You are on page 1of 207

MARIANO MARCOS STATE UNIVERSITY

COLLEGE OF ENGINEERING
DEPARTMENT OF ELECTRICAL ENGINEERING
City of Batac, 2906, Ilocos Norte

Distribution System and Substation Design


(EE 146)

In Partial Fulfillment of the Requirements for the Degree Bachelor of Science in


Electrical Engineering

RANWEL JADE T.
GAOGAO
BSEE IV-D

ENGR. LEMUEL CRIS M. JAMUYOT, PEE


INSTRUCTOR

JUNE 2023
LETTER OF TRANSMITTAL

ENGR. LEMUEL CRIS M. JAMUYOT


Mariano Marcos State University
College of Engineering
Department of Electrical Engineering
City of Batac, Ilocos Norte

Sir,

In compliance with the requirements leading to the Degree of Bachelor of Science

in Electrical Engineering, the undersigned hereby takes the pleasure in conveying this

Distribution System and Substation Design manuscript.

Hence, I have the privileged to present this design.

Respectfully Yours,

RANWEL JADE T. GAOGAO


BS in Electrical Engineering
APPROVAL SHEET

In partial fulfilment of the requirements in EE 146 “Distribution System and

Substation Design” prepared and submitted by RANWEL JADE T. GAOGAO

is hereby recommending your approvals.

ENGR. LEMUEL CRIS M. JAMUYOT

Instructor

Accepted in partial fulfilment of the requirements in electrical engineering


course.

ENGR. LEMUEL CRIS M. JAMUYOT


Instructor
ACKNOWLEDGEMENT

First, to our ALMIGHTY GOD, who has gifted him with knowledge, wisdom,
and the ability to make all things possible. He is the source of my power, strength, and
blessings. I owe You, my GOD, this work.

To ENGR. LEMUEL CRIS M. JAMUYOT for his everlasting support and


expertise that he shared with me. All of those lessons and insights will live on in my
mind and heart.

To my parents, who gave me life and the opportunity to live in this world full of ups
and downs. For their unending financial assistance. They were always present when I
needed their advice and encouragement to continue on my path, to finish what I had
begun. Because this is the only thing they can give me that no one can steal. I consider
myself extremely fortunate and grateful to have parents like them. Give me time, and I
will replace all of your efforts, and you will feel the love of your Future Engineer child.

To my friends, for sharing everything they have, no matter how much or how little.
For sharing every good and bad moment in their lives. For their financial assistance
whenever I require it. For sharing their knowledge in order to fulfill this and other
requirements. Those long journeys on rough routes will always be remembered and
treasured in my heart. I owe so much to you GUYS!
TABLE OF CONTENTS

i. Cover Page i
ii. Letter of Transmittal ii
iii. Approval Sheet iii
iv. Acknowledgement iv
v. Table of Contents v
Chapter 1 INTRODUCTION
1.1 Distribution and Substation Design 1
2.1 Project Objective 2
3.1 Project Location 2
Chapter 2 LOAD CLASIFICATION

2.1 Load Discussion 3


2.2 Load Graphs 4
2.3 Load Schedule 18
Chapter 3 CIRCUIT LAYOUT 78
Chapter 4 DIVERSIFIED DEMAND CURVE AND SIZING OF TRANSFORMERS 99
(CALCULATION OF PERMISSIBLE OVERLOAD)
Chapter 5 VOLTAGE DROP CALCULATION 141
Chapter 5.1 LOAD BALANCING, COMPUTATION OF PERCENT UNBALANCED.
CONCLUSION AND RECOMMENDATION
APPENDICES
A. SINGLE LINE DIAGRAM
B. PROJECT LAYOUT
C. BILL OF MATERIALS
D. REFERENCES
LOAD CLASSIFICATION
LOAD CLASSIFICATION

Discussion of Loads

In this design, it consists of 8 types of residential buildings, 27 different

commercial buildings and 2 different industrial buildings. All residential buildings are

in single-phase typed buildings. The main breakers of residential buildings were

ranged from 60 AT to 225 AT.

Some common loads were the Lighting Outlets (LO’s) and Convenience Outlets

(CO’s) and for the Special Purpose Outlets (SPO’s) for 1-HP and 2-HP of Air

Conditioning Units (ACUs) and water pumps.

In commercial buildings, some of them are in single-phase typed buildings,

on the other hand has three-phase typed buildings like the school and hospital. Some

loads of single-phase commercial buildings had commonly related to the loads of

residential buildings. For the three-phase buildings, it contains the SPO and most

importantly usable circuits depend on what type of building it is.

For industrial buildings, the loads were mostly in three-phase typed machines

and equipment for manufacturing, producing goods, etc.

Other loads of each buildings will be shown at the “Schedule of Loads”.


DEMAND LOAD CURVES
Residential 1

6000

5000

4000

3000

2000

1000

0
1 4 7 10 13 16 19 22 25 28 31 34 37 40 43 46 49 52 55 58 61 64 67 70 73 76 79 82 85 88 91 94
VA Time

Residential 2

6000

5000

4000

3000

2000

1000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

Residential 3
7000

6000

5000

4000

3000

2000

1000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time
Residential 1

6000

5000

4000

3000

2000

1000

0
1 4 7 10 13 16 19 22 25 28 31 34 37 40 43 46 49 52 55 58 61 64 67 70 73 76 79 82 85 88 91 94
VA Time

Residential 2

6000

5000

4000

3000

2000

1000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

Residential 3
7000

6000

5000

4000

3000

2000

1000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time
Residential 4

7000

6000

5000

4000

3000

2000

1000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

Residential 5
8000
7000
6000
5000
4000
3000
2000
1000
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

Residential 6
8000

7000

6000

5000

4000

3000

2000

1000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time
Residential 6
10000
9000
8000
7000
6000
5000
4000
3000
2000
1000
0
1 4 7 10 13 16 19 22 25 28 31 34 37 40 43 46 49 52 55 58 61 64 67 70 73 76 79 82 85 88 91 94

VA Time

Residential 6
16000

14000

12000

10000

8000

6000

4000

2000

0
1 4 7 10 13 16 19 22 25 28 31 34 37 40 43 46 49 52 55 58 61 64 67 70 73 76 79 82 85 88 91 94

VA Time

Elementary
16000
14000
12000
10000
8000
6000
4000
2000
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time
Secondary
25000

20000

15000

10000

5000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

MUNICIPAL HALL
100000
90000
80000
70000
60000
50000
40000
30000
20000
10000
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

Market
12000

10000

8000

6000

4000

2000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time
GROCERY STORE
10000
9000
8000
7000
6000
5000
4000
3000
2000
1000
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

Water Station
18000
16000
14000
12000
10000
8000
6000
4000
2000
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

Restaurant

25000

20000

15000

10000

5000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time
Gas Station
20000
18000
16000
14000
12000
10000
8000
6000
4000
2000
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

Church
12000

10000

8000

6000

4000

2000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

Coffee Shop
20000
18000
16000
14000
12000
10000
8000
6000
4000
2000
0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time
POLICE STATION
12000

10000

8000

6000

4000

2000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

LAUNDRY STATION
7000

6000

5000

4000

3000

2000

1000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

BASKETBALL COURT
3500

3000

2500

2000

1500

1000

500

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95
VA Time
Fire Station
16000

14000

12000

10000

8000

6000

4000

2000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

Gas Station
14000

12000

10000

8000

6000

4000

2000

0
1 4 7 10 13 16 19 22 25 28 31 34 37 40 43 46 49 52 55 58 61 64 67 70 73 76 79 82 85 88 91 94

VA Time
INDUSTRIAL 1

300000

250000

200000

150000

100000

50000

0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95

VA Time

INDUSTRIAL 2
350000

300000

250000

200000

150000

100000

50000

0
1 4 7 10 13 16 19 22 25 28 31 34 37 40 43 46 49 52 55 58 61 64 67 70 73 76 79 82 85 88 91 94

VA Time
SHCEDULE OF LOADS
SCHEDULE OF LOADS (R1)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 CONVENIENT OUTLET LOAD 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 REFRIGERATOR 1 60 230 0.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 ELECTRIC RANGE 1 3200 230 13.91 30 125 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
5 LAUNDRY OUTLET 1 1500 230 6.52 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 1 HP WATER PUMP 1 1840 230 8.00 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 SPARE 1 1500 230 6.52 20 100 2 10
8 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 10 7 6 11860.00 51.57


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-14mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
32mmØ PVC PIPE
ICB = 54.85
USE: 60 AT/100AF, 2P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS (R2)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 CONVENIENT OUTLET LOAD 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 REFRIGERATOR 1 60 230 0.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 RICE COOKER 1 500 230 2.17 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 LAUNDRY OUTLET 1 1500 230 6.52 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 ELECTRIC RANGE 1 3200 230 13.91 30 125 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 SMALL APPLIANCES 1 1500 230 6.52 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 1 HP WATER PUMP 1` 1840 230 8.00 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 SPARE 1 1500 230 6.52 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 11 7 7 13960.00 60.70


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: 2-22mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
40mmØ PVC PIPE
ICB = 62.16
USE: 80 AT/100AF, 2P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS (R3)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 CONVENIENT OUTLET LOAD 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 REFRIGERATOR 1 80 230 0.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 RICE COOKER 1 500 230 2.17 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 LAUNDRY OUTLET 1 1500 230 6.52 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 ELECTRIC RANGE 1 3200 230 13.91 30 125 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 WATER HEATER 1 1125 230 4.89 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 SMALL APPLIANCES 1 1500 230 6.52 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 1 HP ACU 1 1840 230 8.00 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 SPARE 1 1500 230 6.52 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
12 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 12 9 10 18325.00 79.67


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
50mmØ PVC PIPE
ICB = 84.14
USE: 100 AT/100AF, 2P, MCCB Bolt-On Type, 10X kAIC
SCHEDULE OF LOADS (R4)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 8 800 230 3.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 6 600 230 2.61 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 CONVENIENT OUTLET LOAD 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 RICE COOKER 1 700 230 3.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 REFRIGERATOR 1 80 230 0.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 LAUNDRY OUTLET 1 1500 230 6.52 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 ELECTRIC RANGE 1 3200 230 13.91 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
8 WATER HEATER 1 1125 230 4.89 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 WATER HEATER 1 1125 230 4.89 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 SMALL APPLIANCES 1 1500 230 6.52 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 WALL MOUNTED OVEN 1 3200 230 13.91 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 1 HP ACU 1 1840 230 8.00 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
13 1 HP ACU 1 1840 230 8.00 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
15 SPARE 1 1500 230 6.52 20 100 2 10
16 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 14 9 13 24890.00 108.22


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-38mm² + 1-14mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
63mmØ PVC PIPE
ICB = 106.97
USE: 125 AT/225AF, 2P, MCCB Bolt-On Type, 18X kAIC
SCHEDULE OF LOADS (R2)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1?, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
2 CONVENIENT OUTLET LOAD 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm ? PVC
3 REFRIGERATOR 1 60 230 0.26 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm ? PVC
4 RICE COOKER 1 500 230 2.17 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm ? PVC
5 LAUNDRY OUTLET 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm ? PVC
6 ELECTRIC RANGE 1 3200 230 13.91 40 125 2 10 2-8.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm ? PVC
7 SMALL APPLIANCES 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm ? PVC
8 1 HP WATER PUMP 1` 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm ? PVC
9 SPARE 1 1500 230 6.52 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm ? PVC
10 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 11 7 7 13960.00 60.70


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: 2-22mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
40mmØ PVC PIPE
ICB = 62.16
USE: 80 AT/100AF, 2P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS (R3)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 CONVENIENT OUTLET LOAD 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
3 REFRIGERATOR 1 80 230 0.35 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
4 RICE COOKER 1 500 230 2.17 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
5 LAUNDRY OUTLET 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
6 ELECTRIC RANGE 1 3200 230 13.91 40 125 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
7 WATER HEATER 1 1125 230 4.89 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
8 SMALL APPLIANCES 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
9 1 HP ACU 1 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
10 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
11 SPARE 1 1500 230 6.52 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
12 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 12 9 10 18325.00 79.67


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
50mmØ PVC PIPE
ICB = 84.14
USE: 100 AT/100AF, 2P, MCCB Bolt-On Type, 10X kAIC
SCHEDULE OF LOADS (R4)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 8 800 230 3.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 6 600 230 2.61 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 CONVENIENT OUTLET LOAD 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 RICE COOKER 1 700 230 3.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 REFRIGERATOR 1 80 230 0.35 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
6 LAUNDRY OUTLET 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 ELECTRIC RANGE 1 3200 230 13.91 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
8 WATER HEATER 1 1125 230 4.89 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 WATER HEATER 1 1125 230 4.89 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 SMALL APPLIANCES 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 WALL MOUNTED OVEN 1 3200 230 13.91 40 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
12 1 HP ACU 1 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 1 HP ACU 1 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 SPARE 1 1500 230 6.52 20 100 2 10
16 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 14 9 13 24890.00 108.22


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-38mm² + 1-14mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
63mmØ PVC PIPE
ICB = 106.97
USE: 125 AT/225AF, 2P, MCCB Bolt-On Type, 18X kAIC
SCHEDULE OF LOADS (R5)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 9 900 230 3.91 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 9 900 230 3.91 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 CONVENIENT OUTLET LOAD 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 RICE COOKER 1 700 230 3.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 REFRIGERATOR 1 80 230 0.35 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
6 LAUNDRY OUTLET 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 ELECTRIC RANGE 1 4500 230 19.57 40 125 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
8 WATER HEATER 1 1125 230 4.89 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 WATER HEATER 1 1125 230 4.89 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 SMALL APPLIANCES 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 WALL MOUNTED OVEN 1 3200 230 13.91 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 25mm Φ PVC
12 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 1 HP WATER PUMP 1 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 SPARE 1 1500 230 6.52 20 100 2 10
18 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 18 9 15 33030.00 143.61


