Professional Documents
Culture Documents
This specification has been revised as indicated below and described in the revision record
on the following page. Please destroy all previous revisions.
Record of Revisions
Revision Date Description
No.
0 1-13-2011 ISSUED FOR APPROVAL
TABLE OF CONTENTS
1.0 GENERAL
This specification contains the minimum design, installation, testing and commissioning
requirements for automatic wet sprinkler systems. The automatic wet sprinkler system is to
assure the safety of the occupants in the building during a fire. The design of the automatic
wet sprinkler system shall conform to this specification and the complete automatic wet
sprinkler system shall be fully compatible to all components supplied.
2.0 REFERENCES
The referenced codes and standards are intended to provide an acceptable level of quality for
materials, products and workmanship. In case of conflict between these standards and the
text of this Specification, the Specification text shall govern.
The latest revision of the referenced codes and standards shall be used as a minimum guide.
In case of conflict, the Contractor shall propose equipment, materials and processes
conforming to one group of codes and standards.
2.1 MARAFIQ
MQ-SP-P-4900 – PRIVATE FIRE SERVICE MAINS
MQ-SP-P-4901 – PUBLIC FIRE SERVICE MAINS-HYDRANTS AND FLOW
REQUIREMENTS
MQ-SP-P-4904 – AUTOMATIC RACK SPRINKLER SYSTEMS
MQ-SP-P-4905 – AUTOMATIC PREACTION SYSTEMS
MQ-SP-P-4906 – AUTOMATIC PREACTION DELUGE SYSTEMS
MQ-SP-P-4907 – STANDPIPE AND HOSE SYSTEMS
MQ-SP-P-4908 – FOAM-WATER SPRINKLER SYSTEMS
MQ-SP-P-4909 – AUTOMATIC AND SEMI-AUTOMATIC FOAM SYSTEMS
MQ-SP-P-4910 – AUTOMATIC WATER MIST FIRE PROTECTION SYSTEM
MQ-SP-P-4911 – STATIONARY FIRE PUMPS
MQ-SP-P-4912 – WATER STORAGE TANKS AND SUPPLY FOR PRIVATE
FIRE PROTECTION
MQ-SP-P-4913 – NOVEC FIRE SUPPRESSION SYSTEMS
MQ-SP-P-4914 – HIGH-PRESSURE CARBON DIOXIDE-CO2 FIRE SYSTEMS
MQ-SP-P-4915 – LOW-PRESSURE CARBON DIOXIDE-CO2 FIRE
SUPPRESSION SYSTEMS
MQ-SP-P-4916 – AUTOMATIC DRY CHEMICAL EXTINGUISHING SYSTEM
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4902
Project Name: Date: 28 Nov 2011
Contract Number: Page 6 of 22
Revision 3
3.0 DEFINITIONS
Refer to NFPA 13.
Backflow preventers shall be used where potable water could be contaminated through
siphoning or back pressure from fire water piping.
In the absence of any of the above, best accepted industry practice shall be employed
throughout.
5.0 SUBMITTALS
The Contractor shall submit to MARAFIQ, the following items for review and approval before
commencing the work:
Product Data
Product data shall include principal dimensions, general construction and material for
each item intended to be furnished and installed.
Manufacturer's catalog data sheets shall be submitted for all sprinkler heads, alarm check
valves and all other accessories and system components.
Installation Instructions
Submit copies of the manufacturer's installation and maintenance instructions for all
equipment. Include valve data and servicing instructions.
Shop Drawings
Working plans, prepared according to NFPA 13.
Submit Coordination Drawings
Superimposed drawings showing location of each sprinkler and all other activities
simultaneously.
Hydraulic Calculations
The hydraulic calculations for the entire automatic wet sprinkler system shall be by a
computer generated hydraulic calculation program, such as HAS, Elite, or Pipenet.
The calculations shall meet the requirements of NFPA 13 and shall be printed in a
standard NFPA format.
Hydraulic calculations shall be furnished when extending existing automatic wet
sprinkler systems.
