Features
Sensors
(B)
3
types of operation mode are added. Shaded parts ( ) are changed and added Fiber
(total 14 types of operation modes) functions from previous MP5M Series.
Optic
Sensors
Frequency/Revolutions/Speed, Passing speed, Cycle, Passing
time, Time interval, Time differential, Absolute ratio, Density, (C)
Door/Area
Length measurement 1, Length measurement 2, Interval, Sensors
N Indicator
Output (J)
1 Relay single (high-limit) output+NPN open collector output Counters
Item
MP Pulse meter (M)
Tacho /
Speed / Pulse
Specifications Meters
·Operation mode F3, F4, F5, F6 : 0.01 to max. of each time range
Measurement range
·Operation mode F9, F10, F11, F14 : 0 to 99999
·Operation mode F12, F13 : -19999 to 99999
Measurement accuracy ·Operation mode F1, F2, F7, F8 : F.S.±0.05%rdg±1-digit
(23℃±5℃) ·Operation mode F3, F4, F5, F6 : F.S.±0.01%rdg±1-digit
Display cycle OFF (for F2, F14 operation mode), 0.05, 0.5, 1, 2, 4, 8 sec (same as update output cycle)
Frequency/Revolutions/Speed (F1), Passing speed (F2), Cycle (F3), Passing time (F4),
Time interval (F5), Time differential (F6), Absolute ratio (F7), Density (F8), Length measurement 1 (F9),
Operation mode
Interval (F10), Accumulation (F11), Addition/Subtraction-individual input (F12), Addition/Subtraction-phase
difference input (F13), Length measurement 2 (F14)
M-33
MP5M Series
Specifications
MP5M-2N MP5M-4N MP5M-21 MP5M-41 MP5M-22 MP5M-42
Model
Indicator High-limit setting High/Low-limit setting
Prescale function Direct input method (0.0001×10-9 to 9.9999×109)
※1
Hysteresis - 0 to 9999
Relay single 250VACᜠ 3A resistive load 1c -
Main
Relay dual - - 250VACᜠ 3A resistive load 1a ×2
output
NPN open collector Max. 30VDCᜡ 100mA Max. 30VDCᜡ 100mA ×2
Memory retention Non-volatile memory (number of inputs: 100,000 operations)
Insulation resistance Over 100MΩ (at 500VDC megger)
Dielectric strength 2,000VAC 60Hz for 1 min
Noise immunity ±2kV the square wave noise (pulse width: 1㎲) by noise simulator
Mechanical 0.75mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 1 hour
Vibration
Malfunction 0.5mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 10 min
Mechanical 300m/s² (approx. 30G) in each X, Y, Z direction for 3 times
Shock
Malfunction 100m/s² (approx. 30G) in each X, Y, Z direction for 3 times
Relay Mechanical - Min. 5,000,000 operations
life cycle Electrical - Min. 100,000 operations (250VAC 3A resistive load)
Environ- Ambient temp. -10 to 50℃, storage: -20 to 60℃
ment Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
Approval
※2
Weight Approx. 243g (approx. 168g) Approx. 256g (approx. 181g) Approx. 265g (approx. 190g)
※1: Setting range will vary depending on the decimal point.
※2: The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.
