed, then close valve

Table 140: List of Interlocks for 3340-FV-213

T2 Interlock
Tag 3340-FV-214A Description Fluidization Water Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF102
1 F102
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 141: List of Interlocks for 3340-FV-214A

T2 Interlock
Fluidization Water – bubble generator bypass
Tag 3340-FV-214B Description
- flow control valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF102
1 F102
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 163 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 142: List of Interlocks for 3340-FV-214B

T2 Interlock
Tag 3340-XV-217 Description Hydrofloat Underflow Isolation Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF102
1 F102
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow


Separator not overflowing.
In other words it must be filled with liquid
(3340-PIT-113B not on Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-111) greater than the
Low limit setpoint.

AND

No feed valves to any upstream Crossflow


Separators on the tailings launder are
3340-XV-217 may not open (3340-XV-036A.!OPN or 3340-XV-
×
open if 0036B.!OPN)

AND

{The respective Tails Launder Flush Valve


(3340-XV-700.!OPN) is not open AND the
Flush water pump (3340 – PU – 115.!RN)
is not running}.

OR

Respective upstream Crossflow Separator


drain valves (3340-XV-158.OPN or 3340-
XV-168.OPN) are open

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 164 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

OR

Upstream Hydrofloat drain valve (3340-


XV-258.OPN or 3340-XV-268.OPN) are
open}
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 143: List of Interlocks for 3340-XV-217

The hydrofloat underflow discharge slurry must have dilution water assistance in order to be able to be
laundered down the respective tails launder without risk of blockage.

In order to avoid tails launder blockages, only one hydrofloat or crossflow separator may drain at a time
into a respective tails launder.

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be manually
drained of solids to prevent cementation within the unit.

T2 Interlock
Tag 3340-LCV-215 Description Hydrofloat Underflow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF102
1 F102
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If Hydrofloat Outlet Isolation valve is


3340-XV-217.CL ×
closed, then close valve

Table 144: List of Interlocks for 3340-XV-215

T2 Interlock
Tag 3340-XV-218 Description Hydrofloat Drain Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF102
1 F102
Fail Position:
Keep Last (KL) Interlock
Motor Type Interlock
Safe Position: Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 165 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT- 113B.L
not on Low limit)

AND

Respective Modules Crossflow Separator


has a low teeter water flowrate (3340-FIT-
111.L lower than the Low limit).

AND

All feed valves to the upstream Crossflow


Separators (3340-XV-0036A and 3340-
3340-XV-218 may not
XV-0036B) on the tailings launder are ×
open if
closed

AND

The respective Tails Launder Flush Valve


(3340-XV-700.!OPN) is not open OR the
Flush water pump (3340 – PU – 115.!RN)
is not running.

OR

Any of the respective upstream Crossflow


Separator drain valves (3340-XV-
158.OPN or 3340-XV-168.OPN) open

Table 145: List of Interlocks for 3340-XV-218

8.6.4 Alarms and Process Setpoints – 3340HF102

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340HF102
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Pre-Aeration Air Pressure Indicator
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-211A Transmitter

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-211 Transmitter - Received

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-211C Transmitter - Delivered

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 166 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Hydrofloat Pre-Aeration Water Flow Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-212 meter

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-212A Received

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-212D Bubble Generator Feed

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-212C Delivered

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-216B Upper

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-216A Lower

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-213A Received

3340-FIT-213 Air Flow Indicator Transmitter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-213C Delivered

3340-FIT-214A Fluidization Water flow meter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-214A indicator transmitter - Received

Fluidization Water – bubble Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


generator bypass - flow indicator
3340-FIT-214B transmitter

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Indicator Transmitter - Bubble
3340-PIT-214C Generator Feed

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-214D Indicator Transmitter - Delivered

Fluidized Bed Level Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-LIT-215 Transmitter

Table 146: Alarms and Process Setpoint 3340HF102

8.6.5 Binary State Messages – 3340HF102

There are no binary state messages for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 167 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.6.6 Regulatory Control Loops – 3340HF102

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340HF102
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Table 147: Regulatory Control Loops for 3340HF102

Pre-aeration water and air are injected into the units feed hopper at a controlled rate via PID loop
controller and control valves (3340 - FCV –211 and 3340 - FCV – 212).
Fluidisation teeter water and air are injected into the separator at a controlled rate via PID loop
controller and control valves (3340 - FCV –213 and 3340 - FCV –214A/B). Teeter water flowrate
is used to achieve a controlled fluidised bed density as measured by two pressure transmitters
(3340 - PIT –216A and 216B).
The overall solids bed level in the Hydrofloat is measured by a level transmitter (3340 - LIT –215)
and controlled by adjusting the opening of the underflow control valve (3340 - LCV – 215).

8.6.7 Advanced Control Loops – 3340HF102

There are no advanced control loops for this section.

8.6.8 Sequence Description – 3340HF102

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 168 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340HF102
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 042A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via
3340-FC- 214A Flow rate
3340-FV-214A and 3340-FV- 2 60
2. Initiate And above
214B. Refer to vendor functional seconds seconds
3340-FC-214B minimum
specification.
for 10 Sec
Open &
Hydrofloat Pre-Aeration Water Flow rate
2 60
3. Initiate 3340-FC-212 Control above
seconds seconds
3340-FV-212. minimum
for 10 Sec
3340-XV-217 Open underflow Isolation Valve 2second 60
4. Open Open
3340-XV –217 s seconds
Initiate Hydrofloat Underflow
2second 60
5. Initiate 3340-LC-215 Valve Level Control Open
s seconds
3340-LV-215
(Open &
Flow rate
Pre-Aeration air control loop via 2 60
6. Initiate 3340-FC-211 above
3340-FV-211. seconds seconds
minimum
for 10 Sec
(Open &
Flow rate
Air control loop via 3340-FV- 2 60
7. Initiate 3340-FC-213 above
213. seconds seconds
minimum
for 10 Sec

Table 148: Start Sequence 3340HF102

The hydrofloat should be started before the upstream Crossflow Separator is started.
Frother reagent is only to be initiated once feed is added to the hydrofloat.

The hydrofloat shall follow the following steps during shutdown:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 169 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF102 Sub EM 3340HF102
Seq Command Tag Description Transition Min Monitor
Time Time
Stop Air control loop via 3340- 2 60
1. Close 3340-FV-213 Close
FC-213. seconds seconds
Stop Pre-Aeration air control loop 2 60
2. Close 3340-FV-211 Close
via 3340-FC-211. seconds seconds
Close Close Hydrofloat Underflow Valve
2second 60
3. 3340-LV-215 Level Control Close
s seconds
3340-LV-215
Close 3340-XV-217 Close underflow Isolation Valve 2second 60
4. Close
3340-XV –217 s seconds
Close Hydrofloat Pre-Aeration Water Close
2 60
5. 3340-FV-212 Control
seconds seconds
3340-FV-212.
Close 3340-FV- 214A Close
Teeter water control valve 3340- 2 60
6. And
FV-214A and 3340-FV-214B. seconds seconds
3340-FV-214B
Close Teeter water Isolation valve to Close
2 60
7. 3340-XV- 042A close if crossflow separator also
seconds seconds
stopped.

Table 149: Stop Sequence 3340HF102

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be
manually drained of solids to prevent cementation within the unit.

8.7 Engineering Module 1 – 3340SepHF103

8.7.1 Description – 3340SepHF103

8.7.2 Modules of Control 3340SepHF103

The slurry feed to each Crossflow Separator is isolated via actuated valve.

T1 Control Module
UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM

Tag Service
3340-XV-038C Slurry Isolation Valve – Crossflow Separator 3

Table 150: List of Modules of Control for 3340SepHF103

8.7.3 Interlocks – 3340SepHF103

T2 Interlock
Slurry Isolation Valve – Crossflow
Tag 3340-XV-038C Description
Separator 3
SFCPF_ 3340SepH
UN EM1 EM2
SEPHFL1 F103

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 170 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to Crossflow Separator vendor Control Philosophy MQ15-727-TE-3340-IN1002


Crossflow Separator has a high solids Delay time 5
3340-LIT-122.H ×
limit, the valve must close s
Crossflow Separator is not filled with water
Delay time 5
3340-PIT-123B.LL with 3340-PIT-123B on Low Low limit , the ×
s
valve must close
Crossflow Separator teeter water flowrate
Delay time 2
3340-FIT-121.L 3340-FIT-121 low limit exists for 2 ×
minutes
minutes, the valve must close
If only one thickener feed valve (3340-XV-
303 A – C) is closed. A maximum of seven
3340-XV-303A,
Crossflow Separator feed valves may be Delay time 5
3340-XV-303B ×
open. Close the remaining valves, with s
3340-XV-303C
preference for a 4+3 split between
distributors.
3340-XV-303A, If all thickener feed valves (3340-XV-303
Delay time 5
3340-XV-303B A – C) are closed, then the valve must ×
s
3340-XV-303C close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 151: List of Interlocks for 3340-XV-038C

8.7.4 Alarms and Process Setpoints – 3340SepHF103

There are no alarms or process setpoints for this section


8.7.5 Binary State Messages – 3340SepHF103

There are no binary state messages for this section

8.7.6 Regulatory Control Loops – 3340SepHF103

There are no regulatory control loops for this section

8.7.7 Advanced Control Loops – 3340SepHF103

There are no advanced control loops for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 171 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.7.8 Description – 3340SepHF103

Crossflow Separator feed slurry is pumped into a Crossflow Separator Distributor (3340 – DB –
103) at a controlled rate. The five-way distributor discharges slurry evenly to the available
Crossflow Separators (3340 – CF – 101 through 105). Should a Crossflow Separator / Hydrofloat
module not be available, it is isolated by closing the respective distributors discharge valve (3340
– XV - 036 A – E).
An individual Crossflow Feed Valve will close (3340 - XV –036 A – E) if the following is true:
 The solids level in the respective Crossflow Separator (3340 - LIT –102 through 152) has
reached a High limit;
 Water level in the Crossflow Separator (3340 - PIT –103B through 153B) is Low;
 The Crossflow Teeter Water flowrate (3340 - FIT – 101 through 151) has reached a low
limit for a specified time;
 All three thickener feed valves (3340 - XV – 303A, 303B, 303C) are closed.
Should only one Thickener Feed Valve be open (3340 - XV – 303A, 303B, 303C), a maximum of
seven crossflow feed valves may be open when considering both distributor 3340-DB103 and
3340-DB - 104. In this instance it is recommended that two valves from one distributor and one
from the other are closed so as not to reduce the crossflow feed pump flowrate below minimum
sedimentation levels.

8.8 Engineering Module 2 – 3340CF103

8.8.1 Description – 3340CF103

8.8.2 Modules of Control 3340CF103

T1 Control Module
UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM 3340CF103

Tag Service
3340-XV-044A Fluidization water isolation to Crossflow-Hydrofloat
3340-FV-121 Crossflow Teeter Water Control Valve
3340-FIT-121 Crossflow Teeter Water flowmeter
3340-PIT-121A Crossflow Teeter Water feed pressure
3340-PIT-121C Crossflow Teeter Water delivered pressure
3340-LT-122 Crossflow Separator fluidized bed level transmitter
3340-PIT-123B Fluidized bed Pressure Transmitter - Upper
3340-PIT-123A Fluidized bed Pressure Transmitter - Lower
3340-LCV-122 Crossflow Separator Solids Level Control Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 172 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-127 Crossflow Separator underflow Isolation valve


3340-XV-128 Crossflow Separator drain valve

Table 152: List of Modules of Control for 3340CF103

8.8.3 Interlocks – 3340CF103

T2 Interlock
Crossflow Separator and Hydrofloat
Tag 3340-XV-044A Description
Fluidization Water Isolation Valve
3340SepH
UN SFCPF_SEPHFL1 EM Sub EM 3340CF103
F103
Fail Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Both Fluidisation Water Pump 1 (3340 –


3340 – PU – 112!RUN PU – 112)
AND AND ×
3340 – PU – 114!RUN Fluidisation Water Pump 2 (3340 – PU –
114) are not running

Table 153: List of Interlocks for 3340-XV-044A

T2 Interlock
Tag 3340-FV-121 Description Crossflow Teeter Water flow control valve

UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM 3340CF103


Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 154: List of Interlocks for 3340-FV-121

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 173 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-LCV-122 Description Crossflow Separator U/Flow Control Valve
UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM 3340CF103
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If underflow Isolation valve is closed, close


3340-XV-127.CL ×
valve

Table 155: List of Interlocks for 3340-LCV-122

T2 Interlock
Crossflow Separator U/Flow Isolation
Tag 3340-XV-127 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF103
1 F103
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If downstream hydrofloat is not filled with


3340-PIT-226B.LL water with 3340-PIT-226B on Low Low ×
limit. Then, the valve must close
If downstream Hydrofloat Fluidization
3340- FIT – 224A.L
Water flowrates (A and B) are both Low
AND ×
limit for 2 minutes. Then, the valve must
3340- FIT - 224B.L
close
If downstream hydrofloat has a High High
3340 – LIT – 225.HH solids level for 5 minutes, then the valve ×
must close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 156: List of Interlocks for 3340-XV-127

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 174 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3340-XV-128 Description Crossflow Separator Drain Valve


SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF103
1 F103
Fail Position
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT-123B on
Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-121) Lower than the
Low limit setpoint.
AND
3340-XV-128 cannot
All feed valves to all upstream Crossflow ×
open
Separators on the tailings launder are
closed (3340-XV-0036C.CL and 3340-XV-
0036D.CL and 3340-XV-0038D.CL)
AND
The respective Tails Launder Flush Valve
(3340-XV-701.CL) is closed AND the
Flush water pump (3340 – PU – 115!RUN)
is not running.

Table 157: List of Interlocks for 3340-XV-128

8.8.4 Alarms and Process Setpoints – 3340CF103

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM 3340CF103
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-121 Crossflow Teeter Water flowmeter Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
Crossflow Teeter Water feed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-121A pressure

Crossflow Teeter Water delivered Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-121C pressure

Crossflow Separator fluidized bed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-LT-122 level transmitter

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 175 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-123B transmitter – Upper
Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-123A transmitter – Lower

Table 158: Alarms and Process Setpoint 3340CF103

8.8.5 Binary State Messages – 3340CF103

There are no binary state messages for this section


8.8.6 Regulatory Control Loops – 3340CF103

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM 3340CF103
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1002

Table 159: Regulatory Control Loops for 3340CF103

Teeter/fluidisation water is injected into the separator via module isolation valve (3340 - XV –
044A) and teeter water control valve (3340 - FCV –121) which is controlled to a constant fluidised
bed density as measured by two pressure transmitters (3340 - PIT –123A and 123B). There is a
minimum limitation to which the fluidisation water flow can be reduced to.
The overall solids bed level in the Crossflow Separator is measured by a level transmitter (3340
- LIT –122) and controlled by adjusting the opening of the underflow control valve (3340 - LCV –
122).

8.8.7 Advanced Control Loops – 3340CF103

There are no advanced control loops for this section.

8.8.8 Sequence Description – 3340CF103

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 176 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM 3340CF103
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 044A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via Flow rate
2 60
2. Initiate 3340-FC-121 3340-FV-121. Refer to vendor above
seconds seconds
functional specification. minimum
for 10 Sec
2 120
3. Open 3340-XV-127 Underflow Isolation Valve. Open
seconds seconds
Underflow solids level control
3340-LC-123 loop via level control valve 2second 120
6. Initiate Open
3340-LCV-123. Refer to vendor s seconds
functional specification.

Table 160: Start Sequence 3340CF103

The crossflow separator shall follow the following steps during shutdown:
TSQST Stop Sequence Table
UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM 3340CF103
Seq Command Tag Description Transition Min Monitor
Time Time
Stop underflow solids level
control loop via level control valve 2second 120
1. Close 3340-LC-123 Close
3340-LCV-123. Refer to vendor s seconds
functional specification.
2 120
2. Close 3340-XV-127 Underflow Isolation Valve. Close
seconds seconds
Stop Teeter water control loop via
Close 2 60
3. Close 3340-FC-121 3340-FV-121. Refer to vendor
seconds seconds
functional specification.
Close. Wait
for the
hydrofloat 2 60
4. 3340-XV- 044A Teeter water Isolation valve Close
system seconds seconds
3340HF102 to
shutdown first

Table 161: Stop Sequence 3340CF103

If the Crossflow Separator is to not operate for more than approximately two days, the equipment
must be manually drained of solids to prevent cementation within the unit.

8.9 Engineering Module 2 – 3340HF103

8.9.1 Description – 3340HF103

8.9.2 Modules of Control 3340HF103

T1 Control Module

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 177 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM 3340HF103

Tag Service
3340-PIT-221A Pre-Aeration Air Pressure Indicator Transmitter
3340-FIT-221 Pre-Aeration Air Flow Indicator Transmitter - Received
3340-FIT-223 Hydrofloat Pre-Aeration Air Flow Control Valve
3340-FV-223 Pre-Aeration Air Flow Indicator Transmitter - Delivered
3340-PIT-223C Hydrofloat Pre-Aeration Water Flow Control Valve
3340-FV-224A Hydrofloat Pre-Aeration Water Flow Meter
3340-FIT-224A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Received
3340-PIT-224A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Delivered
3340-FIT-224B Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-FV-224B Fluidized Bed Pressure Transmitter – Upper
3340-PIT-224C PRESSURE ELEMENT
3340-PIT-224D PRESSURE ELEMENT
3340-LIT-225 Fluidized Bed Pressure Transmitter – Lower
3340-FV-221 Air Pressure Indicator Transmitter - Received
3340-PIT-221C Air Flow Indicator Transmitter
3340-FV-222 Air Flow Control Valve
3340-FIT-222 Air Pressure Indicator Transmitter - Delivered
3340-PIT-222A Fluidization Water Control Valve
3340-PIT-222D Fluidization Water flow indicator transmitter
3340-PIT-222C Fluidization Water Pressure indicator transmitter - Received
3340-PIT-226B Fluidization Water – bubble generator bypass - flow indicator transmitter
3340-PE-226B Fluidization Water – bubble generator bypass - flow control valve
3340-PE-226A Fluidization Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-226A Fluidization Water Pressure Indicator Transmitter - Delivered
3340-PIT-223A Fluidized Bed Level Indicator Transmitter
3340-LCV-225 Fluidized Bed Level Control Valve
3340-ZE-225 POSITION ELEMENT
3340-XV-227 Underflow Isolation Valve
3340-XV-228 Underflow Drain Valve

Table 162: List of Modules of Control for 3340HF103

8.9.3 Interlocks – 3340HF103

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 178 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Hydrofloat Pre-Aeration Air Flow Control


Tag 3340-FV-221 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF103
1 F103
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-127.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-122.CL ×
control valve is closed, then close valve

Table 163: List of Interlocks for 3340-FV-221

T2 Interlock
Hydrofloat Pre-Aeration Water Flow Control
Tag 3340-FV-222 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF103
1 F103
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL) Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 164: List of Interlocks for 3340-FV-222

T2 Interlock
Tag 3340-FV-223 Description Air Flow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF103
1 F103
Fail Position: Fail Interlock
Motor Type Interlock
Closed (FC) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 179 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-127.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-122.CL ×
control valve is closed, then close valve

Table 165: List of Interlocks for 3340-FV-223

T2 Interlock
Tag 3340-FV-224A Description Fluidization Water Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF103
1 F103
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 166: List of Interlocks for 3340-FV-224A

T2 Interlock
Fluidization Water – bubble generator bypass
Tag 3340-FV-224B Description
- flow control valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF103
1 F103
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 180 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 167: List of Interlocks for 3340-FV-224B

T2 Interlock
Tag 3340-XV-227 Description Hydrofloat Underflow Isolation Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF103
1 F103
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow


Separator not overflowing.
In other words it must be filled with liquid
(3340-PIT-123B not on Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-121) greater than the
Low limit setpoint.

AND

No feed valves to any upstream Crossflow


Separators on the tailings launder are
3340-XV-227 may not open (3340-XV-038D.!OPN and 3340-XV-
×
open if 036A.!OPN and 3340-XV-0036B.!OPN)

AND

{The respective Tails Launder Flush Valve


(3340-XV-701.!OPN) is not open AND the
Flush water pump (3340 – PU – 115.!RN)
is not running}.

OR

Respective upstream Crossflow Separator


drain valves (3340-XV-138.OPN or 3340-
XV-178.OPN or 3340-XV-188.OPN) are

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 181 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

open

OR

Upstream Hydrofloat drain valve (3340-


XV-238 or 3340-XV-278 or 3340-XV-288)
are open}
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 168: List of Interlocks for 3340-XV-227

The hydrofloat underflow discharge slurry must have dilution water assistance in order to be able to be
laundered down the respective tails launder without risk of blockage.

In order to avoid tails launder blockages, only one hydrofloat or crossflow separator may drain at a time
into a respective tails launder.

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be manually
drained of solids to prevent cementation within the unit.

T2 Interlock
Tag 3340-LCV-225 Description Hydrofloat Underflow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF103
1 F103
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If Hydrofloat Outlet Isolation valve is


3340-XV-227.CL ×
closed, then close valve

Table 169: List of Interlocks for 3340-XV-225

T2 Interlock
Tag 3340-XV-228 Description Hydrofloat Drain Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF103
1 F103
Fail Position: Interlock
Motor Type Interlock
Keep Last (KL) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 182 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT- 123B.L
not on Low limit)

AND

Respective Modules Crossflow Separator


has a low teeter water flowrate (3340-FIT-
121.L lower than the Low limit).

AND

All feed valves to the upstream Crossflow


Separators (3340-XV-038D and 3340-XV-
3340-XV-228 may not 0036C and 3340-XV-0036D) on the
×
open if tailings launder are closed

AND

The respective Tails Launder Flush Valve


(3340-XV-701.!OPN) is not open OR the
Flush water pump (3340 – PU – 115.!RN)
is not running.

OR

Any of the respective upstream Crossflow


Separator drain valves (3340-XV-
138.OPN or 3340-XV-178.OPN or 3340-
XV-188.OPN) are open

Table 170: List of Interlocks for 3340-XV-228

8.9.4 Alarms and Process Setpoints – 3340HF103

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM 3340HF103
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Pre-Aeration Air Pressure Indicator
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-221A Transmitter

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-221 Transmitter - Received

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 183 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-221C Transmitter - Delivered

Hydrofloat Pre-Aeration Water Flow Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-222 meter

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-222A Received

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-222D Bubble Generator Feed

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-222C Delivered

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-226B Upper

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-226A Lower

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-223A Received

3340-FIT-223 Air Flow Indicator Transmitter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-223C Delivered

3340-FIT-224A Fluidization Water flow meter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-224A indicator transmitter - Received

Fluidization Water – bubble Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


generator bypass - flow indicator
3340-FIT-224B transmitter

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Indicator Transmitter - Bubble
3340-PIT-224C Generator Feed

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-224D Indicator Transmitter - Delivered

Fluidized Bed Level Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-LIT-225 Transmitter

Table 171: Alarms and Process Setpoint 3340HF103

8.9.5 Binary State Messages – 3340HF103

There are no binary state messages for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 184 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.9.6 Regulatory Control Loops – 3340HF103

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL1 EM 3340SepHF1013 Sub EM 3340HF103
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy

Table 172: Regulatory Control Loops for 3340HF103

Pre-aeration water and air are injected into the units feed hopper at a controlled rate via PID loop
controller and control valves (3340 - FCV –221 and 3340 - FCV – 222).
Fluidisation teeter water and air are injected into the separator at a controlled rate via PID loop
controller and control valves (3340 - FCV –223 and 3340 - FCV –224A/B). Teeter water flowrate
is used to achieve a controlled fluidised bed density as measured by two pressure transmitters
(3340 - PIT –226A and 226B).
The overall solids bed level in the Hydrofloat is measured by a level transmitter (3340 - LIT –225)
and controlled by adjusting the opening of the underflow control valve (3340 - LCV – 225).

8.9.7 Advanced Control Loops – 3340HF103

There are no advanced control loops for this section.

8.9.8 Sequence Description – 3340HF103

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 185 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM 3340HF103
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 044A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via
3340-FC- 224A Flow rate
3340-FV-224A and 3340-FV- 2 60
2. Initiate And above
224B. Refer to vendor functional seconds seconds
3340-FC-224B minimum
specification.
for 10 Sec
Open &
Hydrofloat Pre-Aeration Water Flow rate
2 60
3. Initiate 3340-FC-222 Control above
seconds seconds
3340-FV-222. minimum
for 10 Sec
3340-XV-227 Open underflow Isolation Valve 2second 60
4. Open Open
3340-XV –227 s seconds
Initiate Hydrofloat Underflow
2second 60
5. Initiate 3340-LC-225 Valve Level Control Open
s seconds
3340-LV-225
(Open &
Flow rate
Pre-Aeration air control loop via 2 60
6. Initiate 3340-FC-221 above
3340-FV-221. seconds seconds
minimum
for 10 Sec
(Open &
Flow rate
Air control loop via 3340-FV- 2 60
7. Initiate 3340-FC-223 above
223. seconds seconds
minimum
for 10 Sec

Table 173: Start Sequence 3340HF103

The hydrofloat should be started before the upstream Crossflow Separator is started.
Frother reagent is only to be initiated once feed is added to the hydrofloat.

The hydrofloat shall follow the following steps during shutdown:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 186 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF103 Sub EM 3340HF103
Seq Command Tag Description Transition Min Monitor
Time Time
Stop Air control loop via 3340- 2 60
1. Close 3340-FV-223 Close
FC-223. seconds seconds
Stop Pre-Aeration air control loop 2 60
2. Close 3340-FV-221 Close
via 3340-FC-221. seconds seconds
Close Close Hydrofloat Underflow Valve
2second 60
3. 3340-LV-225 Level Control Close
s seconds
3340-LV-225
Close 3340-XV-227 Close underflow Isolation Valve 2second 60
4. Close
3340-XV –227 s seconds
Close Hydrofloat Pre-Aeration Water Close
2 60
5. 3340-FV-222 Control
seconds seconds
3340-FV-222.
Close 3340-FV- 224A Close
Teeter water control valve 3340- 2 60
6. And
FV-224A and 3340-FV-224B. seconds seconds
3340-FV-224B
Close Teeter water Isolation valve to Close
2 60
7. 3340-XV- 044A close if crossflow separator also
seconds seconds
stopped.

Table 174: Stop Sequence 3340HF103

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be
manually drained of solids to prevent cementation within the unit.

8.10 Engineering Module 1 – 3340SepHF104

8.10.1 Description – 3340SepHF104

8.10.2 Modules of Control 3340SepHF104

The slurry feed to each Crossflow Separator is isolated via actuated valve.

T1 Control Module
UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM

Tag Service
3340-XV-038D Slurry Isolation Valve – Crossflow Separator 4

Table 175: List of Modules of Control for 3340SepHF104

8.10.3 Interlocks – 3340SepHF104

T2 Interlock
Slurry Isolation Valve – Crossflow
Tag 3340-XV-038D Description
Separator 4
SFCPF_ 3340SepH
UN EM1 EM2
SEPHFL1 F104

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 187 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to Crossflow Separator vendor Control Philosophy


Crossflow Separator has a high solids Delay time 5
3340-LIT-132.H ×
limit, the valve must close s
Crossflow Separator is not filled with water
Delay time 5
3340-PIT-133B.LL with 3340-PIT-133B on Low Low limit , the ×
s
valve must close
Crossflow Separator teeter water flowrate
Delay time 2
3340-FIT-131.L 3340-FIT-131 low limit exists for 2 ×
minutes
minutes, the valve must close
If only one thickener feed valve (3340-XV-
303 A – C) is closed. A maximum of seven
3340-XV-303A,
Crossflow Separator feed valves may be Delay time 5
3340-XV-303B ×
open. Close the remaining valves, with s
3340-XV-303C
preference for a 4+3 split between
distributors.
3340-XV-303A, If all thickener feed valves (3340-XV-303
Delay time 5
3340-XV-303B A – C) are closed, then the valve must ×
s
3340-XV-303C close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 176: List of Interlocks for 3340-XV-038D

8.10.4 Alarms and Process Setpoints – 3340SepHF104

There are no alarms or process setpoints for this section


8.10.5 Binary State Messages – 3340SepHF104

There are no binary state messages for this section

8.10.6 Regulatory Control Loops – 3340SepHF104

There are no regulatory control loops for this section

8.10.7 Advanced Control Loops – 3340SepHF104

There are no advanced control loops for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 188 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.10.8 Description – 3340SepHF104

Crossflow Separator feed slurry is pumped into a Crossflow Separator Distributor (3340 – DB –
103) at a controlled rate. The five-way distributor discharges slurry evenly to the available
Crossflow Separators (3340 – CF – 101 through 105). Should a Crossflow Separator / Hydrofloat
module not be available, it is isolated by closing the respective distributors discharge valve (3340
– XV - 036 A – E).
An individual Crossflow Feed Valve will close (3340 - XV –036 A – E) if the following is true:
 The solids level in the respective Crossflow Separator (3340 - LIT –102 through 152) has
reached a High limit;
 Water level in the Crossflow Separator (3340 - PIT –103B through 153B) is Low;
 The Crossflow Teeter Water flowrate (3340 - FIT – 101 through 151) has reached a low
limit for a specified time;
 All three thickener feed valves (3340 - XV – 303A, 303B, 303C) are closed.
Should only one Thickener Feed Valve be open (3340 - XV – 303A, 303B, 303C), a maximum of
seven crossflow feed valves may be open when considering both distributor 3340-DB103 and
3340-DB - 104. In this instance it is recommended that two valves from one distributor and one
from the other are closed so as not to reduce the crossflow feed pump flowrate below minimum
sedimentation levels.

8.11 Engineering Module 2 – 3340CF104

8.11.1 Description – 3340CF104

8.11.2 Modules of Control 3340CF104

T1 Control Module
UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340CF104

Tag Service
3340-XV-046A Fluidization water isolation to Crossflow-Hydrofloat
3340-FV-131 Crossflow Teeter Water Control Valve
3340-FIT-131 Crossflow Teeter Water flowmeter
3340-PIT-131A Crossflow Teeter Water feed pressure
3340-PIT-131C Crossflow Teeter Water delivered pressure
3340-LT-132 Crossflow Separator fluidized bed level transmitter
3340-PIT-133B Fluidized bed Pressure Transmitter - Upper
3340-PIT-133A Fluidized bed Pressure Transmitter - Lower
3340-LCV-132 Crossflow Separator Solids Level Control Valve
3340-XV-137 Crossflow Separator underflow Isolation valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 189 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-138 Crossflow Separator drain valve

Table 177: List of Modules of Control for 3340CF104

8.11.3 Interlocks – 3340CF104

T2 Interlock
Crossflow Separator and Hydrofloat
Tag 3340-XV-046A Description
Fluidization Water Isolation Valve
3340SepH
UN SFCPF_SEPHFL1 EM Sub EM 3340CF104
F104
Fail Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Both Fluidisation Water Pump 1 (3340 –


3340 – PU – 112!RUN PU – 112)
AND AND ×
3340 – PU – 114!RUN Fluidisation Water Pump 2 (3340 – PU –
114) are not running

Table 178: List of Interlocks for 3340-XV-046A

T2 Interlock
Tag 3340-FV-131 Description Crossflow Teeter Water flow control valve

UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340CF104


Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 179: List of Interlocks for 3340-FV-131

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 190 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-LCV-132 Description Crossflow Separator U/Flow Control Valve
UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340CF104
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If underflow Isolation valve is closed, close


3340-XV-137.CL ×
valve

Table 180: List of Interlocks for 3340-LCV-132

T2 Interlock
Crossflow Separator U/Flow Isolation
Tag 3340-XV-137 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF104
1 F104
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If downstream hydrofloat is not filled with


3340-PIT-236B.LL water with 3340-PIT-236B on Low Low ×
limit. Then, the valve must close
If downstream Hydrofloat Fluidization
3340- FIT – 234A.L
Water flowrates (A and B) are both Low
AND ×
limit for 2 minutes. Then, the valve must
3340- FIT - 234B.L
close
If downstream hydrofloat has a High High
3340 – LIT – 235.HH solids level for 5 minutes, then the valve ×
must close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 181: List of Interlocks for 3340-XV-137

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 191 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3340-XV-138 Description Crossflow Separator 1 Drain Valve


SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF104
1 F104
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT-133B on
Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-131) Lower than the
Low limit setpoint.
AND
3340-XV-138 cannot
All feed valves to all upstream Crossflow ×
open
Separators on the tailings launder are
closed (3340-XV-0036C.CL and 3340-XV-
0036D.CL)
AND
The respective Tails Launder Flush Valve
(3340-XV-701.CL) is closed AND the
Flush water pump (3340 – PU – 115!RUN)
is not running.

Table 182: List of Interlocks for 3340-XV-138

8.11.4 Alarms and Process Setpoints – 3340CF104

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340CF104
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-131 Crossflow Teeter Water flowmeter Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
Crossflow Teeter Water feed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-131A pressure

Crossflow Teeter Water delivered Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-131C pressure

Crossflow Separator fluidized bed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-LT-132 level transmitter

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 192 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-133B transmitter – Upper
Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-133A transmitter – Lower

Table 183: Alarms and Process Setpoint 3340CF104

8.11.5 Binary State Messages – 3340CF104

There are no binary state messages for this section


8.11.6 Regulatory Control Loops – 3340CF104

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340CF104
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1002

Table 184: Regulatory Control Loops for 3340CF104

Teeter/fluidisation water is injected into the separator via module isolation valve (3340 - XV –
046A) and teeter water control valve (3340 - FCV –131) which is controlled to a constant fluidised
bed density as measured by two pressure transmitters (3340 - PIT –133A and 133B). There is a
minimum limitation to which the fluidisation water flow can be reduced to.
The overall solids bed level in the Crossflow Separator is measured by a level transmitter (3340
- LIT –132) and controlled by adjusting the opening of the underflow control valve (3340 - LCV –
132).

8.11.7 Advanced Control Loops – 3340CF104

There are no advanced control loops for this section.

8.11.8 Sequence Description – 3340CF104

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 193 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340CF104
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 046A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via Flow rate
2 60
2. Initiate 3340-FC-131 3340-FV-131. Refer to vendor above
seconds seconds
functional specification. minimum
for 10 Sec
2 120
3. Open 3340-XV-137 Underflow Isolation Valve. Open
seconds seconds
Underflow solids level control
3340-LC-133 loop via level control valve 2second 120
6. Initiate Open
3340-LCV-133. Refer to vendor s seconds
functional specification.

Table 185: Start Sequence 3340CF104

The crossflow separator shall follow the following steps during shutdown:
TSQST Stop Sequence Table
UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340CF104
Seq Command Tag Description Transition Min Monitor
Time Time
Stop underflow solids level
control loop via level control valve 2second 120
1. Close 3340-LC-133 Close
3340-LCV-123. Refer to vendor s seconds
functional specification.
2 120
2. Close 3340-XV-137 Underflow Isolation Valve. Close
seconds seconds
Stop Teeter water control loop via
Close 2 60
3. Close 3340-FC-131 3340-FV-121. Refer to vendor
seconds seconds
functional specification.
Close. Wait
for the
hydrofloat 2 60
4. 3340-XV- 046A Teeter water Isolation valve Close
system seconds seconds
3340HF103 to
shutdown first

Table 186: Stop Sequence 3340CF104

If the Crossflow Separator is to not operate for more than approximately two days, the equipment
must be manually drained of solids to prevent cementation within the unit.

8.12 Engineering Module 2 – 3340HF104

8.12.1 Description – 3340HF104

8.12.2 Modules of Control 3340HF104

T1 Control Module

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 194 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340HF104

Tag Service
3340-PIT-231A Pre-Aeration Air Pressure Indicator Transmitter
3340-FIT-231 Pre-Aeration Air Flow Indicator Transmitter - Received
3340-FIT-233 Hydrofloat Pre-Aeration Air Flow Control Valve
3340-FV-233 Pre-Aeration Air Flow Indicator Transmitter - Delivered
3340-PIT-233C Hydrofloat Pre-Aeration Water Flow Control Valve
3340-FV-234A Hydrofloat Pre-Aeration Water Flow Meter
3340-FIT-234A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Received
3340-PIT-234A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Delivered
3340-FIT-234B Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-FV-234B Fluidized Bed Pressure Transmitter – Upper
3340-PIT-234C PRESSURE ELEMENT
3340-PIT-234D PRESSURE ELEMENT
3340-LIT-235 Fluidized Bed Pressure Transmitter – Lower
3340-FV-231 Air Pressure Indicator Transmitter - Received
3340-PIT-231C Air Flow Indicator Transmitter
3340-FV-232 Air Flow Control Valve
3340-FIT-232 Air Pressure Indicator Transmitter - Delivered
3340-PIT-232A Fluidization Water Control Valve
3340-PIT-232D Fluidization Water flow indicator transmitter
3340-PIT-232C Fluidization Water Pressure indicator transmitter - Received
3340-PIT-236B Fluidization Water – bubble generator bypass - flow indicator transmitter
3340-PE-236B Fluidization Water – bubble generator bypass - flow control valve
3340-PE-236A Fluidization Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-236A Fluidization Water Pressure Indicator Transmitter - Delivered
3340-PIT-233A Fluidized Bed Level Indicator Transmitter
3340-LCV-235 Fluidized Bed Level Control Valve
3340-ZE-235 POSITION ELEMENT
3340-XV-237 Underflow Isolation Valve
3340-XV-238 Underflow Drain Valve

Table 187: List of Modules of Control for 3340HF104

8.12.3 Interlocks – 3340HF104

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 195 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Hydrofloat Pre-Aeration Air Flow Control


Tag 3340-FV-231 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF104
1 F104
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-137.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-132.CL ×
control valve is closed, then close valve

Table 188: List of Interlocks for 3340-FV-231

T2 Interlock
Hydrofloat Pre-Aeration Water Flow Control
Tag 3340-FV-232 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF104
1 F104
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL) Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 189: List of Interlocks for 3340-FV-232

T2 Interlock
Tag 3340-FV-233 Description Air Flow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF104
1 F104
Fail Position: Fail Interlock
Motor Type Interlock
Closed (FC) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 196 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-137.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-132.CL ×
control valve is closed, then close valve

Table 190: List of Interlocks for 3340-FV-233

T2 Interlock
Tag 3340-FV-234A Description Fluidization Water Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF104
1 F104
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 191: List of Interlocks for 3340-FV-234A

T2 Interlock
Fluidization Water – bubble generator bypass
Tag 3340-FV-234B Description
- flow control valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF104
1 F104
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 197 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 192: List of Interlocks for 3340-FV-234B

T2 Interlock
Tag 3340-XV-237 Description Hydrofloat Underflow Isolation Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF104
1 F104
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow


Separator not overflowing.
In other words it must be filled with liquid
(3340-PIT-133B not on Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-131) greater than the
Low limit setpoint.

AND

No feed valves to any upstream Crossflow


Separators on the tailings launder are
3340-XV-237 may not open (3340-XV-036A.!OPN and 3340-XV-
×
open if 0036B.!OPN)

AND

{The respective Tails Launder Flush Valve


(3340-XV-701.!OPN) is not open AND the
Flush water pump (3340 – PU – 115.!RN)
is not running}.

OR

Respective upstream Crossflow Separator


drain valves (3340-XV-178.OPN or 3340-
XV-188.OPN) are open

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 198 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

OR

Upstream Hydrofloat drain valve (3340-


XV-278 or 3340-XV-288) are open}
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 193: List of Interlocks for 3340-XV-237

The hydrofloat underflow discharge slurry must have dilution water assistance in order to be able to be
laundered down the respective tails launder without risk of blockage.

In order to avoid tails launder blockages, only one hydrofloat or crossflow separator may drain at a time
into a respective tails launder.

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be manually
drained of solids to prevent cementation within the unit.

T2 Interlock
Tag 3340-LCV-235 Description Hydrofloat Underflow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF104
1 F104
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If Hydrofloat Outlet Isolation valve is


3340-XV-237.CL ×
closed, then close valve

Table 194: List of Interlocks for 3340-XV-235

T2 Interlock
Tag 3340-XV-238 Description Hydrofloat Drain Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF104
1 F104
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 199 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT- 133B.L
not on Low limit)

AND

Respective Modules Crossflow Separator


has a low teeter water flowrate (3340-FIT-
131.L lower than the Low limit).

AND

All feed valves to the upstream Crossflow


Separators (3340-XV-0036C and 3340-
3340-XV-238 may not
XV-0036D) on the tailings launder are ×
open if
closed

AND

The respective Tails Launder Flush Valve


(3340-XV-701.!OPN) is not open OR the
Flush water pump (3340 – PU – 115.!RN)
is not running.

OR

Any of the respective upstream Crossflow


Separator drain valves (3340-XV-
178.OPN or 3340-XV-188.OPN) are open

Table 195: List of Interlocks for 3340-XV-238

8.12.4 Alarms and Process Setpoints – 3340HF104

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340HF104
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Pre-Aeration Air Pressure Indicator
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-231A Transmitter

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-231 Transmitter - Received

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-231C Transmitter - Delivered

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 200 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Hydrofloat Pre-Aeration Water Flow Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-232 meter

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-232A Received

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-232D Bubble Generator Feed

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-232C Delivered

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-236B Upper

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-236A Lower

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-233A Received

3340-FIT-233 Air Flow Indicator Transmitter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-233C Delivered

3340-FIT-234A Fluidization Water flow meter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-234A indicator transmitter - Received

Fluidization Water – bubble Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


generator bypass - flow indicator
3340-FIT-234B transmitter

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Indicator Transmitter - Bubble
3340-PIT-234C Generator Feed

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-234D Indicator Transmitter - Delivered

Fluidized Bed Level Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-LIT-235 Transmitter

Table 196: Alarms and Process Setpoint 3340HF104

8.12.5 Binary State Messages – 3340HF104

There are no binary state messages for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 201 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.12.6 Regulatory Control Loops – 3340HF104

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340HF104
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Table 197: Regulatory Control Loops for 3340HF104

Pre-aeration water and air are injected into the units feed hopper at a controlled rate via PID loop
controller and control valves (3340 - FCV –231 and 3340 - FCV – 232).
Fluidisation teeter water and air are injected into the separator at a controlled rate via PID loop
controller and control valves (3340 - FCV –233 and 3340 - FCV –234A/B). Teeter water flowrate
is used to achieve a controlled fluidised bed density as measured by two pressure transmitters
(3340 - PIT –236A and 236B).
The overall solids bed level in the Hydrofloat is measured by a level transmitter (3340 - LIT –235)
and controlled by adjusting the opening of the underflow control valve (3340 - LCV – 235).

8.12.7 Advanced Control Loops – 3340HF104

There are no advanced control loops for this section.

8.12.8 Sequence Description – 3340HF104

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 202 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340HF104
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 046A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via
3340-FC- 234A Flow rate
3340-FV-234A and 3340-FV- 2 60
2. Initiate And above
234B. Refer to vendor functional seconds seconds
3340-FC-234B minimum
specification.
for 10 Sec
Open &
Hydrofloat Pre-Aeration Water Flow rate
2 60
3. Initiate 3340-FC-232 Control above
seconds seconds
3340-FV-232. minimum
for 10 Sec
3340-XV-237 Open underflow Isolation Valve 2second 60
4. Open Open
3340-XV –237 s seconds
Initiate Hydrofloat Underflow
2second 60
5. Initiate 3340-LC-235 Valve Level Control Open
s seconds
3340-LV-235
(Open &
Flow rate
Pre-Aeration air control loop via 2 60
6. Initiate 3340-FC-231 above
3340-FV-231. seconds seconds
minimum
for 10 Sec
(Open &
Flow rate
Air control loop via 3340-FV- 2 60
7. Initiate 3340-FC-233 above
233. seconds seconds
minimum
for 10 Sec

Table 198: Start Sequence 3340HF104

The hydrofloat should be started before the upstream Crossflow Separator is started.
Frother reagent is only to be initiated once feed is added to the hydrofloat.

The hydrofloat shall follow the following steps during shutdown:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 203 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF104 Sub EM 3340HF104
Seq Command Tag Description Transition Min Monitor
Time Time
Stop Air control loop via 3340- 2 60
1. Close 3340-FV-233 Close
FC-233. seconds seconds
Stop Pre-Aeration air control loop 2 60
2. Close 3340-FV-231 Close
via 3340-FC-231. seconds seconds
Close Close Hydrofloat Underflow Valve
2second 60
3. 3340-LV-235 Level Control Close
s seconds
3340-LV-235
Close 3340-XV-237 Close underflow Isolation Valve 2second 60
4. Close
3340-XV –237 s seconds
Close Hydrofloat Pre-Aeration Water Close
2 60
5. 3340-FV-232 Control
seconds seconds
3340-FV-232.
Close 3340-FV- 234A Close
Teeter water control valve 3340- 2 60
6. And
FV-234A and 3340-FV-234B. seconds seconds
3340-FV-234B
Close Teeter water Isolation valve to Close
2 60
7. 3340-XV- 046A close if crossflow separator also
seconds seconds
stopped.

Table 199: Stop Sequence 3340HF104

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be
manually drained of solids to prevent cementation within the unit.

8.13 Engineering Module 1 – 3340SepHF105

8.13.1 Description – 3340SepHF105

8.13.2 Modules of Control 3340SepHF105

The slurry feed to each Crossflow Separator is isolated via actuated valve.

T1 Control Module
UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM

Tag Service
3340-XV-038E Slurry Isolation Valve – Crossflow Separator 5

Table 200: List of Modules of Control for 3340SepHF105

8.13.3 Interlocks – 3340SepHF105

T2 Interlock
Slurry Isolation Valve – Crossflow
Tag 3340-XV-038E Description
Separator 5
SFCPF_ 3340SepH
UN EM1 EM2
SEPHFL1 F105

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 204 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to Crossflow Separator vendor Control Philosophy MQ15-727-TE-3340-IN1002


Crossflow Separator has a high solids Delay time 5
3340-LIT-142.H ×
limit, the valve must close s
Crossflow Separator is not filled with water
Delay time 5
3340-PIT-143B.LL with 3340-PIT-143B on Low Low limit , the ×
s
valve must close
Crossflow Separator teeter water flowrate
Delay time 2
3340-FIT-141.L 3340-FIT-141 low limit exists for 2 ×
minutes
minutes, the valve must close
If only one thickener feed valve (3340-XV-
303 A – C) is closed. A maximum of seven
3340-XV-303A,
Crossflow Separator feed valves may be Delay time 5
3340-XV-303B ×
open. Close the remaining valves, with s
3340-XV-303C
preference for a 4+3 split between
distributors.
3340-XV-303A, If all thickener feed valves (3340-XV-303
Delay time 5
3340-XV-303B A – C) are closed, then the valve must ×
s
3340-XV-303C close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 201: List of Interlocks for 3340-XV-038E

8.13.4 Alarms and Process Setpoints – 3340SepHF105

There are no alarms or process setpoints for this section


8.13.5 Binary State Messages – 3340SepHF105

There are no binary state messages for this section

8.13.6 Regulatory Control Loops – 3340SepHF105

There are no regulatory control loops for this section

8.13.7 Advanced Control Loops – 3340SepHF105

There are no advanced control loops for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 205 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.13.8 Description – 3340SepHF105

Crossflow Separator feed slurry is pumped into a Crossflow Separator Distributor (3340 – DB –
103) at a controlled rate. The five-way distributor discharges slurry evenly to the available
Crossflow Separators (3340 – CF – 101 through 105). Should a Crossflow Separator / Hydrofloat
module not be available, it is isolated by closing the respective distributors discharge valve (3340
– XV - 036 A – E).
An individual Crossflow Feed Valve will close (3340 - XV –036 A – E) if the following is true:
 The solids level in the respective Crossflow Separator (3340 - LIT –102 through 152) has
reached a High limit;
 Water level in the Crossflow Separator (3340 - PIT –103B through 153B) is Low;
 The Crossflow Teeter Water flowrate (3340 - FIT – 101 through 151) has reached a low
limit for a specified time;
 All three thickener feed valves (3340 - XV – 303A, 303B, 303C) are closed.
Should only one Thickener Feed Valve be open (3340 - XV – 303A, 303B, 303C), a maximum of
seven crossflow feed valves may be open when considering both distributor 3340-DB103 and
3340-DB - 104. In this instance it is recommended that two valves from one distributor and one
from the other are closed so as not to reduce the crossflow feed pump flowrate below minimum
sedimentation levels.

8.14 Engineering Module 2 – 3340CF105

8.14.1 Description – 3340CF105

8.14.2 Modules of Control 3340CF105

T1 Control Module
UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340CF105

Tag Service
3340-XV-048A Fluidization water isolation to Crossflow-Hydrofloat
3340-FV-141 Crossflow Teeter Water Control Valve
3340-FIT-141 Crossflow Teeter Water flowmeter
3340-PIT-141A Crossflow Teeter Water feed pressure
3340-PIT-141C Crossflow Teeter Water delivered pressure
3340-LT-142 Crossflow Separator fluidized bed level transmitter
3340-PIT-143B Fluidised bed Pressure Transmitter - Upper
3340-PIT-143A Fluidized bed Pressure Transmitter - Lower
3340-LCV-142 Crossflow Separator Solids Level Control Valve
3340-XV-147 Crossflow Separator underflow Isolation valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 206 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-148 Crossflow Separator drain valve

Table 202: List of Modules of Control for 3340CF105

8.14.3 Interlocks – 3340CF105

T2 Interlock
Crossflow Separator and Hydrofloat
Tag 3340-XV-048A Description
Fluidization Water Isolation Valve
3340SepH
UN SFCPF_SEPHFL1 EM Sub EM 3340CF105
F105
Fail Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Both Fluidisation Water Pump 1 (3340 –


3340 – PU – 112!RUN PU – 112)
AND AND ×
3340 – PU – 114!RUN Fluidisation Water Pump 2 (3340 – PU –
114) are not running

Table 203: List of Interlocks for 3340-XV-048A

T2 Interlock
Tag 3340-FV-141 Description Crossflow Teeter Water flow control valve

UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340CF105


Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 204: List of Interlocks for 3340-FV-141

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 207 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-LCV-142 Description Crossflow Separator U/Flow Control Valve
UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340CF105
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If underflow Isolation valve is closed, close


3340-XV-147.CL ×
valve

Table 205: List of Interlocks for 3340-LCV-142

T2 Interlock
Crossflow Separator U/Flow Isolation
Tag 3340-XV-147 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF105
1 F105
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If downstream hydrofloat is not filled with


3340-PIT-246B.LL water with 3340-PIT-246B on Low Low ×
limit. Then, the valve must close
If downstream Hydrofloat Fluidization
3340- FIT – 244A.L
Water flowrates (A and B) are both Low
AND ×
limit for 2 minutes. Then, the valve must
3340- FIT - 244B.L
close
If downstream hydrofloat has a High High
3340 – LIT – 245.HH solids level for 5 minutes, then the valve ×
must close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 206: List of Interlocks for 3340-XV-147

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 208 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3340-XV-148 Description Crossflow Separator 1 Drain Valve


SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF105
1 F105
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT-143B on
Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-141) Lower than the
Low limit setpoint.
3340-XV-148 cannot AND
×
open All feed valves to all upstream Crossflow
Separators on the tailings launder are
closed (3340-XV-0036E.CL)
AND
The respective Tails Launder Flush Valve
(3340-XV-702.CL) is closed AND the
Flush water pump (3340 – PU – 115!RUN)
is not running.

Table 207: List of Interlocks for 3340-XV-148

8.14.4 Alarms and Process Setpoints – 3340CF105

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340CF105
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-141 Crossflow Teeter Water flowmeter Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
Crossflow Teeter Water feed
Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-141A pressure

Crossflow Teeter Water delivered


Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-141C pressure

Crossflow Separator fluidized bed


Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-LT-142 level transmitter

Fluidized bed pressure


3340-PIT-143B Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
transmitter – Upper

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 209 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fluidized bed pressure


3340-PIT-143A Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
transmitter – Lower

Table 208: Alarms and Process Setpoint 3340CF105

8.14.5 Binary State Messages – 3340CF105

There are no binary state messages for this section


8.14.6 Regulatory Control Loops – 3340CF105

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340CF105
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1002

Table 209: Regulatory Control Loops for 3340CF105

Teeter/fluidisation water is injected into the separator via module isolation valve (3340 - XV –
048A) and teeter water control valve (3340 - FCV –141) which is controlled to a constant fluidised
bed density as measured by two pressure transmitters (3340 - PIT –143A and 143B). There is a
minimum limitation to which the fluidisation water flow can be reduced to.
The overall solids bed level in the Crossflow Separator is measured by a level transmitter (3340
- LIT –142) and controlled by adjusting the opening of the underflow control valve (3340 - LCV –
142).

8.14.7 Advanced Control Loops – 3340CF105

There are no advanced control loops for this section.

8.14.8 Sequence Description – 3340CF105

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 210 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340CF105
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 048A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via Flow rate
2 60
2. Initiate 3340-FC-141 3340-FV-141. Refer to vendor above
seconds seconds
functional specification. minimum
for 10 Sec
2 120
3. Open 3340-XV-147 Underflow Isolation Valve. Open
seconds seconds
Underflow solids level control
3340-LC-143 loop via level control valve 2second 120
6. Initiate Open
3340-LCV-143. Refer to vendor s seconds
functional specification.

Table 210: Start Sequence 3340CF105

The crossflow separator shall follow the following steps during shutdown:
TSQST Stop Sequence Table
UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340CF105
Seq Command Tag Description Transition Min Monitor
Time Time
Stop underflow solids level
control loop via level control valve 2second 120
1. Close 3340-LC-143 Close
3340-LCV-123. Refer to vendor s seconds
functional specification.
2 120
2. Close 3340-XV-147 Underflow Isolation Valve. Close
seconds seconds
Stop Teeter water control loop via
Close 2 60
3. Close 3340-FC-141 3340-FV-121. Refer to vendor
seconds seconds
functional specification.
Close. Wait
for the
hydrofloat 2 60
4. 3340-XV- 048A Teeter water Isolation valve Close
system seconds seconds
3340HF105 to
shutdown first

Table 211: Stop Sequence 3340CF105

If the Crossflow Separator is to not operate for more than approximately two days, the equipment
must be manually drained of solids to prevent cementation within the unit.

8.15 Engineering Module 2 – 3340HF105

8.15.1 Description – 3340HF105

8.15.2 Modules of Control 3340HF105

T1 Control Module

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 211 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340HF105

Tag Service
3340-PIT-241A Pre-Aeration Air Pressure Indicator Transmitter
3340-FIT-241 Pre-Aeration Air Flow Indicator Transmitter - Received
3340-FIT-243 Hydrofloat Pre-Aeration Air Flow Control Valve
3340-FV-243 Pre-Aeration Air Flow Indicator Transmitter - Delivered
3340-PIT-243C Hydrofloat Pre-Aeration Water Flow Control Valve
3340-FV-244A Hydrofloat Pre-Aeration Water Flow Meter
3340-FIT-244A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Received
3340-PIT-244A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Delivered
3340-FIT-244B Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-FV-244B Fluidized Bed Pressure Transmitter – Upper
3340-PIT-244C PRESSURE ELEMENT
3340-PIT-244D PRESSURE ELEMENT
3340-LIT-245 Fluidized Bed Pressure Transmitter – Lower
3340-FV-241 Air Pressure Indicator Transmitter - Received
3340-PIT-241C Air Flow Indicator Transmitter
3340-FV-242 Air Flow Control Valve
3340-FIT-242 Air Pressure Indicator Transmitter - Delivered
3340-PIT-242A Fluidization Water Control Valve
3340-PIT-242D Fluidization Water flow indicator transmitter
3340-PIT-242C Fluidization Water Pressure indicator transmitter - Received
3340-PIT-246B Fluidization Water – bubble generator bypass - flow indicator transmitter
3340-PE-246B Fluidization Water – bubble generator bypass - flow control valve
3340-PE-246A Fluidization Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-246A Fluidization Water Pressure Indicator Transmitter - Delivered
3340-PIT-243A Fluidized Bed Level Indicator Transmitter
3340-LCV-245 Fluidized Bed Level Control Valve
3340-ZE-245 POSITION ELEMENT
3340-XV-247 Underflow Isolation Valve
3340-XV-248 Underflow Drain Valve

Table 212: List of Modules of Control for 3340HF105

8.15.3 Interlocks – 3340HF105

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 212 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Hydrofloat Pre-Aeration Air Flow Control


Tag 3340-FV-241 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF105
1 F105
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-147.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-142.CL ×
control valve is closed, then close valve

Table 213: List of Interlocks for 3340-FV-241

T2 Interlock
Hydrofloat Pre-Aeration Water Flow Control
Tag 3340-FV-242 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF105
1 F105
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL) Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 214: List of Interlocks for 3340-FV-242

T2 Interlock
Tag 3340-FV-243 Description Air Flow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF105
1 F105
Fail Position: Fail Interlock
Motor Type Interlock
Closed (FC) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 213 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-147.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-142.CL ×
control valve is closed, then close valve

Table 215: List of Interlocks for 3340-FV-243

T2 Interlock
Tag 3340-FV-244A Description Fluidization Water Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF105
1 F105
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 216: List of Interlocks for 3340-FV-244A

T2 Interlock
Fluidization Water – bubble generator bypass
Tag 3340-FV-244B Description
- flow control valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF105
1 F105
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 214 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 217: List of Interlocks for 3340-FV-244B

T2 Interlock
Tag 3340-XV-247 Description Hydrofloat Underflow Isolation Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF105
1 F105
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow


Separator not overflowing.
In other words it must be filled with liquid
(3340-PIT-143B not on Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-141) greater than the
Low limit setpoint.

AND

No feed valves to any upstream Crossflow


Separators on the tailings launder are
3340-XV-247 may not open (3340-XV-036E.!OPN)
×
open if
AND

{The respective Tails Launder Flush Valve


(3340-XV-702.!OPN) is not open AND the
Flush water pump (3340 – PU – 115.!RN)
is not running}.

OR

Respective upstream Crossflow Separator


drain valves (3340-XV-198.OPN) are open

OR

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 215 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Upstream Hydrofloat drain valve (3340-


XV-298.OPN) are open}
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 218: List of Interlocks for 3340-XV-247

The hydrofloat underflow discharge slurry must have dilution water assistance in order to be able to be
laundered down the respective tails launder without risk of blockage.

In order to avoid tails launder blockages, only one hydrofloat or crossflow separator may drain at a time
into a respective tails launder.

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be manually
drained of solids to prevent cementation within the unit.

T2 Interlock
Tag 3340-LCV-245 Description Hydrofloat Underflow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF105
1 F105
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If Hydrofloat Outlet Isolation valve is


3340-XV-247.CL ×
closed, then close valve

Table 219: List of Interlocks for 3340-XV-245

T2 Interlock
Tag 3340-XV-248 Description Hydrofloat Drain Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF105
1 F105
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 216 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT- 143B.L
not on Low limit)

AND

Respective Modules Crossflow Separator


has a low teeter water flowrate (3340-FIT-
141.L lower than the Low limit).

AND

All feed valves to the upstream Crossflow


3340-XV-248 may not Separators (3340-XV-0036E.CL) on the
×
open if tailings launder are closed

AND

The respective Tails Launder Flush Valve


(3340-XV-702.!OPN) is not open OR the
Flush water pump (3340 – PU – 115.!RN)
is not running.

OR

Any of the respective upstream Crossflow


Separator drain valves (3340-XV-
198.OPN) are open

Table 220: List of Interlocks for 3340-XV-248

8.15.4 Alarms and Process Setpoints – 3340HF105

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340HF105
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Pre-Aeration Air Pressure Indicator
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-241A Transmitter

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-241 Transmitter - Received

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-241C Transmitter - Delivered

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 217 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Hydrofloat Pre-Aeration Water Flow Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-242 meter

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-242A Received

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-242D Bubble Generator Feed

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-242C Delivered

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-246B Upper

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-246A Lower

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-243A Received

3340-FIT-243 Air Flow Indicator Transmitter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-243C Delivered

3340-FIT-244A Fluidization Water flow meter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-244A indicator transmitter - Received

Fluidization Water – bubble Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


generator bypass - flow indicator
3340-FIT-244B transmitter

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Indicator Transmitter - Bubble
3340-PIT-244C Generator Feed

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-244D Indicator Transmitter - Delivered

Fluidized Bed Level Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-LIT-245 Transmitter

Table 221: Alarms and Process Setpoint 3340HF105

8.15.5 Binary State Messages – 3340HF105

There are no binary state messages for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 218 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

8.15.6 Regulatory Control Loops – 3340HF105

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340HF105
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Table 222: Regulatory Control Loops for 3340HF105

Pre-aeration water and air are injected into the units feed hopper at a controlled rate via PID loop
controller and control valves (3340 - FCV –241 and 3340 - FCV – 242).
Fluidisation teeter water and air are injected into the separator at a controlled rate via PID loop
controller and control valves (3340 - FCV –243 and 3340 - FCV –244A/B). Teeter water flowrate
is used to achieve a controlled fluidised bed density as measured by two pressure transmitters
(3340 - PIT –246A and 246B).
The overall solids bed level in the Hydrofloat is measured by a level transmitter (3340 - LIT –245)
and controlled by adjusting the opening of the underflow control valve (3340 - LCV – 245).

8.15.7 Advanced Control Loops – 3340HF105

There are no advanced control loops for this section.

8.15.8 Sequence Description – 3340HF105

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 219 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340HF105
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 048A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via
3340-FC- 244A Flow rate
3340-FV-244A and 3340-FV- 2 60
2. Initiate And above
244B. Refer to vendor functional seconds seconds
3340-FC-244B minimum
specification.
for 10 Sec
Open &
Hydrofloat Pre-Aeration Water Flow rate
2 60
3. Initiate 3340-FC-242 Control above
seconds seconds
3340-FV-242. minimum
for 10 Sec
3340-XV-247 Open underflow Isolation Valve 2second 60
4. Open Open
3340-XV –247 s seconds
Initiate Hydrofloat Underflow
2second 60
5. Initiate 3340-LC-245 Valve Level Control Open
s seconds
3340-LV-245
(Open &
Flow rate
Pre-Aeration air control loop via 2 60
6. Initiate 3340-FC-241 above
3340-FV-241. seconds seconds
minimum
for 10 Sec
(Open &
Flow rate
Air control loop via 3340-FV- 2 60
7. Initiate 3340-FC-243 above
243. seconds seconds
minimum
for 10 Sec

Table 223: Start Sequence 3340HF105

The hydrofloat should be started before the upstream Crossflow Separator is started.
Frother reagent is only to be initiated once feed is added to the hydrofloat.

The hydrofloat shall follow the following steps during shutdown:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 220 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN SFCPF_SEPHFL1 EM 3340SepHF105 Sub EM 3340HF105
Seq Command Tag Description Transition Min Monitor
Time Time
Stop Air control loop via 3340- 2 60
1. Close 3340-FV-243 Close
FC-243. seconds seconds
Stop Pre-Aeration air control loop 2 60
2. Close 3340-FV-241 Close
via 3340-FC-241. seconds seconds
Close Close Hydrofloat Underflow Valve
2second 60
3. 3340-LV-245 Level Control Close
s seconds
3340-LV-245
Close 3340-XV-247 Close underflow Isolation Valve 2second 60
4. Close
3340-XV –247 s seconds
Close Hydrofloat Pre-Aeration Water Close
2 60
5. 3340-FV-242 Control
seconds seconds
3340-FV-242.
Close 3340-FV- 244A Close
Teeter water control valve 3340- 2 60
6. And
FV-244A and 3340-FV-244B. seconds seconds
3340-FV-244B
Close Teeter water Isolation valve to Close
2 60
7. 3340-XV- 048A close if crossflow separator also
seconds seconds
stopped.

Table 224: Stop Sequence 3340HF105

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be
manually drained of solids to prevent cementation within the unit.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 221 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

9.0 UNIDAD: SFCPF_SEPHFL2

Refer to:
MQ14 - 08 - DR - 3340 - PD1057 Crossflow Distribution
MQ14 - 08 - DR - 3340 - PD1063 Crossflow Separator #6
MQ14 - 08 - DR - 3340 - PD1064 Crossflow Separator #7
MQ14 - 08 - DR - 3340 - PD1065 Crossflow Separator #8
MQ14 - 08 - DR - 3340 - PD1066 Crossflow Separator #9
MQ14 - 08 - DR - 3340 - PD1067 Crossflow Separator #10
MQ14 - 08 - DR - 3340 - PD1073 Hydrofloat #6
MQ14 - 08 - DR - 3340 - PD1074 Hydrofloat #7
MQ14 - 08 - DR - 3340 - PD1075 Hydrofloat #8
MQ14 - 08 - DR - 3340 - PD1076 Hydrofloat #9
MQ14 - 08 - DR - 3340 - PD1077 Hydrofloat #10
MQ15-727-TE-3340-IN1001 Vendor Hydrofloat Control Philosophy
MQ15-727-TE-3340-IN1002 Vendor Crossflow Separator Control Philosophy

A block flow control diagram is depicted below for the SFCPF_SEPHFL2 system.

3340SepHFL106 3340SepHFL107 3340SepHFL108 3340SepHFL109 3340SepHFL110


3340-XV-036A 3340-XV-036B 3340-XV-036C 3340-XV-036D 3340-XV-036E

SFCPF_SepHFL2

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 222 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 28: Blockflow Control Diagram of SFCPF_SEPHFL2 System

The above control unit is broken into five Engineering Module 1’s, each containing two sub Engineering
Module 2’s:
- 3340SepHFL106
o 3340CF106 (Crossflow Separator 6)
o 3340HF106 (Hydrofloat 6)
- 3340SepHFL107
o 3340CF107 (Crossflow Separator 7)
o 3340HF107 (Hydrofloat 7)
- 3340SepHFL108
o 3340CF108 (Crossflow Separator 8)
o 3340HF108 (Hydrofloat 8)
- 3340SepHFL109
o 3340CF109 (Crossflow Separator 9)
o 3340HF109 (Hydrofloat 9)
- 340SepHFL110
o 3340CF110 (Crossflow Separator 10)
o 3340HF110 (Hydrofloat 10)

9.1 Engineering Module 1 – 3340SepHF106

9.1.1 Description – 3340SepHF106

9.1.2 Modules of Control 3340SepHF106

The slurry feed to each Crossflow Separator is isolated via actuated valve.

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM

Tag Service
3340-XV-036A Slurry Isolation Valve – Crossflow Separator 6

Table 225: List of Modules of Control for 3340SepHF106

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 223 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

9.1.3 Interlocks – 3340SepHF106

T2 Interlock
Slurry Isolation Valve – Crossflow
Tag 3340-XV-036A Description
Separator 6
SFCPF_ 3340SepH
UN EM1 EM2
SEPHFL2 F106
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


Crossflow Separator has a high solids Delay time 5
3340-LIT-152.H ×
limit, the valve must close s
Crossflow Separator is not filled with water
Delay time 5
3340-PIT-153B.LL with 3340-PIT-153B on Low Low limit , the ×
s
valve must close
Crossflow Separator teeter water flowrate
Delay time 2
3340-FIT-151.L 3340-FIT-151 low limit exists for 2 ×
minutes
minutes, the valve must close
If only one thickener feed valve (3340-XV-
303 A – C) is closed. A maximum of seven
3340-XV-303A,
Crossflow Separator feed valves may be Delay time 5
3340-XV-303B ×
open. Close the remaining valves, with s
3340-XV-303C
preference for a 4+3 split between
distributors.
3340-XV-303A, If all thickener feed valves (3340-XV-303
Delay time 5
3340-XV-303B A – C) are closed, then the valve must ×
s
3340-XV-303C close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 226: List of Interlocks for 3340-XV-036A

9.1.4 Alarms and Process Setpoints – 3340SepHF106

There are no alarms or process setpoints for this section


9.1.5 Binary State Messages – 3340SepHF106

There are no binary state messages for this section


9.1.6 Regulatory Control Loops – 3340SepHF106

There are no regulatory control loops for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 224 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

9.1.7 Advanced Control Loops – 3340SepHF106

There are no advanced control loops for this section


9.1.8 Description – 3340SepHF106

Crossflow Separator feed slurry is pumped into a Crossflow Separator Distributor (3340 – DB –
104) at a controlled rate. The five-way distributor discharges slurry evenly to the available
Crossflow Separators (3340 – CF – 106 through 110). Should a Crossflow Separator / Hydrofloat
module not be available, it is isolated by closing the respective distributors discharge valve (3340
– XV - 036 A – E).
An individual Crossflow Feed Valve will close (3340 - XV –036 A – E) if the following is true:
 The solids level in the respective Crossflow Separator (3340 - LIT –152 through 192) has
reached a High limit;
 Water level in the Crossflow Separator (3340 - PIT –153B through 193B) is Low;
 The Crossflow Teeter Water flowrate (3340 - FIT – 151 through 191) has reached a low
limit for a specified time;
 All three thickener feed valves (3340 - XV – 303A, 303B, 303C) are closed.
Should only one Thickener Feed Valve be open (3340 - XV – 303A, 303B, 303C), a maximum of
seven crossflow feed valves may be open when considering both distributor 3340-DB103 and
3340-DB - 104. In this instance it is recommended that two valves from one distributor and one
from the other are closed so as not to reduce the crossflow feed pump flowrate below minimum
sedimentation levels.

9.2 Engineering Module 2 – 3340CF106

9.2.1 Description – 3340CF106

9.2.2 Modules of Control 3340CF106

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340CF106

Tag Service
3340-XV-050A Fluidization water to Crossflow-Hydrofloat
3340-FV-151 Crossflow Teeter Water flow control valve
3340-FIT-151 Crossflow Teeter Water flowmeter
3340-PIT-151A Crossflow Teeter Water feed pressure
3340-PIT-151C Crossflow Teeter Water delivered pressure
3340-LT-152 Crossflow Separator fluidized bed level transmitter

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 225 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PIT-153B Fluidized bed pressure transmitter – Upper


3340-PIT-153A Fluidized bed pressure transmitter – Lower
3340-LCV-152 Crossflow Separator Solids Level Control Valve
3340-XV-157 Crossflow Separator underflow Isolation valve
3340-XV-158 Crossflow Separator drain valve

Table 227: List of Modules of Control for 3340CF106

9.2.3 Interlocks – 3340CF106

T2 Interlock
Crossflow Separator and Hydrofloat
Tag 3340-XV-050A Description
Fluidization Water Isolation Valve
3340SepH
UN SFCPF_SEPHFL2 EM Sub EM 3340CF106
F106
Fail Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Both Fluidisation Water Pump 1 (3340 –


3340 – PU – 112!RUN PU – 112)
AND AND ×
3340 – PU – 114!RUN Fluidisation Water Pump 2 (3340 – PU –
114) are not running

Table 228: List of Interlocks for 3340-XV-050A

T2 Interlock
Tag 3340-FV-151 Description Crossflow Teeter Water flow control valve

UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340CF106


Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 226 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 229: List of Interlocks for 3340-FV-151

T2 Interlock
Tag 3340-LCV-152 Description Crossflow Separator U/Flow Control Valve
UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340CF106
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If underflow Isolation valve is closed, close


3340-XV-157.CL ×
valve

Table 230: List of Interlocks for 3340-LCV-152

T2 Interlock
Crossflow Separator U/Flow Isolation
Tag 3340-XV-157 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF106
2 F106
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If downstream hydrofloat is not filled with


3340-PIT-256B.LL water with 3340-PIT-256B on Low Low ×
limit. Then, the valve must close
If downstream Hydrofloat Fluidization
3340- FIT – 254A.L
Water flowrates (A and B) are both Low
AND ×
limit for 2 minutes. Then, the valve must
3340- FIT - 254B.L
close
If downstream hydrofloat has a High High
3340 – LIT – 255.HH solids level for 5 minutes, then the valve ×
must close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 227 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 231: List of Interlocks for 3340-XV-157

T2 Interlock
Tag 3340-XV-158 Description Crossflow Separator Drain Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF106
2 F106
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT-153B on
Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-151) Lower than the
Low limit setpoint.
3340-XV-158 cannot AND
×
open All feed valves to all upstream Crossflow
Separators on the tailings launder are
closed (3340-XV-0036B.CL)
AND
The respective Tails Launder Flush Valve
(3340-XV-700.CL) is closed AND the
Flush water pump (3340 – PU – 115!RUN)
is not running.

Table 232: List of Interlocks for 3340-XV-158

9.2.4 Alarms and Process Setpoints – 3340CF106

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340CF106
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-151 Crossflow Teeter Water flowmeter Refer to vendor control philosophy MQ15-727-TE-3340-IN1002

Crossflow Teeter Water feed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-151A pressure

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 228 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Crossflow Teeter Water delivered Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-151C pressure

Crossflow Separator fluidized bed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-LT-152 level transmitter

Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-153B transmitter – Upper
Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-153A transmitter – Lower

Table 233: Alarms and Process Setpoint 3340CF106

9.2.5 Binary State Messages – 3340CF106

There are no binary state messages for this section


9.2.6 Regulatory Control Loops – 3340CF106

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340CF106
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1002

Table 234: Regulatory Control Loops for 3340CF106

Teeter/fluidisation water is injected into the separator via module isolation valve (3340 - XV –
050A) and teeter water control valve (3340 - FCV –151) which is controlled to a constant fluidised
bed density as measured by two pressure transmitters (3340 - PIT –153A and 153B). There is a
minimum limitation to which the fluidisation water flow can be reduced to.
The overall solids bed level in the Crossflow Separator is measured by a level transmitter (3340
- LIT –152 through 192) and controlled by adjusting the opening of the underflow control valve
(3340 - LCV – 152 through 192).

9.2.7 Advanced Control Loops – 3340CF106

There are no advanced control loops for this section.

9.2.8 Sequence Description – 3340CF106

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 229 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340CF106
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 050A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via Flow rate
2 60
2. Initiate 3340-FC-151 3340-FV-151. Refer to vendor above
seconds seconds
functional specification. minimum
for 10 Sec
2 120
3. Open 3340-XV-157 Underflow Isolation Valve. Open
seconds seconds
Underflow solids level control
3340-LC-153 loop via level control valve 2second 120
4. Initiate Open
3340-LCV-153. Refer to vendor s seconds
functional specification.

Table 235: Start Sequence 3340CF106

The crossflow separator shall follow the following steps during shutdown:
TSQST Stop Sequence Table
UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340CF106
Seq Command Tag Description Transition Min Monitor
Time Time
Stop underflow solids level
control loop via level control valve 2second 120
1. Close 3340-LC-153 Close
3340-LCV-153. Refer to vendor s seconds
functional specification.
2 120
2. Close 3340-XV-157 Underflow Isolation Valve. Close
seconds seconds
Stop Teeter water control loop via
Close 2 60
3. Close 3340-FC-151 3340-FV-151. Refer to vendor
seconds seconds
functional specification.
Close. Wait
for the
hydrofloat 2 60
4. 3340-XV- 050A Teeter water Isolation valve Close
system seconds seconds
3340HF101 to
shutdown first

Table 236: Stop Sequence 3340CF106

If the Crossflow Separator is to not operate for more than approximately two days, the equipment
must be manually drained of solids to prevent cementation within the unit.

9.3 Engineering Module 2 – 3340HF106

9.3.1 Description – 3340HF106

9.3.2 Modules of Control 3340HF106

T1 Control Module

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 230 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340HF106

Tag Service
3340-PIT-251A Pre-Aeration Air Pressure Indicator Transmitter
3340-FIT-251 Pre-Aeration Air Flow Indicator Transmitter - Received
3340-FV-251 Hydrofloat Pre-Aeration Air Flow Control Valve
3340-PIT-251C Pre-Aeration Air Flow Indicator Transmitter - Delivered
3340-FV-252 Hydrofloat Pre-Aeration Water Flow Control Valve
3340-FIT-252 Hydrofloat Pre-Aeration Water Flow Meter
3340-PIT-252A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Received
3340-PIT-252D Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Delivered
3340-PIT-252C Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-256B Fluidized Bed Pressure Transmitter – Upper
3340-PE-256B PRESSURE ELEMENT
3340-PE-256A PRESSURE ELEMENT
3340-PIT-256A Fluidized Bed Pressure Transmitter – Lower
3340-PIT-253A Air Pressure Indicator Transmitter - Received
3340-FIT-253 Air Flow Indicator Transmitter
3340-FV-253 Air Flow Control Valve
3340-PIT-253C Air Pressure Indicator Transmitter - Delivered
3340-FV-254A Fluidization Water Control Valve
3340-FIT-254A Fluidization Water flow indicator transmitter
3340-PIT-254A Fluidization Water Pressure indicator transmitter - Received
3340-FIT-254B Fluidization Water – bubble generator bypass - flow indicator transmitter
3340-FV-254B Fluidization Water – bubble generator bypass - flow control valve
3340-PIT-254C Fluidization Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-254D Fluidization Water Pressure Indicator Transmitter - Delivered
3340-LIT-255 Fluidized Bed Level Indicator Transmitter
3340-LCV-255 Fluidized Bed Level Control Valve
3340-ZE-255 POSITION ELEMENT
3340-XV-257 Underflow Isolation Valve
3340-XV-258 Underflow Drain Valve

Table 237: List of Modules of Control for 3340HF106

9.3.3 Interlocks – 3340HF106

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 231 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Hydrofloat Pre-Aeration Air Flow Control


Tag 3340-FV-251 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF106
2 F106
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-157.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-152.CL ×
control valve is closed, then close valve

Table 238: List of Interlocks for 3340-FV-251

T2 Interlock
Hydrofloat Pre-Aeration Water Flow Control
Tag 3340-FV-252 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF106
2 F106
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL) Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 239: List of Interlocks for 3340-FV-252

T2 Interlock
Tag 3340-FV-253 Description Air Flow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF106
2 F106
Fail Position: Fail Interlock
Motor Type Interlock
Closed (FC) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 232 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-157.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-152.CL ×
control valve is closed, then close valve

Table 240: List of Interlocks for 3340-FV-253

T2 Interlock
Tag 3340-FV-254A Description Fluidization Water Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF106
2 F106
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 241: List of Interlocks for 3340-FV-254A

T2 Interlock
Fluidization Water – bubble generator bypass
Tag 3340-FV-254B Description
- flow control valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF106
2 F106
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 233 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 242: List of Interlocks for 3340-FV-254B

T2 Interlock
Tag 3340-XV-257 Description Hydrofloat Underflow Isolation Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF106
2 F106
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow


Separator not overflowing.
In other words it must be filled with liquid
(3340-PIT-153B not on Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-151) greater than the
Low limit setpoint.