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-50mm² + 1-14mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
63mmØ IMC/RSC PIPE
ICB = 135.29
USE: 150 AT/255AF, 2P, MCCB Bolt-On Type, 18X kAIC
SCHEDULE OF LOADS (R6)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 8 800 230 3.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 CONVENIENT OUTLET LOAD 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVENIENT OUTLET LOAD 5 900 230 3.91 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 REFRIGERATOR 1 60 230 0.26 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
6 LAUNDRY OUTLET 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 CLOTHES DRYER 1 3200 230 13.91 40 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
8 ELECTRIC RANGE 1 4500 230 19.57 40 100 2 10 2-8.0mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
9 WATER HEATER 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
10 WATER HEATER 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
11 SMALL APPLIANCES 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
12 WALL MOUNTED OVEN 1 3200 230 13.91 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
13 1 HP WATER PUMP 1 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 2 HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
18 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
19 SPARE 1 1500 230 6.52 20 100 2 10
20 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 18 11 16 39380.00 171.22


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-80mm² + 1-14mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
75mmØ IMC/RSC PIPE
ICB = 157.37
USE: 175 AT/225AF, 2P, MCCB Bolt-On Type, 18X kAIC
SCHEDULE OF LOADS (R7)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVENIENT OUTLET LOAD 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVENIENT OUTLET LOAD 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVENIENT OUTLET LOAD 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 REFRIGERATOR 2 120 230 0.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
8 LAUNDRY OUTLET 2 3000 230 13.04 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
9 CLOTHES DRYER 1 3200 230 13.91 40 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
10 ELECTRIC RANGE 1 4500 230 19.57 40 100 2 10 2-8.0mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
11 WATER HEATER 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
12 WATER HEATER 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
13 SMALL APPLIANCES 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
14 WALL MOUNTED OVEN 1 3200 230 13.91 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
15 1 HP WATER PUMP 1 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20mm Φ PVC
16 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20mm Φ PVC
17 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20mm Φ PVC
18 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20mm Φ PVC
19 2 HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20mm Φ PVC
20 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20mm Φ PVC
21 SPARE 1 1500 230 6.52 20 100 2 10
22 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 36 30 18 46160.00 200.70


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-80mm² + 1-14mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
75mmØ IMC/RSC PIPE
ICB = 180.96
USE: 200 AT/225AF, 2P, MCCB Bolt-On Type, 18X kAIC
SCHEDULE OF LOADS (R8)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVENIENT OUTLET LOAD 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVENIENT OUTLET LOAD 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVENIENT OUTLET LOAD 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 REFRIGERATOR 2 120 230 0.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
8 LAUNDRY OUTLET 2 3000 230 13.04 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
9 CLOTHES DRYER 2 6400 230 27.83 40 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
10 ELECTRIC RANGE 1 4500 230 19.57 40 100 2 10 2-8.0mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
11 WATER HEATER 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 WATER HEATER 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 SMALL APPLIANCES 1 3000 230 13.04 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 25mm Φ PVC
14 WALL MOUNTED OVEN 1 3200 230 13.91 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25mm Φ PVC
15 1 HP WATER PUMP 1 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
18 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
19 2 HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
20 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
21 SPARE 1 3000 230 13.04 20 100 2 10
22 SPARE 1 3000 230 13.04 20 100 2 10

TOTAL 36 30 19 53860.00 234.17


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-100mm² + 1-22mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
75mmØ IMC/RSC PIPE
ICB = 207.74
USE: 225 AT/225AF, 2P, MCCB Bolt-On Type, 18X kAIC
SCHEDULE OF LOADS ( ELEMENTARY SCHOOL) C1
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVENIENT OUTLET LOAD 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVENIENT OUTLET LOAD 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 CONVENIENT OUTLET LOAD 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 CONVENIENT OUTLET LOAD 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 REFRIGERATOR 1 60 230 0.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 REFRIGERATOR 1 80 230 0.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 1 HP WATER PUMP 1 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 1HP ACU 1 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 1HP ACU 1 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 2 HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 1.5HP ACU 1 2300 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 SPARE 1 1500 230 6.52 20 100 2 10
18 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 44 33 10 26820.00 116.61


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-38mm² + 1-14mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
63mmØ PVC PIPE
ICB = 113.69
USE: 125 AT/225AF, 2P, MCCB Bolt-On Type, 18X Kaic
SCHEDULE OF LOADS(HS)PB1 (C2)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
12 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
13 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
18 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
19 SPARE 1 1500 230 20 100 2 10
20 SPARE 1 1500 230 6.52 6.52 20 100 2 10

TOTAL 78 56 7 34425.00 47.17 54.43 48.08 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
50mmØ PVC PIPE
ICB = 86.42
USE: 100 AT/100AF, 2P, MCCB Bolt-On Type, 10X Kaic
SCHEDULE OF LOADS(HS)PB2
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC

1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 9 900 230 3.91 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 LIGHTING LOAD 6 600 230 2.61 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 CONVINIENCE OUTLET 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 CONVINIENCE OUTLET 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
12 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
13 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 SPARE 1 1500 230 6.52 20 100 2 10
18 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 60 50 6 28836.00 45.12 40.21 40.04 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: 2-22mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
40mmØ PVC PIPE
ICB = 72.39
USE: 80 AT/100AF, 2P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS(HS)MDP
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 PB1 60 60 9 34425.00 230 47.17 54.43 48.08 100 100 2 10 2-30 mm² THHN + 1-8.0 THW mm² G WIRE 32 mm Φ PVC
2 PB2 75 60 9 28836.00 230 45.12 40.21 40.04 80 100 2 10 2-30 mm² THHN + 1-8.0 THW mm² G WIRE 32 mm Φ PVC
4 SPARE 1 1 10000 230 50 100 2 10 2-30 mm² THHN + 1-8.0 THW mm² G WIRE 32 mm Φ PVC
5 SPARE 1 1 10000 230 50 100 2 10 2-30 mm² THHN + 1-8.0 THW mm² G WIRE 32 mm Φ PVC
TOTAL 135 122 20 83261.00 92.29 94.64 88.12 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: SET 1-100mm² + 1-22mm² G THHN/THWN-1 Wire in
ICB = 209.01 75mmØ PVC PIPE
USE: 225AT/225AF, 3P, MCCB Bolt-On Type, 18 kAIC
SCHEDULE OF LOADS(NUEVA ERA MUNICIPALITY GROUND FLOOR)PB1 (C3)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
12 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
13 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
18 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
19 SPARE 1 1500 230 20 100 2 10
20 SPARE 1 1500 230 6.52 6.52 20 100 2 10

TOTAL 78 56 7 34425.00 47.17 54.43 48.08 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: 2-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
40mmØ IMC/RSC PIPE
ICB = 86.42
USE: 100 AT/100AF, 3P, MCCB Bolt-On Type, kAIC
SCHEDULE OF LOADS(NUEVA ERA MUNICIPALITY SECOND FLOOR)PB2
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 9 900 230 3.91 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 LIGHTING LOAD 6 600 230 2.61 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 CONVINIENCE OUTLET 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 CONVINIENCE OUTLET 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
12 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
13 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
15 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
16 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
17 SPARE 1 1500 230 6.52 20 100 2 10
18 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 60 50 6 28836.00 45.12 40.21 40.04 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: 2-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
40mmØ IMC/RSC PIPE
ICB = 72.39
USE: 100 AT/100AF, 3P, MCCB Bolt-On Type, kAIC
SCHEDULE OF LOADS(NUEVA ERA MUNICIPALITY 2ND BUILDING BACK GROUND FLOOR)PB3
P ANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 9 900 230 3.91 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 6 600 230 2.61 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 SPARE 1 1500 230 6.52 20 100 2 10
16 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 58 40 5 24127.00 36.21 34.13 34.56 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: 2-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
40mmØ IMC/RSC PIPE
ICB = 60.57
USE: 100 AT/100AF, 3P, MCCB Bolt-On Type, kAIC
SCHEDULE OF LOADS(NUEVA ERA MUNICIPALITY 2ND BUILDING BACK GROUND FLOOR)PB4
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 18 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 18 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 18 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 15 2700 230 11.74 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 15 2700 230 11.74 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVINIENCE OUTLET 15 2700 230 11.74 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
8 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 SPARE 1 1500 230 6.52 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE
14 SPARE 1 1500 230 6.52 20 100 2 10
15 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 54 45 9 34254.00 49.64 49.64 49.64 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: 2-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
40mmØ IMC/RSC PIPE
ICB = 85.99
USE: 100 AT/100AF, 3P, MCCB Bolt-On Type, kAIC
SCHEDULE OF LOADS(NUEVA ERA MUNICIPALITY)MDP
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 PB1 60 60 9 34425.00 230 47.17 54.43 48.08 100 225 2 10 2-30 mm² THHN + 1-8.0 THW mm² G WIRE 50 mm Φ PVC
2 PB2 75 60 9 28836.00 230 45.12 40.21 40.04 100 225 2 10 2-30 mm² THHN + 1-8.0 THW mm² G WIRE 50 mm Φ PVC
3 PB3 45 45 9 24127.00 230 36.21 34.13 34.56 100 225 2 10 2-30 mm² THHN + 1-8.0 THW mm² G WIRE 50 mm Φ PVC
4 SPARE 1 1 10000 230 100 225 2 10
5 SPARE 1 1 10000 230 100 225 2 10
6 PB4 54 45 9 34254.00 230 49.64 49.64 49.64 100 225 2 10 2-30 mm² THHN + 1-8.0 THW mm² G WIRE 50 mm Φ PVC
TOTAL 234 212 38 141642.00 178.15 178.41 172.32 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: SETS 1-250mm² + 1-30mm² G THHN/THWN-1 Wire in
ICB = 355.56 110 mmØ PVC PIPE
USE: 400AT/400AF, 3P, MCCB Bolt-On Type, 18kAIC
SCHEDULE OF LOADS (PUBLIC MARKET) (C4)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD(HIGH BAY) 6 600 230 2.61 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVENIENCE OUTLET LOAD 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVENIENCE OUTLET LOAD 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 CONVENIENCE OUTLET LOAD 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 REFRIGERATOR (COOLER) 1 165 230 0.72 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 REFRIGERATOR (COOLER) 165 230 0.72 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 REFRIGERATOR (COOLER) 165 230 0.72 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 FREEZER 1 350 230 1.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 FREEZER 350 230 1.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 FREEZER 350 230 1.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 FREEZER 350 230 1.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 SPARE 1 1500 230 6.52 20 100 2 10
18 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 42 27 6 19475.00 84.67


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
50mmØ PVC PIPE
ICB = 88.14
USE: 100 AT/100AF, 2P, MCCB Bolt-On Type, 10X Kaic
SCHEDULE OF LOADS ( CONVENIENCE STORE) (C5)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVENIENT OUTLET LOAD 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 REFRIGERATOR (COOLER) 1 165 230 0.72 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
6 REFRIGERATOR (COOLER) 1 165 230 0.72 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 FREEZER 1 350 230 1.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
8 FREEZER 1 350 230 1.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
1HPACU 1840 230 8.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 SPARE 1 1500 230 6.52 20 100 2 10
11 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 30 10 7 13430.00 58.39


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-22mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
40mmØ PVC PIPE
ICB = 67.11
USE: 80AT/100AF, 2P, MCCB Bolt-On Type, 18X kAIC
SCHEDULE OF LOADS (WATER STATION) (C6)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 SV100 UV DISINFECTANT 1 390 230 1.70 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 SV100 UV DISINFECTANT 1 390 230 1.70 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 OXYGEN CONCENTRATOR 1 1200 230 5.22 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 OXYGEN CONCENTRATOR 1 1200 230 5.22 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 OZONE GENERATOR 15G 1 250 230 1.09 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 OZONE GENERATOR 15G 1 250 230 1.09 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 ICE MACHINE 1 2100 230 9.13 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 3HP WATER BOOSTER PUMP 1 3910 230 17.00 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
11 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP WATER PUMP 1 2760 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 2HP WATER PUMP 1 2760 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 3HP WATER BOOSTER PUMP 1 3910 230 17.00 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
15 SPARE 1 1500 230 6.52 20 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE
16 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 12 6 14 27160.00 118.09


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
50mmØ PVC PIPE
ICB = 123.37
USE: 125 AT/225AF, 2P, MCCB Bolt-On Type, 18X kAIC
SCHEDULE OF LOADS ( RESTAURANT) (C7)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 8 800 230 3.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 ELECTRIC RANGE 1 4500 230 19.57 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
7 ELECTRIC RANGE 1 4500 230 19.57 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
8 ELECTRIC RANGE 1 4500 230 19.57 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
9 WALL MAOUNTED OVEN 1 4000 230 17.39 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
10 WALL MAOUNTED OVEN 1 4000 230 17.39 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
11 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 SPARE 1 1500 230 6.52 20 100 2 10
14 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 30 18 9 36260.00 157.65