Connections
Indicator (MP5M- N) High-limit setting (MP5M- 1) High/Low-limit setting (MP5M- 2)
Brown
Brown
Brown
Black
Black
Black
Black
Black
Black
Blue
Blue
Blue
HOLD/ HOLD/ HOLD/
※ ※1
※
INA INB +12V 0V RESET 1 INA INB +12V 0V RESET 1 High INA INB +12V 0V RESET High Low
8 9 10 11 12 13 14 8 9 10 11 12 13 14 8 9 10 11 12 13 14
15
15 15
16
16 16
17
17 17
H L
1 2 3 4 5 6 7
1 2 3 4 5 6 7 1 2 3 4 5 6 7
CONTACT OUT: CONTACT OUT:
- + 250VAC 3A 250VAC 3A
※ RESISTIVE LOAD - + RESISTIVE LOAD - +
SOURCE 2 ※ ※
SOURCE 2 SOURCE 2
※1: Operation mode F1 to F10
: Display value HOLD
Operation mode F11 to F14
: Display value RESET
※2: Model Source
MP5M-21
24-48VDC
MP5M-22
24VAC 50/60Hz
MP5M-2N
MP5M-41
100-240VAC
MP5M-42
50/60Hz
MP5M-4N
M-34
Pulse Meter
Dimensions (unit: mm) (A)
Photoelectric
※Nameplate design is changed and rear length is shorten than previous MP5M Series. Sensors
(B)
Fiber
14.3 75 Optic
72 11.8
Sensors
(C)
Door/Area
Sensors
(D)
67.5
Proximity
Sensors
(E)
Pressure
Sensors
(F)
Rotary
Encoders
7.3 Controllers
46 4
(I)
Min. 91
SSRs / Power
68 00.7 Controllers
40.7
(J)
Counters
(K)
Timers
Unit Description 4
(L)
Panel
Meters
(M)
Tacho /
Speed / Pulse
Meters
1 (N)
Display
Units
2
(O)
Sensor
5 Controllers
3
(P)
Switching
Mode Power
Supplies
(Q)
Stepper Motors
& Drivers
& Controllers
※The high-limit setting model (MP5M- 1) does not include the dotted line parts. (R)
Graphic/
1: Display Logic
Panels
Displays current value in RUN mode.
Alternately displays setting parameters and corresponding value in SETTING mode. (S)
Field
2: key Network
Devices
In RUN mode, press the key once to check max./min. value.
In RUN mode, hold the key for over 2 sec to enter parameter groups.
(T)
3: , key Software
Select parameter groups, and select or setting values in the corresponding parameters.
4: Output status indicator
5: Thumbwheel switch for HIGH/LOW setting value
M-35
MP5M Series
Input Specifications
1. Input signal
Standard duty ratio of input signal is 1:1. ON
(1) Solid state input 1 OFF
Input frequency: Max. 50kHz (ON/OFF pulse width: min. 10㎲ of each) Pulse width
(2) Solid state input 2 ON OFF
Input frequency: Max. 5kHz (ON/OFF pulse width: min. 100㎲ of each)
※For F7, F8 operation mode, max. 1kHz (ON/OFF pulse width: min. 500㎲ of each) T
(3) Contact input
※T: Single cycle of input signal
① Input frequency: Max. 45Hz (when each ON/OFF pulse width is over 11ms)
② Contact specifications: 12VDC, stable switching of load current as small as 5mA
②NPN voltage ③NPN open collector ②PNP voltage ③PNP open collector
①Contact ①Contact
output type sensor output type sensor MP5M output type sensor output type sensor MP5M
+12V +12V
Sensor circuit
Sensor circuit
Sensor circuit
Sensor circuit
Sensor circuit
Sensor circuit
3.9kΩ
IN
IN
0V 3.9kΩ
(COM) 0V
(COM)
Parameter Groups
Terminal
input
Parameter 0 group RUN 11-12 HOLD/RESET
(max./min. monitoring value) ※
mode Input
※Operation mode F1 to F10
: Display value HOLD
Operation mode F11 to F14
2 sec 3 sec : Display value RESET
● Parameter 0 group
RUN mode
Flashes
※
alternately 1
hPEK 99999 Max. monitoring value
※Resetting monitoring value
: Hold the key for over 2 sec.
