You are on page 1of 9

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO.

4, JULY 2014 1683

Instability of Wind Turbine Converters During


Current Injection to Low Voltage Grid Faults and
PLL Frequency Based Stability Solution
Ömer Göksu, Student Member, IEEE, Remus Teodorescu, Fellow, IEEE, Claus Leth Bak, Senior Member, IEEE,
Florin Iov, Senior Member, IEEE, and Philip Carne Kjær, Senior Member, IEEE

Abstract—In recent grid codes for wind power integration, wind


turbines are required to stay connected during grid faults even
when the grid voltage drops down to zero; and also to inject reac-
tive current in proportion to the voltage drop. However, a physical
fact, instability of grid-connected converters during current injec-
tion to very low (close to zero) voltage faults, has been omitted, i.e.,
failed to be noticed in the previous wind power studies and grid
code revisions. In this paper, the instability of grid side converters
of wind turbines defined as loss of synchronism (LOS), where the
wind turbines lose synchronism with the grid fundamental fre-
quency (e.g., 50 Hz) during very deep voltage sags, is explored with
its theory, analyzed and a novel stability solution based on PLL fre-
quency is proposed; and both are verified with power system sim- Fig. 1. ENTSO-E FRT requirement for connections above 110 kV [3].
ulations and by experiments on a grid-connected converter setup.
Index Terms—Converters, current control, power system faults,
power system stability, wind power generation.

I. INTRODUCTION

C OMMON to most of the grid codes, wind power plants


(WPPs) are required to stay connected during short-cir-
cuit grid faults, and also to inject reactive current in order to
support the grid voltage [1]–[3]. In the German VDN grid code
[2], which is a well-established code influencing the following Fig. 2. Generic reactive current requirement and active current during fault.
codes, and recently published code of the ENTSO-E [3], which
is proposed as a common frame for all European countries,
the WPPs are expected to stay connected even when the grid current profile is given as the solid line in Fig. 2, where 1 pu
voltage drops down to zero; as shown by the fault ride-through reactive current is required when the voltage drops below 40%
(FRT) voltage profile of the ENTSO-E in Fig. 1. Additionally, of the rated. In [2] and [3] the FRT voltage profile is defined for
the WPPs are required to inject reactive current during fault in the point of common coupling (PCC) of the WPP; whereas the
proportion to the voltage drop, as a proportional voltage control reactive current requirement is stated to be realized at the wind
scheme, where the gain can be adjustable between 0 and 10, with turbine (WT) level at low-voltage side of the WT transformer;
a deadband applied to the voltage deviation. A generic reactive but also verification at PCC level is encouraged in [2]. Addi-
tionally, the dynamics of step response for the reactive current
is defined in [2] and [3], such that the rise time is allowed to be
Manuscript received May 06, 2013; revised August 05, 2013 and November
10, 2013; accepted December 08, 2013. Date of publication January 09, 2014; specified as small as 10 ms in [3].
date of current version June 16, 2014. This work was supported in part by Vestas In accordance with the grid code requirements and progress
Wind Systems A/S under the Vestas Power Programme. Any opinions, findings,
of available technology, modern WTs such as the target platform
and conclusions or recommendations expressed in this material are those of the
authors and do not necessarily reflect those of Vestas Wind Systems A/S. Paper of this paper, the full-scale converter wind turbine (FSCWT),
no. TPWRS-00561-2013. are designed. The FSCWT has the capability that the active
Ö. Göksu, R. Teodorescu, C. L. Bak, and F. Iov are with the Department
and reactive current injection to the grid are independently con-
of Energy Technology, Aalborg University, Aalborg 9220, Denmark (e-mail:
omg@et.aau.dk; ret@et.aau.dk; clb@et.aau.dk; fi@et.aau.dk). trolled within the maximum current capacity of the wind tur-
P. C. Kjær is with Vestas Wind Systems A/S, Århus 8200, Denmark (e-mail: bine, which can be rated value (1 pu) or slightly higher (e.g.,
pck@vestas.com).
1.2 pu). As a conventional method for the FSCWT; while in-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. jecting reactive current as per grid code requirement, any re-
Digital Object Identifier 10.1109/TPWRS.2013.2295261 maining capacity is utilized for active current injection. Excess

0885-8950 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
1684 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO. 4, JULY 2014

Fig. 3. Aggregated WPP and Thevenin equivalent grid for simulation studies ( MVA).