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-50mm² + 1-14mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
63mmØ IMC/RSC PIPE
ICB = 146.52
USE: 150 AT/255AF, 2P, MCCB Bolt-On Type, 18X Kaic
SCHEDULE OF LOADS(GAS STATION) (C8)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT
1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 REFRIGERATOR 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 REFRIGERATOR 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 CLASSIC SERIES FUEL DISPENSER 1 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 CLASSIC SERIES FUEL DISPENSER 1 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 CLASSIC SERIES FUEL DISPENSER 1 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 CLASSIC SERIES FUEL DISPENSER 1 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 CLASSIC SERIES FUEL DISPENSER 1 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
12 CLASSIC SERIES FUEL DISPENSER 1 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
13 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 SPARE 1 1500 230 6.52 20 100 2 10
16 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 20 14 12 19370.00 84.22
M AIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230) USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
ICB = 87.77 50mmØ PVC PIPE
USE: 100 AT/100AF, 2P, MCCB Bolt-On Type, 10X Kaic
SCHEDULE OF LOADS ( CHURCH) (C9)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 8 800 230 3.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 REFRIGERATOR 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 SPARE 1 1500 230 6.52 30 100 2 10
16 SPARE 1 1500 230 6.52 30 100 2 10

TOTAL 43 26 9 28705.00 124.80


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-50mm² + 1-14mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
63mmØ PVC PIPE
ICB = 120.24
USE: 150 AT/255AF, 2P, MCCB Bolt-On Type, 18X Kaic
SCHEDULE OF LOADS (CAFÉ) (C10)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1?, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
3 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
4 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
5 CAKE DISPLAY FRIDGE 1 300 230 1.30 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
6 CHILLER CAKE FRIDGE 1 300 230 1.30 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
7 DRIP COFFEE MAKER 1 550 230 2.39 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
8 COFFEE ESPRESSO MAKER 1 850 230 3.70 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
9 COFFEE MAKER 1 850 230 3.70 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
10 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
11 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
12 REFRIGERATOR (COOLER) 1 165 230 0.72 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
13 REFRIGERATOR (COOLER) 1 165 230 0.72 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
14 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
15 SPARE 1 1500 230 6.52 20 100 2 10
16 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 20 16 12 19340.00 84.09


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
50mmØ PVC PIPE
ICB = 87.67
USE: 100 AT/100AF, 2P, MCCB Bolt-On Type, 10X Kaic
SCHEDULE OF LOADS (PLOICE STATION) (C11)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1?, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
3 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
4 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
5 REFRIGERATOR 1 80 230 0.35 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
6 ELECTRIC RANGE 1 6400 230 27.83 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm ? PVC
7 WATER HEATER 1 1125 230 4.89 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
8 MICROWAVE 1 1500 230 6.52 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
9 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
10 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
11 1.5HP AIRCONDITIONING UNIT 1 2300 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
12 1.5HP AIRCONDITIONING UNIT 1 2300 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
13 SPARE 1 1500 230 6.52 20 100 2 10
14 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 24 14 10 27145.00 118.02
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
50mmØ PVC PIPE
ICB = 114.82
USE: 125 AT/225AF, 2P, MCCB Bolt-On Type, 18X Kaic
SCHEDULE OF LOADS (FIRE STATION) (C12)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1?, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
3 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
4 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
5 REFRIGERATOR 1 80 230 0.35 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
6 ELECTRIC RANGE 1 6400 230 27.83 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm ? PVC
7 WATER HEATER 1 1125 230 4.89 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
8 MICROWAVE 1 1500 230 6.52 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
9 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
10 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
11 1.5HP AIRCONDITIONING UNIT 1 2300 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
12 1.5HP AIRCONDITIONING UNIT 1 2300 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
13 SPARE 1 1500 230 6.52 20 100 2 10
14 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 24 14 10 27145.00 118.02
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
50mmØ PVC PIPE
ICB = 114.82
USE: 125 AT/225AF, 2P, MCCB Bolt-On Type, 18X kAIC
SCHEDULE OF LOADS (LAUNDRY SHOP) (C13)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1?, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
3 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
4 WASHING MACHINE 1 635 230 2.76 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
5 WASHING MACHINE 1 635 230 2.76 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
6 WASHING MACHINE 1 635 230 2.76 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm ? PVC
7 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
8 1.5HP AIRCONDITIONING UNIT 1 2300 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm ? PVC
9 SPARE 1 1500 230 6.52 20 100 2 10
10 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 21 10 7 13865.00 60.28
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-22mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
40mmØ PVC PIPE
ICB = 68.63
USE: 80AT/100AF, 2P, MCCB Bolt-On Type, 10Kaic
SCHEDULE OF LOADS (BASKETBALL COURT) (C14)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
5 SPARE 1 1500 230 6.52 20 100 2 10
6 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 21 6 3 8940.00 38.87
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-14mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
25mmØ PVC PIPE
ICB = 51.50
USE: 60AT/100AF, 2P, MCCB Bolt-On Type,10 kAIC
SCHEDULE OF LOADS( COMPUTER SHOP) (C15)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 CONVINIENCE OUTLET 12 2160 230 9.39 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 12 2160 230 9.39 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 12 2160 230 9.39 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 2HP ACU 1 2760 230 12.00 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 2HP ACU 1 2760 230 12.00 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 2HP ACU 1 2760 230 12.00 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 SPARE 1 1500 230 6.52 20 100 2 10
10 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 24 36 5 20160.00 87.65
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
40mmØ PVC PIPE
ICB = 90.52
USE: 100AT/100AF, 2P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS (WESTERN UNION) (C16)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 CONVINIENCE OUTLET 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 2HP ACU 1 2760 230 12.00 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 SPARE 1 1500 230 6.52 20 100 2 10
6 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 21 7 3 9120.00 39.65
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-14mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
25mmØ PVCPIPE
ICB = 52.12
USE: 60AT/100AF, 2P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS( BUS STATION) (C17)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 REFRIGERATOR (COOLER) 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
6 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 SPARE 1 1500 230 6.52 20 100 2 10
8 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 21 6 5 11865.00 51.59
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-22mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
40mmØ PVC PIPE
ICB = 61.67
USE: 80AT/100AF, 2P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS ( BEER HOUSE) (C18)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 REFRIGERATOR (COOLER) 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 REFRIGERATOR (COOLER) 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 REFRIGERATOR (COOLER) 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 SPARE 1 1500 230 6.52 20 100 2 10
12 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 24 12 8 16335.00 71.02
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-22mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
40mmØ PVC PIPE
ICB = 77.22
USE: 80AT/100AF, 2P, MCCB Bolt-On Type, 10kAIC
SCHEDULE OF LOADS( BAKERY) (19)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 REFRIGERATOR (COOLER) 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 REEL OVEN 1 2000 230 8.70 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 REEL OVEN 1 2000 230 8.70 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 REEL OVEN 1 2000 230 8.70 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 REEL OVEN 1 2000 230 8.70 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 REFRIGERATOR (COOLER) 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 REFRIGERATOR (COOLER) 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 2HP ACU 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 SPARE 1 1500 230 6.52 20 100 2 10
14 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 21 6 11 20195.00 87.80
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
40mmØ PVC PIPE
ICB = 90.64
USE: 100AT/100AF, 2P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS( GYM) (20)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 TREADMILL 2 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 TREADMILL 2 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 TREADMILL 2 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 TREADMILL 2 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 SPARE 1 1500 230 6.52 20 100 2 10
12 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 24 19 12 19140.00 83.22
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
40mmØ PVC PIPE
ICB = 86.97
USE: 100AT/100AF, 2P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS(COMMERCIAL ESTABLISHMENT)PB1 (C22)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
13 SPARE 1 1500 230 6.52 20 100 2 10
14 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 34 37 7 26605.00 37.60 42.25 35.82 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: SET 1-22mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
40mmØ PVC PIPE
ICB = 66.79
USE: 80AT/100AF, 2P, MCCB Bolt-On Type, 10 KAIC
SCHEDULE OF LOADS( SECOND FLOOR)PB2
P ANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 9 900 230 3.91 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVINIENCE OUTLET 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 2HP AIRCONDITIONING UNIT 1 2709 230 11.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 SPARE 1 1500 230 6.52 20 100 2 10
12 SPARE 1 1500 230 6.52 20 100 2 10

TOTAL 43 25 5 19927.00 26.30 31.34 29.00 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: SET 1-14mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
32mmØ PVC PIPE
ICB = 50.02
USE: 60AT/100AF, 3P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS(NUEVA ERA MUNICIPALITY)MDP
P ANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 PB1 60 60 9 37554 230 37.60 42.25 35.82 200 225 2 10 2-80 mm² THHN + 1-14 THW mm² G WIRE 75 mm Φ PVC
2 PB2 75 60 9 39054 230 26.30 31.34 29.00 200 225 2 10 2-80 mm² THHN + 1-14 THW mm² G WIRE 75 mm Φ PVC
4 SPARE 1 30000 230 175 225 2 10 2-80 mm² THHN + 1-14 THW mm² G WIRE 75 mm Φ PVC
5 SPARE 1 30000 230 175 225 2 10 2-80 mm² THHN + 1-14 THW mm² G WIRE 75 mm Φ PVC
TOTAL 135 120 20 136608.00 63.90 73.60 64.81 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: SETS 1-200mm² + 1-30mm² G THHN/THWN-1 Wire in
ICB = 342.93 110mmØ PVC PIPE
USE: 350AT/600AF, 3P, MCCB Bolt-On Type, 18 kAIC
SCHEDULE OF LOADS(BARANGAY HALL) (C23)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 REFRIGERATOR (COOLER) 1 230 0.00 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
6 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 SPARE 1 1500 230 6.52 20 100 2 10
8 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 21 10 5 12420.00 54.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-14mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
32mmØ PVC PIPE
ICB = 63.60
USE: 70AT/100AF, 2P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS (PHARMACY) (C24)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 REFRIGERATOR 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
5 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
6 1HP AIRCONDITIONING UNIT 1 1860 230 8.09 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 25 mm Φ PVC
7 SPARE 1 1500 230 6.52 20 100 2 10
8 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 12 10 6 13545.00 58.89
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-14mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
32mmØ PVC PIPE
ICB = 67.51
USE: 70AT/100AF, 2P, MCCB Bolt-On Type, 10 Kaic
SCHEDULE OF LOADS(DRUG STORE) (C25)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 1Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) (A) AT AF POLE kAIC CONDUIT