AND

No feed valves to any upstream Crossflow


Separators on the tailings launder are
3340-XV-257 may not open (3340-XV-0036B.!OPN)
×
open if
AND

{The respective Tails Launder Flush Valve


(3340-XV-700.!OPN) is not open AND the
Flush water pump (3340 – PU – 115.!RN)
is not running}.

OR

Respective upstream Crossflow Separator


drain valves (3340-XV-168.OPN) are open

OR

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 234 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Upstream Hydrofloat drain valve (3340-


XV-268.OPN) are open}
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 243: List of Interlocks for 3340-XV-257

The hydrofloat underflow discharge slurry must have dilution water assistance in order to be able to be
laundered down the respective tails launder without risk of blockage.

In order to avoid tails launder blockages, only one hydrofloat or crossflow separator may drain at a time
into a respective tails launder.

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be manually
drained of solids to prevent cementation within the unit.

T2 Interlock
Tag 3340-LCV-255 Description Hydrofloat Underflow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF106
2 F106
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If Hydrofloat Outlet Isolation valve is


3340-XV-257.CL ×
closed, then close valve

Table 244: List of Interlocks for 3340-XV-255

T2 Interlock
Tag 3340-XV-258 Description Hydrofloat Drain Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF106
2 F106
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 235 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT- 153B.L
not on Low limit)

AND

Respective Modules Crossflow Separator


has a low teeter water flowrate (3340-FIT-
151.L lower than the Low limit).

AND

All feed valves to the upstream Crossflow


3340-XV-258 may not Separators (3340-XV-0036B) on the
×
open if tailings launder are closed

AND

The respective Tails Launder Flush Valve


(3340-XV-700.!OPN) is not open OR the
Flush water pump (3340 – PU – 115.!RN)
is not running.

OR

Any of the respective upstream Crossflow


Separator drain valves (3340-XV-
168.OPN) open

Table 245: List of Interlocks for 3340-XV-258

9.3.4 Alarms and Process Setpoints – 3340HF106

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340HF106
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Pre-Aeration Air Pressure Indicator
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-251A Transmitter

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-251 Transmitter - Received

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-251C Transmitter - Delivered

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 236 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Hydrofloat Pre-Aeration Water Flow Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-252 meter

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-252A Received

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-252D Bubble Generator Feed

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-252C Delivered

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-256B Upper

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-256A Lower

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-253A Received

3340-FIT-253 Air Flow Indicator Transmitter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-253C Delivered

3340-FIT-254A Fluidization Water flow meter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-254A indicator transmitter - Received

Fluidization Water – bubble Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


generator bypass - flow indicator
3340-FIT-254B transmitter

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Indicator Transmitter - Bubble
3340-PIT-254C Generator Feed

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-254D Indicator Transmitter - Delivered

Fluidized Bed Level Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-LIT-255 Transmitter

Table 246: Alarms and Process Setpoint 3340HF106

9.3.5 Binary State Messages – 3340HF106

There are no binary state messages for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 237 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

9.3.6 Regulatory Control Loops – 3340HF106

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340HF106
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Table 247: Regulatory Control Loops for 3340HF106

Pre-aeration water and air are injected into the units feed hopper at a controlled rate via PID loop
controller and control valves (3340 - FCV –251 and 3340 - FCV – 252).
Fluidisation teeter water and air are injected into the hydrofloat at a controlled rate via PID loop
controller and control valves (3340 - FCV –253 and 3340 - FCV –254A/B). Teeter water flowrate
is used to achieve a controlled fluidised bed density as measured by two pressure transmitters
(3340 - PIT –256A and 256B).
The overall solids bed level in the Hydrofloat is measured by a level transmitter (3340 - LIT –255)
and controlled by adjusting the opening of the underflow control valve (3340 - LCV – 255).

9.3.7 Advanced Control Loops – 3340HF106

There are no advanced control loops for this section.

9.3.8 Sequence Description – 3340HF106

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 238 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340HF106
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 050A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via
3340-FC- 254A Flow rate
3340-FV-254A and 3340-FV- 2 60
2. Initiate And above
254B. Refer to vendor functional seconds seconds
3340-FC-254B minimum
specification.
for 10 Sec
Open &
Hydrofloat Pre-Aeration Water Flow rate
2 60
3. Initiate 3340-FC-252 Control above
seconds seconds
3340-FV-252. minimum
for 10 Sec
3340-XV-257 Open underflow Isolation Valve 2second 60
4. Open Open
3340-XV –257 s seconds
Initiate Hydrofloat Underflow
2second 60
5. Initiate 3340-LC-255 Valve Level Control Open
s seconds
3340-LV-255
(Open &
Flow rate
Pre-Aeration air control loop via 2 60
6. Initiate 3340-FC-251 above
3340-FV-251. seconds seconds
minimum
for 10 Sec
(Open &
Flow rate
Air control loop via 3340-FV- 2 60
7. Initiate 3340-FC-253 above
253. seconds seconds
minimum
for 10 Sec

Table 248: Start Sequence 3340HF106

The hydrofloat should be started before the upstream Crossflow Separator is started.
Frother reagent is only to be initiated once feed is added to the hydrofloat.

The hydrofloat shall follow the following steps during shutdown:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 239 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN SFCPF_SEPHFL2 EM 3340SepHF106 Sub EM 3340HF106
Seq Command Tag Description Transition Min Monitor
Time Time
Stop Air control loop via 3340- 2 60
1. Close 3340-FV-253 Close
FC-253. seconds seconds
Stop Pre-Aeration air control loop 2 60
2. Close 3340-FV-251 Close
via 3340-FC-251. seconds seconds
Close Close Hydrofloat Underflow Valve
2second 60
3. 3340-LV-255 Level Control Close
s seconds
3340-LV-255
Close 3340-XV-257 Close underflow Isolation Valve 2second 60
4. Close
3340-XV –257 s seconds
Close Hydrofloat Pre-Aeration Water Close
2 60
5. 3340-FV-252 Control
seconds seconds
3340-FV-252.
Close 3340-FV- 254A Close
Teeter water control valve 3340- 2 60
6. And
FV-254A and 3340-FV-254B. seconds seconds
3340-FV-254B
Close Teeter water Isolation valve to Close
2 60
7. 3340-XV- 050A close if crossflow separator also
seconds seconds
stopped.

Table 249: Stop Sequence 3340HF106

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be
manually drained of solids to prevent cementation within the unit.

9.4 Engineering Module 1 – 3340SepHF107

9.4.1 Description – 3340SepHF107

9.4.2 Modules of Control 3340SepHF107

The slurry feed to each Crossflow Separator is isolated via actuated valve.

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM

Tag Service
3340-XV-036B Slurry Isolation Valve – Crossflow Separator 7

Table 250: List of Modules of Control for 3340SepHF107

9.4.3 Interlocks – 3340SepHF107

T2 Interlock
Slurry Isolation Valve – Crossflow
Tag 3340-XV-036B Description
Separator
SFCPF_ 3340SepH
UN EM1 EM2
SEPHFL2 F107

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 240 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


Crossflow Separator has a high solids Delay time 5
3340-LIT-162.H ×
limit, the valve must close s
Crossflow Separator is not filled with water
Delay time 5
3340-PIT-163B.LL with 3340-PIT-163B on Low Low limit , the ×
s
valve must close
Crossflow Separator teeter water flowrate
Delay time 2
3340-FIT-161.L 3340-FIT-161 low limit exists for 2 ×
minutes
minutes, the valve must close
If only one thickener feed valve (3340-XV-
303 A – C) is closed. A maximum of seven
3340-XV-303A,
Crossflow Separator feed valves may be Delay time 5
3340-XV-303B ×
open. Close the remaining valves, with s
3340-XV-303C
preference for a 4+3 split between
distributors.
3340-XV-303A, If all thickener feed valves (3340-XV-303
Delay time 5
3340-XV-303B A – C) are closed, then the valve must ×
s
3340-XV-303C close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 251: List of Interlocks for 3340-XV-036B

9.4.4 Alarms and Process Setpoints – 3340SepHF107

There are no alarms or process setpoints for this section


9.4.5 Binary State Messages – 3340SepHF107

There are no binary state messages for this section


9.4.6 Regulatory Control Loops – 3340SepHF107

There are no regulatory control loops for this section


9.4.7 Advanced Control Loops – 3340SepHF107

There are no advanced control loops for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 241 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

9.4.8 Description – 3340SepHF107

Crossflow Separator feed slurry is pumped into a Crossflow Separator Distributor (3340 – DB –
104) at a controlled rate. The five-way distributor discharges slurry evenly to the available
Crossflow Separators (3340 – CF – 106 through 110). Should a Crossflow Separator / Hydrofloat
module not be available, it is isolated by closing the respective distributors discharge valve (3340
– XV - 036 A – E).
An individual Crossflow Feed Valve will close (3340 - XV –036 A – E) if the following is true:
 The solids level in the respective Crossflow Separator (3340 - LIT –152 through 192) has
reached a High limit;
 Water level in the Crossflow Separator (3340 - PIT –153B through 193B) is Low;
 The Crossflow Teeter Water flowrate (3340 - FIT – 151 through 191) has reached a low
limit for a specified time;
 All three thickener feed valves (3340 - XV – 303A, 303B, 303C) are closed.
Should only one Thickener Feed Valve be open (3340 - XV – 303A, 303B, 303C), a maximum of
seven crossflow feed valves may be open when considering both distributor 3340-DB103 and
3340-DB - 104. In this instance it is recommended that two valves from one distributor and one
from the other are closed so as not to reduce the crossflow feed pump flowrate below minimum
sedimentation levels.

9.5 Engineering Module 2 – 3340CF107

9.5.1 Description – 3340CF107

9.5.2 Modules of Control 3340CF107

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM 3340CF107

Tag Service
3340-XV-052A Fluidization water to Crossflow-Hydrofloat
3340-FV-161 Crossflow Teeter Water flow control valve
3340-FIT-161 Crossflow Teeter Water flowmeter
3340-PIT-161A Crossflow Teeter Water feed pressure
3340-PIT-161C Crossflow Teeter Water delivered pressure
3340-LT-162 Crossflow Separator fluidized bed level transmitter
3340-PIT-163B Fluidized bed pressure transmitter – Upper
3340-PIT-163A Fluidized bed pressure transmitter – Lower
3340-LCV-162 Crossflow Separator Solids Level Control Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 242 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-167 Crossflow Separator underflow Isolation valve


3340-XV-168 Crossflow Separator drain valve

Table 252: List of Modules of Control for 3340CF107

9.5.3 Interlocks – 3340CF107

T2 Interlock
Crossflow Separator and Hydrofloat
Tag 3340-XV-052A Description
Fluidization Water Isolation Valve
3340SepH
UN SFCPF_SEPHFL2 EM Sub EM 3340CF107
F107
Fail Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Both Fluidisation Water Pump 1 (3340 –


3340 – PU – 112!RUN PU – 112)
AND AND ×
3340 – PU – 114!RUN Fluidisation Water Pump 2 (3340 – PU –
114) are not running

Table 253: List of Interlocks for 3340-XV-052A

T2 Interlock
Tag 3340-FV-161 Description Crossflow Teeter Water flow control valve

UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM 3340CF107


Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 254: List of Interlocks for 3340-FV-161

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 243 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-LCV-162 Description Crossflow Separator U/Flow Control Valve
UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM 3340CF107
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If underflow Isolation valve is closed, close


3340-XV-167.CL ×
valve

Table 255: List of Interlocks for 3340-LCV-162

T2 Interlock
Crossflow Separator U/Flow Isolation
Tag 3340-XV-167 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF107
2 F107
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If downstream hydrofloat is not filled with


3340-PIT-266B.LL water with 3340-PIT-266B on Low Low ×
limit. Then, the valve must close
If downstream Hydrofloat Fluidization
3340- FIT – 264A.L
Water flowrates (A and B) are both Low
AND ×
limit for 2 minutes. Then, the valve must
3340- FIT - 264B.L
close
If downstream hydrofloat has a High High
3340 – LIT – 265.HH solids level for 5 minutes, then the valve ×
must close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 256: List of Interlocks for 3340-XV-167

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 244 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3340-XV-168 Description Crossflow Separator Drain Valve


SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF107
2 F107
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT-163B on
Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-161) Lower than the
3340-XV-168 cannot
Low limit setpoint. ×
open
AND
The respective Tails Launder Flush Valve
(3340-XV-700.CL) is closed AND the
Flush water pump (3340 – PU – 115!RUN)
is not running.

Table 257: List of Interlocks for 3340-XV-168

9.5.4 Alarms and Process Setpoints – 3340CF107

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM 3340CF107
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-161 Crossflow Teeter Water flowmeter Refer to vendor control philosophy
Crossflow Teeter Water feed Refer to vendor control philosophy
3340-PIT-161A pressure

Crossflow Teeter Water delivered Refer to vendor control philosophy


3340-PIT-161C pressure

Crossflow Separator fluidized bed Refer to vendor control philosophy


3340-LT-162 level transmitter

Fluidized bed pressure Refer to vendor control philosophy


3340-PIT-163B transmitter – Upper
Fluidized bed pressure Refer to vendor control philosophy
3340-PIT-163A transmitter – Lower

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 245 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 258: Alarms and Process Setpoint 3340CF107

9.5.5 Binary State Messages – 3340CF107

There are no binary state messages for this section


9.5.6 Regulatory Control Loops – 3340CF107

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM 3340CF107
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1002

Table 259: Regulatory Control Loops for 3340CF107

Teeter/fluidisation water is injected into the separator via module isolation valve (3340 - XV –
052A) and teeter water control valve (3340 - FCV –161) which is controlled to a constant fluidised
bed density as measured by two pressure transmitters (3340 - PIT –163A and 163B). There is a
minimum limitation to which the fluidisation water flow can be reduced to.
The overall solids bed level in the Crossflow Separator is measured by a level transmitter (3340
- LIT –152 through 192) and controlled by adjusting the opening of the underflow control valve
(3340 - LCV – 152 through 192).

9.5.7 Advanced Control Loops – 3340CF107

There are no advanced control loops for this section.

9.5.8 Sequence Description – 3340CF107

The crossflow separator shall follow the following steps during start-up:
TSQST Start Sequence Table
UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM 3340CF107
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 052A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via Flow rate
2 60
2. Initiate 3340-FC-161 3340-FV-161. Refer to vendor above
seconds seconds
functional specification. minimum
for 10 Sec
2 120
3. Open 3340-XV-167 Underflow Isolation Valve. Open
seconds seconds
Underflow solids level control
3340-LC-163 loop via level control valve 2second 120
4. Initiate Open
3340-LCV-163. Refer to vendor s seconds
functional specification.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 246 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 260: Start Sequence 3340CF107

The crossflow separator shall follow the following steps during shutdown:
TSQST Stop Sequence Table
UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM 3340CF107
Seq Command Tag Description Transition Min Monitor
Time Time
Stop underflow solids level
control loop via level control valve 2second 120
1. Close 3340-LC-163 Close
3340-LCV-163. Refer to vendor s seconds
functional specification.
2 120
2. Close 3340-XV-167 Underflow Isolation Valve. Close
seconds seconds
Stop Teeter water control loop via
Close 2 60
3. Close 3340-FC-161 3340-FV-161. Refer to vendor
seconds seconds
functional specification.
Close. Wait
for the
hydrofloat 2 60
4. 3340-XV- 052A Teeter water Isolation valve Close
system seconds seconds
3340HF101 to
shutdown first

Table 261: Stop Sequence 3340CF107

If the Crossflow Separator is to not operate for more than approximately two days, the equipment
must be manually drained of solids to prevent cementation within the unit.

9.6 Engineering Module 2 – 3340HF107

9.6.1 Description – 3340HF107

9.6.2 Modules of Control 3340HF107

T1 Control Module
Sub
UN SFCPF_SEPHFL2 EM 3340SepHF1077 3340HF107
EM
Tag Service
3340-PIT-261A Pre-Aeration Air Pressure Indicator Transmitter
3340-FIT-261 Pre-Aeration Air Flow Indicator Transmitter - Received
3340-FV-261 Hydrofloat Pre-Aeration Air Flow Control Valve
3340-PIT-261C Pre-Aeration Air Flow Indicator Transmitter - Delivered
3340-FV-262 Hydrofloat Pre-Aeration Water Flow Control Valve
3340-FIT-262 Hydrofloat Pre-Aeration Water Flow Meter
3340-PIT-262A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Received
3340-PIT-262D Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Delivered

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 247 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PIT-262C Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-266B Fluidized Bed Pressure Transmitter – Upper
3340-PE-266B PRESSURE ELEMENT
3340-PE-266A PRESSURE ELEMENT
3340-PIT-266A Fluidized Bed Pressure Transmitter – Lower
3340-PIT-263A Air Pressure Indicator Transmitter - Received
3340-FIT-263 Air Flow Indicator Transmitter
3340-FV-263 Air Flow Control Valve
3340-PIT-263C Air Pressure Indicator Transmitter - Delivered
3340-FV-264A Fluidization Water Control Valve
3340-FIT-264A Fluidization Water flow indicator transmitter
3340-PIT-264A Fluidization Water Pressure indicator transmitter - Received
3340-FIT-264B Fluidization Water – bubble generator bypass - flow indicator transmitter
3340-FV-264B Fluidization Water – bubble generator bypass - flow control valve
3340-PIT-264C Fluidization Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-264D Fluidization Water Pressure Indicator Transmitter - Delivered
3340-LIT-265 Fluidized Bed Level Indicator Transmitter
3340-LCV-265 Fluidized Bed Level Control Valve
3340-ZE-265 POSITION ELEMENT
3340-XV-267 Underflow Isolation Valve
3340-XV-268 Underflow Drain Valve

Table 262: List of Modules of Control for 3340HF107

9.6.3 Interlocks – 3340HF107

T2 Interlock
Hydrofloat Pre-Aeration Air Flow Control
Tag 3340-FV-261 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF107
2 F107
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Upstream crossflow separator underflow


3340-XV-167.CL ×
isolation valve is closed, then close valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 248 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Upstream crossflow separator underflow


3340-LV-162.CL ×
control valve is closed, then close valve

Table 263: List of Interlocks for 3340-FV-261

T2 Interlock
Hydrofloat Pre-Aeration Water Flow Control
Tag 3340-FV-262 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF107
2 F107
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 264: List of Interlocks for 3340-FV-262

T2 Interlock
Tag 3340-FV-263 Description Air Flow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF107
2 F107
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Upstream crossflow separator underflow


3340-XV-167.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-162.CL ×
control valve is closed, then close valve

Table 265: List of Interlocks for 3340-FV-263

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 249 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-FV-264A Description Fluidization Water Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF107
2 F107
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 266: List of Interlocks for 3340-FV-264A

T2 Interlock
Fluidization Water – bubble generator bypass
Tag 3340-FV-264B Description
- flow control valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF107
2 F107
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 267: List of Interlocks for 3340-FV-264B

T2 Interlock
Tag 3340-XV-267 Description Hydrofloat Underflow Isolation Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF107
2 F107

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 250 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fail Position: Fail


Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow


Separator not overflowing.
In other words it must be filled with liquid
(3340-PIT-163B not on Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-161) greater than the
3340-XV-267 may not Low limit setpoint.
×
open if
AND

{The respective Tails Launder Flush Valve


(3340-XV-700.!OPN) is not open AND the
Flush water pump (3340 – PU – 115.!RN)
is not running}.

BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 268: List of Interlocks for 3340-XV-267

The hydrofloat underflow discharge slurry must have dilution water assistance in order to be able to be
laundered down the respective tails launder without risk of blockage.

In order to avoid tails launder blockages, only one hydrofloat or crossflow separator may drain at a time
into a respective tails launder.

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be manually
drained of solids to prevent cementation within the unit.

T2 Interlock
Tag 3340-LCV-265 Description Hydrofloat Underflow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF107
2 F107
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 251 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If Hydrofloat Outlet Isolation valve is


3340-XV-267.CL ×
closed, then close valve

Table 269: List of Interlocks for 3340-XV-265

T2 Interlock
Tag 3340-XV-268 Description Hydrofloat Drain Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF107
2 F107
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT- 163B.L
not on Low limit)

AND

Respective Modules Crossflow Separator


3340-XV-268 may not has a low teeter water flowrate (3340-FIT-
×
open if 161.L lower than the Low limit).

AND

The respective Tails Launder Flush Valve


(3340-XV-700.!OPN) is not open OR the
Flush water pump (3340 – PU – 115.!RN)
is not running.

Table 270: List of Interlocks for 3340-XV-268

9.6.4 Alarms and Process Setpoints – 3340HF107

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM 3340HF107

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 252 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Pre-Aeration Air Pressure Indicator
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-261A Transmitter

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-261 Transmitter - Received

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-261C Transmitter - Delivered

Hydrofloat Pre-Aeration Water Flow Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-262 meter

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-262A Received

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-262D Bubble Generator Feed

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-262C Delivered

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-266B Upper

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-266A Lower

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-263A Received

3340-FIT-263 Air Flow Indicator Transmitter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-263C Delivered

3340-FIT-264A Fluidization Water flow meter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-264A indicator transmitter - Received

Fluidization Water – bubble Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


generator bypass - flow indicator
3340-FIT-264B transmitter

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Indicator Transmitter - Bubble
3340-PIT-264C Generator Feed

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-264D Indicator Transmitter - Delivered

Fluidized Bed Level Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-LIT-265 Transmitter

Table 271: Alarms and Process Setpoint 3340HF107

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 253 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

9.6.5 Binary State Messages – 3340HF107

There are no binary state messages for this section


9.6.6 Regulatory Control Loops – 3340HF107

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM 3340HF107
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Table 272: Regulatory Control Loops for 3340HF107

Pre-aeration water and air are injected into the units feed hopper at a controlled rate via PID loop
controller and control valves (3340 - FCV –261 and 3340 - FCV – 262).
Fluidisation teeter water and air are injected into the hydrofloat at a controlled rate via PID loop
controller and control valves (3340 - FCV –263 and 3340 - FCV –264A/B). Teeter water flowrate
is used to achieve a controlled fluidised bed density as measured by two pressure transmitters
(3340 - PIT –266A and 266B).
The overall solids bed level in the Hydrofloat is measured by a level transmitter (3340 - LIT –265)
and controlled by adjusting the opening of the underflow control valve (3340 - LCV – 265).

9.6.7 Advanced Control Loops – 3340HF107

There are no advanced control loops for this section.

9.6.8 Sequence Description – 3340HF107

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 254 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM 3340HF107
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 052A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via
3340-FC- 264A Flow rate
3340-FV-264A and 3340-FV- 2 60
2. Initiate And above
264B. Refer to vendor functional seconds seconds
3340-FC-264B minimum
specification.
for 10 Sec
Open &
Hydrofloat Pre-Aeration Water Flow rate
2 60
3. Initiate 3340-FC-262 Control above
seconds seconds
3340-FV-262. minimum
for 10 Sec
3340-XV-267 Open underflow Isolation Valve 2second 60
4. Open Open
3340-XV –267 s seconds
Initiate Hydrofloat Underflow
2second 60
5. Initiate 3340-LC-265 Valve Level Control Open
s seconds
3340-LV-265
(Open &
Flow rate
Pre-Aeration air control loop via 2 60
6. Initiate 3340-FC-261 above
3340-FV-261. seconds seconds
minimum
for 10 Sec
(Open &
Flow rate
Air control loop via 3340-FV- 2 60
7. Initiate 3340-FC-263 above
263. seconds seconds
minimum
for 10 Sec

Table 273: Start Sequence 3340HF107

The hydrofloat should be started before the upstream Crossflow Separator is started.
Frother reagent is only to be initiated once feed is added to the hydrofloat.

The hydrofloat shall follow the following steps during shutdown:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 255 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN SFCPF_SEPHFL2 EM 3340SepHF107 Sub EM 3340HF107
Seq Command Tag Description Transition Min Monitor
Time Time
Stop Air control loop via 3340- 2 60
1. Close 3340-FV-263 Close
FC-263. seconds seconds
Stop Pre-Aeration air control loop 2 60
2. Close 3340-FV-261 Close
via 3340-FC-261. seconds seconds
Close Close Hydrofloat Underflow Valve
2second 60
3. 3340-LV-265 Level Control Close
s seconds
3340-LV-265
Close 3340-XV-267 Close underflow Isolation Valve 2second 60
4. Close
3340-XV –267 s seconds
Close Hydrofloat Pre-Aeration Water Close
2 60
5. 3340-FV-262 Control
seconds seconds
3340-FV-262.
Close 3340-FV- 264A Close
Teeter water control valve 3340- 2 60
6. And
FV-264A and 3340-FV-264B. seconds seconds
3340-FV-264B
Close Teeter water Isolation valve to Close
2 60
7. 3340-XV- 052A close if crossflow separator also
seconds seconds
stopped.

Table 274: Stop Sequence 3340HF107

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be
manually drained of solids to prevent cementation within the unit.

9.8 Engineering Module 1 – 3340SepHF108

9.8.1 Description – 3340SepHF108

9.8.2 Modules of Control 3340SepHF108

The slurry feed to each Crossflow Separator is isolated via actuated valve.

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM

Tag Service
3340-XV-036C Slurry Isolation Valve – Crossflow Separator 8

Table 275: List of Modules of Control for 3340SepHF108

9.8.3 Interlocks – 3340SepHF108

T2 Interlock
Slurry Isolation Valve – Crossflow
Tag 3340-XV-036C Description
Separator
SFCPF_ 3340SepH
UN EM1 EM2
SEPHFL2 F108

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 256 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fail Position
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


Crossflow Separator has a high solids Delay time 5
3340-LIT-172.H ×
limit, the valve must close s
Crossflow Separator is not filled with water
Delay time 5
3340-PIT-173B.LL with 3340-PIT-173B on Low Low limit , the ×
s
valve must close
Crossflow Separator teeter water flowrate
Delay time 2
3340-FIT-171.L 3340-FIT-171 low limit exists for 2 ×
minutes
minutes, the valve must close
If only one thickener feed valve (3340-XV-
303 A – C) is closed. A maximum of seven
3340-XV-303A,
Crossflow Separator feed valves may be Delay time 5
3340-XV-303B ×
open. Close the remaining valves, with s
3340-XV-303C
preference for a 4+3 split between
distributors.
3340-XV-303A, If all thickener feed valves (3340-XV-303
Delay time 5
3340-XV-303B A – C) are closed, then the valve must ×
s
3340-XV-303C close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 276: List of Interlocks for 3340-XV-036C

9.8.4 Alarms and Process Setpoints – 3340SepHF108

There are no alarms or process setpoints for this section


9.8.5 Binary State Messages – 3340SepHF108

There are no binary state messages for this section


9.8.6 Regulatory Control Loops – 3340SepHF108

There are no regulatory control loops for this section


9.8.7 Advanced Control Loops – 3340SepHF108

There are no advanced control loops for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 257 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

9.8.8 Description – 3340SepHF108

Crossflow Separator feed slurry is pumped into a Crossflow Separator Distributor (3340 – DB –
104) at a controlled rate. The five-way distributor discharges slurry evenly to the available
Crossflow Separators (3340 – CF – 106 through 110). Should a Crossflow Separator / Hydrofloat
module not be available, it is isolated by closing the respective distributors discharge valve (3340
– XV - 036 A – E).
An individual Crossflow Feed Valve will close (3340 - XV –036 A – E) if the following is true:
 The solids level in the respective Crossflow Separator (3340 - LIT –152 through 192) has
reached a High limit;
 Water level in the Crossflow Separator (3340 - PIT –153B through 193B) is Low;
 The Crossflow Teeter Water flowrate (3340 - FIT – 151 through 191) has reached a low
limit for a specified time;
 All three thickener feed valves (3340 - XV – 303A, 303B, 303C) are closed.
Should only one Thickener Feed Valve be open (3340 - XV – 303A, 303B, 303C), a maximum of
seven crossflow feed valves may be open when considering both distributor 3340-DB103 and
3340-DB - 104. In this instance it is recommended that two valves from one distributor and one
from the other are closed so as not to reduce the crossflow feed pump flowrate below minimum
sedimentation levels.

9.9 Engineering Module 2 – 3340CF108

9.9.1 Description – 3340CF108

9.9.2 Modules of Control 3340CF108

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340CF108

Tag Service
3340-XV-054A Fluidization water to Crossflow-Hydrofloat
3340-FV-171 Crossflow Teeter Water flow control valve
3340-FIT-171 Crossflow Teeter Water flowmeter
3340-PIT-171A Crossflow Teeter Water feed pressure
3340-PIT-171C Crossflow Teeter Water delivered pressure
3340-LT-172 Crossflow Separator fluidized bed level transmitter
3340-PIT-173B Fluidized bed pressure transmitter – Upper
3340-PIT-173A Fluidized bed pressure transmitter – Lower
3340-LCV-172 Crossflow Separator Solids Level Control Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 258 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-177 Crossflow Separator underflow Isolation valve


3340-XV-178 Crossflow Separator drain valve

Table 277: List of Modules of Control for 3340CF108

9.9.3 Interlocks – 3340CF108

T2 Interlock
Crossflow Separator and Hydrofloat
Tag 3340-XV-054A Description
Fluidization Water Isolation Valve
3340SepH
UN SFCPF_SEPHFL2 EM Sub EM 3340CF108
F108
Fail Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Both Fluidisation Water Pump 1 (3340 –


3340 – PU – 112!RUN PU – 112)
AND AND ×
3340 – PU – 114!RUN Fluidisation Water Pump 2 (3340 – PU –
114) are not running

Table 278: List of Interlocks for 3340-XV-054A

T2 Interlock
Tag 3340-FV-171 Description Crossflow Teeter Water flow control valve

UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340CF108


Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 279: List of Interlocks for 3340-FV-171

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 259 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-LCV-172 Description Crossflow Separator U/Flow Control Valve
UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340CF108
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If underflow Isolation valve is closed, close


3340-XV-177.CL ×
valve

Table 280: List of Interlocks for 3340-LCV-172

T2 Interlock
Crossflow Separator U/Flow Isolation
Tag 3340-XV-177 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF107
2 F107
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If downstream hydrofloat is not filled with


3340-PIT-276B.LL water with 3340-PIT-276B on Low Low ×
limit. Then, the valve must close
If downstream Hydrofloat Fluidization
3340- FIT – 274A.L
Water flowrates (A and B) are both Low
AND ×
limit for 2 minutes. Then, the valve must
3340- FIT - 274B.L
close
If downstream hydrofloat has a High High
3340 – LIT – 275.HH solids level for 5 minutes, then the valve ×
must close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 281: List of Interlocks for 3340-XV-177

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 260 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3340-XV-178 Description Crossflow Separator Drain Valve


SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF108
2 F108
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT-173B on
Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-171) Lower than the
Low limit setpoint.
3340-XV-178 cannot AND
×
open All feed valves to all upstream Crossflow
Separators on the tailings launder are
closed (3340-XV-0036D.CL)
AND
The respective Tails Launder Flush Valve
(3340-XV-701.CL) is closed AND the
Flush water pump (3340 – PU – 115!RUN)
is not running.

Table 282: List of Interlocks for 3340-XV-178

9.9.4 Alarms and Process Setpoints – 3340CF108

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340CF108
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-171 Crossflow Teeter Water flowmeter Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
Crossflow Teeter Water feed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-171A pressure

Crossflow Teeter Water delivered Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-171C pressure

Crossflow Separator fluidized bed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-LT-172 level transmitter

Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-173B transmitter – Upper

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 261 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-173A transmitter – Lower

Table 283: Alarms and Process Setpoint 3340CF108

9.9.5 Binary State Messages – 3340CF108

There are no binary state messages for this section


9.9.6 Regulatory Control Loops – 3340CF108

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340CF108
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1002

Table 284: Regulatory Control Loops for 3340CF108

Teeter/fluidisation water is injected into the separator via module isolation valve (3340 - XV –
054A) and teeter water control valve (3340 - FCV –171) which is controlled to a constant fluidised
bed density as measured by two pressure transmitters (3340 - PIT –173A and 173B). There is a
minimum limitation to which the fluidisation water flow can be reduced to.
The overall solids bed level in the Crossflow Separator is measured by a level transmitter (3340
- LIT –172 through 192) and controlled by adjusting the opening of the underflow control valve
(3340 - LCV – 172 through 192).

9.9.7 Advanced Control Loops – 3340CF108

There are no advanced control loops for this section.

9.9.8 Sequence Description – 3340CF108

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 262 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340CF108
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 054A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via Flow rate
2 60
2. Initiate 3340-FC-171 3340-FV-171. Refer to vendor above
seconds seconds
functional specification. minimum
for 10 Sec
2 120
3. Open 3340-XV-177 Underflow Isolation Valve. Open
seconds seconds
Underflow solids level control
3340-LC-173 loop via level control valve 2second 120
4. Initiate Open
3340-LCV-173. Refer to vendor s seconds
functional specification.

Table 285: Start Sequence 3340CF108

The crossflow separator shall follow the following steps during shutdown:
TSQST Stop Sequence Table
UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340CF108
Seq Command Tag Description Transition Min Monitor
Time Time
Stop underflow solids level
control loop via level control valve 2second 120
1. Close 3340-LC-153 Close
3340-LCV-153. Refer to vendor s seconds
functional specification.
2 120
2. Close 3340-XV-157 Underflow Isolation Valve. Close
seconds seconds
Stop Teeter water control loop via
Close 2 60
3. Close 3340-FC-151 3340-FV-151. Refer to vendor
seconds seconds
functional specification.
Close. Wait
for the
2 60
4. hydrofloat 3340-XV- 054A Teeter water Isolation valve Close
seconds seconds
system to
shutdown first

Table 286: Stop Sequence 3340CF108

If the Crossflow Separator is to not operate for more than approximately two days, the equipment
must be manually drained of solids to prevent cementation within the unit.

9.10 Engineering Module 2 – 3340HF108

9.10.1 Description – 3340HF108

9.10.2 Modules of Control 3340HF108

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340HF108

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 263 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag Service
3340-PIT-271A Pre-Aeration Air Pressure Indicator Transmitter
3340-FIT-271 Pre-Aeration Air Flow Indicator Transmitter - Received
3340-FV-271 Hydrofloat Pre-Aeration Air Flow Control Valve
3340-PIT-271C Pre-Aeration Air Flow Indicator Transmitter - Delivered
3340-FV-272 Hydrofloat Pre-Aeration Water Flow Control Valve
3340-FIT-272 Hydrofloat Pre-Aeration Water Flow Meter
3340-PIT-272A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Received
3340-PIT-272D Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Delivered
3340-PIT-272C Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-276B Fluidized Bed Pressure Transmitter – Upper
3340-PE-276B PRESSURE ELEMENT
3340-PE-276A PRESSURE ELEMENT
3340-PIT-276A Fluidized Bed Pressure Transmitter – Lower
3340-PIT-273A Air Pressure Indicator Transmitter - Received
3340-FIT-273 Air Flow Indicator Transmitter
3340-FV-273 Air Flow Control Valve
3340-PIT-273C Air Pressure Indicator Transmitter - Delivered
3340-FV-274A Fluidization Water Control Valve
3340-FIT-274A Fluidization Water flow indicator transmitter
3340-PIT-274A Fluidization Water Pressure indicator transmitter - Received
3340-FIT-274B Fluidization Water – bubble generator bypass - flow indicator transmitter
3340-FV-274B Fluidization Water – bubble generator bypass - flow control valve
3340-PIT-274C Fluidization Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-274D Fluidization Water Pressure Indicator Transmitter - Delivered
3340-LIT-275 Fluidized Bed Level Indicator Transmitter
3340-LCV-275 Fluidized Bed Level Control Valve
3340-ZE-275 POSITION ELEMENT
3340-XV-277 Underflow Isolation Valve
3340-XV-278 Underflow Drain Valve

Table 287: List of Modules of Control for 3340HF108

9.10.3 Interlocks – 3340HF108

T2 Interlock
Hydrofloat Pre-Aeration Air Flow Control
Tag 3340-FV-271 Description
Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 264 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF108
2 F108
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-177.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-172.CL ×
control valve is closed, then close valve

Table 288: List of Interlocks for 3340-FV-271

T2 Interlock
Hydrofloat Pre-Aeration Water Flow Control
Tag 3340-FV-272 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF108
2 F108
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 289: List of Interlocks for 3340-FV-272

T2 Interlock
Tag 3340-FV-273 Description Air Flow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF108
2 F108
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 265 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Upstream crossflow separator underflow


3340-XV-177.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-172.CL ×
control valve is closed, then close valve

Table 290: List of Interlocks for 3340-FV-273

T2 Interlock
Tag 3340-FV-274A Description Fluidization Water Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF108
2 F108
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 291: List of Interlocks for 3340-FV-274A

T2 Interlock
Fluidization Water – bubble generator bypass
Tag 3340-FV-274B Description
- flow control valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF108
2 F108
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 266 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 292: List of Interlocks for 3340-FV-274B

T2 Interlock
Tag 3340-XV-277 Description Hydrofloat Underflow Isolation Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF108
2 F108
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow


Separator not overflowing.
In other words it must be filled with liquid
(3340-PIT-173B not on Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-171) greater than the
Low limit setpoint.

AND

No feed valves to any upstream Crossflow


Separators on the tailings launder are
open (3340-XV-0036D.!OPN)
3340-XV-277 may not
AND ×
open if
{The respective Tails Launder Flush Valve
(3340-XV-701.!OPN) is not open AND the
Flush water pump (3340 – PU – 115.!RN)
is not running}.

OR

Respective upstream Crossflow Separator


drain valves (3340-XV-188.OPN) are open

OR

Upstream Hydrofloat drain valve (3340-


XV-288.OPN) are open}
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 267 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 293: List of Interlocks for 3340-XV-277

The hydrofloat underflow discharge slurry must have dilution water assistance in order to be able to be
laundered down the respective tails launder without risk of blockage.

In order to avoid tails launder blockages, only one hydrofloat or crossflow separator may drain at a time
into a respective tails launder.

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be manually
drained of solids to prevent cementation within the unit.

T2 Interlock
Tag 3340-LCV-275 Description Hydrofloat Underflow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF108
2 F108
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If Hydrofloat Outlet Isolation valve is


3340-XV-277.CL ×
closed, then close valve

Table 294: List of Interlocks for 3340-XV-275

T2 Interlock
Tag 3340-XV-278 Description Hydrofloat Drain Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF108
2 F108
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Respective modules’ Crossflow Separator


3340-XV-278 may not
is not filled with liquid (3340-PIT- 173B.L ×
open if
not on Low limit)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 268 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

AND

Respective Modules Crossflow Separator


has a low teeter water flowrate (3340-FIT-
171.L lower than the Low limit).

AND

All feed valves to the upstream Crossflow


Separators (3340-XV-0036D) on the
tailings launder are closed

AND

The respective Tails Launder Flush Valve


(3340-XV-701.!OPN) is not open OR the
Flush water pump (3340 – PU – 115.!RN)
is not running.

OR

Any of the respective upstream Crossflow


Separator drain valves (3340-XV-
188.OPN) open

Table 295: List of Interlocks for 3340-XV-278

9.10.4 Alarms and Process Setpoints – 3340HF108

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340HF108
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Pre-Aeration Air Pressure Indicator
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-271A Transmitter

Pre-Aeration Air Flow Indicator


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-FIT-271 Transmitter - Received

Pre-Aeration Air Flow Indicator


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-271C Transmitter - Delivered

Hydrofloat Pre-Aeration Water Flow


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-FIT-272 meter

Hydrofloat Pre-Aeration Water


Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-272A Received

Hydrofloat Pre-Aeration Water


Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-272D Bubble Generator Feed

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 269 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Hydrofloat Pre-Aeration Water


Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-272C Delivered

Fluidized Bed Pressure Transmitter –


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-276B Upper

Fluidized Bed Pressure Transmitter –


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-276A Lower

Air Pressure Indicator Transmitter -


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-273A Received

3340-FIT-273 Air Flow Indicator Transmitter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
Air Pressure Indicator Transmitter -
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-273C Delivered

3340-FIT-274A Fluidization Water flow meter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Fluidization Water Pressure


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-274A indicator transmitter - Received

Fluidization Water – bubble


generator bypass - flow indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-FIT-274B transmitter

Fluidization Water Pressure


Indicator Transmitter - Bubble Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-274C Generator Feed

Fluidization Water Pressure


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-274D Indicator Transmitter - Delivered

Fluidized Bed Level Indicator


Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-LIT-275 Transmitter

Table 296: Alarms and Process Setpoint 3340HF108

9.10.5 Binary State Messages – 3340HF108

There are no binary state messages for this section


9.10.6 Regulatory Control Loops – 3340HF108

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340HF108
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Table 297: Regulatory Control Loops for 3340HF108

Pre-aeration water and air are injected into the units feed hopper at a controlled rate via PID loop
controller and control valves (3340 - FCV –271 and 3340 - FCV – 272).
Fluidisation teeter water and air are injected into the hydrofloat at a controlled rate via PID loop
controller and control valves (3340 - FCV –273 and 3340 - FCV –274A/B). Teeter water flowrate

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 270 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

is used to achieve a controlled fluidised bed density as measured by two pressure transmitters
(3340 - PIT –276A and 276B).
The overall solids bed level in the Hydrofloat is measured by a level transmitter (3340 - LIT –275)
and controlled by adjusting the opening of the underflow control valve (3340 - LCV – 275).

9.10.7 Advanced Control Loops – 3340HF108

There are no advanced control loops for this section.

9.10.8 Sequence Description – 3340HF108

The crossflow separator shall follow the following steps during start-up:
TSQST Start Sequence Table
UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340HF108
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 054A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via
3340-FC- 274A Flow rate
3340-FV-274A and 3340-FV- 2 60
2. Initiate And above
274B. Refer to vendor functional seconds seconds
3340-FC-274B minimum
specification.
for 10 Sec
Open &
Hydrofloat Pre-Aeration Water Flow rate
2 60
3. Initiate 3340-FC-272 Control above
seconds seconds
3340-FV-272. minimum
for 10 Sec
3340-XV-277 Open underflow Isolation Valve 2second 60
4. Open Open
3340-XV –277 s seconds
Initiate Hydrofloat Underflow
2second 60
5. Initiate 3340-LC-275 Valve Level Control Open
s seconds
3340-LV-275
(Open &
Flow rate
Pre-Aeration air control loop via 2 60
6. Initiate 3340-FC-271 above
3340-FV-271. seconds seconds
minimum
for 10 Sec
(Open &
Flow rate
Air control loop via 3340-FV- 2 60
7. Initiate 3340-FC-273 above
273. seconds seconds
minimum
for 10 Sec

Table 298: Start Sequence 3340HF108

The hydrofloat should be started before the upstream Crossflow Separator is started.
Frother reagent is only to be initiated once feed is added to the hydrofloat.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 271 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The hydrofloat shall follow the following steps during shutdown:


TSQST Stop Sequence Table
UN SFCPF_SEPHFL2 EM 3340SepHF108 Sub EM 3340HF108
Seq Command Tag Description Transition Min Monitor
Time Time
Stop Air control loop via 3340- 2 60
1. Close 3340-FV-273 Close
FC-273. seconds seconds
Stop Pre-Aeration air control loop 2 60
2. Close 3340-FV-271 Close
via 3340-FC-271. seconds seconds
Close Close Hydrofloat Underflow Valve
2second 60
3. 3340-LV-275 Level Control Close
s seconds
3340-LV-275
Close 3340-XV-277 Close underflow Isolation Valve 2second 60
4. Close
3340-XV –277 s seconds
Close Hydrofloat Pre-Aeration Water Close
2 60
5. 3340-FV-272 Control
seconds seconds
3340-FV-272.
Close 3340-FV- 274A Close
Teeter water control valve 3340- 2 60
6. And
FV-274A and 3340-FV-274B. seconds seconds
3340-FV-274B
Close Teeter water Isolation valve to Close
2 60
7. 3340-XV- 054A close if crossflow separator also
seconds seconds
stopped.

Table 299: Stop Sequence 3340HF108

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be
manually drained of solids to prevent cementation within the unit.

9.12 Engineering Module 1 – 3340SepHF109

9.12.1 Description – 3340SepHF109

9.12.2 Modules of Control 3340SepHF109

The slurry feed to each Crossflow Separator is isolated via actuated valve.

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM

Tag Service
3340-XV-036D Slurry Isolation Valve – Crossflow Separator 9

Table 300: List of Modules of Control for 3340SepHF109

9.12.3 Interlocks – 3340SepHF109

T2 Interlock
Slurry Isolation Valve – Crossflow
Tag 3340-XV-036D Description
Separator

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 272 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

SFCPF_ 3340SepH
UN EM1 EM2
SEPHFL2 F109
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


Crossflow Separator has a high solids Delay time 5
3340-LIT-182.H ×
limit, the valve must close s
Crossflow Separator is not filled with water
Delay time 5
3340-PIT-183B.LL with 3340-PIT-183B on Low Low limit , the ×
s
valve must close
Crossflow Separator teeter water flowrate
Delay time 2
3340-FIT-181.L 3340-FIT-181 low limit exists for 2 ×
minutes
minutes, the valve must close
If only one thickener feed valve (3340-XV-
303 A – C) is closed. A maximum of seven
3340-XV-303A,
Crossflow Separator feed valves may be Delay time 5
3340-XV-303B ×
open. Close the remaining valves, with s
3340-XV-303C
preference for a 4+3 split between
distributors.
3340-XV-303A, If all thickener feed valves (3340-XV-303
Delay time 5
3340-XV-303B A – C) are closed, then the valve must ×
s
3340-XV-303C close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 301: List of Interlocks for 3340-XV-036D

9.12.4 Alarms and Process Setpoints – 3340SepHF109

There are no alarms or process setpoints for this section


9.12.5 Binary State Messages – 3340SepHF109

There are no binary state messages for this section


9.12.6 Regulatory Control Loops – 3340SepHF109

There are no regulatory control loops for this section


9.12.7 Advanced Control Loops – 3340SepHF109

There are no advanced control loops for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 273 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

9.12.8 Description – 3340SepHF109

Crossflow Separator feed slurry is pumped into a Crossflow Separator Distributor (3340 – DB –
104) at a controlled rate. The five-way distributor discharges slurry evenly to the available
Crossflow Separators (3340 – CF – 106 through 110). Should a Crossflow Separator / Hydrofloat
module not be available, it is isolated by closing the respective distributors discharge valve (3340
– XV - 036 A – E).
An individual Crossflow Feed Valve will close (3340 - XV –036 A – E) if the following is true:
 The solids level in the respective Crossflow Separator (3340 - LIT –152 through 192) has
reached a High limit;
 Water level in the Crossflow Separator (3340 - PIT –153B through 193B) is Low;
 The Crossflow Teeter Water flowrate (3340 - FIT – 151 through 191) has reached a low
limit for a specified time;
 All three thickener feed valves (3340 - XV – 303A, 303B, 303C) are closed.
Should only one Thickener Feed Valve be open (3340 - XV – 303A, 303B, 303C), a maximum of
seven crossflow feed valves may be open when considering both distributor 3340-DB103 and
3340-DB - 104. In this instance it is recommended that two valves from one distributor and one
from the other are closed so as not to reduce the crossflow feed pump flowrate below minimum
sedimentation levels.

9.13 Engineering Module 2 – 3340CF109

9.13.1 Description – 3340CF109

9.13.2 Modules of Control 3340CF109

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340CF109

Tag Service
3340-XV-056A Fluidization water to Crossflow-Hydrofloat
3340-FV-181 Crossflow Teeter Water flow control valve
3340-FIT-181 Crossflow Teeter Water flowmeter
3340-PIT-181A Crossflow Teeter Water feed pressure
3340-PIT-181C Crossflow Teeter Water delivered pressure
3340-LT-182 Crossflow Separator fluidized bed level transmitter
3340-PIT-183B Fluidized bed pressure transmitter – Upper
3340-PIT-183A Fluidized bed pressure transmitter – Lower
3340-LCV-182 Crossflow Separator Solids Level Control Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 274 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-187 Crossflow Separator underflow Isolation valve


3340-XV-188 Crossflow Separator drain valve

Table 302: List of Modules of Control for 3340CF109

9.13.3 Interlocks – 3340CF109

T2 Interlock
Crossflow Separator and Hydrofloat
Tag 3340-XV-056A Description
Fluidization Water Isolation Valve
3340SepH
UN SFCPF_SEPHFL2 EM Sub EM 3340CF109
F109
Fail Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Both Fluidisation Water Pump 1 (3340 –


3340 – PU – 112!RUN PU – 112)
AND AND ×
3340 – PU – 114!RUN Fluidisation Water Pump 2 (3340 – PU –
114) are not running

Table 303: List of Interlocks for 3340-XV-056A

T2 Interlock
Tag 3340-FV-181 Description Crossflow Teeter Water flow control valve

UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340CF109


Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 304: List of Interlocks for 3340-FV-181

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 275 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-LCV-182 Description Crossflow Separator U/Flow Control Valve
UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340CF109
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If underflow Isolation valve is closed, close


3340-XV-187.CL ×
valve

Table 305: List of Interlocks for 3340-LCV-182

T2 Interlock
Crossflow Separator U/Flow Isolation
Tag 3340-XV-187 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF109
2 F109
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If downstream hydrofloat is not filled with


3340-PIT-286B.LL water with 3340-PIT-286B on Low Low ×
limit. Then, the valve must close
If downstream Hydrofloat Fluidization
3340- FIT – 284A.L
Water flowrates (A and B) are both Low
AND ×
limit for 2 minutes. Then, the valve must
3340- FIT - 284B.L
close
If downstream hydrofloat has a High High
3340 – LIT – 285.HH solids level for 5 minutes, then the valve ×
must close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 306: List of Interlocks for 3340-XV-187

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 276 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3340-XV-188 Description Crossflow Separator Drain Valve


SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF109
2 F109
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT-183B on
Low limit)
AND
Crossflow Separator has a teeter water
3340-XV-188 cannot flowrate (3340-FIT-181) Lower than the
×
open Low limit setpoint.
AND
The respective Tails Launder Flush Valve
(3340-XV-701.CL) is closed AND the
Flush water pump (3340 – PU – 115!RUN)
is not running.

Table 307: List of Interlocks for 3340-XV-188

9.13.4 Alarms and Process Setpoints – 3340CF109

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340CF109
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-181 Crossflow Teeter Water flowmeter Refer to vendor control philosophy MQ15-727-TE-3340-IN1002

Crossflow Teeter Water feed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-181A pressure

Crossflow Teeter Water delivered Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-181C pressure

Crossflow Separator fluidized bed Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-LT-182 level transmitter

Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002


3340-PIT-183B transmitter – Upper
Fluidized bed pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-183A transmitter – Lower

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 277 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 308: Alarms and Process Setpoint 3340CF109

9.13.5 Binary State Messages – 3340CF109

There are no binary state messages for this section


9.13.6 Regulatory Control Loops – 3340CF109

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340CF109
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy

Table 309: Regulatory Control Loops for 3340CF109

Teeter/fluidisation water is injected into the separator via module isolation valve (3340 - XV –
056A) and teeter water control valve (3340 - FCV –181) which is controlled to a constant fluidised
bed density as measured by two pressure transmitters (3340 - PIT –183A and 183B). There is a
minimum limitation to which the fluidisation water flow can be reduced to.
The overall solids bed level in the Crossflow Separator is measured by a level transmitter (3340
- LIT –152 through 192) and controlled by adjusting the opening of the underflow control valve
(3340 - LCV – 152 through 192).

9.13.7 Advanced Control Loops – 3340CF109

There are no advanced control loops for this section.

9.13.8 Sequence Description – 3340CF109

The crossflow separator shall follow the following steps during start-up:
TSQST Start Sequence Table
UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340CF109
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 056A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via Flow rate
2 60
2. Initiate 3340-FC-181 3340-FV-181. Refer to vendor above
seconds seconds
functional specification. minimum
for 10 Sec
2 120
3. Open 3340-XV-187 Underflow Isolation Valve. Open
seconds seconds
Underflow solids level control
3340-LC-183 loop via level control valve 2second 120
4. Initiate Open
3340-LCV-183. Refer to vendor s seconds
functional specification.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 278 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 310: Start Sequence 3340CF109

The crossflow separator shall follow the following steps during shutdown:
TSQST Stop Sequence Table
UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340CF109
Seq Command Tag Description Transition Min Monitor
Time Time
Stop underflow solids level
control loop via level control valve 2second 120
1. Close 3340-LC-183 Close
3340-LCV-183. Refer to vendor s seconds
functional specification.
2 120
2. Close 3340-XV-187 Underflow Isolation Valve. Close
seconds seconds
Stop Teeter water control loop via
Close 2 60
3. Close 3340-FC-181 3340-FV-181. Refer to vendor
seconds seconds
functional specification.
Close. Wait
for the
2 60
4. hydrofloat 3340-XV- 056A Teeter water Isolation valve Close
seconds seconds
system to
shutdown first

Table 311: Stop Sequence 3340CF109

If the Crossflow Separator is to not operate for more than approximately two days, the equipment
must be manually drained of solids to prevent cementation within the unit.

9.14 Engineering Module 2 – 3340HF109

9.14.1 Description – 3340HF109

9.14.2 Modules of Control 3340HF109

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340HF109

Tag Service
3340-PIT-281A Pre-Aeration Air Pressure Indicator Transmitter
3340-FIT-281 Pre-Aeration Air Flow Indicator Transmitter - Received
3340-FV-281 Hydrofloat Pre-Aeration Air Flow Control Valve
3340-PIT-281C Pre-Aeration Air Flow Indicator Transmitter - Delivered
3340-FV-282 Hydrofloat Pre-Aeration Water Flow Control Valve
3340-FIT-282 Hydrofloat Pre-Aeration Water Flow Meter
3340-PIT-282A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Received
3340-PIT-282D Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Delivered
3340-PIT-282C Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-286B Fluidized Bed Pressure Transmitter – Upper

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 279 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PE-286B PRESSURE ELEMENT


3340-PE-286A PRESSURE ELEMENT
3340-PIT-286A Fluidized Bed Pressure Transmitter – Lower
3340-PIT-283A Air Pressure Indicator Transmitter - Received
3340-FIT-283 Air Flow Indicator Transmitter
3340-FV-283 Air Flow Control Valve
3340-PIT-283C Air Pressure Indicator Transmitter - Delivered
3340-FV-284A Fluidization Water Control Valve
3340-FIT-284A Fluidization Water flow indicator transmitter
3340-PIT-284A Fluidization Water Pressure indicator transmitter - Received
3340-FIT-284B Fluidization Water – bubble generator bypass - flow indicator transmitter
3340-FV-284B Fluidization Water – bubble generator bypass - flow control valve
3340-PIT-284C Fluidization Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-284D Fluidization Water Pressure Indicator Transmitter - Delivered
3340-LIT-285 Fluidized Bed Level Indicator Transmitter
3340-LCV-285 Fluidized Bed Level Control Valve
3340-ZE-285 POSITION ELEMENT
3340-XV-287 Underflow Isolation Valve
3340-XV-288 Underflow Drain Valve

Table 312: List of Modules of Control for 3340HF109

9.14.3 Interlocks – 3340HF109

T2 Interlock
Hydrofloat Pre-Aeration Air Flow Control
Tag 3340-FV-281 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF109
2 F109
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Upstream crossflow separator underflow


3340-XV-187.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-182.CL ×
control valve is closed, then close valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 280 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 313: List of Interlocks for 3340-FV-281

T2 Interlock
Hydrofloat Pre-Aeration Water Flow Control
Tag 3340-FV-282 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF109
2 F109
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 314: List of Interlocks for 3340-FV-282

T2 Interlock
Tag 3340-FV-283 Description Air Flow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF109
2 F109
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Upstream crossflow separator underflow


3340-XV-187.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-182.CL ×
control valve is closed, then close valve

Table 315: List of Interlocks for 3340-FV-283

T2 Interlock
Tag 3340-FV-284A Description Fluidization Water Control Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 281 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF109
2 F109
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 316: List of Interlocks for 3340-FV-284A

T2 Interlock
Fluidization Water – bubble generator bypass
Tag 3340-FV-284B Description
- flow control valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF109
2 F109
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 317: List of Interlocks for 3340-FV-284B

T2 Interlock
Tag 3340-XV-287 Description Hydrofloat Underflow Isolation Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF109
2 F109
Fail Position:
Keep Last (KL) Interlock
Motor Type Interlock
Safe Position: Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 282 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow


Separator not overflowing.
In other words it must be filled with liquid
(3340-PIT-183B not on Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-181) greater than the
3340-XV-287 may not
Low limit setpoint. ×
open if
AND

{The respective Tails Launder Flush Valve


(3340-XV-701.!OPN) is not open AND the
Flush water pump (3340 – PU – 115.!RN)
is not running}.
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 318: List of Interlocks for 3340-XV-287

The hydrofloat underflow discharge slurry must have dilution water assistance in order to be able to be
laundered down the respective tails launder without risk of blockage.

In order to avoid tails launder blockages, only one hydrofloat or crossflow separator may drain at a time
into a respective tails launder.

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be manually
drained of solids to prevent cementation within the unit.

T2 Interlock
Tag 3340-LCV-285 Description Hydrofloat Underflow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF109
2 F109
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 283 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

If Hydrofloat Outlet Isolation valve is


3340-XV-287.CL ×
closed, then close valve

Table 319: List of Interlocks for 3340-XV-285

T2 Interlock
Tag 3340-XV-288 Description Hydrofloat Drain Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF109
2 F109
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT- 183B.L
not on Low limit)

AND

Respective Modules Crossflow Separator


3340-XV-288 may not has a low teeter water flowrate (3340-FIT-
×
open if 181.L lower than the Low limit).

AND

The respective Tails Launder Flush Valve


(3340-XV-701.!OPN) is not open OR the
Flush water pump (3340 – PU – 115.!RN)
is not running.

Table 320: List of Interlocks for 3340-XV-288

9.14.4 Alarms and Process Setpoints – 3340HF109

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340HF109
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Pre-Aeration Air Pressure Indicator
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-281A Transmitter

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 284 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-281 Transmitter - Received

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-281C Transmitter - Delivered

Hydrofloat Pre-Aeration Water Flow Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-282 meter

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-282A Received

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-282D Bubble Generator Feed

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-282C Delivered

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-286B Upper

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-286A Lower

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-283A Received

3340-FIT-283 Air Flow Indicator Transmitter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-273C Delivered

3340-FIT-284A Fluidization Water flow meter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-284A indicator transmitter - Received

Fluidization Water – bubble Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


generator bypass - flow indicator
3340-FIT-284B transmitter

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Indicator Transmitter - Bubble
3340-PIT-284C Generator Feed

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-284D Indicator Transmitter - Delivered

Fluidized Bed Level Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-LIT-285 Transmitter

Table 321: Alarms and Process Setpoint 3340HF109

9.14.5 Binary State Messages – 3340HF109

There are no binary state messages for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 285 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

9.14.6 Regulatory Control Loops – 3340HF109

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340HF109
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Table 322: Regulatory Control Loops for 3340HF109

Pre-aeration water and air are injected into the units feed hopper at a controlled rate via PID loop
controller and control valves (3340 - FCV –281 and 3340 - FCV – 282).
Fluidisation teeter water and air are injected into the hydrofloat at a controlled rate via PID loop
controller and control valves (3340 - FCV –283 and 3340 - FCV –284A/B). Teeter water flowrate
is used to achieve a controlled fluidised bed density as measured by two pressure transmitters
(3340 - PIT –286A and 286B).
The overall solids bed level in the Hydrofloat is measured by a level transmitter (3340 - LIT –285)
and controlled by adjusting the opening of the underflow control valve (3340 - LCV – 285).

9.14.7 Advanced Control Loops – 3340HF109

There are no advanced control loops for this section.

9.14.8 Sequence Description – 3340HF109

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 286 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340HF109
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 056A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via
3340-FC- 284A Flow rate
3340-FV-284A and 3340-FV- 2 60
2. Initiate And above
284B. Refer to vendor functional seconds seconds
3340-FC-284B minimum
specification.
for 10 Sec
Open &
Hydrofloat Pre-Aeration Water Flow rate
2 60
3. Initiate 3340-FC-282 Control above
seconds seconds
3340-FV-282. minimum
for 10 Sec
3340-XV-287 Open underflow Isolation Valve 2second 60
4. Open Open
3340-XV –287 s seconds
Initiate Hydrofloat Underflow
2second 60
5. Initiate 3340-LC-285 Valve Level Control Open
s seconds
3340-LV-285
(Open &
Flow rate
Pre-Aeration air control loop via 2 60
6. Initiate 3340-FC-281 above
3340-FV-281. seconds seconds
minimum
for 10 Sec
(Open &
Flow rate
Air control loop via 3340-FV- 2 60
7. Initiate 3340-FC-283 above
283. seconds seconds
minimum
for 10 Sec

Table 323: Start Sequence 3340HF109

The hydrofloat should be started before the upstream Crossflow Separator is started.
Frother reagent is only to be initiated once feed is added to the hydrofloat.

The hydrofloat shall follow the following steps during shutdown:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 287 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN SFCPF_SEPHFL2 EM 3340SepHF109 Sub EM 3340HF109
Seq Command Tag Description Transition Min Monitor
Time Time
Stop Air control loop via 3340- 2 60
1. Close 3340-FV-283 Close
FC-283. seconds seconds
Stop Pre-Aeration air control loop 2 60
2. Close 3340-FV-281 Close
via 3340-FC-281. seconds seconds
Close Close Hydrofloat Underflow Valve
2second 60
3. 3340-LV-285 Level Control Close
s seconds
3340-LV-285
Close 3340-XV-287 Close underflow Isolation Valve 2second 60
4. Close
3340-XV –287 s seconds
Close Hydrofloat Pre-Aeration Water Close
2 60
5. 3340-FV-282 Control
seconds seconds
3340-FV-282.
Close 3340-FV- 284A Close
Teeter water control valve 3340- 2 60
6. And
FV-284A and 3340-FV-284B. seconds seconds
3340-FV-284B
Close Teeter water Isolation valve to Close
2 60
7. 3340-XV- 056A close if crossflow separator also
seconds seconds
stopped.

Table 324: Stop Sequence 3340HF109

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be
manually drained of solids to prevent cementation within the unit.

9.16 Engineering Module 1 – 3340SepHF110

9.16.1 Description – 3340SepHF110

9.16.2 Modules of Control 3340SepHF110

The slurry feed to each Crossflow Separator is isolated via actuated valve.

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM

Tag Service
3340-XV-036E Slurry Isolation Valve – Crossflow Separator 10

Table 325: List of Modules of Control for 3340SepHF110

9.16.3 Interlocks – 3340SepHF110

T2 Interlock
Slurry Isolation Valve – Crossflow
Tag 3340-XV-036E Description
Separator
SFCPF_ 3340SepH
UN EM1 EM2
SEPHFL2 F110

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 288 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Crossflow Separator has a high solids Delay time 5
3340-LIT-192.H ×
limit, the valve must close s
Crossflow Separator is not filled with water
Delay time 5
3340-PIT-193B.LL with 3340-PIT-193B on Low Low limit , the ×
s
valve must close
Crossflow Separator teeter water flowrate
Delay time 2
3340-FIT-191.L 3340-FIT-191 low limit exists for 2 ×
minutes
minutes, the valve must close
If only one thickener feed valve (3340-XV-
303 A – C) is closed. A maximum of seven
3340-XV-303A,
Crossflow Separator feed valves may be Delay time 5
3340-XV-303B ×
open. Close the remaining valves, with s
3340-XV-303C
preference for a 4+3 split between
distributors.
3340-XV-303A, If all thickener feed valves (3340-XV-303
Delay time 5
3340-XV-303B A – C) are closed, then the valve must ×
s
3340-XV-303C close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 326: List of Interlocks for 3340-XV-036E

9.16.4 Alarms and Process Setpoints – 3340SepHF110

There are no alarms or process setpoints for this section


9.16.5 Binary State Messages – 3340SepHF110

There are no binary state messages for this section


9.16.6 Regulatory Control Loops – 3340SepHF110

There are no regulatory control loops for this section


9.16.7 Advanced Control Loops – 3340SepHF110

There are no advanced control loops for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 289 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

9.16.8 Description – 3340SepHF110

Crossflow Separator feed slurry is pumped into a Crossflow Separator Distributor (3340 – DB –
104) at a controlled rate. The five-way distributor discharges slurry evenly to the available
Crossflow Separators (3340 – CF – 106 through 110). Should a Crossflow Separator / Hydrofloat
module not be available, it is isolated by closing the respective distributors discharge valve (3340
– XV - 036 A – E).
An individual Crossflow Feed Valve will close (3340 - XV –036 A – E) if the following is true:
 The solids level in the respective Crossflow Separator (3340 - LIT –152 through 192) has
reached a High limit;
 Water level in the Crossflow Separator (3340 - PIT –153B through 193B) is Low;
 The Crossflow Teeter Water flowrate (3340 - FIT – 151 through 191) has reached a low
limit for a specified time;
 All three thickener feed valves (3340 - XV – 303A, 303B, 303C) are closed.
Should only one Thickener Feed Valve be open (3340 - XV – 303A, 303B, 303C), a maximum of
seven crossflow feed valves may be open when considering both distributor 3340-DB103 and
3340-DB - 104. In this instance it is recommended that two valves from one distributor and one
from the other are closed so as not to reduce the crossflow feed pump flowrate below minimum
sedimentation levels.

9.17 Engineering Module 2 – 3340CF110

9.17.1 Description – 3340CF110

9.17.2 Modules of Control 3340CF110

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340CF110

Tag Service
3340-XV-058A Fluidization water to Crossflow-Hydrofloat
3340-FV-191 Crossflow Teeter Water flow control valve
3340-FIT-191 Crossflow Teeter Water flowmeter
3340-PIT-191A Crossflow Teeter Water feed pressure
3340-PIT-191C Crossflow Teeter Water delivered pressure
3340-LT-192 Crossflow Separator fluidized bed level transmitter
3340-PIT-193B Fluidized bed pressure transmitter – Upper
3340-PIT-193A Fluidized bed pressure transmitter – Lower
3340-LCV-192 Crossflow Separator Solids Level Control Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 290 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-197 Crossflow Separator underflow Isolation valve


3340-XV-198 Crossflow Separator drain valve

Table 327: List of Modules of Control for 3340CF110

9.17.3 Interlocks – 3340CF110

T2 Interlock
Crossflow Separator and Hydrofloat
Tag 3340-XV-058A Description
Fluidization Water Isolation Valve
3340SepH
UN SFCPF_SEPHFL2 EM Sub EM 3340CF110
F110
Fail Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Both Fluidisation Water Pump 1 (3340 –


3340 – PU – 112!RUN PU – 112)
AND AND ×
3340 – PU – 114!RUN Fluidisation Water Pump 2 (3340 – PU –
114) are not running

Table 328: List of Interlocks for 3340-XV-058A

T2 Interlock
Tag 3340-FV-191 Description Crossflow Teeter Water flow control valve

UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340CF110


Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 329: List of Interlocks for 3340-FV-191

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 291 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-LCV-192 Description Crossflow Separator U/Flow Control Valve
UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340CF110
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If underflow Isolation valve is closed, close


3340-XV-197.CL ×
valve

Table 330: List of Interlocks for 3340-LCV-192

T2 Interlock
Crossflow Separator U/Flow Isolation
Tag 3340-XV-197 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF110
2 F110
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If downstream hydrofloat is not filled with


3340-PIT-296B.LL water with 3340-PIT-296B on Low Low ×
limit. Then, the valve must close
If downstream Hydrofloat Fluidization
3340- FIT – 294A.L
Water flowrates (A and B) are both Low
AND ×
limit for 2 minutes. Then, the valve must
3340- FIT - 294B.L
close
If downstream hydrofloat has a High High
3340 – LIT – 295.HH solids level for 5 minutes, then the valve ×
must close
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 331: List of Interlocks for 3340-XV-197

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 292 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3340-XV-198 Description Crossflow Separator Drain Valve


SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340CF110
2 F110
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT-193B on
Low limit)
AND
Crossflow Separator has a teeter water
3340-XV-198 cannot flowrate (3340-FIT-191) Lower than the
×
open Low limit setpoint.
AND
The respective Tails Launder Flush Valve
(3340-XV-702.CL) is closed AND the
Flush water pump (3340 – PU – 115!RUN)
is not running.

Table 332: List of Interlocks for 3340-XV-198

9.17.4 Alarms and Process Setpoints – 3340CF110

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340CF110
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-191 Crossflow Teeter Water flowmeter Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
Crossflow Teeter Water feed
Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-191A pressure

Crossflow Teeter Water delivered


Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-191C pressure

Crossflow Separator fluidized bed


Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-LT-192 level transmitter

Fluidized bed pressure


Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-193B transmitter – Upper
Fluidized bed pressure
Refer to vendor control philosophy MQ15-727-TE-3340-IN1002
3340-PIT-193A transmitter – Lower

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 293 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 333: Alarms and Process Setpoint 3340CF110

9.17.5 Binary State Messages – 3340CF110

There are no binary state messages for this section


9.17.6 Regulatory Control Loops – 3340CF110

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340CF110
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1002

Table 334: Regulatory Control Loops for 3340CF110

Teeter/fluidisation water is injected into the separator via module isolation valve (3340 - XV –
058A) and teeter water control valve (3340 - FCV –191) which is controlled to a constant fluidised
bed density as measured by two pressure transmitters (3340 - PIT –193A and 193B). There is a
minimum limitation to which the fluidisation water flow can be reduced to.
The overall solids bed level in the Crossflow Separator is measured by a level transmitter (3340
- LIT –152 through 192) and controlled by adjusting the opening of the underflow control valve
(3340 - LCV – 152 through 192).

9.17.7 Advanced Control Loops – 3340CF110

There are no advanced control loops for this section.

9.17.8 Sequence Description – 3340CF110

The crossflow separator shall follow the following steps during start-up:
TSQST Start Sequence Table
UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340CF110
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 058A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via Flow rate
2 60
2. Initiate 3340-FC-191 3340-FV-191. Refer to vendor above
seconds seconds
functional specification. minimum
for 10 Sec
2 120
3. Open 3340-XV-197 Underflow Isolation Valve. Open
seconds seconds
Underflow solids level control
3340-LC-193 loop via level control valve 2second 120
4. Initiate Open
3340-LCV-193. Refer to vendor s seconds
functional specification.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 294 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 335: Start Sequence 3340CF110

The crossflow separator shall follow the following steps during shutdown:
TSQST Stop Sequence Table
UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340CF110
Seq Command Tag Description Transition Min Monitor
Time Time
Stop underflow solids level
control loop via level control valve 2second 120
1. Close 3340-LC-193 Close
3340-LCV-193. Refer to vendor s seconds
functional specification.
2 120
2. Close 3340-XV-197 Underflow Isolation Valve. Close
seconds seconds
Stop Teeter water control loop via
Close 2 60
3. Close 3340-FC-191 3340-FV-191. Refer to vendor
seconds seconds
functional specification.
Close. Wait
for the
2 60
4. hydrofloat 3340-XV- 058A Teeter water Isolation valve Close
seconds seconds
system to
shutdown first

Table 336: Stop Sequence 3340CF110

If the Crossflow Separator is to not operate for more than approximately two days, the equipment
must be manually drained of solids to prevent cementation within the unit.

9.18 Engineering Module 2 – 3340HF110

9.18.1 Description – 3340HF110

9.18.2 Modules of Control 3340HF110

T1 Control Module
UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340HF110

Tag Service
3340-PIT-291A Pre-Aeration Air Pressure Indicator Transmitter
3340-FIT-291 Pre-Aeration Air Flow Indicator Transmitter - Received
3340-FV-291 Hydrofloat Pre-Aeration Air Flow Control Valve
3340-PIT-291C Pre-Aeration Air Flow Indicator Transmitter - Delivered
3340-FV-292 Hydrofloat Pre-Aeration Water Flow Control Valve
3340-FIT-292 Hydrofloat Pre-Aeration Water Flow Meter
3340-PIT-292A Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Received
3340-PIT-292D Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Delivered
3340-PIT-292C Hydrofloat Pre-Aeration Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-296B Fluidized Bed Pressure Transmitter – Upper

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 295 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PE-296B PRESSURE ELEMENT


3340-PE-296A PRESSURE ELEMENT
3340-PIT-296A Fluidized Bed Pressure Transmitter – Lower
3340-PIT-293A Air Pressure Indicator Transmitter - Received
3340-FIT-293 Air Flow Indicator Transmitter
3340-FV-293 Air Flow Control Valve
3340-PIT-293C Air Pressure Indicator Transmitter - Delivered
3340-FV-294A Fluidization Water Control Valve
3340-FIT-294A Fluidization Water flow indicator transmitter
3340-PIT-294A Fluidization Water Pressure indicator transmitter - Received
3340-FIT-294B Fluidization Water – bubble generator bypass - flow indicator transmitter
3340-FV-294B Fluidization Water – bubble generator bypass - flow control valve
3340-PIT-294C Fluidization Water Pressure Indicator Transmitter - Bubble Generator Feed
3340-PIT-294D Fluidization Water Pressure Indicator Transmitter - Delivered
3340-LIT-295 Fluidized Bed Level Indicator Transmitter
3340-LCV-295 Fluidized Bed Level Control Valve
3340-ZE-295 POSITION ELEMENT
3340-XV-297 Underflow Isolation Valve
3340-XV-298 Underflow Drain Valve

Table 337: List of Modules of Control for 3340HF110

9.18.3 Interlocks – 3340HF110

T2 Interlock
Hydrofloat Pre-Aeration Air Flow Control
Tag 3340-FV-291 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF110
2 F110
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Upstream crossflow separator underflow


3340-XV-197.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-192.CL ×
control valve is closed, then close valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 296 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 338: List of Interlocks for 3340-FV-291

T2 Interlock
Hydrofloat Pre-Aeration Water Flow Control
Tag 3340-FV-292 Description
Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF110
2 F110
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 339: List of Interlocks for 3340-FV-292

T2 Interlock
Tag 3340-FV-293 Description Air Flow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF110
2 F110
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Upstream crossflow separator underflow


3340-XV-197.CL ×
isolation valve is closed, then close valve
Upstream crossflow separator underflow
3340-LV-192.CL ×
control valve is closed, then close valve

Table 340: List of Interlocks for 3340-FV-293

T2 Interlock
Tag 3340-FV-294A Description Fluidization Water Control Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 297 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF110
2 F110
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.!OPN
AND
If all three thickener feed valves are not
3340-XV-303B.!OPN ×
open, then close valve
AND
3340-XV-303C.!OPN

Table 341: List of Interlocks for 3340-FV-294A

T2 Interlock
Fluidization Water – bubble generator bypass
Tag 3340-FV-294B Description
- flow control valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF110
2 F110
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 342: List of Interlocks for 3340-FV-294B

T2 Interlock
Tag 3340-XV-297 Description Hydrofloat Underflow Isolation Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF110
2 F110
Fail Position:
Keep Last (KL) Interlock
Motor Type Interlock
Safe Position: Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 298 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow


Separator not overflowing.
In other words it must be filled with liquid
(3340-PIT-193B not on Low limit)
AND
Crossflow Separator has a teeter water
flowrate (3340-FIT-191) greater than the
3340-XV-297 may not
Low limit setpoint. ×
open if
AND

{The respective Tails Launder Flush Valve


(3340-XV-702.!OPN) is not open AND the
Flush water pump (3340 – PU – 115.!RN)
is not running}.
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 343: List of Interlocks for 3340-XV-297

The hydrofloat underflow discharge slurry must have dilution water assistance in order to be able to be
laundered down the respective tails launder without risk of blockage.