active power that cannot be injected to the grid during faults is ously omitted instability problem of grid-connected converters,
dissipated on the chopper resistance of the DC link [4]. For in- and also proposing a novel stability solution. Moreover, aware-
stance for a FSCWT with current capacity of 1.1 pu, remaining ness is provided for the practical phenomenon related to the
capacity for active current injection is given by the gray-shaded zero voltage ride-through and reactive current injection require-
area in Fig. 2. Hence, with the conventional method for current ments, which is underestimated in the existing grid codes. In ad-
injection, for very low (close to zero) voltage faults, FSCWT dition to approaching a timely issue related to recent grid codes
would be injecting: and handling a practical problem, this paper also stands as a
• 1 pu reactive current; general reference for current-controlled converters’ active and
• non-specific active current, depending on the capacity and reactive current transfer limits, which is introduced in the third
power generation of the WT, which can be zero as well. section.
Response of WTs during grid faults has been widely studied
both by academia and wind power industry [4]–[13]. Impact of II. IDENTIFIED PROBLEM: LOSS OF SYNCHRONISM (LOS)
wind turbines’ fault response on power system stability is thor- Structure of a generic WPP, which is utilized in this paper,
oughly studied in [5] and [6]. In [7]–[9], methods to improve is shown in Fig. 3. The WPP, which has a rating of 100 MW,
grid support by WPPs are proposed. Regarding the impact of is aggregated as a single WT. The grid synchronization and
faults on WTs; [10] studies the dc link voltage and generator active/reactive current control action are performed at the low
speed oscillations; and [11] and [12] cover advanced methods to voltage side of the WT transformer. The impedance between
improve grid synchronization performance during faults. How- the WT terminal and the PCC, which is composed of the WT
ever, any of the previous studies does not cover the stability transformer, equivalent of the collector grid, and the WPP main
of the grid-side converters in terms of low-frequency dynamic transformer, has a total magnitude of 0.21 pu and X/R of 8. This
behavior of current regulation and grid synchronization under impedance, which plays an important role, is represented as Z
faults, which is the main focus of this paper as reported in the ( pu), whose angle is 83 [tan (X/R)].
following parts. Additionally, even though the grid codes re- The main grid is represented with its Thevenin equivalent with
quire the reactive current injection for voltage dips down to zero an impedance of 0.14 pu and X/R of 10. The machine side of
volts at the PCC bus [2], [3], the previous wind power fault WT is represented as a constant power source since these parts
studies [4]–[13] are missing the analysis for such severe faults have slow dynamics compared to the short duration of the faults
with remaining voltage less than 10% of the rated. [4]. The current control is based on a synchronous frame pro-
This paper is exploring the low-frequency dynamic instability portional-integral (PI) regulator [1], and tuned to reach a band-
of the grid-connected converters of WPPs during current injec- width complying with the stringent 10 ms rise time requirement
tion to severe faults, where the voltage at the PCC drops close to of ENTSO-E grid code. The utilized grid synchronization al-
zero (e.g., 5% of the rated), which has been failed to be covered gorithm, a generic synchronous frame PI based PLL is shown
in the previous wind power fault studies; additionally proposing in Fig. 4 [1]. As well-known, a frequency signal is calculated
a novel stability solution. As will be given in detail in the fol- within the PLL, which is the frequency of the measured phase
lowing parts, when the grid side converters of FSCWTs are in- voltages at the WT terminal and also the generated phase volt-
jecting currents during severe faults in accordance with the grid ages at the converter output. In practice, saturation limits are
codes (1 pu reactive current and a non-specific magnitude of ac- applied to the calculated PLL frequency, (e.g., Hz
tive current), the synchronization with the main grid frequency and Hz), which are set close to the fundamental fre-
(e.g., 50 Hz) can be lost; which can result in tripping of the WPP, quency value and wide enough to allow frequency excursions
causing generation loss and endangering the power system sta- for sufficient angle tracking performance during transients [14].
bility. The identified instability situation, which is occurring as Accordingly, an anti-windup scheme is applied to the integrator
substantial deviation of WT converter’s frequency from grid of the PI regulator within the PLL. In order to observe dynamic
fundamental frequency, is named as loss of synchronism (LOS) changes substantially during LOS events, saturation limits are
in this paper. not applied to the calculated frequency in this section; whereas,
Outcome of this paper helps the WPPs to comply with the the simulation results for the case with the saturation limits are
stringent zero voltage ride-through and reactive current injec- shown in third section.
tion requirements of the grid codes and consequently helping to The WPP and the grid in Fig. 3 are modeled in SimPower-
sustain power system stability with high share of wind power; Systems toolbox of Matlab/Simulink and a severe fault, where
via exploring, identifying and theoretically analyzing a previ- the voltage at the PCC drops to 2% of the rated, is created as a
GÖKSU et al.: INSTABILITY OF WIND TURBINE CONVERTERS DURING CURRENT INJECTION 1685

Fig. 4. Generic PLL structure.