As-Built Drawings
Clearly indicate sprinklers, systems, locations and symbols on the Shop Drawings
and As-built plans.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4902
Project Name: Date: 28 Nov 2011
Contract Number: Page 9 of 22
Revision 3
The Contractor shall prepare and submit a set of As-Built Drawings and hydraulic calculations
of the system, maintenance and instruction bulletins and the applicable parts of the
Contractor’s material and test certificates covering material and tests certifying that the work
has been completed and tested in accordance with plans and specifications.
All equipment shall be constructed using new materials designs and built in
accordance with the best practices of the industry.
Each item of equipment shall be listed by Underwriters Laboratories (UL) and / or
approved by Factory Mutual (FM).
Each major item of equipment shall bear the manufacturer’s name, trademark, serial
number and a UL or FM label.
Any sprinkler that is damaged, painted, or sprayed with any obstructive material shall
not be accepted.
The fire sprinkler system shall be an automatic wet sprinkler system connected to a water
supply and equipped with firewater sprinklers designed to provide a specific water discharge
and distribution over the protected area.
Backflow preventers shall be used where potable water could be contaminated through
siphoning or back pressure from fire water piping.
The fire sprinkler system shall be designed to avoid undue danger to the lives and safety of its
occupants from a fire.
The minimum and maximum spacing of the fire sprinklers shall be as per NFPA 13.
The system design density and hydraulic calculations shall follow the requirements of NFPA
13 and Project Specifications. The required water supply for each system shall be calculated
back to the source of supply. The required water supply shall include hose allowance as per
NFPA 13.
The fire protection water supply lines, controlling devices, protective devices, alarm systems,
supervisory devices and related equipment shall be made compatible so that all equipment
shall function together as specified.
The design of the fire sprinkler shall be coordinated with architectural, civil, mechanical and
electrical, design and construction documents, to ascertain the required information, to affect
a properly designed fire protection system for the building construction and occupancy
classification.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4902
Project Name: Date: 28 Nov 2011
Contract Number: Page 11 of 22
Revision 3
The design of fire protection systems shall be complete with all necessary accessories for
proper operation.
For each sprinkler zone, provide a control and fire alarm valve assembly, flow switch, self-
contained test and drain assembly and pressure gage, in accordance with NFPA 13.
System design and installation shall reflect high quality professional work that properly
accounts for practical maintenance concerns and aesthetic concerns, as well as meets the
design requirements.
The system and its components shall be suitably designed to withstand ambient temperature
changes, vibration, humidity, impact, clogging and corrosion.
Components within the protected spaces shall be designed to withstand the elevated
temperatures, which could occur during a fire.
The piping system shall be sized in accordance with a hydraulic calculation technique to
ensure availability of flows and pressures required for correct performance of the system.
Each section or area served by an automatic wet sprinkler system shall be capable of being
isolated by one water supply valve only. The stop valve in each section shall be readily
accessible, and its location clearly and permanently indicated.
Duration of the firewater supply shall meet the requirements of NFPA 13 and Project
Specifications.
8.0 PRODUCTS
All goods and products covered by these Specifications shall be procured, when available,
from an in-Kingdom manufacturer. Procurement of all goods and products manufactured out-
of-Kingdom must be approved by MARAFIQ. All products, system components and hardware
shall be in compliance with NFPA 13. Only listed materials and devices shall be used in the
installation of automatic wet sprinkler system. Components that do not affect system
operation, such as drain valves and signs, shall not be required to be listed.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4902
Project Name: Date: 28 Nov 2011
Contract Number: Page 12 of 22
Revision 3
System components shall be rated for the maximum working pressure to which they are
exposed, but not less than 12.1 bar (175 psi). System components installed outside, or in the
presence of a corrosive atmosphere, shall be constructed of materials that will resist corrosion
or shall be suitably protected from corrosion.
All products, system components and hardware shall be in compliance with the applicable
NFPA standards and the Project Specifications.
All valves, sprinklers, alarms and any additional fire fighting equipment shall be UL listed
and/or FM approved.