In order to avoid tails launder blockages, only one hydrofloat or crossflow separator may drain at a time
into a respective tails launder.

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be manually
drained of solids to prevent cementation within the unit.

T2 Interlock
Tag 3340-LCV-295 Description Hydrofloat Underflow Control Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF110
2 F110
Fail Position: Fail
Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 299 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

If Hydrofloat Outlet Isolation valve is


3340-XV-297.CL ×
closed, then close valve

Table 344: List of Interlocks for 3340-XV-295

T2 Interlock
Tag 3340-XV-298 Description Hydrofloat Drain Valve
SFCPF_SEPHFL 3340SepH
UN EM Sub EM 3340HF110
2 F110
Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Respective modules’ Crossflow Separator


is not filled with liquid (3340-PIT- 193B.L
not on Low limit)

AND

Respective Modules Crossflow Separator


3340-XV-298 may not has a low teeter water flowrate (3340-FIT-
×
open if 191.L lower than the Low limit).

AND

The respective Tails Launder Flush Valve


(3340-XV-702.!OPN) is not open OR the
Flush water pump (3340 – PU – 115.!RN)
is not running.

Table 345: List of Interlocks for 3340-XV-298

9.18.4 Alarms and Process Setpoints – 3340HF110

T3 Alarms and Process Setpoints


UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340HF110
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Pre-Aeration Air Pressure Indicator
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001
3340-PIT-291A Transmitter

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 300 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-291 Transmitter - Received

Pre-Aeration Air Flow Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-291C Transmitter - Delivered

Hydrofloat Pre-Aeration Water Flow Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-FIT-292 meter

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-292A Received

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-292D Bubble Generator Feed

Hydrofloat Pre-Aeration Water Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Pressure Indicator Transmitter -
3340-PIT-292C Delivered

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-296B Upper

Fluidized Bed Pressure Transmitter – Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-296A Lower

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-293A Received

3340-FIT-293 Air Flow Indicator Transmitter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Air Pressure Indicator Transmitter - Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-293C Delivered

3340-FIT-294A Fluidization Water flow meter Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-294A indicator transmitter - Received

Fluidization Water – bubble Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


generator bypass - flow indicator
3340-FIT-294B transmitter

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


Indicator Transmitter - Bubble
3340-PIT-294C Generator Feed

Fluidization Water Pressure Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-PIT-294D Indicator Transmitter - Delivered

Fluidized Bed Level Indicator Refer to vendor control philosophy MQ15-727-TE-3340-IN1001


3340-LIT-295 Transmitter

Table 346: Alarms and Process Setpoint 3340HF110

9.18.5 Binary State Messages – 3340HF110

There are no binary state messages for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 301 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

9.18.6 Regulatory Control Loops – 3340HF110

UN SFCPF_SEPHFL1
UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340HF110
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Refer to vendor control philosophy MQ15-727-TE-3340-IN1001

Table 347: Regulatory Control Loops for 3340HF110

Pre-aeration water and air are injected into the units feed hopper at a controlled rate via PID loop
controller and control valves (3340 - FCV –291 and 3340 - FCV – 292).
Fluidisation teeter water and air are injected into the hydrofloat at a controlled rate via PID loop
controller and control valves (3340 - FCV –293 and 3340 - FCV –294A/B). Teeter water flowrate
is used to achieve a controlled fluidised bed density as measured by two pressure transmitters
(3340 - PIT –296A and 296B).
The overall solids bed level in the Hydrofloat is measured by a level transmitter (3340 - LIT –295)
and controlled by adjusting the opening of the underflow control valve (3340 - LCV – 295).

9.18.7 Advanced Control Loops – 3340HF110

There are no advanced control loops for this section.

9.18.8 Sequence Description – 3340HF110

The crossflow separator shall follow the following steps during start-up:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 302 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340HF110
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3340-XV- 058A Teeter water Isolation valve Open
seconds seconds
(Open &
Teeter water control loop via
3340-FC- 294A Flow rate
3340-FV-294A and 3340-FV- 2 60
2. Initiate And above
294B. Refer to vendor functional seconds seconds
3340-FC-294B minimum
specification.
for 10 Sec
Open &
Hydrofloat Pre-Aeration Water Flow rate
2 60
3. Initiate 3340-FC-292 Control above
seconds seconds
3340-FV-292. minimum
for 10 Sec
3340-XV-297 Open underflow Isolation Valve 2second 60
4. Open Open
3340-XV –297 s seconds
Initiate Hydrofloat Underflow
2second 60
5. Initiate 3340-LC-295 Valve Level Control Open
s seconds
3340-LV-295
(Open &
Flow rate
Pre-Aeration air control loop via 2 60
6. Initiate 3340-FC-291 above
3340-FV-291. seconds seconds
minimum
for 10 Sec
(Open &
Flow rate
Air control loop via 3340-FV- 2 60
7. Initiate 3340-FC-293 above
293. seconds seconds
minimum
for 10 Sec

Table 348: Start Sequence 3340HF110

The hydrofloat should be started before the upstream Crossflow Separator is started.
Frother reagent is only to be initiated once feed is added to the hydrofloat.

The hydrofloat shall follow the following steps during shutdown:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 303 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN SFCPF_SEPHFL2 EM 3340SepHF110 Sub EM 3340HF110
Seq Command Tag Description Transition Min Monitor
Time Time
Stop Air control loop via 3340- 2 60
1. Close 3340-FV-293 Close
FC-293. seconds seconds
Stop Pre-Aeration air control loop 2 60
2. Close 3340-FV-291 Close
via 3340-FC-291. seconds seconds
Close Close Hydrofloat Underflow Valve
2second 60
3. 3340-LV-295 Level Control Close
s seconds
3340-LV-295
Close 3340-XV-297 Close underflow Isolation Valve 2second 60
4. Close
3340-XV –297 s seconds
Close Hydrofloat Pre-Aeration Water Close
2 60
5. 3340-FV-292 Control
seconds seconds
3340-FV-292.
Close 3340-FV- 294A Close
Teeter water control valve 3340- 2 60
6. And
FV-294A and 3340-FV-294B. seconds seconds
3340-FV-294B
Close Teeter water Isolation valve to Close
2 60
7. 3340-XV- 058A close if crossflow separator also
seconds seconds
stopped.

Table 349: Stop Sequence 3340HF110

If the Hydrofloat is to not operate for more than approximately two days, the equipment must be
manually drained of solids to prevent cementation within the unit.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 304 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

10.0 UNIDAD: CRCFP_RELAVES

Refer to:
MQ14-08-DR-3340-PD1101 Hydrofloat Reject Launders
MQ14-08-DR-3340-PD1087 Tails Launder
MQ15-720-IOM-3340-ME0002 Vendor Sampler and Analyzer Control Philosophy

A block flow control diagram is depicted below for the CRCFP_Relaves system.
Crossflow O/Flow Deslime Cyclone O/
and Hydrofloat Flow 1 & 2
Rejects 1, 2, 6, 7

Crossflow O/Flow 3340 – LN – 106


andHydrofloat
Rejects 3, 4, 8, 9

Crossflow O/Flow 3340 – LN – 107


andHydrofloat
Rejects 5, 10

3340 - XV- 700 3340 – LN – 108


3340 - XV- 701
Tails Thickener
3340 – LN – 105 Feed Box
3340 – BX – 110 3710 – BX - 003

3340 - XV- 702

Flush Water
3340 - XV- 632B
Vendor Package

3340 - XV- 630 3340-SA-103


3340-AY-105
EM1 = 3340PU170
LC
M
3340631

LT SC
3340 – PU – 170 3340632

FAL M

3340 - XV- 633 3340633


3340-BX-135
FSL
3340 - XV- 632A
GSW 3340 – PU – 197

3340 - XV- 632C


EM1 = 3340PU197

Figure 29: Blockflow Control Diagram of CRCFP_Relaves System

The above control unit is broken into two Engineering Module 1’s and no sub Engineering Module 2’s:
- 3340PU197
- 3340PU170

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 305 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

10.0.1 Modules of Control CRCFP_Relaves

T1 Control Module
UN CRCFP_Relaves EM Sub EM

Tag Service
3340-LIT-631 Tails Return Pump Box Level Transmitter
3340-XV-630A Tails Sampling Isolation Valve
3340-SA-103 Tails Sampler and Analyzer
3340-XV-700 Dilution Water – Launder 1
Dilution Water – Launder 2
3340-XV-701
Dilution Water – Launder 3
3340-XV-702

Table 350: List of Modules of Control for CRCFP_Relaves

10.0.2 Interlocks – CRCFP_Relaves

T2 Interlock
Tag 3340-XV-630A Description Tails Sampling Isolation Valve

UN CRCFP_Relaves EM1 EM2


Fail Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Tails Sample Return Pump (3340 – PU –


3340 – PU – 197.!RN × Note 1
197) stops

Table 351: List of Interlocks for 3340-XV-630A

Note 1 Delay of 30 seconds to allow the valve to open during start-up of the pump.

T2 Interlock
Tag 3340-SA-103 Description Tails Sampler and Analyzer

UN CRCFP_Relaves EM Sub EM
Interlock
Motor Type Interlock
Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 306 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to vendor Control Philosophy. MQ15-720-IOM-3340-ME0002


Start and stop signal derived from start/stop of the tails sampler feed pump 3340-PU-197
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 352: List of Interlocks for 3340-SA-103

T2 Interlock
Flush Water Valve to Tails Launder 3340-
Tag 3340-XV-700 Description
LN-106
UN CRCFP_Relaves EM Sub EM
Keep Last (KL)
Safe Position: Interlock
Motor Type Interlock
Closed (CL) Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-108.CL
3340-XV-118.CL
3340-XV-158.CL
All the respective launders’ Crossflow
3340-XV-168.CL
Separator purge valves are closed (3340-
Are closed
XV-108, 3340-XV-118, 3340-XV-158,
3340-XV-168)
AND
AND
3340-XV-208.CL
All the respective tails launders’ Hydrofloat
3340-XV-218.CL
Purge Valves (3340-XV-208, 3340-XV- Note 1
3340-XV-258.CL ×
218, 3340-XV-258, 3340-XV-268) are Note 2
3340-XV-268.CL
closed
Are closed
AND
All the respective launders’ Hydrofloat
AND
Reject Isolation valves (3340-XV-207,
(3340-XV-207.CL
3340-XV-217, 3340-XV-258, 3340-XV-
3340-XV-217.CL
268) are closed
3340-XV-258.CL
3340-XV-268.CL
Are closed

Table 353: List of Interlocks for 3340-XV-700

Note 1 Delay 1 minute to aid in flushing of launder

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 307 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note 2 All three launder valves (3340-XV-700 and 701 and 702) can be opened together, however
precedence must be given to the CPF slurry pump flush water requirements as detailed in Table
815: Precedence of Opening for Flush Water Valves.

T2 Interlock
Flush Water Valve to Tails Launder 3340-
Tag 3340-XV-701 Description
LN-107
UN CRCFP_Relaves EM Sub EM
Keep Last (KL)
Safe Position: Interlock
Motor Type Interlock
Closed (CL) Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-128.CL
3340-XV-138.CL
3340-XV-178.CL
3340-XV-188.CL
Are closed
All the respective launders’ Crossflow
Separator purge valves are closed
AND
AND
3340-XV-228.CL
All the respective tails launders’ Hydrofloat
3340-XV-238.CL
Purge Valves are closed Note 1
3340-XV-278.CL ×
AND Note 2
3340-XV-288.CL
All the respective launders’ Hydrofloat
Are closed
Reject Isolation valves
AND
are closed
(3340-XV-227.CL
3340-XV-237.CL
3340-XV-278.CL
3340-XV-288.CL
Are closed

Table 354: List of Interlocks for 3340-XV-701

Note 1 Delay 1 minute to aid in flushing of launder

Note 2 Note 2 All three launder valves (3340-XV-700 and 701 and 702) can be opened together,
however precedence must be given to the CPF slurry pump flush water requirements as detailed
in Table 815: Precedence of Opening for Flush Water Valves.

T2 Interlock
Flush Water Valve to Tails Launder 3340-
Tag 3340-XV-702 Description
LN-108
UN CRCFP_Relaves EM Sub EM

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 308 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Keep Last (KL)


Safe Position: Interlock
Motor Type Interlock
Closed (CL) Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-148.CL
3340-XV-198.CL
All the respective launders’ Crossflow
Are closed
Separator purge valves are closed
AND
AND
All the respective tails launders’ Hydrofloat
3340-XV-248.CL
Purge Valves are closed Note 1
3340-XV-298.CL ×
AND Note 2
Are closed
All the respective launders’ Hydrofloat
Reject Isolation valves
AND
(3340-XV-247.CL
are closed
3340-XV-297.CL
Are closed

Table 355: List of Interlocks for 3340-XV-702

Note 1 Delay 1 minute to aid in flushing of launder

Note 2 Note 2 All three launder valves (3340-XV-700 and 701 and 702) can be opened together,
however precedence must be given to the CPF slurry pump flush water requirements as detailed
in Table 815: Precedence of Opening for Flush Water Valves.

10.0.3 Alarms and Process Setpoints – CRCFP_Relaves

T3 Alarms and Process Setpoints


UN CRCFP_Relaves EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-LIT-631 Tails Sample Pump Box Level


0 - 100 % 95 5
Transmitter
3340-SA-103 Tails Sampler and Analyser Refer to vendor control philosophy MQ15-720-IOM-3340-ME0002

Table 356: Alarms and Process Setpoint CRCFP_Relaves

10.0.4 Binary State Messages – CRCFP_Relaves

There are no binary state messages for this section

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 309 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

10.0.5 Regulatory Control Loops – CRCFP_Relaves

T5 Regulatory Control Loops


UN CRCFP_Relaves EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
Tails Return Pump Box Level 0 - 100 % % 0 - 100 30 - 95 Expected
3340-LIC-631
Controller setpoint 50%

Table 357: Regulatory Control Loops for CRCFP_Relaves

10.0.6 Advanced Control Loops – CRCFP_Relaves

There are no advanced control loops for this section

10.1 Engineering Module – 3340PU170

10.1.1 Unit of Control Modules – 3340PU170

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN CRCFP_Relaves EM 3340PU170 Sub EM

Tag Service
3340 – PU - 170 CPF Sump Spillage Pump
3340-TE-703 Bearing temperature switch
3340-LSH-703 Level Switch High

Table 358: List of Unit Controls – 3340PU170

10.1.2 Interlocks – 3340PU170

T2 Interlock
Tag 3340-PU-170 Description CPF Sump Spillage Pump
Sub
UN CRCFP_Relaves EM 3340PU170
EM
Interlock
Motor Type M1 Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 310 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Delay 10
3340-LSH-703.ACT High level switch activated × seconds
Note 1
3340-TE-703.ACT High bearing temperature alarm ×
BLACKOUT Delay 5
Electrical BlackOut Activated ×
ELECTRICO.ACT seconds

Table 359: List of Interlocks for 3340PU170

Note 1: Pump to run 15 minutes after the high level has been removed.
10.1.3 Alarms and Process Setpoints – 3340PU170

T3 Alarms and Process Setpoints


UN CRCFP_Relaves EM 3340PU170 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-LSH-703 CPF Sump Spillage Pump High


0 - 100 % 27%
Switch Alarm

Table 360: Alarms and Process Setpoint 3340PU170

Note: Level switches setpoints set in field, not within PLC.


10.1.4 Binary Messages – 3340PU170

Not applicable.
10.1.5 Regulatory Control Loops – 3340PU170

Not applicable.
10.1.6 Advanced Control Loops – 3340PU170

Not applicable
10.1.7 Description – 3340PU170

Spillage which flows into the CPF Sump Pump bund area will gravitate to the CPF Sump Pump
(3340 – PU – 170). A high bund level switch will start the spillage pump. The pump will discharge
the slurry to the Tails Launder (3340 – LN – 106).
The spillage pump will start when the level in the bund reaches a High Level limit (3340 - LSH -
703) and stop again 15 minutes after the high limit falls away. The time delay in stopping the
pump allows the pump to continue to run while hose down of the area is occurring.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 311 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

10.2 Engineering Module– 3340PU197

10.2.1 Description – 3340PU197

The following figure shows the elements that make up the 3340PU197 equipment module.

Crossflow O/Flow Deslime Cyclone O/


and Hydrofloat Flow 1 & 2
Rejects 1, 2, 6, 7

Crossflow O/Flow 3340 – LN – 106


andHydrofloat
Rejects 3, 4, 8, 9

Crossflow O/Flow 3340 – LN – 107


andHydrofloat
Rejects 5, 10

3340 - XV- 700 3340 – LN – 108


3340 - XV- 701
Tails Thickener
3340 – LN – 105 Feed Box
3340 – BX – 110 3710 – BX - 003

3340 - XV- 702

Flush Water
3340 - XV- 632B
Vendor Package

3340 - XV- 630 3340-SA-103


3340-AY-105
EM1 = 3340PU170
LC
M
3340631

LT SC
3340 – PU – 170 3340632

FAL M

3340 - XV- 633 3340633


3340-BX-135
FSL
3340 - XV- 632A
GSW 3340 – PU – 197

3340 - XV- 632C


EM1 = 3340PU197

Figure 30: Blockflow Control Diagram of the 3340PU197 System

10.2.2 Unit of Control Modules – 3340PU197

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN CRCFP_Relaves EM 3340PU197 Sub EM

Tag Service
3340 – PU - 197 Tails Return Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 312 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-TE-632 Bearing temperature switch


3340-FSL-633 Gland Seal Water Flow switch
3340-XV-633 Gland Seal Water Valve
3340-XV-632A Suction Valve
3340-XV-632B Suction Drain Valve
3340-XV-632C Suction Flush Water Valve

Table 361: List of Unit Controls – 3340PU197

10.2.3 Interlocks – 3340PU197

T2 Interlock
Tag 3340-XV-632A Description Suction valve
Sub
UN CRCFP_Relaves EM 3340PU197
EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-632C.OP Suction drain valve open


OR OR ×
3340-XV-632C.OPNG Suction drain valve opening
3340-PU-197.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-632A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-632A.OPNG)

Table 362: List of Interlocks for 3340-XV-632A

T2 Interlock
Tag 3340-XV-632B Description Suction Flush Water Valve
Sub
UN CRCFP_Relaves EM 3340PU197
EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 313 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 363: List of Interlocks for 3340-XV-632B

Precedence must be given to the CPF slurry pump flush water requirements as detailed in Table 815:
Precedence of Opening for Flush Water Valves.

T2 Interlock
Tag 3340-XV-632C Description Suction Drain Water Valve
Sub
UN CRCFP_Relaves EM 3340PU197
EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 364: List of Interlocks for 3340-XV-632C

T2 Interlock
Tag 3340 – PU – 197 Description Tails Return Pump
Sub
UN CRCFP_Relaves EM 3340PU197
EM
Interlock
Motor Type VFD (Multiple) Intlck_3340BB_SL_01
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-633 !OP ×
If gland seal water valve not open and
AND
3340-PU-197 is running
3340-PU-197.MO1.Run

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 314 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-FSL-633.ACT Flow switch (3340-FSL-633) has a low ×


Time Delay
AND flow alarm for a time delay and 3340-PU-
300 seconds
3340-PU-197-MO1.Run 197 is running
Flow switch (3340-FSL-633) has a low
3340-FSL-633.ACT ×
flow alarm
3340-XV-632A CL ×
Suction valve (3340-XV-632A)
OR CLN Time Delay
Is closed or closing and 3340-PU-197 is
AND 10 seconds
running for a time delay
3340-PU-197-MO1.Run
3340-XV-632C OP OR Suction drain valve (3340-XV-632C) is × Debounce
OPN open or opening
The level of the Tails Return Pump Box × Time Delay
3340-LIT-031.H
(3340-LIT-031) is High 300 seconds
The level of the Tails Return Pump Box × Time Delay
3340-LIT-031.L
(3340-LIT-031) is Low 300 seconds
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340 – PU – 101- Both Deslime Feed Pumps (3340 – PU – ×
MO1.Run 101 and 102)
3340 – PU – 102-
MO1.Run AND
Time Delay
AND
60 seconds
3340 – PU – 185- Both Crossflow Feed Pumps (3340 – PU –
MO1.Run 185 and 186)
3340 – PU – 186-
MO1.Run Are not running
3340 – SA – 103 ×
Tails analyser and Sampler is Unhealthy Delay Time
And
and not running (3340 – AY – 105) 30 seconds
3340-AY-105
×
3340-TE-632 Pump thermistor unhealthy

Table 365: List of Interlocks for 3340 – PU - 197

T2 Interlock
Tag 3340-XV-633 Description Gland Seal Water Valve
Sub
UN CRCFP_Relaves EM 3340PU197
EM
Failure Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If the pump 3340 – PU – 197 is not


3340-PU-197.!RUN ×
running

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 315 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 366: List of Interlocks for 3340-XV-633

10.2.4 Alarms and Process Setpoints – 3340PU197

T3 Alarms and Process Setpoints


UN CRCFP_Relaves EM 3340PU197 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-FSL-633 Tails Return Pump Gland Seal


0-3 m3/hr 1.1
Water Flow switch

Table 367: Alarms and Process Setpoint 3340PU197

10.2.5 Binary Messages – 3340PU197

There are no binary messages for this system.


10.2.6 Regulatory Control Loops – 3340PU197

The pump speed is controlled in order to maintain a set point level in the Tails Return Pump Box. (refer to
3340 – LIC – 631).
Note: Controller will be disabled (tracking action), if pump is stopped

10.2.7 Advanced Control Loops – 3340PU197

Not applicable

10.2.8 Sequence Description – 3340PU197

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. The pump start sequence 3340-PU-197, shall follow the following steps:
TSQST Start Sequence Table
UN CRCFP_Relaves EM 3340PU197 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Close 3340-XV-632C Suction drain Valve Closed
seconds seconds
(Open &
Low Flow
2 60
2. Open 3340-XV-633 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
2 220
3. Open 3340-XV-632B Suction Valve. Open
seconds seconds
10 60
4. Start 3340-PU-185.MO1 Start pump. Working
seconds seconds

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 316 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 368: Start Sequence 3340PU197

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-185 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-197-MO1 stopped
The pump stop sequence 3340-PU-197, shall follow the following steps:
TSQST Stop Sequence Table
UN CRCFP_Relaves EM 3340PU197 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-197.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3340-PU-197.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3340-XV-632A Suction Valve. Closed
seconds seconds
2 60
4. Open 3340-XV-632C Suction Drain valve Opened
seconds seconds
2 20
5. Close 3340-XV-633 Gland Seal Water Valve Closed
seconds seconds
Open for
20 60
6. Open 3340-XV-632B Flush Water valve 20
seconds seconds
seconds
2 20
8. Close 3340-XV-632B Flush Water valve Closed
seconds seconds

Table 369: Stop Sequence 3340PU197

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 317 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

11.0 UNIDAD: RECPF_COLLECTOR3894

Refer to:
MQ14-08-DR-3340-PD1091 Reagent Collector AP3894
MQ14-08-DR-3340-PD1107 Reagent Day Tank Collector AP3894
MQ15-781-DC-3340-IN0001 Reagent Day Tank Vendor Control Philosophy
A block flow control diagram is depicted below for the RECPF_Collector3894 system.
Reagent Bulk
Storage Tank
SC
3520PU179 3350200
M

FAL
3350200
3520 – PU – 179
FSL

FC
3350120 FT
Reagent
LT Discharge 1
3350-XV- 120 3350-FCV- 120
3350201A
3350PU120 FC
LT 3350121 FT
LSH 3350-XV- 202A 3350-XV- 202B Reagent
LSH FAL Discharge 2
3350201B
3350201A PT 3350-XV- 121 3350-FCV- 121
LSL
3350204 FC
LSL
3350201D 3350122
FSL
3350-PU-120 FT
Reagent
PT
Discharge 3
3350-XV- 122 3350-FCV- 122
3350 – TK – 104
3350-XV- 203A 3350-XV- 203B FC
3350-PU-121 3350123 FT
Reagent
3350PU121 Discharge 4
3350-XV- 123 3350-FCV- 123

FC
3350PU120_121 3350124 FT
Reagent
Discharge 5
3350-XV- 124 3350-FCV- 124
FC
3350125 FT
Reagent
Discharge 6
3350-XV- 125 3350-FCV- 125
FC
3350126 FT
Reagent
Discharge 7
3350-XV- 126 3350-FCV- 126
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 127 3350-FCV- 127
FC
3350128 FT
Reagent
Discharge 9
3350-XV- 128 3350-FCV- 128
FC
3350129 FT
Reagent
Discharge 10
3350-XV- 129 3350-FCV- 129

Figure 31: Blockflow Control Diagram of RECPF_Collector3894

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 318 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The above control unit is broken into two Engineering Module 1’s with two sub Engineering Module 2’s:
- 3520PU179
- 3350PU120_121
o 3350PU120
o 3350PU121

11.0.1 Modules of Control RECPF_Collector3894

T1 Control Module
UN RECPF_Collector3894 EM Sub EM

Tag Service
3350-TK-104 Collector AP-3894 Day Tank
3350-LSH-201B NIVEL ALTO EN TANQUE DIARIO
3350-LSL-201B NIVEL LOW EN TANQUE DIARIO
3350-LIT-201A NIVEL EN TANQUE DIARIO
3350-FSL-201A Dosing Pump Flow switch
3350-PT-204 PRESIÓN EN LÍNEA DE RETORNO A TANQUE DIARIO
Crossflow Dosing Isolation Valve
3350-XV-120
Crossflow Dosing Isolation Valve
3350-XV-121
Crossflow Dosing Isolation Valve
3350-XV-122
Crossflow Dosing Isolation Valve
3350-XV-123
Crossflow Dosing Isolation Valve
3350-XV-124
Crossflow Dosing Isolation Valve
3350-XV-125
Crossflow Dosing Isolation Valve
3350-XV-126
Crossflow Dosing Isolation Valve
3350-XV-127
Crossflow Dosing Isolation Valve
3350-XV-128
Crossflow Dosing Isolation Valve
3350-XV-129
3350-FIT-129 CORIOLUS FLOW TRANSMITTER
3350-FIT-128 CORIOLUS FLOW TRANSMITTER
3350-FIT-127 CORIOLUS FLOW TRANSMITTER
3350-FIT-126 CORIOLUS FLOW TRANSMITTER
3350-FIT-125 CORIOLUS FLOW TRANSMITTER
3350-FIT-124 CORIOLUS FLOW TRANSMITTER
3350-FIT-123 CORIOLUS FLOW TRANSMITTER
3350-FIT-122 CORIOLUS FLOW TRANSMITTER
3350-FIT-121 CORIOLUS FLOW TRANSMITTER
3350-FIT-120 CORIOLUS FLOW TRANSMITTER

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 319 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-FCV-120 REGULATES REAGENT AP-3894 TO CROSSFLOW #1


3350-FCV-121 REGULATES REAGENT AP-3894 TO CROSSFLOW #2
3350-FCV-122 REGULATES REAGENT AP-3894 TO CROSSFLOW #3
3350-FCV-123 REGULATES REAGENT AP-3894 TO CROSSFLOW #4
3350-FCV-124 REGULATES REAGENT AP-3894 TO CROSSFLOW #5
3350-FCV-125 REGULATES REAGENT AP-3894 TO CROSSFLOW #6
3350-FCV-126 REGULATES REAGENT AP-3894 TO CROSSFLOW #7
3350-FCV-127 REGULATES REAGENT AP-3894 TO CROSSFLOW #8
3350-FCV-128 REGULATES REAGENT AP-3894 TO CROSSFLOW #9
3350-FCV-129 REGULATES REAGENT AP-3894 TO CROSSFLOW #10

Table 370: List of Modules of Control for RECPF_Collector3894

11.0.2 Interlocks – RECPF_Collector3894

T2 Interlock
Tag 3350-XV-120 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-040.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038A.!OPN
Open

Table 371: List of Interlocks for 3350-XV-120

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-121 Description Crossflow Dosing Isolation Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 320 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-042.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038B.!OPN
Open

Table 372: List of Interlocks for 3350-XV-121

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-122 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-044.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038C.!OPN
Open

Table 373: List of Interlocks for 3350-XV-122

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 321 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-XV-123 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-046.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038D.!OPN
Open

Table 374: List of Interlocks for 3350-XV-123

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-124 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-048.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038E.!OPN
Open

Table 375: List of Interlocks for 3350-XV-124

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 322 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-125 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-050.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036A.!OPN
Open

Table 376: List of Interlocks for 3350-XV-125

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-126 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-052.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036B.!OPN
Open

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 323 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 377: List of Interlocks for 3350-XV-126

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-127 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-054.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036C.!OPN
Open

Table 378: List of Interlocks for 3350-XV-127

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-128 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-056.!OPN IF
Crossflow Separator Fluidisation teeter
× Note 1
OR water valve is not open
OR

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 324 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-036D.!OPN Crossflow Feed Isolation Valve is not


Open

Table 379: List of Interlocks for 3350-XV-128

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-129 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-058.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036E.!OPN
Open

Table 380: List of Interlocks for 3350-XV-129

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
REGULATES REAGENT AP-3894 TO
Tag 3350-FCV-120 Description
CROSSFLOW
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 325 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-120.!OPN ×
open

Table 381: List of Interlocks for 3350-FCV-120

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 326 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
REGULATES REAGENT AP-3894 TO
Tag 3350-FCV-121 Description
CROSSFLOW
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-121.!OPN ×
open

Table 382: List of Interlocks for 3350-FCV-121

T2 Interlock
REGULATES REAGENT AP-3894 TO
Tag 3350-FCV-122 Description
CROSSFLOW
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL) Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-122.!OPN ×
open

Table 383: List of Interlocks for 3350-FCV-122

T2 Interlock
REGULATES REAGENT AP-3894 TO
Tag 3350-FCV-123 Description
CROSSFLOW
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 327 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-123.!OPN ×
open

Table 384: List of Interlocks for 3350-FCV-123

T2 Interlock
REGULATES REAGENT AP-3894 TO
Tag 3350-FCV-124 Description
CROSSFLOW
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-124.!OPN ×
open

Table 385: List of Interlocks for 3350-FCV-124

T2 Interlock
REGULATES REAGENT AP-3894 TO
Tag 3350-FCV-125 Description
CROSSFLOW
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-125.!OPN ×
open

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 328 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 386: List of Interlocks for 3350-FCV-125

T2 Interlock
REGULATES REAGENT AP-3894 TO
Tag 3350-FCV-126 Description
CROSSFLOW
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-126.!OPN ×
open

Table 387: List of Interlocks for 3350-FCV-126

T2 Interlock
REGULATES REAGENT AP-3894 TO
Tag 3350-FCV-127 Description
CROSSFLOW
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-127.!OPN ×
open

Table 388: List of Interlocks for 3350-FCV-127

T2 Interlock
REGULATES REAGENT AP-3894 TO
Tag 3350-FCV-128 Description
CROSSFLOW
RECPF_Collector
UN EM Sub EM
3894
Failure Position: Interlock
Motor Type Interlock
Keep Last (KL) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 329 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-128.!OPN ×
open

Table 389: List of Interlocks for 3350-FCV-128

T2 Interlock
REGULATES REAGENT AP-3894 TO
Tag 3350-FCV-129 Description
CROSSFLOW
RECPF_Collector
UN EM Sub EM
3894
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-129.!OPN ×
open

Table 390: List of Interlocks for 3350-FCV-129

11.0.3 Alarms and Process Setpoints – RECPF_Collector3894

T3 Alarms and Process Setpoints


UN RECPF_Collector3894 EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3350-LSH-201B NIVEL ALTO EN TANQUE DIARIO DE


0 - 100 % 98
COLECTOR AP-3894
3350-LSL-201B NIVEL LOW EN TANQUE DIARIO DE
0 - 100 % 2
COLECTOR AP-3894
3350-LIT-201A NIVEL EN TANQUE DIARIO DE
0 - 100 % 90 10
COLECTOR AP-3894
3350-FSL-201A 0 – 2.4 M3/hr 2.1
Dosing Pump Flow switch AP-3894

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 330 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-PT-204 PRESIÓN EN LÍNEA DE RETORNO A


0 - 500 KPa 500 200
TANQUE DIARIO COLECTOR AP-3894
3350-FIT-129 0 – 11 l/hr 9.05 5.3
CORIOLUS FLOW TRANSMITTER
3350-FIT-128 0 – 11 l/hr 9.05 5.3
CORIOLUS FLOW TRANSMITTER
3350-FIT-127 0 – 11 l/hr 9.05 5.3
CORIOLUS FLOW TRANSMITTER
3350-FIT-126 0 – 11 l/hr 9.05 5.3
CORIOLUS FLOW TRANSMITTER
3350-FIT-125 0 – 11 l/hr 9.05 5.3
CORIOLUS FLOW TRANSMITTER
3350-FIT-124 0 – 11 l/hr 9.05 5.3
CORIOLUS FLOW TRANSMITTER
3350-FIT-123 0 – 11 l/hr 9.05 5.3
CORIOLUS FLOW TRANSMITTER
3350-FIT-122 0 – 11 l/hr 9.05 5.3
CORIOLUS FLOW TRANSMITTER
3350-FIT-121 0 – 11 l/hr 9.05 5.3
CORIOLUS FLOW TRANSMITTER
3350-FIT-120 0 – 11 l/hr 9.05 5.3
CORIOLUS FLOW TRANSMITTER

Table 391: Alarms and Process Setpoint RECPF_Collector3894

Note: Level switches setpoints set in field, not within PLC.


11.0.4 Regulatory Control Loops – RECPF_Collector3894

T5 Regulatory Control Loops


UN RECPF_Collector3894 EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-120 Dosing Flow controller Crossflow 1
ion
Dosing Flow controller Crossflow 2 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-121
ion
Dosing Flow controller Crossflow 3 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-122
ion
Dosing Flow controller Crossflow 4 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-123
ion
Dosing Flow controller Crossflow 5 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-124
ion
Dosing Flow controller Crossflow 6 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-125
ion
Dosing Flow controller Crossflow 7 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-126
ion
Dosing Flow controller Crossflow 8 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-127
ion
Dosing Flow controller Crossflow 9 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-128
ion
Dosing Flow controller Crossflow 10 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-129
ion

Table 392: Regulatory Control Loops for RECPF_Collector3894

Note 1

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 331 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The reagents are dosed individually to the Crossflow Separators and Hydrofloats. The flowrate of
each reagent is based upon the calculated dry mass flow rate to the individual module. Refer to
the Crossflow Feed Pump dry mass flow calculations below.
The dry mass flow discharged into Crossflow Distributor 1 (3340 – DB – 103) is then divided by
the number of Crossflow Feed Valves open (3340-XV-038 A – E) for the mass flow to the
respective downstream modules.
Similarly, the dry mass flow discharged into Crossflow Distributor 2 (3340 – DB – 104) is then
divided by the number of Crossflow Feed Valves open (3340-XV-036 A – E) for the mass flow to
the respective downstream modules.
The setpoint flowrate for each individual Crossflow Separator reagent is then based upon the
formulae:
𝑇 × 𝐷𝑜𝑠𝑎𝑔𝑒
𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒 =
𝐷𝑒𝑛𝑠𝑖𝑡𝑦 × 1 000 000 000
Where:
Flowrate (l/hr) = Reagent Setpoint Dosage for a single module (Crossflow or Hydrofloat)
T (dry tph) = Modular dry mass feed rate
Density (t/m3) = Reagent density
AP3894 = 1.0 t/m3
AP404 = 1.02 t/m3
Z6 / SIPX / Xanthate = 0.97 t/m3
Diesel = 0.84 t/m3
Frother = 1.01 t/m3
Dosage (g / t feed) = The mass dosage reagent per dry ton of modular feed. This is a
selected input available to the plant metallurgist. The following ranges are expected:
AP3894 = 20 – 28 g / t
AP404 = 20 – 28 g /t
Z6 / SIPX / Xanthate = 175 – 245 g/t
Diesel = 10 – 14 g /t
Frother = 20 – 28 g/t
A reagent dosing control loop will compare the calculated setpoint to the measured flowrate
(3350-FIT-120 through 129, 130 through 139, 140 through 149, 160 through 169, 150 through
159) and adjust the position of the dosing flow control valve (3350-FCV-120 through 129, 130
through 139, 140 through 149, 160 through 169, 150 through 159).

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 332 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

11.0.5 Advanced Control Loops – RECPF_Collector3894

Not applicable

11.0.6 Sequence Description – RECPF_Collector3894

Not applicable

11.1 Engineering Module– 3520PU179

11.1.1 Description – 3520PU179

The following figure shows the elements that make up the 3520PU179 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 333 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3520PU179 3350200
M

FAL
3350200
3520 – PU – 179
FSL

FC
3350120 FT
Reagent
LT Discharge 1
3350-XV- 120 3350-FCV- 120
3350201A
3350PU120 FC
LT 3350121 FT
LSH 3350-XV- 202A 3350-XV- 202B Reagent
LSH FAL Discharge 2
3350201B
3350201A PT 3350-XV- 121 3350-FCV- 121
LSL
3350204 FC
LSL
3350201D 3350122
FSL
3350-PU-120 FT
Reagent
PT
Discharge 3
3350-XV- 122 3350-FCV- 122
3350 – TK – 104
3350-XV- 203A 3350-XV- 203B FC
3350-PU-121 3350123 FT
Reagent
3350PU121 Discharge 4
3350-XV- 123 3350-FCV- 123

FC
3350124 FT
Reagent
Discharge 5
3350-XV- 124 3350-FCV- 124
FC
3350125 FT
Reagent
Discharge 6
3350-XV- 125 3350-FCV- 125
FC
3350126 FT
Reagent
Discharge 7
3350-XV- 126 3350-FCV- 126
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 127 3350-FCV- 127
FC
3350128 FT
Reagent
Discharge 9
3350-XV- 128 3350-FCV- 128
FC
3350129 FT
Reagent
Discharge 10
3350-XV- 129 3350-FCV- 129

Figure 32: Blockflow Control Diagram of the 3520PU179 System

11.1.2 Modules of Control RECPF_Collector3894

T1 Control Module
UN RECPF_Collector3894 EM 3520PU179 Sub EM

Tag Service
3520-PU-179 Collector AP-3894 Transfer Pump
3520-FSL-200A Low Flow Switch for Reagent Transfer Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 334 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 393: List of Modules of Control for 3520PU179

11.1.3 Interlocks – 3520PU179

T2 Interlock
Tag 3520-PU-179 Description Collector AP-3894 Transfer Pump
RECPF_Collector 3520PU17
UN EM Sub EM
3894 9
Interlock
Motor Type Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3520 – TK – 001 Level


(others) Delay time 5
Level has a low limit ×
AND s
3520-PU-179.RN
3520-FSL-200A Flow switch (3520-FSL-200A) has a low
Delay time
AND flow limit for a time delay after the pump ×
120s
3520-PU-179.RN motor is running
3350-LIT-201A
Day Tank Level (3350-LIT-201A) has Delay time 5
AND ×
reached a high limit seconds
3520-PU-179.RN
3350-LSH-201B
High Level Limit Switch (3350-LSH-201B) Delay time 5
AND ×
has an alarm seconds
3520-PU-179.RN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 394: List of Interlocks for 3520PU179

11.1.4 Alarms and Process Setpoints – 3520PU179

T3 Alarms and Process Setpoints


UN RECPF_Collector3894 EM 3520PU179 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3520-FSL-
200A Transfer Low Flow Switch alarm 0 - 60 m3/hr 15

Table 395: Alarms and Process Setpoint 3520PU179

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 335 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

11.1.5 Regulatory Control Loops – 3520PU179

Not applicable. The filling of the Reagent Day Tank occurs in batch mode. When 3350-LIT-201A
is Low, the transfer pump is to switch on and then switch off again on attaining a high level
transmitter signal.

11.1.6 Advanced Control Loops – 3520PU179

Not applicable

11.1.7 Sequence Description – 3520PU179

Not applicable

11.2 Engineering Module– 3350PU120_121

11.2.1 Description – 3350PU120_121

The following figure shows the elements that make up the 3350PU120_121 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 336 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3350200
M

FAL
3350200
3520 – PU – 179
FSL

FC
3350120 FT
Reagent
LT Discharge 1
3350-XV- 120 3350-FCV- 120
3350201A
3350PU120 FC
LT 3350121 FT
LSH 3350-XV- 202A 3350-XV- 202B Reagent
LSH FAL Discharge 2
3350201B
3350201A PT 3350-XV- 121 3350-FCV- 121
LSL
3350204 FC
LSL
3350201D 3350122
FSL
3350-PU-120 FT
Reagent
PT
Discharge 3
3350-XV- 122 3350-FCV- 122
3350 – TK – 104
3350-XV- 203A 3350-XV- 203B FC
3350-PU-121 3350123 FT
Reagent
3350PU121 Discharge 4
3350-XV- 123 3350-FCV- 123

FC
3350PU120_121 3350124 FT
Reagent
Discharge 5
3350-XV- 124 3350-FCV- 124
FC
3350125 FT
Reagent
Discharge 6
3350-XV- 125 3350-FCV- 125
FC
3350126 FT
Reagent
Discharge 7
3350-XV- 126 3350-FCV- 126
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 127 3350-FCV- 127
FC
3350128 FT
Reagent
Discharge 9
3350-XV- 128 3350-FCV- 128
FC
3350129 FT
Reagent
Discharge 10
3350-XV- 129 3350-FCV- 129

Figure 33: Blockflow Control Diagram of the 3350PU120_121 System

This engineering module is broken into the following Engineering 2 Modules:


- 3350PU120 (Duty)

- 3350PU121 (Standby)

Only one pump must run at a time. The operator to select the pump manually or plc to select
based on the least number of operating hours at time of start.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 337 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

11.3 Engineering Module 2 – 3350PU120

11.3.1 Description – 3350PU120

The following figure shows the elements that make up the 3350PU120 equipment module.
Reagent Bulk
Storage Tank
SC
3520PU179 3350200
M

FAL
3350200
3520 – PU – 179
FSL

FC
3350120 FT
Reagent
LT Discharge 1
3350-XV- 120 3350-FCV- 120
3350201A
3350PU120 FC
LT 3350121 FT
LSH 3350-XV- 202A 3350-XV- 202B Reagent
LSH FAL Discharge 2
3350201B
3350201A PT 3350-XV- 121 3350-FCV- 121
LSL
3350204 FC
LSL
3350201D 3350122
FSL
3350-PU-120 FT
Reagent
PT
Discharge 3
3350-XV- 122 3350-FCV- 122
3350 – TK – 104
3350-XV- 203A 3350-XV- 203B FC
3350-PU-121 3350123 FT
Reagent
3350PU121 Discharge 4
3350-XV- 123 3350-FCV- 123

FC
3350124 FT
Reagent
Discharge 5
3350-XV- 124 3350-FCV- 124
FC
3350125 FT
Reagent
Discharge 6
3350-XV- 125 3350-FCV- 125
FC
3350126 FT
Reagent
Discharge 7
3350-XV- 126 3350-FCV- 126
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 127 3350-FCV- 127
FC
3350128 FT
Reagent
Discharge 9
3350-XV- 128 3350-FCV- 128
FC
3350129 FT
Reagent
Discharge 10
3350-XV- 129 3350-FCV- 129

Figure 34: Blockflow Control Diagram of the 3350PU120 System

11.3.2 Modules of Control 3350PU120

T1 Control Module

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 338 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Sub
UN RECPF_Collector3894 EM 3350PU120_121 3350PU120
EM
Tag Service
3350-PU-120 AP-3894 Dosing Pump 1
3350-XV-202A Suction Reagent Pump
3350-XV-202B Discharge Reagent Pump

Table 396: List of Modules of Control for 3350PU120

11.3.3 Interlocks – 3350PU120

T2 Interlock
Tag 3350 – XV – 202A Description Suction Valve Reagent Pump
RECPF_Collector 3350PU12
UN EM Sub EM 3350PU120
3894 0_121
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3350 – XV – 203A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3350 – PU – 120.!RN ×
period. 30 seconds

Table 397: List of Interlocks for 3350-XV-202A

T2 Interlock
Tag 3350 – PU - 120 Description Dosing Pump 1
RECPF_Collector 3350PU12
UN EM Sub EM 3350PU120
3894 0_121
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Dosing Tank level switch Low (has a low


3350-LSL-201D.Low ×
alarm

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 339 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Dosing pump flow switch has a low flow Time delay 1


3350-FSL-202A.Low ×
alarm for a time delay second
3350-XV-202A.!Opn Dosing Pump suction valve is not open ×

3350-XV-202B.!Opn Dosing Pump Discharge valve is not open ×


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 398: List of Interlocks for 3350-PU-120

T2 Interlock
Tag 3350 – XV – 202B Description Discharge Valve Reagent Pump
RECPF_Collector 3350PU12
UN EM Sub EM 3350PU120
3894 0_121
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3350 – XV – 203B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3350 – PU – 120.!RN ×
period. 2 seconds

Table 399: List of Interlocks for 3350-XV-202B

11.3.4 Alarms and Process Setpoints – 3350PU120

Not applicable.
11.3.5 Regulatory Control Loops – 3350PU120

Not applicable.

11.3.6 Advanced Control Loops – 3350PU120

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 340 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

11.3.7 Sequence Description – 3350PU120

The pump start sequence 3340-PU-120, shall follow the following steps:
TSQST Start Sequence Table
UN RECPF_Collector3894 EM 3350PU120_121 Sub EM 3350PU120
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3350-XV-202B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3340-XV-202A Open Suction Valve Open
seconds seconds
10 60
3. Start 3340-PU-120.MO1 Start pump. Working
seconds seconds

Table 400: Start Sequence 3350PU120

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3350-PU-120 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3350-PU-120-MO1 stopped
The pump stop sequence 3350-PU-120, shall follow the following steps:
TSQST Stop Sequence Table
UN RECPF_Collector3894 EM 3350PU120_121 Sub EM 3350PU120
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3350-PU-120.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3350-XV-202A Suction Valve. Closed
seconds seconds
2 20
3. Close 3350-XV-202 Discharge Valve Closed
seconds seconds

Table 401: Stop Sequence 3350PU120

11.4 Engineering Module 2 – 3350PU121

11.4.1 Description – 3350PU121

The following figure shows the elements that make up the 3350PU121 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 341 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3520PU179 3350200
M

FAL
3350200
3520 – PU – 179
FSL

FC
3350120 FT
Reagent
LT Discharge 1
3350-XV- 120 3350-FCV- 120
3350201A
3350PU120 FC
LT 3350121 FT
LSH 3350-XV- 202A 3350-XV- 202B Reagent
LSH FAL Discharge 2
3350201B
3350201A PT 3350-XV- 121 3350-FCV- 121
LSL
3350204 FC
LSL
3350201D 3350122
FSL
3350-PU-120 FT
Reagent
PT
Discharge 3
3350-XV- 122 3350-FCV- 122
3350 – TK – 104
3350-XV- 203A 3350-XV- 203B FC
3350-PU-121 3350123 FT
Reagent
3350PU121 Discharge 4
3350-XV- 123 3350-FCV- 123

FC
3350124 FT
Reagent
Discharge 5
3350-XV- 124 3350-FCV- 124
FC
3350125 FT
Reagent
Discharge 6
3350-XV- 125 3350-FCV- 125
FC
3350126 FT
Reagent
Discharge 7
3350-XV- 126 3350-FCV- 126
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 127 3350-FCV- 127
FC
3350128 FT
Reagent
Discharge 9
3350-XV- 128 3350-FCV- 128
FC
3350129 FT
Reagent
Discharge 10
3350-XV- 129 3350-FCV- 129

Figure 35: Blockflow Control Diagram of the 3350PU121 System

11.4.2 Modules of Control 3350PU121

T1 Control Module
Sub
UN RECPF_Collector3894 EM 3350PU120_121 3350PU121
EM

Tag Service
3350-PU-121 AP-3894 Dosing Pump 2
3350-XV-203A Suction Reagent Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 342 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-XV-203B Discharge Reagent Pump

Table 402: List of Modules of Control for 3350PU121

11.4.3 Interlocks – 3350PU121

T2 Interlock
Tag 3350 – XV – 203A Description Suction Valve Reagent Pump
RECPF_Collector 3350PU12
UN EM Sub EM 3350PU121
3894 0_121
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3350 – XV – 202A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3350 – PU – 121.!RN ×
period. 30 seconds

Table 403: List of Interlocks for 3350-XV-203A

T2 Interlock
Tag 3350 – PU - 121 Description Dosing Pump 2
RECPF_Collector 3350PU12
UN EM Sub EM 3350PU121
3894 0_121
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Dosing Tank level switch Low (has a low


3350-LSL-201D.Low ×
alarm
Dosing pump flow switch has a low flow Time delay 1
3350-FSL-203A.Low ×
alarm for a time delay second
3350-XV-203A.!Opn Dosing Pump suction valve is not open ×

3350-XV-203B.!Opn Dosing Pump Discharge valve is not open ×


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 343 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 404: List of Interlocks for 3350-PU-121

T2 Interlock
Tag 3350 – XV – 202B Description Discharge Valve Reagent Pump
RECPF_Collector 3350PU12
UN EM Sub EM 3350PU121
3894 0_121
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3350 – XV – 202B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3350 – PU – 121.!RN ×
period. 2 seconds

Table 405: List of Interlocks for 3350-XV-203B

11.4.4 Alarms and Process Setpoints – 3350PU121

Not applicable.
11.4.5 Regulatory Control Loops – 3350PU121

Not applicable.

11.4.6 Advanced Control Loops – 3350PU121

Not applicable

11.4.7 Sequence Description – 3350PU121

The pump start sequence 3340-PU-121, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 344 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN RECPF_Collector3894 EM 3350PU120_121 Sub EM 3350PU121
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3350-XV-203B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3340-XV-203A Open Suction Valve Open
seconds seconds
10 60
3. Start 3340-PU-121.MO1 Start pump. Working
seconds seconds

Table 406: Start Sequence 3350PU121

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3350-PU-121 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3350-PU-121-MO1 stopped
The pump stop sequence 3350-PU-121, shall follow the following steps:
TSQST Stop Sequence Table
UN RECPF_Collector3894 EM 3350PU120_121 Sub EM 3350PU121
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3350-PU-121.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3350-XV-203A Suction Valve. Closed
seconds seconds
2 20
3. Close 3350-XV-203B Discharge Valve Closed
seconds seconds

Table 407: Stop Sequence 3350PU121

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 345 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

12.0 UNIDAD: RECPF_COLLECTOR404

Refer to:
MQ14-08-DR-3340-PD1092 Reagent Collector AP404
MQ14-08-DR-3340-PD1108 Reagent Day Tank Collector AP404
MQ15-781-DC-3340-IN0001 Reagent Day Tank Vendor Control Philosophy
A block flow control diagram is depicted below for the RECPF_Collector404 system.
Reagent Bulk
Storage Tank
SC
3520PU182 3350205
M

FAL
3350205
3520 – PU – 182
FSL

FC
3350160 FT
Reagent
LT Discharge 1
3350-XV- 160 3350-FCV- 160
3350206A
3350PU160 FC
LT 3350161 FT
LSH 3350-XV- 207A 3350-XV- 207B Reagent
LSH FAL Discharge 2
3350206B
3350206A PT 3350-XV- 161 3350-FCV- 161
LSL
3350204 FC
LSL
3350206D 3350162
FSL
3350-PU-160 FT
Reagent
PT
Discharge 3
3350-XV- 162 3350-FCV- 162
3350 – TK – 103
3350-XV- 208A 3350-XV- 208B FC
3350-PU-161 3350163 FT
Reagent
3350PU161 Discharge 4
3350-XV- 163 3350-FCV- 163

FC
3350164 FT
Reagent
Discharge 5
3350-XV- 164 3350-FCV- 164
FC
3350165 FT
Reagent
Discharge 6
3350-XV- 165 3350-FCV- 165
FC
3350166 FT
Reagent
Discharge 7
3350-XV- 166 3350-FCV- 166
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 167 3350-FCV- 167
FC
3350168 FT
Reagent
Discharge 9
3350-XV- 168 3350-FCV- 168
FC
3350169 FT
Reagent
Discharge 10
3350-XV- 169 3350-FCV- 169

Figure 36: Blockflow Control Diagram of RECPF_Collector404

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 346 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The above control unit is broken into two Engineering Module 1’s with two sub Engineering Module 2’s:
- 3530PU182
- 3350PU160_161
o 3350PU160 (Duty)
o 3350PU161 (Standby)

Only one pump must run at a time. The operator to select the pump manually or plc to select
based on the least number of operating hours at time of start.

12.0.1 Modules of Control RECPF_Collector404

T1 Control Module
UN RECPF_Collector404 EM Sub EM

Tag Service
3350-TK-103 Collector AP-404 Day Tank
3350-LSH-206B NIVEL ALTO EN TANQUE DIARIO
3350-LSL-206B NIVEL LOW EN TANQUE DIARIO
3350-LIT-206A NIVEL EN TANQUE DIARIO
3350-FSL-207A Dosing Pump Flow switch
3350-PT-209 PRESIÓN EN LÍNEA DE RETORNO A TANQUE DIARIO
Crossflow Dosing Isolation Valve
3350-XV-160
Crossflow Dosing Isolation Valve
3350-XV-161
Crossflow Dosing Isolation Valve
3350-XV-162
Crossflow Dosing Isolation Valve
3350-XV-163
Crossflow Dosing Isolation Valve
3350-XV-164
Crossflow Dosing Isolation Valve
3350-XV-165
Crossflow Dosing Isolation Valve
3350-XV-166
Crossflow Dosing Isolation Valve
3350-XV-167
Crossflow Dosing Isolation Valve
3350-XV-168
Crossflow Dosing Isolation Valve
3350-XV-169
3350-FIT-169 CORIOLUS FLOW TRANSMITTER
3350-FIT-168 CORIOLUS FLOW TRANSMITTER
3350-FIT-167 CORIOLUS FLOW TRANSMITTER
3350-FIT-166 CORIOLUS FLOW TRANSMITTER
3350-FIT-165 CORIOLUS FLOW TRANSMITTER
3350-FIT-164 CORIOLUS FLOW TRANSMITTER

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 347 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-FIT-163 CORIOLUS FLOW TRANSMITTER


3350-FIT-162 CORIOLUS FLOW TRANSMITTER
3350-FIT-161 CORIOLUS FLOW TRANSMITTER
3350-FIT-160 CORIOLUS FLOW TRANSMITTER
3350-FCV-16
0 REGULATES REAGENT AP-404 TO CROSSFLOW #1
3350-FCV-161 REGULATES REAGENT AP-404 TO CROSSFLOW #2
3350-FCV-162 REGULATES REAGENT AP-404 TO CROSSFLOW #3
3350-FCV-163 REGULATES REAGENT AP-404 TO CROSSFLOW #4
3350-FCV-164 REGULATES REAGENT AP-404 TO CROSSFLOW #5
3350-FCV-165 REGULATES REAGENT AP-404 TO CROSSFLOW #6
3350-FCV-166 REGULATES REAGENT AP-404 TO CROSSFLOW #7
3350-FCV-167 REGULATES REAGENT AP-404 TO CROSSFLOW #8
3350-FCV-168 REGULATES REAGENT AP-404 TO CROSSFLOW #9
3350-FCV-169 REGULATES REAGENT AP-404 TO CROSSFLOW #10

Table 408: List of Modules of Control for RECPF_Collector404

12.0.2 Interlocks – RECPF_Collector404

T2 Interlock
Tag 3350-XV-160 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-040.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038A.!OPN
Open

Table 409: List of Interlocks for 3350-XV-160

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 348 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-XV-161 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-042.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038B.!OPN
Open

Table 410: List of Interlocks for 3350-XV-161

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-162 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-044.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038C.!OPN
Open

Table 411: List of Interlocks for 3350-XV-162

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 349 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-163 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-046.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038D.!OPN
Open

Table 412: List of Interlocks for 3350-XV-163

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-164 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-048.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038E.!OPN
Open

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 350 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 413: List of Interlocks for 3350-XV-164

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-165 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-050.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036A.!OPN
Open

Table 414: List of Interlocks for 3350-XV-165

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-166 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-052.!OPN IF
Crossflow Separator Fluidisation teeter
× Note 1
OR water valve is not open
OR

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 351 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-036B.!OPN Crossflow Feed Isolation Valve is not


Open

Table 415: List of Interlocks for 3350-XV-166

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-167 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-054.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036C.!OPN
Open

Table 416: List of Interlocks for 3350-XV-167

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-168 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 352 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

IF
3340-XV-056.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036D.!OPN
Open

Table 417: List of Interlocks for 3350-XV-168

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-169 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-058.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036E.!OPN
Open

Table 418: List of Interlocks for 3350-XV-169

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-FCV-160 Description REGULATES REAGENT AP-404 TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 353 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-160.!OPN ×
open

Table 419: List of Interlocks for 3350-FCV-160

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 354 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-FCV-161 Description REGULATES REAGENT AP-404 TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-161.!OPN ×
open

Table 420: List of Interlocks for 3350-FCV-161

T2 Interlock
Tag 3350-FCV-162 Description REGULATES REAGENT AP-404 TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-162.!OPN ×
open

Table 421: List of Interlocks for 3350-FCV-162

T2 Interlock
Tag 3350-FCV-163 Description REGULATES REAGENT AP-404 TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 355 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-163.!OPN ×
open

Table 422: List of Interlocks for 3350-FCV-163

T2 Interlock
Tag 3350-FCV-164 Description REGULATES REAGENT AP-404 TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-164.!OPN ×
open

Table 423: List of Interlocks for 3350-FCV-164

T2 Interlock
Tag 3350-FCV-165 Description REGULATES REAGENT AP-404 TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-165.!OPN ×
open

Table 424: List of Interlocks for 3350-FCV-165

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 356 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-FCV-166 Description REGULATES REAGENT AP-404 TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-166.!OPN ×
open

Table 425: List of Interlocks for 3350-FCV-166

T2 Interlock
Tag 3350-FCV-167 Description REGULATES REAGENT AP-404 TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-167.!OPN ×
open

Table 426: List of Interlocks for 3350-FCV-167

T2 Interlock
Tag 3350-FCV-168 Description REGULATES REAGENT AP-404 TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 357 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-168.!OPN ×
open

Table 427: List of Interlocks for 3350-FCV-168

T2 Interlock
Tag 3350-FCV-169 Description REGULATES REAGENT AP-404 TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
404
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-169.!OPN ×
open

Table 428: List of Interlocks for 3350-FCV-169

12.0.3 Alarms and Process Setpoints – RECPF_Collector404

T3 Alarms and Process Setpoints


UN RECPF_Collector404 EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3350-LSH-207B NIVEL ALTO EN TANQUE DIARIO DE


0 - 100 % 98
COLECTOR AP-404
3350-LSL-207B NIVEL LOW EN TANQUE DIARIO DE
0 - 100 % 2
COLECTOR AP-404
3350-LIT-207A NIVEL EN TANQUE DIARIO DE
0 - 100 % 90 10
COLECTOR AP-404
3350-FSL-207A 0 – 2.4 M3/hr 2.1
Dosing Pump Flow switch AP-404
3350-PT-208 PRESIÓN EN LÍNEA DE RETORNO A
0 - 500 KPa 500 200
TANQUE DIARIO COLECTOR AP-404
3350-FIT-169 0 – 11 l/hr 8.9 5.2
CORIOLUS FLOW TRANSMITTER

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 358 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-FIT-168 0 – 11 l/hr 8.9 5.2


CORIOLUS FLOW TRANSMITTER
3350-FIT-167 0 – 11 l/hr 8.9 5.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-166 0 – 11 l/hr 8.9 5.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-165 0 – 11 l/hr 8.9 5.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-164 0 – 11 l/hr 8.9 5.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-163 0 – 11 l/hr 8.9 5.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-162 0 – 11 l/hr 8.9 5.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-161 0 – 11 l/hr 8.9 5.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-160 0 – 11 l/hr 8.9 5.2
CORIOLUS FLOW TRANSMITTER

Table 429: Alarms and Process Setpoint RECPF_Collector404

Note: Level switches setpoints set in field, not within PLC.


12.0.4 Regulatory Control Loops – RECPF_Collector404

T5 Regulatory Control Loops


UN RECPF_Collector404 EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-160 Dosing Flow controller Crossflow 1
ion
Dosing Flow controller Crossflow 2 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-161
ion
Dosing Flow controller Crossflow 3 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-162
ion
Dosing Flow controller Crossflow 4 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-163
ion
Dosing Flow controller Crossflow 5 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-164
ion
Dosing Flow controller Crossflow 6 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-165
ion
Dosing Flow controller Crossflow 7 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-166
ion
Dosing Flow controller Crossflow 8 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-167
ion
Dosing Flow controller Crossflow 9 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-168
ion
Dosing Flow controller Crossflow 10 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-169
ion

Table 430: Regulatory Control Loops for RECPF_Collector404

Note 1
The reagents are dosed individually to the Crossflow Separators and Hydrofloats. The flowrate of
each reagent is based upon the calculated dry mass flow rate to the individual module. Refer to
the Crossflow Feed Pump dry mass flow calculations below.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 359 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The dry mass flow discharged into Crossflow Distributor 1 (3340 – DB – 103) is then divided by
the number of Crossflow Feed Valves open (3340-XV-038 A – E) for the mass flow to the
respective downstream modules.
Similarly, the dry mass flow discharged into Crossflow Distributor 2 (3340 – DB – 104) is then
divided by the number of Crossflow Feed Valves open (3340-XV-036 A – E) for the mass flow to
the respective downstream modules.
The setpoint flowrate for each individual Crossflow Separator reagent is then based upon the
formulae:
𝑇 × 𝐷𝑜𝑠𝑎𝑔𝑒
𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒 =
𝐷𝑒𝑛𝑠𝑖𝑡𝑦 × 1 000 000 000
Where:
Flowrate (l/hr) = Reagent Setpoint Dosage for a single module (Crossflow or Hydrofloat)
T (dry tph) = Modular dry mass feed rate
Density (t/m3) = Reagent density
AP404 = 1.0 t/m3
AP404 = 1.02 t/m3
Z6 / SIPX / Xanthate = 0.97 t/m3
Diesel = 0.84 t/m3
Frother = 1.01 t/m3
Dosage (g / t feed) = The mass dosage reagent per dry ton of modular feed. This is a
selected input available to the plant metallurgist. The following ranges are expected:
AP404 = 20 – 28 g / t
AP404 = 20 – 28 g /t
Z6 / SIPX / Xanthate = 175 – 245 g/t
Diesel = 10 – 14 g /t
Frother = 20 – 28 g/t
A reagent dosing control loop will compare the calculated setpoint to the measured flowrate
(3350-FIT-120 through 129, 130 through 139, 140 through 149, 160 through 169, 150 through
159) and adjust the position of the dosing flow control valve (3350-FCV-120 through 129, 130
through 139, 140 through 149, 160 through 169, 150 through 159).

12.0.5 Advanced Control Loops – RECPF_Collector404

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 360 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

12.0.6 Sequence Description – RECPF_Collector404

Not applicable

12.1 Engineering Module– 3520PU182

12.1.1 Description – 3520PU182

The following figure shows the elements that make up the 3520PU182 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 361 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3520PU182 3350205
M

FAL
3350205
3520 – PU – 182
FSL

FC
3350160 FT
Reagent
LT Discharge 1
3350-XV- 160 3350-FCV- 160
3350206A
3350PU160 FC
LT 3350161 FT
LSH 3350-XV- 207A 3350-XV- 207B Reagent
LSH FAL Discharge 2
3350206B
3350206A PT 3350-XV- 161 3350-FCV- 161
LSL
3350204 FC
LSL
3350206D 3350162
FSL
3350-PU-160 FT
Reagent
PT
Discharge 3
3350-XV- 162 3350-FCV- 162
3350 – TK – 103
3350-XV- 208A 3350-XV- 208B FC
3350-PU-161 3350163 FT
Reagent
3350PU161 Discharge 4
3350-XV- 163 3350-FCV- 163

FC
3350164 FT

3350PU160_161 Reagent
Discharge 5
3350-XV- 164 3350-FCV- 164
FC
3350165 FT
Reagent
Discharge 6
3350-XV- 165 3350-FCV- 165
FC
3350166 FT
Reagent
Discharge 7
3350-XV- 166 3350-FCV- 166
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 167 3350-FCV- 167
FC
3350168 FT
Reagent
Discharge 9
3350-XV- 168 3350-FCV- 168
FC
3350169 FT
Reagent
Discharge 10
3350-XV- 169 3350-FCV- 169

Figure 37: Blockflow Control Diagram of the 3520PU182 System

12.1.2 Modules of Control RECPF_Collector404

T1 Control Module
UN RECPF_Collector404 EM 3520PU182 Sub EM

Tag Service
3520-PU-182 Collector AP-404 Transfer Pump
3520-FSL-205A Low Flow Switch for Reagent Transfer Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 362 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 431: List of Modules of Control for 3520PU182

12.1.3 Interlocks – 3520PU182

T2 Interlock
Tag 3520-PU-182 Description Collector AP-404 Transfer Pump
RECPF_Collector 3520PU18
UN EM Sub EM
404 2
Interlock
Motor Type Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3520 – TK – 013 Level


(others) Delay time 5
Level has a low limit ×
AND s
3520-PU-182.RN
3520-FSL-205A
Flow switch has a low flow limit for a time Delay time
AND ×
delay after the pump motor is running 120s
3520-PU-182.RN
3350-LIT-206A
Delay time 5
AND Day Tank Level has reached a high limit ×
seconds
3520-PU-182.RN
3350-LSH-206B
Delay time 5
AND High Level Limit Switch has an alarm ×
seconds
3520-PU-182.RN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 432: List of Interlocks for 3520PU182

12.1.4 Alarms and Process Setpoints – 3520PU182

T3 Alarms and Process Setpoints


UN RECPF_Collector404 EM 3520PU1782 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3520-FSL-
205A Transfer Low Flow Switch alarm 0 - 60 m3/hr 15

Table 433: Alarms and Process Setpoint 3520PU182

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 363 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

12.1.5 Regulatory Control Loops – 3520PU182

Not applicable. The filling of the Reagent Day Tank occurs in batch mode. When 3350-LIT-206A
is Low, the transfer pump is to switch on and then switch off again on attaining a high level
transmitter signal.

12.1.6 Advanced Control Loops – 3520PU182

Not applicable

12.1.7 Sequence Description – 3520PU182

Not applicable

12.2 Engineering Module 2 – 3350PU160

12.2.1 Description – 3350PU160

The following figure shows the elements that make up the 3350PU160 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 364 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3520PU182 3350205
M

FAL
3350205
3520 – PU – 182
FSL

FC
3350160 FT
Reagent
LT Discharge 1
3350-XV- 160 3350-FCV- 160
3350206A
3350PU160 FC
LT 3350161 FT
LSH 3350-XV- 207A 3350-XV- 207B Reagent
LSH FAL Discharge 2
3350206B
3350206A PT 3350-XV- 161 3350-FCV- 161
LSL
3350204 FC
LSL
3350206D 3350162
FSL
3350-PU-160 FT
Reagent
PT
Discharge 3
3350-XV- 162 3350-FCV- 162
3350 – TK – 103
3350-XV- 208A 3350-XV- 208B FC
3350-PU-161 3350163 FT
Reagent
3350PU161 Discharge 4
3350-XV- 163 3350-FCV- 163

FC
3350164 FT

3350PU160_161 Reagent
Discharge 5
3350-XV- 164 3350-FCV- 164
FC
3350165 FT
Reagent
Discharge 6
3350-XV- 165 3350-FCV- 165
FC
3350166 FT
Reagent
Discharge 7
3350-XV- 166 3350-FCV- 166
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 167 3350-FCV- 167
FC
3350168 FT
Reagent
Discharge 9
3350-XV- 168 3350-FCV- 168
FC
3350169 FT
Reagent
Discharge 10
3350-XV- 169 3350-FCV- 169

Figure 38: Blockflow Control Diagram of the 3350PU160 System

12.2.2 Modules of Control 3350PU160

T1 Control Module
Sub
UN RECPF_Collector404 EM 3350PU160_161 3350PU160
EM

Tag Service
3350-PU-160 AP-404 Dosing Pump 1
3350-XV-207A Suction Reagent Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 365 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-XV-207B Discharge Reagent Pump

Table 434: List of Modules of Control for 3350PU160

12.2.3 Interlocks – 3350PU160

T2 Interlock
Tag 3350 – XV – 207A Description Suction Valve Reagent Pump
RECPF_Collector 3350PU16
UN EM Sub EM 3350PU160
404 0_161
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3350 – XV – 208A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3350 – PU – 160.!RN ×
period. 30 seconds

Table 435: List of Interlocks for 3350-XV-207A

T2 Interlock
Tag 3350 – PU - 160 Description Dosing Pump 1
RECPF_Collector 3350PU16
UN EM Sub EM 3350PU160
404 0_161
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Dosing Tank level switch Low (has a low


3350-LSL-206D.Low ×
alarm
Dosing pump flow switch has a low flow Time delay 1
3350-FSL-207A.Low ×
alarm for a time delay second
3350-XV-207A.!Opn Dosing Pump suction valve is not open ×

3350-XV-207B.!Opn Dosing Pump Discharge valve is not open ×

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 366 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 436: List of Interlocks for 3350-PU-160

T2 Interlock
Tag 3350 – XV – 207B Description Discharge Valve Reagent Pump
RECPF_Collector 3350PU16
UN EM Sub EM 3350PU160
404 0_161
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3350 – XV – 208B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3350 – PU – 160.!RN ×
period. 2 seconds

Table 437: List of Interlocks for 3350-XV-207B

12.2.4 Alarms and Process Setpoints – 3350PU160

Not applicable.
12.2.5 Regulatory Control Loops – 3350PU160

Not applicable.

12.2.6 Advanced Control Loops – 3350PU160

Not applicable

12.2.7 Sequence Description – 3350PU160

The pump start sequence 3340-PU-160, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 367 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN RECPF_Collector404 EM 3350PU160_161 Sub EM 3350PU160
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3350-XV-207B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3340-XV-207A Open Suction Valve Open
seconds seconds
10 60
3. Start 3340-PU-160.MO1 Start pump. Working
seconds seconds

Table 438: Start Sequence 3350PU160

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3350-PU-160 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3350-PU-160-MO1 stopped
The pump stop sequence 3350-PU-160, shall follow the following steps:
TSQST Stop Sequence Table
UN RECPF_Collector404 EM 3350PU160_161 Sub EM 3350PU160
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3350-PU-160.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3350-XV-207A Suction Valve. Closed
seconds seconds
2 20
3. Close 3350-XV-207B Discharge Valve Closed
seconds seconds

Table 439: Stop Sequence 3350PU160

12.3 Engineering Module 2 – 3350PU161

12.3.1 Description – 3350PU161

The following figure shows the elements that make up the 3350PU161 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 368 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3520PU182 3350205
M

FAL
3350205
3520 – PU – 182
FSL

FC
3350160 FT
Reagent
LT Discharge 1
3350-XV- 160 3350-FCV- 160
3350206A
3350PU160 FC
LT 3350161 FT
LSH 3350-XV- 207A 3350-XV- 207B Reagent
LSH FAL Discharge 2
3350206B
3350206A PT 3350-XV- 161 3350-FCV- 161
LSL
3350204 FC
LSL
3350206D 3350162
FSL
3350-PU-160 FT
Reagent
PT
Discharge 3
3350-XV- 162 3350-FCV- 162
3350 – TK – 103
3350-XV- 208A 3350-XV- 208B FC
3350-PU-161 3350163 FT
Reagent
3350PU161 Discharge 4
3350-XV- 163 3350-FCV- 163

FC
3350164 FT

3350PU160_161 Reagent
Discharge 5
3350-XV- 164 3350-FCV- 164
FC
3350165 FT
Reagent
Discharge 6
3350-XV- 165 3350-FCV- 165
FC
3350166 FT
Reagent
Discharge 7
3350-XV- 166 3350-FCV- 166
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 167 3350-FCV- 167
FC
3350168 FT
Reagent
Discharge 9
3350-XV- 168 3350-FCV- 168
FC
3350169 FT
Reagent
Discharge 10
3350-XV- 169 3350-FCV- 169

Figure 39: Blockflow Control Diagram of the 3350PU161 System

12.3.2 Modules of Control 3350PU161

T1 Control Module
Sub
UN RECPF_Collector404 EM 3350PU160_161 3350PU161
EM

Tag Service
3350-PU-161 AP-404 Dosing Pump 2
3350-XV-208A Suction Reagent Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 369 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-XV-208B Discharge Reagent Pump

Table 440: List of Modules of Control for 3350PU161

12.3.3 Interlocks – 3350PU161

T2 Interlock
Tag 3350 – XV – 208A Description Suction Valve Reagent Pump
RECPF_Collector 3350PU16
UN EM Sub EM 3350PU161
404 0_161
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3350 – XV – 207A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3350 – PU – 161.!RN ×
period. 30 seconds

Table 441: List of Interlocks for 3350-XV-208A

T2 Interlock
Tag 3350 – PU - 161 Description Dosing Pump 1
RECPF_Collector 3350PU16
UN EM Sub EM 3350PU161
404 0_161
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Dosing Tank level switch Low (has a low


3350-LSL-206D.Low ×
alarm
Dosing pump flow switch has a low flow Time delay 1
3350-FSL-207A.Low ×
alarm for a time delay second
3350-XV-208A.!Opn Dosing Pump suction valve is not open ×

3350-XV-208B.!Opn Dosing Pump Discharge valve is not open ×


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 370 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 442: List of Interlocks for 3350-PU-161

T2 Interlock
Tag 3350 – XV – 208B Description Discharge Valve Reagent Pump
RECPF_Collector 3350PU16
UN EM Sub EM 3350PU161
404 0_161
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3350 – XV – 207B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3350 – PU – 161.!RN ×
period. 2 seconds

Table 443: List of Interlocks for 3350-XV-208B

12.3.4 Alarms and Process Setpoints – 3350PU161

Not applicable.
12.3.5 Regulatory Control Loops – 3350PU161

Not applicable.

12.3.6 Advanced Control Loops – 3350PU161

Not applicable

12.3.7 Sequence Description – 3350PU161

The pump start sequence 3340-PU-161, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 371 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN RECPF_Collector404 EM 3350PU160_161 Sub EM 3350PU161
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3350-XV-208B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3340-XV-208A Open Suction Valve Open
seconds seconds
10 60
3. Start 3340-PU-161.MO1 Start pump. Working
seconds seconds

Table 444: Start Sequence 3350PU161

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3350-PU-161 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3350-PU-161-MO1 stopped
The pump stop sequence 3350-PU-161, shall follow the following steps:
TSQST Stop Sequence Table
UN RECPF_Collector404 EM 3350PU160_161 Sub EM 3350PU161
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3350-PU-161.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3350-XV-208A Suction Valve. Closed
seconds seconds
2 20
3. Close 3350-XV-208B Discharge Valve Closed
seconds seconds

Table 445: Stop Sequence 3350PU161

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 372 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

13.0 UNIDAD: RECPF_COLLECTORZ6

Refer to:
MQ14-08-DR-3340-PD1093 Reagent Collector Z6
MQ14-08-DR-3340-PD1109 Reagent Day Tank Collector Z6
MQ15-781-DC-3340-IN0001 Reagent Day Tank Vendor Control Philosophy
MQ15-775-IOM-3340-ME0001 Safety Eye Wash and Shower Control Philosophy
A block flow control diagram is depicted below for the RECPF_CollectorZ6 system.
Reagent Bulk
Storage Tank
SC
3520PU181 3350210
M

FAL
3350210
3520 – PU – 181
FSL

FC
3350150 FT
Reagent
LT Discharge 1
3350-XV- 150 3350-FCV- 150
3350211A
3350PU150 FC
LT 3350151 FT
LSH 3350-XV- 212A 3350-XV- 212B Reagent
LSH FAL Discharge 2
3350211B
3350212A PT 3350-XV- 151 3350-FCV- 151
LSL
3350214 FC
LSL
3350211D 3350152
FSL
3350-PU-150 FT
Reagent
PT
Discharge 3
3350-XV- 152 3350-FCV- 152
3350 – TK – 108
3350-XV- 213A 3350-XV- 213B FC
3350-PU-151 3350153 FT
Reagent
3350PU151 Discharge 4
3350-XV- 153 3350-FCV- 153

FC
3350154 FT

3350PU150_151 Reagent
Discharge 5
3350-XV- 154 3350-FCV- 154
FC
3350155 FT
Reagent
Discharge 6
3350-XV- 155 3350-FCV- 155
FC
3350156 FT
Reagent
Discharge 7
3350-XV- 156 3350-FCV- 156
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 157 3350-FCV- 157
FC
3350158 FT
Reagent
Discharge 9
3350-XV- 158 3350-FCV- 158
FC
3350159 FT
Reagent
Discharge 10
3350-XV- 159 3350-FCV- 159

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 373 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 40: Blockflow Control Diagram of RECPF_CollectorZ6

The above control unit is broken into two Engineering Module 1’s with two sub Engineering Module 2’s:
- 3520PU181
- 3350PU150_151
o 3350PU150 (Duty)
o 3350PU151 (Standby)

Only one pump must run at a time. The operator to select the pump manually or plc to select
based on the least number of operating hours at time of start.