Fig. 6. Case-2: LOS—Frequency Rise. (a) PCC bus phase voltages. (b) WT
active and reactive current reference and measured values. (c)
WT terminal phase voltages. (d) WT phase currents. (e) WT PLL frequency.

TABLE I
SUMMARY OF FAULT SIMULATION RESULTS

Fig. 5. Case-1: LOS—Frequency Fall. (a) PCC bus phase voltages. (b) WT
active and reactive current reference and measured values. (c)
WT terminal phase voltages. (d) WT phase currents. (e) WT PLL frequency.

solid fault at the PCC with fault resistance of 1.5 . The fault
is created at s and cleared after 400 ms. In the simula- very high values, such as 150 Hz, as seen in Fig. 6(e); and sim-
tions, any tripping or protection scheme is not employed for the ilarly the WT voltage and current, as seen in Fig. 6(c) and (d).
WPP. Based on the conventional method given in the introduc- This event is named as LOS—frequency rise.
tion, during very low (close to zero) voltage faults, WT has ref- It is interesting (but verified also with experiments in the fol-
erences as 1 pu reactive current and a non-specific magnitude lowing parts) that even though the frequency at the faulted point
of active current. Results for two severe fault cases are given (PCC) and the main grid are still around 50 Hz during fault [as
below. seen in Figs. 5(a) and 6(a)], the voltage and current generated by
1) Case-1 pu, pu: In case-1, the WT deviate substantially from 50 Hz. The WPP side of the
whose results are given in Fig. 5, the WT is referenced to inject 1 network behaves like out-of-synchronism and “isolated” from
pu pure reactive current during the fault, i.e., zero active current, the main grid side.
as seen in Fig. 5(b) ( pu; It is observed in three more fault cases, which are not shown
pu, ). In this case, the WT frequency, which is the here due to the space limitations, that the LOS do not occur; if
frequency of the voltage at the WT terminals, calculated by the the current injection is kept as zero during the fault, or if the
PLL, drops close to 0 Hz during the fault, as seen in Fig. 5(e). current is injected as having the same angle of the impedance
In other words, frequency of the voltage and current generated Z (between WT and PCC) such that
by the WT drop to 0 Hz as seen in Fig. 5(c) and (d). This event ( pu, ), or if the remaining PCC voltage
is named as LOS—frequency fall. during fault is not close to zero (e.g., 25% of the rated). Sum-
2) Case-2 pu, pu: In case-2, mary of the total five cases are given in Table I. As observed
whose results are given in Fig. 6 below, the WT is referenced to in Figs. 5 and 6, because of the LOS the WT cannot restore to
inject 1 pu reactive current and also 0.65 pu active current, as stable operation even after the fault is cleared.
seen in Fig. 6(b) ( As will be shown in the next section, during LOS the PLL
pu, ). In this case of high active current injection, the angle estimation becomes erroneous which implies incorrect
frequency of the voltage at the WT terminal increases towards active and reactive (vector) current control. Hence in practice,
1686 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO. 4, JULY 2014

Fig. 7. (a) PCC and WT voltage and current phasors. (b) Limit current case. Fig. 8. Out of transfer limit situation for .

LOS creates a high risk of tripping of the WPP, which might be


due to reasons as loss of current control, or frequency protection
settings. It will be shown in the next section that the LOS is ob-
served also when the saturation limits (e.g., Hz and
Hz) are applied to the WT PLL frequency signal.