(reset current value)
M-36
Pulse Meter
● Parameter 1 group (A)
Photoelectric
Sensors
2 sec
RUN mode PARa1 PARa2 PARa3 (B)
Fiber
Optic
Sensors
3 sec (C)
Flashes Door/Area
※ Sensors
alternately 1 Operation mode
MODE F
ㄹ 1 ●Setting range: F1 to F14 (D)
Proximity
Sensors
(H)
●Setting range Temperature
Controllers
Parameter Output mode Parameter Output mode
STARD S (Standard) OUT-B B (Block) (I)
OUT-T Output mode
STARD OUT-H H (High) OUT-I I (One-shot) SSRs / Power
Controllers
OUT-L L (Low) OUT-F F (Deflection)
※Only appears in high/low-limit setting model. (J)
Counters
Output hysteresis
HYS 0001 ●Setting range: 0000 to 9999 (K)
Timers
(the setting range varies depending on the decimal point setting)
※Only appears in high-limit setting models, high/low-limit setting models.
(L)
Panel
Meters
(S)
Field
Network
MEMO Memory retention Devices
OFF ●Setting range: ㅒㅜON, OFF
(T)
Software
M-37
MP5M Series
● Parameter 2 group
2 sec
RUN mode PARa1 PARa2 PARa3
3 sec
Flashes
※
alternately 1 Decimal point location of display value
DOT 00000 ●Setting range: 00000, 000)0, 00)00, 0)000, )0000
● Parameter 3 group
2 sec
RUN mode PARa1 PARa2 PARa3
Flashes
※
alternately 1
Lock
LOC OFF ●Setting range: Parameter Function
3 sec OFF Unlock
LOc0 Locks all
LOc1 Parameter 1, 2, 3 lock
LOc2 Parameter 2, 3 lock
LOc3 Parameter 3 lock
M-38
Pulse Meter
Operation Mode by Parameter Groups ( : parameter display, X: no parameter display) (A)
Photoelectric
Sensors
Operation
mode F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 (B)
Parameter Fiber
Optic
Sensors
hPEK
0
(C)
lPEK Door/Area
Sensors
MODE
Appears in all operation modes (F1 to F14).
IN-A (D)
Proximity
※1 ※3 Sensors
IN-B
※2 ※4
OUT-T (E)
※1 Pressure
1 HYS Sensors
GVARD (F)
Rotary
AVToA Encoders
AVToB (G)
Connectors/
Connector Cables/
MEMO Sensor Distribution
Boxes/Sockets
DOT
(H)
tUNT Temperature
Controllers
PScaH
(I)
PScaY SSRs / Power
2 Controllers
PScbH
PScbY (J)
Counters
※5
DISpT
ㅊCOUnB (K)
Timers
3 LOC Appears in all operation modes (F1 to F14).
(N)
Monitoring delay function by output mode Display
Units
(Q)
Stepper Motors
& Drivers
& Controllers
(R)
Graphic/
Logic
Panels
(S)
Field
Network
Devices
(T)
Software
M-39
MP5M Series
Operation Modes [MODE]
Select operation mode from operation mode[MODE]of parameter 1 group.
MP5M has 14 operation modes.
F1 Mode: Frequency/Revolutions/Speed
Measures the frequency of input A and displays the calculated frequency, revolutions, and speed.
Hz 1 Timing chart
Frequency
kHz 0.001
rps 1 Input A
Revolutions
rpm (default) 60 t1 t2 t3 t4 t5 t6
Hold
mm/sec 1,000L input
cm/sec 100L 1 α 1 α 1 α 1 α 1 α
Display t1 t2 t3 t5 t6
Speed m/sec 1L
m/min 60L
km/hour 3.6L
F3 Mode: Cycle
Displays the measured time from Input A ON to the next ON.