13.0.1 Modules of Control RECPF_CollectorZ6

T1 Control Module
UN RECPF_CollectorZ6 EM Sub EM

Tag Service
3350-TK-108 Collector Z6 Day Tank
3350-LSH-211B NIVEL ALTO EN TANQUE DIARIO
3350-LSL-211B NIVEL LOW EN TANQUE DIARIO
3350-LIT-211A NIVEL EN TANQUE DIARIO
3350-FSL-212A Dosing Pump Flow switch
3350-PT-214 PRESIÓN EN LÍNEA DE RETORNO A TANQUE DIARIO
Crossflow Dosing Isolation Valve
3350-XV-150
Crossflow Dosing Isolation Valve
3350-XV-151
Crossflow Dosing Isolation Valve
3350-XV-152
Crossflow Dosing Isolation Valve
3350-XV-153
Crossflow Dosing Isolation Valve
3350-XV-154
Crossflow Dosing Isolation Valve
3350-XV-155
Crossflow Dosing Isolation Valve
3350-XV-156
Crossflow Dosing Isolation Valve
3350-XV-157
Crossflow Dosing Isolation Valve
3350-XV-158
Crossflow Dosing Isolation Valve
3350-XV-159
3350-FIT-159 CORIOLUS FLOW TRANSMITTER
3350-FIT-158 CORIOLUS FLOW TRANSMITTER
3350-FIT-157 CORIOLUS FLOW TRANSMITTER
3350-FIT-156 CORIOLUS FLOW TRANSMITTER

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 374 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-FIT-155 CORIOLUS FLOW TRANSMITTER


3350-FIT-154 CORIOLUS FLOW TRANSMITTER
3350-FIT-153 CORIOLUS FLOW TRANSMITTER
3350-FIT-152 CORIOLUS FLOW TRANSMITTER
3350-FIT-151 CORIOLUS FLOW TRANSMITTER
3350-FIT-150 CORIOLUS FLOW TRANSMITTER
3350-FCV-15
0 REGULATES REAGENT Z6 TO CROSSFLOW #1
3350-FCV-151 REGULATES REAGENT Z6 TO CROSSFLOW #2
3350-FCV-152 REGULATES REAGENT Z6 TO CROSSFLOW #3
3350-FCV-153 REGULATES REAGENT Z6 TO CROSSFLOW #4
3350-FCV-154 REGULATES REAGENT Z6 TO CROSSFLOW #5
3350-FCV-155 REGULATES REAGENT Z6 TO CROSSFLOW #6
3350-FCV-156 REGULATES REAGENT Z6 TO CROSSFLOW #7
3350-FCV-157 REGULATES REAGENT Z6 TO CROSSFLOW #8
3350-FCV-158 REGULATES REAGENT Z6 TO CROSSFLOW #9
3350-FCV-159 REGULATES REAGENT Z6 TO CROSSFLOW #10
3350-ES-102 Reagent Day Tank Safety Shower And Eye Wash Station
3350-LSL-660 WATER LEVEL IN EYEWASH TANK
3350-YL-660 INDICATION LIGHT

Table 446: List of Modules of Control for RECPF_CollectorZ6

13.0.2 Interlocks – RECPF_CollectorZ6

T2 Interlock
Tag 3350-XV-150 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-040.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038A.!OPN
Open

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 375 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 447: List of Interlocks for 3350-XV-150

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-151 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-042.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038B.!OPN
Open

Table 448: List of Interlocks for 3350-XV-151

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-152 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-044.!OPN
IF × Note 1

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 376 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

OR Crossflow Separator Fluidisation teeter


water valve is not open
3340-XV-038C.!OPN OR
Crossflow Feed Isolation Valve is not
Open

Table 449: List of Interlocks for 3350-XV-152

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-153 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-046.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038D.!OPN
Open

Table 450: List of Interlocks for 3350-XV-153

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-154 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 377 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-048.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038E.!OPN
Open

Table 451: List of Interlocks for 3350-XV-154

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-155 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-050.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036A.!OPN
Open

Table 452: List of Interlocks for 3350-XV-155

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-156 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
Z6

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 378 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-052.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036B.!OPN
Open

Table 453: List of Interlocks for 3350-XV-156

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-157 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-054.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036C.!OPN
Open

Table 454: List of Interlocks for 3350-XV-157

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 379 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-XV-158 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-056.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036D.!OPN
Open

Table 455: List of Interlocks for 3350-XV-158

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-159 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-058.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036E.!OPN
Open

Table 456: List of Interlocks for 3350-XV-159

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 380 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-FCV-150 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-150.!OPN ×
open

Table 457: List of Interlocks for 3350-FCV-150

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 381 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-FCV-151 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-151.!OPN ×
open

Table 458: List of Interlocks for 3350-FCV-151

T2 Interlock
Tag 3350-FCV-152 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-152.!OPN ×
open

Table 459: List of Interlocks for 3350-FCV-152

T2 Interlock
Tag 3350-FCV-153 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 382 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-153.!OPN ×
open

Table 460: List of Interlocks for 3350-FCV-153

T2 Interlock
Tag 3350-FCV-154 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-154.!OPN ×
open

Table 461: List of Interlocks for 3350-FCV-154

T2 Interlock
Tag 3350-FCV-155 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-155.!OPN ×
open

Table 462: List of Interlocks for 3350-FCV-155

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 383 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-FCV-156 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-156.!OPN ×
open

Table 463: List of Interlocks for 3350-FCV-156

T2 Interlock
Tag 3350-FCV-157 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-157.!OPN ×
open

Table 464: List of Interlocks for 3350-FCV-157

T2 Interlock
Tag 3350-FCV-158 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 384 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-158.!OPN ×
open

Table 465: List of Interlocks for 3350-FCV-158

T2 Interlock
Tag 3350-FCV-159 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
Z6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-159.!OPN ×
open

Table 466: List of Interlocks for 3350-FCV-159

T2 Interlock
Reagent Day Tank Safety Shower And Eye
Tag 3350-ES-102 Description
Wash Station
RECPF_Collector
UN EM Sub EM
Z6
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 467: List of Interlocks for 3350-ES-102

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 385 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note: Refer to vendor control philosophy. There are no interlocks which affect the operation of
the CPF.

13.0.3 Alarms and Process Setpoints – RECPF_CollectorZ6

T3 Alarms and Process Setpoints


UN RECPF_CollectorZ6 EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3350-LSH-211B 0 - 100 % 98
NIVEL ALTO EN TANQUE DIARIO
3350-LSL-211B 0 - 100 % 2
NIVEL LOW EN TANQUE DIARIO
3350-LIT-211A 0 - 100 % 90 10
NIVEL EN TANQUE DIARIO
3350-FSL-212A 0 – 2.4 M3/hr 2.1
Dosing Pump Flow switch
3350-PT-214 PRESIÓN EN LÍNEA DE RETORNO A
0 - 500 KPa 500 200
TANQUE DIARIO
3350-FIT-159 0 – 11 l/hr 81.6 10.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-158 0 – 11 l/hr 81.6 10.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-157 0 – 11 l/hr 81.6 10.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-156 0 – 11 l/hr 81.6 10.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-155 0 – 11 l/hr 81.6 10.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-154 0 – 11 l/hr 81.6 10.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-153 0 – 11 l/hr 81.6 10.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-152 0 – 11 l/hr 81.6 10.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-151 0 – 11 l/hr 81.6 10.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-150 0 – 11 l/hr 81.6 10.2
CORIOLUS FLOW TRANSMITTER
3350-LSL-660 Refer to vendor control philosophy
WATER LEVEL IN EYEWASH TANK
3350-LSL-660 Refer to vendor control philosophy
WATER LEVEL IN EYEWASH TANK

Table 468: Alarms and Process Setpoint RECPF_CollectorZ6

Note: Level switches setpoints set in field, not within PLC.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 386 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

13.0.4 Regulatory Control Loops – RECPF_CollectorZ6

T5 Regulatory Control Loops


UN RECPF_CollectorZ6 EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-150 Dosing Flow controller Crossflow 1
ion
Dosing Flow controller Crossflow 2 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-151
ion
Dosing Flow controller Crossflow 3 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-152
ion
Dosing Flow controller Crossflow 4 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-153
ion
Dosing Flow controller Crossflow 5 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-154
ion
Dosing Flow controller Crossflow 6 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-155
ion
Dosing Flow controller Crossflow 7 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-156
ion
Dosing Flow controller Crossflow 8 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-157
ion
Dosing Flow controller Crossflow 9 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-158
ion
Dosing Flow controller Crossflow 10 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-159
ion

Table 469: Regulatory Control Loops for RECPF_CollectorZ6

Note 1
The reagents are dosed individually to the Crossflow Separators and Hydrofloats. The flowrate of
each reagent is based upon the calculated dry mass flow rate to the individual module. Refer to
the Crossflow Feed Pump dry mass flow calculations below.
The dry mass flow discharged into Crossflow Distributor 1 (3340 – DB – 103) is then divided by
the number of Crossflow Feed Valves open (3340-XV-038 A – E) for the mass flow to the
respective downstream modules.
Similarly, the dry mass flow discharged into Crossflow Distributor 2 (3340 – DB – 104) is then
divided by the number of Crossflow Feed Valves open (3340-XV-036 A – E) for the mass flow to
the respective downstream modules.
The setpoint flowrate for each individual Crossflow Separator reagent is then based upon the
formulae:
𝑇 × 𝐷𝑜𝑠𝑎𝑔𝑒
𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒 =
𝐷𝑒𝑛𝑠𝑖𝑡𝑦 × 1 000 000 000
Where:
Flowrate (l/hr) = Reagent Setpoint Dosage for a single module (Crossflow or Hydrofloat)
T (dry tph) = Modular dry mass feed rate

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 387 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Density (t/m3) = Reagent density


AP3894 = 1.0 t/m3
AP404 = 1.02 t/m3
Z6 / SIPX / Xanthate = 0.97 t/m3
Diesel = 0.84 t/m3
Frother = 1.01 t/m3
Dosage (g / t feed) = The mass dosage reagent per dry ton of modular feed. This is a
selected input available to the plant metallurgist. The following ranges are expected:
AP3894 = 20 – 28 g / t
AP404 = 20 – 28 g /t
Z6 / SIPX / Xanthate = 175 – 245 g/t
Diesel = 10 – 14 g /t
Frother = 20 – 28 g/t
A reagent dosing control loop will compare the calculated setpoint to the measured flowrate
(3350-FIT-120 through 129, 130 through 139, 140 through 149, 160 through 169, 150 through
159) and adjust the position of the dosing flow control valve (3350-FCV-120 through 129, 130
through 139, 140 through 149, 160 through 169, 150 through 159).

13.0.5 Advanced Control Loops – RECPF_CollectorZ6

Not applicable

13.0.6 Sequence Description – RECPF_CollectorZ6

Not applicable

13.1 Engineering Module– 3520PU181

13.1.1 Description – 3520PU181

The following figure shows the elements that make up the 3520PU181 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 388 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3520PU181 3350210
M

FAL
3350210
3520 – PU – 181
FSL

FC
3350150 FT
Reagent
LT Discharge 1
3350-XV- 150 3350-FCV- 150
3350211A
3350PU150 FC
LT 3350151 FT
LSH 3350-XV- 212A 3350-XV- 212B Reagent
LSH FAL Discharge 2
3350211B
3350212A PT 3350-XV- 151 3350-FCV- 151
LSL
3350214 FC
LSL
3350211D 3350152
FSL
3350-PU-150 FT
Reagent
PT
Discharge 3
3350-XV- 152 3350-FCV- 152
3350 – TK – 108
3350-XV- 213A 3350-XV- 213B FC
3350-PU-151 3350153 FT
Reagent
3350PU151 Discharge 4
3350-XV- 153 3350-FCV- 153

FC
3350154 FT

3350PU150_151 Reagent
Discharge 5
3350-XV- 154 3350-FCV- 154
FC
3350155 FT
Reagent
Discharge 6
3350-XV- 155 3350-FCV- 155
FC
3350156 FT
Reagent
Discharge 7
3350-XV- 156 3350-FCV- 156
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 157 3350-FCV- 157
FC
3350158 FT
Reagent
Discharge 9
3350-XV- 158 3350-FCV- 158
FC
3350159 FT
Reagent
Discharge 10
3350-XV- 159 3350-FCV- 159

Figure 41: Blockflow Control Diagram of the 3520PU181 System

13.1.2 Modules of Control RECPF_Collector404

T1 Control Module
UN RECPF_CollectorZ6 EM 3520PU181 Sub EM

Tag Service
3520-PU-181 Collector Transfer Pump
3520-FSL-210A Low Flow Switch for Reagent Transfer Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 389 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 470: List of Modules of Control for 3520PU181

13.1.3 Interlocks – 3520PU181

T2 Interlock
Tag 3520-PU-181 Description Collector Transfer Pump
RECPF_Collector 3520PU18
UN EM Sub EM
Z6 1
Interlock
Motor Type Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3520 – TK – 003 Level


(others) Delay time 5
Level has a low limit ×
AND s
3520-PU-181.RN
3520-FSL-210A
Flow switch has a low flow limit for a time Delay time
AND ×
delay after the pump motor is running 120s
3520-PU-181.RN
3350-LIT-211A
Delay time 5
AND Day Tank Level has reached a high limit ×
seconds
3520-PU-181.RN
3350-LSH-211B
Delay time 5
AND High Level Limit Switch has an alarm ×
seconds
3520-PU-181.RN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 471: List of Interlocks for 3520PU181

13.1.4 Alarms and Process Setpoints – 3520PU181

T3 Alarms and Process Setpoints


UN RECPF_CollectorZ6 EM 3520PU181 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3520-FSL-
210A Transfer Low Flow Switch alarm 0 - 60 m3/hr 15

Table 472: Alarms and Process Setpoint 3520PU181

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 390 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

13.1.5 Regulatory Control Loops – 3520PU181

Not applicable. The filling of the Reagent Day Tank occurs in batch mode. When 3350-LIT-211A
is Low, the transfer pump is to switch on and then switch off again on attaining a high level
transmitter signal.

13.1.6 Advanced Control Loops – 3520PU181

Not applicable

13.1.7 Sequence Description – 3520PU181

Not applicable
13.2 Engineering Module 2 – 3350PU150

13.2.1 Description – 3350PU150

The following figure shows the elements that make up the 3350PU150 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 391 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3520PU181 3350210
M

FAL
3350210
3520 – PU – 181
FSL

FC
3350150 FT
Reagent
LT Discharge 1
3350-XV- 150 3350-FCV- 150
3350211A
3350PU150 FC
LT 3350151 FT
LSH 3350-XV- 212A 3350-XV- 212B Reagent
LSH FAL Discharge 2
3350211B
3350212A PT 3350-XV- 151 3350-FCV- 151
LSL
3350214 FC
LSL
3350211D 3350152
FSL
3350-PU-150 FT
Reagent
PT
Discharge 3
3350-XV- 152 3350-FCV- 152
3350 – TK – 108
3350-XV- 213A 3350-XV- 213B FC
3350-PU-151 3350153 FT
Reagent
3350PU151 Discharge 4
3350-XV- 153 3350-FCV- 153

FC
3350154 FT

3350PU150_151 Reagent
Discharge 5
3350-XV- 154 3350-FCV- 154
FC
3350155 FT
Reagent
Discharge 6
3350-XV- 155 3350-FCV- 155
FC
3350156 FT
Reagent
Discharge 7
3350-XV- 156 3350-FCV- 156
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 157 3350-FCV- 157
FC
3350158 FT
Reagent
Discharge 9
3350-XV- 158 3350-FCV- 158
FC
3350159 FT
Reagent
Discharge 10
3350-XV- 159 3350-FCV- 159

Figure 42: Blockflow Control Diagram of the 3350PU150 System

13.2.2 Modules of Control 3350PU150

T1 Control Module
Sub
UN RECPF_CollectorZ6 EM 3350PU150_151 3350PU150
EM

Tag Service
3350-PU-150 Dosing Pump 1
3350-XV-212A Suction Reagent Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 392 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-XV-212B Discharge Reagent Pump

Table 473: List of Modules of Control for 3350PU150

13.2.3 Interlocks – 3350PU150

T2 Interlock
Tag 3350 – XV – 212A Description Suction Valve Reagent Pump
RECPF_Collector 3350PU15
UN EM Sub EM 3350PU150
Z6 0_151
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3350 – XV – 212A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3350 – PU – 150.!RN ×
period. 30 seconds

Table 474: List of Interlocks for 3350-XV-212A

T2 Interlock
Tag 3350 – PU - 150 Description Dosing Pump 1
RECPF_Collector 3350PU15
UN EM Sub EM 3350PU150
Z6 0_151
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Dosing Tank level switch Low (has a low


3350-LSL-212D.Low ×
alarm
Dosing pump flow switch has a low flow Time delay 1
3350-FSL-212A.Low ×
alarm for a time delay second
3350-XV-212A.!Opn Dosing Pump suction valve is not open ×

3350-XV-212B.!Opn Dosing Pump Discharge valve is not open ×

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 393 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 475: List of Interlocks for 3350-PU-150

T2 Interlock
Tag 3350 – XV – 212B Description Discharge Valve Reagent Pump
RECPF_Collector 3350PU15
UN EM Sub EM 3350PU150
Z6 0_151
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3350 – XV – 213B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3350 – PU – 150.!RN ×
period. 2 seconds

Table 476: List of Interlocks for 3350-XV-212B

13.2.4 Alarms and Process Setpoints – 3350PU150

Not applicable.
13.2.5 Regulatory Control Loops – 3350PU150

Not applicable.

13.2.6 Advanced Control Loops – 3350PU150

Not applicable

13.2.7 Sequence Description – 3350PU150

The pump start sequence 3340-PU-150, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 394 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN RECPF_CollectorZ6 EM 3350PU150_151 Sub EM 3350PU150
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3350-XV-212B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3340-XV-212A Open Suction Valve Open
seconds seconds
10 60
3. Start 3340-PU-150.MO1 Start pump. Working
seconds seconds

Table 477: Start Sequence 3350PU150

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3350-PU-150 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3350-PU-150-MO1 stopped
The pump stop sequence 3350-PU-150, shall follow the following steps:
TSQST Stop Sequence Table
UN RECPF_CollectorZ6 EM 3350PU150_151 Sub EM 3350PU150
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3350-PU-150.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3350-XV-212A Suction Valve. Closed
seconds seconds
2 20
3. Close 3350-XV-212B Discharge Valve Closed
seconds seconds

Table 478: Stop Sequence 3350PU150

13.3 Engineering Module 2 – 3350PU151

13.3.1 Description – 3350PU151

The following figure shows the elements that make up the 3350PU151 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 395 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3520PU181 3350210
M

FAL
3350210
3520 – PU – 181
FSL

FC
3350150 FT
Reagent
LT Discharge 1
3350-XV- 150 3350-FCV- 150
3350211A
3350PU150 FC
LT 3350151 FT
LSH 3350-XV- 212A 3350-XV- 212B Reagent
LSH FAL Discharge 2
3350211B
3350212A PT 3350-XV- 151 3350-FCV- 151
LSL
3350214 FC
LSL
3350211D 3350152
FSL
3350-PU-150 FT
Reagent
PT
Discharge 3
3350-XV- 152 3350-FCV- 152
3350 – TK – 108
3350-XV- 213A 3350-XV- 213B FC
3350-PU-151 3350153 FT
Reagent
3350PU151 Discharge 4
3350-XV- 153 3350-FCV- 153

FC
3350154 FT

3350PU150_151 Reagent
Discharge 5
3350-XV- 154 3350-FCV- 154
FC
3350155 FT
Reagent
Discharge 6
3350-XV- 155 3350-FCV- 155
FC
3350156 FT
Reagent
Discharge 7
3350-XV- 156 3350-FCV- 156
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 157 3350-FCV- 157
FC
3350158 FT
Reagent
Discharge 9
3350-XV- 158 3350-FCV- 158
FC
3350159 FT
Reagent
Discharge 10
3350-XV- 159 3350-FCV- 159

Figure 43: Blockflow Control Diagram of the 3350PU151 System

13.3.2 Modules of Control 3350PU151

T1 Control Module
Sub
UN RECPF_CollectorZ6 EM 3350PU150_151 3350PU151
EM

Tag Service
3350-PU-151 Dosing Pump 2
3350-XV-213A Suction Reagent Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 396 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-XV-212B Discharge Reagent Pump

Table 479: List of Modules of Control for 3350PU151

13.3.3 Interlocks – 3350PU151

T2 Interlock
Tag 3350 – XV – 213A Description Suction Valve Reagent Pump
RECPF_Collector 3350PU15
UN EM Sub EM 3350PU151
Z6 0_151
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3350 – XV – 212A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3350 – PU – 151.!RN ×
period. 30 seconds

Table 480: List of Interlocks for 3350-XV-213A

T2 Interlock
Tag 3350 – PU - 151 Description Dosing Pump 1
RECPF_Collector 3350PU15
UN EM Sub EM 3350PU151
Z6 0_151
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Dosing Tank level switch Low (has a low


3350-LSL-211D.Low ×
alarm
Dosing pump flow switch has a low flow Time delay 1
3350-FSL-212A.Low ×
alarm for a time delay second
3350-XV-213A.!Opn Dosing Pump suction valve is not open ×

3350-XV-213B.!Opn Dosing Pump Discharge valve is not open ×

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 397 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 481: List of Interlocks for 3350-PU-161

T2 Interlock
Tag 3350 – XV – 213B Description Discharge Valve Reagent Pump
RECPF_Collector 3350PU15
UN EM Sub EM 3350PU151
Z6 0_151
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3350 – XV – 212B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3350 – PU – 151.!RN ×
period. 2 seconds

Table 482: List of Interlocks for 3350-XV-213B

13.3.4 Alarms and Process Setpoints – 3350PU151

Not applicable.
13.3.5 Regulatory Control Loops – 3350PU151

Not applicable.

13.3.6 Advanced Control Loops – 3350PU151

Not applicable

13.3.7 Sequence Description – 3350PU151

The pump start sequence 3340-PU-151, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 398 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN RECPF_CollectorZ6 EM 3350PU150_151 Sub EM 3350PU151
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3350-XV-213B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3340-XV-213A Open Suction Valve Open
seconds seconds
10 60
3. Start 3340-PU-151.MO1 Start pump. Working
seconds seconds

Table 483: Start Sequence 3350PU151

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3350-PU-151 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3350-PU-151-MO1 stopped
The pump stop sequence 3350-PU-151, shall follow the following steps:
TSQST Stop Sequence Table
UN RECPF_CollectorZ6 EM 3350PU150_151 Sub EM 3350PU151
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3350-PU-151.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3350-XV-213A Suction Valve. Closed
seconds seconds
2 20
3. Close 3350-XV-213B Discharge Valve Closed
seconds seconds

Table 484: Stop Sequence 3350PU151

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 399 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

14.0 UNIDAD: RECPF_COLLECTORDIESEL

Refer to:
MQ14-08-DR-3340-PD1094 Reagent Collector Diesel
MQ14-08-DR-3340-PD1110 Reagent Day Tank Collector DIESEL
MQ15-781-DC-3340-IN0001 Reagent Day Tank Vendor Control Philosophy
MQ15-775-IOM-3340-ME0001 Safety Eye Wash and Shower Control Philosophy
A block flow control diagram is depicted below for the RECPF_CollectorDIESEL system.
Reagent Bulk
Storage Tank
SC
3520PU180 3350215
M

FAL
3350215
3520 – PU – 180
FSL

FC
3350130 FT
Reagent
LT Discharge 1
3350-XV- 130 3350-FCV- 130
3350216A
3350PU130 FC
LT 3350131 FT
LSH 3350-XV- 217A 3350-XV- 217B Reagent
LSH FAL Discharge 2
3350216B
3350217A PT 3350-XV- 131 3350-FCV- 131
LSL
3350219 FC
LSL
3350216D 3350132
FSL
3350-PU-130 FT
Reagent
PT
Discharge 3
3350-XV- 132 3350-FCV- 132
3350 – TK – 105
3350-XV- 218A 3350-XV- 218B FC
3350-PU-131 3350133 FT
Reagent
3350PU131 Discharge 4
3350-XV- 133 3350-FCV- 133

FC
3350134 FT

3350PU130_131 Reagent
Discharge 5
3350-XV- 134 3350-FCV- 134
FC
3350135 FT
Reagent
Discharge 6
3350-XV- 135 3350-FCV- 135
FC
3350136 FT
Reagent
Discharge 7
3350-XV- 136 3350-FCV- 136
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 137 3350-FCV- 137
FC
3350138 FT
Reagent
Discharge 9
3350-XV- 138 3350-FCV- 138
FC
3350139 FT
Reagent
Discharge 10
3350-XV- 139 3350-FCV- 139

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 400 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Figure 44: Blockflow Control Diagram of RECPF_CollectorDIESEL

The above control unit is broken into two Engineering Module 1’s with two sub Engineering Module 2’s:
- 3520PU180
- 3350PU130_131
o 3350PU130 (Duty)
o 3350PU131 (Standby)

Only one pump must run at a time. The operator to select the pump manually or plc to select
based on the least number of operating hours at time of start.

14.0.1 Modules of Control RECPF_CollectorDIESEL

T1 Control Module
UN RECPF_CollectorDIESEL EM Sub EM

Tag Service
3350-TK-105 Collector DIESEL Day Tank
3350-LSH-216B NIVEL ALTO EN TANQUE DIARIO
3350-LSL-216B NIVEL LOW EN TANQUE DIARIO
3350-LIT-216A NIVEL EN TANQUE DIARIO
3350-FSL-217A Dosing Pump Flow switch
3350-PT-219 PRESIÓN EN LÍNEA DE RETORNO A TANQUE DIARIO COLECTOR DIESEL
Crossflow Dosing Isolation Valve
3350-XV-130
Crossflow Dosing Isolation Valve
3350-XV-131
Crossflow Dosing Isolation Valve
3350-XV-132
Crossflow Dosing Isolation Valve
3350-XV-133
Crossflow Dosing Isolation Valve
3350-XV-134
Crossflow Dosing Isolation Valve
3350-XV-135
Crossflow Dosing Isolation Valve
3350-XV-136
Crossflow Dosing Isolation Valve
3350-XV-137
Crossflow Dosing Isolation Valve
3350-XV-138
Crossflow Dosing Isolation Valve
3350-XV-139
3350-FIT-139 CORIOLUS FLOW TRANSMITTER
3350-FIT-138 CORIOLUS FLOW TRANSMITTER
3350-FIT-137 CORIOLUS FLOW TRANSMITTER
3350-FIT-136 CORIOLUS FLOW TRANSMITTER

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 401 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-FIT-135 CORIOLUS FLOW TRANSMITTER


3350-FIT-134 CORIOLUS FLOW TRANSMITTER
3350-FIT-133 CORIOLUS FLOW TRANSMITTER
3350-FIT-132 CORIOLUS FLOW TRANSMITTER
3350-FIT-131 CORIOLUS FLOW TRANSMITTER
3350-FIT-130 CORIOLUS FLOW TRANSMITTER
3350-FCV-13
0 REGULATES REAGENT DIESEL TO CROSSFLOW #1
3350-FCV-131 REGULATES REAGENT DIESEL TO CROSSFLOW #2
3350-FCV-132 REGULATES REAGENT DIESEL TO CROSSFLOW #3
3350-FCV-133 REGULATES REAGENT DIESEL TO CROSSFLOW #4
3350-FCV-134 REGULATES REAGENT DIESEL TO CROSSFLOW #5
3350-FCV-135 REGULATES REAGENT DIESEL TO CROSSFLOW #6
3350-FCV-136 REGULATES REAGENT DIESEL TO CROSSFLOW #7
3350-FCV-137 REGULATES REAGENT DIESEL TO CROSSFLOW #8
3350-FCV-138 REGULATES REAGENT DIESEL TO CROSSFLOW #9
3350-FCV-139 REGULATES REAGENT DIESEL TO CROSSFLOW #10

Table 485: List of Modules of Control for RECPF_CollectorDIESEL

14.0.2 Interlocks – RECPF_CollectorDiesel

T2 Interlock
Tag 3350-XV-130 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-040.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038A.!OPN
Open

Table 486: List of Interlocks for 3350-XV-130

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 402 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-131 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-042.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038B.!OPN
Open

Table 487: List of Interlocks for 3350-XV-131

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-132 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-044.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038C.!OPN
Open

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 403 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 488: List of Interlocks for 3350-XV-132

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-133 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-046.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-038D.!OPN
Open

Table 489: List of Interlocks for 3350-XV-133

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-134 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-048.!OPN IF
Crossflow Separator Fluidisation teeter
× Note 1
OR water valve is not open
OR

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 404 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-038E.!OPN Crossflow Feed Isolation Valve is not


Open

Table 490: List of Interlocks for 3350-XV-134

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-135 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-050.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036A.!OPN
Open

Table 491: List of Interlocks for 3350-XV-135

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-136 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 405 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

IF
3340-XV-052.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036B.!OPN
Open

Table 492: List of Interlocks for 3350-XV-136

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-137 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-054.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036C.!OPN
Open

Table 493: List of Interlocks for 3350-XV-137

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-138 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 406 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-056.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036D.!OPN
Open

Table 494: List of Interlocks for 3350-XV-138

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-XV-139 Description Crossflow Dosing Isolation Valve
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-058.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR × Note 1
OR
Crossflow Feed Isolation Valve is not
3340-XV-036E.!OPN
Open

Table 495: List of Interlocks for 3350-XV-139

Note 1 Important protect interlock that cannot be by passable. Dosing reagent into the crossflow separator
without feed and/or fluidisation water can harm the units lining material.

T2 Interlock
Tag 3350-FCV-130 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
DIESEL

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 407 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-130.!OPN ×
open

Table 496: List of Interlocks for 3350-FCV-130

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 408 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-FCV-131 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-131.!OPN ×
open

Table 497: List of Interlocks for 3350-FCV-131

T2 Interlock
Tag 3350-FCV-132 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-132.!OPN ×
open

Table 498: List of Interlocks for 3350-FCV-132

T2 Interlock
Tag 3350-FCV-133 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 409 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-133.!OPN ×
open

Table 499: List of Interlocks for 3350-FCV-133

T2 Interlock
Tag 3350-FCV-134 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-134.!OPN ×
open

Table 500: List of Interlocks for 3350-FCV-134

T2 Interlock
Tag 3350-FCV-135 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
Diesel
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-135.!OPN ×
open

Table 501: List of Interlocks for 3350-FCV-135

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 410 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-FCV-136 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-136.!OPN ×
open

Table 502: List of Interlocks for 3350-FCV-136

T2 Interlock
Tag 3350-FCV-137 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-137.!OPN ×
open

Table 503: List of Interlocks for 3350-FCV-137

T2 Interlock
Tag 3350-FCV-138 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 411 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-138.!OPN ×
open

Table 504: List of Interlocks for 3350-FCV-138

T2 Interlock
Tag 3350-FCV-139 Description REGULATES REAGENT TO CROSSFLOW
RECPF_Collector
UN EM Sub EM
DIESEL
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Crossflow Dosing Isolation Valve is not


3350-XV-139.!OPN ×
open

Table 505: List of Interlocks for 3350-FCV-139

14.0.3 Alarms and Process Setpoints – RECPF_CollectorDIESEL

T3 Alarms and Process Setpoints


UN RECPF_CollectorDIESEL EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3350-LSH-216B 0 - 100 % 98
NIVEL ALTO EN TANQUE DIARIO
3350-LSL-216B 0 - 100 % 2
NIVEL LOW EN TANQUE DIARIO
3350-LIT-216A 0 - 100 % 90 10
NIVEL EN TANQUE DIARIO
3350-FSL-217A 0 – 2.4 M3/hr 2.1
Dosing Pump Flow switch
3350-PT-219 PRESIÓN EN LÍNEA DE RETORNO A
0 - 500 KPa 500 200
TANQUE DIARIO
3350-FIT-139 0 – 11 l/hr 5.4 3.2
CORIOLUS FLOW TRANSMITTER

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 412 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-FIT-138 0 – 11 l/hr 5.4 3.2


CORIOLUS FLOW TRANSMITTER
3350-FIT-137 0 – 11 l/hr 5.4 3.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-136 0 – 11 l/hr 5.4 3.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-135 0 – 11 l/hr 5.4 3.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-134 0 – 11 l/hr 5.4 3.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-133 0 – 11 l/hr 5.4 3.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-132 0 – 11 l/hr 5.4 3.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-131 0 – 11 l/hr 5.4 3.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-130 0 – 11 l/hr 5.4 3.2
CORIOLUS FLOW TRANSMITTER

Table 506: Alarms and Process Setpoint RECPF_CollectorDIESEL

Note: Level switches setpoints set in field, not within PLC.


14.0.4 Regulatory Control Loops – RECPF_CollectorDIESEL

T5 Regulatory Control Loops


UN RECPF_CollectorDiesel EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-130 Dosing Flow controller Crossflow 1
ion
Dosing Flow controller Crossflow 2 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-131
ion
Dosing Flow controller Crossflow 3 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-132
ion
Dosing Flow controller Crossflow 4 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-133
ion
Dosing Flow controller Crossflow 5 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-134
ion
Dosing Flow controller Crossflow 6 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-135
ion
Dosing Flow controller Crossflow 7 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-136
ion
Dosing Flow controller Crossflow 8 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-137
ion
Dosing Flow controller Crossflow 9 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-138
ion
Dosing Flow controller Crossflow 10 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-139
ion

Table 507: Regulatory Control Loops for RECPF_CollectorDIESEL

Note 1
The reagents are dosed individually to the Crossflow Separators and Hydrofloats. The flowrate of
each reagent is based upon the calculated dry mass flow rate to the individual module. Refer to
the Crossflow Feed Pump dry mass flow calculations below.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 413 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The dry mass flow discharged into Crossflow Distributor 1 (3340 – DB – 103) is then divided by
the number of Crossflow Feed Valves open (3340-XV-038 A – E) for the mass flow to the
respective downstream modules.
Similarly, the dry mass flow discharged into Crossflow Distributor 2 (3340 – DB – 104) is then
divided by the number of Crossflow Feed Valves open (3340-XV-036 A – E) for the mass flow to
the respective downstream modules.
The setpoint flowrate for each individual Crossflow Separator reagent is then based upon the
formulae:
𝑇 × 𝐷𝑜𝑠𝑎𝑔𝑒
𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒 =
𝐷𝑒𝑛𝑠𝑖𝑡𝑦 × 1 000 000 000
Where:
Flowrate (l/hr) = Reagent Setpoint Dosage for a single module (Crossflow or Hydrofloat)
T (dry tph) = Modular dry mass feed rate
Density (t/m3) = Reagent density
AP3894 = 1.0 t/m3
AP404 = 1.02 t/m3
Z6 / SIPX / Xanthate = 0.97 t/m3
Diesel = 0.84 t/m3
Frother = 1.01 t/m3
Dosage (g / t feed) = The mass dosage reagent per dry ton of modular feed. This is a
selected input available to the plant metallurgist. The following ranges are expected:
AP3894 = 20 – 28 g / t
AP404 = 20 – 28 g /t
Z6 / SIPX / Xanthate = 175 – 245 g/t
Diesel = 10 – 14 g /t
Frother = 20 – 28 g/t
A reagent dosing control loop will compare the calculated setpoint to the measured flowrate
(3350-FIT-120 through 129, 130 through 139, 140 through 149, 160 through 169, 150 through
159) and adjust the position of the dosing flow control valve (3350-FCV-120 through 129, 130
through 139, 140 through 149, 160 through 169, 150 through 159).

14.0.5 Advanced Control Loops – RECPF_CollectorDIESEL

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 414 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

14.0.6 Sequence Description – RECPF_CollectorDIESEL

Not applicable

14.1 Engineering Module– 3520PU180

14.1.1 Description – 3520PU180

The following figure shows the elements that make up the 3520PU180 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 415 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3520PU180 3350215
M

FAL
3350215
3520 – PU – 180
FSL

FC
3350130 FT
Reagent
LT Discharge 1
3350-XV- 130 3350-FCV- 130
3350216A
3350PU130 FC
LT 3350131 FT
LSH 3350-XV- 217A 3350-XV- 217B Reagent
LSH FAL Discharge 2
3350216B
3350217A PT 3350-XV- 131 3350-FCV- 131
LSL
3350219 FC
LSL
3350216D 3350132
FSL
3350-PU-130 FT
Reagent
PT
Discharge 3
3350-XV- 132 3350-FCV- 132
3350 – TK – 105
3350-XV- 218A 3350-XV- 218B FC
3350-PU-131 3350133 FT
Reagent
3350PU131 Discharge 4
3350-XV- 133 3350-FCV- 133

FC
3350134 FT

3350PU130_131 Reagent
Discharge 5
3350-XV- 134 3350-FCV- 134
FC
3350135 FT
Reagent
Discharge 6
3350-XV- 135 3350-FCV- 135
FC
3350136 FT
Reagent
Discharge 7
3350-XV- 136 3350-FCV- 136
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 137 3350-FCV- 137
FC
3350138 FT
Reagent
Discharge 9
3350-XV- 138 3350-FCV- 138
FC
3350139 FT
Reagent
Discharge 10
3350-XV- 139 3350-FCV- 139

Figure 45: Blockflow Control Diagram of the 3520PU180 System

14.1.2 Modules of Control RECPF_CollectorDiesel

T1 Control Module
UN RECPF_CollectorDIESEL EM 3520PU180 Sub EM

Tag Service
3520-PU-180 Collector Transfer Pump
3520-FSL-215A Low Flow Switch for Reagent Transfer Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 416 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 508: List of Modules of Control for 3520PU180

14.1.3 Interlocks – 3520PU180

T2 Interlock
Tag 3520-PU-180 Description Collector Transfer Pump
RECPF_Collector 3520PU18
UN EM Sub EM
DIESEL 0
Interlock
Motor Type Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3520 – TK – 016 Level


(others) Delay time 5
Level has a low limit ×
AND s
3520-PU-180.RN
3520-FSL-215A
Flow switch has a low flow limit for a time Delay time
AND ×
delay after the pump motor is running 120s
3520-PU-180.RN
3350-LIT-216A
Delay time 5
AND Day Tank Level has reached a high limit ×
seconds
3520-PU-180.RN
3350-LSH-216B
Delay time 5
AND High Level Limit Switch has an alarm ×
seconds
3520-PU-180.RN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 509: List of Interlocks for 3520PU180

14.1.4 Alarms and Process Setpoints – 3520PU180

T3 Alarms and Process Setpoints


UN RECPF_CollectorDIESEL EM 3520PU180 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3520-FSL-
215A Transfer Low Flow Switch alarm 0 - 60 m3/hr 15

Table 510: Alarms and Process Setpoint 3520PU180

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 417 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

14.1.5 Regulatory Control Loops – 3520PU180

Not applicable. The filling of the Reagent Day Tank occurs in batch mode. When 3350-LIT-216A
is Low, the transfer pump is to switch on and then switch off again on attaining a high level
transmitter signal.

14.1.6 Advanced Control Loops – 3520PU180

Not applicable

14.1.7 Sequence Description – 3520PU180

Not applicable

14.2 Engineering Module 2 – 3350PU130

14.2.1 Description – 3350PU130

The following figure shows the elements that make up the 3350PU130 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 418 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3520PU180 3350215
M

FAL
3350215
3520 – PU – 180
FSL

FC
3350130 FT
Reagent
LT Discharge 1
3350-XV- 130 3350-FCV- 130
3350216A
3350PU130 FC
LT 3350131 FT
LSH 3350-XV- 217A 3350-XV- 217B Reagent
LSH FAL Discharge 2
3350216B
3350217A PT 3350-XV- 131 3350-FCV- 131
LSL
3350219 FC
LSL
3350216D 3350132
FSL
3350-PU-130 FT
Reagent
PT
Discharge 3
3350-XV- 132 3350-FCV- 132
3350 – TK – 105
3350-XV- 218A 3350-XV- 218B FC
3350-PU-131 3350133 FT
Reagent
3350PU131 Discharge 4
3350-XV- 133 3350-FCV- 133

FC
3350134 FT

3350PU130_131 Reagent
Discharge 5
3350-XV- 134 3350-FCV- 134
FC
3350135 FT
Reagent
Discharge 6
3350-XV- 135 3350-FCV- 135
FC
3350136 FT
Reagent
Discharge 7
3350-XV- 136 3350-FCV- 136
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 137 3350-FCV- 137
FC
3350138 FT
Reagent
Discharge 9
3350-XV- 138 3350-FCV- 138
FC
3350139 FT
Reagent
Discharge 10
3350-XV- 139 3350-FCV- 139

Figure 46: Blockflow Control Diagram of the 3350PU130 System

14.2.2 Modules of Control 3350PU130

T1 Control Module
Sub
UN RECPF_CollectorDIESEL EM 3350PU130_131 3350PU130
EM

Tag Service
3350-PU-130 Dosing Pump 1
3350-XV-217A Suction Reagent Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 419 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-XV-217B Discharge Reagent Pump

Table 511: List of Modules of Control for 3350PU130

14.2.3 Interlocks – 3350PU130

T2 Interlock
Tag 3350 – XV – 217A Description Suction Valve Reagent Pump
RECPF_Collector 3350PU13
UN EM Sub EM 3350PU130
DIESEL 0_131
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3350 – XV – 218A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3350 – PU – 130.!RN ×
period. 30 seconds

Table 512: List of Interlocks for 3350-XV-217A

T2 Interlock
Tag 3350 – PU - 130 Description Dosing Pump 1
RECPF_Collector 3350PU13
UN EM Sub EM 3350PU130
DIESEL 0_131
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Dosing Tank level switch Low (has a low


3350-LSL-216D.Low ×
alarm
Dosing pump flow switch has a low flow Time delay 1
3350-FSL-217A.Low ×
alarm for a time delay second
3350-XV-217A.!Opn Dosing Pump suction valve is not open ×

3350-XV-217B.!Opn Dosing Pump Discharge valve is not open ×

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 420 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 513: List of Interlocks for 3350-PU-130

T2 Interlock
Tag 3350 – XV – 217B Description Discharge Valve Reagent Pump
RECPF_Collector 3350PU13
UN EM Sub EM 3350PU130
DIESEL 0_131
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3350 – XV – 218B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3350 – PU – 130.!RN ×
period. 2 seconds

Table 514: List of Interlocks for 3350-XV-217B

14.2.4 Alarms and Process Setpoints – 3350PU130

Not applicable.
14.2.5 Regulatory Control Loops – 3350PU130

Not applicable.

14.2.6 Advanced Control Loops – 3350PU130

Not applicable

14.2.7 Sequence Description – 3350PU130

The pump start sequence 3340-PU-160, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 421 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN RECPF_CollectorDIESEL EM 3350PU130_131 Sub EM 3350PU130
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3350-XV-217B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3340-XV-217A Open Suction Valve Open
seconds seconds
10 60
3. Start 3340-PU-130.MO1 Start pump. Working
seconds seconds

Table 515: Start Sequence 3350PU130

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3350-PU-130 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3350-PU-130-MO1 stopped
The pump stop sequence 3350-PU-130, shall follow the following steps:
TSQST Stop Sequence Table
UN RECPF_CollectorDIESEL EM 3350PU130_131 Sub EM 3350PU130
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3350-PU-130.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3350-XV-217A Suction Valve. Closed
seconds seconds
2 20
3. Close 3350-XV-217B Discharge Valve Closed
seconds seconds

Table 516: Stop Sequence 3350PU130

14.3 Engineering Module 2 – 3350PU131

14.3.1 Description – 3350PU131

The following figure shows the elements that make up the 3350PU131 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 422 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Reagent Bulk
Storage Tank
SC
3520PU180 3350215
M

FAL
3350215
3520 – PU – 180
FSL

FC
3350130 FT
Reagent
LT Discharge 1
3350-XV- 130 3350-FCV- 130
3350216A
3350PU130 FC
LT 3350131 FT
LSH 3350-XV- 217A 3350-XV- 217B Reagent
LSH FAL Discharge 2
3350216B
3350217A PT 3350-XV- 131 3350-FCV- 131
LSL
3350219 FC
LSL
3350216D 3350132
FSL
3350-PU-130 FT
Reagent
PT
Discharge 3
3350-XV- 132 3350-FCV- 132
3350 – TK – 105
3350-XV- 218A 3350-XV- 218B FC
3350-PU-131 3350133 FT
Reagent
3350PU131 Discharge 4
3350-XV- 133 3350-FCV- 133

FC
3350134 FT

3350PU130_131 Reagent
Discharge 5
3350-XV- 134 3350-FCV- 134
FC
3350135 FT
Reagent
Discharge 6
3350-XV- 135 3350-FCV- 135
FC
3350136 FT
Reagent
Discharge 7
3350-XV- 136 3350-FCV- 136
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 137 3350-FCV- 137
FC
3350138 FT
Reagent
Discharge 9
3350-XV- 138 3350-FCV- 138
FC
3350139 FT
Reagent
Discharge 10
3350-XV- 139 3350-FCV- 139

Figure 47: Blockflow Control Diagram of the 3350PU131 System

14.3.2 Modules of Control 3350PU131

T1 Control Module
Sub
UN RECPF_CollectorDIESEL EM 3350PU130_131 3350PU131
EM

Tag Service
3350-PU-131 Dosing Pump 2
3350-XV-218A Suction Reagent Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 423 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-XV-218B Discharge Reagent Pump

Table 517: List of Modules of Control for 3350PU131

14.3.3 Interlocks – 3350PU131

T2 Interlock
Tag 3350 – XV – 218A Description Suction Valve Reagent Pump
RECPF_Collector 3350PU13
UN EM Sub EM 3350PU131
DIESEL 0_131
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3350 – XV – 217A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3350 – PU – 131.!RN ×
period. 30 seconds

Table 518: List of Interlocks for 3350-XV-218A

T2 Interlock
Tag 3350 – PU - 131 Description Dosing Pump 2
RECPF_Collector 3350PU13
UN EM Sub EM 3350PU131
DIESEL 0_131
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Dosing Tank level switch Low (has a low


3350-LSL-216D.Low ×
alarm
Dosing pump flow switch has a low flow Time delay 1
3350-FSL-217A.Low ×
alarm for a time delay second
3350-XV-218A.!Opn Dosing Pump suction valve is not open ×

3350-XV-218B.!Opn Dosing Pump Discharge valve is not open ×

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 424 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 519: List of Interlocks for 3350-PU-161

T2 Interlock
Tag 3350 – XV – 218B Description Discharge Valve Reagent Pump
RECPF_Collector 3350PU13
UN EM Sub EM 3350PU131
DIESEL 0_131
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3350 – XV – 217B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3350 – PU – 131.!RN ×
period. 2 seconds

Table 520: List of Interlocks for 3350-XV-218B

14.3.4 Alarms and Process Setpoints – 3350PU131

Not applicable.
14.3.5 Regulatory Control Loops – 3350PU131

Not applicable.

14.3.6 Advanced Control Loops – 3350PU131

Not applicable

14.3.7 Sequence Description – 3350PU131

The pump start sequence 3340-PU-131, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 425 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN RECPF_CollectorDIESEL EM 3350PU130_131 Sub EM 3350PU131
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3350-XV-218B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3340-XV-218A Open Suction Valve Open
seconds seconds
10 60
3. Start 3340-PU-131.MO1 Start pump. Working
seconds seconds

Table 521: Start Sequence 3350PU131

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3350-PU-131 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3350-PU-131-MO1 stopped
The pump stop sequence 3350-PU-131, shall follow the following steps:
TSQST Stop Sequence Table
UN RECPF_CollectorDIESEL EM 3350PU160_131 Sub EM 3350PU131
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3350-PU-131.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3350-XV-218A Suction Valve. Closed
seconds seconds
2 20
3. Close 3350-XV-218B Discharge Valve Closed
seconds seconds

Table 522: Stop Sequence 3350PU131

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 426 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

15.0 UNIDAD: RECPF_ALMESPUMANTE

Refer to:
MQ14-08-DR-3340-PD1095 Reagent Frother Polypropylene
MQ15-780-PRC-3340-GA0001 Frother Bulk Storage and Transfer Control Philosophy
A block flow control diagram is depicted below for the RECPF_AlmEspumante system.
LT
3350PU178 3350221B
SC
LT
FAL 3350220
LSH
SC 3350PU176_177
LSH 3350222
3350220 3350221A
M
FSL M

3350 – PU – 176
XV – 3350101 3350 – PU – 178 3350 – TK – 110
SC
3350223
M

FAL
3350223
3350 – PU – 178
FSL

Reagent Day
Tank

LAH
3350107 3340PU199
M Tails Launder
LSH
TE

3340 – PU – 199

Figure 48: Blockflow Control Diagram of RECPF_AlmEspumante

The above control unit is broken into three Engineering Module 1’s with no sub Engineering Module 2’s:
- 3350PU199
- 3350PU76_177
- 3350PU178

15.0.1 Modules of Control RECPF_AlmEspumante

T1 Control Module
UN RECPF_AlmEspumante EM Sub EM

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 427 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag Service
3350-LIT-221B NIVEL EN TANQUE ALMACENAMIENTO DE POLYPROPILENO
3350-LSHH-221A NIVEL MUY ALTO EN TANQUE ALMACENAMIENTO

Table 523: List of Modules of Control for RECPF_AlmEspumante

15.0.2 Interlocks – RECPF_AlmEspumante

There are no interlocks


15.0.3 Alarms and Process Setpoints – RECPF_AlmEspumante

T3 Alarms and Process Setpoints


UN RECPF_AlmEspumante EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
NIVEL EN TANQUE
3350-LIT-221B ALMACENAMIENTO DE 0 - 100 % 98 95 10 5
POLYPROPILENO
3350-LSHH-
221A NIVEL MUY ALTO EN TANQUE 0 - 100 % 98
ALMACENAMIENTO

Table 524: Alarms and Process Setpoint RECPF_AlmEspumante

Note: Level switches setpoints set in field, not within PLC.


15.0.4 Regulatory Control Loops – RECPF_AlmEspumante

There are no regulatory control loops for this section.

15.0.5 Advanced Control Loops – RECPF_AlmEspumante

Not applicable

15.0.6 Sequence Description – RECPF_AlmEspumante

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 428 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

15.1 Engineering Module– 3350PU178

15.1.1 Description – 3350PU178

The following figure shows the elements that make up the 3350PU178 equipment module.
LT
3350PU178 3350221B
SC
LT
FAL 3350220
LSH
SC 3350PU176_177
LSH 3350222
3350220 3350221A
M
FSL M

3350 – PU – 176
XV – 3350101 3350 – PU – 178 3350 – TK – 110
SC
3350223
M

FAL
3350223
3350 – PU – 178
FSL

Reagent Day
Tank

LAH
3350107 3340PU199
M Tails Launder
LSH
TE

3340 – PU – 199

Figure 49: Blockflow Control Diagram of the 3350PU178 System

15.1.2 Modules of Control 3350PU178

T1 Control Module
UN RECPF_AlmEspumante EM 3350PU178 Sub EM

Tag Service
3350-PU-178 Polypropylene Glycol Frother Supply Pump
3350-XV-220A Polypropylene Glycol Frother Supply Pump Suction Valve
3350-FSL-220A REACTIVO POLYPROPILENO BOMBA 3350-PU-178

Table 525: List of Modules of Control for 3350PU178

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 429 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

15.1.3 Interlocks – 3350PU178

T2 Interlock
Tag 3350-PU-178 Description Polypropylene Glycol Frother Supply Pump

RECPF_AlmEspu
UN EM 3350PU17 Sub EM
mante
8
Interlock
Motor Type Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3350 – LIT – 221A.H


Delay time 5
OR Level has a high or High High limit ×
s
3350 – LIT – 221A.HH
3520-FSL-220A.L
Flow switch has a low flow limit for a time Delay time
AND ×
delay after the pump motor is running 120s
3520-PU-176.RN
3350-XV-220.!Opn
Delay time 5
AND Suction Valve not open ×
seconds
3520-PU-176.RN
Delay time 5
3350-LSH-221B High Level Limit Switch has an alarm ×
seconds
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 526: List of Interlocks for 3350 – PU – 178

T2 Interlock
Polypropylene Glycol Frother Supply Pump
Tag 3350-XV - 220 Description
Suction Valve
RECPF_AlmEspu
UN EM 3350PU17 Sub EM
mante
8
Failure Position:
Fail Closed (FC)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Time Delay
3340 – PU – 178.!RN Pump has not run for a time delay ×
30 seconds
3340 – PU – 178 not Time Delay
If Pump is not ready to run ×
ready to run 30 seconds

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 430 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 527: List of Interlocks for 3350 – XV - 220

15.1.4 Alarms and Process Setpoints – 3350PU178

T3 Alarms and Process Setpoints


UN RECPF_AlmEspumante EM 3350PU178 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3350-FSL-
220A Transfer Low Flow Switch alarm 0 - 60 m3/hr 15

Table 528: Alarms and Process Setpoint 3350PU178

15.1.5 Regulatory Control Loops – 3350PU178

Not applicable. The filling of the Polypropylene Glycol Tank occurs in batch mode when the
offloading truck is connected to the offloading pump. When 3350-LIT-224A is High or high high
or 3350-LSH-221B is high, the pump is to switch off.

15.1.6 Advanced Control Loops – 3350PU178

Not applicable

15.1.7 Sequence Description – 3350PU178

Not applicable

15.2 Engineering Module– 3350PU176_177

15.2.1 Description – 3350PU176_177

The following figure shows the elements that make up the 3350PU176_177 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 431 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

LT
3350PU178 3350221B
SC
LT
FAL 3350220
LSH
SC 3350PU176_177
LSH 3350222
3350220 3350221A
M
FSL M

3350 – PU – 176
XV – 3350101 3350 – PU – 178 3350 – TK – 110
SC
3350223
M

FAL
3350223
3350 – PU – 178
FSL

Reagent Day
Tank

LAH
3350107 3340PU199
M Tails Launder
LSH
TE

3340 – PU – 199

Figure 50: Blockflow Control Diagram of the 3350PU176_177 System

15.2.2 Modules of Control 3350PU176_177

T1 Control Module
UN RECPF_AlmEspumante EM Sub EM
3350PU176_177
Tag Service
3350-PU-176 Polypropylene Glycol Frother Pump 1
3350-FSL-223A REACTIVO POLYPROPILENO BOMBAS 3350-PU-176/177
3350-PU-177 Polypropylene Glycol Frother Pump 2

Table 529: List of Modules of Control for 3350PU176_177

Pumps 3340-PU-176 and 3340-PU-177 are a duty and standby configuration. Only one pump
must run at any time. Only one pump must run at a time. The operator to select the pump
manually or plc to select based on the least number of operating hours at time of start.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 432 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

15.2.3 Interlocks – 3350PU176_177

T2 Interlock
Tag 3350-PU-176 Description Polypropylene Glycol Frother Pump 1

RECPF_AlmEspu
UN EM 3350PU17 Sub EM
mante
6_177
Interlock
Motor Type Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3350 – LIT – 221.L


Delay time 5
OR Level has a low or Low Low limit ×
s
3350 – LIT – 221.LL
3520-FSL-223A
Flow switch has a low flow limit for a time Delay time
AND ×
delay after the pump motor is running 120s
3520-PU-176.RN
3350-LIT-224A.H
Delay time 5
AND Day Tank Level has reached a high limit ×
seconds
3520-PU-176.RN
3350-LSH-224B
Delay time 5
AND High Level Limit Switch has an alarm ×
seconds
3520-PU-176.RN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 530: List of Interlocks for 3350 – PU – 176

T2 Interlock
Tag 3350-PU-177 Description Polypropylene Glycol Frother Pump 2

RECPF_AlmEspu
UN EM 3350PU17 Sub EM
mante
6_177
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3350 – LIT – 221.L


Delay time 5
OR Level has a low or Low Low limit ×
s
3350 – LIT – 221.LL
3520-FSL-223A
Flow switch has a low flow limit for a time Delay time
AND ×
delay after the pump motor is running 120s
3520-PU-176.RN
3350-LIT-224A.H
Delay time 5
AND Day Tank Level has reached a high limit ×
seconds
3520-PU-176.RN

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 433 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-LSH-224B
Delay time 5
AND High Level Limit Switch has an alarm ×
seconds
3520-PU-176.RN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 531: List of Interlocks for 3350 – PU - 177

15.2.4 Alarms and Process Setpoints – 3350PU176_177

T3 Alarms and Process Setpoints


UN RECPF_AlmEspumante EM 3350PU176_177 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3350-FSL-
223A Transfer Low Flow Switch alarm 0 - 60 m3/hr 15

Table 532: Alarms and Process Setpoint 3350PU176_177

15.2.5 Regulatory Control Loops – 3350PU176_177

Not applicable. The filling of the Reagent Day Tank occurs in batch mode. When 3350-LIT-224A
is Low, the transfer pump is to switch on and then switch off again on attaining a high level
transmitter signal.

15.2.6 Advanced Control Loops – 3350PU176_177

Not applicable

15.2.7 Sequence Description – 3350PU176_177

Not applicable

15.3 Engineering Module 2 – 3350PU199

15.3.1 Unit of Control Modules – 3350PU199

The following table shows the details of the Control Modules considered for this Equipment
Module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 434 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T1 Control Module
UN RECPF_AlmEspumante EM 3350PU199 Sub EM

Tag Service
3350-TE-107 Bearing temperature switch
3350-LSH-107 Level Switch High

Table 533: List of Unit Controls – 3350PU199

15.3.2 Interlocks – 3350PU199

T2 Interlock
Tag 3350-PU-199 Description Bulk Reagent Spillage Pump
RECPF_AlmEspu Sub
UN EM 3350PU199
mante EM
Interlock
Motor Type M1 Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Delay 10
3350-LSH-107.ACT High level switch activated × seconds
Note 1
3350-TE-107.ACT High bearing temperature alarm ×
BLACKOUT Delay 5
Electrical BlackOut Activated ×
ELECTRICO.ACT seconds

Table 534: List of Interlocks for 3350-PU-199

Note 1: Pump to run 15 minutes after the high level has been removed.
15.3.3 Alarms and Process Setpoints – 3350PU199

T3 Alarms and Process Setpoints


UN RECPF_AlmEspumante EM 3350PU199 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3350-LSH-107 Bulk Reagent Spillage Pump


0 - 100 % 27%
High Switch Alarm

Table 535: Alarms and Process Setpoint 3350PU199

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 435 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note: Level switches setpoints set in field, not within PLC.


15.3.4 Binary Messages – 3350PU199

Not applicable.
15.3.5 Regulatory Control Loops – 3350PU199

Not applicable.
15.3.6 Advanced Control Loops – 3350PU199

Not applicable
15.3.7 Description – 3350PU199

Spillage in the Bulk Reagent Storage area will gravitate to the Bulk Reagent Spillage Pump (3350
– PU – 199). The pump will discharge by manual selection to either:
 The Emergency Tails Launder (3340 – LN - 104);
This equipment can operate in manual mode or automatic mode. In manual mode, the start and
stop by the PLC will depend on the start/stop command that the operator. The operation of the
pump in Automatic Mode will occur if:
- The pump will start automatically, if it is ready to Operate in Sequence, and if Sump level
switch is high.
- The sump pump will stop automatically 15 minutes after the level switch high has fallen
away. The time delay in stopping the pump allows the pump to continue to run while hose
down of the area is occurring.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 436 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

16.0 UNIDAD: RECPF_ ESPUMANTE

Refer to:
MQ14-08-DR-3340-PD1095 Reagent Polypropylene
MQ14-08-DR-3340-PD1109 Reagent Day Tank Polypropylene
MQ15-781-DC-3340-IN0001 Reagent Day Tank Vendor Control Philosophy
MQ15-775-IOM-3340-ME0001 Safety Eye Wash and Shower Control Philosophy
A block flow control diagram is depicted below for the RECPF_Espumante system.
Bulk Storage
Transfer

FC
3350140 FT
Reagent
LT Discharge 1
3350-XV- 140 3350-FCV- 140
3350224A
3350PU140 FC
LT 3350141 FT
LSH FAL
3350-XV- 225A 3350-XV- 225B Reagent
LSH Discharge 2
3350224B 3350225A PT 3350-XV- 141 3350-FCV- 141
LSL 3350226
FC
LSL FSL
3350224D 3350142 FT
3350-PU-140
PT Reagent
Discharge 3
3350-XV- 142 3350-FCV- 142
3350 – TK – 106
3350-XV- 226A 3350-XV- 226B FC
3350-PU-141 3350143 FT
Reagent
3350PU141 Discharge 4
3350-XV- 143 3350-FCV- 143

FC
3350144 FT
3350PU140_141 Reagent
Discharge 5
3350-XV- 144 3350-FCV- 144
FC
3350145 FT
Reagent
Discharge 6
3350-ES-101 3350-XV- 145 3350-FCV- 145
FC
3350146 FT
Reagent
Discharge 7
3350-XV- 146 3350-FCV- 146
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 147 3350-FCV- 147
FC
3350148 FT
Reagent
Discharge 9
3350-XV- 148 3350-FCV- 148
FC
3350149 FT
Reagent
Discharge 10
3350-XV- 149 3350-FCV- 149

Figure 51: Blockflow Control Diagram of RECPF_Espumante

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 437 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The above control unit is broken into one Engineering Module 1’s with two sub Engineering Module 2’s:
- 3340PU150_151
o 3340PU150 (Duty)
o 3340PU151 (Standby)

Only one pump must run at a time. The operator to select the pump manually or plc to select
based on the least number of operating hours at time of start.

16.0.1 Modules of Control RECPF_Espumante

T1 Control Module
UN RECPF_Espumante EM Sub EM

Tag Service
3350-TK-106 Frother Day Tank
3350-LSH-224B NIVEL ALTO EN TANQUE DIARIO
3350-LSL-224B NIVEL LOW EN TANQUE DIARIO
3350-LIT-224A NIVEL EN TANQUE DIARIO
3350-FSL-225A Dosing Pump Flow switch
3350-PT-227 PRESIÓN EN LÍNEA DE RETORNO A TANQUE DIARIO
Crossflow Dosing Isolation Valve
3350-XV-140
Crossflow Dosing Isolation Valve
3350-XV-141
Crossflow Dosing Isolation Valve
3350-XV-142
Crossflow Dosing Isolation Valve
3350-XV-143
Crossflow Dosing Isolation Valve
3350-XV-144
Crossflow Dosing Isolation Valve
3350-XV-145
Crossflow Dosing Isolation Valve
3350-XV-146
Crossflow Dosing Isolation Valve
3350-XV-147
Crossflow Dosing Isolation Valve
3350-XV-148
Crossflow Dosing Isolation Valve
3350-XV-149
3350-FIT-149 CORIOLUS FLOW TRANSMITTER
3350-FIT-158 CORIOLUS FLOW TRANSMITTER
3350-FIT-147 CORIOLUS FLOW TRANSMITTER
3350-FIT-146 CORIOLUS FLOW TRANSMITTER
3350-FIT-145 CORIOLUS FLOW TRANSMITTER
3350-FIT-144 CORIOLUS FLOW TRANSMITTER
3350-FIT-143 CORIOLUS FLOW TRANSMITTER

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 438 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3350-FIT-142 CORIOLUS FLOW TRANSMITTER


3350-FIT-141 CORIOLUS FLOW TRANSMITTER
3350-FIT-140 CORIOLUS FLOW TRANSMITTER
3350-FCV-14
0 REGULATES REAGENT Z6 TO CROSSFLOW #1
3350-FCV-141 REGULATES REAGENT Z6 TO CROSSFLOW #2
3350-FCV-142 REGULATES REAGENT Z6 TO CROSSFLOW #3
3350-FCV-143 REGULATES REAGENT Z6 TO CROSSFLOW #4
3350-FCV-144 REGULATES REAGENT Z6 TO CROSSFLOW #5
3350-FCV-145 REGULATES REAGENT Z6 TO CROSSFLOW #6
3350-FCV-146 REGULATES REAGENT Z6 TO CROSSFLOW #7
3350-FCV-147 REGULATES REAGENT Z6 TO CROSSFLOW #8
3350-FCV-148 REGULATES REAGENT Z6 TO CROSSFLOW #9
3350-FCV-149 REGULATES REAGENT Z6 TO CROSSFLOW #10
3350-ES-101 Reagent Day Tank Safety Shower And Eye Wash Station
3350-LSL-661 WATER LEVEL IN EYEWASH TANK
3350-YL-661 INDICATION LIGHT

Table 536: List of Modules of Control for RECPF_Espumante

16.0.2 Interlocks – RECPF_Espumante

T2 Interlock
Tag 3350-XV-140 Description Hydrofloat Dosing Isolation Valve
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-040.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR ×
OR
Crossflow Underflow Isolation Valve is not
3340-XV-107.!OPN
Open

Table 537: List of Interlocks for 3350-XV-140

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 439 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-XV-141 Description Hydrofloat Dosing Isolation Valve
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-042.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR ×
OR
Crossflow Underflow Isolation Valve is not
3340-XV-117.!OPN
Open

Table 538: List of Interlocks for 3350-XV-141

T2 Interlock
Tag 3350-XV-142 Description Hydrofloat Dosing Isolation Valve
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-044.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR ×
OR
Crossflow Underflow Isolation Valve is not
3340-XV-127.!OPN
Open

Table 539: List of Interlocks for 3350-XV-142

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 440 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-XV-143 Description Hydrofloat Dosing Isolation Valve
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-046.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR ×
OR
Crossflow Underflow Isolation Valve is not
3340-XV-137.!OPN
Open

Table 540: List of Interlocks for 3350-XV-143

T2 Interlock
Tag 3350-XV-144 Description Hydrofloat Dosing Isolation Valve
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-048.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR ×
OR
Crossflow Underflow Isolation Valve is not
3340-XV-147.!OPN
Open

Table 541: List of Interlocks for 3350-XV-144

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 441 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3350-XV-145 Description Hydrofloat Dosing Isolation Valve


RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-050.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR ×
OR
Crossflow Underflow Isolation Valve is not
3340-XV-157.!OPN
Open

Table 542: List of Interlocks for 3350-XV-145

T2 Interlock
Tag 3350-XV-146 Description Hydrofloat Dosing Isolation Valve
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-052.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR ×
OR
Crossflow Underflow Isolation Valve is not
3340-XV-167.!OPN
Open

Table 543: List of Interlocks for 3350-XV-146

T2 Interlock
Tag 3350-XV-147 Description Hydrofloat Dosing Isolation Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 442 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-054.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR ×
OR
Crossflow Underflow Isolation Valve is not
3340-XV-177.!OPN
Open

Table 544: List of Interlocks for 3350-XV-147

T2 Interlock
Tag 3350-XV-148 Description Hydrofloat Dosing Isolation Valve
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

IF
3340-XV-056.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR ×
OR
Crossflow Underflow Isolation Valve is not
3340-XV-187.!OPN
Open

Table 545: List of Interlocks for 3350-XV-148

T2 Interlock
Tag 3350-XV-149 Description Hydrofloat Dosing Isolation Valve
RECPF_Espuma
UN EM Sub EM
nte

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 443 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF
3340-XV-058.!OPN
Crossflow Separator Fluidisation teeter
water valve is not open
OR ×
OR
Crossflow Underflow Isolation Valve is not
3340-XV-197.!OPN
Open

Table 546: List of Interlocks for 3350-XV-149

T2 Interlock
Tag 3350-FCV-140 Description REGULATES REAGENT TO Hydrofloat
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Hydrofloat Dosing Isolation Valve is not


3350-XV-140.!OPN ×
open

Table 547: List of Interlocks for 3350-FCV-140

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 444 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-FCV-141 Description REGULATES REAGENT TO HYDROFLOAT
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Hydrofloat Dosing Isolation Valve is not


3350-XV-141.!OPN ×
open

Table 548: List of Interlocks for 3350-FCV-141

T2 Interlock
Tag 3350-FCV-142 Description REGULATES REAGENT TO HYDROFLOAT
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Hydrofloat Dosing Isolation Valve is not


3350-XV-142.!OPN ×
open

Table 549: List of Interlocks for 3350-FCV-142

T2 Interlock
Tag 3350-FCV-143 Description REGULATES REAGENT TO HYDROFLOAT
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 445 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Hydrofloat Dosing Isolation Valve is not


3350-XV-143.!OPN ×
open

Table 550: List of Interlocks for 3350-FCV-143

T2 Interlock
Tag 3350-FCV-144 Description REGULATES REAGENT TO HYDROFLOAT
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Hydrofloat Dosing Isolation Valve is not


3350-XV-144.!OPN ×
open

Table 551: List of Interlocks for 3350-FCV-144

T2 Interlock
Tag 3350-FCV-145 Description REGULATES REAGENT TO HYDROFLOAT
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Hydrofloat Dosing Isolation Valve is not


3350-XV-145.!OPN ×
open

Table 552: List of Interlocks for 3350-FCV-145

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 446 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350-FCV-146 Description REGULATES REAGENT TO HYDROFLOAT
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Hydrofloat Dosing Isolation Valve is not


3350-XV-146.!OPN ×
open

Table 553: List of Interlocks for 3350-FCV-146

T2 Interlock
Tag 3350-FCV-147 Description REGULATES REAGENT TO HYDROFLOAT
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Hydrofloat Dosing Isolation Valve is not


3350-XV-147.!OPN ×
open

Table 554: List of Interlocks for 3350-FCV-147

T2 Interlock
Tag 3350-FCV-148 Description REGULATES REAGENT TO HYDROFLOAT
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 447 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Hydrofloat Dosing Isolation Valve is not


3350-XV-148.!OPN ×
open

Table 555: List of Interlocks for 3350-FCV-148

T2 Interlock
Tag 3350-FCV-149 Description REGULATES REAGENT TO HYDROFLOAT
RECPF_Espuma
UN EM Sub EM
nte
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Hydrofloat Dosing Isolation Valve is not


3350-XV-149.!OPN ×
open

Table 556: List of Interlocks for 3350-FCV-149

T2 Interlock
Reagent Bulk Storage Safety Shower And Eye
Tag 3350-ES-101 Description
Wash Station
RECPF_Espuma
UN EM Sub EM
nte
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 557: List of Interlocks for 3350-ES-101

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 448 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note: Refer to vendor control philosophy. There are no interlocks which affect the operation of
the CPF.

16.0.3 Alarms and Process Setpoints – RECPF_Espumante

T3 Alarms and Process Setpoints


UN RECPF_Espumante EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3350-LSH-224B 0 - 100 % 98
NIVEL ALTO EN TANQUE DIARIO
3350-LSL-224B 0 - 100 % 2
NIVEL LOW EN TANQUE DIARIO
3350-LIT-224A 0 - 100 % 90 10
NIVEL EN TANQUE DIARIO
3350-FSL-225A 0 – 2.4 M3/hr 2.1
Dosing Pump Flow switch
3350-PT-227 PRESIÓN EN LÍNEA DE RETORNO A
0 - 500 KPa 500 200
TANQUE DIARIO
3350-FIT-149 0 – 11 l/hr 4.0 2.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-148 0 – 11 l/hr 4.0 2.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-147 0 – 11 l/hr 4.0 2.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-146 0 – 11 l/hr 4.0 2.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-145 0 – 11 l/hr 4.0 2.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-144 0 – 11 l/hr 4.0 2.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-143 0 – 11 l/hr 4.0 2.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-142 0 – 11 l/hr 4.0 2.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-141 0 – 11 l/hr 4.0 2.2
CORIOLUS FLOW TRANSMITTER
3350-FIT-140 0 – 11 l/hr 4.0 2.2
CORIOLUS FLOW TRANSMITTER
3350-LSL-661 Refer to vendor control philosophy
WATER LEVEL IN EYEWASH TANK
3350-LSL-661 Refer to vendor control philosophy
WATER LEVEL IN EYEWASH TANK

Table 558: Alarms and Process Setpoint RECPF_Espumante

Note: Level switches setpoints set in field, not within PLC.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 449 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

16.0.4 Regulatory Control Loops – RECPF_Espumante

T5 Regulatory Control Loops


UN RECPF_Espumante EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-140 Dosing Flow controller Hydrofloat 1
ion
Dosing Flow controller Hydrofloat 2 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-141
ion
Dosing Flow controller Hydrofloat 3 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-142
ion
Dosing Flow controller Hydrofloat 4 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-143
ion
Dosing Flow controller Hydrofloat 5 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-144
ion
Dosing Flow controller Hydrofloat 6 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-145
ion
Dosing Flow controller Hydrofloat 7 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-146
ion
Dosing Flow controller Hydrofloat 8 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-147
ion
Dosing Flow controller Hydrofloat 9 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-148
ion
Dosing Flow controller Hydrofloat 10 0 - 100 % % 0 - 100 Calculat Note 1
3350-FIC-149
ion

Table 559: Regulatory Control Loops for RECPF_Espumante

Note 1
The reagents are dosed individually to the Crossflow Separators and Hydrofloats. The flowrate of
each reagent is based upon the calculated dry mass flow rate to the individual module. Refer to
the Crossflow Feed Pump dry mass flow calculations below.
The dry mass flow discharged into Crossflow Distributor 1 (3340 – DB – 103) is then divided by
the number of Crossflow Feed Valves open (3340-XV-038 A – E) for the mass flow to the
respective downstream modules.
Similarly, the dry mass flow discharged into Crossflow Distributor 2 (3340 – DB – 104) is then
divided by the number of Crossflow Feed Valves open (3340-XV-036 A – E) for the mass flow to
the respective downstream modules.
The setpoint flowrate for each individual Crossflow Separator reagent is then based upon the
formulae:
𝑇 × 𝐷𝑜𝑠𝑎𝑔𝑒
𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒 =
𝐷𝑒𝑛𝑠𝑖𝑡𝑦 × 1 000 000 000
Where:
Flowrate (l/hr) = Reagent Setpoint Dosage for a single module (Crossflow or Hydrofloat)
T (dry tph) = Modular dry mass feed rate

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 450 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Density (t/m3) = Reagent density


AP3894 = 1.0 t/m3
AP404 = 1.02 t/m3
Z6 / SIPX / Xanthate = 0.97 t/m3
Diesel = 0.84 t/m3
Frother = 1.01 t/m3
Dosage (g / t feed) = The mass dosage reagent per dry ton of modular feed. This is a
selected input available to the plant metallurgist. The following ranges are expected:
AP3894 = 20 – 28 g / t
AP404 = 20 – 28 g /t
Z6 / SIPX / Xanthate = 175 – 245 g/t
Diesel = 10 – 14 g /t
Frother = 20 – 28 g/t
A reagent dosing control loop will compare the calculated setpoint to the measured flowrate
(3350-FIT-120 through 129, 130 through 139, 140 through 149, 160 through 169, 150 through
159) and adjust the position of the dosing flow control valve (3350-FCV-120 through 129, 130
through 139, 140 through 149, 160 through 169, 150 through 159).

16.0.5 Advanced Control Loops – RECPF_Espumante

Not applicable

16.0.6 Sequence Description – RECPF_Espumante

Not applicable

16.1 Engineering Module 2 – 3350PU140

16.1.1 Description – 3350PU140

The following figure shows the elements that make up the 3350PU140 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 451 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Bulk Storage
Transfer

FC
3350140 FT
Reagent
LT Discharge 1
3350-XV- 140 3350-FCV- 140
3350224A
3350PU140 FC
LT 3350141 FT
LSH FAL
3350-XV- 225A 3350-XV- 225B Reagent
LSH Discharge 2
3350224B 3350225A PT 3350-XV- 141 3350-FCV- 141
LSL 3350226
FC
LSL FSL
3350224D 3350142 FT
3350-PU-140
PT Reagent
Discharge 3
3350-XV- 142 3350-FCV- 142
3350 – TK – 106
3350-XV- 226A 3350-XV- 226B FC
3350-PU-141 3350143 FT
Reagent
3350PU141 Discharge 4
3350-XV- 143 3350-FCV- 143

FC
3350144 FT
3350PU140_141 Reagent
Discharge 5
3350-XV- 144 3350-FCV- 144
FC
3350145 FT
Reagent
Discharge 6
3350-ES-101 3350-XV- 145 3350-FCV- 145
FC
3350146 FT
Reagent
Discharge 7
3350-XV- 146 3350-FCV- 146
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 147 3350-FCV- 147
FC
3350148 FT
Reagent
Discharge 9
3350-XV- 148 3350-FCV- 148
FC
3350149 FT
Reagent
Discharge 10
3350-XV- 149 3350-FCV- 149

Figure 52: Blockflow Control Diagram of the 3350PU140 System

16.1.2 Modules of Control 3350PU140

T1 Control Module
Sub
UN RECPF_Espumante EM 3350PU150_141 3350PU140
EM
Tag Service
3350-PU-140 Dosing Pump 1
3350-XV-225A Suction Reagent Pump
3350-XV-225B Discharge Reagent Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 452 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 560: List of Modules of Control for 3350PU140

16.1.3 Interlocks – 3350PU140

T2 Interlock
Tag 3350 – XV – 225A Description Suction Valve Reagent Pump
RECPF_Espuma 3350PU14
UN EM Sub EM 3350PU140
nte 0_141
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3350 – XV – 226A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3350 – PU – 140.!RN ×
period. 30 seconds

Table 561: List of Interlocks for 3350-XV-225A

T2 Interlock
Tag 3350 – PU - 140 Description Dosing Pump 1
RECPF_Espuma 3350PU14
UN EM Sub EM 3350PU140
nte 0_141
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Dosing Tank level switch Low (has a low


3350-LSL-224D.Low ×
alarm
Dosing pump flow switch has a low flow Time delay 1
3350-FSL-224A.Low ×
alarm for a time delay second
3350-XV-224A.!Opn Dosing Pump suction valve is not open ×

3350-XV-224B.!Opn Dosing Pump Discharge valve is not open ×


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 453 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 562: List of Interlocks for 3350-PU-140

T2 Interlock
Tag 3350 – XV – 225B Description Discharge Valve Reagent Pump
RECPF_Espuma 3350PU14
UN EM Sub EM 3350PU140
nte 0_141
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3350 – XV – 226B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3350 – PU – 140.!RN ×
period. 2 seconds

Table 563: List of Interlocks for 3350-XV-225B

16.1.4 Alarms and Process Setpoints – 3350PU140

Not applicable.
16.1.5 Regulatory Control Loops – 3350PU140

Not applicable.