1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 8 800 230 3.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 REFRIGERATOR 1 165 230 0.72 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
8 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 1HP AIRCONDITIONING UNIT 1 1860 230 8.09 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 SPARE 1 1500 230 6.52 20 100 2 10
12 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 28 18 7 19345.00 84.11
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = (((Total Connected Load - Highest Motor Load) * Demand Factor)/230)
USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
+ 250% Highest Motor Load
40mmØ PVC PIPE
ICB = 87.69
USE: 100AT/100AF, 2P, MCCB Bolt-On Type, 10 Kaic
SCHEDULE OF LOADS(NUEVA ERA HOSPITAL SECOND FLOOR)PB1 (C26)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 8 800 230 3.48 15 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 9 900 230 3.91 15 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 15 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 8 800 230 3.48 15 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 LIGHTING LOAD 11 1100 230 4.78 15 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 LIGHTING LOAD 12 1200 230 5.22 15 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
8 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 CONVINIENCE OUTLET 7 1260 230 5.48 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 CONVINIENCE OUTLET 10 1800 230 7.83 20 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 1.5HP AIRCONDITIONING UNIT 1 2300 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 SPARE 1 1500 230 6.52 20 100 2 10
18 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 60 55 6 29480.00 44.61 38.96 44.61 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: SET 1-22mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
40mmØ PVC PIPE
ICB = 74.00
USE: 80 AT/100AF, 3P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS(NUEVA ERA HOSPITAL THIRD FLOOR)PB2
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 8 800 230 3.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 CONVINIENCE OUTLET 8 1440 230 6.26 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
8 CONVINIENCE OUTLET 8 1440 230 6.26 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 1.5HP AIRCONDITIONING UNIT 1 2300 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 SPARE 1 1500 230 6.52 20 100 2 10
14 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 52 26 6 23460.00 31.48 34.35 36.17 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: SET 1-14mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
32mmØ PVC PIPE
ICB = 58.89
USE: 60AT/100AF, 3P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS(NUEVA ERA HOSPITAL FOURTH FLOOR)PB3
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
8 1.5HP AIRCONDITIONING UNIT 1 2300 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 1.5HP AIRCONDITIONING UNIT 1 2300 230 10.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 1HP AIRCONDITIONING UNIT 1 1860 230 8.09 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 1HP AIRCONDITIONING UNIT 1 1860 230 8.09 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 SPARE 1 1500 230 6.52 20 100 2 10
14 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 36 30 8 25840.00 39.65 37.65 35.04 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: SET 1-14mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
32mmØ PVC PIPE
ICB = 64.87
USE: 70 AT/100AF, 3P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS(NUEVA ERA HOSPITAL DIAGNOSTIC LABORATORY & IMAGING)PB4
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 BIOCHEMISTRY ANALYZER 5 500 230 2.17 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 HEMATOLOGY ANALYZER 5 800 230 3.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 ELECTRODIAGRAM MACHINE 5 200 230 0.87 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 X-RAY MACHINE 1 32000 230 139.13 175 225 2 10 2-80 mm² THHN + 1-14 THW mm² G WIRE 75 mm Φ PVC
5 X-RAY MACHINE 1 32000 230 139.13 175 225 2 10 2-80 mm² THHN + 1-14 THW mm² G WIRE 75 mm Φ PVC
6 X-RAY MACHINE 1 32000 230 139.13 175 225 2 10 2-80 mm² THHN + 1-14 THW mm² G WIRE 75 mm Φ PVC
7 ULTRASOUND 5 800 230 3.48 20 100 2 10
8 SPARE 1 1500 230 6.52 20 100 2 10
9 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 0 0 23 101300.00 144.78 149.13 146.52 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: SET 1-150mm² + 1-22mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
90mmØ PVC PIPE
ICB = 254.29
USE: 300 AT/400AF, 3P, MCCB Bolt-On Type, 18kAIC
SCHEDULE OF LOADS(NUEVA ERA HOSPITAL CRITICAL CARE/ ICU)PB5
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 PATIENT MONITOR 15 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 PATIENT MONITOR 15 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 PATIENT MONITOR 15 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 PATIENT MONITOR 15 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 DEFIBRILLATORS 1 4500 230 19.57 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
6 VENTILATORS 10 380 230 1.65 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 INFUSION PUMP 8 800 230 3.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 SYRINGE PUMP 10 550 230 2.39 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 SPARE 1 1500 230 6.52 20 100 2 10
10 DEFIBRILLATORS 1 4500 230 19.57 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 SPARE 1 1500 230 6.52 20 100 2 10
12 DEFIBRILLATORS 1 4500 230 19.57 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
TOTAL 0 0 60 23030.00 33.48 33.69 32.96 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: SET 1-14mm² + 1-8.0mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
32mmØ IMC/RSC PIPE
ICB = 57.81
USE: 60 AT/100AF, 3P, MCCB Bolt-On Type, 10kAIC
SCHEDULE OF LOADS(NUEVA ERA HOSPITAL OPERATING ROOM)PB6
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 SURGICAL LIGHTS 3 1500 230 6.52 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
ELECTROSURGICAL UNIT/CAUTERY
2 4 1600 230 6.96 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
MACHINE
3 ANESTHESIA MACHINE 5 400 230 1.74 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 SUCTION APPARATUS 10 400 230 1.74 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 STERILIZER 10 250 230 1.09 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 SPARE 1 1500 230 6.52 20 100 2 10
7 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 0 0 33 7150.00 8.26 8.04 14.78 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: SET 1-5.5mm² + 1-5.5mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%)
20mmØ PVC PIPE
ICB = 17.95
USE: 30 AT/50AF, 3P, MCCB Bolt-On Type, 10 kAIC
SCHEDULE OF LOADS(NUEVA ERA HOSPITAL) MDP
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3?, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
LOAD DESCRIPTION VA 3? SIZE AND TYPE OF WIRE
NO. LO CO SPO (V) AB CA BC AT AF POLE kAIC CONDUIT
1 PB1 29480.00 230 44.61 38.96 44.61 80 100 2 10 2-150 mm² THHN + 1-22 THW mm² G WIRE 40 mm ? PVC
2 PB2 23460.00 230 31.48 34.35 36.17 60 100 2 10 2-150 mm² THHN + 1-22 THW mm² G WIRE 32 mm ? PVC
3 PB3 25840.00 230 39.65 37.65 35.04 70 100 2 18 2-150 mm² THHN + 1-22 THW mm² G WIRE 32 mm ? PVC
4 PB4 101300.00 230 144.78 149.13 146.52 300 400 2 35 2 SET 2-150 mm² THHN + 1-38 THW mm² G WIRE90 mm ? PVC
5 PB5 23030.00 230 33.48 33.69 32.96 70 100 2 10 2-38 mm² THHN + 1-14 THW mm² G WIRE 32 mm ? PVC
6 SPARE 15000 230 100 100 2 18
7 PB6 7150.00 230 8.26 8.04 14.78 30 100 2 10 2-14 mm² THHN + 1-8.0 THW mm² G WIRE 20mm ? PVC
8 SPARE 15000 230 100 225 2 10

TOTAL 0 0 0 240260.00 302.26 301.82 310.09 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand
Factor)/(230*?3)) × 125% USE: 3 SET 2-200mm² + 1-60mm² G THHN/THWN-1 Wire in
(Assumed Demand Factor 80%) 110mmØ PVC PIPE
ICB = 603.12
USE: 700AT/800AF, 3P, MCCB Bolt-On Type, 35kAIC
SCHEDULE OF LOADS OF APARTMENT PB1
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 8 1440 230 6.26 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 ELECTRIC RANGE 1 3200 230 13.91
8 REFRIGERATOR 1 190 230 0.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 REFRIGERATOR 1 190 230 0.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 WASHING MACHINE 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 WASHING MACHINE 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 2 HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 SPARE 1 3000 230 13.04 20 100 2 10
18 SPARE 1 3000 230 13.04 20 100 2 10

TOTAL 34 28 12 34820.00 56.61 43.87 50.91 0.00

MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:


ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
ICB = 87.41 50mmØ PVC
USE: 100 AT/100AF, 3P, MCCB Bolt-On Type, 10kAIC
SCHEDULE OF LOADS OF APARTMENT PB2
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
4 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 8 1440 230 6.26 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 ELECTRIC RANGE 1 3200 230 13.91 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
8 REFRIGERATOR 1 190 230 0.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 REFRIGERATOR 1 190 230 0.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 WASHING MACHINE 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 WASHING MACHINE 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 2HP AIRCONDITIONING UNIT 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 2 HP WATER PUMP 1 2760 230 12.00 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 SPARE 1 3000 230 13.04 20 100 2 10
18 SPARE 1 3000 230 13.04 20 100 2 10
TOTAL 34 28 12 34820.00 56.61 43.87 50.91 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: SET 1-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in
ICB = 87.41 50mmØ PVC
USE: 100 AT/100AF, 3P, MCCB Bolt-On Type, 10kAIC
SCHEDULE OF LOADS OF APARTMENT MDP
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 PB1 10 34820.00 230 56.61 43.87 50.91 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
2 PB2 12 34820.00 230 56.61 43.87 50.91 20 100 2 10 2-3.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
3 SPARE 1 1500 230 20 100 2 10
4 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 22 0 2 72640.00 113.22 94.26 101.83 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: SET 1-80mm² + 1-14mm² G THHN/THWN-1 Wire in
ICB = 182.35 75mmØ PVC
USE: 200 AT/225AF, 3P, MCCB Bolt-On Type, 18 kAIC
SCHEDULE OF LOADS (PB1) INDUSTRIAL 1
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 12 1200 230 5.22 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 3HP ACU 1 3825 230 16.63 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 2HP ACU 1 2709 230 11.78 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 2HP ACU 1 2709 230 11.78 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 2HP ACU 1 2709 230 11.78 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 2HP ACU 1 2709 230 11.78 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 SPARE 1 3000 230
15 SPARE 1 3000 230

TOTAL 48 30 7 30861.00 30.04 41.45 36.60 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 3-22mm² + 1-8.0mm² G THHN/THWN-1 Wire in 32mmØ
ICB = 77.47 PVC PIPE
USE: 80AT/100AF, 3P, MCCB Bolt-On Type, XX kAIC
SCHEDULE OF LOADS(PB2)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 12 1200 230 5.22 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
6 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
7 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
8 5HP ACU 1 6055 230 26.33 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
9 5HP ACU 1 6055 230 26.33 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
10 5HP ACU 1 6055 230 26.33 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
11 8KW-RJWJ 200C SOFTGELMACHINE 1 8000 230 34.78 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
12 8KW-RJWJ 200C SOFTGELMACHINE 1 8000 230 34.78 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
13 8KW-RJWJ 200C SOFTGELMACHINE 1 8000 230 34.78 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
14 7KW-CPT150 CAPSULE FILLER 1 7000 230 30.43 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
15 7KW-CPT150 CAPSULE FILLER 1 7000 230 30.43 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
16 7KW-CPT150 CAPSULE FILLER 1 7000 230 30.43 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
17 SPARE 1 1500 230
18 SPARE 1 1500 230

TOTAL 48 30 11 76365.00 109.80 104.59 104.59 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 3-80mm² + 1-14mm² G THHN/THWN-1 Wire in 65mmØ
ICB = 191.70 PVC PIPE
USE: 200AT/225AF, 3P, MCCB Bolt-On Type, 18kAIC
SCHEDULE OF LOADS(PB3)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 10 1000 230 4.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
6 CONVINIENCE OUTLET 8 1440 230 6.26 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
7 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
8 4KW-T2 TUMBLER DRYING UNIT 1 4000 230 17.39 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
9 4KW-T2 TUMBLER DRYING UNIT 1 4000 230 17.39 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
10 4KW-T2 TUMBLER DRYING UNIT 1 4000 230 17.39 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
11 4KW-T2 TUMBLER DRYING UNIT 1 4000 230 17.39 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
12 4KW-T2 TUMBLER DRYING UNIT 1 4000 230 17.39 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
13 4KW-T2 TUMBLER DRYING UNIT 1 4000 230 17.39 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
14 SPARE 1 1500 230
15 SPARE 1 1500 230

TOTAL 34 28 8 35440.00 47.83 45.39 47.83 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 3-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in 40mmØ
ICB = 88.96 IMC/RSC PIPE
USE: 100AT/100AF, 3P, MCCB Bolt-On Type, XX kAIC
SCHEDULE OF LOADS(PB4)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 12 1200 230 5.22 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 12 1200 230 5.22 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
6 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
7 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
8 5HP ACU 1 6055 230 26.33 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
9 5HP ACU 1 6055 230 26.33 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
10 5HP ACU 1 6055 230 26.33 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
11 SPARE 1 1500 230
12 SPARE 1 1500 230

TOTAL 48 30 5 31365.00 44.59 39.37 39.37 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 3-22mm² + 1-8.0mm² G THHN/THWN-1 Wire in 32mmØ
ICB = 78.74 IMC/RSC PIPE
USE: 80AT/100AF, 3P, MCCB Bolt-On Type, XX kAIC
SCHEDULE OF LOADS(PB5)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 8 800 230 3.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 6 600 230 2.61 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 LIGHTING LOAD 10 1000 230 4.35 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 7 1260 230 5.48 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
6 CONVINIENCE OUTLET 5 900 230 3.91 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
7 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
8 5HP ACU 1 6055 230 26.33 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
9 5HP ACU 1 6055 230 26.33 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
10 5HP ACU 1 6055 230 26.33 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
11 7KW BLISTER PACK MACHINE 1 7000 230 30.43 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
12 7KW BLISTER PACK MACHINE 1 7000 230 30.43 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
13 2.2KW VACUUM HOMOGINIZER 1 2200 230 9.57 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
14 2.2KW VACUUM HOMOGINIZER 1 2200 230 9.57 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
15 4KW-GEL METER 1 4000 230 17.39 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
16 4KW-GEL METER 1 4000 230 17.39 40 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
17 SPARE 1 1500 230
18 SPARE 1 1500 230

TOTAL 36 22 11 55125.00 70.67 75.28 80.67 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 3-50mm² + 1-14mm² G THHN/THWN-1 Wire in 63mmØ
ICB = 138.38 PVC PIPE
USE: 150AT/225AF, 3P, MCCB Bolt-On Type, 18 kAIC
SCHEDULE OF LOADS(PB6)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 LIGHTING LOAD 12 1200 230 5.22 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 LIGHTING LOAD 11 1100 230 4.78 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 LIGHTING LOAD 6 600 230 2.61 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
7 CONVINIENCE OUTLET 10 1800 230 7.83 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 30 mm Φ PVC
8 5HP ACU 1 6055 230 26.33 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
9 5HP ACU 1 6055 230 26.33 30 100 2 10 2-8.0 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
10 5HP ACU 1 6055 230 26.33 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
11 2.2KW CHILLING MACHINE 1 2200 230 9.57 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
12 2.2KW CHILLING MACHINE 1 2200 230 9.57 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
13 1.5KW SOFTGEL PULVERISER 1 1500 230 6.52 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
14 4KW BG600 FILM COATING MACHINE 1 4000 230 17.39 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
1.1KW-NF
15 SERIES TUBE FILLING AND SEALING MACHINE 1 1100 230 4.78 40 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
16 1.5KW -WZH1 PACKAGING CARTOON MACHINE 1 1500 230 6.52 40 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 30 mm Φ PVC
17 SPARE 1 1500 230
18 SPARE 1 1500 230

TOTAL 29 20 11 40165.00 53.72 51.98 55.89 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 3-38mm² + 1-14mm² G THHN/THWN-1 Wire in 40mmØ
ICB = 100.83 PVC PIPE
USE: 125AT/225AF, 3P, MCCB Bolt-On Type, 18 kAIC
SCHEDULE OF LOADS ( MDP)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 PB1 30861.00 230 30.04 41.45 36.60 80 100 3 10 2-22 mm² THHN + 1-8.0THW mm² G WIRE 32 mm Φ PVC
2 PB2 76365.00 230 109.80 104.59 104.59 200 100 3 10 2-80 mm² THHN + 1-14 THW mm² G WIRE 65mm Φ PVC
3 PB3 35440.00 230 47.83 45.39 47.83 100 100 3 10 2-30 mm² THHN + 1-8.0THW mm² G WIRE 30 mm Φ PVC
4 PB4 31365.00 230 44.59 39.37 39.37 150 100 3 10 2-50 mm² THHN + 1-14 THW mm² G WIRE 50 mm Φ PVC
5 PB5 55125.00 230 70.67 75.28 80.67 150 100 3 10 2-50 mm² THHN + 1-14 THW mm² G WIRE 50 mm Φ PVC
6 PB6 40165.00 230 53.72 51.98 55.89 125 100 3 10 2-38 mm² THHN + 1-14 THW mm² G WIRE 50mm Φ PVC
7 SPARE 1500 230
8 SPARE 1500 230

