CTDA1 Float Compressor discharge TC 1.


CTDA2 Float Compressor discharge TC 2.
KSPL1 Float Maximum CTDA constant.
KSPL2 Float Minimum CTDA constant.
KSPL3 Float CTD gain constant.

TTXM Float Average exhaust temperature.


KSPL4 Float TX gain constant.
KSPL5 Float TX offset constant.
KSPL6 Float Maximum reportable spread.
KSPL7 Float Minimum reportable spread.
TTXSPO Float Allowable spread offset.
L83SPO Boolean Allowable spread offset enable.
KSPL8 Float Maximum allowable bias.
KSPL9 Float Allowable bias removal time constant.
L83SPMB Boolean Allowable bias enable.
TTXD2[ ]Float Exhaust TCs ranked by value.
KSP1 Float Allowable spread gain constant.
KSP2 Float Allowable spread gain constant.
KSP3 Float Allowable spread gain constant.
KSP4 Float Allowable spread gain constant.
L83SPM Boolean Spread alarm permissive.
JXD[ ] Long Integer Index of TC positions array.
TXTOTTC Long Integer Total number of TCs configured.

Output
CTD Float Highest compressor temperature.
LJCTDA Boolean CTD limited.
TTXSPL Float Allowable spread temperature.
BIAS Float Filtered bias value.
TTXSP1 Float Calculated temperature spread 1.
TTXSP2 Float Calculated temperature spread 2.
TTXSP3 Float Calculated temperature spread 3.
L60SP1 Boolean Exhaust temperature spread 1 alarm 1.
L60SP2 Boolean Exhaust temperature spread 1 alarm 2.
L60SP3 Boolean Exhaust temperature spread 2 alarm.
L60SP4 Boolean Exhaust temperature spread 3 alarm.
L60SP5 Boolean Exhaust temperature spread low adjacency alarm (1 to 2).
L60SP6 Boolean Exhaust temperature spread low adjacency alarm (2 to 3).