All fire department connections, couplings and thread types shall be fully coordinated and
matched with Local Fire Department requirements. No single thread type or coupling shall be
purchased before confirming and fulfilling Local Fire Department conditions.
8.2 Valves
All valves shall be specifically designed for the Fire Protection Service. All valves
shall meet or exceed NFPA 13; of type, construction and class.
Drain valves and test valves shall be UL listed and/or FM approved.
Swing type check valve, when selected shall have rubber coated clapper assembly
hinged to a removable access cover for periodic inspection as required in NFPA 25.
All check valves must have non-slamming characteristics.
Check valves shall be UL Listed and/or FM approved for fire protection service.
8.10WATERFLOW ALARMS
Waterflow alarm apparatus shall be listed for fire service.
8.11Waterflow Switches
UL 346 and/or FM Approved for the application in which it is used. Include 2 sets of
single pole double throw (SPDT) circuit micro-switches for isolated alarm and
auxiliary contacts.
8.12Pressure Switches
Pressure switches shall be electrical-supervision-type, water-flow switch with
adjustable retarding feature. They shall include SPDT, normally closed contacts and
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4902
Project Name: Date: 28 Nov 2011
Contract Number: Page 14 of 22
Revision 3
design that operate on rising pressure and signals water flow. The alarm pressure
switch shall be compatible with system devices.
Pressure switches shall be UL Listed and/or FM Approved for the application in which
it is used.
8.15Alarms
Alarms shall be as per NFPA 13.
An alarm unit shall include a listed mechanical alarm, horn, or siren or a listed electric
gong, bell, speaker, horn, or siren.
Outdoor water motor-operated or electrically operated bells shall be weatherproofed
and guarded.
Outdoor alarms attachments shall be listed for outdoor use.
The water motor alarm shall be furnished with an approved Y-strainer. All piping to
water motor-operated devices shall be provided with galvanized or other corrosion-
resistant material acceptable by NFPA 13 and of a size not less than 20 mm (¾ in.).
The water motor alarm shall be UL Listed and / or FM Approved for the application in
which it is used.
8.18Pressure Gauges
The required pressure gauges shall have a maximum limit not less than twice the
normal system working pressure at the point where installed.
Pressure gauges shall be moisture proof and weather resistant type.
Pressure gauges shall meet or exceed NFPA 13 requirements and are UL Listed
and/or FM Approved for firewater service.
9.0 EXECUTION
All products and equipment shall be installed in accordance with MARAFIQ regulations,
applicable local codes and standards, the manufacturer's written installation instructions and
Project Specifications.
The fire sprinkler system shall be installed in accordance the applicable NFPA standards.
Cover and protect equipment and materials from dirt, water, chemical or mechanical damage.
10.0 INSTALLATION
All materials and equipment used in the installation of the fire protection systems shall be new
and the latest design by the manufacturer.
All materials, valves and devices essential to successful system operation shall be UL Listed
and/or FM approved.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4902
Project Name: Date: 28 Nov 2011
Contract Number: Page 16 of 22
Revision 3
Components that do not affect system performance such as drain piping, drain valves and
signs are not required to be listed.
All fire department connection, coupling and thread type shall be fully coordinated and
matched with Local Fire Department requirements.
All valves shall meet or exceed NFPA 13; of type, construction and class.
10.2Sprinklers
Sprinklers shall be listed for the specific hazard and type of system in which they shall
be used.
Temperature characteristics, temperature ratings, classifications and color coding
shall be in accordance with NFPA 13 and as determined by the particular application
and hazard.
Sprinklers subject to corrosive environments shall be listed as corrosion-resistant.
Fire sprinklers shall be of one manufacturer throughout the building. No mixing of
sprinkler brands shall be permitted.
All sprinklers shall be permanently marked with a manufacturer symbol and model
number, so as to identify unique sprinkler identification for every change in orifice size
or shape, deflector characteristic, pressure rating and thermal sensitivity.
Keep sprinklers with protective caps or bulb shields contained within the caps or
shields during installation.
Take care not to damage the corrosion-resistant coating, when installing corrosion-
resistant sprinklers.
