Professional Documents
Culture Documents
Introduction
1.1 Scope and purpose
This Code of Practice sets out the requirements for the design, specification, installation,
commissioning,operation and maintenance of grid-connected solar photovoltaic (PV) systems
installed in the UK.
A PV roof tile is designed to replace conventional roofing materials. PV roof tiles vary in their
size and framing details.
The frame of a PV roof tile is designed to allow units to interlock and provide a weather-tight
seal A variety of materials are used for PV tile frames, including plastics and aluminum.
BBIPV is a generic term that describes any module that is used to replace a standard part of a
building envelope, such as a façade or an area of glazing.
The standard module include:
● A glass rear sheet this allows the module to be transparent,
● The lack of frame many BBIPV modules are supplied as an unframed laminate
● Bespoke sizes, BBIPV modules can be much larger (and smaller) than a standard
modules.
● Bespoke shapes: while most modules are rectangular, BBIPV shapes can vary,
● Cable details for example, cables may exit from module edges;
● Additional layers: for example, BBIPV may be built into double glazed units.
A solar PV cell is a device that exhibits the photovoltaic effect, capturing solar radiation
(photons) from the Sun and converting it into electricity.
● A number of solar PV cells are connected in series to achieve the desired output voltage
of the PV module.
● To achieve the desired output current, a number of these series-connected strings of
cells may also be wired in parallel.
Various IEC standards are in place to provide safety and performance tests for solar PV
modules.
Three classes are defined:
● Class A module: commonly available 'standard' modules. Modules are considered to
meet the requirements for safety class II.
● Class B module considered to meet the requirements for safety class 0.
● Class C module: considered to meet the requirements for safety class III.
2.2 Inverters
General
An inverter is an electrical device that converts direct current (DC) into alternating current (AC).
As the output of a PV module is DC and the UK electricity network is AC, an inverter forms a
key component of a grid-connected PV system.
Section 3
Solar PV array and module operating characteristics and behavior
3.1 General
The DC side requires an understanding of three key characteristics of a PV module/array:
1. Traditionally, PV arrays have not had a fixed voltage, some newer technologies do work on a
fixed voltage. Both technologies do not have a fixed current.
Section 4
System performance
4.1 Pitch and orientation
In the UK, maximizing the annual output from a grid-connected PV array will generally be
achieved by orientating the array due south and at a pitch related to the site latitude and
predominant weather conditions.
● A site that consistently has cloud at one end of the day may favour an orientation
towards the sunnier part of the day,
● A site with hills, buildings or other obstacles that obscure the Sun at one end of the day
may favour an orientation away from the obstacles;
● Roof construction may dictate the array pitch and orientation (though some arrays
frames will allow arrays to face in a different orientation/pitch to the roof).
In the UK geographically the coastal sites are also generally better than those further inland.
Coastal sites tend to be sunnier due to lower cloud levels.
● Dirt/ soiling
● Far shading
● Near shading
● Cell temperature losses
● Module quality losses
● Mismatch losses
● DC wiring ohmic losses
● AC wiring ohmic losses
● AC connection losses
● Equipment failures losses
A number of different software tools and procedures are available for estimating the
performance to be expected from a grid-connected PV system in calculating the result,
including:
a) Module and inverter-manufacturer and model.
b) nominal array power used in calculations;
c) May orientation and pitch used in calculations,
d) Site location assumed in calculations;
e) Details on the irradiance files used (including the source of the data and the geographic
location the irradiance data is based on)
f) A description of the shade situation on the array to include both near and far shade.
g) Where an estimate includes payback or other financial calculations, the financial
assumptions used in compiling the report.
—-------------------------
Section 5
5.1 General
DC system-general requirements
DC cables
● Cable shall be double insulated, or have equivalent performance according to BS 767
● In systems with Uoc_stc>1000Vdc access to the entire PV atay and associated wiring
and protection shall be restricted to a on defined in BS IEC 62548
DC connectors
● Shall be class or equivalent construction and selected in accordance with RS EN 62852
5.2
DC system voltage and current ratings
5.2.1
General
5.2.2
Voltage and current rating: crystalline silicon modules
Formula
The values of (Udc_max) and (ldc_max)can be calculated as follows
● (Udc_max) x1.2
● (ldc_max)×1.25
5.2.3
Voltage and current rating: other module types
Due to their differing characteristics, it is not possible to provide a simple pair of multipliers to
apply to modules that are not constructed using crystalline silicon cells. For such modules
installed in the UK individual calculations need to be performed as follows
Systems with other module types:
Using manufacturer's data, the values of (Udc_max) and (ldc_max) shall be calculated
assuming a minimum temperature of 15'C and a maximum irradiance of 1.250 W/m².
5.2.4
Voltage and current rating: Modules fitted with DC power
5.3
DC system: voltage considerations
The DC voltage encountered in a PV array is set by the maximum voltage of the (Udc_max)
and the number of modules connected in series. All parts of the DC array circuit shall be rated
to the maximum system voltage. It can be calculated by formula.
