Professional Documents
Culture Documents
The controller compares the measured value to the set point and
takes the appropriate corrective action by calculating the
controller output and transmitting it as an electronic signal to the
control valve.
Simple diagram of a feedback controller
Analog vs Digital
BASIC CONTROL MODES
Proportional Control
𝑒 𝑡 = 𝑥𝑠𝑝 𝑡 − 𝑥𝑚 (𝑡)
𝑥𝑠𝑝 𝑡 = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
𝑥𝑚 (𝑡)
𝑥𝑚 𝑡 > 𝑒𝑥𝑠𝑝 𝑡
𝑒 𝑡 <0
(-) Kc (-)
e(t) Proportional p
Controller W2
In this case Kc must be a positive number
For proportional controllers, bias 𝑝ҧ can be adjusted,
a procedure referred to as manual reset.
e KC p
On the other hand, in analyzing control systems it can be
more convenient to express the error signal in engineering
units such as C or mol/L.
and thus
Only then does the integral term begin to decrease. After the
integral term becomes sufficiently small, the controller output
moves away from the saturation limit and has the value
determined by
Reset windup occurs when a PI or PID controller encounters
a sustained error, for example, during the start-up of a batch
process or after a large set-point change.
Note that the controller parameters for the expanded form are
three "gains, "KC , KI and KD , rather than the standard
parameters, Kc, τI , and τD ·
Also assume that the control valve is designed so that the flow
rate through the valve increases as the signal to the valve, p(t),
increases. In this case the valve is designated as air-to-open
(or fail close).
The question is: should the flow controller have direct or
reverse action?
Clearly, when the measured flow rate is higher than the set
point, we want to reduce the flow by closing the control valve.
For an air-to-open valve, the controller output signal should be
decreased. Thus, the controller should be reverse-acting.
But what if the control valve is air-to-close (or fail open) rather
than air-to-open? Now when the flow rate is too high, the
controller output should increase to further close the valve.
Here, a direct-acting controller is required.
General Guideline for Specifying the Controller Action (Direct
or Reverse):
where pmax and pmin denote the on and off values, respectively
These two possible values of controller output also indicates why on-off
control is sometimes referred to as two-position or bang-bang control.
Characteristics of an On-Off Control Action
Note that on-off control can be considered a special case of
proportional control with a very high controller gain.
Proportional control speeds up the process response and reduces the offset.
The addition of integral control action eliminates offset but tends to make the
response more oscillatory.
Adding derivative action reduces both the degree of oscillation and the response
time.
Proportional control: effect of controller gain