TOTAL 0 0 0 272321.00 356.65 358.06 364.95 0.00


MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 3 SETS-250mm² + 1-60mm² G THHN/THWN-1 Wire in 3
ICB = 683.61 SETS 90mmØ PVC PIPE
USE: 700AT/800AF, 3P, MCCB Bolt-On Type, 35kAIC
SCHEDULE OF LOADS(INDUSTRIAL BUILDING 1 LIGHTS & OUTLET) PB1
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 37.5W LED DT SERIES 4'x1' 10 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 37.5W LED DT SERIES 4'x1' 7 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE
3 37.5W LED DT SERIES 4'x1' 8 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 37.5W LED DT SERIES 4'x1' 10 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE
5 37.5W LED DT SERIES 4'x1' 10 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 37.5W LED DT SERIES 4'x1' 8 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE
7 37.5W LED DT SERIES 4'x1' 10 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE
8 70W HIGH QUALITY LED WALL LIGHT 6 490 230 2.13 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 70W HIGH QUALITY LED WALL LIGHT 8 560 230 2.43 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 70W HIGH QUALITY LED WALL LIGHT 8 630 230 2.74 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 70W HIGH QUALITY LED WALL LIGHT 11 770 230 3.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
12 LED HBM SERIES MODULAR HIGBAY 200W 9 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 LED HBM SERIES MODULAR HIGBAY 200W 9 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 LED HBM SERIES MODULAR HIGBAY 200W 8 1600 230 6.96 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 LED HBM SERIES MODULAR HIGBAY 200W 9 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 LED HBM SERIES MODULAR HIGBAY 200W 7 490 230 2.13 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
18 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
19 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
20 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
21 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
22 CONVINIENCE OUTLET 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
23 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
24 CONVINIENCE OUTLET 5 900 230 3.91 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
25 SPARE 1 1500 230 6.52 20 100 2 10
26 SPARE 1 1500 230 6.52 20 100 2 10
TOTAL 138 58 2 28630.00 40.74 43.48 40.26 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125%
USE: 2-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in 40mmØ
(Assumed Demand Factor 80%)
IMC/RSC PIPE
ICB = 71.87
USE: 80 AT/100AF, 3P, MCCB Bolt-On Type, Kaic
SCHEDULE OF LOADS(INDUSTRIAL ACU) PB2
PANEL TAG : PB-2 FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 3HP ACU 3835 230 16.67 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 3HP ACU 3835 230 16.67 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE
3 3HP ACU 3835 230 16.67 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 3HP ACU 3835 230 16.67 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE
5 3HP ACU 3835 230 16.67 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 3HP ACU 3835 230 16.67 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE
7 5HP ACU 6055 230 26.33 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE
8 5HP ACU 6055 230 26.33 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 5HP ACU 6055 230 26.33 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 5HP ACU 6055 230 26.33 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 5HP ACU 6055 230 26.33
12 5HP ACU 6055 230 26.33
13 SPARE 770 230 3.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
14 SPARE 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
TOTAL 0 0 0 61910.00 89.35 93.83 86.00 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 2-80mm² + 1-14mm² G THHN/THWN-1 Wire in 65mmØ
ICB = 155.41 IMC/RSC PIPE
USE: 175 AT/225AF, 3P, MCCB Bolt-On Type, Kaic
SCHEDULE OF LOADS(INDUSTRIAL BUILDING 1 LIGHTS & OUTLET) PB3
PANEL TAG :PB-3 FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 37.5W LED DT SERIES 4'x1' 10 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
2 37.5W LED DT SERIES 4'x1' 7 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
3 37.5W LED DT SERIES 4'x1' 8 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
4 37.5W LED DT SERIES 4'x1' 10 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
5 37.5W LED DT SERIES 4'x1' 10 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
6 37.5W LED DT SERIES 4'x1' 8 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
7 37.5W LED DT SERIES 4'x1' 10 750 230 3.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
8 70W HIGH QUALITY LED WALL LIGHT 6 490 230 2.13 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
9 70W HIGH QUALITY LED WALL LIGHT 8 560 230 2.43 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
10 70W HIGH QUALITY LED WALL LIGHT 8 630 230 2.74 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 70W HIGH QUALITY LED WALL LIGHT 11 770 230 3.35 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
12 LED HBM SERIES MODULAR HIGBAY 200W 9 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 LED HBM SERIES MODULAR HIGBAY 200W 9 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
14 LED HBM SERIES MODULAR HIGBAY 200W 8 1600 230 6.96 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
15 LED HBM SERIES MODULAR HIGBAY 200W 9 1800 230 7.83 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
16 LED HBM SERIES MODULAR HIGBAY 200W 7 490 230 2.13 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
17 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
18 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
19 CONVINIENCE OUTLET 8 1440 230 6.26 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
20 CONVINIENCE OUTLET 6 1080 230 4.70 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
21 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
22 CONVINIENCE OUTLET 7 1260 230 5.48 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
23 CONVINIENCE OUTLET 9 1620 230 7.04 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
24 CONVINIENCE OUTLET 5 900 230 3.91 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC

25 SPARE 1 1500 230 6.52 20 100 2 10

26 SPARE 1 1500 230 6.52 20 100 2 10


TOTAL 138 58 2 28630.00 40.74 43.48 40.26 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 2-30mm² + 1-8.0mm² G THHN/THWN-1 Wire in 40mmØ
ICB = 71.87 IMC/RSC PIPE
USE: 80 AT/100AF, 3P, MCCB Bolt-On Type, Kaic
SCHEDULE OF LOADS(INDUSTRIAL BUILDING ACU 2)PB4
PANEL TAG : PB-4 FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 3HP ACU 10 3825 230 16.63 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
2 3HP ACU 7 3825 230 16.63 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
3 3HP ACU 8 3825 230 16.63 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
4 2HP ACU 10 2709 230 11.78 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
5 2HP ACU 8 2709 230 11.78 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
6 2HP ACU 10 2709 230 11.78 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
7 5HP ACU 6 6055 230 26.33 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
8 5HP ACU 8 6055 230 26.33 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
9 5HP ACU 8 6055 230 26.33 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
10 1.5HP ACU 11 2390 230 10.39 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
11 1.5HP ACU 9 2390 230 10.39 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
12 3HP ACU 9 3825 230 16.63 30 100 2 10 2-5.5 mm² THHN + 1-5.5 THW mm² G WIRE 20 mm Φ PVC
13 SPARE 8 1600 230 6.96
14 SPARE 9 1800 230 7.83
TOTAL 121 0 0 49772.00 71.37 72.08 72.95 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 2-38mm² + 1-14mm² G THHN/THWN-1 Wire in 50mmØ
ICB = 124.94 IMC/RSC PIPE
USE: 125 AT/225AF, 3P, MCCB Bolt-On Type, Kaic
SCHEDULE OF LOADS(INDUSTRIAL MOTORS)1 PB5
PANEL TAG : PB-5 FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 7HP CONVEYOR BELT 8764 230 38.10 70 100 2 10 2-14 mm² THHN + 1-8.0 THW mm² G WIRE 32 mm Φ PVC
2 5HP SERVO MOTOR ARM 6055 230 26.33 40 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
3 1 HP POLISHING MACHINE 1674 230 7.28 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
4 5HP SERVO MOTOR ARM 6055 230 26.33 40 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
5 6KV WELDING MACHINE 6000 230 26.09 40 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
6 3HP AIRBRUSH COMPRESSOR 3825 230 16.63 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
7 1.5HP SERVO MOTOR ARM 2390 230 10.39 0 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
8 5HP SERVO MOTOR ARM 6055 230 26.33 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
9 10HP CONVEYOR BELT 11154 230 48.50 70 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
10 2HP EXHAUST FAN 2708 230 11.77 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 SPARE 1600 230 6.96 20 100
12 SPARE 1800 230 7.83 20 100
TOTAL 0 0 0 58080.00 86.60 85.70 80.23 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 2-38mm² + 1-14mm² G THHN/THWN-1 Wire in 50mmØ
ICB = 145.80 IMC/RSC PIPE
USE: 150 AT/225AF, 3P, MCCB Bolt-On Type, Kaic
SCHEDULE OF LOADS(INDUSTRIAL MOTORS)1 PB5
PANEL TAG : PB-5 FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 7HP CONVEYOR BELT 8764 230 38.10 70 100 2 10 2-14 mm² THHN + 1-8.0 THW mm² G WIRE 32 mm Φ PVC
2 5HP SERVO MOTOR ARM 6055 230 26.33 40 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
3 1 HP POLISHING MACHINE 1674 230 7.28 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
4 5HP SERVO MOTOR ARM 6055 230 26.33 40 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
5 6KV WELDING MACHINE 6000 230 26.09 40 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
6 3HP AIRBRUSH COMPRESSOR 3825 230 16.63 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
7 1.5HP SERVO MOTOR ARM 2390 230 10.39 0 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
8 5HP SERVO MOTOR ARM 6055 230 26.33 30 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
9 10HP CONVEYOR BELT 11154 230 48.50 70 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 25 mm Φ PVC
10 2HP EXHAUST FAN 2708 230 11.77 20 100 2 10 2-3.5 mm² THHN + 1-3.5 THW mm² G WIRE 20 mm Φ PVC
11 SPARE 1600 230 6.96 20 100
12 SPARE 1800 230 7.83 20 100
TOTAL 0 0 0 58080.00 86.60 85.70 80.23 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 2-38mm² + 1-14mm² G THHN/THWN-1 Wire in 50mmØ
ICB = 145.80 IMC/RSC PIPE
USE: 150 AT/225AF, 3P, MCCB Bolt-On Type, Kaic
SCHEDULE OF LOADS(INDUSTRIAL MDP)
PANEL TAG : DP-G FEED FROM : UTILITY COMPANY NOTES:
LOCATION: AS SHOWN ON PLAN ENCLOSURE : INDOOR NEMA-1 1. Use Industrial Type CIRCUIT BREAKER.
SERVICE VOLTAGE : 230V, 3Φ, 60HZ MOUNTING : RECESSED MOUNTED 2. Brand and Specification is for Approval.
3. Kindly Coordinate if there is Clarification on Plan.
CKT NO. OF OUTLETS VOLTS PHASE CURRENT CIRCUIT BREAKER SIZE AND TYPE OF
NO.
LOAD DESCRIPTION VA
(V)
3Φ SIZE AND TYPE OF WIRE
CONDUIT
LO CO SPO AB CA BC AT AF POLE kAIC
1 PB-1 28630.00 230 40.74 43.48 40.26 80 100 3 10 2-22mm² + 1-8.0mm² G THHN/THWN-1 Wire 40mm Φ PVC
2 PB-2 61910.00 230 89.35 93.83 86.00 175 225 3 18 2-80mm² + 1-14mm² G THHN/THWN-1 Wire 75 mm Φ PVC
3 PB-3 28630.00 230 40.74 43.48 40.26 80 100 3 10 2-22mm² + 1-8.0mm² G THHN/THWN-1 Wire 40 mm Φ PVC
4 PB-4 49772.00 230 71.37 72.08 72.95 125 225 3 18 2-38mm² + 1-14mm² G THHN/THWN-1 Wire 63 mm Φ PVC
5 PB-5 58080.00 230 86.60 85.70 80.23 150 225 3 18 2-38mm² + 1-14mm² G THHN/THWN-1 Wire 64 mm Φ PVC
6 PB-6 58080.00 230 86.60 85.70 80.23 150 225 3 18 2-38mm² + 1-14mm² G THHN/THWN-1 Wire 65 mm Φ PVC
7 SPARE 10000
8 SPARE 10000
TOTAL 0 0 0 305102.00 415.38 424.26 399.93 0.00
MAIN BREAKER COMPUTATION: FEEDER CONDUCTOR:
ICB = ((Total Connected Load * Demand Factor)/(230*√3)) × 125% USE: 2 SET-250mm² + 1-50mm² G THHN/THWN-1 Wire in 2
ICB = 765.90 SET-90mmØ PVC PIPE
USE: 800AT/800AF, 3P, MCCB Bolt-On Type, Kaic
CIRCUIT LAYOUT
TRANSFORMER 1

TRANSFORMER 2
TRANSFORMER 3

TRANSFORMER 4
TRANSFORMER 5

TRANSFORMER 6
TRANSFORMER 7

TRANSFORMER 8
TRANSFORMER 9

TRANSFORMER 10
TRANSFORMER 11

TRANSFORMER 12
TRANSFORMER 17

TRANSFORMER 18
TRANSFORMER 13

TRANSFORMER 14
TRANSFORMER 19

TRANSFORMER 20
TRANSFORMER 15

TRANSFORMER 16
TRANSFORMER 21

TRANSFORMER 22
TRANSFORMER 23

TRANSFORMER 24
TRANSFORMER 27

TRANSFORMER 28
TRANSFORMER 25

TRANSFORMER 26
TRANSFORMER 31

TRANSFORMER 32
TRANSFORMER 29

TRANSFORMER 30
TRANSFORMER 33

TRANSFORMER 34
TRANSFORMER 35

TRANSFORMER 36
TRANSFORMER 39

TRANSFORMER 40
TRANSFORMER 37

TRANSFORMER 38
TRANSFORMER 41

TRANSFORMER 42
TRANSFORMER 43

TRANSFORMER 44

TRANSFORMER 45
DIVERSIFIED DEMAND AND
SIZING OF TRANSFORMERS
(CALCULATION OF PERMISSIBLE OVERLOAD BASED ON NEMA PUB. NO.
TR 98-1964 FOR TRANSFORMERS 65° RISE
DIVERSIFIED DEMAND OF T1
60
50
40
KVA