5.4
DC system: current considerations
The DC current encountered in a PV array is set by the current of the modules and the number
of PV strings connected in parallel.
For a system using standard crystalline modules where no power optimizers are fitted all parts
of the circuit (to include cables, isolators, switchgear and connectors) shall be rated to the
current values described in following formula.
● Array formed of single PV string
5.5
Overcurrent protection
5.5.1
General
This Section relates to a system where the PV array provides the only source of fault.
● For systems with one of the active conductors functionally earthed: the overcurrent
protective devices shall be installed in all unearthed conductors
● For systems without any functional earth connection: the overcurrent protective devices
are only required in one of the active conductors.
5.5.2
String overcurrent protection
String Overcurrent protection shall be fitted to all PV arrays (and sub-arrays) where:
1.35 x Imod_max_ocpr < (Ns-1) x Isc_max
Note:
This calculation applies to an array with parallel connected strings.
i. Device selection
The string overcurrent protective device shall be selected with a rated current (In) such that
following conditions are met
String overcurrent protective devices shall be located at the end of the PV string cables at the
where the strings are paralleled and overcurrent protective devices shall be readily
accessible-for example, at the string combiner box or inverter.
5.5.3
Sub-array overcurrent protection
Sub-ray overcurrent protection shall be provided if more than two sub-arrays are single inverter
i. Device selection
The sub-array overcurrent protective device shall be selected with a rated curent (such the
following conditions are met:
● In > 1.25 x Isc_sub_array
● In <= 2.4 x Isc_sub_array
Sub-array overcurrent protection devices shall be located at the end of the sub-array cabl point
where the sub-arrays are paralleled andovercurrent protective devices shall be readily
accessible-for example, at the sub-array combiner box or inverter.
5.5.4
Array overcurrent protection
Array overcurrent protection is required where the array is connected to a battery (DC coupled).
i. Device selection
The array overcurrent protective device shall be selected with a rated current (I.) such that both
of the following conditions are met:
● In > 1.25 x Isc_sub_array
● In <= 2.4 x Isc_sub_array
Array overcurrent protection devices shall be located where the array connects to the source of
the fault current-le, at the battery connection in battery systems.Array overcurrent protective
devices shall be readily accessible.
5.6
Overcurrent protection of grouped strings
Where the overcurrent protection rating of a PV module is much larger than its normal operating
current, it may be possible to group a number of PV stings under the protection of a single
overcurrent protective device.
This is a special case and is not possible for most typical modules.
Grouping of strings can generally only be performed where
Imod_max_ocpr > 4 x Isc_mod
Condition
where:
5.7.1 General
The PV array shall be equipped with devices for isolation and switching according to following
conditions.
i. PV string
● For small systems isolation is achieved by suitably located plug and socket connectors.
● For large systems isolation is typically achieved using removable strings fuses in the
array combiner box
ii. Sub-array
● For small systems N/A
● For large systems isolation is typically achieved using a removable sub-array fuse or
switch disconnector.
iii. Array
● For small systems isolation is typically achieved using a switch disconnector or circuit
breaker.
● For large systems isolation is typically achieved using a switch disconnector or rated
suitably circuit breaker.
5.8
Combiner boxes
String or sub-array combiner boxes need to be selected and erected to maintain the insulation
class afforded by the rest of the circuit. The design of the box also needs to take into
consideration segregation between positive and negative parts, so as to permit safe installation
and maintenance and to minimize the risks of arcs. The combiner box shall be rated for the
voltage and current maxima calculated for the circuit (see Section 5.2, 5.3 and
5.9
PV array plug and socket connections
Correctly selected and erected plug and socket connections provide a quick safe and durable
Interconnecting PV string circuits. The majority of PV modules come with a plug and socket
connection Many inverters also come with plug and socket connections as standard. The plug
and socket shall be rated for the voltage and current maxima calculated for the circuit
(see Section 5.2, 5.3 and 5.4).
5.10
DC cables
5.10.1
Cable ratings
Within the DC circuits of a PV array shall comply with the following basic requirements;
i. Voltage rating
PV array cables shall be rated for the DC voltage maxime calculated for the circuit (Section 5.3)
● PV amay cables shall have a DC current-carrying capacity of greater than the current
maxime calculated for the circuit (see Sections 5.2 and 5.4, and as required by BS 7671.
● Appendix 4 of BS 7671 contains further guidance to determine the current carrying
capacity Izc(dc) of cables under the event conditions.
● Cables shall be selected to ensure that they are rated for the environment in which they
will be installed (temperature, UV, water resistance etc).
● Cables routed behind a PV array shall have a temperature rating of at least 70°C.
5.10.2
PV string cables
The cables used to interconnect PV modules (PV string cables) shall comply with BS-EN-50618
Electric cables for photovoltaic systems.
5.10.3
Cable installation
Cables Installed within buildings may need to meet additional requirements, such as use of low
smoke and fume (LSF) cable types.
