You are on page 1of 2

Name: Mahmoud Afify Mohamed

ID:19016563
Alexandria university
Faculty of Engineering
Mechanical Engineering Department
st
1 term 2023

LG HVAC SOLUTION WATER COOLED SCREW CHILLER:

Standard conditions:
Entering / leaving chilled water temperature is 12/ 7 °C (53.6 / 44.6 °F).
Entering / leaving cooling water temperature is 32/ 37 °C (89.6 / 98.6 °F).
➢ Selecting the model RCWWO22CA2A which has the following:
cc = 713 kw
power = 147.07 kw
cop = 4.8
Assuming the following data:
Tchilled water = 7 °C & ∆Te= 5 °C
Tcondenser = 37 °C & ∆Tc= 10 °C

✓ Therefore
Tevaporator = 7-5=2 °C
Tcondenser = 37+10 = 47 °C

✓ From chart R134a


h1= 399 kw/kg
h2=425 kw/kg
h3=h4=270 kw/kg

✓ Calculations:
ṁ=cc/(h1- h4)= 5.48 kg/s
power= ṁ*( h2- h1)= 137.12 kw
cop= cc/power= 5.2