A HIGH HIGH CONDUCTIVITY QT1A Conductivity has reached set limit (PLC-set)
Action: Measures:
Stops boiler VA1A Check that blow-down switch is in automatic mode (in Selections
menu).
Note: Check blow-down set point.
Alarm is inactivated if water level i less Check blow-down valve and its pilot valve with solenoid.
than 50% (level below conductivity Check instrument air pressure.
electrode). Check conductivity of boiler water.
Check conductivity transmitter.
Check that all valves in blow-down pipe are open.
A HIGH HIGH CONDUCTIVITY QT1B Conductivity has reached set limit (PLC-set)
Action: Measures:
Stops boiler VA1B Check that blow-down switch is in automatic mode (in Selections
menu).
Note: Check blow-down set point.
Alarm is inactivated if water level i less Check blow-down valve and its pilot valve with solenoid.
than 50% (level below conductivity Check instrument air pressure.
electrode). Check conductivity of boiler water.
Check conductivity transmitter.
Check that all valves in blow-down pipe are open.
A HIGH HIGH STEAM PRESSURE PS1A Pressure has reached set pressure relay limit
Action: Measures:
Stops boiler VA1A Check steam pressure.
Check pressure controller's set point.
Check that pressure controller is in automatic mode.
Optimize controller's parameters for gain and I-time if pressure relay
tripped during normal operation.
Check pressure relay's set point.
A HIGH HIGH STEAM PRESSURE PS1B Pressure has reached set pressure relay limit
Action: Measures:
Stops boiler VA1B Check steam pressure.
Check pressure controller's set point.
Check that pressure controller is in automatic mode.
Optimize controller's parameters for gain and I-time if pressure relay
tripped during normal operation.
Check pressure relay's set point.
A HIGH HIGH WATER LEVEL LS1A Level has reached high level electrode
Action: Measures:
Stops boiler VA1A Check water level.
Check that overflow switch is in automatic mode (in Selections
menu).
Check overflow set point.
Check overflow valve and its pilot valve with solenoid.
Check instrument air pressure.
Check level transmitter.
Check level electrode.
Check that all valves in overflow pipe are open.
A HIGH HIGH WATER LEVEL LS1B Level has reached high level electrode
Action: Measures:
Stops boiler VA1B Check water level.
Check that overflow switch is in automatic mode (in Selections
menu).
Check overflow set point.
Check overflow valve and its pilot valve with solenoid.
Check instrument air pressure.
Check level transmitter.
Check level electrode.
Check that all valves in overflow pipe are open.
A HIGH TEMP. HEATER BOX TS1A Temp. has reached set thermostat limit
Action: Measures:
Stops boiler VA1A Check temperature in heater box.
Check ventilation fan in heater box.
Check for water leakage from elements and element flanges.
Check thermostat's set point.
A HIGH TEMP. HEATER BOX TS1B Temp. has reached set thermostat limit
Action: Measures:
Stops boiler VA1B Check temperature in heater box.
Check ventilation fan in heater box.
Check for water leakage from elements and element flanges.
Check thermostat's set point.
A HIGH TEMP. HEATER BOX TS2A Temp. has reached set thermostat limit
Action: Measures:
Stops boiler VA1A Check temperature in heater box.
Check ventilation fan in heater box.
Check for water leakage from elements and element flanges.
Check thermostat's set point.
A HIGH TEMP. HEATER BOX TS2B Temp. has reached set thermostat limit
Action: Measures:
Stops boiler VA1B Check temperature in heater box.
Check ventilation fan in heater box.
Check for water leakage from elements and element flanges.
Check thermostat's set point.
A LOW LOW WATER LEVEL LS2A Level is below low level electrode
Action: Measures:
Stops boiler VA1A Check water level.
Check feed water valve, its actuator and positioner.
Check instrument air pressure.
Check level controller's set point.
Check that level controller is in automatic mode.
Check level transmitter.
Check level electrode.
Check that all valves in feed water pipe are open.
Check that overflow valve is closed.
Check that blow-down valve is closed.
Check that boiler's drain valve is closed.
A LOW LOW WATER LEVEL LS2B Level is below low level electrode
Action: Measures:
Stops boiler VA1B Check water level.
Check feed water valve, its actuator and positioner.
Check instrument air pressure.
Check level controller's set point.
Check that level controller is in automatic mode.
Check level transmitter.
Check level electrode.
Check that all valves in feed water pipe are open.
Check that overflow valve is closed.
Check that blow-down valve is closed.
Check that boiler's drain valve is closed.
B HIGH STEAM PRESSURE PT1A Pressure has reached set limit (PLC-set)
Action: Measures:
Indication Check steam pressure.
Check pressure controller's set point.
Check that pressure controller is in automatic mode.
Optimize controller's parameters for gain and I-time if pressure relay
tripped during normal operation.
Check set point for pressure limit.
B HIGH STEAM PRESSURE PT1B Pressure has reached set limit (PLC-set)
Action: Measures:
Indication Check steam pressure.
Check pressure controller's set point.
Check that pressure controller is in automatic mode.
Optimize controller's parameters for gain and I-time if pressure relay
tripped during normal operation.
Check set point for pressure limit.
B HIGH WATER LEVEL LT1A Level has reached set limit (PLC-set)
Action: Measures:
Indication Check water level.
Check that overflow switch is in automatic mode (in Selections
menu).
Check overflow set point.
Check overflow valve and its pilot valve with solenoid.
Check instrument air pressure..
Check level transmitter.
Check level electrode.
Check that all valves in overflow pipe are open.
B HIGH WATER LEVEL LT1B Level has reached set limit (PLC-set)
Action: Measures:
Indication Check water level.
Check that overflow switch is in automatic mode (in Selections
menu).
Check overflow set point.
Check overflow valve and its pilot valve with solenoid.
Check instrument air pressure..
Check level transmitter.
Check level electrode.
Check that all valves in overflow pipe are open.
B SIGNAL FAULT T01 VA1AAT-1 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT T01 VA1AAT-2 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT T01 VA1BAT-1 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT T01 VA1BAT-2 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT T02 VA1AAT-1 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT T02 VA1AAT-2 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT T02 VA1BAT-1 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT T02 VA1BAT-2 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT T03 VA1AAT-1 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT T03 VA1AAT-2 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT T03 VA1BAT-1 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT T03 VA1BAT-2 Signal from current transformer out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT U08/CH1 VA1-AT External power limit signal for VA1A out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT U08/CH2 VA1-AT External power limit signal for VA1B out of range
Action: Measures:
Indication Check current transformer and its built-in 4-20mA transmitter.
Check signal connections
B SIGNAL FAULT VC1AP Signal from valve position transm. out of range
Action: Measures:
Stops boiler VA1A Check valve position transmitter on feed water valve's
actuator/positioner..
Check signal connections
B SIGNAL FAULT VC1BP Signal from valve position transm. out of range
Action: Measures:
Stops boiler VA1B Check valve position transmitter on feed water valve's
actuator/positioner..
Check signal connections