III. THEORETICAL ANALYSIS OF LOS PROBLEM


It is observed in the previous section that the LOS is occurring
when the remaining voltage at the PCC bus is close to zero and
the WT current characteristics (active and reactive ratio) is not
in accordance with the characteristics of the impedance Z. The
understanding to this situation can be given as follows: During a
severe fault at PCC, WT is referenced to inject active and reac-
tive currents over Z, which is a resistive-inductive (RL) path. If
the reactive and active current references are not having a ratio
close to the X/R ratio of the resistive-inductive path (the angle
of Z), the LOS can occur.
Fig. 9. Active and reactive current transfer limits (pu).
A. Active and Reactive Current Transfer Limits
In classical power system studies the active and reactive
power flow between two buses is obtained as a function of magnitude becomes larger than in Fig. 7(b), the magnitude of
sending and receiving end bus voltage magnitudes and phase the becomes larger as expected. However, with this large
angle between them; from where the well-known power-angle magnitude of and its fixed angle with respect to
equation is derived. However, in case of power electronics , as shown in Fig. 8; the tip of the phasor cannot intersect
based converter applications, basically active and reactive with the circle. This implies that a larger is required,
currents are controlled at the sending end (WT), and the grid which means that there is not any operating point with
voltage magnitude at the receiving end (PCC) is constant. for that angle.
Hence, in order to reach the operating point phasor solution The equation of the current magnitude limit as a function of
of the WT bus and PCC bus voltages with controlled current the and is obtained as in (1) via solving the limit
injection from the WT, an approach similar to the one in [13] case in Fig. 7(b). Similarly solving for the maximum limit of
is utilized, as shown in Fig. 7. The PCC voltage , which the current magnitude for all injection angles, i.e., from 0 to
has constant magnitude and is very low during fault, is shown 360 with active and reactive current combinations, the current
with a circle with radius equal to its magnitude. Since active transfer limits in Fig. 9 is obtained. It should be noted that for
and reactive currents are controlled with reference to , the active and reactive power consumption cases, the WT voltage
voltage is located on the horizontal reference axis, and decreases to zero when the limit is reached:
the controlled current phasor, , with current angle with
respect to , is as shown in Fig. 7(a). For that current phasor,
the voltage phasor on the impedance, , has fixed angle (1)
with respect to as . Then, and phasors
are determined via locating the phasor such that the tip of As seen in Fig. 9, the current transfer limits is a band with
the is on the circle and the end of the is on the the width depending on the PCC voltage and impedance
reference axis, while keeping the angle of fixed at . (Z) magnitudes; and the angle of the band depending on
In Fig. 7(a), such a solution is obtained for a WT current with of the impedance. As explained above, for
angle . In Fig. 7(b), the operating point with the WT current any current outside this limit area, a valid operating point does
with the same angle, , but larger magnitude is obtained. It is not exist. The related limit values for the severe fault case of
important to observe that the current magnitude in Fig. 7(b) is the previous section ( pu and pu)
the limit magnitude for that current injection angle, . If the are imposed to Fig. 9 as values in parentheses. The points
GÖKSU et al.: INSTABILITY OF WIND TURBINE CONVERTERS DURING CURRENT INJECTION 1687

Fig. 11. Quasi-stationary model of the PLL [15].

stability of the PLL requires a negative feedback magnitude


larger than the positive feedback as given in (8) and (9):
Fig. 10. Wind turbine voltage as superposition of two sources [15].

designated as 1 and 2 in Fig. 9 represent the current references (8)


in fault cases 1 and 2 respectively in Figs. 5 and 6, which were (9)
causing LOS.
The constraint for current magnitude providing large-signal
stability can be written as in (10) for equal to :
B. Stability Analysis of PLL During Low Voltage Faults

As observed in previous results, if a current reference out of (10)


the current transfer limits is given, LOS occurs; and during the
LOS event, the PLL fails to track the main grid fundamental The large-signal stability limit in (10) is observed to be the
frequency. In order to analyze dynamics of the PLL, the large- same as the current transfer limits (1), which implies that any
signal stability analysis in [15], which was specifically devel- current reference outside the transfer limits drives the PLL into
oped for weak-grid connection studies, is utilized here for the large-signal instability, as LOS. As also seen in (10), large-
fault study. The analysis is based on the aggregated WPP in signal stability depends on the current injection angle , such
Fig. 3 and the generic PLL structure in Fig. 4. Based on the that injection angle close to the impedance angle re-
separation principle the voltage at the WT terminal can be duces the positive feedback component towards zero,
obtained as superposition of two sources; the grid side (faulted broadening the stability limit. Additionally, the circle around
point) voltage , and the WT’s own current injection; as the origin in Fig. 9 and also (10) show that, when the current
shown in Fig. 10. magnitude is smaller than , stability is provided. In other
The voltage, which is the feedback to the PLL, can be words, if the voltage drop on the impedance Z due to WT’s own
written as composition of two voltages as in (2)–(4): current injection is smaller than the voltage, there is no
risk of LOS. Assuming the WT current injection magnitude as
1 pu, the LOS risk exists for the faults with PCC voltage less
- - (2) than the magnitude of the impedance Z (e.g., 0.2 pu).
- (3) In Fig. 12, simulation results are given for the severe fault
- (4) case-2 (from Section II) with the PLL saturation limits applied
as Hz and Hz. The error component
As well-known and also shown in Fig. 4, the q-axis compo- of the PLL is shown to be non-zero during the fault, which im-
nent of the WT voltage is the error input of the PI compensator plies incorrect angle estimation due to LOS and the WT fre-
within the PLL. The q-axis component can be written in terms quency deviates to 60 Hz limit. In practice, even with the limited
of the q-axis components of the two sources from (3) and (4) PLL frequency, the risk of tripping still exists due to the incor-
above as in (5)–(7) below, where is the phase difference be- rect angle estimation, which results in loss of active and reactive
tween PCC and WT bus voltages: current control, and due to the frequency protection settings.