30
20
10
0
12:00 AM
1:00 AM
2:00 AM
3:00 AM
4:00 AM
5:00 AM
6:00 AM
7:00 AM
8:00 AM
9:00 AM
10:00 AM
11:00 AM
12:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
10:00 PM
11:00 PM
1R6 2C5 C11 TIME

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD DURATION 2 HOURS BEFOREOVERLOAD


52.48 43.68 43.68
53.12
12:00 PM 43.68 43.68
53.12 10:00 AM 10:00 AM
53.12 43.68 43.68
12:15 50.36 43.68 43.68
12:30 50.36 43.68 43.68
43.68 43.68
11:00 AM 11:00 AM
43.68 43.68
PEAK 53.12 43.68 43.68
AVE 43.68 AVE 43.68

TRANSFORMER 1:
53.1200
➢ Max demand:
➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 3.12
➢ Duration of Overload: 2 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 43.68
%Load: 87.36
❖ 24 hours:
Average: 35.21
%Load: 70.42

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 142
➢ Max overload for transformer 71
➢ Higher than max overload 53.12
DIVERSIFIED DEMAND OF T2
80
70
60
50
KVA

40
30
20
10
0

4:00 AM
5:00 AM

12:00 PM

7:00 PM
8:00 PM

10:00 PM
11:00 PM
1:00 AM
2:00 AM
3:00 AM

6:00 AM
7:00 AM
8:00 AM
9:00 AM
12:00 AM

10:00 AM
11:00 AM

1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM

9:00 PM
TIME

3R4 3R5 C12 C21 C24

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD


ESTABLISHMENT NO OF LOADS
67.88 37.22
67.88 37.22 R4 3
12:00 PM
67.88 10:00 AM 36.86 R5 3
67.88 36.86 C12 1
12:15 PM 56.48 37.72 C21 1
12:30 PM 52.28 37.72 C24 1
11:00 AM 37.72
PEAK 67.88 40.82
AVE 37.7675
TOTAL 9

TRANSFORMER 1:
67.8800
➢ Max demand:
➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 17.88
➢ Duration of Overload: 1.5 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 37.77
%Load: 75.54
❖ 24 hours:
Average: 36.83
%Load: 73.66

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 151
➢ Max overload for transformer 75.5
➢ Higher than max overload 67.88
70 DIVERSIFIED DEMAND OF T3
60

50

40
KVA

30

20

10

3:00 PM

6:00 PM
12:00 PM

10:00 PM

11:00 PM
12:00 AM

1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

10:00 AM

11:00 AM

1:00 PM

2:00 PM

4:00 PM

5:00 PM

7:00 PM

8:00 PM

9:00 PM
TIME
2R2 1R3 1R5 C6 C7 C15

DURATION OVERLOAD
DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS
51.06
51.06 49.77 R1 2
57.5 49.77 R3 1
57.5 48.79
3-4 PM R5 1
57.5 46.43
2-3 PM C6 1
57.5 40.07
57.5 C7 1
40.07
57.5 40.07 C15 1
39.35
PEAK 57.5 TOTAL 7
AVE 44.29

TRANSFORMER 3:
57.5000
➢ Max demand:
➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 7.50
➢ Duration of Overload: 2 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 44.61
%Load: 89.22
❖ 24 hours:
Average: 33.85
%Load: 67.70

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 151
➢ Max overload for transformer 75.5
➢ Higher than max overload 57.50
DIVERSIFIED DEMAND OF T4
60
50
40
KVA

30
20
10
0

12:00 PM

10:00 PM

11:00 PM
7:00 AM

2:00 PM

9:00 PM
12:00 AM

1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

8:00 AM

9:00 AM

10:00 AM

11:00 AM

1:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM
TIME

3R1 3R2 1R4 1R5 C19

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

52.55 39.2 R1 3
52.55 35.6 R2 3
3:15-4:15 PM 1:15 PM
52.55 35.6 R4 1
52.55 35.16 R5 1
34.08 C19 1
PEAK 52.55 35.68
2:15 PM
35.68 TOTAL 9
44.38
AVE 36.9225

TRANSFORMER 4:

➢ Max demand 54.42

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 4.42
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 44.18
%Load: 88.36
❖ 24 hours:
Average: 40.87
%Load: 81.74

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 54.42
DIVERSIFIED DEMAND OF T5
60

50

40
KVA

30

20

10

9:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM
12:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

12:00 PM

10:00 PM

11:00 PM
TIME
4R2 2R3 1R4 2R5 R6 C4

DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS


DURATION OVERLOAD
38.115 R2 4
53.775 38.115 R3 2
10:00 AM
54.415 46.195 R4 1
12:00 PM
54.415 46.195 R5 2
54.415 46.195 R6 1
46.195 C4 1
11:00 AM
PEAK 54.415 46.195 TOTAL 11
46.195
AVE 44.175

TRANSFORMER 5:

➢ Max demand: 80.90

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 17.88
➢ Duration of Overload: 1.5 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 37.77
%Load: 75.54
❖ 24 hours:
Average: 36.83
%Load: 73.66

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 151
➢ Max overload for transformer 75.5
➢ Higher than max overload 67.88
DIVERSIFIED DEMAND OF T6
90
80
70
60
KVA

50
40
30
20
10
0

7:00 AM

12:00 PM

10:00 PM
11:00 PM
12:00 AM
1:00 AM
2:00 AM
3:00 AM
4:00 AM
5:00 AM
6:00 AM

8:00 AM
9:00 AM
10:00 AM
11:00 AM

1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
TIME

5R2 3R3 2R4 2R5 R6 C19

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

79.9 50.06 R2 5
79.9 50.06 R3 3
12:00 PM 10:00 AM
79.9 60.32 R4 2
79.9 60.32 R5 2
60.32 R6 1
PEAK 79.9 60.32 C4 1
11:00 AM
60.32 TOTAL 14
60.32
AVE 57.755

TRANSFORMER 6:

➢ Max demand: 79.90

➢ Transformer rating in kVA: 75

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 4.90
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 57.76
%Load: 77.01
❖ 24 hours:
Average: 55.04
%Load: 73.39

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 161
➢ Max overload for transformer 120.75
➢ Higher than max overload 79.90
DIVERSIFIED DEMAND OF T7
90

80

70

60

50
KVA

40

30

20

10

12:00 PM

10:00 PM
11:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
12:00 AM

10:00 AM
11:00 AM
1:00 AM
2:00 AM
3:00 AM
4:00 AM
5:00 AM
6:00 AM
7:00 AM
8:00 AM
9:00 AM
TIME
5R4 3R5 1R6 C5 C13 C19

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

75.405 51.265 R4 5
77.965 51.265 R5 3
12:00 PM 10:00 AM
77.965 51.265 R6 2
77.965 51.265 C5 1
51.265 C13 1
PEAK 77.965 51.265 C19
11:00 AM
51.265
51.265 TOTAL 12
AVE 51.265

TRANSFORMER 7:

➢ Max demand 77.97

➢ Transformer rating in kVA: 75

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 2.97
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 51.27
%Load: 68.36
❖ 24 hours:
Average: 50.95
%Load: 67.93

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 151
➢ Max overload for transformer 113.25
➢ Higher than max overload 77.97
DIVERSIFIED DEMAND OF T8
45
40
35
30
25
KVA

20
15
10
5
0

10:00 PM
12:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM

11:00 PM
1:00 AM

4:00 AM

7:00 AM

10:00 AM
12:00 AM

2:00 AM
3:00 AM

5:00 AM
6:00 AM

8:00 AM
9:00 AM

11:00 AM
TIME

3R1 2R2 2R4 R6

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

42.78 25.8 R1 3
42.78 25.8 R2 2
12:00 PM 10:00 AM
42.78 28.68 R4 2
42.78 28.68 R6 1
26.52
PEAK 42.78 26.52
11:00 AM
26.52
26.52 TOTAL 8
AVE 26.88

TRANSFORMER 8:

➢ Max demand 42.78

➢ Transformer rating in kVA: 37.5

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 5.28
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 26.88
%Load: 71.68
❖ 24 hours:
Average: 26.56
%Load: 70.83

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 161
➢ Max overload for transformer 60.375
➢ Higher than max overload 42.78
DIVERSIFIED DEMAND OF T9
100
90
80
70
60
KVA

50
40
30
20
10
0

12:00 PM

10:00 PM

11:00 PM
12:00 AM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
8:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

9:00 AM
TIME
3R1 2R2 3R4 2R5 C8 C14 C15

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

86.01 59.805 R1 3
86.01 59.805 R2 2
49 41
86.01 62.565 R4 3
86.01 62.565 R5 2
60.405 C8 1
PEAK 86.01 60.405 C14 1
45
60.405 C15 1
60.405 TOTAL 13
AVE 60.795

TRANSFORMER 9:

➢ Max demand 86.01

➢ Transformer rating in kVA: 75

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 11.01
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 60.80
%Load: 81.07
❖ 24 hours:
Average: 51.38
%Load: 68.51

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 161
➢ Max overload for transformer 120.75
➢ Higher than max overload 86.01
DIVERSIFIED DEMAND OF T10
90
80
70
60
KVA

50
40
30
20
10
0

12:00 PM

10:00 PM

11:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

8:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

9:00 AM
TIME
3R4 3R5 C5 C7 C10

DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS


DURATION OVERLOAD
58.48 R4 3
78.96 58.48 R5 3
10:00 AM
78.96 58.12 C5 1
12:00 PM
78.96 58.12 C7 1
78.96 57.22 C10 1
57.22
11:00 AM
PEAK 78.96 57.22
57.22 TOTAL 9
AVE 57.76

TRANSFORMER 10:

➢ Max demand 76.96

➢ Transformer rating in kVA: 75

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 3.96
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 57.76
%Load: 77.01
❖ 24 hours:
Average: 47.97
%Load: 63.96

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 120
➢ Higher than max overload 78.96
DIVERSIFIED DEMAND OF T11
90
80
70
60
KVA

50
40
30
20
10
0

12:00 PM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM

10:00 PM

11:00 PM
6:00 AM
12:00 AM

1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

7:00 AM

8:00 AM

9:00 AM

10:00 AM

11:00 AM
TIME
6R1 3R2 2R4 3R6

DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS


DURATION OVERLOAD
55.74 R1 6
81.72 55.74 R2 3
10:00 AM
81.72 59.88 R4 2
12:00 PM
81.72 59.88 R6 3
81.72 54.12
54.12
11:00 AM
PEAK 81.72 54.12
54.12 TOTAL 14
AVE 55.965

TRANSFORMER 11:

➢ Max demand 81.72

➢ Transformer rating in kVA: 75

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 6.72
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 55.97
%Load: 74.63
❖ 24 hours:
Average: 51.89
%Load: 69.19

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 120
➢ Higher than max overload 81.72
DIVERSIFIED DEMAND OF T12
60

50

40
KVA

30

20

10

12:00 PM

10:00 PM
11:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
12:00 AM

10:00 AM
11:00 AM
1:00 AM
2:00 AM
3:00 AM
4:00 AM
5:00 AM
6:00 AM
7:00 AM
8:00 AM
9:00 AM
TIME
5R1 3R2 2R4 1R6

DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS


DURATION OVERLOAD
35.4 R1 6
55.6 35.4 R2 3
10:00 AM
55.6 39.78 R4 2
12:00 PM
55.6 39.78 R6 3
55.6 36.18
36.18
11:00 AM
PEAK 55.6 36.18
36.18 TOTAL 14
AVE 36.885

TRANSFORMER 12:

➢ Max demand 55.60

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 5.60
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 36.89
%Load: 73.78
❖ 24 hours:
Average: 35.53
%Load: 71.06

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 80
➢ Higher than max overload 55.60
DIVERSIFIED DEMAND OF T13
90

80

70

60

50
KVA

40

30

20

10

12:00 PM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM

10:00 PM

11:00 PM
12:00 AM

1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

10:00 AM

11:00 AM
TIME
2R4 2R5 2R7 2R8 C23 C7 C13
DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

79.975 59.195 R4 2
80.895 59.195 R5 2
12:00 PM 10:00 AM
80.895 58.955 R7 2
80.895 58.955 R8 2
56.975 C23 1
PEAK 80.895 56.975 C7 1
11:00 AM
56.975 C13 1
56.975 TOTAL 11
AVE 58.025

TRANSFORMER 13:

➢ Max demand 80.90

➢ Transformer rating in kVA: 75

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 5.90
➢ Duration of Overload: 0.5 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 58.03
%Load: 77.37
❖ 24 hours:
Average: 54.75
%Load: 73.00

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 180
➢ Max overload for transformer 135
➢ Higher than max overload 80.90
DIVERSIFIED DEMAND OF T14
60

50

40
KVA

30

20

10

12:00 PM

10:00 PM

11:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

6:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

7:00 AM

8:00 AM

9:00 AM
TIME
1R6 2C5 C11 C22 C25

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

52.48 43.68 R6 1
53.12 43.68 C5 2
12:00 PM 10:00 AM
53.12 43.68 C11 1
53.12 43.68 C22 1
50.36 43.68 C25 1
50.36 43.68
1:00 PM 11:00 AM
43.68
43.68 TOTAL 6
AVE 43.68
PEAK 53.12

TRANSFORMER 14:

