1 Lap ends of wire mesh a minimum of

6 inches.
6" min.
3"
2 Concrete collar is required when
annular space between the outside
Trim pipe of the pipe and the wall of the
and fill voids structure is 2 inches or greater.
with mortar. Wall of Precast Manhole
6"
min. or Intake Structure 3 Provide two #4 hoop bars in concrete
collar. Lap bars a minimum of 6 inches.
6"
min.
4 Trowel concrete flush with inside
4" min. wall of structure.

2 4
1 6"x6" - w2xw2
(8ga.) Wire Mesh

TYPE PC-1 CONCRETE COLLAR CONNECTION

12" 12"

3
n
mi. 3"
6"

CONCRETE COLLAR FOR PIPES 12" AND SMALLER

Wall of Precast Manhole


or Intake Structure

9" min.
1
6"x6" - w2xw2 4" min.
(8ga) Wire Mesh

TYPE PC-2 CONCRETE COLLAR CONNECTION 2 4

Pipe Joint
Overlap fabric
FI

12" 12" 12" at top of pipe.


GURE 4020.

min. min.
REVISION

2 04-17-18

3
FIGURE 4020.211 STANDARD ROAD PLAN
SW-211
211

SHEET 1 of 1
REVISIONS: Removed 'Invert' callout on Pipe to Structure View. Retitled and replaced old
Iowa DOT and SUDAS logos with new logos.
SHEET 1 OF 1

CONCRETE COLLAR FOR PIPES GREATER THAN 12"


SUDAS DIRECTOR DESIGN METHODS ENGINEER
Engineering
Fabric PIPE JOINT WRAPPING

STORM SEWER PIPE CONNECTIONS


PIPE TO PIPE CONNECTION PIPE TO STRUCTURE CONNECTION