IV. PROPOSED SOLUTION: PLL FREQUENCY


(5) BASED ACTIVE CURRENT INJECTION
(6) As summary of the previous analysis, three main reasons trig-
(7) gering the LOS are listed as follows:
1) severe fault occurring nearby PCC with remaining voltage
The quasi-stationary model of the PLL based on (5)–(7) is given close to zero (e.g., less than 20% of the rated);
in Fig. 11. 2) grid codes’ reactive current injection requirement during
As seen in Fig. 11, the feedback sourcing from the PCC faults, including zero voltage faults;
voltage in (5) provides the necessary negative feedback 3) active and reactive current (vector) control with references
for the PLL to track the grid phase angle, . However, the generated by the conventional method, without consid-
feedback sourcing from the WT’s own current injection ering the impedance angle, i.e., the current transfer limits.
in (6) behaves as a positive feedback, which can be considered In [16]–[19], focusing on weak-grid connection of WTs, in-
as a disturbance to the stability of the PLL. The large-signal stability situations similar to LOS are proposed to be solved by
1688 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO. 4, JULY 2014

Fig. 13. Proposed PLL frequency based active current injection algorithm.

Fig. 12. Case-2’: LOS—Frequency Rise with PLL Saturation. (a) PCC bus Fig. 14. Current profile with proposed PLL frequency based method.
phase voltages. (b) WT active and reactive current reference and mea-
sured values. (c) WT terminal phase-a voltage and current. (d) WT ter-
minal d and q normalized voltages in PLL. (e) WT PLL frequency.
which can be used as the rated (e.g., 50 Hz) or prefault fre-
quency. In practice, a deadband (e.g., mHz) can be applied
fast detection of the instability and immediate cease or decrease to the frequency error, to guarantee that the controller does not
of the power or current injection. Such a solution with reduced act for small frequency deviations. In the algorithm, in Fig. 13,
or zero current injection during faults can help to avoid LOS; the resultant current magnitude is calculated and the references
however, do not comply with the grid codes. The solution pro- are scaled down if the resultant magnitude exceeds the capacity
posed in [13], which is the only existing study covering the LOS of the WT.
during faults, is to decrease the active current injection in accor- The resultant active and reactive current profile with the PLL
dance with the voltage drop. Such a solution can help for cases frequency based active current injection is shown in Fig. 14. As
with high active current reference (e.g., case-2 above); however seen in the figure, the active current is adjusted to be within a
can fail when pure reactive current is referenced (e.g., case-1 band with the decreasing voltage, which in turn keeps the cur-
above). Another straightforward way to avoid LOS is to inject rent references inside the current transfer limit band of Fig. 9. In
active and reactive currents in accordance with the angle of the Fig. 15, simulation result of the PLL frequency based method
impedance, as equal to R/X. In [6]–[9], current is shown for the severe fault case-1 (Fig. 5) from Section II. As
injection based on X/R is proposed with the aim of improving seen in Fig. 14(a), during the fault active current reference is
the grid support by WPPs without aiming to avoid LOS. Never- generated by the PLL frequency based algorithm and the fre-
theless, injecting in accordance with the X/R of the impedance quency is kept stable around 50 Hz without LOS. It should be
can help to avoid LOS. However, the need to obtain or estimate noted in Fig. 15 that; with additional active current injection,
the precise X/R value brings practical difficulties. the total current increases over 1 pu. In case the capacity of the
In this paper a closed loop control method based on PLL fre- WT is not larger than 1 pu, then the reactive current magnitude
quency is proposed as solution to avoid LOS, while complying needs to be scaled down to create capacity for the necessary ac-
with the grid codes’ reactive current injection during very low tive current.
voltage grid faults. The PLL frequency based method utilizes
the PLL frequency signal as a feedback to detect any LOS and
V. EXPERIMENTAL VERIFICATION OF LOS PROBLEM
regulates the active current reference accordingly to avoid LOS,
AND PLL FREQUENCY BASED SOLUTION
as shown in Fig. 13. The reactive current reference is set pri-
marily as required by the grid codes [2], [3]. The active current In this section, a grid-connected converter, which is repre-
reference is generated by the conventional algo- senting an aggregated WPP and injecting active and reactive
rithm; and the frequency regulator acts in parallel to regulate it currents during a low voltage fault, is experimentally inves-
such that the resultant current reference is kept within the cur- tigated. The small-scale (2 kW) dSpace controlled three-level
rent transfer limits avoiding LOS. The frequency compensator converter and the impedance, which is inserted to emulate the
is designed as a PI compensator. The frequency feedback, impedance between the WT and PCC, are shown in Fig. 16. The
calculated by the PLL in Fig. 4, is compared with a reference impedance has magnitude of 0.04 pu (
GÖKSU et al.: INSTABILITY OF WIND TURBINE CONVERTERS DURING CURRENT INJECTION 1689

Fig. 15. Simulation results with PLL frequency based method. (a) WT active
and reactive current reference and measured values. (b) WT Fig. 18. Experimental results with PLL frequency based algorithm. (a) WT
terminal phase-a voltage and current. (c) WT PLL frequency. active and reactive current reference and measured values.
(b) WT terminal phase-a voltage and current. (c) WT PLL frequency.