16.1.6 Advanced Control Loops – 3350PU140

Not applicable

16.1.7 Sequence Description – 3350PU140

The pump start sequence 3340-PU-140, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 454 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN RECPF_Espumante EM 3350PU140_141 Sub EM 3350PU140
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3350-XV-225B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3340-XV-225A Open Suction Valve Open
seconds seconds
10 60
3. Start 3340-PU-140.MO1 Start pump. Working
seconds seconds

Table 564: Start Sequence 3350PU140

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3350-PU-140 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3350-PU-140-MO1 stopped
The pump stop sequence 3350-PU-140, shall follow the following steps:
TSQST Stop Sequence Table
UN RECPF_Espumante EM 3350PU140_141 Sub EM 3350PU140
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3350-PU-140.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3350-XV-225A Suction Valve. Closed
seconds seconds
2 20
3. Close 3350-XV-225B Discharge Valve Closed
seconds seconds

Table 565: Stop Sequence 3350PU140

16.2 Engineering Module 2 – 3350PU141

16.2.1 Description – 3350PU141

The following figure shows the elements that make up the 3350PU141 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 455 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Bulk Storage
Transfer

FC
3350140 FT
Reagent
LT Discharge 1
3350-XV- 140 3350-FCV- 140
3350224A
3350PU140 FC
LT 3350141 FT
LSH FAL
3350-XV- 225A 3350-XV- 225B Reagent
Discharge 2
3350224B LSH 3350225A PT 3350-XV- 141 3350-FCV- 141
LSL 3350226
FC
LSL FSL
3350224D 3350142 FT
3350-PU-140
PT Reagent
Discharge 3
3350-XV- 142 3350-FCV- 142
3350 – TK – 106
3350-XV- 226A 3350-XV- 226B FC
3350-PU-141 3350143 FT
Reagent
3350PU141 Discharge 4
3350-XV- 143 3350-FCV- 143

FC
3350144 FT
3350PU140_141 Reagent
Discharge 5
3350-XV- 144 3350-FCV- 144
FC
3350145 FT
Reagent
Discharge 6
3350-ES-101 3350-XV- 145 3350-FCV- 145
FC
3350146 FT
Reagent
Discharge 7
3350-XV- 146 3350-FCV- 146
FC
3350177 FT
Reagent
Discharge 8
3350-XV- 147 3350-FCV- 147
FC
3350148 FT
Reagent
Discharge 9
3350-XV- 148 3350-FCV- 148
FC
3350149 FT
Reagent
Discharge 10
3350-XV- 149 3350-FCV- 149

Figure 53: Blockflow Control Diagram of the 3350PU141 System

16.2.2 Modules of Control 3350PU141

T1 Control Module
Sub
UN RECPF_Espumante EM 3350PU140_141 3350PU141
EM
Tag Service
3350-PU-141 Dosing Pump 2
3350-XV-226A Suction Reagent Pump
3350-XV-226B Discharge Reagent Pump

Table 566: List of Modules of Control for 3350PU141

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 456 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

16.2.3 Interlocks – 3350PU141

T2 Interlock
Tag 3350 – XV – 226A Description Suction Valve Reagent Pump
RECPF_Espuma 3350PU14
UN EM Sub EM 3350PU141
nte 0_141
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3350 – XV – 225A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3350 – PU – 141.!RN ×
period. 30 seconds

Table 567: List of Interlocks for 3350-XV-226A

T2 Interlock
Tag 3350 – PU - 141 Description Dosing Pump 2
RECPF_Espuma 3350PU14
UN EM Sub EM 3350PU141
nte 0_141
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Dosing Tank level switch Low (has a low


3350-LSL-224D.Low ×
alarm
Dosing pump flow switch has a low flow Time delay 1
3350-FSL-224A.Low ×
alarm for a time delay second
3350-XV-226A.!Opn Dosing Pump suction valve is not open ×

3350-XV-226B.!Opn Dosing Pump Discharge valve is not open ×


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 568: List of Interlocks for 3350-PU-141

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 457 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3350 – XV – 226B Description Discharge Valve Reagent Pump
RECPF_Espuma 3350PU14
UN EM Sub EM 3350PU141
nte 0_141
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3350 – XV – 225B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3350 – PU – 141.!RN ×
period. 2 seconds

Table 569: List of Interlocks for 3350-XV-226B

16.2.4 Alarms and Process Setpoints – 3350PU141

Not applicable.
16.2.5 Regulatory Control Loops – 3350PU141

Not applicable.

16.2.6 Advanced Control Loops – 3350PU141

Not applicable

16.2.7 Sequence Description – 3350PU141

The pump start sequence 3340-PU-141, shall follow the following steps:
TSQST Start Sequence Table
UN RECPF_Espumante EM 3350PU150_151 Sub EM 3350PU151
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3350-XV-226B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3340-XV-226A Open Suction Valve Open
seconds seconds
10 60
3. Start 3340-PU-141.MO1 Start pump. Working
seconds seconds

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 458 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 570: Start Sequence 3350PU141

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3350-PU-141 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3350-PU-141-MO1 stopped
The pump stop sequence 3350-PU-141, shall follow the following steps:
TSQST Stop Sequence Table
UN RECPF_Espumante EM 3350PU140_141 Sub EM 3350PU141
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3350-PU-141.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3350-XV-226A Suction Valve. Closed
seconds seconds
2 20
3. Close 3350-XV-226B Discharge Valve Closed
seconds seconds

Table 571: Stop Sequence 3350PU141

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 459 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

17.0 UNIDAD: FCPF_ALIMENTACION

Refer to:
MQ14 - 08 - DR - 3340 - PD1105 Flocculant Dosing
A block flow control diagram is depicted below for the FCPF_Alimentacion system.
Crossflow Feed
Solids
FC
3340713
3340 – XV - 104A 3340 – XV - 104B
FT
3520 – MX – 001
Thickener 1
3340 – FCV - 713

3520 – PU – 195

3340710
3520PU195

FC

FT
Flocculant

3340 – FCV - 710


3520MX001

3340 – XV - 105A 3340 – XV - 105B


3520 – PU – 196
3520PU196
Dilution
Water
FC
3340714

FT 3520 – MX – 002
Thickener 2
3340 – FCV - 714

3340711
FC

FT

3340 – FCV - 711


3520MX002

FC
3340715

FT 3520 – MX – 003
Thickener 3
3340 – FCV - 715
3340712
FC

FT

3520MX003 3340 – FCV - 712

Figure 54: Blockflow Control Diagram of FCPF_Alimentacion System

The above control unit is broken into five Engineering Module 1’s, with no sub Engineering Module 2’s:
- 3520PU195 (Duty)
- 3520PU196 (Standby)
- 3340MX001
- 3340MX002
- 3340MX003

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 460 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Only one pump must run at a time. The operator to select the pump manually or plc to select
based on the least number of operating hours at time of start.

17.0 Engineering Module – 3520PU195

17.0.1 Description – 3520PU195

The following figure shows the elements that make up the 3520PU195 equipment module.
Crossflow Feed
Solids
FC
3340713
3340 – XV - 104A 3340 – XV - 104B
FT
3520 – MX – 001
Thickener 1
3340 – FCV - 713

3520 – PU – 195

3340710
3520PU195

FC

FT
Flocculant

3340 – FCV - 710


3520MX001

3340 – XV - 105A 3340 – XV - 105B


3520 – PU – 196
3520PU196
Dilution
Water
FC
3340714

FT 3520 – MX – 002
Thickener 2
3340 – FCV - 714
3340711
FC

FT

3340 – FCV - 711


3520MX002

FC
3340715

FT 3520 – MX – 003
Thickener 3
3340 – FCV - 715
3340712
FC

FT

3520MX003 3340 – FCV - 712

Figure 55: Blockflow Control Diagram of the 3520PU195 System

17.0.2 Modules of Control 3520PU195

T1 Control Module
Sub
UN FCPF_Alimentacion EM 3520PU195
EM
Tag Service
3520-PU-195 Dosing Pump 1
3520-XV-104A Suction Flocculant Pump

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 461 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3520-XV-104B Discharge Flocculant Pump

Table 572: List of Modules of Control for 3520PU195

17.0.3 Interlocks – 3520PU195

T2 Interlock
Tag 3520-XV-104A Description Suction valve Flocculant Pump
FCPF_Alimentaci 3520PU19
UN EM Sub EM
on 5
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3520 – XV – 105A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3520 – PU – 195.!RN ×
period. 30 seconds

Table 573: List of Interlocks for 3520-XV-104A

T2 Interlock
Tag 3520 – PU - 195 Description Dosing Pump 1
FCPF_Alimentaci 3520PU19
UN EM Sub EM
on 5
Interlock
Motor Type VFD Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3520-LIT-345A.LL If both dosing tanks (Fluor Tanks 3520-


AND TK-011 and 3520-TK-012) have a low low ×
3520-LIT-345B.LL level alarm.
3520-XV-104A.!Opn Dosing Pump suction valve is not open ×

3520-XV-104B.!Opn Dosing Pump Discharge valve is not open ×


Both Crossflow Feed Pumps
3340 – PU – 185.!RN Delay Time
3340 – PU – 185 ×
3340 – PU – 186.!RN 10 minutes
AND

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 462 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340 – PU – 186
Are not running for a delay time
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 574: List of Interlocks for 3520-PU-195

T2 Interlock
Tag 3520 – XV – 104B Description Discharge Valve Flocculant Pump
FCPF_Alimentaci 3520PU19
UN EM Sub EM
on 5
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3520 – XV – 105B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3520 – PU – 195.!RN ×
period. 5 seconds

Table 575: List of Interlocks for 3520-XV-104B

17.0.4 Alarms and Process Setpoints – 3520PU195

Not applicable.
17.0.5 Regulatory Control Loops – 3520PU195

Not applicable.
The pumps are variable speed but will not control any variable. Their speed will be manually set
to achieve the maximum required total flowrate of the system (4m 3/hr @ 0.2% concentration). A
pressure sustaining valve (3520 - PCV – 106) will maintain a sustained pressure in the discharge
manifold.

17.0.6 Advanced Control Loops – 3520PU195

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 463 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

17.0.7 Sequence Description – 3520PU195

The pump start sequence 3520-PU-195, shall follow the following steps:
TSQST Start Sequence Table
UN FCPF_Alimentacion EM 3520PU195 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3520-XV-104B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3520-XV-104A Open Suction Valve Open
seconds seconds
10 60
3. Start 3520-PU-195.MO1 Start pump. Working
seconds seconds

Table 576: Start Sequence 3520PU195

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3520-PU-195 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3520-PU-195-MO1 stopped
The pump stop sequence 3520-PU-195, shall follow the following steps:
TSQST Stop Sequence Table
UN FCPF_Alimentacion EM 3520PU195 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3520-PU-195.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3520-XV-104A Suction Valve. Closed
seconds seconds
2 20
3. Close 3520-XV-104B Discharge Valve Closed
seconds seconds

Table 577: Stop Sequence 3520PU195

17.1 Engineering Module – 3520PU196

17.1.1 Description – 3520PU196

The following figure shows the elements that make up the 3520PU196 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 464 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Crossflow Feed
Solids
FC
3340713
3340 – XV - 104A 3340 – XV - 104B
FT
3520 – MX – 001
Thickener 1
3340 – FCV - 713

3520 – PU – 195

3340710
3520PU195

FC

FT
Flocculant

3340 – FCV - 710


3520MX001

3340 – XV - 105A 3340 – XV - 105B


3520 – PU – 196
3520PU196
Dilution
Water
FC
3340714

FT 3520 – MX – 002
Thickener 2
3340 – FCV - 714

3340711
FC

FT
3340 – FCV - 711
3520MX002

FC
3340715

FT 3520 – MX – 003
Thickener 3
3340 – FCV - 715

3340712
FC

FT
3520MX003 3340 – FCV - 712

Figure 56: Blockflow Control Diagram of the 3520PU196 System

17.1.2 Modules of Control 3520PU196

T1 Control Module
Sub
UN FCPF_Alimentacion EM 3520PU196
EM
Tag Service
3520-PU-196 Dosing Pump 2
3520-XV-105A Suction Flocculant Pump
3520-XV-105B Discharge Flocculant Pump

Table 578: List of Modules of Control for 3520PU196

17.1.3 Interlocks – 3520PU196

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 465 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3520-XV-105A Description Suction Valve Flocculant Pump


FCPF_Alimentaci 3520PU19
UN EM Sub EM
on 6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate suction valve is open, close Delay time


3520 – XV – 104A.OPN ×
valve 10 s
If dosing pump is not running for a time Time Delay
3520 – PU – 196.!RN ×
period. 30 seconds

Table 579: List of Interlocks for 3520-XV-105A

T2 Interlock
Tag 3520 – PU - 196 Description Dosing Pump 2
FCPF_Alimentaci 3520PU19
UN EM Sub EM
on 6
Interlock
Motor Type VFD Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3520-LIT-345A.LL If both dosing tanks (Fluor Tanks 3520-


AND TK-011 and 3520-TK-012) have a low low ×
3520-LIT-345B.LL level alarm.
3520-XV-105A.!Opn Dosing Pump suction valve is not open ×

3520-XV-105B.!Opn Dosing Pump Discharge valve is not open ×


Both Crossflow Feed Pumps
3340 – PU – 185
3340 – PU – 185.!RN Delay Time
AND ×
3340 – PU – 186.!RN 10 minutes
3340 – PU – 186
Are not running for a delay time
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 580: List of Interlocks for 3520-PU-196

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 466 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3520 – XV – 105B Description Discharge Valve Flocculant Pump


FCPF_Alimentaci 3520PU19
UN EM Sub EM
on 6
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If the alternate discharge valve is open, Delay time 2


3520 – XV – 104B.OPN ×
close valve s
If dosing pump is not running for a time Time Delay
3520 – PU – 196.!RN ×
period. 5 seconds

Table 581: List of Interlocks for 3520-XV-105B

17.1.4 Alarms and Process Setpoints – 3520PU196

Not applicable.
17.1.5 Regulatory Control Loops – 3520PU196

Not applicable.
The pumps are variable speed but will not control any variable. Their speed will be manually set
to achieve the maximum required total flowrate of the system (4m 3/hr @ 0.2% concentration). A
pressure sustaining valve (3520 - PCV – 106) will maintain a sustained pressure in the discharge
manifold.

17.1.6 Advanced Control Loops – 3520PU196

Not applicable

17.1.7 Sequence Description – 3520PU196

The pump start sequence 3520-PU-196, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 467 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN FCPF_Alimentacion EM 3520PU196 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Open 3520-XV-105B Open Discharge Valve Open
seconds seconds
2 60
2. Open 3520-XV-105A Open Suction Valve Open
seconds seconds
10 60
3. Start 3520-PU-196.MO1 Start pump. Working
seconds seconds

Table 582: Start Sequence 3520PU196

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3520-PU-196 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3520-PU-196-MO1 stopped
The pump stop sequence 3520-PU-196, shall follow the following steps:
TSQST Stop Sequence Table
UN FCPF_Alimentacion EM 3520PU196 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3520-PU-196.MO1 Stop pump. Stopped
seconds seconds
2 20
2. Close 3520-XV-105A Suction Valve. Closed
seconds seconds
2 20
3. Close 3520-XV-105B Discharge Valve Closed
seconds seconds

Table 583: Stop Sequence 3520PU196

17.2 Engineering Module – 3340MX001

17.2.1 Description – 3340MX001

The following figure shows the elements that make up the 3340MX001 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 468 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Crossflow Feed
Solids
FC
3340713
3340 – XV - 104A 3340 – XV - 104B
FT
3520 – MX – 001
Thickener 1
3340 – FCV - 713

3520 – PU – 195

3340710
3520PU195

FC

FT
Flocculant

3340 – FCV - 710


3520MX001

3340 – XV - 105A 3340 – XV - 105B


3520 – PU – 196
3520PU196
Dilution
Water
FC
3340714

FT 3520 – MX – 002
Thickener 2
3340 – FCV - 714

3340711
FC

FT
3340 – FCV - 711
3520MX002

FC
3340715

FT 3520 – MX – 003
Thickener 3
3340 – FCV - 715

3340712
FC

FT
3520MX003 3340 – FCV - 712

Figure 57: Blockflow Control Diagram of the 3340MX001 System

17.2.2 Modules of Control 3340MX001

T1 Control Module
Sub
UN FCPF_Alimentacion EM 3340MX001
EM
Tag Service
3340-MX-001 Flocculant Static Mixer 1
3340-FIT-710 MAG FLOW TRANSMITTER – Process Water Dilution
3340-FCV-710 REGULATES WATER TO STATIC MIXER
3340-FCV-713 REGULATES FLOCCULANT TO STATIC MIXER
3340-FIT-713 MAG FLOW TRANSMITTER – Flocculant Dosing

Table 584: List of Modules of Control for 3340MX001

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 469 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

17.2.3 Interlocks – 3340MX001

T2 Interlock
Tag 3340-FCV-710 Description REGULATES WATER TO STATIC MIXER
FCPF_Alimentaci 3340MX0
UN EM Sub EM
on 01
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Delay Time
3340 – FCV – 713.CL If flocculant dosing valve is closed ×
2 minutes

Table 585: List of Interlocks for 3340-FCV-710

T2 Interlock
Tag 3340-FCV-713 Description REGULATES FLOCCULANT TO STATIC MIXER
FCPF_Alimentaci 3340MX0
UN EM Sub EM
on 01
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Delay Time
3340 - XV – 303A If thickener feed valve is closed ×
2 minutes
3340-XV-040A.CL
AND
3340-XV-042A.CL
AND
3340-XV-044A.CL
AND
3340-XV-046A.CL
All Crossflow/Hydrofloat Modules Delay Time
AND ×
fluidisation water valves are closed 2 minutes
3340-XV-048A.CL
AND
3340-XV-050A.CL
AND
3340-XV-052A.CL
AND
3340-XV-054A.CL

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 470 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

AND
3340-XV-056A.CL
AND
3340-XV-058A.CL

Table 586: List of Interlocks for 3340-FCV-713

17.2.4 Alarms and Process Setpoints – 3340MX001

T3 Alarms and Process Setpoints


UN FCPF_Alimentacion EM 3340MX001 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-710 MAG FLOW TRANSMITTER – Process
0 - 100 m3/hr
Water Dilution
3340-FIT-710 MAG FLOW TRANSMITTER –
0 - 100 m3/hr
Flocculant Dosing

Table 587: Alarms and Process Setpoints for 3340MX001 System

17.2.5 Regulatory Control Loops – 3340MX001

T5 Regulatory Control Loops


UN Flocculant EM 3340-MX-001 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % m3/hr 0 - 100 Expected
3340 – FIC - Flocculant Addition Flow control – setpoint 1.5
710 Settler 1 m3/hr. Note
2
0 - 100 % m3/hr 0 - 100 Expected
3340 – FIC - setpoint 13
Dilution Water Flow control – Settler 1
713 m3/hr. Note
1

Table 588: Regulatory Control Loops for 3340MX001 System

Note 1: Flocculant Dosing

The summed total flowrate required to be dosed to all three thickeners is based upon the total dry
solids Crossflow Separator feed rate as given by the following equation:

𝐷𝑜𝑠𝑎𝑔𝑒 × 𝐹𝑒𝑒𝑑 𝑅𝑎𝑡𝑒 × 𝑌𝑖𝑒𝑙𝑑 𝐹𝑎𝑐𝑡𝑜𝑟


𝐹𝑙𝑜𝑐𝑐𝑢𝑙𝑎𝑛𝑡 𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒 =
1 000 000 × (𝐶𝑜𝑛𝑐𝑒𝑛𝑡𝑟𝑎𝑡𝑖𝑜𝑛/100)

Where:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 471 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Flocculant Flowrate [m3/hr] = Total Flocculant to be dosed into all available thickeners
Dosage [g / dry ton] = Manual input by control room operator within a range 0 – 25
Feed Rate [dry tph] = Measured/calculated total dry solids feed to Crossflow Separators
Yield Factor [%] = Manual Input by control room operator, (typically 3 - 6%). This can be calculated
by the daily or monthly dry solids returned as concentrate product by the CPF to the Papajuane
concentrator, divided by the total crossflow feed solids over the same period.
Concentration = Flocculant make-up concentration stated as 0.2.
Flocculant flowrate setpoint for each individual thickener should then be divided by the number of
thickeners that have feed valves open (3340 - XV – 303A / 303B / 303C) and compared to the
measured value by flow transmitter (3340 - FIT – 710 / 711 / 712). The flowrate is then adjusted
by changing the position of the flow control valve (3340 - FC – 710 / 711 / 712).

Note 2: Flocculant Dilution

Flocculant is then diluted to the required dosing concentration by the controlled addition of
process water as measured by flow transmitter (3340 - FIT - 713 / 714 / 715). The flowrate is then
adjusted by changing the position of the flow control valve (3340 - FC – 713 / 714 / 715). The
setpoint for the flow controller for dilution water is provided by the following equation:

𝐷𝑜𝑠𝑎𝑔𝑒 × 𝐹𝑒𝑒𝑑 𝑅𝑎𝑡𝑒 × 𝑌𝑖𝑒𝑙𝑑 𝐹𝑎𝑐𝑡𝑜𝑟


𝐷𝑖𝑙𝑢𝑡𝑖𝑜𝑛 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒 = − 𝐹𝑙𝑜𝑐𝑐𝑢𝑙𝑎𝑛𝑡 𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒
𝐶𝑜𝑛𝑐𝑒𝑛𝑡𝑟𝑎𝑡𝑖𝑜𝑛
1 000 000 ×
100
Where:
Dilution Water Flowrate [m3/hr] = Dilution water required for each individual thickener
Dosage [g / dry ton] = Identical value used in flocculant control above
Feed Rate [dry tph] = Measured/calculated total dry solids feed to Crossflow Separators
Yield Factor [%] = Identical value used in flocculant control above
Concentration = Flocculant dosing concentration stated as 0.015
Flocculant Flowrate [m3/hr] = Value of total flocculant flow calculated above divided by the number
of operating thickeners.
The dilution water flow control valves (3340 - FC –713 / 714 / 715) shall close if the thickener feed
valve (3340 - XV – 303A / 303B / 303C) is not open.
Static mixers (3340 – MX – 001 / 002 / 003) ensure that the flocculant is properly mixed prior to
being discharged into the thickener feed.

17.2.6 Advanced Control Loops – 3340MX001

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 472 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

17.2.7 Sequence Description – 3340MX001

Not applicable

17.3 Engineering Module – 3340MX002

17.3.1 Description – 3340MX002

The following figure shows the elements that make up the 3340MX002 equipment module.
Crossflow Feed
Solids
FC
3340713
3340 – XV - 104A 3340 – XV - 104B
FT
3520 – MX – 001
Thickener 1
3340 – FCV - 713

3520 – PU – 195

3340710
3520PU195 FC

FT
Flocculant

3340 – FCV - 710


3520MX001

3340 – XV - 105A 3340 – XV - 105B


3520 – PU – 196
3520PU196
Dilution
Water
FC
3340714

FT 3520 – MX – 002
Thickener 2
3340 – FCV - 714
3340711
FC

FT

3340 – FCV - 711


3520MX002

FC
3340715

FT 3520 – MX – 003
Thickener 3
3340 – FCV - 715
3340712
FC

FT

3520MX003 3340 – FCV - 712

Figure 58: Blockflow Control Diagram of the 3340MX002 System

17.3.2 Modules of Control 3340MX002

T1 Control Module
Sub
UN FCPF_Alimentacion EM 3340MX002
EM
Tag Service

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 473 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-MX-002 Flocculant Static Mixer 2


3340-FIT-711 MAG FLOW TRANSMITTER – Process Water Dilution
3340-FCV-711 REGULATES WATER TO STATIC MIXER
3340-FCV-714 REGULATES FLOCCULANT TO STATIC MIXER
3340-FIT-714 MAG FLOW TRANSMITTER – Flocculant Dosing

Table 589: List of Modules of Control for 3340MX002

17.3.3 Interlocks – 3340MX002

T2 Interlock
Tag 3340-FCV-711 Description REGULATES WATER TO STATIC MIXER
FCPF_Alimentaci 3340MX0
UN EM Sub EM
on 02
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Delay Time
3340 – FCV – 714.CL If flocculant dosing valve is closed ×
2 minutes

Table 590: List of Interlocks for 3340-FCV-711

T2 Interlock
Tag 3340-FCV-714 Description REGULATES FLOCCULANT TO STATIC MIXER
FCPF_Alimentaci 3340MX0
UN EM Sub EM
on 02
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Delay Time
3340 - XV – 303B If thickener feed valve is closed ×
2 minutes
3340-XV-040A.CL All Crossflow/Hydrofloat Modules Delay Time
×
AND fluidisation water valves are closed 2 minutes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 474 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-042A.CL
AND
3340-XV-044A.CL
AND
3340-XV-046A.CL
AND
3340-XV-048A.CL
AND
3340-XV-050A.CL
AND
3340-XV-052A.CL
AND
3340-XV-054A.CL
AND
3340-XV-056A.CL
AND
3340-XV-058A.CL

Table 591: List of Interlocks for 3340-FCV-714

17.3.4 Alarms and Process Setpoints – 3340MX002

T3 Alarms and Process Setpoints


UN FCPF_Alimentacion EM 3340MX002 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-711 MAG FLOW TRANSMITTER – Process
0 - 100 m3/hr
Water Dilution
3340-FIT-711 MAG FLOW TRANSMITTER –
0 - 100 m3/hr
Flocculant Dosing

Table 592: Alarms and Process Setpoints for 3340MX002 System

17.3.5 Regulatory Control Loops – 3340MX002

T5 Regulatory Control Loops


UN Flocculant EM 3340-MX-002 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % m3/hr 0 - 100 Expected
3340 – FIC – Flocculant Addition Flow control – setpoint 1.5
711 Settler 2 m3/hr. Note
2
0 - 100 % m3/hr 0 - 100 Expected
3340 – FIC - setpoint 13
Dilution Water Flow control – Settler 2
714 m3/hr. Note
1

Table 593: Regulatory Control Loops for 3340MX001 System

Note 1: Flocculant Dosing

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 475 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The summed total flowrate required to be dosed to all three thickeners is based upon the total dry
solids Crossflow Separator feed rate as given by the following equation:

𝐷𝑜𝑠𝑎𝑔𝑒 × 𝐹𝑒𝑒𝑑 𝑅𝑎𝑡𝑒 × 𝑌𝑖𝑒𝑙𝑑 𝐹𝑎𝑐𝑡𝑜𝑟


𝐹𝑙𝑜𝑐𝑐𝑢𝑙𝑎𝑛𝑡 𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒 =
1 000 000 × (𝐶𝑜𝑛𝑐𝑒𝑛𝑡𝑟𝑎𝑡𝑖𝑜𝑛/100)

Where:
Flocculant Flowrate [m3/hr] = Total Flocculant to be dosed into all available thickeners
Dosage [g / dry ton] = Manual input by control room operator within a range 0 – 25
Feed Rate [dry tph] = Measured/calculated total dry solids feed to Crossflow Separators
Yield Factor [%] = Manual Input by control room operator, (typically 3 - 6%). This can be calculated
by the daily or monthly dry solids returned as concentrate product by the CPF to the Papajuane
concentrator, divided by the total crossflow feed solids over the same period.
Concentration = Flocculant make-up concentration stated as 0.2.
Flocculant flowrate setpoint for each individual thickener should then be divided by the number of
thickeners that have feed valves open (3340 - XV – 303A / 303B / 303C) and compared to the
measured value by flow transmitter (3340 - FIT – 710 / 711 / 712). The flowrate is then adjusted
by changing the position of the flow control valve (3340 - FC – 710 / 711 / 712).

Note 2: Flocculant Dilution

Flocculant is then diluted to the required dosing concentration by the controlled addition of
process water as measured by flow transmitter (3340 - FIT - 713 / 714 / 715). The flowrate is then
adjusted by changing the position of the flow control valve (3340 - FC – 713 / 714 / 715). The
setpoint for the flow controller for dilution water is provided by the following equation:

𝐷𝑜𝑠𝑎𝑔𝑒 × 𝐹𝑒𝑒𝑑 𝑅𝑎𝑡𝑒 × 𝑌𝑖𝑒𝑙𝑑 𝐹𝑎𝑐𝑡𝑜𝑟


𝐷𝑖𝑙𝑢𝑡𝑖𝑜𝑛 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒 = − 𝐹𝑙𝑜𝑐𝑐𝑢𝑙𝑎𝑛𝑡 𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒
𝐶𝑜𝑛𝑐𝑒𝑛𝑡𝑟𝑎𝑡𝑖𝑜𝑛
1 000 000 ×
100
Where:
Dilution Water Flowrate [m3/hr] = Dilution water required for each individual thickener
Dosage [g / dry ton] = Identical value used in flocculant control above
Feed Rate [dry tph] = Measured/calculated total dry solids feed to Crossflow Separators
Yield Factor [%] = Identical value used in flocculant control above
Concentration = Flocculant dosing concentration stated as 0.015

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 476 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Flocculant Flowrate [m3/hr] = Value of total flocculant flow calculated above divided by the number
of operating thickeners.
The dilution water flow control valves (3340 - FC –713 / 714 / 715) shall close if the thickener feed
valve (3340 - XV – 303A / 303B / 303C) is not open.
Static mixers (3340 – MX – 001 / 002 / 003) ensure that the flocculant is properly mixed prior to
being discharged into the thickener feed.

17.3.6 Advanced Control Loops – 3340MX002

Not applicable

17.3.7 Sequence Description – 3340MX002

Not applicable

17.4 Engineering Module – 3340MX003

17.4.1 Description – 3340MX003

The following figure shows the elements that make up the 3340MX003 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 477 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Crossflow Feed
Solids
FC
3340713
3340 – XV - 104A 3340 – XV - 104B
FT
3520 – MX – 001
Thickener 1
3340 – FCV - 713

3520 – PU – 195

3340710
3520PU195

FC

FT
Flocculant

3340 – FCV - 710


3520MX001

3340 – XV - 105A 3340 – XV - 105B


3520 – PU – 196
3520PU196
Dilution
Water
FC
3340714

FT 3520 – MX – 002
Thickener 2
3340 – FCV - 714

3340711
FC

FT
3340 – FCV - 711
3520MX002

FC
3340715

FT 3520 – MX – 003
Thickener 3
3340 – FCV - 715

3340712
FC

FT
3520MX003 3340 – FCV - 712

Figure 59: Blockflow Control Diagram of the 3340MX003 System

17.4.2 Modules of Control 3340MX003

T1 Control Module
Sub
UN FCPF_Alimentacion EM 3340MX003
EM
Tag Service
3340-MX-003 Flocculant Static Mixer 3
3340-FIT-712 MAG FLOW TRANSMITTER – Process Water Dilution
3340-FCV-712 REGULATES WATER TO STATIC MIXER
3340-FCV-715 REGULATES FLOCCULANT TO STATIC MIXER
3340-FIT-715 MAG FLOW TRANSMITTER – Flocculant Dosing

Table 594: List of Modules of Control for 3340MX003

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 478 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

17.4.3 Interlocks – 3340MX003

T2 Interlock
Tag 3340-FCV-712 Description REGULATES WATER TO STATIC MIXER
FCPF_Alimentaci 3340MX0
UN EM Sub EM
on 03
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Delay Time
3340 – FCV – 715.CL If flocculant dosing valve is closed ×
2 minutes

Table 595: List of Interlocks for 3340-FCV-712

T2 Interlock
Tag 3340-FCV-715 Description REGULATES FLOCCULANT TO STATIC MIXER
FCPF_Alimentaci 3340MX0
UN EM Sub EM
on 03
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Delay Time
3340 - XV – 303C If thickener feed valve is closed ×
2 minutes
3340-XV-040A.CL
AND
3340-XV-042A.CL
AND
3340-XV-044A.CL
AND
3340-XV-046A.CL
All Crossflow/Hydrofloat Modules Delay Time
AND ×
fluidisation water valves are closed 2 minutes
3340-XV-048A.CL
AND
3340-XV-050A.CL
AND
3340-XV-052A.CL
AND
3340-XV-054A.CL

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 479 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

AND
3340-XV-056A.CL
AND
3340-XV-058A.CL

Table 596: List of Interlocks for 3340-FCV-715

17.4.4 Alarms and Process Setpoints – 3340MX003

T3 Alarms and Process Setpoints


UN FCPF_Alimentacion EM 3340MX003 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-712 MAG FLOW TRANSMITTER – Process
0 - 100 m3/hr
Water Dilution
3340-FIT-712 MAG FLOW TRANSMITTER –
0 - 100 m3/hr
Flocculant Dosing

Table 597: Alarms and Process Setpoints for 3340MX003 System

17.4.5 Regulatory Control Loops – 3340MX003

T5 Regulatory Control Loops


UN Flocculant EM 3340-MX-002 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % m3/hr 0 - 100 Expected
3340 – FIC – Flocculant Addition Flow control – setpoint 1.5
712 Settler 3 m3/hr. Note
2
0 - 100 % m3/hr 0 - 100 Expected
3340 – FIC - setpoint 13
Dilution Water Flow control – Settler 3
715 m3/hr. Note
1

Table 598: Regulatory Control Loops for 3340MX001 System

Note 1: Flocculant Dosing

The summed total flowrate required to be dosed to all three thickeners is based upon the total dry
solids Crossflow Separator feed rate as given by the following equation:

𝐷𝑜𝑠𝑎𝑔𝑒 × 𝐹𝑒𝑒𝑑 𝑅𝑎𝑡𝑒 × 𝑌𝑖𝑒𝑙𝑑 𝐹𝑎𝑐𝑡𝑜𝑟


𝐹𝑙𝑜𝑐𝑐𝑢𝑙𝑎𝑛𝑡 𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒 =
1 000 000 × (𝐶𝑜𝑛𝑐𝑒𝑛𝑡𝑟𝑎𝑡𝑖𝑜𝑛/100)

Where:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 480 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Flocculant Flowrate [m3/hr] = Total Flocculant to be dosed into all available thickeners
Dosage [g / dry ton] = Manual input by control room operator within a range 0 – 25
Feed Rate [dry tph] = Measured/calculated total dry solids feed to Crossflow Separators
Yield Factor [%] = Manual Input by control room operator, (typically 3 - 6%). This can be calculated
by the daily or monthly dry solids returned as concentrate product by the CPF to the Papajuane
concentrator, divided by the total crossflow feed solids over the same period.
Concentration = Flocculant make-up concentration stated as 0.2.
Flocculant flowrate setpoint for each individual thickener should then be divided by the number of
thickeners that have feed valves open (3340 - XV – 303A / 303B / 303C) and compared to the
measured value by flow transmitter (3340 - FIT – 710 / 711 / 712). The flowrate is then adjusted
by changing the position of the flow control valve (3340 - FC – 710 / 711 / 712).

Note 2: Flocculant Dilution

Flocculant is then diluted to the required dosing concentration by the controlled addition of
process water as measured by flow transmitter (3340 - FIT - 713 / 714 / 715). The flowrate is then
adjusted by changing the position of the flow control valve (3340 - FC – 713 / 714 / 715). The
setpoint for the flow controller for dilution water is provided by the following equation:

𝐷𝑜𝑠𝑎𝑔𝑒 × 𝐹𝑒𝑒𝑑 𝑅𝑎𝑡𝑒 × 𝑌𝑖𝑒𝑙𝑑 𝐹𝑎𝑐𝑡𝑜𝑟


𝐷𝑖𝑙𝑢𝑡𝑖𝑜𝑛 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒 = − 𝐹𝑙𝑜𝑐𝑐𝑢𝑙𝑎𝑛𝑡 𝐹𝑙𝑜𝑤𝑟𝑎𝑡𝑒
𝐶𝑜𝑛𝑐𝑒𝑛𝑡𝑟𝑎𝑡𝑖𝑜𝑛
1 000 000 ×
100
Where:
Dilution Water Flowrate [m3/hr] = Dilution water required for each individual thickener
Dosage [g / dry ton] = Identical value used in flocculant control above
Feed Rate [dry tph] = Measured/calculated total dry solids feed to Crossflow Separators
Yield Factor [%] = Identical value used in flocculant control above
Concentration = Flocculant dosing concentration stated as 0.015
Flocculant Flowrate [m3/hr] = Value of total flocculant flow calculated above divided by the number
of operating thickeners.
The dilution water flow control valves (3340 - FC –713 / 714 / 715) shall close if the thickener feed
valve (3340 - XV – 303A / 303B / 303C) is not open.
Static mixers (3340 – MX – 001 / 002 / 003) ensure that the flocculant is properly mixed prior to
being discharged into the thickener feed.

17.4.6 Advanced Control Loops – 3340MX003

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 481 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

17.4.7 Sequence Description – 3340MX003

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 482 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

18.0 UNIDAD: ECPF_ALIMENTACION

Refer to:
MQ14-08-DR-3340-PD1078 Thickener Feed Box
MQ14-08-DR-3340-PD1080 Thickener Underflow

A block flow control diagram is depicted below for the ECPF_ALIMENTACION system.

3340BX109
3340-XV-301
Hydrofloat
Concentrate
3340 – BX - 109

Flush Water
3340XV302_303A
3340-XV-302A
3340-XV-303A
Settler 1
3340 – TH - 101

3340XV302_303B
3340-XV-302B
3340-XV-303B

Settler 2
3340 – TH - 102

3340-XV-302C
3340-XV-303C
Settler 3
3340XV302_303C 3340 – TH - 103

LAHH LAH 3340PU171


3340359 3340359

M
LSH
H
LSH Tails Launder
TE

3340 – PU – 171

Figure 60: Blockflow Control Diagram of ECPF_ALIMENTACION

The above control unit is broken into five Engineering Module 1’s with no sub Engineering Module 2’s:
- 3340BX109
- 3340XV302_303A
- 3340XV302_303B

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 483 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

- 3340XV302_303C
- 3340PU171
18.0 Engineering Module – 3340BX109

18.0.1 Description – 3340BX109

The following figure shows the elements that make up the 3340BX109 equipment module.

3340BX109
3340-XV-301
Hydrofloat
Concentrate
3340 – BX - 109

Flush Water
3340XV302_303A
3340-XV-302A
3340-XV-303A
Settler 1
3340 – TH - 101

3340XV302_303B
3340-XV-302B
3340-XV-303B

Settler 2
3340 – TH - 102

3340-XV-302C
3340-XV-303C
Settler 3
3340XV302_303C 3340 – TH - 103

LAHH LAH 3340PU171


3340359 3340359

LSH M
H
LSH Tails Launder
TE

3340 – PU – 171

Figure 61: Blockflow Control Diagram of the 3340BX109 System

18.0.2 Modules of Control 3340BX109

T1 Control Mod
Sub
UN ECPF_ALIMENTACION EM 3340BX109
EM
Tag Service
3340-BX-109 Concentrate Thickener Feed Box
3340-XV-301A Froth Suppression Water Isolation – Settler Feed Box

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 484 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 599: List of Modules of Control for 3340BX109

18.0.3 Interlocks – 3340BX109

T2 Interlock
Froth Suppression Water Isolation –
Tag 3340-XV-301A Description
Settler Feed Box
UN ECPF_ALIMENTACION EM 3340BX109 Sub EM
Failure Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Closed Interlock
Type
(CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340 - XV-303A.CL Thickener Feed Valves


AND 3340 - XV- 303A is closed
3340 - XV- 303B.CL AND
×
AND 3340 - XV- 303B is closed
3340 - XV- 303C.CL AND
3340 - XV- 303C is closed

Table 600: List of Interlocks for 3340-XV-301A

18.0.4 Alarms and Process Setpoints – 3340BX109

Not applicable

18.0.5 Regulatory Control Loops – 3340BX109

Not applicable

18.0.6 Advanced Control Loops – 3340BX109

Not applicable

18.0.7 Sequence Description – 3340BX109

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 485 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

18.1 Engineering Module – 3340XV302_303A

18.1.1 Description – 3340XV302_303A

The following figure shows the elements that make up the 3340XV302_303A equipment module.

3340BX109
3340-XV-301
Hydrofloat
Concentrate
3340 – BX - 109

Flush Water
3340XV302_303A
3340-XV-302A
3340-XV-303A
Settler 1
3340 – TH - 101

3340XV302_303B
3340-XV-302B
3340-XV-303B

Settler 2
3340 – TH - 102

3340-XV-302C
3340-XV-303C
Settler 3
3340XV302_303C 3340 – TH - 103

LAHH LAH 3340PU171


3340359 3340359

M
LSH
H
LSH Tails Launder
TE

3340 – PU – 171

Figure 62: Blockflow Control Diagram of the 3340XV302_303A System

18.1.2 Modules of Control 3340XV302_303A

T1 Control Mod
Sub
UN ECPF_ALIMENTACION EM 3340XV302_303A
EM

Tag Service
3340-XV-303A SLURRY TO SETTLER
3340-XV-302A FLUSH WATER TO PIPELINE

Table 601: List of Modules of Control for 3340XV302_303A

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 486 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

18.1.3 Interlocks – 3340XV302_303A

T2 Interlock
Tag 3340-XV-303A Description SLURRY TO SETTLER
3340XV302
UN ECPF_ALIMENTACION EM Sub EM
_303A
Failure Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Closed Interlock
Type
(CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Just before Opening 3340 - XV-303A must


flush prior to the settler feed valve for a
Flush Time
time delay. Feed valve to open
Delay 30
3340 - XV – immediately thereafter flushing complete.
× seconds
302A.FLUSH
Open flush water valve
Note 1
3340 - XV –302A
For a time delay, then close
3340 – LIT - 310 has a High solids mud
Time Delay
3340 - LIT – 310.H bed alarm ×
30 seconds
Underflow Pump (3340 – PU – 104) Time Delay
3340 – PU – 104.!RN ×
is not running 30 seconds

Table 602: List of Interlocks for 3340-XV-303A

It is important that prior to the thickener feed valve being opened, that its feed line is flushed of
solids. This is a process step that cannot be a process sequence, but rather interlocked ensuring
adherence by operations.

T2 Interlock
Tag 3340-XV-302A Description FLUSH WATER TO PIPELINE
3340XV302
UN ECPF_ALIMENTACION EM Sub EM
_303A
Failure Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Closed Interlock
Type
(CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 487 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Froth Suppression and dilution water


3340 – PU – 109.!RN pump (3340 – PU – 109) ×
is not running

Table 603: List of Interlocks for 3340-XV-302A

18.1.4 Alarms and Process Setpoints – 3340XV302_303A

Not applicable

18.1.5 Regulatory Control Loops – 3340XV302_303A

Not applicable

18.1.6 Advanced Control Loops – 3340XV302_303A

Not applicable

18.1.7 Sequence Description – 3340XV302_303A

Not applicable
Although three deep cone settlers are installed, one can be utilised as a standby if required (i.e.,
two operating). Under normal circumstances however, all three will operate to reduce up flow
velocity and maximise overflow water clarity. An electric actuated, Thickener Feed Valve (3340-
XV-303A, 303B, 303C) isolates the individual thickener should it contain a high level of solids
(3340-LIT-310 / 312 / 314) or if the respective thickener underflow pump is not running. Before
re-opening the thickener feed valve, backflush water must first be injected by opening a flush
valve (3340- XV – 302A, 302B, 302C) for a specified time, prior to the feed valve opening to re-
fluidise any solids build-up. The Froth Suppression and Dilution Water pump (3340 – PU – 109)
must be running before the flush water valves can open.

18.2 Engineering Module – 3340XV302_303B

18.2.1 Description – 3340XV302_303B

The following figure shows the elements that make up the 3340XV302_303B equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 488 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340BX109
3340-XV-301
Hydrofloat
Concentrate
3340 – BX - 109

Flush Water
3340XV302_303A
3340-XV-302A
3340-XV-303A
Settler 1
3340 – TH - 101

3340XV302_303B
3340-XV-302B
3340-XV-303B

Settler 2
3340 – TH - 102

3340-XV-302C
3340-XV-303C
Settler 3
3340XV302_303C 3340 – TH - 103

LAHH LAH 3340PU171


3340359 3340359

M
LSH
H
LSH Tails Launder
TE

3340 – PU – 171

Figure 63: Blockflow Control Diagram of the 3340XV302_303B System

18.2.2 Modules of Control 3340XV302_303B

T1 Control Mod
Sub
UN ECPF_ALIMENTACION EM 3340XV302_303B
EM
Tag Service
3340-XV-303B SLURRY TO SETTLER
3340-XV-302B FLUSH WATER TO PIPELINE

Table 604: List of Modules of Control for 3340XV302_303B

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 489 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

18.2.3 Interlocks – 3340XV302_303B

T2 Interlock
Tag 3340-XV-303B Description SLURRY TO SETTLER
3340XV302
UN ECPF_ALIMENTACION EM Sub EM
_303B
Failure Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Closed Interlock
Type
(CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Just before Opening 3340 - XV-303B must


flush prior to the settler feed valve for a
Flush Time
time delay. Feed valve to open
Delay 30
3340 - XV – immediately thereafter flushing complete.
× seconds
302B.FLUSH
Open flush water valve
Note 1
3340 - XV –302B
For a time delay, then close
3340 – LIT - 312 has a High solids mud
Time Delay
3340 - LIT – 312.H bed alarm ×
30 seconds
Underflow Pump (3340 – PU – 105) Time Delay
3340 – PU – 105.!RN ×
is not running 30 seconds

Table 605: List of Interlocks for 3340-XV-303B

It is important that prior to the thickener feed valve being opened, that its feed line is flushed of
solids. This is a process step that cannot be a process sequence, but rather interlocked ensuring
adherence by operations.

T2 Interlock
Tag 3340-XV-302B Description FLUSH WATER TO PIPELINE
3340XV302
UN ECPF_ALIMENTACION EM Sub EM
_303B
Failure Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Closed Interlock
Type
(CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 490 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Froth Suppression and dilution water


3340 – PU – 109.!RN pump (3340 – PU – 109) ×
is not running

Table 606: List of Interlocks for 3340-XV-302B

18.2.4 Alarms and Process Setpoints – 3340XV302_303B

Not applicable

18.2.5 Regulatory Control Loops – 3340XV302_303B

Not applicable

18.2.6 Advanced Control Loops – 3340XV302_303B

Not applicable
18.2.7 Sequence Description – 3340XV302_303B

Not applicable
Although three deep cone settlers are installed, one can be utilised as a standby if required (i.e.,
two operating). Under normal circumstances however, all three will operate to reduce up flow
velocity and maximise overflow water clarity. An electric actuated, Thickener Feed Valve (3340-
XV-303A, 303B, 303C) isolates the individual thickener should it contain a high level of solids
(3340-LIT-310 / 312 / 314) or if the respective thickener underflow pump is not running. Before
re-opening the thickener feed valve, backflush water must first be injected by opening a flush
valve (3340- XV – 302A, 302B, 302C) for a specified time, prior to the feed valve opening to re-
fluidise any solids build-up. The Froth Suppression and Dilution Water pump (3340 – PU – 109)
must be running before the flush water valves can open.

18.3 Engineering Module – 3340XV302_303C

18.3.1 Description – 3340XV302_303C

The following figure shows the elements that make up the 3340XV302_303C equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 491 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340BX109
3340-XV-301
Hydrofloat
Concentrate
3340 – BX - 109

Flush Water
3340XV302_303A
3340-XV-302A
3340-XV-303A
Settler 1
3340 – TH - 101

3340XV302_303B
3340-XV-302B
3340-XV-303B

Settler 2
3340 – TH - 102

3340-XV-302C
3340-XV-303C
Settler 3
3340XV302_303C 3340 – TH - 103

LAHH LAH 3340PU171


3340359 3340359

M
LSH
LSH Tails Launder
H
TE

3340 – PU – 171

Figure 64: Blockflow Control Diagram of the 3340XV302_303C System

18.3.2 Modules of Control 3340XV302_303C

T1 Control Mod
Sub
UN ECPF_ALIMENTACION EM 3340XV302_303C
EM
Tag Service
3340-XV-303C SLURRY TO SETTLER
3340-XV-302C FLUSH WATER TO PIPELINE

Table 607: List of Modules of Control for 3340XV302_303C


18.3.3 Interlocks – 3340XV302_303C

T2 Interlock
Tag 3340-XV-303C Description SLURRY TO SETTLER
3340XV302
UN ECPF_ALIMENTACION EM Sub EM
_303C
Failure Position: Keep Interlock
Motor Type Interlock
Last (KL) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 492 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position: Closed


(CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Just before Opening 3340 - XV-303C


must flush prior to the settler feed valve
Flush Time
for a time delay. Feed valve to open
Delay 30
3340 - XV – immediately thereafter flushing complete.
× seconds
302C.FLUSH
Open flush water valve
Note 1
3340 - XV –302C
For a time delay, then close
3340 – LIT - 314 has a High solids mud
Time Delay
3340 - LIT – 314.H bed alarm ×
30 seconds
Underflow Pump (3340 – PU – 108) Time Delay
3340 – PU – 108.!RN ×
is not running 30 seconds

Table 608: List of Interlocks for 3340-XV-303C

It is important that prior to the thickener feed valve being opened, that its feed line is flushed of
solids. This is a process step that cannot be a process sequence, but rather interlocked ensuring
adherence by operations.

T2 Interlock
Tag 3340-XV-302C Description FLUSH WATER TO PIPELINE
3340XV302
UN ECPF_ALIMENTACION EM Sub EM
_303C
Failure Position: Keep
Last (KL)
Interlock
Motor Type Safe Position: Closed Interlock
Type
(CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Froth Suppression and dilution water


3340 – PU – 109.!RN pump (3340 – PU – 109) ×
is not running

Table 609: List of Interlocks for 3340-XV-302C

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 493 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

18.3.4 Alarms and Process Setpoints – 3340XV302_303C

Not applicable

18.3.5 Regulatory Control Loops – 3340XV302_303C

Not applicable

18.3.6 Advanced Control Loops – 3340XV302_303C

Not applicable
18.3.7 Sequence Description – 3340XV302_303C

Not applicable
Although three deep cone settlers are installed, one can be utilised as a standby if required (i.e.,
two operating). Under normal circumstances however, all three will operate to reduce up flow
velocity and maximise overflow water clarity. An electric actuated, Thickener Feed Valve (3340-
XV-303A, 303B, 303C) isolates the individual thickener should it contain a high level of solids
(3340-LIT-310 / 312 / 314) or if the respective thickener underflow pump is not running. Before
re-opening the thickener feed valve, backflush water must first be injected by opening a flush
valve (3340- XV – 302A, 302B, 302C) for a specified time, prior to the feed valve opening to re-
fluidise any solids build-up. The Froth Suppression and Dilution Water pump (3340 – PU – 109)
must be running before the flush water valves can open.

18.4 Engineering Module 2 – 3340PU171

18.4.1 Description – 3340PU171

The following figure shows the elements that make up the 3340PU171 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 494 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340BX109
3340-XV-301
Hydrofloat
Concentrate
3340 – BX - 109

Flush Water
3340XV302_303A
3340-XV-302A
3340-XV-303A
Settler 1
3340 – TH - 101

3340XV302_303B
3340-XV-302B
3340-XV-303B

Settler 2
3340 – TH - 102

3340-XV-302C
3340-XV-303C
Settler 3
3340XV302_303C 3340 – TH - 103

LAHH LAH 3340PU171


3340359 3340359

LSH M
H
LSH Tails Launder
TE

3340 – PU – 171

Figure 65: Blockflow Control Diagram of the 3340PU171 System

18.4.2 Unit of Control Modules – 3340PU171

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN ECPF_ALIMENTACION EM 3340PU171 Sub EM

Tag Service
3340-TE-359 Bearing temperature switch
3340-LSH-359 Level Switch High
3340-LSHH-359 Level Switch High High – Settler Bund area

Table 610: List of Unit Controls – 3340PU171

18.4.3 Interlocks – 3340PU171

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 495 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag 3340-PU-171 Description Thickener Spillage Pump


ECPF_ALIMENT Sub
UN EM 3340PU171
ACION EM
Interlock
Motor Type M1 Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Delay 10
3340-LSH-359.ACT High level switch activated × seconds
Note 1
3340-TE-359.ACT High bearing temperature alarm ×
BLACKOUT Delay 5
Electrical BlackOut Activated ×
ELECTRICO.ACT seconds

Table 611: List of Interlocks for 3340-PU-171

Note 1: Pump to run 15 minutes after the high level has been removed.
18.4.4 Alarms and Process Setpoints – 3340PU171

T3 Alarms and Process Setpoints


UN ECPF_ALIMENTACION EM 3340PU171 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-LSH-359 Thickener Spillage Pump High


0 - 100 % 27%
Switch Alarm
3340-LSHH- Thickener Spillage Pump High
359 0 - 100 % 85%
High Switch Alarm

Table 612: Alarms and Process Setpoint 3340-PU-171

Note: Level switches setpoints set in field, not within PLC.


18.4.5 Binary Messages – 3340PU171

T4 Binary State Messages


UN ECPF_ALIMENTACION EM 3340PU171 Sub EM
Tag Description OFF ON
3340-LSHH- Thickener BUND AREA HIGH HIGH
359 × Delay 5 seconds
SLURRY LEVEL

Table 613: Binary State Messages 3340PU171

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 496 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

18.4.6 Regulatory Control Loops – 3340PU171

Not applicable.
18.4.7 Advanced Control Loops – 3340PU171

Not applicable
18.4.8 Description – 3340PU171

Spillage in the thickener bund area will gravitate to the Thickener Spillage Pump (3340 – PU –
171). The pump will discharge by manual selection to either:
 The Thickener Feed Distribution Box (3340 – BX - 109);
 Or to the CPF Tails Launder (3340 – LN - 106).
This equipment can operate in manual mode or automatic mode. In manual mode, the start and
stop by the PLC will depend on the start/stop command that the operator. The operation of the
pump in Automatic Mode will occur if:
- The pump will start automatically, if it is ready to Operate in Sequence, and if Sump level
switch is high.
- The sump pump will stop automatically 15 minutes after the level switch high has fallen
away. The time delay in stopping the pump allows the pump to continue to run while hose
down of the area is occurring.
An additional High High limit switch is included to alarm the operator that significant spillage is
occurring in the area requiring operator intervention.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 497 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

19.0 UNIDAD: ECPF_3340TH101

Refer to:
MQ14-08-DR-3340-PD1078 Thickener Feed Box
MQ14-08-DR-3340-PD1079 Thickener Feed Box
MQ14-08-DR-3340-PD1080 Thickener Underflow
MQ15-51-TE-3340-GA0601 Settler vendor Control Philosophy

A block flow control diagram is depicted below for the ECPF_3340TH101 system.
3340TH101_RECIR
Regrind Mill
3340-XV-351E

3340-XV-348
Regrind Cyclone
Feed Density

3340-XV-351D
Thickener
Feed Box
Flush Water

3340-XV-304
3340-XV-351B

3340 – TH – 101

Thickener
Feed Box Fluidisation
Water Tank
3340-LT- 310
LT
PT

3340-PT- 311A
PT

3340-PT- 311B
DC FC
SC
PT

3340355
3340356
3340-DCV-305 3340-PT- 311C 3340351

M DT FT

3340-XV-351A
3340 – PU – 104

FAL
3340-XV-351C
3340353
3340-XV- 353 3340TH101UF
FSL

GSW

Figure 66: Blockflow Control Diagram of ECPF_3340TH101

The above control unit is broken into two Engineering Module 1’s with no sub Engineering Module 2’s:
- 3340TH101UF
- 3340TH101_RECIR

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 498 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

19.0.1 Modules of Control ECPF_3340TH101

T1 Control Mod
Sub
UN ECPF_3340TH101 EM
EM
Tag Service
3340-TH-101 Deep Cone Settler 1
3340-DCV-305 Underflow Density Control Valve
3340-XV-304 Froth Suppression Spray Water Isolation
3340-LIT-310 BED LEVEL MEASUREMENT
3340-PIT-311A BED PRESSURE MEASUREMENT
3340-PIT-311B BED PRESSURE MEASUREMENT
3340-PIT-311C BED PRESSURE MEASUREMENT

Table 614: List of Modules of Control for ECPF_3340TH101

19.0.2 Interlocks – ECPF_3340TH101

T2 Interlock
Tag 3340-DCV-305 Description Underflow Density Control Valve
ECPF_3340TH10 Sub
UN EM
1 EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If thickener underflow pump is not running Delay Time


3340-PU104.!RN ×
for a delay time 30 seconds

Table 615: List of Interlocks for 3340-DCV305

T2 Interlock
Tag 3340-XV-304 Description Froth Suppression Spray Water Isolation
ECPF_3340TH10 Sub
UN EM
1 EM
Failure Position: Interlock
Motor Type Interlock
Keep Last (KL) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 499 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303A.CL If thickener feed valve is closed ×

Table 616: List of Interlocks for 3340-XV-304

19.0.3 Alarms and Process Setpoints – ECPF_3340TH101

T3 Alarms and Process Setpoints


UN ECPF_3340TH101 EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Typicall
3340 - LIT – y 10.
310 Ultrasonic Settler Mud Bed Level 0 - 100 % 95
Not for
control
3340 - PIT – % of
Mud Bed Pressure Transmitter –
311A 0 - 100 max 0 10
Upper cone
KPa
3340 - PIT – % of
Mud Bed Pressure Transmitter –
311B 0 - 100 max 0 10
Middle cone
KPa
3340 - PIT – % of 0 – 30
Mud Bed Pressure Transmitter –
311C 0 - 100 max (Typical 30
Lower cone
KPa ly 15)

Table 617: Alarms and Process Setpoint ECPF_3340TH101

Each settler has three pressure transmitters (3340- PIT – 311A/B/C, 313A/B/C and 315A/B/C)
located vertically above each other to assess the total solids above each unit’s location. The
following water and maximum pressure values are possible on each PIT, allowing the percentage
of maximum filled to be calculated and displayed to the operator.
Height of Overflow Expected Pressure with Maximum Pressure
Tag Name
Above PIT [m] Water Only [KPa] with Slurry [KPa]4

Lower Cone Pressure


3340- PIT – 311C 10.15 99.5 146.8
Transmitter

Middle Cone Pressure


3340 - PIT – 311B 7.02 68.8 101.5
Transmitter

4
Assumes a maximum compacted density of 1.476 t/m3 (50%mass)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 500 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Upper Cone Pressure


3340- PIT – 311A 5.40 52.9 78.1
Transmitter

Table 618: Settler Pressure Transmitter Solids Calculation Constants

The percentage fill of solids above each transmitter will be calculated and displayed to the control
room operator.
Percent Fill of PIT A = (Actual [KPa] – 52.9 ) / (78.1 – 52.9) × 100%
Percent Fill of PIT B = (Actual [KPa] – 68.8 ) / (101.5 – 68.8) × 100%
Percent Fill of PIT C = (Actual [KPa] – 99.5 ) / (146.8 – 99.5) × 100%
The three separate pressure transmitters are utilised to ensure that no bridging is occurring on
the outlet of each individual transmitter. Consequently, the lowest pressure transmitter (C), should
always contain the greatest quantity of solids fill, followed by (B) and lastly (A). If this is not the
case, then an alarm must alert the operator. Should a high limit be achieved on any of the three
pressure transmitters, then an alarm must alert the operator.
Similarly, a separate ultrasonic level transmitter (3340 – LIT - 310 / 312 / 314) provides an
alternative measurement of the height of the solids mud bed within the settler. Should a high limit
be achieved on this level transmitter, then an alarm must alert the operator, but also the respective
thickener feed valve (3340 - XV – 303A, 303B, 303C) must close.
Once settled at the base of the thickener, solids will quickly compact to a high density and will
require re-fluidisation prior to being pumped from the thickener at a controlled slurry density to
the Regrind Mill circuit. For this to occur, dilution water is injected at a controlled rate into the base
of the thickener via a modulating control valve (3340 - DCV – 305 / 307 / 309).
19.0.4 Binary Messages – ECPF_3340TH101

T4 Binary State Messages


UN ECPF_3340TH101 EM Sub EM
Tag Description OFF ON
3340-LIT-310.H High Solids level in 3340-TH101 × Delay 5 seconds
3340 - PIT – High Solids level in 3340-TH-101
311A.H × Delay 5 seconds
Upper Cone
3340 - PIT – High Solids level in 3340-TH-101
311B.H × Delay 5 seconds
Middle Cone
3340 - PIT – High Solids level in 3340-TH-101
311C.H × Delay 5 seconds
Lower Cone
3340-PIT-311B
>
Bridging of Solids in 3340 – TH - 101 × Delay 5 seconds
3340-PIT311C

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 501 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PIT-311A
>
(3340-PIT311C
Bridging of Solids in 3340 – TH - 101 × Delay 5 seconds
OR
3340-PIT311B)

Table 619: Binary State Messages ECPF_3340TH101

19.0.5 Regulatory Control Loops – ECPF_3340TH101

Once settled at the base of the thickener, solids will quickly compact to a high density and will
require re-fluidisation prior to being pumped from the thickener at a controlled slurry density to
the Regrind Mill circuit. For this to occur, dilution water is injected at a controlled rate into the base
of the thickener via a modulating control valve (3340 - DCV – 305 / 307 / 309).

T5 Regulatory Control Loops


UN ECPF_3340TH101 EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 – 100 Expected
(0% = setpoint 22%
99.5KP = 110 KPa
3340 - PIC – Mud Bed Solids level Pressure
a
311C Controller – Lower cone
100% =
146.8K
Pa)

The underflow pump speed when pumping to the regrind section (see 3340TH101) is adjusted in
order to maintain a relatively low solids level inside the settler.

19.0.6 Advanced Control Loops – ECPF_3340TH101

Not applicable

19.0.7 Sequence Description – ECPF_3340TH101

The settler feed start sequence, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 502 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN ECPF_3340TH101 EM Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
10 60
1. Start 3340-PU-109.MO1 Start pump. Working
seconds seconds
Open Feed Box Froth 2 60
2. Open 3340 – XV – 301A Open
suppression isolation valve seconds seconds
Open Flush Water Valve for 30 2 60
3. Open 3340 - XV – 302A Open
seconds seconds seconds
2 60
4. Close 3340 - XV – 302A Close Flush Water Valve Open
seconds seconds
2 60
5. Open 3340 - XV – 303A Open Thickener Feed Valve Open
seconds seconds
2 60
6. Open 3340 - XV – 304 Settler Froth Suppression Valve Open
seconds seconds

Table 620: Start Sequence ECPF_3340TH101

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-109 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-109-MO1 stopped
The settler feed stop sequence, shall follow the following steps:
TSQST Stop Sequence Table
UN ECPF_3340TH101 EM Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 20
1. Close 3340 - XV – 304 Settler Froth Suppression Valve Closed
seconds seconds
2 20
2. Close 3340 - XV – 303A Thickener Feed Valve Closed
seconds seconds
3. Proceed only if all three thickener feed valves (3340-XV-303A AND 3340-XV 0 303B AND 3340-XV – 303C) are closed
Open Feed Box Froth 2 20
4. Close 3340 – XV – 301A Close
suppression isolation valve seconds seconds
10 60
5. Stop 3340-PU-109.MO1 Stop Pump Stopped
seconds seconds

Table 621: Stop Sequence ECPF_3340TH101

19.1 Engineering Module 2 – 3340TH101UF

19.1.1 Description – 3340TH101UF

The following figure shows the elements that make up the 3340TH101UF equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 503 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340TH101_RECIR
Regrind Mill
3340-XV-351E

3340-XV-348
Regrind Cyclone
Feed Density

3340-XV-351D
Thickener
Feed Box
Flush Water

3340-XV-304

3340 – TH – 101
3340-XV-351B

Thickener
Feed Box Fluidisation
Water Tank
3340-LT- 310
LT
PT

3340-PT- 311A
PT

3340-PT- 311B
DC FC
SC
PT

3340355
3340356
3340-DCV-305 3340-PT- 311C 3340351

M DT FT

3340-XV-351A
3340 – PU – 104

FAL
3340-XV-351C
3340353
3340-XV- 353 3340TH101UF
FSL

GSW

Figure 67: Blockflow Control Diagram of the 3340TH101UF System

19.1.2 Unit of Control Modules – 3340TH101UF

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN ECPF_3340TH101 EM 3340TH101UF Sub EM

Tag Service
3340-PU-104 Thickener Underflow Pump 1
3340-TE-351 Underflow Pump Thermistor
3340-DIT-356 DENSIDAD UNDERFLOW SETTLER #1
3340-FSL-353 GLAND SEAL WATER
3340-XV-351A SUCTION Valve
3340-XV-351C Suction Drain Valve
3340-XV-351B FLUSH WATER TO Suction Pipeline
3340-FIT-355 SONAR FLOW TRANSMITTER
3340-XV-353 GLAND SEAL WATER

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 504 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-DX-356 DENSIDAD UNDERFLOW SETTLER Isolator

Table 622: List of Unit Controls – 3340TH101UF

19.1.3 Interlocks – 3340TH101UF

T2 Interlock
Tag 3340-XV-351A Description Suction valve
ECPF_3340TH10 3340TH101U Sub
UN EM
1 F EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-351C.OP Suction drain valve open


OR OR ×
3340-XV-351C.OPNG Suction drain valve opening
3340-PU-104.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-351A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-351A.OPNG)

Table 623: List of Interlocks for 3340-XV-351A

T2 Interlock
Tag 3340-XV-351B Description Suction Flush Water Valve
ECPF_3340TH10 3340TH101U Sub
UN EM
1 F EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 505 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 624: List of Interlocks for 3340-XV-351B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Tag 3340-XV-351C Description Suction Drain Water Valve
ECPF_3340TH10 3340TH101U Sub
UN EM
1 F EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 625: List of Interlocks for 3340-XV-351C

T2 Interlock
Tag 3340 – PU – 104 Description Thickener Underflow Pump
ECPF_3340TH10 3340TH101U Sub
UN EM
1 F EM
Interlock
Motor Type VFD Intlck_3340BB_SL_01
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-353 !OP ×
If gland seal water valve not open and
AND Note 1
pump is running
3340-PU-104.MO1.Run
3340-FSL-353.ACT ×
Flow switch has a low flow alarm for a Time Delay
AND
time delay and pump is running 300 seconds
3340-PU-104-MO1.Run
3340-FSL-353.ACT Flow switch has a low flow alarm ×
3340-XV-351A CL ×
OR CLN Suction valve Is closed or closing and Time Delay
AND pump is running for a time delay 10 seconds
3340-PU-104-MO1.Run
3340-XV-351C OP OR × Debounce
Suction drain valve is open or opening
OPN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 506 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-FIT-355.LL AND ×
Slurry flowrate is Low Low and pump is Time Delay
3340-PU-104-
running 600 seconds
MO1.RUN
3340 - XV –351E.CL or Both Regrind Feed Valve (3340 - XV –
CLN 351E)
3340 - XV –351D.CL or AND Time Delay
×
CLN Bypass Valve (3340 - XV –351D) 60 seconds
AND Are closed or closing and pump is running
3340-PU-104-MO1.Run for a time delay
×
3340 - TE - 351 Pump Thermistor alarm
Instrument Air Pressure (3340-PIT-675) is × Time Delay
3340-PIT-675.LL
Low Low for a time delay 10 seconds
Either ×
3340-PIT-670.LL
3340-PIT-670
OR
OR
3340-PIT-671.LL Time Delay
3340-PIT-671
OR 60 seconds
OR
3340-PIT-678.LL
3340-PIT-678
is Low Low for a time delay
CPF Make-Up Water Pressure 3720-PIT- × Time Delay
3720-PIT-116.LL
116 is Low Low for a time delay 180 seconds
Fluidisation Water pressure (3340-PIT- × Delay time
3340-PIT-647.LL
647) is low low for a delay time 60 seconds
Flush Water Pressure (3340-PIT-648) is × Delay time 5
3340-PIT-648.LL
not low low for a delay time minutes
3340-XV-303A CL ×
OR CLN All thickener feed valves are closed or
AND closing
3340-XV-303B CL (3340-XV-303A
OR CLN AND Delay time 3
AND 3340-XV-303B minutes
3340-XV-303C CL AND
OR CLN 3340-XV-303C)
AND and pump is running for a time delay
3340-PU-104-MO1.Run
Gland seal water pressure (3340-PIT-656) × Delay time
3340-PIT-656.LL
is Low Low for a delay time 60 seconds
Boosted gland seal water pressure (3340- × Delay time
3340-PIT-659.LL
PIT-659) is Low Low for a delay time 60 seconds

Table 626: List of Interlocks for 3340 – PU - 104

Additional interlocks have been included for this pump in order to prevent solids from being
pumped downstream when plant operations are becoming unstable and there is a likelihood of a
plant crash stop. Stopping the pump timeously will reduce solids loading in downstream pipelines
and reduce risk of blockages / spillage during a crash stop.

T2 Interlock
Densitometer Nuclear Source Isolation
Tag 3340-DX-356 Description
Shutter
ECPF_3340TH10 3340TH101U Sub
UN EM
1 F EM
Interlock Intlck_OBTURADOR_DENSI
Motor Type
Type METRO_01

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 507 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-104.!RUN If the pump is not running ×

Table 627: List of Interlocks for 3340-DX-356

T2 Interlock
Tag 3340-XV-353 Description Pump Gland Seal Water Valve
ECPF_3340TH10 3340TH101U Sub
UN EM
1 F EM
Failure Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-104.!RUN If the pump is not running ×

Table 628: List of Interlocks for 3340-XV-353

19.1.4 Alarms and Process Setpoints – 3340TH101UF

T3 Alarms and Process Setpoints


UN ECPF_3340TH101 EM 3340TH101UF Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-355 Pump Flowmeter 0 - 1000 m3/hr 155 90
3340-DIT-356 Pump densitometer 1.0 – 2.0 t/m3 1.60
3340-FSL-353 Pump Gland Seal Water Flow
0 – 4.0 m3/hr 1.58
switch

Table 629: Alarms and Process Setpoint 3340TH101UF

The alarms associated with the Density transmitter, as well as the flow measurement should be
inhibited when pump 3340-PU-104 is not running.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 508 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

By combining the flow transmitter and densitometer readings, a totalized mass flow to the regrind
mills will be calculated based upon the following formulae:
𝑆𝐺
𝑇 = 𝑉𝑝 (𝑑𝑝 − 1) × )
𝑆𝐺 − 1
Where: T = Dry Solids Mass [tph]
Vp = Volumetric Flowrate [m3/hr] 3340-FIT-355
dp = Slurry density [t/m3] 3340-DIT-356
SG = Solids Specific Gravity = 2.82 t/m3
Solids mass pumped to the regrind mills will be summed with the other to settlers underflow
discharges and totalized on an hour, shift, day and monthly basis when the following is true:
a) 3340 – XV – 351E is open, and
b) 3340 – PU – 104 is running.
This mass flow combined with the mass flows from the other two settlers, will be visible to the
control room operator. Together with the concentrate product mass returned to concentrator flow
rate calculation, this value will provide input into the calculation of the mill recirculating load (see
section later).
19.1.5 Binary Messages – 3340TH101UF

T4 Binary State Messages


UN ECPF_3340TH101 EM 3340TH101UF Sub EM
Tag Description OFF ON

3340-ZSC-356 LINE RADIOACTIVE SOURCE


× Note 2
PUMP 3340-PU-104 CLOSED
3340-ZSO-356 LINE RADIOACTIVE SOURCE
× Note 1
PUMP 3340-PU-104 OPEN

Table 630: Binary State Messages 3340TH101UF

Note:
1) Condition should alarm, if the valve is open 5 seconds after the pump 3340-PU-104 has
stopped.
2) Condition should alarm, if the valve is closed, 5 seconds after the pump 3340-PU-104 is
running. If this condition occurs, calculation of the mass flowrate and average value % of
solids should not occur.
3) An alarm should be provided when a nuclear density meter reading (tag 3340-DIT-356)
provides a difference in measured value greater than 10%, under normal operating
conditions. Alarm will not be triggered when only one pump is operating, when the pump
is under start-up conditions.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 509 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

19.1.6 Regulatory Control Loops – 3340TH101UF

T5 Regulatory Control Loops


UN ECPF_3340TH101 EM 3340TH101UF Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
3340 - FIC – 63 - 100 % m3/hr 155 - Note 2
Thickener Underflow Pump Flowmeter
355 1000
0 - 100 % t/m3 1.0 – Note 1
3340 - DIC – Thickener Underflow Pump 2.0 Expected
356 densitometer setpoint 1.48
t/m3.

Table 631: Regulatory Control Loops for 3340TH101UF

Note 1: Controller will be disabled (tracking action), if pump is stopped


Note 2 The thickener underflow pump speed is adjusted to achieve a flowrate setpoint.
The setpoint will be placed on minimum value when the underflow is recirculating
to the thickener feed (i.e. 3340 – XV – 351E closed or closing).
When pumping underflow to the Regrind Milling circuit (i.e. 3340 – XV – 351E open
or opening), the setpoint is adjusted to maintain a solids level in the thickener as
measured by 3340 - PIT- 311C.
While the slurry is being pumped to the regrind mills, the maximum flowrate shall
be limited by the regrind cyclone feed pump maximum density limit (3340 – DIT -
607).