Note:
1. Solar PV DC cables (cables to BS EN 50618) shall not be directly buried in walls or
otherwise encased in the fabric of the building. Where burial in walls cannot be avoided.
2. Conductors shall be suitably protected from mechanical damage; and a plan showing
cable locations shall be provided in the system Operation and Maintenance (O & M)
manual.
Procedure for buried Solar PV DC cablels
● BurIed in the ground at a suitable depth considering the use of the area under which the
buried ( see Section E2).
NOTE 1: Standard PV cables are not suitable for direct burial as mechanical damage would be
very difficult to detect and could lead to a fire risk.
NOTE 2:Direct burial in walls or building fabric is taken to mean where cables are cast into part
of the building (for example,within plaster or concrete).
NOTE 3: Suitable methods of mechanical protection for cables concealed in walls or building
fabric may include the use of earthed metallic conduit or trunking. Cables within the metallic
containment are still required to meet the requirements for double or reinforced insulation.
NOTE 4: The requirement for double or reinforced insulation on the DC side and separation of
L+ and L- conductors (see Regulation 712.521.101 of BS 7671) precludes the use of certain
wiring systems.
5.10.4
Cable labelling
The DC cables in a PV array remain energized whenever the PV array is generating, particularly
during daylight, and much of the DC circuit will stay live even after DC isolators have been
operated. As a result DC cables need to be clearly identified.
"DC cables shall be balled PV array cable-live during daylight for equivalent)".
5.10.5
Cable sizing
To maximize the output of the solar PV system and losses in the PV array DC cables need to be
minimized.
Note: For systems of up to 50 kWp, DC cables shall be sized such that the voltage drop at the
rated power ( Vmmp, Impp) is less than 3%.
5.11.1
Insulation faults can be the result of a wide variety of causes, including:
● Water ingress into junction boxes or PV laminates.
● Rodent or abrasion damage to cables.
● Insulation damage due to thermal, UV or wind cycling of cables or other components.
● Impact or storm damage.
5.11.2
Earth insulation resistance
A PV array needs an insulation resistance to Earth that is sufficiently high to minimize the extent
of earth leakage currents. Earth leakage currents will naturally occur in all PV arrays, primarily
from the PV modules but also from other parts such as the wiring system.
NOTE: The extent of naturally occurring leakage currents is determined largely by the size of
the PV array the larger surface area the lower the insulation resistance) Earth insulation
resistance is determined, using the principle of Ohm's Law, by applying a voltage.
● ≤20. 30 ΚΩ
● > 20 to ≤ 30 20 kQ
● >30 to ≤ 50 15 kQ
● >50 to ≤ 100 10 ΚΩ
● >100 to ≤200 7 kQ
● ≥ 400k to ≤ 500 3 ΚΩ
● > 500 1 kQ
A residual current monitoring device (RCM) monitors the current on the two cables that supply a
circuit In an ideal fault-free system, the sum of the two currents should be zero.
The RCM shall incorporate both continuous and step-change monitoring with fault thresholds
determined according to Table 5.4.
The earth fault alarm can be triggered by either the insulation resistance or the residual current
monitors in systems in which the system is designed to continue to operate in the event of an
insulation or residual current fault.
● 0 –- 25 KWp ≤ 1A
● >50–-100 KWp. ≤ 3A
● >100–-250 KWp ≤ 4A
● >250 KWp ≤ 5A
5.13.1 General
When designing the earthing and bonding arrangements of a PV array frame it is important to
understand various terms.
(d) Array frame functional earthing is the connection of the array frame to earth to enable a
part of the PV system to function correctly.
—----------------------
Section 6
Protection against lighting and overvoltage
6.1 General
Action may be required to bring down the lighting effect by fitting an external Lighting Protection
System (LPS) and Surge protection Device (SPD) lighting current or surge arrestors or
combination of both. An external LPS consists of an air termination network, down conductors
and earthing system.
An SPD operates by diverting or limiting potentially harmful surge currents. Two types of SPD
generally need to be considered
● Type 1: Lightning current arrester designed to discharge very high levels of lightning
current.
● Type 2: Surge arrester intended to divert lightning induced surges Used to protect
particular components or parts of a system.
● Combined Type 1-Type 2 arrestors are available and are commonly used.
—----------------------
Section 7
Inverter
7.1.1 General
To ensure an effective system, an inverter needs to be selected so that the PV array stays within
the MPP voltage range of the inverter (this may be 80-200% oversizing with current systems)
under normal operating conditions.
Inverter selection
● An Inverter shall be suitable for the voltage maxima calculated for the circuit to which it is
connected ( see Section 5.3)
Inverter location
inverters shall be installed in a location that is suitable to their design. The following factors will
typically need to be considered.
● Indoor or outdoor location
● Ventilation requirements
● Clearance distance
● Cabling requirements
● Acces requirements
● Orientation
● Fire detection
● Adjacent materials
—----------------------