Metal cabinet containing the spare sprinklers shall be located adjacent to the alarm
valve within each building, or as otherwise indicated.
10.3Sprinkler Finishes
Finishes shall be chrome-plated, bronze or factory painted; as required by Project
Specifications.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4902
Project Name: Date: 28 Nov 2011
Contract Number: Page 17 of 22
Revision 3
10.4Sprinkler Guards
Furnish head guards, as required, from the same manufacturer as the sprinkler head.
Wire-cage type, including fastening device for attaching to sprinkler.
10.6Cabinets
Provide a separate cabinet for each type of sprinkler head; and a sprinkler head
wrench on the project.
10.7Piping
Installed piping, valves and fittings shall meet or exceed the requirements of NFPA 13
and Project Specifications.
Make connections between underground and above-ground piping using an approved
transition piece strapped or fastened to prevent separation.
Do not extend water supply connection into a building or through a building wall
unless such connection is under the control of an outside listed indicating valve or an
inside listed indicating valve located near the outside wall of the building.
Close pipe openings with caps or plugs during installation.
Use pipes, fittings and hangers that resist corrosion; or apply a protective coating to
all unprotected exposed surfaces of the sprinkler system, where corrosive conditions
exist due to moisture or fumes from corrosive chemicals or both.
Power and Water Utility Company for Jubail and Yanbu (MARAFIQ) Master Specification MQ-SP-B-4902
Project Name: Date: 28 Nov 2011
Contract Number: Page 18 of 22
Revision 3
10.9Isolation Valves
At least one listed indicating valve shall be installed in each source of water supply.
Locate all control valves where they shall be readily accessible and free of
obstructions.
Install a valve at the base of each riser.
Provide access doors or panels where control or drain valves are located behind
plaster or gypsum walls or ceilings as necessary. Access and signage shall be
obvious.
Sleeves for underground pipe shall have mechanical rubber seals and be watertight.
Signs shall be placed at the alarm valve or wet pipe valve supplying the
corresponding hydraulically designed area.
Each fire department connection to sprinkler systems shall be designated by a sign
having raised or engraved letters at least 25 mm (1 in.) in height on plate or fitting
reading service design.
The installation of signs required by NFPA 13 shall be verified.
11.0 PAINTING
Sprinklers shall only be painted by the sprinkler manufacturer.
Painting of all exposed pipe, fittings and equipment shall be per MARAFIQ Painting
Specification.
13.0 COORDINATION
Installation of sprinklers shall be coordinated with other work including duct and electric fixture
installation to prevent sprinkler obstructions.
Coordinate the location, signage, keying and access of fire sprinkler shutoff and zone valves
with MARAFIQ.
Coordinate location of each sprinkler head with reflected ceiling plan, including lighting and
diffuser/grille layout.
Coordinate location of drains shown on plumbing drawings with requirements of fire sprinkler
system.
15.0 TESTING
All new fire protection systems shall be tested prior to the occupancy of the building or the
area the system is protecting.
Testing of the fire protection systems shall be in accordance with NFPA 13, 25, and Project
Specifications.
Any or all of the system component or portion which fail the specified tests shall be retested
after corrective measures have been taken.
15.1Concealed Work
Concealed work (including underground) shall be tested and approval obtained from
MARAFIQ prior to covering.
All products shall be inspected at time of delivery for damage and for compliance with
specifications.
Sprinklers shall be delivered in their original packages, containers or bundles bearing the
brand name and the name of the material.
Pipe, fittings, valves, alarm valves and sprinkler heads shall be stored with open ends sealed
until removed for installation.
Materials shall be protected from weather, soil; and damage during delivery, storage and
construction.
Any products that are damaged or found not to be in accordance with the specifications shall
be immediately replaced.
17.0 CERTIFICATION
The Contractor shall prepare and submit a set of As-built Drawings and hydraulic calculations
of the system, maintenance and instruction bulletins, and the applicable parts of the
Contractor’s material and test certificates covering material and tests certifying that the work
has been completed and tested in accordance with plans and specifications.