19.1.7 Advanced Control Loops – 3340PU104

Not applicable

19.1.8 Sequence Description – 3340PU104

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. The pump start sequence 3340-PU-104, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 510 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN ECPF_3340TH101 EM 3340TH101UF Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Close 3340-XV-351C Suction drain Valve Closed
seconds seconds
(Open &
Low Flow
2 60
2. Open 3340-XV-353 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
Open
and 2 220
3. Open 3340-XV-351B Suction Valve.
3340-XM- seconds seconds
185.RUN
10 60
4. Start 3340-PU-104.MO1 Start pump. Working
seconds seconds

Table 632: Start Sequence 3340PU104

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-104 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-104-MO1 stopped
The pump stop sequence 3340-PU-104, shall follow the following steps:
TSQST Stop Sequence Table
UN ECPF_3340TH101 EM 3340TH101UF Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-104.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3340-PU-104.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3340-XV-351A Suction Valve. Closed
seconds seconds
2 60
4. Open 3340-XV-351C Suction Drain valve Opened
seconds seconds
2 20
5. Close 3340-XV-353 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-351B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-351B Closed
valve seconds seconds

Table 633: Stop Sequence 3340PU104

The Shutter of the Nuclear Density Meter (3340-DX-356) will open 5 seconds after the pump
3340-PU-104 is operational. The shutter will close when the pump stops.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 511 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

19.2 Engineering Module 2 – 3340TH101_RECIR

19.2.1 Description – 3340TH101_RECIR

The following figure shows the elements that make up the 3340TH101_RECIR equipment
module.
3340TH101_RECIR
Regrind Mill
3340-XV-351E

3340-XV-348
Regrind Cyclone
Feed Density

3340-XV-351D
Thickener
Feed Box
Flush Water

3340-XV-304

3340 – TH – 101
3340-XV-351B

Thickener
Feed Box Fluidisation
Water Tank
3340-LT- 310
LT
PT

3340-PT- 311A
PT

3340-PT- 311B
DC FC
SC
PT

3340355
3340356
3340-DCV-305 3340-PT- 311C 3340351

M DT FT

3340-XV-351A
3340 – PU – 104

FAL
3340-XV-351C
3340353
3340-XV- 353 3340TH101UF
FSL

GSW

Figure 68: Blockflow Control Diagram of the 3340TH101_RECIR System

19.2.2 Unit of Control Modules – 3340TH101_RECIR

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN ECPF_3340TH101 EM 3340TH101_RECIR Sub EM

Tag Service
3340-XV-351E Regrind Feed Valve
3340-XV-351D Bypass Recirculating Valve
3340-XV-348 Regrind Feed Drain Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 512 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 634: List of Unit Controls – 3340TH101_RECIR

19.2.3 Interlocks – 3340TH101_RECIR

T2 Interlock
Tag 3340-XV-351E Description Regrind Feed Valve
ECPF_3340TH10 3340TH101_ Sub
UN EM
1 RECIR EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340 - XV – 348.!CL or Regrind Feed Drain Valve is not closed Time Delay
×
!CLN for a time delay 60 seconds
3340 - XV – 602A.!OP
Both Regrind Cyclone Feed Pump Suction Time Delay
AND ×
Valves are not open for a time delay 30 seconds
3340 - XV – 603A!OP
Bypass Recirculating Valve is open for a Time Delay
3340 - XV – 351D.OP ×
time delay 15 seconds

Table 635: List of Interlocks for 3340-XV-351E

T2 Interlock
Tag 3340-XV-351D Description Bypass Recirculating Valve
ECPF_3340TH10 3340TH101_ Sub
UN EM
1 RECIR EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340 - XV –352E.OP or Regrind Feed Valve is open or opening for Time Delay
×
OPN a time delay 5 seconds

Table 636: List of Interlocks for 3340-XV-351D

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 513 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-XV-348 Description Regrind Feed Drain Valve
ECPF_3340TH10 3340TH101_ Sub
UN EM
1 RECIR EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If Regrind Feed Valve is Closed for a time Time Delay


3340 - XV – 351E.CL ×
delay 5 seconds

Table 637: List of Interlocks for 3340-XV-348

19.2.4 Alarms and Process Setpoints – 3340TH101_RECIR

Not Applicable

19.2.5 Binary Messages – 3340TH101_RECIR

Not Applicable
19.2.6 Regulatory Control Loops – 3340TH101_RECIR

Not Applicable

19.2.7 Advanced Control Loops – 3340TH101_RECIR

Not applicable

19.2.8 Sequence Description – 3340PU104

The sequence below tabulates the steps to be completed when changing from directing slurry
from the thickener feed distribution box (3340 – BX – 109) and redirecting it to the regrind mills

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 514 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Regrind Feed Sequence Table


UN ECPF_3340TH101 EM 3340TH101_RECIR Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 20
1. Close 3340-XV-348 Regrind Feed Drain Valve Closed
seconds seconds
Open 2 30
2. Open 3340-XV-351E Regrind Feed Valve
seconds seconds
2 30
3. Close 3340-XV-351D Bypass Recirculating Valve Closed
seconds seconds

Table 638: Regrind Feed Sequence

The sequence below tabulates the steps to be completed when changing from directing slurry
from the regrind mills to the thickener feed distribution box (3340 – BX – 109).
:
TSQST Thickener Recirculation Sequence Table
UN ECPF_3340TH101 EM 3340TH101_RECIR Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 30
1. Open 3340-XV-351D Bypass Recirculating Valve Open
seconds seconds
Closed 2 30
2. Close 3340-XV-351E Regrind Feed Valve
seconds seconds
2 20
3. Open 3340-XV-348 Regrind Feed Drain Valve Closed
seconds seconds

Table 639: Thickener Recirculation Sequence

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 515 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

20.0 UNIDAD: ECPF_3340TH102

Refer to:
MQ14-08-DR-3340-PD1078 Thickener Feed Box
MQ14-08-DR-3340-PD1079 Thickener Feed Box
MQ14-08-DR-3340-PD1080 Thickener Underflow
MQ15-51-TE-3340-GA0601 Settler vendor Control Philosophy

A block flow control diagram is depicted below for the ECPF_3340TH102 system.
3340TH102_RECIR
Regrind Mill
3340-XV-352E

3340-XV-349
Regrind Cyclone
Feed Density

3340-XV-352D
Thickener
Feed Box
Flush Water

3340-XV-306

3340 – TH – 102
3340-XV-352B

Thickener
Feed Box Fluidisation
Water Tank
3340-LT- 312
LT
PT

3340-PT- 313A
PT

3340-PT- 313B
DC FC
SC
PT

3340357
3340358
3340-DCV-307 3340-PT- 313C 3340352

M DT FT

3340-XV-352A
3340 – PU – 105

FAL
3340-XV-352C
3340354
3340-XV- 354 3340TH102UF
FSL

GSW

Figure 69: Blockflow Control Diagram of ECPF_3340TH102

The above control unit is broken into two Engineering Module 1’s with no sub Engineering Module 2’s:
- 3340TH102UF
- 3340TH102_RECIR

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 516 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

20.0.1 Modules of Control ECPF_3340TH102

T1 Control Mod
Sub
UN ECPF_3340TH102 EM
EM
Tag Service
3340-TH-102 Deep Cone Settler
3340-DCV-307 Underflow Density Control Valve
3340-XV-306 Froth Suppression Spray Water Isolation
3340-LIT-312 BED LEVEL MEASUREMENT
3340-PIT-313A BED PRESSURE MEASUREMENT
3340-PIT-313B BED PRESSURE MEASUREMENT
3340-PIT-313C BED PRESSURE MEASUREMENT

Table 640: List of Modules of Control for ECPF_3340TH102

20.0.2 Interlocks – ECPF_3340TH102

T2 Interlock
Tag 3340-DCV-307 Description Underflow Density Control Valve
ECPF_3340TH10 Sub
UN EM
2 EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If thickener underflow pump is not running Delay Time


3340-PU105.!RN ×
for a delay time 30 seconds

Table 641: List of Interlocks for 3340-DCV305

T2 Interlock
Tag 3340-XV-306 Description Froth Suppression Spray Water Isolation
ECPF_3340TH10 Sub
UN EM
2 EM
Failure Position: Interlock
Motor Type Interlock
Keep Last (KL) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 517 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303B.CL If thickener feed valve is closed ×

Table 642: List of Interlocks for 3340-XV-306

20.0.3 Alarms and Process Setpoints – ECPF_3340TH102

T3 Alarms and Process Setpoints


UN ECPF_3340TH102 EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Typicall
3340 - LIT – y 10.
312 Ultrasonic Settler Mud Bed Level 0 - 100 % 95
Not for
control
3340 - PIT – % of
Mud Bed Pressure Transmitter –
313A 0 - 100 max 0 10
Upper cone
KPa
3340 - PIT – % of
Mud Bed Pressure Transmitter –
313B 0 - 100 max 0 10
Middle cone
KPa
3340 - PIT – % of 0 – 30
Mud Bed Pressure Transmitter –
313C 0 - 100 max (Typical 30
Lower cone
KPa ly 15)

Table 643: Alarms and Process Setpoint ECPF_3340TH102

Each settler has three pressure transmitters (3340- PIT – 311A/B/C, 313A/B/C and 315A/B/C)
located vertically above each other to assess the total solids above each unit’s location. The
following water and maximum pressure values are possible on each PIT, allowing the percentage
of maximum filled to be calculated and displayed to the operator.
Height of Overflow Expected Pressure with Maximum Pressure
Tag Name
Above PIT [m] Water Only [KPa] with Slurry [KPa]5

Lower Cone Pressure


3340- PIT – 313C 10.15 99.5 146.8
Transmitter

Middle Cone Pressure


3340 - PIT – 313B 7.02 68.8 101.5
Transmitter

5
Assumes a maximum compacted density of 1.476 t/m3 (50%mass)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 518 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Upper Cone Pressure


3340- PIT – 313A 5.40 52.9 78.1
Transmitter

Table 644: Settler Pressure Transmitter Solids Calculation Constants

The percentage fill of solids above each transmitter will be calculated and displayed to the control
room operator.
Percent Fill of PIT A = (Actual [KPa] – 52.9 ) / (78.1 – 52.9) × 100%
Percent Fill of PIT B = (Actual [KPa] – 68.8 ) / (101.5 – 68.8) × 100%
Percent Fill of PIT C = (Actual [KPa] – 99.5 ) / (146.8 – 99.5) × 100%
The three separate pressure transmitters are utilised to ensure that no bridging is occurring on
the outlet of each individual transmitter. Consequently, the lowest pressure transmitter (C), should
always contain the greatest quantity of solids fill, followed by (B) and lastly (A). If this is not the
case, then an alarm must alert the operator. Should a high limit be achieved on any of the three
pressure transmitters, then an alarm must alert the operator.
Similarly, a separate ultrasonic level transmitter (3340 – LIT - 310 / 312 / 314) provides an
alternative measurement of the height of the solids mud bed within the settler. Should a high limit
be achieved on this level transmitter, then an alarm must alert the operator, but also the respective
thickener feed valve (3340 - XV – 303A, 303B, 303C) must close.
Once settled at the base of the thickener, solids will quickly compact to a high density and will
require re-fluidisation prior to being pumped from the thickener at a controlled slurry density to
the Regrind Mill circuit. For this to occur, dilution water is injected at a controlled rate into the base
of the thickener via a modulating control valve (3340 - DCV – 305 / 307 / 309).
20.0.4 Binary Messages – ECPF_3340TH102

T4 Binary State Messages


UN ECPF_3340TH102 EM Sub EM
Tag Description OFF ON
3340-LIT-312.H High Solids level in 3340-TH102 × Delay 5 seconds
3340 - PIT – High Solids level in 3340-TH-102
313A.H × Delay 5 seconds
Upper Cone
3340 - PIT – High Solids level in 3340-TH-102
313B.H × Delay 5 seconds
Middle Cone
3340 - PIT – High Solids level in 3340-TH-102
313C.H × Delay 5 seconds
Lower Cone
3340-PIT-313B
>
Bridging of Solids in 3340 – TH – 102 × Delay 5 seconds
3340-PIT313C

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 519 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PIT-313A
>
(3340-PIT313C
Bridging of Solids in 3340 – TH - 102 × Delay 5 seconds
OR
3340-PIT313B)

Table 645: Binary State Messages ECPF_3340TH102

20.0.5 Regulatory Control Loops – ECPF_3340TH102

Once settled at the base of the thickener, solids will quickly compact to a high density and will
require re-fluidisation prior to being pumped from the thickener at a controlled slurry density to
the Regrind Mill circuit. For this to occur, dilution water is injected at a controlled rate into the base
of the thickener via a modulating control valve (3340 - DCV – 305 / 307 / 309).

T5 Regulatory Control Loops


UN ECPF_3340TH102 EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 – 100 Expected
(0% = setpoint 22%
99.5KP = 110 KPa
3340 - PIC – Mud Bed Solids level Pressure
a
313C Controller – Lower cone
100% =
146.8K
Pa)

The underflow pump speed when pumping to the regrind section (see 3340TH102) is adjusted in
order to maintain a relatively low solids level inside the settler.

20.0.6 Advanced Control Loops – ECPF_3340TH102

Not applicable

20.0.7 Sequence Description – ECPF_3340TH102

The settler feed start sequence, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 520 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN ECPF_3340TH102 EM Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
10 60
1. Start 3340-PU-109.MO1 Start pump. Working
seconds seconds
Open Feed Box Froth 2 60
2. Open 3340 – XV – 301A Open
suppression isolation valve seconds seconds
Open Flush Water Valve for 30 2 60
3. Open 3340 - XV – 302B Open
seconds seconds seconds
2 60
4. Close 3340 - XV – 302B Close Flush Water Valve Open
seconds seconds
2 60
5. Open 3340 - XV – 303B Open Thickener Feed Valve Open
seconds seconds
2 60
6. Open 3340 - XV – 306 Settler Froth Suppression Valve Open
seconds seconds

Table 646: Start Sequence ECPF_3340TH102

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-109 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-109-MO1 stopped
The settler feed stop sequence, shall follow the following steps:
TSQST Stop Sequence Table
UN ECPF_3340TH102 EM Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 20
1. Close 3340 - XV – 306 Settler Froth Suppression Valve Closed
seconds seconds
2 20
2. Close 3340 - XV – 303B Thickener Feed Valve Closed
seconds seconds
3. Proceed only if all three thickener feed valves (3340-XV-303A AND 3340-XV - 303B AND 3340-XV – 303C) are closed
Open Feed Box Froth 2 20
4. Close 3340 – XV – 301A Close
suppression isolation valve seconds seconds
10 60
5. Stop 3340-PU-109.MO1 Stop Pump Stopped
seconds seconds

Table 647: Stop Sequence ECPF_3340TH102

20.1 Engineering Module 2 – 3340TH102UF

20.1.1 Description – 3340TH102UF

The following figure shows the elements that make up the 3340TH102UF equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 521 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340TH102_RECIR
Regrind Mill
3340-XV-352E

3340-XV-349
Regrind Cyclone
Feed Density

3340-XV-352D
Thickener
Feed Box
Flush Water

3340-XV-306

3340 – TH – 102
3340-XV-352B

Thickener
Feed Box Fluidisation
Water Tank
3340-LT- 312
LT
PT

3340-PT- 313A
PT

3340-PT- 313B
DC FC
SC
PT

3340357
3340358
3340-DCV-307 3340-PT- 313C 3340352

M DT FT

3340-XV-352A
3340 – PU – 105

FAL
3340-XV-352C
3340354
3340-XV- 354 3340TH102UF
FSL

GSW

Figure 70: Blockflow Control Diagram of the 3340TH102UF System

20.1.2 Unit of Control Modules – 3340TH102UF

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN ECPF_3340TH102 EM 3340TH102UF Sub EM

Tag Service
3340-PU-105 Thickener Underflow Pump 2
3340-TE-352 Underflow Pump Thermistor
3340-DIT-358 DENSIDAD UNDERFLOW
3340-FSL-354 GLAND SEAL WATER
3340-XV-352A SUCTION Valve
3340-XV-352C Suction Drain Valve
3340-XV-352B FLUSH WATER TO Suction Pipeline
3340-FIT-357 SONAR FLOW TRANSMITTER
3340-XV-354 GLAND SEAL WATER

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 522 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-DX-358 DENSIDAD UNDERFLOW SETTLER Isolator

Table 648: List of Unit Controls – 3340TH102UF

20.1.3 Interlocks – 3340TH102UF

T2 Interlock
Tag 3340-XV-352A Description Suction valve
ECPF_3340TH10 3340TH102U Sub
UN EM
2 F EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-352C.OP Suction drain valve open


OR OR ×
3340-XV-352C.OPNG Suction drain valve opening
3340-PU-105.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-352A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-352A.OPNG)

Table 649: List of Interlocks for 3340-XV-352A

T2 Interlock
Tag 3340-XV-352B Description Suction Flush Water Valve
ECPF_3340TH10 3340TH102U Sub
UN EM
2 F EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 523 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 650: List of Interlocks for 3340-XV-352B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Tag 3340-XV-352C Description Suction Drain Water Valve
ECPF_3340TH10 3340TH102U Sub
UN EM
2 F EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 651: List of Interlocks for 3340-XV-352C

T2 Interlock
Tag 3340 – PU – 105 Description Thickener Underflow Pump
ECPF_3340TH10 3340TH102U Sub
UN EM
2 F EM
Interlock
Motor Type VFD Intlck_3340BB_SL_01
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-354 !OP ×
If gland seal water valve not open and
AND Note 1
pump is running
3340-PU-105.MO1.Run
3340-FSL-354.ACT ×
Flow switch has a low flow alarm for a Time Delay
AND
time delay and pump is running 300 seconds
3340-PU-105-MO1.Run
3340-FSL-354.ACT Flow switch has a low flow alarm ×
3340-XV-352A CL ×
OR CLN Suction valve Is closed or closing and Time Delay
AND pump is running for a time delay 10 seconds
3340-PU-105-MO1.Run
3340-XV-352C OP OR × Debounce
Suction drain valve is open or opening
OPN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 524 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-FIT-357.LL AND ×
Slurry flowrate is Low Low and pump is Time Delay
3340-PU-105-
running 600 seconds
MO1.RUN
3340 - XV–352E.CL or Both Regrind Feed Valve (3340 – XV-
CLN 352E)
3340 - XV–352D.CL or AND Time Delay
×
CLN Bypass Valve (3340 - XV–352D) 60 seconds
AND Are closed or closing and pump is running
3340-PU-105-MO1.Run for a time delay
×
3340 - TE - 352 Pump Thermistor alarm
Instrument Air Pressure (3340-PIT-675) is × Time Delay
3340-PIT-675.LL
Low Low for a time delay 10 seconds
Either ×
3340-PIT-670.LL
3340-PIT-670
OR
OR
3340-PIT-671.LL Time Delay
3340-PIT-671
OR 60 seconds
OR
3340-PIT-678.LL
3340-PIT-678
is Low Low for a time delay
CPF Make-Up Water Pressure 3720-PIT- × Time Delay
3720-PIT-116.LL
116 is Low Low for a time delay 180 seconds
Fluidisation Water pressure (3340-PIT- × Delay time
3340-PIT-647.LL
647) is low low for a delay time 60 seconds
Flush Water Pressure (3340-PIT-648) is × Delay time 5
3340-PIT-648.LL
not low low for a delay time minutes
3340-XV-303A CL ×
OR CLN All thickener feed valves are closed or
AND closing
3340-XV-303B CL (3340-XV-303A
OR CLN AND Delay time 3
AND 3340-XV-303B minutes
3340-XV-303C CL AND
OR CLN 3340-XV-303C)
AND and pump is running for a time delay
3340-PU-105-MO1.Run
Gland seal water pressure (3340-PIT-656) × Delay time
3340-PIT-656.LL
is Low Low for a delay time 60 seconds
Boosted gland seal water pressure (3340- × Delay time
3340-PIT-659.LL
PIT-659) is Low Low for a delay time 60 seconds

Table 652: List of Interlocks for 3340 – PU - 105

Additional interlocks have been included for this pump in order to prevent solids from being
pumped downstream when plant operations are becoming unstable and there is a likelihood of a
plant crash stop. Stopping the pump timeously will reduce solids loading in downstream pipelines
and reduce risk of blockages / spillage during a crash stop.

T2 Interlock
Densitometer Nuclear Source Isolation
Tag 3340-DX-358 Description
Shutter
ECPF_3340TH10 3340TH102U Sub
UN EM
2 F EM
Interlock Intlck_OBTURADOR_DENSI
Motor Type
Type METRO_01

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 525 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-105.!RUN If the pump is not running ×

Table 653: List of Interlocks for 3340-DX-358

T2 Interlock
Tag 3340-XV-354 Description Pump Gland Seal Water Valve
ECPF_3340TH10 3340TH102U Sub
UN EM
2 F EM
Failure Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-105.!RUN If the pump is not running ×

Table 654: List of Interlocks for 3340-XV-354

20.1.4 Alarms and Process Setpoints – 3340TH102UF

T3 Alarms and Process Setpoints


UN ECPF_3340TH102 EM 3340TH102UF Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-357 Pump Flowmeter 0 - 1000 m3/hr 155 90
3340-DIT-358 Pump densitometer 1.0 – 2.0 t/m3 1.60
3340-FSL-354 Pump Gland Seal Water Flow
0 – 4.0 m3/hr 1.58
switch

Table 655: Alarms and Process Setpoint 3340TH102UF

The alarms associated with the Density transmitter, as well as the flow measurement should be
inhibited when pump 3340-PU-105 is not running.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 526 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

By combining the flow transmitter and densitometer readings, a totalized mass flow to the regrind
mills will be calculated based upon the following formulae:
𝑆𝐺
𝑇 = 𝑉𝑝 (𝑑𝑝 − 1) × )
𝑆𝐺 − 1
Where: T = Dry Solids Mass [tph]
Vp = Volumetric Flowrate [m3/hr] 3340-FIT-357
dp = Slurry density [t/m3] 3340-DIT-358
SG = Solids Specific Gravity = 2.82 t/m3
Solids mass pumped to the regrind mills will be summed with the other to settlers underflow
discharges and totalized on an hour, shift, day and monthly basis when the following is true:
a) 3340 – XV-352E is open, and
b) 3340 – PU-105 is running.
This mass flow combined with the mass flows from the other two settlers, will be visible to the
control room operator. Together with the concentrate product mass returned to concentrator flow
rate calculation, this value will provide input into the calculation of the mill recirculating load (see
section later).
20.1.5 Binary Messages – 3340TH102UF

T4 Binary State Messages


UN ECPF_3340TH102 EM 3340TH102UF Sub EM
Tag Description OFF ON

3340-ZSC-358 LINE RADIOACTIVE SOURCE


× Note 2
PUMP 3340-PU-105 CLOSED
3340-ZSO-358 LINE RADIOACTIVE SOURCE
× Note 1
PUMP 3340-PU-105 OPEN

Table 656: Binary State Messages 3340TH102UF

Note:
1) Condition should alarm, if the valve is open 5 seconds after the pump 3340-PU-105 has
stopped.
2) Condition should alarm, if the valve is closed, 5 seconds after the pump 3340-PU-105 is
running. If this condition occurs, calculation of the mass flowrate and average value % of
solids should not occur.
3) An alarm should be provided when a nuclear density meter reading (tag 3340-DIT-358)
provides a difference in measured value greater than 10%, under normal operating
conditions. Alarm will not be triggered when only one pump is operating, when the pump
is under start-up conditions.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 527 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

20.1.6 Regulatory Control Loops – 3340TH102UF

T5 Regulatory Control Loops


UN ECPF_3340TH102 EM 3340TH102UF Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
3340 – FIC- 63 - 100 % m3/hr 155 - Note 2
Thickener Underflow Pump Flowmeter
357 1000
0 - 100 % t/m3 1.0 – Note 1
3340 – DIC- Thickener Underflow Pump 2.0 Expected
358 densitometer setpoint 1.48
t/m3.

Table 657: Regulatory Control Loops for 3340TH102UF

Note 1: Controller will be disabled (tracking action), if pump is stopped


Note 2 The thickener underflow pump speed is adjusted to achieve a flowrate setpoint.
The setpoint will be placed on minimum value when the underflow is recirculating
to the thickener feed (i.e. 3340 – XV-352E closed or closing).
When pumping underflow to the Regrind Milling circuit (i.e. 3340 – XV-352E open
or opening), the setpoint is adjusted to maintain a solids level in the thickener as
measured by 3340 – PIT-313C.
While the slurry is being pumped to the regrind mills, the maximum flowrate shall
be limited by the regrind cyclone feed pump maximum density limit (3340 – DIT -
607).

20.1.7 Advanced Control Loops – 3340PU105

Not applicable

20.1.8 Sequence Description – 3340PU105

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. The pump start sequence 3340-PU-105, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 528 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN ECPF_3340TH102 EM 3340TH102UF Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Close 3340-XV-352C Suction drain Valve Closed
seconds seconds
(Open &
Low Flow
2 60
2. Open 3340-XV-354 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
Open
and 2 220
3. Open 3340-XV-352B Suction Valve.
3340-XM- seconds seconds
185.RUN
10 60
4. Start 3340-PU-105.MO1 Start pump. Working
seconds seconds

Table 658: Start Sequence 3340PU105

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-105 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-105-MO1 stopped
The pump stop sequence 3340-PU-105, shall follow the following steps:
TSQST Stop Sequence Table
UN ECPF_3340TH102 EM 3340TH102UF Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-105.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3340-PU-105.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3340-XV-352A Suction Valve. Closed
seconds seconds
2 60
4. Open 3340-XV-352C Suction Drain valve Opened
seconds seconds
2 20
5. Close 3340-XV-354 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-352B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-352B Closed
valve seconds seconds

Table 659: Stop Sequence 3340PU105

The Shutter of the Nuclear Density Meter (3340-DX-358) will open 5 seconds after the pump
3340-PU-105 is operational. The shutter will close when the pump stops.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 529 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

20.2 Engineering Module 2 – 3340TH102_RECIR

20.2.1 Description – 3340TH102_RECIR

The following figure shows the elements that make up the 3340TH102_RECIR equipment
module.
3340TH102_RECIR
Regrind Mill
3340-XV-352E

3340-XV-349
Regrind Cyclone
Feed Density

3340-XV-352D
Thickener
Feed Box
Flush Water

3340-XV-306

3340 – TH – 102
3340-XV-352B

Thickener
Feed Box Fluidisation
Water Tank
3340-LT- 312
LT
PT

3340-PT- 313A
PT

3340-PT- 313B
DC FC
SC
PT

3340357
3340358
3340-DCV-307 3340-PT- 313C 3340352

M DT FT

3340-XV-352A
3340 – PU – 105

FAL
3340-XV-352C
3340354
3340-XV- 354 3340TH102UF
FSL

GSW

Figure 71: Blockflow Control Diagram of the 3340TH102_RECIR System

20.2.2 Unit of Control Modules – 3340TH102_RECIR

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN ECPF_3340TH102 EM 3340TH102_RECIR Sub EM

Tag Service
3340-XV-352E Regrind Feed Valve
3340-XV-352D Bypass Recirculating Valve
3340-XV-349 Regrind Feed Drain Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 530 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 660: List of Unit Controls – 3340TH102_RECIR

20.2.3 Interlocks – 3340TH102_RECIR

T2 Interlock
Tag 3340-XV-352E Description Regrind Feed Valve
ECPF_3340TH10 3340TH102_ Sub
UN EM
2 RECIR EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340 – XV-349 .!CL or Regrind Feed Drain Valve is not closed Time Delay
×
!CLN for a time delay 60 seconds
3340 - XV – 602A.!OP
Both Regrind Cyclone Feed Pump Suction Time Delay
AND ×
Valves are not open for a time delay 30 seconds
3340 - XV – 603A!OP
Bypass Recirculating Valve is open for a Time Delay
3340 – XV-352D.OP ×
time delay 15 seconds

Table 661: List of Interlocks for 3340-XV-352E

T2 Interlock
Tag 3340-XV-352D Description Bypass Recirculating Valve
ECPF_3340TH10 3340TH102_ Sub
UN EM
2 RECIR EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340 - XV –352E.OP or Regrind Feed Valve is open or opening for Time Delay
×
OPN a time delay 5 seconds

Table 662: List of Interlocks for 3340-XV-352D

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 531 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-XV-349 Description Regrind Feed Drain Valve
ECPF_3340TH10 3340TH102_ Sub
UN EM
2 RECIR EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If Regrind Feed Valve is Closed for a time Time Delay


3340 – XV-352 E.CL ×
delay 5 seconds

Table 663: List of Interlocks for 3340-XV-349

20.2.4 Alarms and Process Setpoints – 3340TH102_RECIR

Not Applicable

20.2.5 Binary Messages – 3340TH102_RECIR

Not Applicable
20.2.6 Regulatory Control Loops – 3340TH102_RECIR

Not Applicable

20.2.7 Advanced Control Loops – 3340TH102_RECIR

Not applicable

20.2.8 Sequence Description – 3340PU105

The sequence below tabulates the steps to be completed when changing from directing slurry
from the thickener feed distribution box (3340 – BX – 109) and redirecting it to the regrind mills

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 532 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Regrind Feed Sequence Table


UN ECPF_3340TH102 EM 3340TH102_RECIR Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 20
1. Close 3340-XV-349 Regrind Feed Drain Valve Closed
seconds seconds
Open 2 30
2. Open 3340-XV-352E Regrind Feed Valve
seconds seconds
2 30
3. Close 3340-XV-352D Bypass Recirculating Valve Closed
seconds seconds

Table 664: Regrind Feed Sequence

The sequence below tabulates the steps to be completed when changing from directing slurry
from the regrind mills to the thickener feed distribution box (3340 – BX – 109).
:
TSQST Thickener Recirculation Sequence Table
UN ECPF_3340TH102 EM 3340TH102_RECIR Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 30
1. Open 3340-XV-352D Bypass Recirculating Valve Open
seconds seconds
Closed 2 30
2. Close 3340-XV-352E Regrind Feed Valve
seconds seconds
2 20
3. Open 3340-XV-349 Regrind Feed Drain Valve Closed
seconds seconds

Table 665: Thickener Recirculation Sequence

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 533 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

21.0 UNIDAD: ECPF_3340TH103

Refer to:
MQ14-08-DR-3340-PD1078 Thickener Feed Box
MQ14-08-DR-3340-PD1079 Thickener Feed Box
MQ14-08-DR-3340-PD1080 Thickener Underflow
MQ15-51-TE-3340-GA0601 Settler vendor Control Philosophy

A block flow control diagram is depicted below for the ECPF_3340TH103 system.
3340TH103_RECIR
Regrind Mill
3340-XV-391E

3340-XV-350
Regrind Cyclone
Feed Density

3340-XV-391D
Thickener
Feed Box
Flush Water

3340-XV-308

3340 – TH – 103
3340-XV-391B

Thickener
Feed Box Fluidisation
Water Tank
3340-LT- 314
LT
PT

3340-PT- 315A
PT

3340-PT- 315B
DC FC
SC
PT

3340393
3340394
3340-DCV-309 3340-PT- 315C 3340391

M DT FT

3340-XV-391A
3340 – PU – 108

FAL
3340-XV-391C
3340392
3340-XV- 392 3340TH103UF
FSL

GSW

Figure 72: Blockflow Control Diagram of ECPF_3340TH103

The above control unit is broken into two Engineering Module 1’s with no sub Engineering Module 2’s:
- 3340TH103UF
- 3340TH103_RECIR

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 534 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

21.0.1 Modules of Control ECPF_3340TH103

T1 Control Mod
Sub
UN ECPF_3340TH103 EM
EM
Tag Service
3340-TH-103 Deep Cone Settler
3340-DCV-309 Underflow Density Control Valve
3340-XV-308 Froth Suppression Spray Water Isolation
3340-LIT-314 BED LEVEL MEASUREMENT
3340-PIT-315A BED PRESSURE MEASUREMENT
3340-PIT-315B BED PRESSURE MEASUREMENT
3340-PIT-315C BED PRESSURE MEASUREMENT

Table 666: List of Modules of Control for ECPF_3340TH103

21.0.2 Interlocks – ECPF_3340TH103

T2 Interlock
Tag 3340-DCV-309 Description Underflow Density Control Valve
ECPF_3340TH10 Sub
UN EM
3 EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If thickener underflow pump is not running Delay Time


3340-PU108.!RN ×
for a delay time 30 seconds

Table 667: List of Interlocks for 3340-DCV305

T2 Interlock
Tag 3340-XV-308 Description Froth Suppression Spray Water Isolation
ECPF_3340TH10 Sub
UN EM
3 EM
Failure Position: Interlock
Motor Type Interlock
Keep Last (KL) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 535 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-303C.CL If thickener feed valve is closed ×

Table 668: List of Interlocks for 3340-XV-308

21.0.3 Alarms and Process Setpoints – ECPF_3340TH103

T3 Alarms and Process Setpoints


UN ECPF_3340TH103 EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Typicall
3340 - LIT – y 10.
314 Ultrasonic Settler Mud Bed Level 0 - 100 % 95
Not for
control
3340 - PIT – % of
Mud Bed Pressure Transmitter –
315A 0 - 100 max 0 10
Upper cone
KPa
3340 - PIT – % of
Mud Bed Pressure Transmitter –
315B 0 - 100 max 0 10
Middle cone
KPa
3340 - PIT – % of 0 – 30
Mud Bed Pressure Transmitter –
315C 0 - 100 max (Typical 30
Lower cone
KPa ly 15)

Table 669: Alarms and Process Setpoint ECPF_3340TH103

Each settler has three pressure transmitters (3340- PIT – 311A/B/C, 313A/B/C and 315A/B/C)
located vertically above each other to assess the total solids above each unit’s location. The
following water and maximum pressure values are possible on each PIT, allowing the percentage
of maximum filled to be calculated and displayed to the operator.
Height of Overflow Expected Pressure with Maximum Pressure
Tag Name
Above PIT [m] Water Only [KPa] with Slurry [KPa]6

Lower Cone Pressure


3340- PIT – 315C 10.15 99.5 146.8
Transmitter

Middle Cone Pressure


3340 - PIT – 315B 7.02 68.8 101.5
Transmitter

6
Assumes a maximum compacted density of 1.476 t/m3 (50%mass)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 536 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Upper Cone Pressure


3340- PIT – 315A 5.40 52.9 78.1
Transmitter

Table 670: Settler Pressure Transmitter Solids Calculation Constants

The percentage fill of solids above each transmitter will be calculated and displayed to the control
room operator.
Percent Fill of PIT A = (Actual [KPa] – 52.9 ) / (78.1 – 52.9) × 100%
Percent Fill of PIT B = (Actual [KPa] – 68.8 ) / (101.5 – 68.8) × 100%
Percent Fill of PIT C = (Actual [KPa] – 99.5 ) / (146.8 – 99.5) × 100%
The three separate pressure transmitters are utilised to ensure that no bridging is occurring on
the outlet of each individual transmitter. Consequently, the lowest pressure transmitter (C), should
always contain the greatest quantity of solids fill, followed by (B) and lastly (A). If this is not the
case, then an alarm must alert the operator. Should a high limit be achieved on any of the three
pressure transmitters, then an alarm must alert the operator.
Similarly, a separate ultrasonic level transmitter (3340 – LIT - 310 / 312 / 314) provides an
alternative measurement of the height of the solids mud bed within the settler. Should a high limit
be achieved on this level transmitter, then an alarm must alert the operator, but also the respective
thickener feed valve (3340 - XV – 303A, 303B, 303C) must close.
Once settled at the base of the thickener, solids will quickly compact to a high density and will
require re-fluidisation prior to being pumped from the thickener at a controlled slurry density to
the Regrind Mill circuit. For this to occur, dilution water is injected at a controlled rate into the base
of the thickener via a modulating control valve (3340 - DCV – 305 / 307 / 309).
21.0.4 Binary Messages – ECPF_3340TH103

T4 Binary State Messages


UN ECPF_3340TH103 EM Sub EM
Tag Description OFF ON
3340-LIT-314.H High Solids level in 3340-TH103 × Delay 5 seconds
3340 - PIT – High Solids level in 3340-TH-103
315A.H × Delay 5 seconds
Upper Cone
3340 - PIT – High Solids level in 3340-TH-103
315B.H × Delay 5 seconds
Middle Cone
3340 - PIT – High Solids level in 3340-TH-103
315C.H × Delay 5 seconds
Lower Cone
3340-PIT-315B
>
Bridging of Solids in 3340 – TH – 103 × Delay 5 seconds
3340-PIT315C

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 537 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PIT-315A
>
(3340-PIT315C
Bridging of Solids in 3340 – TH - 103 × Delay 5 seconds
OR
3340-PIT315B)

Table 671: Binary State Messages ECPF_3340TH103

21.0.5 Regulatory Control Loops – ECPF_3340TH103

Once settled at the base of the thickener, solids will quickly compact to a high density and will
require re-fluidisation prior to being pumped from the thickener at a controlled slurry density to
the Regrind Mill circuit. For this to occur, dilution water is injected at a controlled rate into the base
of the thickener via a modulating control valve (3340 - DCV – 305 / 307 / 309).

T5 Regulatory Control Loops


UN ECPF_3340TH103 EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 – 100 Expected
(0% = setpoint 22%
99.5KP = 110 KPa
3340 - PIC – Mud Bed Solids level Pressure
a
315C Controller – Lower cone
100% =
146.8K
Pa)

The underflow pump speed when pumping to the regrind section (see 3340TH103) is adjusted in
order to maintain a relatively low solids level inside the settler.

21.0.6 Advanced Control Loops – ECPF_3340TH103

Not applicable

21.0.7 Sequence Description – ECPF_3340TH103

The settler feed start sequence, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 538 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN ECPF_3340TH103 EM Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
10 60
1. Start 3340-PU-109.MO1 Start pump. Working
seconds seconds
Open Feed Box Froth 2 60
2. Open 3340 – XV – 301A Open
suppression isolation valve seconds seconds
Open Flush Water Valve for 30 2 60
3. Open 3340 - XV – 302C Open
seconds seconds seconds
2 60
4. Close 3340 - XV – 302C Close Flush Water Valve Open
seconds seconds
2 60
5. Open 3340 - XV – 303C Open Thickener Feed Valve Open
seconds seconds
2 60
6. Open 3340 - XV – 308 Settler Froth Suppression Valve Open
seconds seconds

Table 672: Start Sequence ECPF_3340TH103

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-109 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-109-MO1 stopped
The settler feed stop sequence, shall follow the following steps:
TSQST Stop Sequence Table
UN ECPF_3340TH103 EM Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 20
1. Close 3340 - XV – 308 Settler Froth Suppression Valve Closed
seconds seconds
2 20
2. Close 3340 - XV – 303C Thickener Feed Valve Closed
seconds seconds
3. Proceed only if all three thickener feed valves (3340-XV-303A AND 3340-XV - 303B AND 3340-XV – 303C) are closed
Open Feed Box Froth 2 20
4. Close 3340 – XV – 301A Close
suppression isolation valve seconds seconds
10 60
5. Stop 3340-PU-109.MO1 Stop Pump Stopped
seconds seconds

Table 673: Stop Sequence ECPF_3340TH103

21.1 Engineering Module 2 – 3340TH103UF

21.1.1 Description – 3340TH103UF

The following figure shows the elements that make up the 3340TH103UF equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 539 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340TH103_RECIR
Regrind Mill
3340-XV-391E

3340-XV-350
Regrind Cyclone
Feed Density

3340-XV-391D
Thickener
Feed Box
Flush Water

3340-XV-308

3340 – TH – 103
3340-XV-391B

Thickener
Feed Box Fluidisation
Water Tank
3340-LT- 314
LT
PT

3340-PT- 315A
PT

3340-PT- 315B
DC FC
SC
PT

3340393
3340394
3340-DCV-309 3340-PT- 315C 3340391

M DT FT

3340-XV-391A
3340 – PU – 108

FAL
3340-XV-391C
3340392
3340-XV- 392 3340TH103UF
FSL

GSW

Figure 73: Blockflow Control Diagram of the 3340TH103UF System

21.1.2 Unit of Control Modules – 3340TH103UF

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN ECPF_3340TH103 EM 3340TH103UF Sub EM

Tag Service
3340-PU-108 Thickener Underflow Pump 3
3340-TE-391 Underflow Pump Thermistor
3340-DIT-394 DENSIDAD UNDERFLOW
3340-FSL-354 GLAND SEAL WATER
3340-XV-391A SUCTION Valve
3340-XV-391C Suction Drain Valve
3340-XV-391B FLUSH WATER TO Suction Pipeline
3340-FIT-393 SONAR FLOW TRANSMITTER
3340-XV-392 GLAND SEAL WATER

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 540 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-DX-394 DENSIDAD UNDERFLOW SETTLER Isolator

Table 674: List of Unit Controls – 3340TH103UF

21.1.3 Interlocks – 3340TH103UF

T2 Interlock
Tag 3340-XV-391A Description Suction valve
ECPF_3340TH10 3340TH103U Sub
UN EM
3 F EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-391C.OP Suction drain valve open


OR OR ×
3340-XV-391C.OPNG Suction drain valve opening
3340-PU-108.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-391A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-391A.OPNG)

Table 675: List of Interlocks for 3340-XV-391A

T2 Interlock
Tag 3340-XV-391B Description Suction Flush Water Valve
ECPF_3340TH10 3340TH103U Sub
UN EM
3 F EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 541 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 676: List of Interlocks for 3340-XV-391B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Tag 3340-XV-391C Description Suction Drain Water Valve
ECPF_3340TH10 3340TH103U Sub
UN EM
3 F EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 677: List of Interlocks for 3340-XV-391C

T2 Interlock
Tag 3340 – PU – 108 Description Thickener Underflow Pump
ECPF_3340TH10 3340TH103U Sub
UN EM
3 F EM
Interlock
Motor Type VFD Intlck_3340BB_SL_01
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-392 !OP ×
If gland seal water valve not open and
AND Note 1
pump is running
3340-PU-108.MO1.Run
3340-FSL-354.ACT ×
Flow switch has a low flow alarm for a Time Delay
AND
time delay and pump is running 300 seconds
3340-PU-108-MO1.Run
3340-FSL-354.ACT Flow switch has a low flow alarm ×
3340-XV-391A CL ×
OR CLN Suction valve Is closed or closing and Time Delay
AND pump is running for a time delay 10 seconds
3340-PU-108-MO1.Run
3340-XV-391C OP OR × Debounce
Suction drain valve is open or opening
OPN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 542 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-FIT-393.LL AND ×
Slurry flowrate is Low Low and pump is Time Delay
3340-PU-108-
running 600 seconds
MO1.RUN
3340 - XV–352E.CL or Both Regrind Feed Valve (3340 – XV-
CLN 391E)
3340 - XV–352D.CL or AND Time Delay
×
CLN Bypass Valve (3340 - XV–352D) 60 seconds
AND Are closed or closing and pump is running
3340-PU-108-MO1.Run for a time delay
×
3340 - TE - 352 Pump Thermistor alarm
Instrument Air Pressure (3340-PIT-675) is × Time Delay
3340-PIT-675.LL
Low Low for a time delay 10 seconds
Either ×
3340-PIT-670.LL
3340-PIT-670
OR
OR
3340-PIT-671.LL Time Delay
3340-PIT-671
OR 60 seconds
OR
3340-PIT-678.LL
3340-PIT-678
is Low Low for a time delay
CPF Make-Up Water Pressure 3720-PIT- × Time Delay
3720-PIT-116.LL
116 is Low Low for a time delay 180 seconds
Fluidisation Water pressure (3340-PIT- × Delay time
3340-PIT-647.LL
647) is low low for a delay time 60 seconds
Flush Water Pressure (3340-PIT-648) is × Delay time 5
3340-PIT-648.LL
not low low for a delay time minutes
3340-XV-303A CL ×
OR CLN All thickener feed valves are closed or
AND closing
3340-XV-303B CL (3340-XV-303A
OR CLN AND Delay time 3
AND 3340-XV-303B minutes
3340-XV-303C CL AND
OR CLN 3340-XV-303C)
AND and pump is running for a time delay
3340-PU-108-MO1.Run
Gland seal water pressure (3340-PIT-656) × Delay time
3340-PIT-656.LL
is Low Low for a delay time 60 seconds
Boosted gland seal water pressure (3340- × Delay time
3340-PIT-659.LL
PIT-659) is Low Low for a delay time 60 seconds

Table 678: List of Interlocks for 3340 – PU - 108

Additional interlocks have been included for this pump in order to prevent solids from being
pumped downstream when plant operations are becoming unstable and there is a likelihood of a
plant crash stop. Stopping the pump timeously will reduce solids loading in downstream pipelines
and reduce risk of blockages / spillage during a crash stop.

T2 Interlock
Densitometer Nuclear Source Isolation
Tag 3340-DX-394 Description
Shutter
ECPF_3340TH10 3340TH103U Sub
UN EM
3 F EM
Interlock Intlck_OBTURADOR_DENSI
Motor Type
Type METRO_01

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 543 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-108.!RUN If the pump is not running ×

Table 679: List of Interlocks for 3340-DX-394

T2 Interlock
Tag 3340-XV-392 Description Pump Gland Seal Water Valve
ECPF_3340TH10 3340TH103U Sub
UN EM
3 F EM
Failure Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-108.!RUN If the pump is not running ×

Table 680: List of Interlocks for 3340-XV-392

21.1.4 Alarms and Process Setpoints – 3340TH103UF

T3 Alarms and Process Setpoints


UN ECPF_3340TH103 EM 3340TH103UF Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340-FIT-393 Pump Flowmeter 0 - 1000 m3/hr 155 90
3340-DIT-394 Pump densitometer 1.0 – 2.0 t/m3 1.60
3340-FSL-354 Pump Gland Seal Water Flow
0 – 4.0 m3/hr 1.58
switch

Table 681: Alarms and Process Setpoint 3340TH103UF

The alarms associated with the Density transmitter, as well as the flow measurement should be
inhibited when pump 3340-PU-108 is not running.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 544 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

By combining the flow transmitter and densitometer readings, a totalized mass flow to the regrind
mills will be calculated based upon the following formulae:
𝑆𝐺
𝑇 = 𝑉𝑝 (𝑑𝑝 − 1) × )
𝑆𝐺 − 1
Where: T = Dry Solids Mass [tph]
Vp = Volumetric Flowrate [m3/hr] 3340-FIT-393
dp = Slurry density [t/m3] 3340-DIT-394
SG = Solids Specific Gravity = 2.82 t/m3
Solids mass pumped to the regrind mills will be summed with the other to settlers underflow
discharges and totalized on an hour, shift, day and monthly basis when the following is true:
a) 3340 – XV-391E is open, and
b) 3340 – PU-108 is running.
This mass flow combined with the mass flows from the other two settlers, will be visible to the
control room operator. Together with the concentrate product mass returned to concentrator flow
rate calculation, this value will provide input into the calculation of the mill recirculating load (see
section later).
21.1.5 Binary Messages – 3340TH103UF

T4 Binary State Messages


UN ECPF_3340TH103 EM 3340TH103UF Sub EM
Tag Description OFF ON

3340-ZSC-394 LINE RADIOACTIVE SOURCE


× Note 2
PUMP 3340-PU-108 CLOSED
3340-ZSO-394 LINE RADIOACTIVE SOURCE
× Note 1
PUMP 3340-PU-108 OPEN

Table 682: Binary State Messages 3340TH103UF

Note:
4) Condition should alarm, if the valve is open 5 seconds after the pump 3340-PU-108 has
stopped.
5) Condition should alarm, if the valve is closed, 5 seconds after the pump 3340-PU-108 is
running. If this condition occurs, calculation of the mass flowrate and average value % of
solids should not occur.
6) An alarm should be provided when a nuclear density meter reading (tag 3340-DIT-394)
provides a difference in measured value greater than 10%, under normal operating
conditions. Alarm will not be triggered when only one pump is operating, when the pump
is under start-up conditions.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 545 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

21.1.6 Regulatory Control Loops – 3340TH103UF

T5 Regulatory Control Loops


UN ECPF_3340TH103 EM 3340TH103UF Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
3340 – FIC- 63 - 100 % m3/hr 155 - Note 2
Thickener Underflow Pump Flowmeter
393 1000
0 - 100 % t/m3 1.0 – Note 1
3340 – DIC- Thickener Underflow Pump 2.0 Expected
394 densitometer setpoint 1.48
t/m3.

Table 683: Regulatory Control Loops for 3340TH103UF

Note 1: Controller will be disabled (tracking action), if pump is stopped


Note 2 The thickener underflow pump speed is adjusted to achieve a flowrate setpoint.
The setpoint will be placed on minimum value when the underflow is recirculating
to the thickener feed (i.e. 3340 – XV-391E closed or closing).
When pumping underflow to the Regrind Milling circuit (i.e. 3340 – XV-391E open
or opening), the setpoint is adjusted to maintain a solids level in the thickener as
measured by 3340 – PIT-315C.
While the slurry is being pumped to the regrind mills, the maximum flowrate shall
be limited by the regrind cyclone feed pump maximum density limit (3340 – DIT -
607).

21.1.7 Advanced Control Loops – 3340PU108

Not applicable

21.1.8 Sequence Description – 3340PU108

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. The pump start sequence 3340-PU-108, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 546 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN ECPF_3340TH103 EM 3340TH103UF Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Close 3340-XV-391C Suction drain Valve Closed
seconds seconds
(Open &
Low Flow
2 60
2. Open 3340-XV-392 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
Open
and 2 220
3. Open 3340-XV-391B Suction Valve.
3340-XM- seconds seconds
185.RUN
10 60
4. Start 3340-PU-108.MO1 Start pump. Working
seconds seconds

Table 684: Start Sequence 3340PU108

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-108 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-108-MO1 stopped
The pump stop sequence 3340-PU-108, shall follow the following steps:
TSQST Stop Sequence Table
UN ECPF_3340TH103 EM 3340TH103UF Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-108.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3340-PU-108.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3340-XV-391A Suction Valve. Closed
seconds seconds
2 60
4. Open 3340-XV-391C Suction Drain valve Opened
seconds seconds
2 20
5. Close 3340-XV-392 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-391B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-391B Closed
valve seconds seconds

Table 685: Stop Sequence 3340PU108

The Shutter of the Nuclear Density Meter (3340-DX-394) will open 5 seconds after the pump
3340-PU-108 is operational. The shutter will close when the pump stops.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 547 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

21.2 Engineering Module 2 – 3340TH103_RECIR

21.2.1 Description – 3340TH103_RECIR

The following figure shows the elements that make up the 3340TH103_RECIR equipment
module.
3340TH103_RECIR
Regrind Mill
3340-XV-391E

3340-XV-350
Regrind Cyclone
Feed Density

3340-XV-391D
Thickener
Feed Box
Flush Water

3340-XV-308

3340 – TH – 103
3340-XV-391B

Thickener
Feed Box Fluidisation
Water Tank
3340-LT- 314
LT
PT

3340-PT- 315A
PT

3340-PT- 315B
DC FC
SC
PT

3340393
3340394
3340-DCV-309 3340-PT- 315C 3340391

M DT FT

3340-XV-391A
3340 – PU – 108

FAL
3340-XV-391C
3340392
3340-XV- 392 3340TH103UF
FSL

GSW

Figure 74: Blockflow Control Diagram of the 3340TH103_RECIR System

21.2.2 Unit of Control Modules – 3340TH103_RECIR

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN ECPF_3340TH103 EM 3340TH103_RECIR Sub EM

Tag Service
3340-XV-391E Regrind Feed Valve
3340-XV-391D Bypass Recirculating Valve
3340-XV-350 Regrind Feed Drain Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 548 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 686: List of Unit Controls – 3340TH103_RECIR

21.2.3 Interlocks – 3340TH103_RECIR

T2 Interlock
Tag 3340-XV-391E Description Regrind Feed Valve
ECPF_3340TH10 3340TH103_ Sub
UN EM
3 RECIR EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340 – XV-350 .!CL or Regrind Feed Drain Valve is not closed Time Delay
×
!CLN for a time delay 60 seconds
3340 - XV – 602A.!OP
Both Regrind Cyclone Feed Pump Suction Time Delay
AND ×
Valves are not open for a time delay 30 seconds
3340 - XV – 603A!OP
Bypass Recirculating Valve is open for a Time Delay
3340 – XV-391D.OP ×
time delay 15 seconds

Table 687: List of Interlocks for 3340-XV-391E

T2 Interlock
Tag 3340-XV-391D Description Bypass Recirculating Valve
ECPF_3340TH10 3340TH103_ Sub
UN EM
3 RECIR EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340 - XV –352E.OP or Regrind Feed Valve is open or opening for Time Delay
×
OPN a time delay 5 seconds

Table 688: List of Interlocks for 3340-XV-391D

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 549 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-XV-350 Description Regrind Feed Drain Valve
ECPF_3340TH10 3340TH103_ Sub
UN EM
3 RECIR EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If Regrind Feed Valve is Closed for a time Time Delay


3340 – XV-391 E.CL ×
delay 5 seconds

Table 689: List of Interlocks for 3340-XV-350

21.2.4 Alarms and Process Setpoints – 3340TH103_RECIR

Not Applicable

21.2.5 Binary Messages – 3340TH103_RECIR

Not Applicable
21.2.6 Regulatory Control Loops – 3340TH103_RECIR

Not Applicable

21.2.7 Advanced Control Loops – 3340TH103_RECIR

Not applicable

21.2.8 Sequence Description – 3340PU108

The sequence below tabulates the steps to be completed when changing from directing slurry
from the thickener feed distribution box (3340 – BX – 109) and redirecting it to the regrind mills

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 550 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Regrind Feed Sequence Table


UN ECPF_3340TH103 EM 3340TH103_RECIR Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 20
1. Close 3340-XV-350 Regrind Feed Drain Valve Closed
seconds seconds
Open 2 30
2. Open 3340-XV-391E Regrind Feed Valve
seconds seconds
2 30
3. Close 3340-XV-391D Bypass Recirculating Valve Closed
seconds seconds

Table 690: Regrind Feed Sequence

The sequence below tabulates the steps to be completed when changing from directing slurry
from the regrind mills to the thickener feed distribution box (3340 – BX – 109).
:
TSQST Thickener Recirculation Sequence Table
UN ECPF_3340TH103 EM 3340TH103_RECIR Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 30
1. Open 3340-XV-391D Bypass Recirculating Valve Open
seconds seconds
Closed 2 30
2. Close 3340-XV-391E Regrind Feed Valve
seconds seconds
2 20
3. Open 3340-XV-350 Regrind Feed Drain Valve Closed
seconds seconds

Table 691: Thickener Recirculation Sequence

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 551 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

22.0 UNIDAD: RMCPF_3340BX103

Refer to:
MQ14-08-DR-3340-PD1081 Regrind Cyclone Cluster
MQ14-08-DR-3340-PD1084 Regrind Cyclone Pumping
MQ14-08-DR-3340-PD1085 Regrind Cyclone Pumps (Vendor)
MQ14-08-DR-3340-PD1086 Product Pumping
MQ15-720-IOM-3340-ME0002 Sampler and Analyser Operating Manual
MQ15-718-TE-3340-IN0001 Vendor Regrind Cyclone Control Philosophy
MQ15-718-TE-3340-IN0101 Vendor Large Slurry Pump Control Philosophy
A block flow control diagram is depicted below for the RMCPF_3340BX103 system.
3340-PT-364
3340CY110
PT
3340-SA-101
Product Return Vendor Package 3340-AY-101
Density Control

3340-CY-110
Flush Water Concentrate
Vendor Package Return

Mill 1 Product

Mill Feed
Mill 2 Product Distributor

3340PU106_107

3340-LCV-601
3340606
FC

FT

Process Water
3340-XV-602B

Make-Up
LC
3340601
Settler Feed
3340607

Settler U/Flow
1, 2 & 3
DC
DT

Flowrate Control

LT SC
3340602
3340-XV-602D
3340-XV-602A M

3340-BX-103
Vendor Package
3340-XV-603D

3340 – PU – 106
3340-XV-602C FAL
3340-XV-602C

3340604

3340-XV-604
FSL

SC
3340-XV-603B

3340603
LAH 3340PU173
3340PU106 Vendor Package 3340608
M
M
LSH
TE

3340-XV-603A
3340 – PU - 107
FAL 3340 – PU – 173
3340-XV-603C 3340605
3340-XV-603C

GSW 3340-XV-605 LAH 3340PU175


FSL 3340609

M
3340PU107 LSH Tails Launder
TE

3340 – PU – 175

Figure 75: Blockflow Control Diagram of RMCPF_3340BX103

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 552 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The above control unit is broken into four Engineering Module 1’s with one module having two sub
Engineering Module 2’s:
- 3340CY110
- 3340PU106_107
o 3340PU106
o 3340PU107
- 3340PU173
- 3340PU175
22.0.1 Modules of Control RMCPF_3340BX103

T1 Control Mod
Sub
UN RMCPF_3340BX103 EM
EM

Tag Service
3340-SA-101 Primary Product Sampler
3340-AY-101 Primary Product Analyzer
3340-BX-103 Regrind Cyclone Feed Box
3340-LIT-601 LEVEL INDICATOR TRANSMITTER
3340-LCV-600A Level Control Valve

Table 692: List of Modules of Control for RMCPF_3340BX103

22.0.2 Interlocks – RMCPF_3340BX103

T2 Interlock
Tag 3340-LCV-600A Description Level Control Valve
RMCPF_3340BX
UN EM Sub EM
103
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 693: List of Interlocks for 3340-LCV-600A

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 553 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-SA-101 Description Primary Product Sampler
RMCPF_3340BX
UN EM Sub EM
103
Interlock
Motor Type Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Refer to vendor Control Philosophy MQ15-720-IOM-3340-ME0002. Start and stop signal derived from the start/stop of both the
Regrind Cyclone feed pumps 3340-PU-106 and 3340-PU-107
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 694: List of Interlocks for 3340-SA-101

Note that the Product Sampler (3340 – SA – 101) and Product Analyser (3340 – AY – 101) are all contained
within the same vendor package.
22.0.3 Alarms and Process Setpoints – RMCPF_3340BX103

T3 Alarms and Process Setpoints


UN RMCPF_3340BX103 EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-LIT-601 Typical
0 - 100 % 95 10
LEVEL INDICATOR TRANSMITTER 50
3340-SA-101
And Product Sampler and Analyser Refer to vendor control philosophy
3340-AY-101

Table 695: Alarms and Process Setpoint RMCPF_3340BX103

22.0.4 Binary State Messages – RMCPF_3340BX103

There are no binary state messages for this section


22.0.5 Regulatory Control Loops – RMCPF_3340BX103

T5 Regulatory Control Loops


UN RMCPF_3340BX103 EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 - 100 10 - 100 Expected
Regrind Cyclone Feed Pump Box
3340-LIC-601 setpoint 50%
Level Controller
tank level

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 554 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 696: Regulatory Control Loops for RMCPF_3340BX103

22.0.6 Advanced Control Loops – RMCPF_3340BX103

There are no advanced control loops for this section.

22.0.7 Description

The regrind mill product gravitates into the Regrind Cyclone Feed Box (3340 – BX – 103) where
it is diluted with process water and pumped by a running / standby variable speed pump (3340 –
PU – 106 / 107) at a controlled density to the Regrind Cyclone Cluster (3340 – CY – 110).
The slurry level in the box is controlled to a selected setpoint by varying the percentage opening
of the sumps level control valve (3340 LCV – 600A).
The Product Sampler (3340 – SA – 101) and Analyser (3340 – AY – 101) are contained within
the same vendor package item. The vendor control philosophy shall apply. The unit provides an
online information of specific elemental analysis which confirms to the operator the online real
time estimate of the CPF product grade. A physical, metallurgical grade quality sample is also
obtained from the sampler over a period of time, facilitating laboratory analysis and weekly
analyser calibration. The sampler and analyser are equipped with their own PLC controller. The
start / stop signal will be provided by either Regrind Cyclone Feed Pump (3340 – PU – 106 / 107)
running signals being healthy. Should the product sampler and analyser be unhealthy, no
interlocks will prevent production from continuing.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 555 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

22.1 Engineering Module– 3340PU106

22.1.1 Description – 3340PU106

The following figure shows the elements that make up the 3340PU106 equipment module.
3340-PT-364
3340CY110
PT
3340-SA-101
Product Return Vendor Package 3340-AY-101
Density Control

3340-CY-110
Flush Water Concentrate
Vendor Package Return

Mill 1 Product

Mill Feed
Mill 2 Product Distributor

3340PU106_107

3340-LCV-601
3340606
FC

FT
Process Water
3340-XV-602B

Make-Up
LC
3340601
Settler Feed

3340607
Settler U/Flow
1, 2 & 3

DC
DT
Flowrate Control

LT SC
3340602
3340-XV-602D
3340-XV-602A M

3340-BX-103
Vendor Package
3340-XV-603D

3340 – PU – 106
3340-XV-602C FAL
3340-XV-602C

3340604

3340-XV-604
FSL

SC
3340-XV-603B

3340603
LAH 3340PU173
3340PU106 Vendor Package 3340608
M
M
LSH
TE

3340-XV-603A
3340 – PU - 107
FAL 3340 – PU – 173
3340-XV-603C 3340605
3340-XV-603C

GSW 3340-XV-605 LAH 3340PU175


FSL 3340609

M
3340PU107 LSH Tails Launder
TE

3340 – PU – 175

Figure 76: Blockflow Control Diagram of the 3340PU106 System

22.1.2 Unit of Control Modules – 3340PU106

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN RMCPF_3340BX103 EM 3340PU106 Sub EM

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 556 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag Service
3340-PU-106 Regrind Hydrocyclone Feed Pump 1
3340-PU-106-LU1FA1 Regrind Hydrocyclone Feed Pump Lube Oil Fan
3340-PU-106-LU1HE1 Regrind Hydrocyclone Feed Pump Lube Heater 1
3340-PU-106-LU1HE2 Regrind Hydrocyclone Feed Pump Lube Heater 2
3340-PU-106-MO1FA1 Regrind Hydrocyclone Feed Pump 1 Motor Fan 1
3340-PU-106-MO1FA2 Regrind Hydrocyclone Feed Pump 1 Motor Fan 2
3340-PU-106-MO1FA3 Regrind Hydrocyclone Feed Pump 1 Motor Fan 3
3340-DIT-607 Regrind Cyclone Feed Density Transmitter
3340-FSL-604 Gland Seal Water Flow switch
3340-XV-602D DISCHARGE ISOLATION VALVE OF SLURRY PUMP 3340-PU-106
3340-XV-602A SUCTION VALVE OF SLURRY PUMP 3340-PU-106
3340-XV-602B FLUSH WATER VALVE TO PIPELINE
3340-XV-602C Suction Drain Valve
3340-FIT-606 Regrind Cyclone Feed Flow Transmitter
3340-VT-602C1/2 VIBRATION TRANSMITTER 3340-PU-106
3340-VT-602C3/4 VIBRATION TRANSMITTER 3340-PU-106
3340-TT-602B3/4 TEMPERATURE TRANSMITTER 3340-PU-106
3340-TT-602B1/2 TEMPERATURE TRANSMITTER 3340-PU-106
3340-TT-602A2 TEMPERATURE TRANSMITTER 3340-PU-106
3340-TT-602A1 TEMPERATURE TRANSMITTER 3340-PU-106
3340-VT-602B1/2 VIBRATION TRANSMITTER 3340-PU-106
3340-VT-602B3/4 VIBRATION TRANSMITTER 3340-PU-106
3340-TT-602B5 TEMPERATURE TRANSMITTER 3340-PU-106
3340-LSL-602B LEVEL SWITCH LOW 3340-PU-106
3340-PSL-602B PRESSURE SWITCH LOW 3340-PU-106
3340-XV-604 Gland Seal Water Valve
3340-DX-607 DENSITY SOURCE ISOLATION 3340-PU-106

Table 697: List of Unit Controls – 3340PU106

22.1.3 Interlocks – 3340PU106

T2 Interlock
Tag 3340-XV-602A Description Suction valve
RMCPF_3340BX Sub
UN EM 3340PU106
103 EM
Failure Position: Interlock
Motor Type Interlock
Keep Last (KL) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 557 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-602C.OP Suction drain valve open


OR OR ×
3340-XV-602C.OPNG Suction drain valve opening
3340-PU-106.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-602A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-602A.OPNG)

Table 698: List of Interlocks for 3340-XV-602A

T2 Interlock
Tag 3340-XV-602B Description Suction Flush Water Valve
RMCPF_3340BX Sub
UN EM 3340PU106
103 EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 699: List of Interlocks for 3340-XV-602B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Tag 3340-XV-602C Description Suction Drain Water Valve
RMCPF_3340BX Sub
UN EM 3340PU106
103 EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 558 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 700: List of Interlocks for 3340-XV-602C

T2 Interlock
Tag 3340 – PU – 106 Description Regrind Cyclone Feed Pump 1
RMCPF_3340BX Sub
UN EM 3340PU106
103 EM
Interlock
Motor Type VFD (Multiple) Intlck_3340BB_SL_01
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. Note 1. MQ15-718-TE-3340-IN0101


3340-XV-604 !OP ×
If gland seal water valve not open and
AND Note 1
pump is running
3340-PU-106.MO1.Run
3340-FSL-604.ACT × Note 1
Flow switch has a low flow alarm for a
AND Time Delay
time delay and pump is running
3340-PU-106-MO1.Run 300 seconds
3340-FSL-604.ACT Flow switch has a low flow alarm × Note 1
3340-XV-602A CL ×
Note 1
OR CLN Suction valve is closed or closing and
Time Delay
AND pump is running for a time delay
10 seconds
3340-PU-106-MO1.Run
× Note 1
3340-XV-602C. OP OR
Suction drain valve is open or opening Debounce
OPN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-602D !OP × Note 1
If discharge valve not open and pump is
AND Time Delay
running for a time delay
3340-PU-106.MO1.Run 30 seconds
×
3340-XV-603D !CL If alternate discharge valve not closed Note 1
3340-FIT-606.LL AND × Note 1
Slurry flowrate is Low Low and pump is
3340-PU-106- Time Delay
running
MO1.RUN 600 seconds
3340-XV- × Note 1
Number of Crossflow Feed Isolation
365.V_OPEN_HLIM Time Delay
Valves available < 6
(3340-XV-365 A thru N) 600 seconds

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 559 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340 XV – 612A !OP Both 1st stage conc return pump Note 1
AND suction valves are not open for a time × Time Delay
3340 XV - 613A !OP delay 15 seconds
3340 – MI – 101- Regrind Mill 1 is not running
AND Note 1
MO1.!Run
× Time Delay
AND 3340 ZY – 370 is discharging slurry
60 seconds
3340 ZY –370 to Mill 1 to mill 1 for a time delay
3340 – MI – 102- Regrind Mill 2 is not running
AND Note 1
MO1.!Run
× Time delay
AND 3340 ZY – 370 is discharging slurry
60 seconds
3340 ZY –370 to Mill 2 to mill 2 for a time delay
3340 – MI – 101-MO1 Both Regrind Mills
!Run 3340 – MI – 101
AND AND × Note 1
3340 – MI – 102 – MO1 3340 – MI – 102
!Run Are not running

Table 701: List of Interlocks for 3340 – PU - 106

Note 1 On stopping 3340 – PU – 106, its gearbox lubrication cooling and heating system
may continue to run. Refer to vendor functional specification

T2 Interlock
DISCHARGE ISOLATION VALVE OF
Tag 3340-XV-602D Description
SLURRY PUMP
RMCPF_3340BX Sub
UN EM 3340PU106
103 EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If Regrind Cyclone Feed Pump 2 Delay time


3340 XV- 603D.!CL ×
discharge valve is not closed 15 seconds
Regrind Cyclone Feed Pump 1 has not Time Delay
3340 – PU – 106 .!RN ×
run for a time delay 10 seconds

Table 702: List of Interlocks for 3340-XV-602D

T2 Interlock
Regrind Cyclone Feed Pump
Tag 3340-DX-607 Description Densitometer Nuclear Source Isolation
Shutter

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 560 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

RMCPF_3340BX Sub
UN EM 3340PU106
103 EM
Interlock Intlck_OBTURADOR_DENSI
Motor Type
Type METRO_01

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-106.!RUN
If both Regrind cyclone feed pumps are
AND ×
not running
3340-PU-107 !RUN

Table 703: List of Interlocks for 3340-DX-607

T2 Interlock
Regrind Cyclone Feed Pump 1 Gland
Tag 3340-XV-604 Description
Seal Water Valve
RMCPF_3340BX Sub
UN EM 3340PU106
103 EM
Failure Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-106.!RUN If the pump is not running ×

Table 704: List of Interlocks for 3340-XV-604

22.1.4 Alarms and Process Setpoints – 3340PU106

T3 Alarms and Process Setpoints


UN RMCPF_3340BX103 EM 3340PU106 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Refer to vendor control philosophy for pump specific Alarms and Process Setpoints MQ15-718-TE-3340-IN0101
3340 FSL – Regrind Cyclone Feed Pump
604 0 - 15 m3/hr 7.9
GSW flow switch 1
3340 FIT – Regrind Cyclone Feed Pump
606 0 - 5000 m3/hr 1600 900 700
Flowmeter

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 561 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340 DIT – Regrind Cyclone Feed Pump


607 1.0 – 2.0 t/m3 1.62 1.635
densitometer

Table 705: Alarms and Process Setpoint 3340PU106

The alarms associated with the Density transmitter, as well as the flow measurement should be
inhibited when both Regrind Cyclone Feed Pumps are not running.
22.1.5 Binary Messages – 3340PU106

T4 Binary State Messages


UN RMCPF_3340BX103 EM 3340PU106 Sub EM
Tag Description OFF ON

3340-ZSC-607 LINE RADIOACTIVE SOURCE


× Note 2
CYCLONE 3340-CY-110 CLOSED
3340-ZSO-607 LINE RADIOACTIVE SOURCE
× Note 1
CYCLONE 3340-CY-110 OPEN

Table 706: Binary State Messages 3340PU106

Note:
1) Condition should alarm, if the valve is open 5 seconds after both Regrind Cyclone Feed
Pumps have stopped.
2) Condition should alarm, if the valve is closed, 5 seconds after both Regrind Cyclone Feed
Pumps are running. If this condition occurs, calculation of the mass flowrate and average
value % of solids should not occur.
3) An alarm should be provided when a nuclear density meter reading (tag 3340-DIT-607)
provides a difference in measured value greater than 10%, under normal operating
conditions. Alarm will not be triggered when only one pump is operating, when the pump
is under start-up conditions.
22.1.6 Regulatory Control Loops – 3340PU106

T5 Regulatory Control Loops


UN RMCPF_3340BX103 EM 3340PU106 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % % 0 - 100 1.00 – Expected
Regrind Cyclone Feed Pump
3340 DC - 607 1.635 setpoint 1.62
densitometer
t/m3. Note 1
75 - 100 % t/m3 1.00 – 1.00 – Expected
Regrind Cyclone Feed Pump
3340 FC - 606 2.00 2.00 setpoint 1.24
Flowmeter
t/m3. Note 2

Table 707: Regulatory Control Loops for 3340PU106

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 562 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note 1 Density controlled by manipulating the flowrate setpoint of the three Settler Underflow
Pumps (3340 FC – 355/357/393).

Note 2 The flowrate setpoint is adjusted in order to control to the operating concentrate return
density setpoint. (3340 DC – 381 or 3340 DC – 383). Flowrate may not reduce below the
minimum flow value specified. Flowrate is adjusted by manipulating pump speed.

Note 3: Controller provides the setpoint to the one operating Regrind Cyclone Feed Pump.
It will be disabled (tracking action), if both pumps are is stopped.
The regrind cyclone feed flowrate setpoint is adjusted to achieve a final concentrate product return
slurry solids concentration to the Papajuane concentrator of 30%mass. If this concentrate return
density (3340 DIT-381 / 383) is too high, the regrind cyclone feed flowrate (3340 FIT – 606)
setpoint will increase. This will speed up the variable speed regrind cyclone feed pump and vice
versa. At all times however, a minimum flowrate level shall be maintained in the regrind cyclone
feed line to prevent any risk of pipeline sedimentation blockage.
Slurry density is also measured (334-DIT-607) for mass balancing purposes. Should this density
rise above a maximum limit, the new mill feed from the thickener underflow pumps will reduce
(see Thickener/Settler underflow pump control description).
By combining the flow transmitter and densitometer readings, a totalized mass flow in the regrind
cyclone feed pipeline will be calculated based upon the following formulae:
𝑆𝐺
𝑇 = 𝑉𝑝 (𝑑𝑝 − 1) ×
(𝑆𝐺 − 1)
Where: T = Dry Solids Mass [tph]
Vp = Volumetric Flowrate [m3/hr] 3340 FIT – 606
Dp = Slurry density [t/m3] (334-DIT-607)
SG = Solids Specific Gravity = 2.82 t/m3
Solids mass pumped to the regrind cyclones will be totalized on an hour, shift, day and monthly
basis and will be visible to the control room operator. Mass flow will only be calculated/totalised
when either of the two regrind cyclone feed pumps are running.
This, together with the thickener underflow mass flow rate calculation will provide input into the
calculation of the mill recirculating load (see thickener underflow pump control description).
𝑇 𝐶𝑦𝑐𝑙𝑜𝑛𝑒 𝐹𝑒𝑒𝑑
𝑀𝑖𝑙𝑙 𝑅𝑒𝑐𝑖𝑟𝑐𝑢𝑙𝑎𝑡𝑖𝑛𝑔 𝐿𝑜𝑎𝑑 =
(𝑇 𝑇ℎ𝑖𝑐𝑘𝑒𝑛𝑒𝑟 𝑈𝑛𝑑𝑒𝑟𝑓𝑙𝑜𝑤)
Where:
TCyclone Feed = Regrind Cyclone dry solids mass flow [tph]
TThickener Underflow = Thickener underflow dry solids mass flow [tph] when directed to
mills.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 563 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The mill recirculating load will be logged on an hour, shift, day and monthly basis and will be
visible to the control room operator.

22.1.7 Advanced Control Loops – 3340PU106

Not applicable

22.1.8 Sequence Description – 3340PU106

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. The pump start sequence 3340-PU-106, shall follow the following steps:
TSQST Start Sequence Table
UN RMCPF_3340BX103 EM 3340PU106 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Close 3340-XV-602C Suction drain Valve Closed
seconds seconds
(Open &
Low Flow
2 60
2. Open 3340-XV-604 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
2 120
3. Open 3340-XV-602D Discharge Valve Open
seconds seconds
2 120
4. Open 3340-XV-602B Suction Valve. Open
seconds seconds
3340-PU-106-LU1FA1
3340-PU-106-LU1HE1
Start Pump lubrication
3340-PU-106-LU1HE2 10 120
5. Start sequences. Refer to vendor
3340-PU-106-MO1FA1 seconds seconds
functional specification.
3340-PU-106-MO1FA2
3340-PU-106-MO1FA3
Start pump. Refer to vendor 10 60
6. Start 3340-PU-106.MO1 Working
functional specification. seconds seconds

Table 708: Start Sequence 3340PU106

Reference should be made to the Regrind Cyclone Feed Pump (3340-PU-106) functional
specification for its start/stop sequence of the lubrication system and monitoring requirements.
The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-106 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-106-MO1 stopped
The pump stop sequence 3340-PU-106, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 564 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN RMCPF_3340BX103 EM 3340PU106 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-106.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
Stop pump.
20 60
2. Stop 3340-PU-106.MO1 Refer to vendor functional Stopped
seconds seconds
specification
2 180
3. Close 3340-XV-602A Suction Valve. Closed
seconds seconds
2 60
4. Close 3340-XV-602D Discharge Valve Closed
seconds seconds
2 60
5. Open 3340-XV-602C Suction Drain valve Opened
seconds seconds
2 20
6. Close 3340-XV-604 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-602B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-602B Closed
valve seconds seconds

Table 709: Stop Sequence 3340PU106

The Shutter of the Nuclear Density Meter (3340-DX-607) will open 5 seconds after the pump
3340-PU-106 is operational. The shutter will close when both Regrind Cyclone Feed Pumps are
not running.