As seen in Fig. 18(a), the active current is generated as 0.5 pu by


the PLL frequency based algorithm, as required by the X/R ratio
of 2 and 1 pu reactive current. In Fig. 18(c) the WT frequency
is observed to be kept stable at 50 Hz.
As given in the theoretical analysis and also observed in the
Fig. 16. Experimental small-scale grid-connected setup.
results, certain amount of active current is required to accom-
pany 1 pu reactive current injection to severe faults. Hence, in
case the available active power generation level of the WT (or
WPP) is not enough due to low wind conditions, then the re-
quired reactive current might not be injected.

VI. FURTHER CONSIDERATIONS

The rate of deviation of frequency during LOS depends on


factors such as the PLL and current controller gains, and the
fault level. For instance, for the severe fault case-1 (Fig. 5) from
Section II, the frequency deviates down to 0 Hz within the fault
duration of 400 ms, which is intentionally kept long in order to
observe a substantial deviation. In practice, with a smaller fault
clearing time (e.g., 100 ms), the frequency proportionally devi-
ates less. However, successful restoration of the WT to normal
Fig. 17. Experimental results with conventional algorithm. (a) WT active and
operation after the LOS depends on many factors such as trip-
reactive current reference and measured values. (b) WT ter- ping mechanism and protection settings of the WT and WPP,
minal phase-a voltage and current. (c) WT PLL frequency. fault level, operating point and grid characteristics, which can
be considered as a separate study.
It is shown that a current reference out of transfer limits
pu) with a low X/R ratio of 2. The fault is created at the PCC causes large-signal instability for the WT. However, a current
point as a zero voltage dip by using the autotransformer. reference inside the current transfer limits band but close
First, the problematic case-1 (Fig. 5) from Section II with to the limits can also cause small-signal instability problem
pure reactive current injection is performed to observe LOS ex- depending on the controller gains, fault level and grid charac-
perimentally. As seen in Fig. 17, if pure reactive current refer- teristics, which is not covered in this study. For instance in [20],
ence is generated during the severe fault, then the WT frequency a small-signal instability situation of a weak-grid connected
and also the frequency of the generated voltage and current fall converter is proposed to be solved by reducing the PLL gains,
towards 0 Hz. In the experiments, the PCC voltage is not re- compromising the dynamic transient performance.
stored back to rated, since there is the risk of damage after losing The LOS has not been observed for asymmetrical faults since
current control capability because of the LOS. the positive sequence voltage drop is not severe during these
In Fig. 18, the results with the implementation of the PLL faults. However, it is worth analyzing low-frequency dynamic
frequency based active current injection algorithm are shown. stability of WTs under unbalanced grid conditions.
1690 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO. 4, JULY 2014