➢ Max demand 53.12

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 3.12
➢ Duration of Overload: 2 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 43.68
%Load: 87.36
❖ 24 hours:
Average: 35.21
%Load: 70.42

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 1.42
➢ Max overload for transformer 0.71
➢ Higher than max overload 53.12
DIVERSIFIED DEMAND OF T15
50
45
40
35
30
KVA

25
20
15
10
5
0

12:00 PM

10:00 PM
11:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
12:00 AM

4:00 AM

10:00 AM
11:00 AM
1:00 AM
2:00 AM
3:00 AM

5:00 AM
6:00 AM
7:00 AM
8:00 AM
9:00 AM
TIME
1R3 2R4 1R5 C1 C5

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

44.7 41 R3 1
46.32 42 R4 2
12:00 PM 10:00 AM
46.32 43 R5 1
46.32 44 C1 1
45 C5 1
PEAK 46.32 46
25.88
47
48 TOTAL 6
AVE 3.287083333

TRANSFORMER 15:

➢ Max demand 46.32

➢ Transformer rating in kVA: 37.5

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 8.82
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 25.65
%Load: 68.40
❖ 24 hours:
Average: 25.42
%Load: 67.79

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 60
➢ Higher than max overload 46.32
DIVERSIFIED DEMAND OF T16
60

50

40
KVA

30

20

10

12:00 PM

10:00 PM

11:00 PM
10:00 AM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

TIME
3R3 3R4 1R5

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

54.3 41 R3 3
54.3 42 R4 3
12:00 PM 10:00 AM
54.3 43 R5 1
54.3 44 C5 2
45 C9 1
PEAK 54.3 46
11:00 AM
47
48 TOTAL 10
AVE 0.109375

TRANSFORMER 16:

➢ Max demand 54.30

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 4.30
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 38.19
%Load: 76.38
❖ 24 hours:
Average: 34.78
%Load: 69.56

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 54.30
DIVERSIFIED DEMAND OF T17

60

50

40
KVA

30

20

10

8:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

9:00 PM
12:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

12:00 PM

10:00 PM

11:00 PM
TIME
2R1 R2 4R3 2R4 2R6

DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS


DURATION OVERLOAD
37.32 R1 2
54.74 37.32 R2 1
10:00 AM
56.02 42.98 R3 4
12:00 PM
56.02 42.98 R4 2
56.02 41.54 R6 2
41.54
11:00 AM
PEAK 56.02 41.54
41.54 TOTAL 11
AVE 40.845

TRANSFORMER 17:

➢ Max demand 56.02

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 6.02
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 40.85
%Load: 81.70
❖ 24 hours:
Average: 37.90
%Load: 75.80

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 56.02
DIVERSIFIED DEMAND OF T18
140

120

100

80
KVA

60

40

20

12:00 PM

10:00 PM

11:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

6:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

7:00 AM

8:00 AM

9:00 AM

TIME
1R4 1R5 2R6 C2 C5 C24 TOTAL

DURATION OVERLOAD

52.84
DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS
54.12
54.12 44.06 R4 1
12:00-1:30 PM
54.12 44.06 R5 1
10:00 AM
50.32 43.94 R6 2
50.32 43.94 C2 1
43.94 C5 1
0 43.94 C24
11:00 AM
43.94
PEAK 54.12 43.94 TOTAL 6
AVE 43.97

TRANSFORMER 18:

➢ Max demand 54.12

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 4.12
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 43.97
%Load: 87.94
❖ 24 hours:
Average: 32.06
%Load: 64.12

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 54.12
DIVERSIFIED DEMAND OF T19
45
40
35
30
KVA

25
20
15
10
5
0

12:00 PM

10:00 PM

11:00 PM
10:00 AM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

2:00 AM

11:00 AM
1:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM
TIME
2R3 1R4 2R5 C5 C6

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

38.49 28.395 R3 2
38.85 30.195 R4 1
8:00 AM 6:00 AM
39.56 30.195 R5 2
39.56 30.195 C5 1
26.825 C6 1
PEAK 39.56 28.26
7:00 AM
28.26
28.26 TOTAL 7
AVE 28.823125

TRANSFORMER 19:

➢ Max demand 39.56

➢ Transformer rating in kVA: 37.5

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 2.06
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 28.82
%Load: 76.85
❖ 24 hours:
Average: 26.36
%Load: 70.29

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 60
➢ Higher than max overload 39.56
DIVERSIFIED DEMAND OF T20
80
70
60
50
KVA

40
30
20
10
0

12:00 PM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM

10:00 PM

11:00 PM
12:00 AM

1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

10:00 AM

11:00 AM
TIME
5R1 3R2 4R3

DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS


DURATION OVERLOAD
37.9 R1 5
52.22 37.9 R2 3
10:00 AM
52.22 46.56 R3 4
12:00 PM
52.22 46.56
52.22 42.96
42.96
11:00 AM
PEAK 52.22 42.96
42.96 TOTAL 12
AVE 42.595

TRANSFORMER 20:

➢ Max demand 52.22

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 2.22
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 42.60
%Load: 85.20
❖ 24 hours:
Average: 37.85
%Load: 75.70

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 80
➢ Higher than max overload 52.22
DIVERSIFIED DEMAND OF T21
70
60
50
40
KVA

30

20
10
0

12:00 PM

10:00 PM

11:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

5:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM
TIME
4R2 2R3 1R4 2R5 C20

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

56.36 36.54 R2 4
56.36 36.54 R3 2
12:00 PM 10:00 AM
56.36 44.38 R4 1
56.36 44.38 R5 2
44.38 C20 1
44.38
11:00 AM
44.38
44.38 TOTAL 10
AVE 42.42
PEAK 56.36

TRANSFORMER 21:

➢ Max demand 56.36

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 6.36
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 42.42
%Load: 84.84
❖ 24 hours:
Average: 37.09
%Load: 74.18

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 80
➢ Higher than max overload 56.36
DIVERSIFIED DEMAND OF T22
70
60
50
KVA
40
30
20
10
0

12:00 PM

10:00 PM

11:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

2:00 AM

6:00 AM

10:00 AM

11:00 AM
1:00 AM

3:00 AM

4:00 AM

5:00 AM

7:00 AM

8:00 AM

9:00 AM
TIME
2R1 1R2 1R3 1R4 3R5 2R6
DURATION OVERLOAD
DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS
54
55.28 38.74 R1 2
12:00 PM
55.28 38.74 R2 1
10:00 AM
55.28 40.92 R3 1
40.92 R4 1
39.48 R5 3
39.48 R6 2
11:00 AM
39.48
39.48 TOTAL 10
PEAK 55.28 AVE 39.655

TRANSFORMER 22:

➢ Max demand 55.28

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 5.28
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 39.66
%Load: 79.32
❖ 24 hours:
Average: 35.41
%Load: 70.82

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 55.28
DIVERSIFIED DEMAND OF T23
70

60

50

40
KVA

30

20

10

0
12:00 AM

10:00 AM

11:00 AM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

12:00 PM

10:00 PM

11:00 PM
TIME
7R1 2R3 2R4

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

53.36 37.98 R1 7
53.36 37.98 R3 2
12:00 PM 10:00 AM
53.36 40.06 R4 2
53.36 40.06
35.02
35.02
11:00 AM
35.02
35.02 TOTAL 11
AVE 37.02
PEAK 53.36

TRANSFORMER 23:

➢ Max demand 53.36

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 3.36
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 37.02
%Load: 74.04
❖ 24 hours:
Average: 34.62
%Load: 69.24

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 80
➢ Higher than max overload 53.36
DIVERSIFIED DEMAND OF T24
70

60

50

40
KVA

30

20

10

12:00 PM

10:00 PM
11:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
12:00 AM

2:00 AM

7:00 AM

10:00 AM
11:00 AM
1:00 AM

3:00 AM
4:00 AM
5:00 AM
6:00 AM

8:00 AM
9:00 AM
TIME
4R4 2R6 C10

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

53.13 35.13 R4 4
54.41 35.13 R6 2
12:00 PM 11:00 AM
54.41 35.13 C10 1
54.41 35.13
35.13
35.13
12:00 PM
35.13
35.13 TOTAL 7
AVE 35.13
PEAK 54.41

TRANSFORMER 24:

➢ Max demand 54.41


➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 4.41
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 35.13
%Load: 70.26
❖ 24 hours:
Average: 31.92
%Load: 63.84

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 54.41
DIVERSIFIED DEMAND OF T26
70

60

50

40
KVA

30

20

10

12:00 PM

10:00 PM

11:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM
TIME
3R3 3R5 C17

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

39.86 29.72 R3 3
39.86 29.72 R5 3
12:00 PM 10:00 AM
39.86 32.48 C17 1
39.86 32.48
32.48
32.48
11:00 AM
32.48
32.48 TOTAL 7
AVE 31.79
PEAK 39.86

TRANSFORMER 26:

➢ Max demand 39.86

➢ Transformer rating in kVA: 37.5

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 2.36
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 31.79
%Load: 84.77
❖ 24 hours:
Average: 27.47
%Load: 73.25

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 60
➢ Higher than max overload 39.86
DIVERSIFIED DEMAND OF T25
70

60

50

40
KVA

30

20

10

0
12:00 AM
1:00 AM
2:00 AM
3:00 AM
4:00 AM
5:00 AM
6:00 AM
7:00 AM
8:00 AM
9:00 AM
10:00 AM
11:00 AM
12:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
10:00 PM
11:00 PM
TIME
1R2 2R4 1R5 C5 C21 C22
DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

57.44 41.72 R2 1
57.44 41.72 R4 2
12:00 PM 10:00 AM
57.44 43.1 R5 1
57.44 43.1 C5 1
43.96 C21 1
43.96 C22 1
11:00 AM
43.96
PEAK 57.44 43.96 TOTAL 7
AVE 43.185

TRANSFORMER 25:

➢ Max demand 57.44

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 7.44
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 43.19
%Load: 86.38
❖ 24 hours:
Average: 35.34
%Load: 70.68

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 80
➢ Higher than max overload 57.44
DIVERSIFIED DEMAND OF T27
90
80
70
60
KVA

50
40
30
20
10
0

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

12:00 PM

10:00 PM

11:00 PM
TIME
4R4 C24 C6 C16 C19 C22

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

79.3 54 53.64 R4 4
79.3 55 53.64 C24 1
3-4:15PM 79.3 56 53.64 C6 1
79.3 57 51.88 C16 1
75.3 58 51.88 C19 1
59 65.19 C22 1
60 65.19
61 71.13 TOTAL 9
AVE 58.27375
PEAK 79.3

TRANSFORMER 27:

➢ Max demand 79.80

➢ Transformer rating in kVA: 75

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 4.30
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 58.27
%Load: 77.69
❖ 24 hours:
Average: 43.84
%Load: 58.45

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 120
➢ Higher than max overload 79.30
DIVERSIFIED DEMAND OF T28
60

50

40
KVA

30

20

10

12:00 PM

10:00 PM

11:00 PM
11:00 AM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

10:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM
TIME
2R5 2R6 R7 C8 C9
DURATION OVERLOAD
DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS
50.49
50 50.49 49.405 R5 2
50.49 49.165 R6 2
42
49.165 R7 1
43.105 C8 1
43.105 C9 1
43.105
46
43.105
48.75 TOTAL 7
PEAK 50.49 AVE 46.113125

TRANSFORMER 28:

➢ Max demand 39.86

➢ Transformer rating in kVA: 37.5

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 2.36
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 31.79
%Load: 84.77
❖ 24 hours:
Average: 27.47
%Load: 73.25

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 160
➢ Max overload for transformer 60
➢ Higher than max overload 39.86
DIVERSIFIED DEMAND OF T29
60

50

40
KVA

30

20

10

12:00 PM

10:00 PM

11:00 PM
12:00 AM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM
TIME
4R1 2R2 2R3 2R4 1R7

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

53.94 36.44 R1 4
54.4 36.44 R2 2
12:00 PM 10:00 AM
54.4 41.52 R3 2
54.4 41.52 R4 2
38.1 R7 1
38.1
11:00 AM
38.1
38.1 TOTAL 11
AVE 38.54
PEAK 54.4

TRANSFORMER 29:

➢ Max demand 54.40

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 4.40
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 38.54
%Load: 77.08
❖ 24 hours:
Average: 37.61
%Load: 75.22

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 54.40
DIVERSIFIED DEMAND OF T30
90
80
70
60
KVA

50
40
30
20
10
0

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

10:00 AM

12:00 PM

10:00 PM

11:00 PM
TIME
8R1 2R2 3R3 2R4 1R5 1R6

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

82.1 58.52 R1 8
82.74 58.52 R2 2
10:00 AM
12:00 PM 82.74 64.52 R3 3
82.74 64.52 R4 2
58.76 R5 1
58.76 R6 1
11:00 AM
58.76
58.76 TOTAL 17
AVE 60.14
PEAK 82.74

TRANSFORMER 30:

➢ Max demand 82.74

➢ Transformer rating in kVA: 75

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 7.74
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 60.14
%Load: 80.19
❖ 24 hours:
Average: 55.04
%Load: 73.39

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 112.5
➢ Higher than max overload 82.74
DIVERSIFIED DEMAND OF T31
90
80
70
60
KVA

50
40
30
20
10
0

12:00 PM

10:00 PM

11:00 PM
12:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
TIME
R4 2R5 R6 R8 C24 C27

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

57 43.3 R4 1
57.64 43.3 R5 2
10:00 AM
57.64 43.06 R6 1
12-1-30 PM
57.64 43.06 R8 1
53.84 43.06 C24 1
53.84 43.06 C25 1
11:00 AM
43.06
43.06 TOTAL 7
AVE 43.12
PEAK 57.64