22.2 Engineering Module– 3340PU107

22.2.1 Description – 3340PU107

The following figure shows the elements that make up the 3340PU107 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 565 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PT-364
3340CY110
PT
3340-SA-101
Product Return Vendor Package 3340-AY-101
Density Control

3340-CY-110
Flush Water Concentrate
Vendor Package Return

Mill 1 Product

Mill Feed
Mill 2 Product Distributor

3340PU106_107

3340-LCV-601

3340606
FC

FT
Process Water
3340-XV-602B

Make-Up
LC
3340601
Settler Feed

3340607
Settler U/Flow
1, 2 & 3

DC
DT
Flowrate Control

LT SC
3340602
3340-XV-602D
3340-XV-602A M

3340-BX-103
Vendor Package

3340-XV-602C FAL
3340 – PU – 106 3340-XV-603D
3340-XV-602C

3340604

3340-XV-604
FSL

SC
3340-XV-603B

3340603
LAH 3340PU173
3340PU106 Vendor Package 3340608
M
M
LSH
TE

3340-XV-603A
3340 – PU - 107
FAL 3340 – PU – 173
3340-XV-603C 3340605
3340-XV-603C

GSW 3340-XV-605 LAH 3340PU175


FSL 3340609

M
3340PU107 LSH Tails Launder
TE

3340 – PU – 175

Figure 77: Blockflow Control Diagram of the 3340PU107 System

22.2.2 Unit of Control Modules – 3340PU107

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN RMCPF_3340BX103 EM 3340PU107 Sub EM

Tag Service
3340-PU-107 Regrind Hydrocyclone Feed Pump 2
3340-PU-107-LU1FA1 Regrind Hydrocyclone Feed Pump Lube Oil Fan
3340-PU-107-LU1HE1 Regrind Hydrocyclone Feed Pump Lube Heater 1
3340-PU-107-LU1HE2 Regrind Hydrocyclone Feed Pump Lube Heater 2

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 566 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PU-107-MO1FA1 Regrind Hydrocyclone Feed Pump 1 Motor Fan 1


3340-PU-107-MO1FA2 Regrind Hydrocyclone Feed Pump 1 Motor Fan 2
3340-PU-107-MO1FA3 Regrind Hydrocyclone Feed Pump 1 Motor Fan 3
3340-FSL-605 Gland Seal Water flow switch
3340-XV-603D DISCHARGE ISOLATION VALVE OF SLURRY PUMP 3340-PU-107
3340-XV-603A SUCTION VALVE OF SLURRY PUMP 3340-PU-107
3340-XV-603B FLUSH WATER VALVE TO PIPELINE
3340-XV-603C Suction Drain Valve
3340-VT-603C1/2 VIBRATION TRANSMITTER 3340-PU-107
3340-VT-603C3/4 VIBRATION TRANSMITTER 3340-PU-107
3340-TT-603B3/4 TEMPERATURE TRANSMITTER 3340-PU-107
3340-TT-603B1/2 TEMPERATURE TRANSMITTER 3340-PU-107
3340-TT-603A2 TEMPERATURE TRANSMITTER 3340-PU-107
3340-TT-603A1 TEMPERATURE TRANSMITTER 3340-PU-107
3340-VT-603B1/2 VIBRATION TRANSMITTER 3340-PU-107
3340-VT-603B3/4 VIBRATION TRANSMITTER 3340-PU-107
3340-TT-603B5 TEMPERATURE TRANSMITTER 3340-PU-107
3340-LSL-603B LEVEL SWITCH LOW 3340-PU-107
3340-PSL-603B PRESSURE SWITCH LOW 3340-PU-107
3340-XV-605 Gland Seal Water Valve

Table 710: List of Unit Controls – 3340PU107

22.2.3 Interlocks – 3340PU107

T2 Interlock
Tag 3340-XV-603A Description Suction valve
RMCPF_3340BX Sub
UN EM 3340PU107
103 EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-603C.OP Suction drain valve open


OR OR ×
3340-XV-603C.OPNG Suction drain valve opening

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 567 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PU-107.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-603A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-603A.OPNG)

Table 711: List of Interlocks for 3340-XV-603A

T2 Interlock
Tag 3340-XV-603B Description Suction Flush Water Valve
RMCPF_3340BX Sub
UN EM 3340PU107
103 EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 712: List of Interlocks for 3340-XV-603B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Tag 3340-XV-603C Description Suction Drain Water Valve
RMCPF_3340BX Sub
UN EM 3340PU107
103 EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 713: List of Interlocks for 3340-XV-603C

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 568 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340 – PU – 107 Description Regrind Cyclone Feed Pump 2
RMCPF_3340BX Sub
UN EM 3340PU107
103 EM
Interlock
Motor Type VFD (Multiple) Intlck_3340BB_SL_01
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. Note 1 MQ15-718-TE-3340-IN0101


3340-XV-605 !OP ×
If gland seal water valve not open and
AND Note 1
pump is running
3340-PU-107.MO1.Run
3340-FSL-605.ACT × Note 1
Flow switch has a low flow alarm for a
AND Time Delay
time delay and pump is running
3340-PU-107-MO1.Run 300 seconds
3340-FSL-605.ACT Flow switch has a low flow alarm × Note 1
3340-XV-603A CL ×
Note 1
OR CLN Suction valve is closed or closing and
Time Delay
AND pump is running for a time delay
10 seconds
3340-PU-107-MO1.Run
× Note 1
3340-XV-603C. OP OR
Suction drain valve is open or opening Debounce
OPN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-603D !OP × Note 1
If discharge valve not open and pump is
AND Time Delay
running for a time delay
3340-PU-107.MO1.Run 30 seconds
×
3340-XV-602D !CL If alternate discharge valve not closed Note 1
3340-FIT-606.LL AND × Note 1
Slurry flowrate is Low Low and pump is
3340-PU-107- Time Delay
running
MO1.RUN 600 seconds
3340-XV- × Note 1
Number of Crossflow Feed Isolation
365.V_OPEN_HLIM Time Delay
Valves available < 6
(3340-XV-365 A thru N) 600 seconds
3340 XV – 612A !OP Note 1
Both 1st stage conc return pump suction
AND × Time Delay
valves are not open for a time delay
3340 XV - 613A !OP 15 seconds
3340 – MI – 101- Regrind Mill 1 is not running
Note 1
MO1.!Run AND
× Time Delay
AND 3340 ZY – 370 is discharging slurry to mill
60 seconds
3340 ZY –370 to Mill 1 1 for a time delay
3340 – MI – 102- Regrind Mill 2 is not running
Note 1
MO1.!Run AND
× Time delay
AND 3340 ZY – 370 is discharging slurry to mill
60 seconds
3340 ZY –370 to Mill 2 2 for a time delay
3340 – MI – 101-MO1 Both Regrind Mills
!Run 3340 – MI – 101
AND AND × Note 1
3340 – MI – 102 – MO1 3340 – MI – 102
!Run Are not running

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 569 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 714: List of Interlocks for 3340 – PU-107

Note 1 On stopping 3340 – PU – 107, its gearbox lubrication cooling and heating system
may continue to run. Refer to vendor functional specification

T2 Interlock
DISCHARGE ISOLATION VALVE OF
Tag 3340-XV-603D Description
SLURRY PUMP
RMCPF_3340BX Sub
UN EM 3340PU107
103 EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If Regrind Cyclone Feed Pump 1 Delay time


3340 XV- 602D.!CL ×
discharge valve is not closed 15 seconds
Regrind Cyclone Feed Pump 2 has not Time Delay
3340 – PU – 107 .!RN ×
run for a time delay 10 seconds

Table 715: List of Interlocks for 3340-XV-603D

T2 Interlock
Regrind Cyclone Feed Pump 1 Gland
Tag 3340-XV-605 Description
Seal Water Valve
RMCPF_3340BX Sub
UN EM 3340PU107
103 EM
Failure Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-PU-107.!RUN If the pump is not running ×

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 570 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 716: List of Interlocks for 3340-XV-605

22.2.4 Alarms and Process Setpoints – 3340PU107

T3 Alarms and Process Setpoints


UN RMCPF_3340BX103 EM 3340PU107 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Refer to vendor control philosophy for pump specific Alarms and Process Setpoints MQ15-718-TE-3340-IN0101
3340 FSL – Regrind Cyclone Feed Pump
604 0 - 15 m3/hr 7.9
GSW flow switch 1

Table 717: Alarms and Process Setpoint 3340PU107

The Regrind Cyclone Feed Pump 2 (3340 – PU – 107) is a running/standby combination with
3340 – PU – 106. Flowmeter (3340 – FIT – 606) and Densitometer (3340 – DIT – 607) are
common for both pumps along with their respective controllers. The alarms associated with the
Density transmitter, as well as the flow measurement should be inhibited when both Regrind
Cyclone Feed Pumps are not running.
22.2.5 Binary Messages – 3340PU107

Not applicable
22.2.6 Regulatory Control Loops – 3340PU107

The Regrind Cyclone Feed Pump 2 (3340 – PU – 107) is a running/standby combination with
3340 – PU – 106. Flowmeter (3340 – FIT – 606) and Densitometer (3340 – DIT – 607) are
common for both pumps along with their respective controllers. Refer to 3340PU106 Regulatory
Control Loops Description
22.2.7 Advanced Control Loops – 3340PU107

Not applicable
22.2.8 Sequence Description – 3340PU107

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. The pump start sequence 3340-PU-107, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 571 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN RMCPF_3340BX103 EM 3340PU107 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Close 3340-XV-603C Suction drain Valve Closed
seconds seconds
(Open &
Low Flow
2 60
2. Open 3340-XV-605 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
2 120
3. Open 3340-XV-603D Discharge Valve Open
seconds seconds
2 120
4. Open 3340-XV-603B Suction Valve. Open
seconds seconds
3340-PU-107-LU1FA1
3340-PU-107-LU1HE1
Start Pump lubrication
3340-PU-107-LU1HE2 10 120
5. Start sequences. Refer to vendor
3340-PU-107-MO1FA1 seconds seconds
functional specification.
3340-PU-107-MO1FA2
3340-PU-107-MO1FA3
Start pump. Refer to vendor 10 60
6. Start 3340-PU-107.MO1 Working
functional specification. seconds seconds

Table 718: Start Sequence 3340PU107

Reference should be made to the Regrind Cyclone Feed Pump (3340-PU-107) functional
specification for its start/stop sequence of the lubrication system and monitoring requirements.
The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-107 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-107-MO1 stopped
The pump stop sequence 3340-PU-107, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 572 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN RMCPF_3340BX103 EM 3340PU107 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-107.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
Stop pump.
20 60
2. Stop 3340-PU-107.MO1 Refer to vendor functional Stopped
seconds seconds
specification
2 180
3. Close 3340-XV-603A Suction Valve. Closed
seconds seconds
2 60
4. Close 3340-XV-603D Discharge Valve Closed
seconds seconds
2 60
5. Open 3340-XV-603C Suction Drain valve Opened
seconds seconds
2 20
6. Close 3340-XV-605 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-603B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-603B Closed
valve seconds seconds

Table 719: Stop Sequence 3340PU107

The Shutter of the Nuclear Density Meter (3340-DX-607) will open 5 seconds after the pump
3340-PU-107 is operational. The shutter will close when both Regrind Cyclone Feed Pumps are
not running.

22.3 Engineering Module – 3340CY110

22.3.1 Description – 3340CY110

The following figure shows the elements that make up the 3340CY110 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 573 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PT-364
3340CY110
PT
3340-SA-101
Product Return Vendor Package 3340-AY-101
Density Control

3340-CY-110
Flush Water Concentrate
Vendor Package Return

Mill 1 Product

Mill Feed
Mill 2 Product Distributor

3340PU106_107

3340-LCV-601

3340606
FC

FT
Process Water
3340-XV-602B

Make-Up
LC
3340601
Settler Feed

3340607
Settler U/Flow
1, 2 & 3

DC
DT
Flowrate Control

LT SC
3340602
3340-XV-602D
3340-XV-602A M

3340-BX-103
Vendor Package

3340-XV-602C FAL
3340 – PU – 106 3340-XV-603D
3340-XV-602C

3340604

3340-XV-604
FSL

SC
3340-XV-603B

3340603
LAH 3340PU173
3340PU106 Vendor Package 3340608
M
M
LSH
TE

3340-XV-603A
3340 – PU - 107
FAL 3340 – PU – 173
3340-XV-603C 3340605
3340-XV-603C

GSW 3340-XV-605 LAH 3340PU175


FSL 3340609

M
3340PU107 LSH Tails Launder
TE

3340 – PU – 175

Figure 78: Blockflow Control Diagram of the 3340CY110 System

22.3.2 Unit of Control Modules – 3340CY110

T1 Control Module
UN RMCPF_3340BX103 EM 3340CY110 Sub EM

Tag Service
3340-CY-110 Regrind Mill Hydro Cyclone Cluster
3340-PIT-364A DENSITY INDICATOR TRANSMITTER
3340-XV-365A CYCLONE VALVE
3340-XV-365B CYCLONE VALVE
3340-XV-365C CYCLONE VALVE
3340-XV-365D CYCLONE VALVE
3340-XV-365E CYCLONE VALVE

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 574 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-365F CYCLONE VALVE


3340-XV-365G CYCLONE VALVE
3340-XV-365H CYCLONE VALVE
3340-XV-365I CYCLONE VALVE
3340-XV-365J CYCLONE VALVE
3340-XV-365K CYCLONE VALVE
3340-XV-365L CYCLONE VALVE
3340-XV-365M CYCLONE VALVE
3340-XV-365N CYCLONE VALVE

Table 720: List of Unit Controls – 3340CY110

22.3.3 Interlocks – 3340CY110

T2 Interlock
3340-XV-365 A Deslime Cyclone Cluster 1 Feed Valves
Tag Description
thru N (30 in total)
RMCPF_3340BX Sub
UN EM 3340CY110
103 EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

No Interlocks

Table 721: List of Interlocks for 3340-XV-365 A though N

22.3.4 Alarms and Process Setpoints – 3340CY110

T3 Alarms and Process Setpoints


UN RMCPF_3340BX103 EM 3340CY110 Sub EM
High Low
Tag Description Range Unit SP HYS High Low
High Low

3340-PIT-364 Regrind Cyclone Cluster Feed


0 - 1000 KPa 137 69
Pressure Transmitter

Table 722: Alarms and Process Setpoint 3340CY110

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 575 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note

1) Low pressure Cyclone cluster feed pressure alarms must be inhibited if both pumps 3340-PU-106 and
3340 – PU – 107 are not running.

22.3.5 Binary State Messages – 3340CY110

Not applicable

22.3.6 Regulatory Control Loops – 3340CY110

T5 Regulatory Control Loops


UN RMCPF_3340BX103 EM 3340CY110 Sub EM
Tag Description Range Unit MV Unit Range Range Conditions MV
MV PV/SP PV SP
0 - 14 # cyclones KPa 70 - 3340PU106.!R
1357 un OR
(3340PU106.R
UN &
APC_CY110-
ON)

Regrind Cyclone Cluster Pressure OR


3340-PIC-364
Controller
3340PU107.!R
un OR
(3340PU107.R
UN &
APC_CY110-
ON)

Table 723: Regulatory Control Loops for 3340-PIC-364

The control loop 3340-PIC-364, corresponds to a Rule-based Controller, the which will enter into
operations when the APC Controller that controls the operation of the Cyclone Battery is not operational.

Tabulated below are the rules for the operation of the intervening block.

ID Condition Action
1. 3340-PIT-364 > HTH Increase by one (1) N° Cyclones.
2. 3340-PIT-364 < LTH Decrease by one (1) N° Cyclones.
Where:

PV1: 3340-PIT-364

PV1.HTH = 124 KPa

PV1.LTH = 90KPa

7
Expected setpoint 104KPa

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 576 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Selection of the valves to open / close in the cluster based upon the longest open time.

The Intervening Block will be evaluated 1 time every 60 seconds, in order to update (increase or
decrease), the number of Cyclones required to achieve an adequate Classification of the mineral. The
Controller based on the Controller block, tag 3340-PIC-364, will work in conjunction with the Advanced
Control Loop 3340-UIC-364 described in the subsection "Advanced Control Loops", and “Description" of
the EM 3340CY110.

22.3.7 Advanced Control Loops – 3340CY110

T5 Regulatory Control Loops


3340-UIC-364A/
Tag APC Type APC 10
APC-3340-PIC-364A
UN RMCPF_3340BX103 EM 3340CY110 Sub EM
Tag Description Unit Variable Type Notes
Regrind Cyclone Cluster Pressure KPa CV1
3340-PIT-364
Controller
Hydrocyclone Cluster – Control # MV1 Note 1
3340-KC-
Opening/Cyclone Closure cyclone
364.RSP
s

Note:

1) The 3340KC364 controller corresponds to the Opening and Closing Control block of Cyclones (CL14).
The cyclone cluster has fourteen (14) cyclones in total, where six (6) cyclones (LLIM1) will be the
minimum of devices that will be able to operate, while Twelve (12) cyclones (HLIM1), will be a maximum
of devices that can operate. On the other hand, two (2) Cyclones will be available in Stand By condition,
for replace any unit in case of failure. Block CL24 will be activated with the operating status of either
3340-PU-106 or 3340 – PU - 107 pumps.

22.3.8 Description – 3340CY110

The objective of the cyclone cluster 3340-CY-110 is to classify the mineral received by the CPF, in order
to differentiate it between material that needs to be recirculated to the mill and material which is
sufficiently fine to be returned to the concentrator rougher flotation circuit.

The coarse material, will be obtained through the spigot underflow of the cyclones, while the fines
material will overflow the cyclone and product concentrate. The cyclone cluster feed pressure is
controlled by opening or closing the isolation valve of each cyclone, opening a valve in case the pressure
exceeds a limit value, or closing a valve in case the pressure falls below the limit value defined for such
purposes.

For this purpose, the control logic to be implemented is to use of the CL14 block of the AAPL library,
which is capable of commanding the opening or closing of up to 14 power valves of a cyclone battery,
depending on the value of the quantity of cyclones that are required. Before this Set Point of number of
cyclones required for operation, the CL14 block will keep the number of cyclones open required,
automatically replacing those cyclones that cannot continue operating (cyclones with problems with the
actuation of their insulation valve, or that have been moved to maintenance for repair).

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 577 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

For more details of the control scheme considered to control the cyclone cluster 3340-CY-110, see
document Anglo-American, AGS 69, "Process Control - Control Template Specification r1.2a”, sección
4.1, “Controller Configuration Template”, configuración “Controller Configuration Template for the Cyclone
Cluster APC controller”.

Annex B, "Regulatory Control Grinding", sheet 1, shows the control scheme regulatory considered, where
the use of the scheme described in this section is appreciated, applied to the Project.

22.4 Engineering Module – 3340PU173

22.4.1 Description – 3340PU173

The following figure shows the elements that make up the 3340PU173 equipment module.
3340-PT-364
3340CY110
PT
3340-SA-101
Product Return Vendor Package 3340-AY-101
Density Control

3340-CY-110
Flush Water Concentrate
Vendor Package Return

Mill 1 Product

Mill Feed
Mill 2 Product Distributor

3340PU106_107

3340-LCV-601
3340606
FC

FT

Process Water
3340-XV-602B

Make-Up
LC
3340601
Settler Feed
3340607

Settler U/Flow
1, 2 & 3
DC
DT

Flowrate Control

LT SC
3340602
3340-XV-602D
3340-XV-602A M

3340-BX-103
Vendor Package
3340-XV-603D

3340 – PU – 106
3340-XV-602C FAL
3340-XV-602C

3340604

3340-XV-604
FSL

SC
3340-XV-603B

3340603
LAH 3340PU173
3340PU106 Vendor Package 3340608
M
M
LSH
TE

3340-XV-603A
3340 – PU - 107
FAL 3340 – PU – 173
3340-XV-603C 3340605
3340-XV-603C

GSW 3340-XV-605 LAH 3340PU175


FSL 3340609

M
3340PU107 LSH Tails Launder
TE

3340 – PU – 175

Figure 79: Blockflow Control Diagram of the 3340PU173 System

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 578 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

22.4.2 Unit of Control Modules – 3340PU173

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN RMCPF_3340BX103 EM 3340PU173 Sub EM

Tag Service
3340-TE-608 Bearing temperature switch
3340-LSH-608 Level Switch High

Table 724: List of Unit Controls – 3340PU173

22.4.3 Interlocks – 3340PU173

T2 Interlock
Tag 3340-PU-173 Description Regrind Area Spillage Pump
RMCPF_3340BX Sub
UN EM 3340PU173
103 EM
Interlock
Motor Type M1 Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Delay 10
3340-LSH-608.ACT High level switch activated × seconds
Note 1

3340-TE-608.ACT High bearing temperature alarm ×

BLACKOUT Delay 5
Electrical BlackOut Activated ×
ELECTRICO.ACT seconds

Table 725: List of Interlocks for 3340-PU-173

Note 1: Pump to run 15 minutes after the high level has been removed.
22.4.4 Alarms and Process Setpoints – 3340PU173

T3 Alarms and Process Setpoints


UN RMCPF_3340BX103 EM 3340PU173 Sub EM

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 579 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-LSH-608 Regrind Spillage Pump High


0 - 100 % 27%
Switch Alarm

Table 726: Alarms and Process Setpoint 3340-PU-173

Note: Level switches setpoints set in field, not within PLC.


22.4.5 Binary Messages – 3340PU173

Not applicable.
22.4.6 Regulatory Control Loops – 3340PU173

Not applicable.
22.4.7 Advanced Control Loops – 3340PU173

Not applicable
22.4.8 Description – 3340PU173

Spillage in the Regrind bund area will gravitate to the Regrind Spillage Pump (3340 – PU – 173).
The pump will discharge by manual selection to either:
 The Regrind Cyclone Feed Pump Box
This equipment can operate in manual mode or automatic mode. In manual mode, the start and
stop by the PLC will depend on the start/stop command that the operator. The operation of the
pump in Automatic Mode will occur if:
- The pump will start automatically, if it is ready to Operate in Sequence, and if Sump level
switch is high.
- The sump pump will stop automatically 15 minutes after the level switch high has fallen
away. The time delay in stopping the pump allows the pump to continue to run while hose
down of the area is occurring.

22.5 Engineering Module – 3340PU175

22.5.1 Description – 3340PU175

The following figure shows the elements that make up the 3340PU175 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 580 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PT-364
3340CY110
PT
3340-SA-101
Product Return Vendor Package 3340-AY-101
Density Control

3340-CY-110
Flush Water Concentrate
Vendor Package Return

Mill 1 Product

Mill Feed
Mill 2 Product Distributor

3340PU106_107

3340-LCV-601

3340606
FC

FT
Process Water
3340-XV-602B

Make-Up
LC
3340601
Settler Feed

3340607
Settler U/Flow
1, 2 & 3

DC
DT
Flowrate Control

LT SC
3340602
3340-XV-602D
3340-XV-602A M

3340-BX-103
Vendor Package

3340-XV-602C FAL
3340 – PU – 106 3340-XV-603D
3340-XV-602C

3340604

3340-XV-604
FSL

SC
3340-XV-603B

3340603
LAH 3340PU173
3340PU106 Vendor Package 3340608
M
M
LSH
TE

3340-XV-603A
3340 – PU - 107
FAL 3340 – PU – 173
3340-XV-603C 3340605
3340-XV-603C

GSW 3340-XV-605 LAH 3340PU175


FSL 3340609

M
3340PU107 LSH Tails Launder
TE

3340 – PU – 175

Figure 80: Blockflow Control Diagram of the 3340PU175 System

22.5.2 Unit of Control Modules – 3340PU175

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN RMCPF_3340BX103 EM 3340PU175 Sub EM

Tag Service
3340-TE-609 Bearing temperature switch
3340-LSH-609 Level Switch High

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 581 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 727: List of Unit Controls – 3340PU175

22.5.3 Interlocks – 3340PU175

T2 Interlock
Tag 3340-PU-173 Description Fluidization Water Spillage Pump
RMCPF_3340BX Sub
UN EM 3340PU175
103 EM
Interlock
Motor Type M1 Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Delay 10
3340-LSH-609.ACT High level switch activated × seconds
Note 1

3340-TE-609.ACT High bearing temperature alarm ×

BLACKOUT Delay 5
Electrical BlackOut Activated ×
ELECTRICO.ACT seconds

Table 728: List of Interlocks for 3340-PU-175

Note 1: Pump to run 15 minutes after the high level has been removed.
22.5.4 Alarms and Process Setpoints – 3340PU175

T3 Alarms and Process Setpoints


UN RMCPF_3340BX103 EM 3340PU175 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-LSH-609 Fluidization Water Spillage Pump


0 - 100 % 27%
High Switch Alarm

Table 729: Alarms and Process Setpoint 3340-PU-175

Note: Level switches setpoints set in field, not within PLC.


22.5.5 Binary Messages – 3340PU175

Not applicable.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 582 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

22.5.6 Regulatory Control Loops – 3340PU175

Not applicable.
22.5.7 Advanced Control Loops – 3340PU175

Not applicable
22.5.8 Description – 3340PU175

Spillage in the Fluidisation Water bund area will gravitate to the Fluidisation Water Spillage Pump
(3340 – PU – 175). The pump will discharge by manual selection to either:
 The Regrind Cyclone Feed Pump Box
 Tails Launder
This equipment can operate in manual mode or automatic mode. In manual mode, the start and
stop by the PLC will depend on the start/stop command that the operator. The operation of the
pump in Automatic Mode will occur if:
- The pump will start automatically, if it is ready to Operate in Sequence, and if Sump level
switch is high.
- The sump pump will stop automatically 15 minutes after the level switch high has fallen
away. The time delay in stopping the pump allows the pump to continue to run while hose
down of the area is occurring.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 583 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

23.0 UNIDAD: RMCPF_ALIMENTACION

Refer to:
MQ14-08-DR-3340-PD1081 Regrind Cyclone Cluster
A block flow control diagram is depicted below for the RMCPF_Alimentacion system.
3340-PT-364
PT
Vendor Package 3340-SA-101
3340-AY-101

3340-CY-110
Concentrate
Product Return Return
Density Control
Vendor Package

Flush Water
3340DB105
3340-DB-105
3340-ZV/Y - 370

3340-XV-602B 3340-HT-101 3340-ZA-101


3340-XV-360
3340-XV-603B

3340-LCV-601 3340-MI-101 3340-MI-102


Vendor Package Vendor Package
Process Water
Make-Up Settler U/Flow
LC Flowrate Control
3340601
Settler Feed
1, 2 & 3
DC FC
LT SC
3340606
3340607
3340602/3
3340-XV-602D
3340-XV-603D
M DT FT

3340-BX-103
Vendor Package
3340-XV-602A
3340-XV-603A 3340 – PU – 106
3340 – PU - 107

3340-XV-602C
3340-XV-603C
FAL
3340604
3340-XV-604 3340605
3340-XV-605

FSL

GSW

Figure 81: Blockflow Control Diagram of RMCPF_Alimentacion

The above control unit is broken into zero Engineering Module 1’s with zero sub Engineering Module 2’s.
23.0.1 Modules of Control RMCPF_Alimentacion

T1 Control Mod
Sub
UN RMCPF_Alimentacion EM
EM

Tag Service
3340-DB-105 Underflow Distributor
3340-ZV-370 TWO WAY DISTRIBUTOR

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 584 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-HT-101 Ball Loading Hoist


3340-ZA-101 Ball Loading Hopper
3340-XV-360 BALL LOAD TO REGRIND MILLS Sputnik

Table 730: List of Modules of Control for RMCPF_Alimentacion

23.0.2 Interlocks – RMCPF_Alimentacion

T2 Interlock
Tag 3340-ZV-370 Description TWO WAY DISTRIBUTOR
RMCPF_Alimenta
UN EM Sub EM
cion
Interlock
Motor Type Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340 – MI – 101 – MO1


Regrind Mill 1 is not running × Note 1
.!RN
3340 – MI – 102 – MO1
Regrind Mill 2 is not running × Note 2
.!RN

Table 731: List of Interlocks for 3340-ZV-370

Note 1 If Regrind Mill 1 (3340 – MI – 101) is not running, the distributor must fully retract
and distribute all the feed slurry to Regrind Mill 2 (3340 – MI – 102).

Note 2 If Regrind Mill 2 (3340 – MI – 102) is not running, the distributor must fully extend
and distribute all the feed slurry to Regrind Mill 1 (3340 – MI – 101).

23.0.3 Alarms and Process Setpoints – RMCPF_Alimentacion

T3 Alarms and Process Setpoints


UN RMCPF_Alimentacion EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340-ZV-370 Typical
TWO WAY DISTRIBUTOR 0 - 100 %
50

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 585 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 732: Alarms and Process Setpoint RMCPF_Alimentacion

The distributor normally distributes feed slurry evenly between two operating mills with a 50%
extension.
23.0.4 Binary State Messages – RMCPF_Alimentacion

There are no binary state messages for this section


23.0.5 Regulatory Control Loops – RMCPF_Alimentacion

There are no regulatory control loops for this section


23.0.6 Advanced Control Loops – RMCPF_Alimentacion

There are no advanced control loops for this section.

23.0.7 Description

Regrind cyclone underflow is combined with thickener underflow (i.e. mill new feed) in a Thickener
Underflow Collection Box (3340 – BX – 140) and discharged into the Underflow Distributor (3340
– DB – 105). The distributor allows for an adjustable, even split of the slurry to occur between the
two regrind mills. Under normal conditions, the splitter will be positioned manually by the control
room operator such that an even (50:50) split of slurry is effected. This can either be visually
assessed by an operator in the field or alternatively by comparing the power draw of the two mills.
Should one mill be offline, the distributor can be swung over by the control room operator to fully
discharge exclusively to the operating mill.
A ball reload hopper (3340 – ZA – 101) is used to manually discharge balls into a sputnik skip
(3340 – ZA – 102). The actuator position is changed by the operator in the plant with a field switch.
The sputnik is then raised to the respective mill by an electric hoist (3340 – HT – 101) and then
manually discharged. All these functions are conducted by the operator in the field.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 586 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

24.0 UNIDAD: RMCPF_3340MI101

Refer to:
MQ14-08-DR-3340-PD1081 Regrind Cyclone Cluster
MQ14-08-DR-3340-PD1082 Regrind Mill 1 (Vendor)
MQ15-51-DR-3340-EE0011 Regrind Mill Functional Description (Vendor)

A block flow control diagram is depicted below for the RMCPF_3340MI101 system.
3340-PT-364
PT
Vendor Package 3340-SA-101
3340-AY-101

3340-CY-110
Concentrate
Product Return Return
Density Control
Vendor Package
3340-DB-105
3340-ZV/Y - 370
Flush Water

3340-XV-602B 3340-HT-101 3340-ZA-101


3340-XV-360
3340-XV-603B
3340-XV-367A

3340-XV-366A
3340-LCV-601 3340-MI-101 3340-MI-102
Vendor Package Vendor Package
Process Water 3340MI101
Make-Up Settler U/Flow
LC Flowrate Control
3340601
Settler Feed
1, 2 & 3
DC FC
LT SC 3340606
3340607
3340602/3
3340-XV-602D
3340-XV-603D
M DT FT

3340-BX-103
Vendor Package
3340-XV-602A
3340-XV-603A 3340 – PU – 106
3340 – PU - 107

3340-XV-602C
3340-XV-603C
FAL
3340604
3340-XV-604 3340605
3340-XV-605

FSL

GSW

Figure 82: Blockflow Control Diagram of RMCPF_3340MI101

The above control unit is broken into one Engineering Module with zero sub Engineering Module 2’s.
- 3340MI101

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 587 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

24.0.1 Modules of Control RMCPF_3340MI101

T1 Control Mod
Sub
UN RMCPF_3340MI101 EM 3340MI101
EM
Tag Service
3340-MI-101 REGRIND MILL No.1
3340-VT-406 VIBRATION TRANSMITTER
3340-VT-407 VIBRATION TRANSMITTER
3340-TSL/H-412A
3340-TSL/H-412B
3340-TSL-412 TEMPERATURE SWITCH LOW
3340-VT-413 VIBRATION TRANSMITTER
3340-VT-414 VIBRATION TRANSMITTER
3340-VT-415 VIBRATION TRANSMITTER
3340-VT-416 VIBRATION TRANSMITTER
3340-TT-412 TEMPERATURE IN REDUCER
3340-FSLL-410 FLOW SWITCH LOW LOW
3340-FSL-410 FLOW SWITCH LOW
3340-FSLL-411 FLOW SWITCH LOW LOW
3340-FSL-411 FLOW SWITCH LOW
3340-PDSH-422 PRESSURE DIFFERENTIAL SWITCH HIGH
3340-PDSH-423 PRESSURE DIFFERENTIAL SWITCH HIGH
3340-XV-367A Regrind Mill 1 Flush Water Isolation Valve

Table 733: List of Modules of Control for RMCPF_3340MI101

24.0.2 Interlocks – RMCPF_3340MI101

T2 Interlock
Tag 3340-MI-101 Description Regrind Mill 1, lubrication and grease systems
RMCPF_3340MI1 3340MI10
UN EM Sub EM
01 1
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 588 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Refer to vendor functional specification MQ15-51-DR-3340-EE0011

Table 734: List of Interlocks for 3340-MI-101

T2 Interlock
Tag 3340-XV-367A Description Regrind Mill 1 Flush Water Isolation Valve
RMCPF_3340MI1 3340MI10
UN EM Sub EM
01 1
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 735: List of Interlocks for 3340-XV-367A

24.0.3 Alarms and Process Setpoints – RMCPF_3340MI101

T3 Alarms and Process Setpoints


UN RMCPF_3340MI101 EM 3340MI101 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Refer to vendor functional specification MQ15-51-DR-3340-EE0011

Table 736: Alarms and Process Setpoint RMCPF_3340MI101

24.0.4 Binary State Messages – RMCPF_3340MI101

Refer to vendor functional specification. MQ15-51-DR-3340-EE0011


There are no binary state messages outside of the vendor package.
24.0.5 Regulatory Control Loops – RMCPF_3340MI101

There are no regulatory control loops for this section outside the vendor package. Refer to vendor
functional specification. MQ15-51-DR-3340-EE0011

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 589 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

24.0.6 Advanced Control Loops – RMCPF_3340MI101

There are no advanced control loops for this section outside the vendor package. Refer to vendor
functional specification. MQ15-51-DR-3340-EE0011

24.0.7 Description – RMCPF_3340MI101

Two Regrind Mills (3340 – MI – 101 / 102) complete with lubrication system are a vendor package
item. As such the vendor functional specification for the mill operation shall be adhered to.
During shutdown conditions, the mills are required to be operated until their product slurry density
drops below a specified value as defined in the vendor functional specification. While the slurry is
being purged from the mill, flush water is injected into the mill by opening the automated flush
water valve (3340 XV – 366A / 367A). The opening and closing of these actuated valves would
be done at the request of the operator in the field. These valves are normally closed while the
mills operate.
The power consumption (KW / ton) of the individual mills shall be calculated and displayed for the
control room operator. This is calculated by the following:
𝑀𝑖𝑙𝑙 𝑃𝑜𝑤𝑒𝑟 × 𝑁𝑜. 𝑀𝑖𝑙𝑙𝑠
𝑀𝑖𝑙𝑙 𝑃𝑜𝑤𝑒𝑟 𝐷𝑟𝑎𝑤 =
T

Where: Mill Power [KW] = Power draw of the respective mill


TRegrind Pumps = Dry solids (tph) pumped by the Regrind Cyclone Feed Pumps
No. Mills = Total number of mills operating with feed.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 590 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

25.0 UNIDAD: RMCPF_3340MI102

Refer to:
MQ14-08-DR-3340-PD1081 Regrind Cyclone Cluster
MQ14-08-DR-3340-PD1083 Regrind Mill 2 (Vendor)
MQ15-51-DR-3340-EE0011 Regrind Mill Functional Description (Vendor)

A block flow control diagram is depicted below for the RMCPF_3340MI102 system.
3340-PT-364
PT
Vendor Package 3340-SA-101
3340-AY-101

3340-CY-110
Concentrate
Product Return Return
Density Control
Vendor Package
3340-DB-105
3340-ZV/Y - 370
Flush Water

3340-XV-602B 3340-HT-101 3340-ZA-101


3340-XV-360
3340-XV-603B
3340-XV-367A

3340-XV-366A
3340-LCV-601 3340-MI-101 3340-MI-102
Vendor Package Vendor Package
Process Water 3340MI101
Make-Up Settler U/Flow
LC Flowrate Control
3340601
Settler Feed
1, 2 & 3
DC FC
LT SC 3340606
3340607
3340602/3
3340-XV-602D
3340-XV-603D
M DT FT

3340-BX-103
Vendor Package
3340-XV-602A
3340-XV-603A 3340 – PU – 106
3340 – PU - 107

3340-XV-602C
3340-XV-603C
FAL
3340604
3340-XV-604 3340605
3340-XV-605

FSL

GSW

Figure 83: Blockflow Control Diagram of RMCPF_3340MI102

The above control unit is broken into one Engineering Module with zero sub Engineering Module 2’s.
- 3340MI102

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 591 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

25.0.1 Modules of Control RMCPF_3340MI102

T1 Control Mod
Sub
UN RMCPF_3340MI102 EM 3340MI102
EM
Tag Service
3340-MI-102 REGRIND MILL No.2
3340-VT-506 VIBRATION TRANSMITTER
3340-VT-507 VIBRATION ALARM HIGH
3340-TSL/H-512A
3340-TSL/H-512B
3340-TSL-512 TEMPERATURE SWITCH LOW
3340-VT-513 VIBRATION TRANSMITTER
3340-VT-514 VIBRATION TRANSMITTER
3340-VT-515 VIBRATION TRANSMITTER
3340-VT-516 VIBRATION TRANSMITTER
3340-TT-512 TEMPERATURE IN REDUCER
3340-FSLL-510 FLOW SWITCH LOW LOW
3340-FSL-510 FLOW SWITCH LOW
3340-FSLL-511 FLOW SWITCH LOW LOW
3340-FSL-511 FLOW SWITCH LOW
3340-PDSH-522 PRESSURE DIFFERENTIAL SWITCH HIGH
3340-PDSH-523 PRESSURE DIFFERENTIAL SWITCH HIGH
3340-XV-366A PROCESS WATER TO REGRIND MILL 3340-MI-102

Table 737: List of Modules of Control for RMCPF_3340MI102

25.0.2 Interlocks – RMCPF_3340MI102

T2 Interlock
Tag 3340-MI-102 Description Regrind Mill 2, lubrication and grease systems
RMCPF_3340MI1 3340MI10
UN EM Sub EM
02 2
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 592 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Refer to vendor functional specification MQ15-51-DR-3340-EE0011

Table 738: List of Interlocks for 3340-MI-102

T2 Interlock
Tag 3340-XV-366A Description Regrind Mill 2 Flush Water Isolation Valve
RMCPF_3340MI1 3340MI10
UN EM Sub EM
02 2
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 739: List of Interlocks for 3340-XV-366A

25.0.3 Alarms and Process Setpoints – RMCPF_3340MI102

T3 Alarms and Process Setpoints


UN RMCPF_3340MI102 EM 3340MI102 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
Refer to vendor functional specification MQ15-51-DR-3340-EE0011

Table 740: Alarms and Process Setpoint RMCPF_3340MI102

25.0.4 Binary State Messages – RMCPF_3340MI102

Refer to vendor functional specification. MQ15-51-DR-3340-EE0011


There are no binary state messages outside of the vendor package.
25.0.5 Regulatory Control Loops – RMCPF_3340MI102

There are no regulatory control loops for this section outside the vendor package. Refer to vendor
functional specification. MQ15-51-DR-3340-EE0011

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 593 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

25.0.6 Advanced Control Loops – RMCPF_3340MI102

There are no advanced control loops for this section outside the vendor package. Refer to vendor
functional specification. MQ15-51-DR-3340-EE0011

25.0.7 Description – RMCPF_3340MI102

Two Regrind Mills (3340 – MI – 101 / 102) complete with lubrication system are a vendor package
item. As such the vendor functional specification for the mill operation shall be adhered to.
During shutdown conditions, the mills are required to be operated until their product slurry density
drops below a specified value as defined in the vendor functional specification. While the slurry is
being purged from the mill, flush water is injected into the mill by opening the automated flush
water valve (3340 XV – 366A / 367A). The opening and closing of these actuated valves would
be done at the request of the operator in the field. These valves are normally closed while the
mills operate.
The power consumption (KW / ton) of the individual mills shall be calculated and displayed for the
control room operator. This is calculated by the following:
𝑀𝑖𝑙𝑙 𝑃𝑜𝑤𝑒𝑟 × 𝑁𝑜. 𝑀𝑖𝑙𝑙𝑠
𝑀𝑖𝑙𝑙 𝑃𝑜𝑤𝑒𝑟 𝐷𝑟𝑎𝑤 =
T

Where: Mill Power [KW] = Power draw of the respective mill


TRegrind Pumps = Dry solids (tph) pumped by the Regrind Cyclone Feed Pumps
No. Mills = Total number of mills operating with feed.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 594 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

26.0 UNIDAD: CRCFP_RETORNOCONC

Refer to:
MQ14-08-DR-3340-PD1086 Product Pumping
MQ14-08-DR-3340-PD1102 Product Pumping Second Stage

A block flow control diagram is depicted below for the CRCFP_RETORNOCONC system.
Flush Water

Regrind Cyclone
Feed Flowrate
3340-XV-612B 3340-XV-384B
3340-LCV-611 3340-XV-388A
Tails Launder
Process Water
Make-Up LC
3340611
Prod Cyclone 3340PU111
O/Flow
FC SC
3340PU110 DC
LT SC 3340380 3340384
3340381
3340612 3340-XV-386A
3340-XV-384D
3340-XV-612A M DT FT
M
Milled Conc
Return
3340-BX-106
3340-XV-384A 3340 – PU – 111 3340-XV-386B
3340 – PU – 110

3340-XV-384C

3340389
FSL

FAL
3340-XV-612C Milled Conc
Return

FAL
3340-XV-389
3340614
3340-XV-614 Milled Conc
Return
3340-XV-386C
FSL

DC
FC SC 3340-XV-385D
SC 3340382 3340-XV-385B 3340385
3340-XV-613B 3340383
3340613

3340-XV-613A M
M DT FT

3340-XV-385A 3340 – PU – 191


3340PU190 3340 – PU - 190
3340-XV-613C 3340-XV-384C 3340PU191
3340390
FSL

FAL

FAL
3340615
3340-XV-615
3340-XV-390 Tails Launder
FSL
3340-XV-387A
GSW

HP GSW

Figure 84: Blockflow Control Diagram of CRCFP_RETORNOCONC

The above control unit is broken into one Engineering Module 1 with four sub Engineering Module 2’s:
- 3340PU110_191
o 3340PU110
o 3340PU111
o 3340PU190
o 3340PU191

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 595 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

26.0.1 Modules of Control CRCFP_RETORNOCONC

T1 Control Mod
Sub
UN CRCFP_RETORNOCONC EM
EM
Tag Service
3340-BX-106 Concentrate Return Collection Box
3340-LIT-611 LEVEL INDICATOR TRANSMITTER
3340-LCV-611A Level Control Valve – 3340-BX-106
3340-DIT-381 DENSITY INDICATOR TRANSMITTER
3340-FIT-380 SONAR FLOW TRANSMITTER
3340-DX-381 DENSITY SOURCE Isolation
3340-FIT-382 SONAR FLOW TRANSMITTER
3340-DIT-383 DENSITY INDICATOR TRANSMITTER
3340-DX-383 DENSITY SOURCE Isolation

Table 741: List of Modules of Control for CRCFP_RETORNOCONC

26.0.2 Interlocks – CRCFP_RETORNOCONC

T2 Interlock
Tag 3340-LCV-611A Description Level Control Valve – 3340-BX-106
CRCFP_RETOR
UN EM Sub EM
NOCONC
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If the pump box level is not low, the level


3340 – LIT – 611. !L ×
control valve must remain closed

Table 742: List of Interlocks for 3340-LCV-611A

T2 Interlock
Densitometer Nuclear Source Isolation
Tag 3340-DX-381 Description
Shutter for 3340-PU-110

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 596 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

CRCFP_RETOR Sub
UN EM
NOCONC EM
Interlock Intlck_OBTURADOR_DENSI
Motor Type
Type METRO_01

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-110.!RUN If concentrate return pump 1 is not running ×

Table 743: List of Interlocks for 3340-DX-381

T2 Interlock
Densitometer Nuclear Source Isolation
Tag 3340-DX-383 Description
Shutter for 3340-PU-190
CRCFP_RETOR Sub
UN EM
NOCONC EM
Interlock Intlck_OBTURADOR_DENSI
Motor Type
Type METRO_01

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-190.!RUN If concentrate return pump 2 is not running ×

Table 744: List of Interlocks for 3340-DX-383

26.0.3 Alarms and Process Setpoints – CRCFP_RETORNOCONC

T3 Alarms and Process Setpoints


UN CRCFP_RETORNOCONC EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

3340 LIT -611 Concentrate Return Collection


0 - 100 % 95 45
Box Level Controller
3340 FIT –380 3340-PU-110 pump flowmeter 0 - 1000 m3/hr 530 250
3340 FIT –382 3340-PU-190 pump flowmeter 0 - 1000 m3/hr 530 250
3340 DIT – 1.00 –
381 3340-PU-110 pump densitometer t/m3
2.00
3340 DIT – 1.00 –
383 3340-PU-190 pump densitometer t/m3
2.00

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 597 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 745: Alarms and Process Setpoint CRCFP_RETORNOCONC

26.0.4 Binary State Messages – CRCFP_RETORNOCONC

T4 Binary State Messages


UN CRCFP_RETORNOCONC EM Sub EM
Tag Description OFF ON

3340-ZSC-381 LINE RADIOACTIVE SOURCE


× Note 2
PUMP 3340-PU-110 CLOSED
3340-ZSO-381 LINE RADIOACTIVE SOURCE
× Note 1
PUMP 3340-PU-110 OPEN
3340-ZSC-383 LINE RADIOACTIVE SOURCE
× Note 2
PUMP 3340-PU-190 CLOSED
3340-ZSO-383 LINE RADIOACTIVE SOURCE
× Note 1
PUMP 3340-PU-190 OPEN

Table 746: Binary State Messages CRCFP_RETORNOCONC

Note:
1) Condition should alarm, if the valve is open 5 seconds after the pump 3340-PU-110 or
3340-PU-190 has stopped.
2) Condition should alarm, if the valve is closed, 5 seconds after the pump 3340-PU-110 or
3340-PU-190 is running. If this condition occurs, calculation of the mass flowrate and
average value % of solids should not occur.
3) An alarm should be provided when a nuclear density meter reading (tag 3340-DIT-381
and 3340-DIT-383) provides a difference in measured value greater than 10%, under
normal operating conditions (both pumps operating). Alarm will not be triggered when only
one pump is operating, when the pump is under start-up conditions.
4) This is a running/standby arrangement and as such, only one densitometer will be utilised
at one time.
26.0.5 Regulatory Control Loops – CRCFP_RETORNOCONC

T5 Regulatory Control Loops


UN CRCFP_RETORNOCONC EM Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
55 - 100 % % 0 - 100 45 - 100 Expected
Concentrate Return Collection Box setpoint 65%
3340 LC -611
level controller tank level.
Note 3
0 - 100 % t/m3 1.00 – 1.00 – Expected
3340-PU-110 density control if pump
3340 DC - 381 2.00 2.00 setpoint 1.24
running
t/m3. Note 1
0 - 100 % t/m3 1.00 – 1.00 – Expected
3340-PU-190 density control if pump
3340 DC -383 2.00 2.00 setpoint 1.24
running
t/m3. Note 2

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 598 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 747: Regulatory Control Loops for CRCFP_RETORNOCONC

Note 1 Density only controlled when 3340-PU-110 is selected and running. Density controlled by
manipulating the flowrate setpoint of Regrind Cyclone Feed pump (3340 FC –606).

Note 2 Density only controlled when 3340-PU-190 is selected and running. Density controlled by
manipulating the flowrate setpoint of Regrind Cyclone Feed pump (3340 FC –606).

Note 3 Pump box level (3340 – LIT – 611) is controlled by manipulating the speed of the pump in
operation. Only if the pump box level reduces to below the low alarm limit is the level control
water valve allowed to open.

In the event that the plant is discharging slurry to the tails launder (3340 – XV – 387A or
3340 – XV – 388A not closed), the first stage pump (either 3340 – PU – 110 or 3340 – PU
– 190) speed is manipulated for pump box level control. The pump speed is limited to
maintain a minimum pipeline flowrate velocity specified.

In the event that the plant is discharging slurry to the concentrator (either 3340 – XV –
384A or 3340 – XV – 385A are open and 3340 XV – 386C is closed ), the first stage pump
(either 3340 – PU – 110 or 3340 – PU – 190) speed is fixed at maximum and the second
stage pump (3340 – PU – 111 or 3340 – PU – 191) is manipulated for pump box level
control. The pump speed is limited to maintain a minimum pipeline flowrate velocity
specified.

26.0.6 Advanced Control Loops – CRCFP_RETORNOCONC

There are no advanced control loops for this section.

26.0.7 Description – CRCFP_RETORNOCONC

The CPF concentrate product gravitates into the Concentrate Return Collection Box (3340 – BX
– 106). The slurry level in the box is controlled by varying the speed of the concentrate return
pumps and therefore under normal conditions no water is added to the tank. However, a minimum
line velocity must be maintained within the return pipeline and hence a level control water valve
(3340 LCV-611) will additionally be used to maintain the level of the sump when it falls to the low
level limit.
Two pumps in series are required to return the CPF concentrate to the Papajuane rougher
flotation circuit. A standby two-stage pump system is installed. Due to project space limitation, the
first and second stage pumps are in different areas of the CPF, thus requiring more complex
piping/flushing considerations.
The CPF concentrate slurry can discharge to three locations:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 599 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

 Normal operation is to discharge concentrate to the Papajuane rougher flotation circuit


feed box (3310 – BX - 005). A two-stage pumping system is required for this to occur. The
first stage pump will operate at maximum (100% VFD, fixed) speed, while the second
stage pump speed will be adjusted to maintain a consistent Concentrate Return Collection
Box level (3340 LIT-611). A minimum flowrate limit will prevent the flowrate from reducing
to where pipeline sedimentation blockage could occur;
 CPF Tails launder. This will typically be utilised while purging the CPF during shutdown
occasions when the second stage pump system is stopped. In this case, the first stage
pump speed will be adjusted to maintain a consistent Concentrate Return Collection Box
level (3340 LIT-611). The discharge location to the Tails launder is indicated when the
bypass valve (3340 XV – 387A or 388A) not closed. A minimum flowrate limit will prevent
the flowrate from reducing to where pipeline sedimentation blockage could occur;
 CPF Plant Feed Box. This will be utilised to operate the full CPF circuit, recycling product
back into the CPF feed, without affecting the operation of the Papajuane concentrator.
Proving all interlocks and process flow systems in this manor will be invaluable during
commissioning. Although the slurry will pass through the second stage pump, it will not be
required to provide additional energy to the slurry system. Consequently, the first stage
pump speed will be adjusted to maintain a consistent Concentrate Return Collection Box
level (3340 LIT-611) while the second stage will merely rotate/idle. The discharge location
to the CPF Plant Feed Box is indicated when the valve (3340 XV – 386C) is not closed. A
minimum flowrate limit will prevent the flowrate from reducing to where pipeline
sedimentation blockage could occur.
Flowrate is measured in the two running/standby pipelines from the first stage pumps (3340 - FIT-
380 or 3340 - FIT - 382) and should it reduce to a low limit, the pump speed will be increased to
ensure line velocities are maintained above low limits. Above this limit, the pump speed will be
adjusted to control the level in the concentrate return pump box (3340-BX-106). Slurry density is
also measured (3340 - DIT-381 or 3340 - DIT-383) and controlled to 30% mass solids density in
order not to dilute the Papajuane concentrators’ rougher feed. The density is controlled by varying
the flowrate setpoint of the regrind cyclone feed pumps (3340 FIC-606). Refer to the next section
below. However, the line flowrate setpoint will have a low limitation to avoid pipeline sedimentation
blockage risks.
Volumetric flowrate is measured by flow transmitter (3340 FIT – 380 or 382). Slurry density is
measured by densitometer (3340 DIT – 381 or 383).
By combining the flow transmitter and densitometer readings, a totalized mass flow in the
concentrate return pipeline will be calculated based upon the following formulae:
𝑆𝐺
𝑇 = 𝑉𝑝 (𝑑𝑝 − 1) ×
(𝑆𝐺 − 1)
Where: T = Dry Solids Mass [tph]
Vp = Volumetric Flowrate [m3/hr] 3340 - FIT-380 or 3340 - FIT - 382
Dp = Slurry density [t/m3] 3340 - DIT-381 or 3340 - DIT-383

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 600 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

SG = Solids Specific Gravity = 2.82 t/m3


Solids mass returned to the concentrator will be totalized on an hour, shift, day and monthly basis
and will be visible to the control room operator. Solids returned as CPF product to the concentrator
should only be totalised if all the bypass valves (3340 - XV-387A, 3340 - XV-388A and 3340 - XV-
386C) in the line being operated are closed.
26.1 Engineering Module– 3340PU110

26.1.1 Description – 3340PU110

The following figure shows the elements that make up the 3340PU110 equipment module.
Flush Water

Regrind Cyclone
Feed Flowrate
3340-XV-612B 3340-XV-384B
3340-LCV-611 3340-XV-388A
Tails Launder
Process Water
Make-Up LC
3340611
Prod Cyclone 3340PU111
O/Flow
FC SC
3340PU110 DC
LT SC 3340380 3340384
3340381
3340612 3340-XV-386A
3340-XV-384D
3340-XV-612A M DT FT
M
Milled Conc
Return
3340-BX-106
3340-XV-384A 3340 – PU – 111 3340-XV-386B
3340 – PU – 110

3340-XV-384C
3340389

3340-XV-612C
FSL

FAL

Milled Conc
Return

FAL
3340-XV-389
3340614
3340-XV-614 Milled Conc
Return
3340-XV-386C
FSL

DC
FC SC 3340-XV-385D
SC 3340382 3340-XV-385B 3340385
3340-XV-613B 3340383
3340613

3340-XV-613A M
M DT FT

3340-XV-385A 3340 – PU – 191


3340PU190 3340 – PU - 190
3340-XV-613C 3340-XV-384C 3340PU191
3340390
FSL

FAL

FAL
3340615
3340-XV-615
3340-XV-390 Tails Launder
FSL
3340-XV-387A
GSW

HP GSW

Figure 85: Blockflow Control Diagram of the 3340PU110 System

26.1.2 Unit of Control Modules – 3340PU110

The following table shows the details of the Control Modules considered for this Equipment
Module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 601 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T1 Control Module
UN CRCFP_RETORNOCONC EM 3340PU110 Sub EM

Tag Service
3340-PU-110 Concentrate Return Pump 1
3340-FSL-614 GLAND SEAL WATER Flow switch
3340-XV-612A SUCTION Valve OF SLURRY PUMP 3340-PU-110
3340-XV-612B Suction Flush Water Isolation
3340-XV-612C Suction Drian Valve
3340-XV-614 Gland Seal Water Isolation

Table 748: List of Unit Controls – 3340PU110

26.1.3 Interlocks – 3340PU110

T2 Interlock
Tag 3340-XV-612A Description Suction valve
CRCFP_RETOR Sub
UN EM 3340PU110
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-612C.OP Suction drain valve open


OR OR ×
3340-XV-612C.OPNG Suction drain valve opening
3340-PU-110.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-612A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-612A.OPNG)

Table 749: List of Interlocks for 3340-XV-612A

T2 Interlock
Tag 3340-XV-612B Description Suction Flush Water Valve
CRCFP_RETOR Sub
UN EM 3340PU110
NOCONC EM
Failure Position: Interlock
Motor Type
Keep Last (KL) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 602 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 750: List of Interlocks for 3340-XV-612B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Tag 3340-XV-612C Description Suction Drain Water Valve
CRCFP_RETOR Sub
UN EM 3340PU110
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 751: List of Interlocks for 3340-XV-612C

T2 Interlock
Tag 3340 – PU – 110 Description Concentrate Return Pump 1
CRCFP_RETOR Sub
UN EM 3340PU110
NOCONC EM
Interlock
Motor Type VFD Intlck_3340BB_SL_01
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-614 !OP If gland seal water valve not open and ×


Note 1
AND pump is running

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 603 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PU-110.MO1.Run

3340-FSL-614.ACT × Note 1
Flow switch has a low flow alarm for a
AND Time Delay
time delay and pump is running
3340-PU-110-MO1.Run 300 seconds
3340-FSL-614.ACT Flow switch has a low flow alarm × Note 1
3340-XV-612A CL ×
Note 1
OR CLN Suction valve is closed or closing and
Time Delay
AND pump is running for a time delay
10 seconds
3340-PU-110-MO1.Run
× Note 1
3340-XV-612C. OP OR
Suction drain valve is open or opening Debounce
OPN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-388A !OP ×
Note 1
AND If both discharge valves not open and
Time Delay
3340-XV-384A !OP pump is running for a time delay
30 seconds
3340-PU-110.MO1.Run
3340-FIT-380.LL AND × Note 1
Slurry flowrate is Low Low and pump is
3340-PU-110- Time Delay
running
MO1.RUN 600 seconds
3340 TE - 612 Pump Thermistor alarm ×

Table 752: List of Interlocks for 3340 – PU - 110

T2 Interlock
Tag 3340-XV-614 Description Pump Gland Seal Water Valve
CRCFP_RETOR Sub
UN EM 3340PU110
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-PU-110.!RUN If the pump is not running ×

Table 753: List of Interlocks for 3340-XV-614

26.1.4 Alarms and Process Setpoints – 3340PU110

T3 Alarms and Process Setpoints


UN CRCFP_RETORNOCONC EM 3340PU110 Sub EM

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 604 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340 FSL -
614 3340-PU-110 pump flow switch 0 – 5.1 m3/hr 2.7

Table 754: Alarms and Process Setpoint 3340PU110

26.1.5 Binary Messages – 3340PU110

Not applicable
26.1.6 Regulatory Control Loops – 3340PU110

Not applicable. Refer to section CRCFP_RETORNOCONC

26.1.7 Advanced Control Loops – 3340PU110

Not applicable

26.1.8 Sequence Description – 3340PU110

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped.
The pump is started by pumping slurry to the tails launder. In order to then change the discharge
location to the concentrator, the second stage pump start sequence must be initiated.
The pump start sequence 3340-PU-110, shall follow the following steps:
TSQST Start Sequence Table
UN CRCFP_RETORNOCONC EM 3340PU110 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Close 3340-XV-612C Suction drain Valve Closed
seconds seconds
(Open &
Low Flow
2 60
2. Open 3340-XV-614 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
Discharge Valve to Tails 2 120
3. Open 3340-XV-388A Open
Launder seconds seconds
Suction Valve - second stage 2 120
4. Close 3340 – XV – 384A Close
pump seconds seconds
2 120
5. Open 3340-XV-612B Suction Valve. Open
seconds seconds
10 60
6. Start 3340-PU-110.MO1 Start pump. Working
seconds seconds

Table 755: Start Sequence 3340PU106

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 605 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-110 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-110-MO1 stopped
The pump stop sequence 3340-PU-110, shall follow the following steps:
TSQST Stop Sequence Table
UN CRCFP_RETORNOCONC EM 3340PU110 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-110.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3340-PU-110.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3340-XV-612A Suction Valve. Closed
seconds seconds
Suction Valve - second stage 2 60
4. Close 3340-XV-384A Closed
pump seconds seconds
2 60
5. Open 3340-XV-388A Discharge Valve to Tails Launder Opened
seconds seconds
2 60
5. Open 3340-XV-612C Suction Drain valve Opened
seconds seconds
2 20
6. Close 3340-XV-614 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-612B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-612B Closed
valve seconds seconds

Table 756: Stop Sequence 3340PU110

The Shutter of the Nuclear Density Meter (3340-DX-381) will open 5 seconds after the pump
3340-PU-110 is operational. The shutter will close when the Pump is not running.

26.2 Engineering Module– 3340PU190

26.2.1 Description – 3340PU190

The following figure shows the elements that make up the 3340PU190 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 606 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Flush Water

Regrind Cyclone
Feed Flowrate
3340-XV-612B 3340-XV-384B
3340-LCV-611 3340-XV-388A
Tails Launder
Process Water
Make-Up LC
3340611
Prod Cyclone 3340PU111
O/Flow
FC SC
3340PU110 DC
LT SC 3340380 3340384
3340381
3340612 3340-XV-386A
3340-XV-384D
3340-XV-612A M DT FT
M
Milled Conc
Return
3340-BX-106
3340-XV-384A 3340 – PU – 111 3340-XV-386B
3340 – PU – 110

3340-XV-384C

3340389
3340-XV-612C

FSL

FAL
Milled Conc
Return

FAL
3340-XV-389
3340614
3340-XV-614 Milled Conc
Return
3340-XV-386C
FSL

DC
FC SC 3340-XV-385D
SC 3340382 3340-XV-385B 3340385
3340-XV-613B 3340383
3340613

3340-XV-613A M
M DT FT

3340-XV-385A 3340 – PU – 191


3340PU190 3340 – PU - 190
3340-XV-613C 3340-XV-384C 3340PU191
3340390
FSL

FAL
FAL
3340615
3340-XV-615
3340-XV-390 Tails Launder
FSL
3340-XV-387A
GSW

HP GSW

Figure 86: Blockflow Control Diagram of the 3340PU190 System

26.2.2 Unit of Control Modules – 3340PU190

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN CRCFP_RETORNOCONC EM 3340PU190 Sub EM

Tag Service
3340-PU-190 Concentrate Return Pump 3
3340-FSL-615 GLAND SEAL WATER Flow switch
3340-XV-613A SUCTION Valve OF SLURRY PUMP 3340-PU-190
3340-XV-613B Suction Flush Water Isolation
3340-XV-613C Suction Drian Valve
3340-XV-615 Gland Seal Water Isolation

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 607 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 757: List of Unit Controls – 3340PU190

26.2.3 Interlocks – 3340PU190

T2 Interlock
Tag 3340-XV-613A Description Suction valve
CRCFP_RETOR Sub
UN EM 3340PU190
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-613C.OP Suction drain valve open


OR OR ×
3340-XV-613C.OPNG Suction drain valve opening
3340-PU-190.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-613A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-613A.OPNG)

Table 758: List of Interlocks for 3340-XV-613A

T2 Interlock
Tag 3340-XV-613B Description Suction Flush Water Valve
CRCFP_RETOR Sub
UN EM 3340PU190
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 759: List of Interlocks for 3340-XV-613B

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 608 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Tag 3340-XV-613C Description Suction Drain Water Valve
CRCFP_RETOR Sub
UN EM 3340PU190
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 760: List of Interlocks for 3340-XV-613C

T2 Interlock
Tag 3340 – PU – 190 Description Concentrate Return Pump 3
CRCFP_RETOR Sub
UN EM 3340PU190
NOCONC EM
Interlock
Motor Type VFD Intlck_3340BB_SL_01
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-615 !OP ×
If gland seal water valve not open and
AND Note 1
pump is running
3340-PU-190.MO1.Run
3340-FSL-615.ACT × Note 1
Flow switch has a low flow alarm for a
AND Time Delay
time delay and pump is running
3340-PU-190-MO1.Run 300 seconds
3340-FSL-615.ACT Flow switch has a low flow alarm × Note 1
3340-XV-613A CL ×
Note 1
OR CLN Suction valve is closed or closing and
Time Delay
AND pump is running for a time delay
10 seconds
3340-PU-190-MO1.Run
× Note 1
3340-XV-613C. OP OR
Suction drain valve is open or opening Debounce
OPN
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-387A !OP If both discharge valves not open and ×
Note 1
AND pump is running for a time delay

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 609 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-385A !OP Time Delay


3340-PU-190.MO1.Run 30 seconds
3340-FIT-382.LL AND × Note 1
Slurry flowrate is Low Low and pump is
3340-PU-190- Time Delay
running
MO1.RUN 600 seconds
3340 TE - 384 Pump Thermistor alarm ×

Table 761: List of Interlocks for 3340 – PU - 190

T2 Interlock
Tag 3340-XV-615 Description Pump Gland Seal Water Valve
CRCFP_RETOR Sub
UN EM 3340PU190
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-PU-190.!RUN If the pump is not running ×

Table 762: List of Interlocks for 3340-XV-615

26.2.4 Alarms and Process Setpoints – 3340PU190

T3 Alarms and Process Setpoints


UN CRCFP_RETORNOCONC EM 3340PU190 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340 FSL -
615 3340-PU-190 pump flow switch 0 – 5.1 m3/hr 2.7

Table 763: Alarms and Process Setpoint 3340PU190

26.2.5 Binary Messages – 3340PU190

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 610 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

26.2.6 Regulatory Control Loops – 3340PU190

Not applicable. Refer to section CRCFP_RETORNOCONC

26.2.7 Advanced Control Loops – 3340PU190

Not applicable

26.2.8 Sequence Description – 3340PU190

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped.
The pump is started by pumping slurry to the tails launder. In order to then change the discharge
location to the concentrator, the second stage pump start sequence must be initiated.
The pump start sequence 3340-PU-190, shall follow the following steps:
TSQST Start Sequence Table
UN CRCFP_RETORNOCONC EM 3340PU190 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Close 3340-XV-613C Suction drain Valve Closed
seconds seconds
(Open &
Low Flow
2 60
2. Open 3340-XV-615 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
Discharge Valve to Tails 2 120
3. Open 3340-XV-387A Open
Launder seconds seconds
Suction Valve - second stage 2 120
4. Close 3340 – XV – 384A Close
pump seconds seconds
2 120
5. Open 3340-XV-613B Suction Valve. Open
seconds seconds
10 60
6. Start 3340-PU-190.MO1 Start pump. Working
seconds seconds

Table 764: Start Sequence 3340PU106

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-190 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-190-MO1 stopped
The pump stop sequence 3340-PU-190, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 611 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Stop Sequence Table


UN CRCFP_RETORNOCONC EM 3340PU190 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-190.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3340-PU-190.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3340-XV-613A Suction Valve. Closed
seconds seconds
Suction Valve - second stage 2 60
4. Close 3340-XV-385A Closed
pump seconds seconds
2 60
5. Open 3340-XV-387A Discharge Valve to Tails Launder Opened
seconds seconds
2 60
5. Open 3340-XV-613C Suction Drain valve Opened
seconds seconds
2 20
6. Close 3340-XV-615 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-613B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-613B Closed
valve seconds seconds

Table 765: Stop Sequence 3340PU190

The Shutter of the Nuclear Density Meter (3340-DX-383) will open 5 seconds after the pump
3340-PU-190 is operational. The shutter will close when the Pump is not running.

26.3 Engineering Module– 3340PU111

26.3.1 Description – 3340PU111

The following figure shows the elements that make up the 3340PU111 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 612 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Flush Water

Regrind Cyclone
Feed Flowrate
3340-XV-612B 3340-XV-384B
3340-LCV-611 3340-XV-388A
Tails Launder
Process Water
Make-Up LC
3340611
Prod Cyclone 3340PU111
O/Flow
FC SC
3340PU110 DC
LT SC 3340380 3340384
3340381
3340612 3340-XV-386A
3340-XV-384D
3340-XV-612A M DT FT
M
Milled Conc
Return
3340-BX-106
3340-XV-384A 3340 – PU – 111 3340-XV-386B
3340 – PU – 110

3340-XV-384C

3340389
3340-XV-612C

FSL

FAL
Drain to 3340-
BX-103

FAL
3340-XV-389
3340614
3340-XV-614 Recirc to
3340-BX-103
3340-XV-386C
FSL

DC
FC SC 3340-XV-385D
SC 3340382 3340-XV-385B 3340385
3340-XV-613B 3340383
3340613

3340-XV-613A M
M DT FT

3340-XV-385A 3340 – PU – 191


3340PU190 3340 – PU - 190
3340-XV-613C 3340-XV-384C 3340PU191
3340390
FSL

FAL
FAL
3340615
3340-XV-615
3340-XV-390 Tails Launder
FSL
3340-XV-387A
GSW

HP GSW

Figure 87: Blockflow Control Diagram of the 3340PU111 System

26.3.2 Unit of Control Modules – 3340PU111

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN CRCFP_RETORNOCONC EM 3340PU111 Sub EM

Tag Service
3340-PU-111 Concentrate Return Pump 2
3340-XV-384D DISCHARGE Valve OF CONCENTRATE PUMP 3340-PU-111
3340-XV-384A SUCTION Valve OF CONCENTRATE PUMP 3340-PU-111
3340-FSL-389 GLAND SEAL WATER FLOWSWITCH
3340-XV-384B FLUSH WATER ISOLATION To Pump Suction
3340-XV-384C Suction Drian Valve

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 613 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-386A Concentrate Slurry to Concentrator Isolation Valve


3340-XV-386B Concentrate Slurry to Concentrator drain Valve
3340-XV-386C CPF Concentrate Recirculation Isolation Valve
3340-XV-388A Concentrate Purge to Tails Launder Isolation Valve
3340-XV-389 GLAND SEAL WATER Isolation Valve

Table 766: List of Unit Controls – 3340PU111

26.3.3 Interlocks – 3340PU111

T2 Interlock
Tag 3340-XV-384A Description Suction valve
CRCFP_RETOR Sub
UN EM 3340PU111
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340-XV-384C.OP Suction drain valve open


OR OR ×
3340-XV-384C.OPNG Suction drain valve opening
3340-PU-111.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-384A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-384A.OPNG)
3340-XV-388A . OP or If concentrate tails launder isolation valve Time Delay
×
OPN is open or opening for a time delay 30 seconds

Table 767: List of Interlocks for 3340-XV-384A

T2 Interlock
Tag 3340-XV-384B Description Suction Flush Water Valve
CRCFP_RETOR Sub
UN EM 3340PU111
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 614 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 768: List of Interlocks for 3340-XV-384B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Tag 3340-XV-384C Description Suction Drain Water Valve
CRCFP_RETOR Sub
UN EM 3340PU111
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 769: List of Interlocks for 3340-XV-384C

T2 Interlock
Tag 3340 – PU – 111 Description Concentrate Return Pump 2
CRCFP_RETOR Sub
UN EM 3340PU111
NOCONC EM
Interlock
Motor Type VFD Intlck_3340BB_SL_01
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-389 !OP ×
If gland seal water valve not open and
AND Note 1
pump is running
3340-PU-111.MO1.Run
3340-FSL-389.ACT Flow switch has a low flow alarm for a ×
Note 1
AND time delay and pump is running

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 615 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PU-111-MO1.Run Time Delay


300 seconds
3340-FSL-389.ACT Flow switch has a low flow alarm × Note 1
3340-XV-384A CL ×
Note 1
OR CLN Suction valve is closed or closing and
Time Delay
AND pump is running for a time delay
10 seconds
3340-PU-111-MO1.Run
× Note 1
3340-XV-384C. OP OR
Suction drain valve is open or opening Debounce
OPN
If Discharge Valve not open for a delay Delay time
3340 XV –384D !OP ×
time 45 s
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-386A !OP ×
Note 1
AND If both discharge valves not open and
Time Delay
3340-XV-386C !OP pump is running for a time delay
30 seconds
3340-PU-111.MO1.Run
3340-FIT-380.LL AND × Note 1
Slurry flowrate is Low Low and pump is
3340-PU-111- Time Delay
running
MO1.RUN 600 seconds
3340 TE - 612 Pump Thermistor alarm ×

Table 770: List of Interlocks for 3340 – PU – 111

T2 Interlock
DISCHARGE ISOLATION VALVE OF
Tag 3340-XV-384D Description
SLURRY PUMP
CRCFP_RETOR Sub
UN EM 3340PU111
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If Conc Return Pump 4 discharge Delay time


3340 XV- 385D.!CL ×
valve is not closed 15 seconds

Table 771: List of Interlocks for 3340-XV-384D

T2 Interlock
Concentrate Return Line 2 Tails Launder
Tag 3340 XV –388A Description
Isolation Valve
CRCFP_RETOR
UN EM 3340PU111 Sub EM
NOCONC

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 616 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If 3340 XV - 384A . OP If the Second Stage Suction Valve is open Time Delay
×
for a time delay 30 s

Table 772: List of Interlocks for 3340 XV - 388A

T2 Interlock
Tag 3340-XV-389 Description Pump Gland Seal Water Valve
CRCFP_RETOR Sub
UN EM 3340PU111
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-PU-111.!RUN If the pump is not running ×

Table 773: List of Interlocks for 3340-XV-389

T2 Interlock
Concentrate Return Discharge Valve to
Tag 3340 XV –386A Description
Concentrator
CRCFP_RETOR
UN EM 3340PU111 Sub EM
NOCONC
Failure Position:
Keep Last (KL) Interlock Concentrate Return Discharge Valve to
Motor Type
Safe Position: Type Concentrator
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 617 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Concentrator Rougher All Concentrator Rougher Flotation lines


×
Not available Circuit are not available

Table 774: List of Interlocks for 3340 XV –386A

T2 Interlock
Concentrate Return Drain Valve to
Tag 3340 XV –386B Description
Concentrator
CRCFP_RETOR
UN EM 3340PU111 Sub EM
NOCONC
Failure Position:
Keep Last (KL)
Interlock Concentrate Return Drain Valve to
Motor Type Safe Position:
Type Concentrator
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

IF Concentrate Return Discharge Valve to


3340 XV –386A .OP ×
Concentrator is open
IF Concentrate Return Discharge Valve to
3340 XV –386A .CL Concentrator is closed, this drain valve ×
must open

Table 775: List of Interlocks for 3340 XV –386B

T2 Interlock
Concentrate Return Feed Tank Purge
Tag 3340 XV –386C Description
Valve
CRCFP_RETOR
UN EM 3340PU111 Sub EM
NOCONC
Failure Position:
Keep Last (KL)
Interlock Concentrate Return Feed Tank Purge
Motor Type Safe Position:
Type Valve
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 618 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340 XV –386A. OP or If Concentrate Return Discharge Valve to


×
OPN Concentrator is open or opening
IF Concentrate Return Discharge Valve to
3340 XV –386A . CL Concentrator is closed, this drain valve ×
must open

Table 776: List of Interlocks for 3340 XV –386C

26.3.4 Alarms and Process Setpoints – 3340PU111

T3 Alarms and Process Setpoints


UN CRCFP_RETORNOCONC EM 3340PU111 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340 FSL -
614 3340-PU-111 pump flow switch 0 – 5.1 m3/hr 2.7

Table 777: Alarms and Process Setpoint 3340PU111

26.3.5 Binary Messages – 3340PU111

Not applicable
26.3.6 Regulatory Control Loops – 3340PU111

Not applicable. Refer to section CRCFP_RETORNOCONC

26.3.7 Advanced Control Loops – 3340PU111

Not applicable

26.3.8 Sequence Description – 3340PU111

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. As a pre-requisite for this sequence to run, the first stage pump must be running with
the slurry discharging to the tails launder (i.e. 3340-XV-388A is open) and 3340-XV-384A is
closed).
The pump is started by pumping slurry to the tails launder. In order to then change the discharge
location to the concentrator, the second stage pump start sequence must be initiated.
The pump start sequence 3340-PU-111, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 619 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN CRCFP_RETORNOCONC EM 3340PU111 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Close 3340-XV-384C Suction drain Valve Closed
seconds seconds
(Open &
Low Flow
2 60
2. Open 3340-XV-389 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
Discharge Valve to 2 120
3. Open 3340-XV-386A Open
Concentrator seconds seconds
Discharge Drain Valve to 2 120
4. Close 3340-XV-386B Close
Concentrator seconds seconds
Concentrate Return Feed Tank 2 120
5. Close 3340-XV-386C Close
Purge Valve seconds seconds
Suction Valve - second stage 2 120
6. Close 3340 – XV – 384A Close
pump seconds seconds
10 60
7. Start 3340-PU-111.MO1 Start pump. Working
seconds seconds

Table 778: Start Sequence 3340PU111

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-111 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-111-MO1 stopped
The pump stop sequence 3340-PU-111, shall follow the following steps:
TSQST Stop Sequence Table
UN CRCFP_RETORNOCONC EM 3340PU111 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-111.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3340-PU-111.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3340-XV-384A Suction Valve. Closed
seconds seconds
2 60
4. Close 3340-XV-386A Discharge Valve to Concentrator Opened
seconds seconds
2 60
5. Open 3340-XV-384C Suction Drain valve Opened
seconds seconds
Discharge Valve to Concentrator 2 60
4. Open 3340-XV-386B Opened
drain valve seconds seconds
2 20
6. Close 3340-XV-389 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-384B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-384B Closed
valve seconds seconds

Table 779: Stop Sequence 3340PU111

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 620 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The first stage pump will swing over to discharge into the tails launder and its speed adjusted to
control the level in the concentrate return pump box (3340-BX-106).

26.4 Engineering Module– 3340PU191

26.4.1 Description – 3340PU191

The following figure shows the elements that make up the 3340PU191 equipment module.
Flush Water

Regrind Cyclone
Feed Flowrate
3340-XV-612B 3340-XV-384B
3340-LCV-611 3340-XV-388A
Tails Launder
Process Water
Make-Up LC
3340611
Prod Cyclone 3340PU111
O/Flow
FC SC
3340PU110 DC
LT SC 3340380 3340384
3340381
3340612 3340-XV-386A
3340-XV-384D
3340-XV-612A M DT FT
M
Milled Conc
Return
3340-BX-106
3340-XV-384A 3340 – PU – 111 3340-XV-386B
3340 – PU – 110

3340-XV-384C

3340389
3340-XV-612C
FSL

FAL
Drain to 3340-
BX-103

FAL
3340-XV-389
3340614
3340-XV-614 Recirc to
3340-BX-103
3340-XV-386C
FSL

DC
FC SC 3340-XV-385D
SC 3340382 3340-XV-385B 3340385
3340-XV-613B 3340383
3340613

3340-XV-613A M
M DT FT

3340-XV-385A 3340 – PU – 191


3340PU190 3340 – PU - 190
3340-XV-613C 3340-XV-384C 3340PU191
3340390
FSL

FAL

FAL
3340615
3340-XV-615
3340-XV-390 Tails Launder
FSL
3340-XV-387A
GSW

HP GSW

Figure 88: Blockflow Control Diagram of the 3340PU191 System

26.4.2 Unit of Control Modules – 3340PU191

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN CRCFP_RETORNOCONC EM 3340PU191 Sub EM

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 621 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag Service
3340-PU-191 Concentrate Return Pump 2
3340-XV-385D DISCHARGE Valve OF CONCENTRATE PUMP 3340-PU-191
3340-XV-385A SUCTION Valve OF CONCENTRATE PUMP 3340-PU-191
3340-FSL-390 GLAND SEAL WATER FLOWSWITCH
3340-XV-385B FLUSH WATER ISOLATION To Pump Suction
3340-XV-385C Suction Drian Valve
3340-XV-387A Concentrate Purge to Tails Launder Isolation Valve
3340-XV-390 GLAND SEAL WATER Isolation Valve

Table 780: List of Unit Controls – 3340PU191

26.4.3 Interlocks – 3340PU191

T2 Interlock
Tag 3340-XV-385A Description Suction valve
CRCFP_RETOR Sub
UN EM 3340PU191
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-XV-385C.OP Suction drain valve open


OR OR ×
3340-XV-385C.OPNG Suction drain valve opening
3340-PU-191.!RUN
Pump Stopped
AND
AND Time Delay
(3340-XV-385A.OP ×
Suction Valve Open OR Opening 180 seconds
OR
3340-XV-385A.OPNG)
3340-XV-387A . OP or If concentrate tails launder isolation valve Time Delay
×
OPN is open or opening for a time delay 30 seconds

Table 781: List of Interlocks for 3340-XV-385A

T2 Interlock
Tag 3340-XV-385B Description Suction Flush Water Valve
CRCFP_RETOR Sub
UN EM 3340PU191
NOCONC EM

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 622 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 782: List of Interlocks for 3340-XV-385B

Note Order of precedence for flush water valve opening shall be adhered to. Refer to flush water pump
(3340-PU-115) control specifications.