VII. CONCLUSION [9] F. Sulla, “Fault behavior of wind turbines,” Ph.D. dissertation, Lund
Univ., Lund, Sweden, 2012.
[10] C. Jauch, “Transient and dynamic control of a variable speed wind tur-
In this paper, low-frequency dynamic stability of WTs’ grid bine with synchronous generator,” Wind Energy, no. 10, pp. 247–269,
side converters during current injection to very low voltage grid 2007.
[11] A. Mullane, G. Lightbody, and R. Yacamini, “Wind-turbine fault ride-
faults is investigated. It is shown that when 1 pu reactive current, through enhancement,” IEEE Trans. Power Syst., vol. 20, no. 4, pp.
which is required by the grid codes, is injected together with 1929–1937, Nov. 2005.
non-specific amount of active current during very low voltage [12] P. Rodriguez, A. Luna, I. Candela, R. Mujal, R. Teodorescu, and F.
Blaabjerg, “Multiresonant frequency-locked loop for grid synchroniza-
(e.g., less than 10% of the rated) faults, WTs can lose their syn- tion of power converters under distorted grid conditions,” IEEE Trans.
chronism with the grid fundamental frequency (e.g., 50 Hz). Ind. Electron., vol. 58, pp. 127–138, 2011.
This instability situation, which has been omitted in the previous [13] I. Erlich, F. Shewarega, S. Engelhardt, J. Kretschmann, J. Fortmann,
and F. Koch, “Effect of wind turbine output current during faults on
wind power studies and grid code revisions, is demonstrated by grid voltage and the transient stability of wind parks,” in Proc. 2009
both simulations and experiments, and theoretically analyzed; IEEE Power and Energy Society General Meeting, pp. 1–8.
and named as LOS. It is shown that the WTs experience LOS [14] A. Yazdani and R. Iravani, Voltage-Sourced Converters in Power Sys-
tems. Piscataway, NJ, USA: IEEE Press/Wiley, 2010.
during severe faults, where the grid voltage at the PCC of the [15] D. Dong, J. Li, D. Boroyevich, P. Mattavelli, I. Cvetkovic, and Y. Xue,
WPP is dropping close to zero, and if the ratio of the reac- “Frequency behavior and its stability of grid-interface converter in dis-
tive and active current references is not close to the X/R ratio tributed generation systems,” in Proc. 2012 IEEE Applied Power Elec-
tronics Conf. Expo., pp. 1887–1893.
of the impedance between the WT and the faulted point (e.g., [16] S. Engelhardt and A. Geniusz, “Method for Operating a Wind Turbine,”
PCC). The related active and reactive current transfer limits, U.S. patent 2011/0006528 A1, Jan. 13, 2011.
which constitute the currents that can be injected without LOS, [17] E. V. Larsen, A. M. Klodowski, and S. A. Barker, “Method and Sys-
tems for Operating a Wind Turbine,” U.S. patent 8,046,109 B2, Oct.
are derived for the first time in this paper. The analysis of the 25, 2011.
LOS problem and the current transfer limits also stand as a gen- [18] V. Diedrichs, A. Beekmann, K. Busker, S. Nikolai, and S. Adloff,
eral reference for stability and control of grid-connected cur- “Control of wind power plants utilizing voltage source converter in
high impedance grids,” in Proc. 2012 IEEE Power and Energy Society
rent-controlled converter applications, especially for weak-grid General Meeting, pp. 1–9.
connected wind turbine or HVDC converters. [19] W. Kuhn, “Method and Apparatus for Automatic Network Stabiliza-
A novel stability method, PLL frequency based active cur- tion in Electric Power Supply Systems Using at Least one Converter,”
W.O. patent 2012/119136 A1, Oct. 21, 2010.
rent injection algorithm, is proposed and shown to solve the [20] J. Zhou and A. M. Gole, “VSC transmission limitations imposed by
LOS problem via injecting necessary amount of active current AC system strength and AC impedance characteristics,” in Proc. 2012
based on the PLL frequency feedback; and verified by simula- Int. Conf. AC and DC Power Transmission, pp. 1–6.
tions and also experiments on a small-scale grid-connected con-
verter setup.
The LOS problem introduced in this paper, and the derived
active and reactive current transfer limits provide insight for
grid connection of the current-controlled converters and also
for future revisions of the grid codes, in order to provide stable Ömer Göksu (S’07) was born in Izmir, Turkey,
in 1982. He received the B.Sc. and M.Sc. degrees
power system operation with high share of wind power. in electrical and electronics engineering from the
Middle East Technical University (METU), Ankara,
Turkey, in 2004 and 2008, respectively, and the Ph.D.
degree from the Department of Energy Technology,
Aalborg University, Denmark, in 2012.
REFERENCES He was employed as a systems engineer in Aselsan
Inc. from 2004 to 2009 during his M.Sc. and as a re-
[1] R. Teodorescu, M. Liserre, and P. Rodriguez, Grid Converters for searcher from 2009 to 2012 during his Ph.D. under
Photovoltaic and Wind Power Systems. Piscataway, NJ, USA: IEEE the Vestas Power Program. His research interest in-
Press/Wiley, 2011. cludes grid connection of wind power, wind turbine control, power electronics,
[2] VDN-e.v. beim VDEW: Transmission Code 2007. Networks and integration of power electronics to power systems, and electrical motor drives.
System Rules of the German Transmission System Operators, Aug.
2007.
[3] European Network for Transmission System Operators for Electricity,
“ENTSO-E network code for requirements for grid connection appli- Remus Teodorescu (S’94–A’97–M’99–SM’02–
cable to all generators,” Jun. 2012. F’12) received the Dipl.Ing. degree in electrical engi-
[4] J. F. Conroy and R. Watson, “Low-voltage ride-through of a full con- neering from Polytechnical University of Bucharest,
verter wind turbine with permanent magnet generator,” IET Renew. Romania, in 1989, and the Ph.D. degree in power
Power Gen., vol. 1, no. 3, pp. 182–189, Sep. 2007. electronics from University of Galati, Romania, in
[5] N. R. Ullah, T. Thiringer, and D. Karlsson, “Voltage and transient sta- 1994.
bility support by wind farms complying with the E.ON Netz grid code,” In 1998, he joined Aalborg University, Den-
IEEE Trans. Power Syst., vol. 22, no. 4, pp. 1647–1656, Nov. 2007. mark, Department of Energy Technology, power
[6] N. R. Ullah and T. Thiringer, “Variable speed wind turbines for power electronics section where he currently works as a
system stability enhancement,” IEEE Trans. Energy Convers., vol. 22, full professor. Since 2013, he has been a visiting
no. 1, pp. 52–60, Mar. 2007. professor at Chalmers University. He has coauthored
[7] M. Kayikci and J. V. Milanovic, “Reactive power control strategies for the book Grid Converters for Photovoltaic and Wind Power Systems (New
DFIG-based plants,” IEEE Trans. Energy Convers., vol. 22, no. 2, pp. York, NY, USA: Wiley, 2011) and over 200 IEEE journals and conference
389–396, Jun. 2007. papers. His areas of interests include: design and control of grid-connected
[8] J. M. Garcia, P. C. Kjaer, P. Rodriguez, and R. Teodorescu, “Active converters for photovoltaic and wind power systems, HVDC/FACTS based on
current control in wind power plants during grid faults,” Wind Energy, MMC, SiC-based converters, storage systems for utility based on Li-Ion battery
vol. 13, no. 8, 2010. technology. He was the coordinator of the Vestas Power Program 2008–2013.
GÖKSU et al.: INSTABILITY OF WIND TURBINE CONVERTERS DURING CURRENT INJECTION 1691