Cycle (T) = t ※t: measurement time[sec]
Display t1 t2 t3 t5 t6
M-40
Pulse Meter
F4 Mode: Passing Time (A)
Measures the time from Input A ON to the next ON, and displays the passing time of the arbitrary distance. Photoelectric
Sensors
Passing time[sec]= t × α
(B)
L[m]
(α= ) Fiber
Distance advanced in 1 pulse cycle [m] Optic
Sensors
(H)
Temperature
Controllers
(I)
F5 Mode: Time Interval SSRs / Power
Controllers
Displays measured time of Input A ON
Time interval (T) = t
(J)
※t: measured time of input A ON [sec] MP5M Counters
Motor
Stamp (K)
Display value and display unit ([tUNT] of parameter 2) Timers
Sensor B (R)
Graphic/
Display value and display unit ([tUNT] of parameter 2) Logic
Sensor A Panels
M-41
MP5M Series
F7 Mode: Absolute Ratio
Measures and displays relative speed, amount, speed, etc.
of input B against input A in percentage (%).
Absolute ratio = (Input B / Input A) × 100% Flow meter A Flow meter B
Frequency of input B[Hz] × Bα
Absolute ratio = × 100[%]
Frequency of input A[Hz] × Aα
MP5M Liquid
※Aα: Prescale value of input A, Bα: Prescale value of input B
Timing chart
Input A
Display value and display unit
fA
Display value Display unit Input B
Absolute ratio % fB
※Hold: When the hold signal turns ON, the display value is Frequency of input B[Hz] × Bα
Display = × 100[%]
maintained until the display cycle turns to hold OFF. Frequency of input A[Hz] × Aα
F8 Mode: Density
Measures and displays the density ratio (%) of input B against the total sum of input A
and input B.
Input B
Density = × 100[%]
Input A + Input B Flow meter A Flow meter B
Frequency of Input B[Hz] × Bα
Density = × 100[%]
(Frequency of input A[Hz] × Aα) + (Frequency of input B[Hz] × Bα)
※Aα: Prescale value of input A, Bα: Prescale value of input B MP5M Liquid
Timing chart
Display value and display unit Input A
Display value Display unit fA
Density % Input B
fB
※Hold: When the hold signal turns ON, the display value is
maintained until the display cycle turns to hold OFF.
Photoelectric sensor
Display value and display unit MP5M
Display 6 α 2 α 4 α
M-42
Pulse Meter
F10 Mode: Interval MP5M
(A)
Measures and displays the number of input A pulses from Input B Photoelectric
Sensors
ON to the next ON.
Interval = P × α (B)
Fiber
※P: Number of input A pulses, α: Prescale value Optic
Sensors
③When RESET input is ON, the integrated counted value will be reset ※α=1 display value
to "0". (L)
Panel
Meters
(addition)
Timing chart (O)
Display value and display unit Sensor
H Controllers
Display value Display unit Input A L
(P)
Addition/ H Switching
Input B Mode Power
Subtraction Quantity L Supplies
(individual input) H
RESET (Q)
L Stepper Motors
& Drivers
Operation and timing chart & Controllers
Display 0 1 2 32 0 1 2 3 2 1
Pulse of input A is added, and pulse of input B is subtracted.