T2 Interlock
Tag 3340-XV-385C Description Suction Drain Water Valve
CRCFP_RETOR Sub
UN EM 3340PU191
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Table 783: List of Interlocks for 3340-XV-385C

T2 Interlock
Tag 3340 – PU – 191 Description Concentrate Return Pump 4
CRCFP_RETOR Sub
UN EM 3340PU191
NOCONC EM
Interlock
Motor Type VFD Intlck_3340BB_SL_01
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 623 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-XV-390 !OP ×
If gland seal water valve not open and
AND Note 1
pump is running
3340-PU-191.MO1.Run
3340-FSL-390.ACT × Note 1
Flowswitch has a low flow alarm for a time
AND Time Delay
delay and pump is running
3340-PU-191-MO1.Run 300 seconds
3340-FSL-390.ACT Flowswitch has a low flow alarm × Note 1
3340-XV-385A CL ×
Note 1
OR CLN Suction valve is closed or closing and
Time Delay
AND pump is running for a time delay
10 seconds
3340-PU-191-MO1.Run
× Note 1
3340-XV-385C. OP OR
Suction drain valve is open or opening Debounce
OPN
If Discharge Valve not open for a delay Delay time
3340 XV –385D !OP ×
time 45 s
BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-386A !OP ×
Note 1
AND If both discharge valves not open and
Time Delay
3340-XV-386C !OP pump is running for a time delay
30 seconds
3340-PU-191.MO1.Run
3340-FIT-382.LL AND × Note 1
Slurry flowrate is Low Low and pump is
3340-PU-191- Time Delay
running
MO1.RUN 600 seconds
3340 TE - 385 Pump Thermistor alarm ×

Table 784: List of Interlocks for 3340 – PU – 191

T2 Interlock
DISCHARGE ISOLATION VALVE OF
Tag 3340-XV-385D Description
SLURRY PUMP
CRCFP_RETOR Sub
UN EM 3340PU191
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

If Conc Return Pump 3 discharge Delay time


3340 XV- 384D.!CL ×
valve is not closed 15 seconds

Table 785: List of Interlocks for 3340-XV-385D

T2 Interlock

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 624 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Concentrate Return Line 2 Tails Launder


Tag 3340 XV –387A Description
Isolation Valve
CRCFP_RETOR
UN EM 3340PU191 Sub EM
NOCONC
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position:
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

If 3340 XV - 385A . OP If the Second Stage Suction Valve is open Time Delay
×
for a time delay 30 s

Table 786: List of Interlocks for 3340 XV - 387A

T2 Interlock
Tag 3340-XV-390 Description Pump Gland Seal Water Valve
CRCFP_RETOR Sub
UN EM 3340PU191
NOCONC EM
Failure Position:
Keep Last (KL)
Interlock Intlck_VLV_gland seal water
Motor Type Safe Position:
Type O_01
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

3340-PU-191.!RUN If the pump is not running ×

Table 787: List of Interlocks for 3340-XV-390

26.4.4 Alarms and Process Setpoints – 3340PU191

T3 Alarms and Process Setpoints


UN CRCFP_RETORNOCONC EM 3340PU191 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340 FSL -
614 3340-PU-191 pump flowswitch 0 – 5.1 m3/hr 2.7

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 625 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 788: Alarms and Process Setpoint 3340PU191

26.4.5 Binary Messages – 3340PU191

Not applicable
26.4.6 Regulatory Control Loops – 3340PU191

Not applicable. Refer to section CRCFP_RETORNOCONC

26.4.7 Advanced Control Loops – 3340PU191

Not applicable

26.4.8 Sequence Description – 3340PU191

The pump has its own system of suction, drain and flush valves, for when the pump is started or
stopped. As a pre-requisite for this sequence to run, the first stage pump must be running with
the slurry discharging to the tails launder (ie 3340-XV-387A is open) and 3340-XV-385A is
closed).
The pump is started by pumping slurry to the tails launder. In order to then change the discharge
location to the concentrator, the second stage pump start sequence must be initiated.
The pump start sequence 3340-PU-191, shall follow the following steps:
TSQST Start Sequence Table
UN CRCFP_RETORNOCONC EM 3340PU191 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 60
1. Close 3340-XV-385C Suction drain Valve Closed
seconds seconds
(Open &
Low Flow
2 60
2. Open 3340-XV-390 Gland seal water valve Switch
seconds seconds
Ok) for 10
Sec
Discharge Valve to 2 120
3. Open 3340-XV-386A Open
Concentrator seconds seconds
Discharge Drain Valve to 2 120
4. Close 3340-XV-386B Close
Concentrator seconds seconds
Concentrate Return Feed Tank 2 120
5. Close 3340-XV-386C Close
Purge Valve seconds seconds
Suction Valve - second stage 2 120
6. Close 3340 – XV – 385A Close
pump seconds seconds
10 60
7. Start 3340-PU-191.MO1 Start pump. Working
seconds seconds

Table 789: Start Sequence 3340PU191

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 626 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-191 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-191-MO1 stopped
The pump stop sequence 3340-PU-191, shall follow the following steps:
TSQST Stop Sequence Table
UN CRCFP_RETORNOCONC EM 3340PU191 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-191.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3340-PU-191.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3340-XV-385A Suction Valve. Closed
seconds seconds
2 60
4. Close 3340-XV-386A Discharge Valve to Concentrator Opened
seconds seconds
2 60
5. Open 3340-XV-385C Suction Drain valve Opened
seconds seconds
Discharge Valve to Concentrator 2 60
4. Open 3340-XV-386B Opened
drain valve seconds seconds
2 20
6. Close 3340-XV-390 Gland Seal Water Valve Closed
seconds seconds
Open for
Flush Water valve, post-suction 20 60
7. Open 3340-XV-385B 20
valve seconds seconds
seconds
Flush Water valve, post-suction 2 20
8. Close 3340-XV-385B Closed
valve seconds seconds

Table 790: Stop Sequence 3340PU191

The first stage pump will swing over to discharge into the tails launder and its speed adjusted to
control the level in the concentrate return pump box (3340-BX-106).

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 627 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

27.0 UNIDAD: SCPF_AGUAPROCESOS

Refer to:
MQ14-08-DR-3340-PD1088 Fluidisation and Flush Water Pumps
MQ14-08-DR-3340-PD1089 Process Water Pumping
MQ14-08-DR-3340-PD1104 Froth Suppression and Flush Water Pumps
MQ15-715-DC-3340-IN0101 Control System and Philosophy (Vendor)

A block flow control diagram is depicted below for the SCPF_AGUAPROCESOS system.
3720PU007

SC
3720109
M 3720-XV-110
DRA
Process Water
Make-Up
Fluor
3720 – PU - 007 PC
3720116

3720PU008
PT
SC
M 3720-XV-115 CPF Process
3720114 Water

3720 – PU - 008

SC PC
3340-XV-645A M 3340PU112
3340644 3340647

3340-XV-644A 3340-PIT-647
3340-LIT-643 PT

3340 – PU - 112 CPF Fluidisation


LC Water
LT
3340643
SC
3340645
M
3340PU114
3340 – TK - 104
3340-XV-645A
3340 – PU - 114
LC
3340-LIT-648
LT PC
3340648
3340647

SC
3340646
M 3340PU115
PT
3340 – TK - 102 Flush Water

3340 – PU - 115

3340-LIT-649
LC
LT
3340649 3340PU109 PC
3340650
SC 3340 – PU - 109
M
3340649 PT
Froth Supp &
3340 – TK - 103 Dilution

Figure 89: Blockflow Control Diagram of SCPF_AGUAPROCESOS

The above control unit is broken into six Engineering Module 1 with zero sub Engineering Module 2’s:
- 3720PU007

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 628 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

- 3720PU008
- 3340PU112
- 3340PU114
- 3340PU109
- 3340PU115

27.0.1 Modules of Control SCPF_AGUAPROCESOS

T1 Control Mod
Sub
UN SCPF_AGUAPROCESOS EM
EM

Tag Service
3340-TK-102 Fluidization Water Tank 2
3340-LIT-648 LEVEL INDICATOR TRANSMITTER Tank 2
3340-TK-103 Fluidization Water Tank 3
3340-LIT-649 LEVEL INDICATOR TRANSMITTER Tank 3
3340-TK-104 Fluidization Water Tank 1
3340-LIT-643 LEVEL INDICATOR TRANSMITTER Tank 1
3340-XV-640A PROCESS WATER TO TANK 3340-TK-104

Table 791: List of Modules of Control for CRCFP_RETORNOCONC

27.0.2 Interlocks – SCPF_AGUAPROCESOS

T2 Interlock
Tag 3340-XV-640A Description PROCESS WATER TO TANK 3340-TK-104
SCPF_AGUAPR
UN EM Sub EM
OCESOS
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Fluidization Water Tank Make-Up Valve


3340- LT –643 . L or LL must open if the tank level is Low or Low ×
Low.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 629 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Fluidization Water Tank Make-Up Valve


3340- LT – 643 .H or
must close if the tank level is High or High ×
HH
High

Table 792: List of Interlocks for 3340-XV-640A

27.0.3 Alarms and Process Setpoints – SCPF_AGUAPROCESOS

T3 Alarms and Process Setpoints


UN SCPF_AGUAPROCESOS EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340- LIT - Level Transmitter of Fluidisation
643 Water Tank 1
0 - 100 % 99 908 709 30
3340- LIT - Level Transmitter of Fluidisation
648 0 - 100 % 99 30
Water Tank 2
3340- LIT - Level Transmitter of Fluidisation
649 0 - 100 % 99 30
Water Tank 3
IF (3340- LIT
–643) >≠
Average of
3340- LIT-643
Alarm if tank level more than
AND
percentage difference to the 0 - 100 % 5
3340- LIT-648 average of all three tanks.

AND
3340- LIT-649
IF (3340- LIT
–648) >≠
Average of
3340- LIT-643
Alarm if tank level more than
AND
percentage difference to the 0 - 100 % 5
3340- LIT-648 average of all three tanks.

AND
3340- LIT-649
IF (3340- LIT
–649) >≠
Average of
3340- LIT-643 Alarm if tank level more than
AND percentage difference to the 0 - 100 % 5
average of all three tanks.
3340- LIT-648
AND

8
No High alarm signal required for operator acknowledgement. This is used for process control only
9
No Low alarm signal required for operator acknowledgement. This is used for process control only

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 630 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340- LIT-649

Table 793: Alarms and Process Setpoint SCPF_AGUAPROCESOS

27.0.4 Binary Messages – SCPF_AGUAPROCESOS

T4 Binary State Messages


UN SCPF_AGUAPROCESOS EM Sub EM
Tag Description OFF ON
IF (3340- LIT –
643) >≠
Average of
3340- LIT-643
Level in 3340-TK-104 differs from
AND
average level in Fluidisation Water × Note 1
3340- LIT-648 Tanks

AND
3340- LIT-649
3340-LIT-643
.LL Level in 3340-TK-104 is Low Low ×

3340-LIT-643
.HH Level in 3340-TK-104 is High High ×

IF (3340- LIT –
648) >≠
Average of
3340- LIT-643
Level in 3340-TK-102 differs from
AND
average level in Fluidisation Water × Note 1
3340- LIT-648 Tanks

AND
3340- LIT-649
3340-LIT-648
.LL Level in 3340-TK-102 is Low Low ×

3340-LIT-648
.HH Level in 3340-TK-102 is High High ×

IF (3340- LIT –
649) >≠
Average of
3340- LIT-643
Level in 3340-TK-103 differs from
AND
average level in Fluidisation Water × Note 1
3340- LIT-648 Tanks

AND
3340- LIT-649
3340-LIT-649
.LL Level in 3340-TK-103 is Low Low ×

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 631 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-LIT-649
.HH Level in 3340-TK-103 is High High ×

Table 794: Binary State Messages SCPF_AGUAPROCESOS

Note:
1) It is possible to manually isolate the Fluidisation water tanks 2 and 3 while the plant
continues to operate at reduced water tank residence times. Alarm message is to alert the
control room operator of this condition.
2) An alarm message is required to alert the control room operator as to the Low Low level
in the Fluidisation Water Tanks. At Low Low levels within the Fluidisation Water Tanks,
certain pumps are stopped within the CPF to in order to allow downstream slurry pipelines
to have their solids content reduced thereby preventing blockages should the level in the
tanks continues to reduce.
3) An alarm message is required to alert the control room operator as to the High High level
in the Fluidisation Water Tanks.

27.0.5 Regulatory Control Loops – SCPF_AGUAPROCESOS

Not applicable.
The Fluidisation Water Tank Make-Up Valve is to open when the tank level is Low or Low Low
and close when the level reaches High or High High.

27.0.6 Advanced Control Loops – SCPF_AGUAPROCESOS

Not applicable

27.0.7 Sequence Description – SCPF_AGUAPROCESOS

Three Fluidisation Water Tanks (3340 – TK – 102 / 103 / 104) are hydraulically connected in
parallel with each other and provide the storage capacity necessary for the CPF fluidisation, flush
and froth suppression water requirements. The tank levels are measured by individual level
transmitters (3340- LIT-643 / 648 & 649) respectively. Unless a tank is bypassed, they should
provide very similar readings. Should the readings differ by a significant margin, an alarm will be
generated.
The tanks are filled with water via the CPF make-up water pumps via an open/shut isolation valve
(3340- XV-640A) and mechanical pressure sustaining valve (3340- PCV-642). The make-up
water valve will open on a Low level and close on a High Level in tank in 3340-TK-104. In the
event of a High High or Low Low level, an alarm will be generated.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 632 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

27.1 Engineering Module– 3340PU112

27.1.1 Description – 3340PU112

The following figure shows the elements that make up the 3340PU112 equipment module.
3720PU007

SC
3720109
M 3720-XV-110
DRA
Process Water
Make-Up
Fluor
3720 – PU - 007 PC
3720116

3720PU008
PT
SC
M 3720-XV-115 CPF Process
3720114 Water

3720 – PU - 008

SC PC
3340-XV-645A M 3340PU112
3340644 3340647

3340-XV-644A 3340-PIT-647
3340-LIT-643 PT
CPF Fluidisation
3340 – PU - 112 Water
LC
LT
3340643
SC
3340645
M
3340PU114
3340 – TK - 104
3340-XV-645A
3340 – PU - 114
LC
3340-LIT-648
LT PC
3340648
3340647

SC
3340646
M 3340PU115 PT
3340 – TK - 102 Flush Water

3340 – PU - 115

3340-LIT-649
LC
LT
3340649 3340PU109 PC
3340650
SC 3340 – PU - 109
M
3340649 PT
Froth Supp &
3340 – TK - 103 Dilution

Figure 90: Blockflow Control Diagram of the 3340PU112 System

27.1.2 Unit of Control Modules – 3340PU112

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_AGUAPROCESOS EM 3340PU112 Sub EM

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 633 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Tag Service
3340-PU-112 Fluidization Water Pump 1
3340-PIT-647 PRESSURE INDICATOR TRANSMITTER 3340-PU-112
3340-XV-644A DISCHARGE OF WATER PUMP 3340-PU-112
3340-VT-644B VIBRATION TRANSMITTER 3340-PU-112
3340-VT-644A VIBRATION TRANSMITTER 3340-PU-112
3340- TE – 644A Process Fluidization Water Make-Up Pump 1 Temperature Switch A
3340- TE – 644B Process Fluidization Water Make-Up Pump 1 Temperature Switch B
3340- TE – 644C Process Fluidization Water Make-Up Pump 1 Temperature Switch C
3340- TE – 644D Process Fluidization Water Make-Up Pump 1 Temperature Switch D
3340- TE – 644E Process Fluidization Water Make-Up Pump 1 Temperature Switch E
3340- TE – 644F Process Fluidization Water Make-Up Pump 1 Temperature Switch F
3340- TE – 644G Process Fluidization Water Make-Up Pump 1 Temperature Switch G
3340- TE – 644H Process Fluidization Water Make-Up Pump 1 Temperature Switch H

Table 795: List of Unit Controls – 3340PU112

27.1.3 Interlocks – 3340PU112

T2 Interlock
Tag 3340-PU-112 Description Fluidization Water Pump 1
SCPF_AGUAPR Sub
UN EM 3340PU112
OCESOS EM
Interlock
Motor Type VFD Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. MQ15-715-DC-3340-IN0101

BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-644A !OP ×
If discharge valve not open and pump is Time Delay
AND
running for a time delay 45 seconds
3340-PU-112.MO1.Run
3340-PIT-647 .LL If discharge pressure is Low Low for a
Delay time 5
AND time delay ×
minutes
3340-PU-112.MO1.Run

Table 796: List of Interlocks for 3340-PU-112

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 634 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

T2 Interlock
Tag 3340-XV-644A Description DISCHARGE OF WATER PUMP 3340-PU-112
SCPF_AGUAPR Sub
UN EM 3340PU112
OCESOS EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340 – PU – 112-MO1 Time delay


If pump is not running for a time delay ×
.!RN 10 seconds

Table 797: List of Interlocks for 3340-XV-644A

27.1.4 Alarms and Process Setpoints – 3340PU112

T3 Alarms and Process Setpoints


UN SCPF_AGUAPROCESOS EM 3340PU112 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

Refer to vendor control philosophy for equipment package specific alarms and setpoints MQ15-715-DC-3340-IN0101
Fluidization Water Pump
3340-PT-647 0 - 1000 KPa 460 420
Discharge Pressure Transmitter

Table 798: Alarms and Process Setpoint 3340PU112

27.1.5 Binary Messages – 3340PU112

T4 Binary State Messages


UN SCPF_AGUAPROCESOS EM 3340PU112 Sub EM
Tag Description OFF ON
3340-PT-647.L
or LL for 2 Fluidisation Water Pressure is Low or
×
minutes Low Low

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 635 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 799: Binary State Messages 3340PU112

Note:
1) Both Fluidisation Water Pumps discharge into a common header providing water to the
(10 installed + 2 future) modules. Each pump has the capacity to provide water to six
modules.

27.1.6 Regulatory Control Loops – 3340PU112

T5 Regulatory Control Loops


UN SCPF_AGUAPROCESOS EM 3340PU112 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
75 - 100 % KPa 0 - 1000 460 – Expected
Fluidisation Water Pump Discharge
3340-PC-647 1000 setpoint 520
Header Pressure Control
KPa

Table 800: Regulatory Control Loops for 3340PU112

The common pressure controller adjusts the speed of both Fluidisation Water Pumps (3340-PU-
112 and 3340-PU-114) to maintain the selected setpoint.

27.1.7 Advanced Control Loops – 3340PU112

Not applicable

27.1.8 Description – 3340PU112

Two variable speed Fluidisation Water Pumps (3340 – PU – 112 / 114) provide the fluidisation
water requirements for the Crossflow Separators and Hydrofloats via a common header pipe.
Each pump has sufficient capacity for six crossflow/hydrofloat modules. It is therefore very likely
that both pumps will always be required to run for the CPF to operate and therefore no swingover
sequence is provided. The fluidisation water pressure is measured via pressure transmitter (3340-
PIT – 647) and controlled by Proportional, Integral, Differential (PID) loop controller to achieve
the required setpoint pressure by varying the speeds of the pumps. An alarm will activate if the
line pressure is Low after running a pump for the specified time.
Following a start signal to the pump, the motor must ramp up from its minimum speed setpoint
and the discharge valve is to commence opening immediately. This will ensure that sufficient
back-pressure always exists on the pump.

The pump start sequence 3340-PU-112, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 636 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SCPF_AGUAPROCESOS EM 3340PU112 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Start pump at minimum speed 10 60
1. Start 3340-PU-112.MO1 Working
allowing speed control ramp up seconds seconds
2 120
2. Open 3340-XV-644A Discharge Valve Open
seconds seconds

Table 801: Start Sequence 3340PU112

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-112 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-112-MO1 stopped
The pump stop sequence 3340-PU-112, shall follow the following steps:
TSQST Stop Sequence Table
UN SCPF_AGUAPROCESOS EM 3340PU112 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-112.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3340-PU-112.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3340-XV-644A Discharge Valve. Closed
seconds seconds

Table 802: Stop Sequence 3340PU112

27.2 Engineering Module– 3340PU114

27.2.1 Description – 3340PU114

The following figure shows the elements that make up the 3340PU114 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 637 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3720PU007

SC
3720109
M 3720-XV-110
DRA
Process Water
Make-Up
Fluor
3720 – PU - 007 PC
3720116

3720PU008
PT
SC
M 3720-XV-115 CPF Process
3720114 Water

3720 – PU - 008

SC PC
3340-XV-645A M 3340PU112
3340644 3340647

3340-XV-644A 3340-PIT-647
3340-LIT-643 PT

3340 – PU - 112 CPF Fluidisation


LC Water
LT
3340643
SC
3340645
M
3340PU114
3340 – TK - 104
3340-XV-645A
3340 – PU - 114
LC
3340-LIT-648
LT PC
3340648
3340647

SC
3340646
M 3340PU115
PT
3340 – TK - 102 Flush Water

3340 – PU - 115

3340-LIT-649
LC
LT
3340649 3340PU109 PC
3340650
SC 3340 – PU - 109
M
3340649 PT
Froth Supp &
3340 – TK - 103 Dilution

Figure 91: Blockflow Control Diagram of the 3340PU114 System

27.2.2 Unit of Control Modules – 3340PU114

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_AGUAPROCESOS EM 3340PU114 Sub EM

Tag Service
3340-PU-114 Fluidization Water Pump
3340-XV-645A DISCHARGE OF WATER PUMP
3340-VT-645B VIBRATION TRANSMITTER
3340-VT-645A VIBRATION TRANSMITTER
3340- TE – 654A PumpTemperature Switch A

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 638 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340- TE – 645B PumpTemperature Switch B


3340- TE – 645C PumpTemperature Switch C
3340- TE – 645D PumpTemperature Switch D
3340- TE – 645E PumpTemperature Switch E
3340- TE – 645F PumpTemperature Switch F
3340- TE – 645G PumpTemperature Switch G
3340- TE – 645H PumpTemperature Switch H

Table 803: List of Unit Controls – 3340PU114

27.2.3 Interlocks – 3340PU114

T2 Interlock
Tag 3340-PU-114 Description Fluidization Water Pump 2
SCPF_AGUAPR Sub
UN EM 3340PU114
OCESOS EM
Interlock
Motor Type VFD Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. MQ15-715-DC-3340-IN0101


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-645A !OP ×
If discharge valve not open and pump is Time Delay
AND
running for a time delay 45 seconds
3340-PU-114.MO1.Run
3340-PIT-647 .LL If discharge pressure is Low Low for a
Delay time 5
AND time delay ×
minutes
3340-PU-114.MO1.Run

Table 804: List of Interlocks for 3340-PU-114

T2 Interlock
Tag 3340-XV-645A Description DISCHARGE OF WATER PUMP
SCPF_AGUAPR Sub
UN EM 3340PU114
OCESOS EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 639 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340 – PU – 114-MO1 Time delay


If pump is not running for a time delay ×
.!RN 10 seconds

Table 805: List of Interlocks for 3340-XV-645A

27.2.4 Alarms and Process Setpoints – 3340PU114

T3 Alarms and Process Setpoints


UN SCPF_AGUAPROCESOS EM 3340PU114 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

Refer to vendor control philosophy for equipment package specific alarms and setpoints MQ15-715-DC-3340-IN0101

Table 806: Alarms and Process Setpoint 3340PU114

27.2.5 Binary Messages – 3340PU114

Not applicable

27.2.6 Regulatory Control Loops – 3340PU114

T5 Regulatory Control Loops


UN SCPF_AGUAPROCESOS EM 3340PU114 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
75 - 100 % KPa 0 - 1000 460 – Expected
Fluidisation Water Pump Discharge
3340-PC-647 1000 setpoint 520
Header Pressure Control
KPa

Table 807: Regulatory Control Loops for 3340PU114

The common pressure controller adjusts the speed of both Fluidisation Water Pumps (3340-PU-
112 and 3340-PU-114) to maintain the selected setpoint.

27.2.7 Advanced Control Loops – 3340PU114

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 640 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

27.2.8 Description – 3340PU114

Two variable speed Fluidisation Water Pumps (3340 – PU – 112 / 114) provide the fluidisation
water requirements for the Crossflow Separators and Hydrofloats via a common header pipe.
Each pump has sufficient capacity for six crossflow/hydrofloat modules. It is therefore very likely
that both pumps will always be required to run for the CPF to operate and therefore no swingover
sequence is provided. The fluidisation water pressure is measured via pressure transmitter (3340-
PIT – 647) and controlled by Proportional, Integral, Differential (PID) loop controller to achieve
the required setpoint pressure by varying the speeds of the pumps. An alarm will activate if the
line pressure is Low after running a pump for the specified time.
Following a start signal to the pump, the motor must ramp up from its minimum speed setpoint
and the discharge valve is to commence opening immediately. This will ensure that sufficient
back-pressure always exists on the pump.

The pump start sequence 3340-PU-114, shall follow the following steps:
TSQST Start Sequence Table
UN SCPF_AGUAPROCESOS EM 3340PU114 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Start pump at minimum speed 10 60
1. Start 3340-PU-114.MO1 Working
allowing speed control ramp up seconds seconds
2 120
2. Open 3340-XV-645A Discharge Valve Open
seconds seconds

Table 808: Start Sequence 3340PU114

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-114 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-114-MO1 stopped
The pump stop sequence 3340-PU-114, shall follow the following steps:
TSQST Stop Sequence Table
UN SCPF_AGUAPROCESOS EM 3340PU114 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3340-PU-114.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3340-PU-114.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3340-XV-645A Discharge Valve. Closed
seconds seconds

Table 809: Stop Sequence 3340PU114

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 641 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

27.3 Engineering Module– 3340PU115

27.3.1 Description – 3340PU115

The following figure shows the elements that make up the 3340PU115 equipment module.
3720PU007

SC
3720109
M 3720-XV-110
DRA
Process Water
Make-Up
Fluor
3720 – PU - 007 PC
3720116

3720PU008
PT
SC
M 3720-XV-115 CPF Process
3720114 Water

3720 – PU - 008

SC PC
3340-XV-645A M 3340PU112
3340644 3340647

3340-XV-644A 3340-PIT-647
3340-LIT-643 PT

3340 – PU - 112 CPF Fluidisation


LC Water
LT
3340643
SC
3340645
M
3340PU114
3340 – TK - 104
3340-XV-645A
3340 – PU - 114
LC
3340-LIT-648
LT PC
3340648
3340647

SC
3340646
M 3340PU115
PT
3340 – TK - 102 Flush Water

3340 – PU - 115

3340-LIT-649
LC
LT
3340649 3340PU109 PC
3340650
SC 3340 – PU - 109
M
3340649 PT
Froth Supp &
3340 – TK - 103 Dilution

Figure 92: Blockflow Control Diagram of the 3340PU115 System

27.3.2 Unit of Control Modules – 3340PU115

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_AGUAPROCESOS EM 3340PU115 Sub EM

Tag Service

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 642 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PU-115 Flush Water Pump


3340-PIT-646 PRESSURE TRANSMITTER 3340-PU-115
3340-VT-646A VIBRATION TRANSMITTER 3340-PU-115
3340-VT-646B VIBRATION TRANSMITTER 3340-PU-115
3340- TE – 646A Pump Temperature Switch A
3340- TE – 646B Pump Temperature Switch B
3340- TE – 646C Pump Temperature Switch C
3340- TE – 646D Pump Temperature Switch D
3340- TE – 646E Pump Temperature Switch E
3340- TE – 646F Pump Temperature Switch F
3340- TE – 646G Pump Temperature Switch G
3340- TE – 646H Pump Temperature Switch H

Table 810: List of Unit Controls – 3340PU115

27.3.3 Interlocks – 3340PU115

T2 Interlock
Tag 3340-PU-115 Description Flush Water Pump
SCPF_AGUAPR Sub
UN EM 3340PU115
OCESOS EM
Interlock
Motor Type VFD Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. MQ15-715-DC-3340-IN0101


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-PIT-646 .LL If discharge pressure is Low Low for a
Delay time 5
AND time delay ×
minutes
3340-PU-115.MO1.Run

Table 811: List of Interlocks for 3340-PU-115

27.3.4 Alarms and Process Setpoints – 3340PU115

T3 Alarms and Process Setpoints

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 643 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

UN SCPF_AGUAPROCESOS EM 3340PU115 Sub EM


H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

Refer to vendor control philosophy for equipment package specific alarms and setpoints MQ15-715-DC-3340-IN0101
Flush Water Pump Discharge
3340-PT-646 0 - 1000 KPa 340
Pressure Transmitter

Table 812: Alarms and Process Setpoint 3340PU115

27.3.5 Binary Messages – 3340PU115

T4 Binary State Messages


UN SCPF_AGUAPROCESOS EM 3340PU115 Sub EM
Tag Description OFF ON
3340-PT-646.L
or LL for 2 Flush Water Pressure is Low or Low
×
minutes Low

Table 813: Binary State Messages 3340PU115

27.3.6 Regulatory Control Loops – 3340PU115

T5 Regulatory Control Loops


UN SCPF_AGUAPROCESOS EM 3340PU115 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
50 - 100 % KPa 0 - 1000 340 – Expected
Flush Water Pump Discharge
3340 PC - 646 1000 setpoint 550
Pressure Controller
KPa

Table 814: Regulatory Control Loops for 3340PU115

The flush water pump provides hose down water for the plant operations as well as hard-piped
flush water to most slurry pump suctions and other locations, including the tails launders. Flush
water is introduced by opening the relevant flush water valve before the pump or launder.
To ensure the flush water pump capacity is not exceeded while flushing multiple lines, not all
flushing valves may be opened simultaneously. The table below details the precedence of valves
to be opened when respective flushing is simultaneously required. Please refer to the relevant
sections for flushing line durations. Should multiple valves require being opened simultaneously,
the sequences with valves of lower precedence shall hold until the priority sequences have
completed.
Tag Name Precedence
3340- XV-384B Concentrate Return Pump 3 1

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 644 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340- XV-385B Concentrate Return Pump 4 2


3340- XV-612B Concentrate Return Pump 1 3
3340- XV-613B Concentrate Return Pump 2 4
3340- XV-002B Deslime Feed Pump 1 5
3340- XV-003B Deslime Feed Pump 2 6
3340- XV-021B Crossflow Feed Pump 1 7
3340 XV-022B Crossflow Feed Pump 2 8
3340 XV-602B Regrind Cyclone Feed Pump 1 9
3340 XV-603B Regrind Cyclone Feed Pump 2 10
3340 XV-632C Tails Sample Return Pump flush 11
3340 XV-700, 701 and 702
Tails Launder Flush 1, 2 and 3 12
simultaneously10
3340 XV - 039 Crossflow Surge Tank Flush 13

Table 815: Precedence of Opening for Flush Water Valves

27.3.7 Advanced Control Loops – 3340PU115

Not applicable

27.3.8 Description – 3340PU115

A variable speed Flush Water Pump (3340 – PU – 115) provides the CPF flush water
requirements. The flush water pressure is measured via pressure transmitter (3340- PIT – 646)
and controlled by Proportional, Integral, Differential (PID) loop controller to achieve the required
setpoint pressure by varying the speed of the pump. An alarm will activate if the line pressure is
Low after running the pump for the specified time.
Following a start signal to the pump, the motor must ramp up from its minimum speed setpoint.
This will ensure that sufficient back-pressure always exists on the pump.

27.4 Engineering Module– 3340PU109

27.4.1 Description – 3340PU109

The following figure shows the elements that make up the 3340PU109 equipment module.

10
All three valves 3340-XV-700, 701 and 702 may open simultaneously at this location in the order of precedence.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 645 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3720PU007

SC
3720109
M 3720-XV-110
DRA
Process Water
Make-Up
Fluor
3720 – PU - 007 PC
3720116

3720PU008
PT
SC
M 3720-XV-115 CPF Process
3720114 Water

3720 – PU - 008

SC PC
3340-XV-645A M 3340PU112
3340644 3340647

3340-XV-644A 3340-PIT-647
3340-LIT-643 PT

3340 – PU - 112 CPF Fluidisation


LC Water
LT
3340643
SC
3340645
M
3340PU114
3340 – TK - 104
3340-XV-645A
3340 – PU - 114
LC
3340-LIT-648
LT PC
3340648
3340647

SC
3340646
M 3340PU115
PT
3340 – TK - 102 Flush Water

3340 – PU - 115

3340-LIT-649
LC
LT
3340649 3340PU109 PC
3340650
SC 3340 – PU - 109
M
3340649 PT
Froth Supp &
3340 – TK - 103 Dilution

Figure 93: Blockflow Control Diagram of the 3340PU109 System

27.4.2 Unit of Control Modules – 3340PU109

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_AGUAPROCESOS EM 3340PU109 Sub EM

Tag Service
3340-PU-109 Froth Suppression and Dilution Water Pump
3340-PIT-650 PRESSURE TRANSMITTER

Table 816: List of Unit Controls – 3340PU109

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 646 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

27.4.3 Interlocks – 3340PU109

T2 Interlock
Tag 3340-PU-109 Description Froth Suppression and Dilution Water Pump
SCPF_AGUAPR Sub
UN EM 3340PU109
OCESOS EM
Interlock
Motor Type VFD Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. MQ15-715-DC-3340-IN0101


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-PIT-650 .LL If discharge pressure is Low Low for a
Delay time 5
AND time delay ×
minutes
3340-PU-109.MO1.Run

Table 817: List of Interlocks for 3340-PU-109

27.4.4 Alarms and Process Setpoints – 3340PU109

T3 Alarms and Process Setpoints


UN SCPF_AGUAPROCESOS EM 3340PU109 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

Refer to vendor control philosophy for equipment package specific alarms and setpoints MQ15-715-DC-3340-IN0101
Froth Suppression and Dilution
3340-PT-650 Water Pump Discharge Pressure 0 - 1000 KPa 340
Transmitter

Table 818: Alarms and Process Setpoint 3340PU109

27.4.5 Binary Messages – 3340PU109

T4 Binary State Messages


UN SCPF_AGUAPROCESOS EM 3340PU109 Sub EM
Tag Description OFF ON

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 647 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PT-650.L
or LL for 2 Flush Water Pressure is Low or Low
×
minutes Low

Table 819: Binary State Messages 3340PU109

27.4.6 Regulatory Control Loops – 3340PU109

T5 Regulatory Control Loops


UN SCPF_AGUAPROCESOS EM 3340PU109 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
50 - 100 % KPa 0 - 1000 340 – Expected
Flush Water Pump Discharge
3340 PC - 650 1000 setpoint 440
Pressure Controller
KPa

Table 820: Regulatory Control Loops for 3340PU109

27.4.7 Advanced Control Loops – 3340PU109

Not applicable

27.4.8 Description – 3340PU109

A variable speed Froth Suppression and Dilution Water Pump (3340 – PU – 109) provides the
deep cone settlers water capacity requirements. The flush water pressure is measured via
pressure transmitter (3340- PIT – 650) and controlled by Proportional, Integral, Differential (PID)
loop controller to achieve the required setpoint pressure by varying the speed of the pump. An
alarm will activate if the line pressure is Low after running the pump for the specified time.
Following a start signal to the pump, the motor must ramp up from its minimum speed setpoint.
This will ensure that sufficient back-pressure always exists on the pump.

27.5 Engineering Module– 3720PU007

27.5.1 Description – 3720PU007

The following figure shows the elements that make up the 3720PU007 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 648 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3720PU007

SC
3720109
M 3720-XV-110
DRA
Process Water
Make-Up
Fluor
3720 – PU - 007 PC
3720116

3720PU008
PT
SC
M 3720-XV-115 CPF Process
3720114 Water

3720 – PU - 008

SC PC
3340-XV-645A M 3340PU112
3340644 3340647

3340-XV-644A 3340-PIT-647
3340-LIT-643 PT

3340 – PU - 112 CPF Fluidisation


LC Water
LT
3340643
SC
3340645
M
3340PU114
3340 – TK - 104
3340-XV-645A
3340 – PU - 114
LC
3340-LIT-648
LT PC
3340648
3340647

SC
3340646
M 3340PU115
PT
3340 – TK - 102 Flush Water

3340 – PU - 115

3340-LIT-649
LC
LT
3340649 3340PU109 PC
3340650
SC 3340 – PU - 109
M
3340649 PT
Froth Supp &
3340 – TK - 103 Dilution

Figure 94: Blockflow Control Diagram of the 3720PU007 System

27.5.2 Unit of Control Modules – 3720PU007

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_AGUAPROCESOS EM 3720PU007 Sub EM

Tag Service
3720-PU-007 Make-up Water Pump 1
3720-XV-110 DISCHARGE OF WATER PUMP 3340-PU-007
3720-PIT-116 PRESSURE TRANSMITTER 3720-PU-007
3720-VT-109A VIBRATION TRANSMITTER 3720-PU-007
3720-VT-109B VIBRATION TRANSMITTER 3720-PU-007

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 649 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3720- TE – 109A Pump Temperature Switch A


3720- TE – 109B Pump Temperature Switch B
3720- TE – 109C Pump Temperature Switch C
3720- TE – 109D Pump Temperature Switch D
3720- TE – 109E Pump Temperature Switch E
3720- TE – 109F Pump Temperature Switch F
3720- TE – 109G Pump Temperature Switch G
3720- TE – 109H Pump Temperature Switch H

Table 821: List of Unit Controls – 3720PU007

27.5.3 Interlocks – 3720PU007

T2 Interlock
Tag 3720-PU-007 Description Make-Up Water Pump 1
SCPF_AGUAPR Sub
UN EM 3720PU007
OCESOS EM
Interlock
Motor Type VFD Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. MQ15-715-DC-3340-IN0101


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3720-XV-110 !OP ×
If discharge valve not open and pump is Time Delay
AND
running for a time delay 45 seconds
3720-PU-007.MO1.Run
3720-PIT-116 .LL If discharge pressure is Low Low for a
Delay time 5
AND time delay ×
minutes
3720-PU-007.MO1.Run

Table 822: List of Interlocks for 3720-PU-007

T2 Interlock
Tag 3720-XV-110 Description DISCHARGE OF WATER PUMP
SCPF_AGUAPR Sub
UN EM 3720PU007
OCESOS EM
Failure Position: Interlock
Motor Type Interlock
Keep Last (KL) Type

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 650 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Safe Position:
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3720 – PU – 007-MO1 Time delay


If pump is not running for a time delay ×
.!RN 10 seconds

Table 823: List of Interlocks for 3720-XV-110

27.5.4 Alarms and Process Setpoints – 3720PU007

T3 Alarms and Process Setpoints


UN SCPF_AGUAPROCESOS EM 3720PU007 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

Refer to vendor control philosophy for equipment package specific alarms and setpoints MQ15-715-DC-3340-IN0101
3720- PT - Process Water Make-Up Pump
0 - 1100 KPa 725 640
116 Discharge Pressure

Table 824: Alarms and Process Setpoint 3720PU007

27.5.5 Binary Messages – 3720PU007

T4 Binary State Messages


UN SCPF_AGUAPROCESOS EM 3720PU007 Sub EM
Tag Description OFF ON
3720-PT-116.L
or LL for 30 Process Water Make-Up Pressure is
×
seconds Low or Low Low

Table 825: Binary State Messages 3720PU007

Note:
1) The CPF uses the make-up water for both Fluidisation Water Tank level control as well as
process pump box level control water. Maintaining a pressurised line is therefore important
to avoid pipeline blockages within the CPF

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 651 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

27.5.6 Regulatory Control Loops – 3720PU007

T5 Regulatory Control Loops


UN SCPF_AGUAPROCESOS EM 3720PU007 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % KPa 0 - 1100 730 – Expected
Make-Up Water Pump Discharge
3720-PC-116 1100 setpoint 875
Header Pressure Control
KPa

Table 826: Regulatory Control Loops for 3720PU007

The common pressure controller adjusts the speed of both Make-Up Water Pumps (3720-PU-007
and 3720-PU-008) to maintain the selected setpoint.

27.5.7 Advanced Control Loops – 3720PU007

Not applicable

27.5.8 Description – 3720PU007

CPF Process water is derived from the Papajuane concentrators Recovered Water Dam (3720-
TK -002) provided by others. Two CPF Make-Up Water Pumps 1 & 2 (3720 – PU – 007 & 008)
deliver water to the CPF at a controlled pressure measured by a pressure transmitter (3720- PIT
–116). Both pumps have variable speed drives, which will be adjusted via Proportional, Integral,
Differential (PID) loop controller to achieve the required setpoint pressure.
The pump discharge valves (3720- XV – 110 / 115) are electrically actuated and therefore do not
require a healthy instrument air pressure signal to operate.
For the CPF to operate at full capacity, both pumps must run. Should one pump be unavailable,
it is highly likely that one half stream capacity within the CPF is stopped. Following a start signal
to the pump, the motor must ramp up from its minimum speed setpoint and the discharge valve
is to commence opening immediately. This will ensure that sufficient back-pressure always exists
on the pump.
The pump start sequence 3720-PU-007, shall follow the following steps:
TSQST Start Sequence Table
UN SCPF_AGUAPROCESOS EM 3720PU007 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Start pump at minimum speed 10 60
1. Start 3720-PU-007.MO1 Working
allowing speed control ramp up seconds seconds
2 120
2. Open 3720-XV-110 Discharge Valve Open
seconds seconds

Table 827: Start Sequence 3720PU007

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 652 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3720-PU-007 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3720-PU-007-MO1 stopped
The pump stop sequence 3720-PU-007, shall follow the following steps:
TSQST Stop Sequence Table
UN SCPF_AGUAPROCESOS EM 3720PU007 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3720-PU-007.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3720-PU-007.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3720-XV-110 Discharge Valve. Closed
seconds seconds

Table 828: Stop Sequence 3720PU007

27.6 Engineering Module– 3720PU008

27.6.1 Description – 3720PU008

The following figure shows the elements that make up the 3720PU008 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 653 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3720PU007

SC
3720109
M 3720-XV-110
DRA
Process Water
Make-Up
Fluor
3720 – PU - 007 PC
3720116

3720PU008
PT
SC
M 3720-XV-115 CPF Process
3720114 Water

3720 – PU - 008

SC PC
3340-XV-645A M 3340PU112
3340644 3340647

3340-XV-644A 3340-PIT-647
3340-LIT-643 PT

3340 – PU - 112 CPF Fluidisation


LC Water
LT
3340643
SC
3340645
M
3340PU114
3340 – TK - 104
3340-XV-645A
3340 – PU - 114
LC
3340-LIT-648
LT PC
3340648
3340647

SC
3340646
M 3340PU115
PT
3340 – TK - 102 Flush Water

3340 – PU - 115

3340-LIT-649
LC
LT
3340649 3340PU109 PC
3340650
SC 3340 – PU - 109
M
3340649 PT
Froth Supp &
3340 – TK - 103 Dilution

Figure 95: Blockflow Control Diagram of the 3720PU008 System

27.6.2 Unit of Control Modules – 3720PU008

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_AGUAPROCESOS EM 3720PU008 Sub EM

Tag Service
3720-PU-008 Make-up Water Pump 2
3720-XV-115 DISCHARGE OF WATER PUMP 3340-PU-008
3720-VT-114A VIBRATION TRANSMITTER 3720-PU-008
3720-VT-114B VIBRATION TRANSMITTER 3720-PU-008
3720- TE – 654A Pump Temperature Switch A

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 654 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3720- TE – 114B Pump Temperature Switch B


3720- TE – 114C Pump Temperature Switch C
3720- TE – 114D Pump Temperature Switch D
3720- TE – 114E Pump Temperature Switch E
3720- TE – 114F Pump Temperature Switch F
3720- TE – 114G Pump Temperature Switch G
3720- TE – 114H Pump Temperature Switch H

Table 829: List of Unit Controls – 3720PU008

27.6.3 Interlocks – 3720PU008

T2 Interlock
Tag 3720-PU-008 Description Make-Up Water Pump 2
SCPF_AGUAPR Sub
UN EM 3720PU008
OCESOS EM
Interlock
Motor Type VFD Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. MQ15-715-DC-3340-IN0101


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3720-XV-115 !OP ×
If discharge valve not open and pump is Time Delay
AND
running for a time delay 45 seconds
3720-PU-008.MO1.Run
3720-PIT-115 .LL If discharge pressure is Low Low for a
Delay time 5
AND time delay ×
minutes
3720-PU-008.MO1.Run

Table 830: List of Interlocks for 3720-PU-008

T2 Interlock
Tag 3720-XV-115A Description DISCHARGE OF WATER PUMP
SCPF_AGUAPR Sub
UN EM 3720PU008
OCESOS EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 655 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3720 – PU – 008-MO1 Time delay


If pump is not running for a time delay ×
.!RN 10 seconds

Table 831: List of Interlocks for 3720-XV-115A

27.6.4 Alarms and Process Setpoints – 3720PU008

T3 Alarms and Process Setpoints


UN SCPF_AGUAPROCESOS EM 3720PU008 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

Refer to vendor control philosophy for equipment package specific alarms and setpoints MQ15-715-DC-3340-IN0101

Table 832: Alarms and Process Setpoint 3720PU008

27.6.5 Binary Messages – 3720PU008

Not applicable

27.6.6 Regulatory Control Loops – 3720PU008

T5 Regulatory Control Loops


UN SCPF_AGUAPROCESOS EM 3720PU008 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % KPa 0 - 1100 730 – Expected
Make-Up Water Pump Discharge
3720-PC-116 1100 setpoint 875
Header Pressure Control
KPa

Table 833: Regulatory Control Loops for 3720PU007

The common pressure controller adjusts the speed of both Make-Up Water Pumps (3720-PU-007
and 3720-PU-008) to maintain the selected setpoint.

27.6.7 Advanced Control Loops – 3720PU008

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 656 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

27.6.8 Description – 3720PU008

CPF Process water is derived from the Papajuane concentrators Recovered Water Dam (3720-
TK -002) provided by others. Two CPF Make-Up Water Pumps 1 & 2 (3720 – PU – 007 & 008)
deliver water to the CPF at a controlled pressure measured by a pressure transmitter (3720- PIT
–116). Both pumps have variable speed drives, which will be adjusted via Proportional, Integral,
Differential (PID) loop controller to achieve the required setpoint pressure.
The pump discharge valves (3720- XV – 110 / 115) are electrically actuated and therefore do not
require a healthy instrument air pressure signal to operate.
For the CPF to operate at full capacity, both pumps must run. Should one pump be unavailable,
it is highly likely that one half stream capacity within the CPF is stopped. Following a start signal
to the pump, the motor must ramp up from its minimum speed setpoint and the discharge valve
is to commence opening immediately. This will ensure that sufficient back-pressure always exists
on the pump.
The pump start sequence 3720-PU-008, shall follow the following steps:
TSQST Start Sequence Table
UN SCPF_AGUAPROCESOS EM 3720PU008 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Start pump at minimum speed 10 60
1. Start 3720-PU-008.MO1 Working
allowing speed control ramp up seconds seconds
2 120
2. Open 3720-XV-115 Discharge Valve Open
seconds seconds

Table 834: Start Sequence 3720PU008

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3720-PU-008 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3720-PU-008-MO1 stopped
The pump stop sequence 3720-PU-008, shall follow the following steps:
TSQST Stop Sequence Table
UN SCPF_AGUAPROCESOS EM 3720PU008 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
Feedback
Ramp down 2 60
1. 3720-PU-008.MO1 Slow down MV1 % controller
pump speed seconds seconds
<= MV1
20 60
2. Stop 3720-PU-008.MO1 Stop pump. Stopped
seconds seconds
2 180
3. Close 3720-XV-115 Discharge Valve. Closed
seconds seconds

Table 835: Stop Sequence 3720PU008

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 657 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

28.0 UNIDAD: SCPF_AGUASELLO

Refer to:
MQ14-08-DR-3340-PD1090 Gland Seal Water

A block flow control diagram is depicted below for the SCPF_AGUASELLO system.
3340-PT-656
DRA PT

GSW Feed Low Pressure


GSW Ringmain
Fluor
3340-XV-650A

3340-XV-654A
3340PU192

3340-XV-654B

3340-PT-659
PT

3340 – PU - 192 High Pressure


GSW Ringmain

3340PU193
3340-XV-655A

3340-XV-655B

3340 – PU - 193

Figure 96: Blockflow Control Diagram of SCPF_AGUASELLO

The above control unit is broken into two Engineering Module 1 with zero sub Engineering Module 2’s:
- 3340PU192 (Duty)
- 3340PU193 (Standby)

Only one pump must run at a time. The operator to select the pump manually or plc to select
based on the least number of operating hours at time of start.

28.0.1 Modules of Control SCPF_AGUASELLO

T1 Control Mod
Sub
UN SCPF_AGUASELLO EM
EM

Tag Service
3340-PIT-656 Low Pressure GSW Pressure Transmitter
3340-XV-650A VÁLVULA DE CORTE, AGUA DE SELLO DESDE PLANTA

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 658 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PIT-659 High Pressure Gland Seal Water Pressure Transmitter

Table 836: List of Modules of Control for SCPF_AGUASELLO

28.0.2 Interlocks – SCPF_AGUASELLO

T2 Interlock
VÁLVULA DE CORTE, AGUA DE SELLO DESDE
Tag 3340-XV-650 Description
PLANTA
SCPF_AGUASEL Sub
UN EM
LO EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 837: List of Interlocks for 3340-XV-650

28.0.3 Alarms and Process Setpoints – SCPF_AGUASELLO

T3 Alarms and Process Setpoints


UN SCPF_AGUASELLO EM Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
0 – 1000
3340- PIT -
GSW Feed Pressure (Normal KPa 690 600
656
720)
0 – 1500 KPa
3340- PIT - GSW Booster Pump Discharge
(Normal 890 860
659 Pressure
1050)

Table 838: Alarms and Process Setpoint SCPF_AGUASELLO

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 659 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

28.0.4 Binary Messages – SCPF_AGUASELLO

T4 Binary State Messages


UN SCPF_AGUASELLO EM Sub EM
Tag Description OFF ON
3340-PT-656.L Gland Seal Water Pressure is Low or
or LL ×
Low Low
3340-PT-659.L Boosted Gland Seal Water Pressure
or LL ×
is Low or Low Low

Table 839: Binary State Messages SCPF_AGUASELLO

When the gland water pressure and boosted gland water pressure is low or low low, material is
prevented from entering the CPF at certain strategic points in order to allow the CPF system to
purge itself of solids thereby preventing blockages on any potential crash stop.
Individual slurry pumps will stop when their respective GSW flowswitches provide a low flow alarm
for a specified time delay.

28.0.5 Regulatory Control Loops – SCPF_AGUASELLO

Not applicable.

28.0.6 Advanced Control Loops – SCPF_AGUASELLO

Not applicable

28.0.7 Description – SCPF_AGUASELLO

Clean gland seal water is gravity fed to the CPF via the Papajuane concentrators’ gland seal
water pipeline. Manual valves as well as an actuated valve (3340- XV-650) allows the gland seal
water to the CPF to be isolated if required.

The feed pressure of the gland seal water offtake is sufficient for most CPF applications and will
be monitored via pressure transmitter (3340- PIT – 656). Should the pressure be Low, an alarm
will be generated, and no pump start sequences will be enabled. In the event of a Low Low
pressure, feed to the CPF will be stopped and the pipelines be allowed to purge themselves of
solids to prevent chokes. Each individual slurry pump is protected via a gland seal water
flowswitch which must be healthy for the pump to run (refer to the relevant pump sections below).

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 660 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

The boosted pressure of the gland seal water booster pump discharge will be monitored via
pressure transmitter (3340- PIT – 659). Only one gland seal water booster pump needs to operate
at a time (i.e. running/standby).

28.1 Engineering Module– 3340PU192

28.1.1 Description – 3340PU192

The following figure shows the elements that make up the 3340PU192 equipment module.
3340-PT-656
DRA PT

GSW Feed Low Pressure


GSW Ringmain
Fluor
3340-XV-650A

3340-XV-654A
3340PU192

3340-XV-654B

3340-PT-659
PT

3340 – PU - 192 High Pressure


GSW Ringmain

3340PU193
3340-XV-655A

3340-XV-655B

3340 – PU - 193

Figure 97: Blockflow Control Diagram of the 3340PU192 System

28.1.2 Unit of Control Modules – 3340PU192

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_AGUASELLO EM 3340PU192 Sub EM

Tag Service
3340-PU-192 Gland Seal Water Pump 1
3340-XV-654B DISCHARGE OF WATER PUMP 3340-PU-192
3340-XV-654A SUCTION OF WATER PUMP 3340-PU-192

Table 840: List of Unit Controls – 3340PU192

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 661 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

28.1.3 Interlocks – 3340PU192

T2 Interlock
Tag 3340-XV-654A Description SUCTION OF WATER PUMP 3340-PU-192
SCPF_AGUASEL Sub
UN EM 3340PU192
LO EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 841: List of Interlocks for 3340-XV-654A

T2 Interlock
Tag 3340-PU-192 Description Gland Seal Water Pump 1
SCPF_AGUASEL Sub
UN EM 3340PU192
LO EM
Interlock
Motor Type Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-654A CL ×
OR CLN Suction valve is closed or closing and Time Delay
AND pump is running for a time delay 1 seconds
3340-PU-192-MO1.Run
3340-XV-654B!OP ×
If discharge valve not open and pump is Time Delay
AND
running for a time delay 5 seconds
3340-PU-192.MO1.Run
3340-PIT-656 .LL If Suction pressure is Low Low for a time
Delay time
AND delay ×
30 seconds
3340-PU-192.MO1.Run
3340-PIT-659 .LL If discharge pressure is Low Low for a
Delay time 5
AND time delay ×
minutes
3340-PU-192.MO1.Run

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 662 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 842: List of Interlocks for 3340-PU-192

T2 Interlock
Tag 3340-XV-654B Description DISCHARGE OF WATER PUMP
SCPF_AGUASEL Sub
UN EM 3340PU192
LO EM
Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340 – PU – 192-MO1 Time delay


If pump is not running for a time delay ×
.!RN 10 seconds

Table 843: List of Interlocks for 3340-XV-654B

28.1.4 Alarms and Process Setpoints – 3340PU192

Not applicable
28.1.5 Binary Messages – 3340PU192

Not applicable

28.1.6 Regulatory Control Loops – 3340PU192

Not applicable

28.1.7 Advanced Control Loops – 3340PU192

Not applicable

28.1.8 Description – 3340PU192

The pump start sequence 3340-PU-192, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 663 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SCPF_AGUASELLO EM 3340PU192 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 120
1. Open 3340-XV-650A Open GSW feed valve to CPF Open
seconds seconds
Open GSW Suction Valve to 2 120
2. Open 3340-XV-654A Open
pump seconds seconds
Open GSW Discharge Valve to 2 120
3. Open 3340-XV-654B Open
pump seconds seconds
10 60
4. Start 3340-PU-192.MO1 Start pump Working
seconds seconds

Table 844: Start Sequence 3340PU192

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-192 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-192-MO1 stopped
The pump stop sequence 3340-PU-192, shall follow the following steps:
TSQST Stop Sequence Table
UN SCPF_AGUASELLO EM 3340PU192 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3340-PU-192.MO1 Stop pump. Stopped
seconds seconds
2 60
2. Close 3340-XV-654B Discharge Valve. Closed
seconds seconds
2 60
3. Close 3340-XV-654A Suction Valve Closed
seconds seconds

Table 845: Stop Sequence 3340PU192

28.2 Engineering Module– 3340PU193

28.2.1 Description – 3340PU193

The following figure shows the elements that make up the 3340PU193 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 664 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-PT-656
DRA PT

GSW Feed Low Pressure


GSW Ringmain
Fluor
3340-XV-650A

3340-XV-654A
3340PU192

3340-XV-654B

3340-PT-659
PT

3340 – PU - 192 High Pressure


GSW Ringmain

3340PU193
3340-XV-655A

3340-XV-655B

3340 – PU - 193

Figure 98: Blockflow Control Diagram of the 3340PU193 System

28.2.2 Unit of Control Modules – 3340PU193

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_AGUASELLO EM 3340PU193 Sub EM

Tag Service
3340-PU-193 Gland Seal Water Pump 2
3340-XV-655B DISCHARGE OF WATER PUMP 3340-PU-193
3340-XV-655A SUCTION OF WATER PUMP 3340-PU-193

Table 846: List of Unit Controls – 3340PU193

28.2.3 Interlocks – 3340PU193

T2 Interlock
Tag 3340-XV-655A Description SUCTION OF WATER PUMP 3340-PU-193
SCPF_AGUASEL Sub
UN EM 3340PU193
LO EM
Failure Position:
Keep Last (KL) Interlock
Motor Type Interlock
Safe Position: Type
Closed (CL)

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 665 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Table 847: List of Interlocks for 3340-XV-655A

T2 Interlock
Tag 3340-PU-193 Description Gland Seal Water Pump 2
SCPF_AGUASEL Sub
UN EM 3340PU193
LO EM
Interlock
Motor Type Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT
3340-XV-655A CL ×
OR CLN Suction valve is closed or closing and Time Delay
AND pump is running for a time delay 1 seconds
3340-PU-192-MO1.Run
3340-XV-655B!OP ×
If discharge valve not open and pump is Time Delay
AND
running for a time delay 5 seconds
3340-PU-193.MO1.Run
3340-PIT-656 .LL If Suction pressure is Low Low for a time
Delay time
AND delay ×
30 seconds
3340-PU-193.MO1.Run
3340-PIT-659 .LL If discharge pressure is Low Low for a
Delay time 5
AND time delay ×
minutes
3340-PU-193.MO1.Run

Table 848: List of Interlocks for 3340-PU-193

T2 Interlock
Tag 3340-XV-655B Description DISCHARGE OF WATER PUMP
SCPF_AGUASEL Sub
UN EM 3340PU193
LO EM

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 666 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Failure Position:
Keep Last (KL)
Interlock
Motor Type Safe Position: Interlock
Type
Closed (CL)

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

3340 – PU – 193-MO1 Time delay


If pump is not running for a time delay ×
.!RN 10 seconds

Table 849: List of Interlocks for 3340-XV-655B

28.2.4 Alarms and Process Setpoints – 3340PU193

Not applicable
28.2.5 Binary Messages – 3340PU193

Not applicable

28.2.6 Regulatory Control Loops – 3340PU193

Not applicable

28.2.7 Advanced Control Loops – 3340PU193

Not applicable

28.2.8 Description – 3340PU193

The pump start sequence 3340-PU-193, shall follow the following steps:

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 667 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

TSQST Start Sequence Table


UN SCPF_AGUASELLO EM 3340PU193 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
2 120
1. Open 3340-XV-650A Open GSW feed valve to CPF Open
seconds seconds
Open GSW Suction Valve to 2 120
2. Open 3340-XV-655A Open
pump seconds seconds
Open GSW Discharge Valve to 2 120
3. Open 3340-XV-655B Open
pump seconds seconds
10 60
4. Start 3340-PU-193.MO1 Start pump Working
seconds seconds

Table 850: Start Sequence 3340PU193

The monitoring time of the Start/Stop and Forced Stop of the Equipment Module 3340-PU-193 is
260 seconds. After the last step (while the module of equipment is active), failure of any of the
following conditions will cause the Equipment module failure condition:
- Motor Pump Motor 3340-PU-193-MO1 stopped
The pump stop sequence 3340-PU-193, shall follow the following steps:
TSQST Stop Sequence Table
UN SCPF_AGUASELLO EM 3340PU193 Sub EM
Seq Command Tag Description Transition Min Monitor
Time Time
20 60
1. Stop 3340-PU-193.MO1 Stop pump. Stopped
seconds seconds
2 60
2. Close 3340-XV-655B Discharge Valve. Closed
seconds seconds
2 60
3. Close 3340-XV-655A Suction Valve Closed
seconds seconds

Table 851: Stop Sequence 3340PU193

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 668 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

29.0 UNIDAD: SCPF_INSTAIR

Refer to:
MQ14-08-DR-3340-PD1096 Compressed Air Generation
MQ15-760-DR-3340-IN0001 OPTIMIZER 4.0 and Profibus DP Gateway (Vendor)
MQ15-760-TE-3340-IN0001 Profibus Communication Map Compressors (Vendor)
MQ15-760-TE-3340-IN0002 Profibus Communication Map Compressors (Drier)

A block flow control diagram is depicted below for the SCPF_InstAir system.

3340CP101_103 3340AR102

PT
NC-3340670
SC Instrument
M Air (CPF)
3340670 3340 – PT - 675
3340-PT-670
PT

3340 – AR - 101 3340 – DR - 101 3340 – AR - 102

3340 – CP - 101 3340AR103


PT
NC-3340671 Instrument Air
SC (Front End)
M
3340671 3340 – PT - 677
3340 – AR - 103
3340-PT-671
PT

3340 – PT - 672
3340 – CP - 102 3340AR101
PT
Plant /
SC
NC-3340678 Flotation Air
M
3340678

3340-PT-678
PT

3340 – CP - 103

Figure 99: Blockflow Control Diagram of SCPF_InstAir

The above control unit is broken into four Engineering Module 1 with zero sub Engineering Module 2’s:
- 3340CP101_103
- 3340AR101
- 3340AR102

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 669 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

- 3340AR103

29.0 Engineering Module– 3340CP101_103

29.0.1 Description – 3340CP101_103

The following figure shows the elements that make up the 3340CP101_103 equipment module.

3340CP101_103 3340AR102

PT
NC-3340670
SC Instrument
M Air (CPF)
3340670 3340 – PT - 675
3340-PT-670
PT

3340 – AR - 101 3340 – DR - 101 3340 – AR - 102

3340 – CP - 101 3340AR103


PT
NC-3340671 Instrument Air
SC (Front End)
M
3340671 3340 – PT - 677
3340 – AR - 103
3340-PT-671
PT

3340 – PT - 672
3340 – CP - 102 3340AR101
PT
Plant /
SC
NC-3340678 Flotation Air
M
3340678

3340-PT-678
PT

3340 – CP - 103

Figure 100: Blockflow Control Diagram of the 3340CP101_103 System

29.0.2 Unit of Control Modules – 3340CP101_103

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_InstAir EM 3340CP101_103 Sub EM

Tag Service

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 670 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340-CP-101 Air Compressor 1


3340-PIT-670 PRESSURE TRANSMITTER – Compressor 1
3340-CP-102 Air Compressor 2 (Standby)
3340-PIT-671 PRESSURE TRANSMITTER – Compressor 2
3340-CP-103 Air Compressor 3
3340-PIT-678 PRESSURE TRANSMITTER – Compressor 3

Table 852: List of Unit Controls – 3340CP101_103

29.0.3 Interlocks – 3340CP101_103

T2 Interlock
Tag 3340-CP-101 Description Air Compressor 1
3340CP101_ Sub
UN SCPF_InstAir EM
103 EM
Interlock
Motor Type VFD Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. MQ15-760-TE-3340-IN0001


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 853: List of Interlocks for 3340-CP-101

T2 Interlock
Tag 3340-CP-102 Description Air Compressor 2
3340CP101_ Sub
UN SCPF_InstAir EM
103 EM
Interlock
Motor Type VFD Interlock
Type
Description
Interlock

Bypass
Protect

Permit

Permit

QC

Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. MQ15-760-TE-3340-IN0001


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 671 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Table 854: List of Interlocks for 3340-CP-102

T2 Interlock
Tag 3340-CP-103 Description Air Compressor 3
3340CP101_ Sub
UN SCPF_InstAir EM
103 EM
Interlock
Motor Type VFD Interlock
Type

Description
Interlock

Bypass
Protect

Permit

Permit

QC
Tag Service Notes

Vendor interlocks as specified in equipment control philosophy. MQ15-760-TE-3340-IN0001


BLACKOUT ×
Electrical blackout Active
ELECTRICO.ACT

Table 855: List of Interlocks for 3340-CP-103

29.0.4 Alarms and Process Setpoints – 3340CP101_103

T3 Alarms and Process Setpoints


UN SCPF_InstAir EM 3340CP101_103 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S

Refer to vendor control philosophy for equipment package specific alarms and setpoints MQ15-760-TE-3340-IN0001
Compressor 1 discharge 0 - 1000
3340 PIT-070 KPa 800 600 550
pressure transmitter
Compressor 2 discharge 0 - 1000 KPa
3340 PIT-071 800 600 550
pressure transmitter
Compressor 3 discharge 0 - 1000 KPa
3340 PIT-078 800 600 550
pressure transmitter

Table 856: Alarms and Process Setpoint 3340CP101_103

29.0.5 Binary Messages – 3340CP101_103

Not applicable.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 672 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

29.0.6 Regulatory Control Loops – 3340CP101_103

T5 Regulatory Control Loops


UN SCPF_InstAir EM 3340CP101_103 Sub EM
Tag Description Range Unit Unit Range Range Conditions
MV MV PV/SP PV SP MV
0 - 100 % KPa 0 - 1000 600 – Expected
3340-PC-675 Instrument Air Pressure Control
800 setpoint 750

Table 857: Regulatory Control Loops for 3340CP101_103

The common pressure controller is adjusted by the Optmiser 4.0 package supplied by the vendor.
This adjusts the speed of all three compressors and determines which and how many should
operate (3340-CP-101, 3340-CP-102 and 3340-CP-103) to maintain the selected instrument air
pressure setpoint for the CPF.

29.0.7 Advanced Control Loops – 3340CP101_103

Not applicable

29.0.8 Description – 3340CP101_103

Compressed air for the CPF is supplied from three air compressors (3340-CP-101 / 102 / 103).
The compressors are stopped/started via vendor supplied controller which also controls their VFD
speeds to maintain the setpoint pressure of the instrument air (3340-PIT-675).

The vendor functional specification for the compressors and air dryer shall be utilized for their
control.

29.1 Engineering Module– 3340AR101

29.1.1 Description – 3340AR101

The following figure shows the elements that make up the 3340AR101 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 673 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340CP101_103 3340AR102

PT
NC-3340670
SC Instrument
M Air (CPF)
3340670 3340 – PT - 675
3340-PT-670
PT

3340 – AR - 101 3340 – DR - 101 3340 – AR - 102

3340 – CP - 101 3340AR103


PT
NC-3340671 Instrument Air
SC (Front End)
M
3340671 3340 – PT - 677
3340 – AR - 103
3340-PT-671
PT

3340 – PT - 672
3340 – CP - 102 3340AR101
PT
Plant /
SC
NC-3340678 Flotation Air
M
3340678

3340-PT-678
PT

3340 – CP - 103

Figure 101: Blockflow Control Diagram of the 3340AR101 System

29.1.2 Unit of Control Modules – 3340AR101

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_InstAir EM 3340AR101 Sub EM

Tag Service
3340-AR-101 Plant Air Receiver
3340-PIT-672 PRESSURE TRANSMITTER – Plant/Flotation Air

Table 858: List of Unit Controls – 3340AR101

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 674 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

29.1.3 Interlocks – 3340AR101

Not applicable

29.1.4 Alarms and Process Setpoints – 3340AR101

T3 Alarms and Process Setpoints


UN SCPF_InstAir EM 3340AR101 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340 PIT-672 Plant Air Pressure Transmitter 0 - 1000 KPa 600

Table 859: Alarms and Process Setpoint 3340AR101

29.1.5 Binary Messages – 3340AR101

T4 Binary State Messages


UN SCPF_InstAir EM 3340AR101 Sub EM
Tag Description OFF ON
Absolute {3340-
PIT-672}
- Compressed Air Difference – Plant
×
Absolute { Air to Instrument Air
3340-PIT-675}
> 30 KPa

Table 860: Binary State Messages 3340AR101

The control room operator should be alerted when an undue difference in pressure occurs
between plant and instrument air headers. This would likely be caused by manual valve isolation
in the field.

29.1.6 Regulatory Control Loops – 3340AR101

Not applicable

29.1.7 Advanced Control Loops – 3340AR101

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 675 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

29.1.8 Description – 3340AR101

The compressors discharge into a common pipe manifold which feeds the Plant Air Receiver
(3340 - AR – 101) that provides a buffer storage capacity for the CPF plant air requirements.
Water condensate which may accumulate at the base of the accumulator is periodically
discharged via a mechanical relief valve. The accumulator is also equipped with a safety pressure
relief valve to ensure the compressed air pressure does not exceed the line pressure rating.

Compressed air is then either directed to:

 The hydroflotation cells.

 CPF pneumatic air header. The pressure in this line is measured by a pressure
transmitter (3340-PIT-672) and should it drop a low level, an alarm shall be generated.

 Instrument air drier.

29.2 Engineering Module– 3340AR102

29.2.1 Description – 3340AR102

The following figure shows the elements that make up the 3340AR102 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 676 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340CP101_103 3340AR102

PT
NC-3340670
SC Instrument
M Air (CPF)
3340670 3340 – PT - 675
3340-PT-670
PT

3340 – AR - 101 3340 – DR - 101 3340 – AR - 102

3340 – CP - 101 3340AR103


PT
NC-3340671 Instrument Air
SC (Front End)
M
3340671 3340 – PT - 677
3340 – AR - 103
3340-PT-671
PT

3340 – PT - 672
3340 – CP - 102 3340AR101
PT
Plant /
SC
NC-3340678 Flotation Air
M
3340678

3340-PT-678
PT

3340 – CP - 103

Figure 102: Blockflow Control Diagram of the 3340AR102 System

29.2.2 Unit of Control Modules – 3340AR102

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_InstAir EM 3340AR102 Sub EM

Tag Service
3340-DR-101 Air Drier
3340-AR-102 Instrument Air Receiver
3340-PIT-675 PRESSURE TRANSMITTER – Instrument Air

Table 861: List of Unit Controls – 3340AR102

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 677 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

29.2.3 Interlocks – 3340AR102

Not applicable
The instrument desiccant air drier is mechanical in nature and controlled by the vendor Optimiser
4 package.

29.2.4 Alarms and Process Setpoints – 3340AR102

T3 Alarms and Process Setpoints


UN SCPF_InstAir EM 3340AR102 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340 PIT-675 Instrument Air Pressure 0 - 1000 KPa
800 600 550
Transmitter

Table 862: Alarms and Process Setpoint 3340AR102

29.2.5 Binary Messages – 3340AR102

Not applicable

29.2.6 Regulatory Control Loops – 3340AR102

Not applicable

29.2.7 Advanced Control Loops – 3340AR102

Not applicable

29.2.8 Description – 3340AR102

The instrument Air drier pre-filters (3340-FL-101 / 103) are in a running/standby configuration and
can be manually alternated by the filed operator.

The desiccant air drier (3340 - DR – 101) reduces the moisture content of the compressed air but
can be manually bypassed under emergencies during breakdown periods.

Post-drier filters (3340-FL-102 / 104) remove final oil and dust particles. They are in a
running/standby configuration and can be manually alternated by the field operator.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 678 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

Instrument Air is then piped into the Instrument Air Receiver (3340 - AR – 102) that provides a
buffer storage capacity for the CPF instrument air requirements. Water condensate which may
accumulate at the base of the accumulator is periodically discharged via a mechanical relief valve.
The accumulator is also equipped with a safety pressure relief valve to ensure the compressed
air pressure does not exceed the line pressure rating.

Instrument air is then either directed to:

 The Front End Instrument Air Receiver (3340-AR-103). The pressure in this line is
measured by a pressure transmitter (3340- PIT-677) and should it drop a Low level an
alarm shall be generated.

 CPF instrument air header. The pressure in this line is measured by a pressure
transmitter (3340- PIT-675). The pressure in the instrument airline is controlled by varying
the number and speed of the compressors.

29.3 Engineering Module– 3340AR103

29.3.1 Description – 3340AR103

The following figure shows the elements that make up the 3340AR103 equipment module.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 679 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

3340CP101_103 3340AR102

PT
NC-3340670
SC Instrument
M Air (CPF)
3340670 3340 – PT - 675
3340-PT-670
PT

3340 – AR - 101 3340 – DR - 101 3340 – AR - 102

3340 – CP - 101 3340AR103


PT
NC-3340671 Instrument Air
SC (Front End)
M
3340671 3340 – PT - 677
3340 – AR - 103
3340-PT-671
PT

3340 – PT - 672
3340 – CP - 102 3340AR101
PT
Plant /
SC
NC-3340678 Flotation Air
M
3340678

3340-PT-678
PT

3340 – CP - 103

Figure 103: Blockflow Control Diagram of the 3340AR103 System

29.3.2 Unit of Control Modules – 3340AR103

The following table shows the details of the Control Modules considered for this Equipment
Module.

T1 Control Module
UN SCPF_InstAir EM 3340AR103 Sub EM

Tag Service
3340-AR-103 Instrument Air Receiver – Front End
3340-PIT-677 PRESSURE TRANSMITTER – Instr Air Front End

Table 863: List of Unit Controls – 3340AR103

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 680 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

29.3.3 Interlocks – 3340AR103

Not applicable

29.3.4 Alarms and Process Setpoints – 3340AR103

T3 Alarms and Process Setpoints


UN SCPF_InstAir EM 3340AR103 Sub EM
H
High Low
Tag Description Range Unit SP Y High Low
High Low
S
3340 PIT-677 Plant Air Pressure Transmitter 0 - 1000 KPa 600

Table 864: Alarms and Process Setpoint 3340AR103

29.3.5 Binary Messages – 3340AR103

T4 Binary State Messages


UN SCPF_InstAir EM 3340AR103 Sub EM
Tag Description OFF ON
Absolute {3340-
PIT-677}
Compressed Air Difference – Front
-
End Instr Air Pessure to CPF ×
Absolute {
Instrument Air Pressure
3340-PIT-675}
> 30 KPa

Table 865: Binary State Messages 3340AR103

The control room operator should be alerted when an undue difference in pressure occurs
between the front end instrument air pressure and instrument air header within the CPF. This
would likely be caused by manual valve isolation in the field.

29.3.6 Regulatory Control Loops – 3340AR103

Not applicable

29.3.7 Advanced Control Loops – 3340AR103

Not applicable

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 681 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

29.3.8 Description – 3340AR103

This front end air header provides a buffer storage of air a distance from the compressors thereby
reducing the risk of pressure drops under instantaneous high usage events.

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 682 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

30.0 APPENDIX – VENDOR CONTROL PHILOSOPHIES

30.0.1 Hydraulic Valves

MQ14 - 08 - DR - 3340 - PD1103


Document awaiting issuance.

30.0.2 Large Slurry Pumps

MQ15-718-TE-3340-IN0101

MQ15-718-TE-3340-
IN0101_4.pdf

30.0.3 Agitator

MQ15-722-DC-3340-IN0001

MQ15-722-DC-3340
-IN0001+(11510-21-ING-01-DOC-EL-01_0+CERT).pdf

30.0.4 Crossflow Separator

MQ15-727-TE-3340-IN1002

MQ15-727-TE-3340-
IN1002_0_Approved.pdf

30.0.5 Hydrofloat

MQ15-727-TE-3340-IN1001

MQ15-727-TE-3340-
IN1001_0_Approved.pdf

30.0.6 Product and Tails Sampler and Analyser

MQ15-720-IOM-3340-ME0002

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 683 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

MQ15-720-IOM-334
0-ME0002_0.pdf

30.0.7 Reagent Day Tank Dosing

MQ15-781-DC-3340-IN0001

MQ15-781-DC-3340
-IN0001_1.pdf

30.0.8 Frother Bulk Offloading and Storage

MQ15-780-PRC-3340-GA0001_1

MQ15-780-PRC-334
0-GA0001_1 (1).pdf

30.0.9 High Rate Settlers

MQ15-780-PRC-3340-GA0001_1

MQ15-51-TE-3340-G
A0601_1 approved 20220525.pdf

30.0.10 Regrind Cyclone

MQ15-718-TE-3340-IN0001

MQ15-718-TE-3340-
IN0001_1.pdf

30.0.11 Regrind Mill

MQ15-51-DR-3340-EE0011

MQ15-51-DR-3340-
EE0011_0+Functional+Description+(900111330).pdf

PROCESS
Anglo American Quellaveco S.A. MQ15-08-TE-3340-FS0001
CPF Quellaveco Project Page 684 of 684

COARSE PARTICLE FLOTATION PLANT FUNCTIONAL SPECIFICATION

30.0.12 Water Pumps

MQ15-715-DC-3340-IN0101

MQ15-715-DC-3340
-IN0101_Control+System+and+Philosophies.pdf

30.0.13 Compressed Air

MQ15-760-DR-3340-IN0001
MQ15-760-TE-3340-IN0001
MQ15-760-TE-3340-IN0002

MQ15-760-TE-3340- MQ15-760-TE-3340- MQ15-760-DR-3340


IN0001.pdf IN0002.pdf -IN0001.pdf