Claus Leth Bak (M’94–SM’08) was born in Århus, and wind power systems. From 2010 to 2012, he held a position as Power
Denmark, on April 13, 1965. He received the B.Sc. System Research Specialist in Vestas Wind Systems working with new ancil-
degree with honors in electrical power engineering lary services for augmented wind power plants. Since 2013, he has been with
in 1992 and the M.Sc. degree in electrical power the Institute of Energy Technology focusing on research within smart grids. His
engineering at the Department of Energy Technology research covers control and application of electrical machines and power elec-
(ET) at Aalborg University (AAU), Denmark, in tronic converters for grid integration of renewable energy sources and, operation
1994. and control of dispersed generation in modern power systems. He is author or
After his studies, he worked as a professional en- co-author of more than 100 journal/conference papers in his research areas.
gineer with Electric Power Transmission and Substa-
tions with specializations within the area of power
system protection at the NV Net Transmission Com-
pany. In 1999 he was employed as an Assistant Professor at ET-AAU, where he Philip Carne Kjaer (M’93–SM’11) received the
holds a Professor position today. His main research areas include corona phe- M.Sc. degree in electrical engineering from Aalborg
nomena on overhead lines, power system modeling and transient simulations, University, Aalborg, Denmark, in 1993, and the
underground cable transmission, power system protection and HVDC-VSC off- Ph.D. degree from the University of Glasgow,
shore transmission networks. He is the author/coauthor of approximately 100 Glasgow, U.K., in 1997.
publications. From 1993 to 1998, he was a Research Assistant at
Prof. Bak is a member of Cigré C4.502, Cigré SC C4, and Danish Cigré Na- the University of Glasgow, working with advanced
tional Committee. control of switched reluctance machines and drives.
From 1998 to 2003, he was with ABB Corporate
Research, Vasteras, Sweden, where, as a Develop-
ment Engineer, he worked on servo-motor-based
Florin Iov (S’98–M’04–SM’06) received the Dipl. high-voltage circuit breaker drives, factory testing of synchronous machines,
Eng. degree in electrical engineering from the Uni- power converters for HVDC power transmission, and multi-megawatt vari-
versity of Romania in 1993 and the Ph.D. degree from able-speed drives. Between 2000 and 2003, he also functioned as Department
Galati University, Romania, in 2003, with a special Manager. In October 2003, he joined Vestas Wind Systems, Arhus, Denmark,
focus in the modeling, simulation and control of large where he currently holds the position as Chief Specialist for power plants. His
wind turbines. research covers control and application of power electronic converters.
He was a staff member at Galati University, Ro- Dr. Kjaer is a Chartered Engineer in the U.K., a Member of the Institution of
mania, from 1993 to 2001. He was with the Insti- Electrical Engineers, U.K., member of the Danish national committee of Cigré
tute of Energy Technology, Aalborg University, Den- and of Cigré study committee B4, and the recipient of the 2004 Richard M. Bass
mark, between 2001 and 2009 where he was involved Outstanding Young Power Electronics Engineer Award.
mainly in research projects regarding wind turbines

You might also like