(R)
※α, β=1 display value Graphic/
Logic
Panels
(S)
F13 Mode: Addition/Subtraction- Phase difference input Field
Input A Network
When input A is low, counting is added to the low of input B. Devices
When input A is low, counting is subtracted from the high of input B. Input B
Addition/Subtraction (phase difference) (T)
Software
= Detects position and speed using A and B phases of MP5M
encoder outputs as input. Timing chart
H
Display value and display unit Input A L
Display value Display unit H
Input B
L
Up/Down counting
(phase difference Quantity H
RESET
input) L
Display 0 1 2 3 2 1 0 1 2 0
M-43
MP5M Series
F14 Mode: Length Measurement 2
Timing chart (e.g.) setting value of Input B=4
Measures and displays the number of pulses from input A until the value
of input B reaches the set value. H
Input A L
Length measurement 2 = P × α (until the setting value of Input B)
H 1 2 1 2 3 4 1 2 3
※P: Number of input A pulses, α: Prescale value Input B L
Comparative H
Comparative H value L
value L 0.3 sec (fixed)
※1
H
H Output 0.3 sec (fixed)
Output L
L ※1
H output : Comparative value H ≤ Display value H output : Comparative value H ≤ Display value
L output : Comparative value L ≥ Display value L output : Comparative value L ≤ Display value
Comparative H Comparative H
value L value L
※1 ※1
H H
Output Output
L ※1 L ※1
H output : Comparative value H ≤ Display value H output : Comparative value H ≥ Display value
L output : Comparative value L ≤ Display value L output : Comparative value L ≥ Display value
M-44
Pulse Meter
Function Comparative setting value H
(A)
Photoelectric
Hysteresis [HYS] Sensors
Near the comparative setting value, the output may turn ON/OFF Comparative setting value L
frequently and unstably. A (B)
Fiber
To prevent this, the hysteresis value is set based on the comparative A Optic
Sensors
setting value. Output H
※A: hysteresis value (C)
※The hysteresis value can be set to "0" but the actual operation value is "1". Output L Door/Area
Sensors
Delay Monitoring [GUArD]
After supplying power, the starting current of motors and other inputs are changeable. This function allows stable control by limiting all (D)
Proximity
outputs for a certain period period of time, until the target measurement unit stabilizes. It may also control L outputs until a specific output is Sensors
reached.
Comparative output limit function [fDEFY] (E)
: Only for S (Standard), B (Block), F (Deflection) output mode. Pressure
Sensors
: Limits L output before H output.
1) During S (Standard), B (Block) output mode 2) During F (Deflection) output mode
(F)
Rotary
Comparative output limit
Comparative
Encoders
Comparative
H function removal
value
H deviation (G)
value
Connectors/
L Setting value Connector Cables/
Sensor Distribution
L deviation Boxes/Sockets
H
Output H (H)
Temperature
L output Controllers
Comparative output limit L
function removal (I)
SSRs / Power
※After supplying power, there is no initial L comparative output ( ). ※After supplying power, there is no comparative output of L Controllers
Set monitoring delay time so that there is no output during the delay time.
L (L)
Panel
Meters
(M)
No output Tacho /
Auto-Zero Time Setting [AUToA, AUToB] L output Speed / Pulse
Meters
When there is no input signal during auto-zero setting time, the display value is automatically set to 0 (zero). Please set the auto-zero setting
time so that it is longer than the interval of the slowest input signal. If the setting time is too long and there is no input signal, the rate at which (N)
Display
the display value falls to 0 (zero) decrease, and output response rate may slow down. Units
MP5M = f×15
(Q)
Stepper Motors
Setting prescale value (α=15) ※f: The number of input pulses per second[Hz], & Drivers
& Controllers
Set mantissa (X) as 1.5000, and exponent (Y) as 1 for prescale value (α)=15. α: Prescale value
The same display value can be obtained with α value set as X=0.1500, and Y=2. N: The number of pulses per revolution (R)
Graphic/
● Please separate the unit wiring from high voltage lines or power lines to prevent inductive noise. (S)
Field
● Install a power switch or circuit breaker to control the power supply. Network
● In case of 24VAC, 24-48VDC model, power supply should be insulated and limited voltage/current or Class 2 SELV power supply device. Devices
● The power switch or circuit breaker should be installed where it is easily accessible by the user.
● Do not use the unit in the following environments. (T)
Software
① Environments with high vibration or shock.
② Environments with exposure to direct sunlight.
③ Near machinery which produce strong magnetic force or electric noise.
● Storing the unit
When storing the unit for an extended period, please avoid direct exposure to sunlight. Ambient temperature should be between -20℃ to
60℃ and ambient humidity should be between 35% to 85%RH. Store in factory packaging for best results.
● Input line
Please use a shield wire in environments where noise may occur or instances where long measurement input lines are required.
● Please maintain distance between the power supply line and measurement input line.
● This product may be used in the following environments
① Indoors ② Max. altitude: 2,000m
③ Pollution degree 2 ④ Installation category II
M-45