TRANSFORMER 31:

➢ Max demand 57.64

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 7.64
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 43.12
%Load: 86.24
❖ 24 hours:
Average: 37.08
%Load: 74.16

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 57.64
DIVERSIFIED DEMAND OF T32
50
45
40
35
30
KVA

25
20
15
10
5
0

6:00 AM
12:00 AM
1:00 AM
2:00 AM
3:00 AM
4:00 AM
5:00 AM

7:00 AM
8:00 AM
9:00 AM
10:00 AM
11:00 AM

11:00 PM
12:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
10:00 PM
TIME

2R4 R5 R6 C5 C21 C25


DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

47.5 31.16 R4 2
48.14 31.16 R5 1
10:00 AM
48.14 31.04 R6 1
49
48.14 31.04 C5 1
40.54 31.9 C24 1
40.54 31.9 C25 1
11:00 AM
31.9
31.9 TOTAL 7
AVE 31.5
PEAK 48.14

TRANSFORMER 32:

➢ Max demand 48.14

➢ Transformer rating in kVA: 37.5

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 10.64
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 31.50
%Load: 84.00
❖ 24 hours:
Average: 29.40
%Load: 78.40

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 56.25
➢ Higher than max overload 48.14
DIVERSIFIED DEMAND OF T33
90
80
70
60
50
KVA

40
30
20
10
0

12:00 PM

10:00 PM
11:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
12:00 AM

10:00 AM
11:00 AM
1:00 AM
2:00 AM
3:00 AM
4:00 AM
5:00 AM
6:00 AM
7:00 AM
8:00 AM
9:00 AM
TIME
3R4 C5 C7 C15

DURATION OVERLOAD
DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS
56.75
56.75 41.11 R4 3
12:00 PM
56.75 41.11 C5 1
10:00 AM
56.75 41.11 C7 1
41.11 C15 1
40.21
40.21
11:00 AM
40.21
40.21 TOTAL 6
PEAK 56.75 AVE 40.66

TRANSFORMER 33:

➢ Max demand 56.65

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 6.75
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 40.66
%Load: 81.32
❖ 24 hours:
Average: 33.29
%Load: 66.58

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 56.75
DIVERSIFIED DEMAND OF 34
90
80
70
60
KVA

50
40
30
20
10
0

12:00 PM

10:00 PM

11:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

7:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

8:00 AM

9:00 AM
TIME

2R2 R3 R4 2R5 R6 C7 C16 C22

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

78.13 64.79 R2 2
78.77 64.79 R3 1
12:00 PM 10:00 AM
78.77 68.59 R4 1
78.77 68.59 R5 2
67.69 R6 1
67.69 C7 1
11:00 AM
67.69 C16 1
67.69 C22 1
AVE 67.19
PEAK 78.77 TOTAL 10

TRANSFORMER 34:

➢ Max demand 78.77

➢ Transformer rating in kVA: 75

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 3.77
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 67.19
%Load: 89.59
❖ 24 hours:
Average: 50.25
%Load: 67.00

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 112.5
➢ Higher than max overload 78.77
DIVERSIFIED DEMAND OF 35
100
90
80
70
60
KVA

50
40
30
20
10
0
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

12:00 PM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM

10:00 PM

11:00 PM
12:00 AM

10:00 AM

11:00 AM
TIME
4R2 3R3 2R5 1R6 C10 C20 C25

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

80.85 61.47 R2 4
81.49 61.47 R3 3
10:00 AM
12:00-1:15 PM 81.49 70.35 R5 2
81.49 70.35 R6 1
76.45 70.35 C10 1
70.35 C20 1
11:00 AM
70.35 C25 1
70.35 TOTAL 13
AVE 68.13
PEAK 81.49

TRANSFORMER 35:

➢ Max demand 81.49

➢ Transformer rating in kVA: 75

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 6.49
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 68.13
%Load: 90.84
❖ 24 hours:
Average: 54.48
%Load: 72.64

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 112.5
➢ Higher than max overload 81.49
DIVERSIFIED DEMAND OF T36
60

50

40
KVA

30

20

10

12:00 PM

10:00 PM

11:00 PM
11:00 AM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

10:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM
TIME
2R1 2R2 R3 3R4 C18

DURATION OVERLOAD

51.16
DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS
51.16
12:00 PM
51.16 31 R1 2
51.16 31 R2 2
10:00 AM
35.04 R3 1
35.04 R4 3
33.6 C18 1
33.6
11:00 AM
33.6
PEAK 51.16 33.6 TOTAL 9
AVE 33.31

TRANSFORMER 36:

➢ Max demand 51.16

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 1.16
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 33.31
%Load: 66.62
❖ 24 hours:
Average: 34.74
%Load: 69.48

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 51.16
DIVERSIFIED DEMAND OF T37
60

50

40
KVA

30

20

10

12:00 PM

10:00 PM

11:00 PM
12:00 AM

10:00 AM

11:00 AM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM
TIME
3R1 3R2 3R3 2R4

DURATION OVERLOAD
DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS
53.92
53.92 32.98 R1 3
12:00 PM
53.92 32.98 R2 3
10:00 AM
53.92 40.6 R3 3
40.6 R4 2
38.44
38.44
11:00 AM
38.44
38.44 TOTAL 11
PEAK 53.92 AVE 37.615

TRANSFORMER 37:

➢ Max demand 53.92

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 3.92
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 37.62
%Load: 75.24
❖ 24 hours:
Average: 36.26
%Load: 72.52

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 53.92
DIVERSIFIED DEMAND OF T38
45
40
35
30
KVA

25
20
15
10
5
0

12:00 PM

10:00 PM

11:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

1:00 AM

10:00 AM

11:00 AM
2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM
TIME
3R1 2R2 1R3 2R5

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

39.3 27.94 R1 3
39.3 27.94 R2 2
12:00 PM 10:00 AM
39.3 31.74 R3 1
39.3 31.74 R5 2
29.58
29.58
11:00 AM
29.58
29.58 TOTAL 8
AVE 29.71
PEAK 39.3

TRANSFORMER 38:

➢ Max demand 39.30

➢ Transformer rating in kVA: 37.5

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 1.80
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 29.71
%Load: 79.23
❖ 24 hours:
Average: 26.30
%Load: 70.13

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 56.25
➢ Higher than max overload 39.30
DIVERSIFIED DEMAND OF T39
50
45
40
35
30
KVA

25
20
15
10
5
0

12:00 PM

10:00 PM

11:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 AM

8:00 AM

10:00 AM

11:00 AM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

9:00 AM
TIME
2R1 2R2 2R3 2R5

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

39.56 27.44 R1 2
39.56 27.44 R2 2
12:00 PM 10:00 AM
39.56 32.28 R3 2
39.56 32.28 R4 2
30.84
30.84
11:00 AM
30.84
30.84 TOTAL 8
AVE 30.35
PEAK 39.56

TRANSFORMER 39:

➢ Max demand 39.56

➢ Transformer rating in kVA: 37.5

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 2.06
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 30.35
%Load: 80.93
❖ 24 hours:
Average: 26.88
%Load: 71.68

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 56.25
➢ Higher than max overload 39.56
DIVERSIFIED DEMAND OF 40
50
45
40
35
30
KVA
25
20
15
10
5
0

12:00 PM

10:00 PM
11:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
12:00 AM

3:00 AM
4:00 AM
5:00 AM

10:00 AM
11:00 AM
1:00 AM
2:00 AM

6:00 AM
7:00 AM
8:00 AM
9:00 AM
TIME
5R1 1R2 3R3
DURATION
DURATION OVERLOAD 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

39.04 30.3 R1 5
39.04 30.3 R2 1
12:00 PM 10:00 AM
39.04 34.92 R3 3
39.04 34.92
31.32
31.32
11:00 AM
31.32
31.32 TOTAL 9
AVE 31.965
PEAK 39.04

TRANSFORMER 40:

➢ Max demand 39.04

➢ Transformer rating in kVA: 37.5

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 1.54
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 31.97
%Load: 85.25
❖ 24 hours:
Average: 27.95
%Load: 74.53

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 56.25
➢ Higher than max overload 39.04
DIVERSIFIED DEMAND OF T41
70
60
50
KVA

40
30
20
10
0

12:00 PM

10:00 PM
11:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
12:00 AM

10:00 AM
11:00 AM
1:00 AM
2:00 AM
3:00 AM
4:00 AM
5:00 AM
6:00 AM
7:00 AM
8:00 AM
9:00 AM
TIME
4R1 3R2 2R4 R6 R8
DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

60.9 36.32 R1 4
61.54 36.32 R2 3
12:00 PM 10:00 AM
61.54 40.82 R4 2
61.54 40.82 R6 1
37.94 R8 1
37.94
11:00 AM
37.94
37.94 TOTAL 11
AVE 38.255
PEAK 61.54

TRANSFORMER 41:

➢ Max demand 61.54

➢ Transformer rating in kVA: 50

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 11.54
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 38.26
%Load: 76.52
❖ 24 hours:
Average: 39.43
%Load: 78.86

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 75
➢ Higher than max overload 61.54
DIVERSIFIED DEMAND OF T42
350
300
250
KVA

200
150
100
50
0

12:00 PM

10:00 PM
11:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
12:00 AM

2:00 AM

6:00 AM

10:00 AM
11:00 AM
1:00 AM

3:00 AM
4:00 AM
5:00 AM

7:00 AM
8:00 AM
9:00 AM
TIME
C26
DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

110.0466667 82.16833333
110.0466667 82.16833333 C26 1
11:00 AM
1:00-2:15 110.0466667 82.26
110.0466667 82.26
110.0466667 82.26
83.57333333
12:00 PM
PEAK 110.0466667 83.57333333
83.57333333 TOTAL 1
AVE 82.72958333

TRANSFORMER 42:

➢ Max demand 110.05

➢ Transformer rating in kVA: 100

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 10.05
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 82.73
%Load: 82.73
❖ 24 hours:
Average: 62.05
%Load: 62.05

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 150
➢ Higher than max overload 110.05
DIVERSIFIED DEMAND OF T43
70
60
50
KVA

40
30
20
10
0

5:00 PM
1:00 PM

2:00 PM

3:00 PM

4:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM
12:00 PM

10:00 PM

11:00 PM
1:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM
12:00 AM

10:00 AM

11:00 AM
TIME
C3

DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS


DURATION OVERLOAD
11.54
16.57333333 11.54
9:00 AM C3 1
16.57333333 11.54
10:45-12:00pm 16.57333333 11.54
16.57333333 11.54
16.57333333 11.54
10:00 AM
11.54
PEAK 16.57333333 11.54 TOTAL 1
AVE 11.54

TRANSFORMER 43:

➢ Max demand 16.57

➢ Transformer rating in kVA: 15

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 1.57
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 11.54
%Load: 76.93
❖ 24 hours:
Average: 10.69
%Load: 71.27

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 22.5
➢ Higher than max overload 16.57
DIVERSIFIED DEMAND OF T44
400
350
300
250
KVA

200
150
100
50
0

12:00 PM

1:00 PM

2:00 PM

3:00 PM

4:00 PM

5:00 PM

6:00 PM

7:00 PM

8:00 PM

9:00 PM

10:00 PM

11:00 PM
1:00 AM
12:00 AM

2:00 AM

3:00 AM

4:00 AM

5:00 AM

6:00 AM

7:00 AM

8:00 AM

9:00 AM

10:00 AM

11:00 AM
TIME
INDUSTRIAL1

DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD


ESTABLISHMENT NO OF LOADS
108.2466667 85.94333333
108.2466667 85.94333333
108.2466667 85.94333333
INDUSTRIAL1 1
12:45-1:30 pm 108.2466667 85.94333333
10:45-12:45
111.25 85.94333333
111.25 89.51833333
111.25 89.51833333
89.51833333
PEAK 111.25 AVE 87.28395833 TOTAL 1

TRANSFORMER 44:

➢ Max demand 111.25

➢ Transformer rating in kVA: 100

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 11.25
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 87.28
%Load: 87.28
❖ 24 hours:
Average: 65.76
%Load: 65.76

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 150
➢ Higher than max overload 111.25
DIVERSIFIED DEMAND OF T45
350
300
250
KVA

200
150
100
50
0

12:00 PM

10:00 PM
11:00 PM
1:00 PM
2:00 PM
3:00 PM
4:00 PM
5:00 PM
6:00 PM
7:00 PM
8:00 PM
9:00 PM
10:00 AM
12:00 AM
1:00 AM
2:00 AM
3:00 AM
4:00 AM
5:00 AM
6:00 AM
7:00 AM
8:00 AM
9:00 AM

11:00 AM
TIME
INDUSTRIAL1
DURATION OVERLOAD DURATION 2 HOURS BEFOREOVERLOAD ESTABLISHMENT NO OF LOADS

109.1833333 71.56
109.1833333 71.56
INDUSTRIAL2 1
109.1833333 71.56
11-Oct
104.52 85.57333333
19-Sep
104.52 85.57333333
104.52 85.57333333
85.57333333
85.57333333 TOTAL 1
AVE 80.31833333
PEAK 109.1833333

TRANSFORMER 45:

➢ Max demand 109.18

➢ Transformer rating in kVA: 100

➢ Calculation for the Permissible


Overload
➢ kVA Overload: 9.18
➢ Duration of Overload: 1 hours

➢ Average overload (KVA)


❖ 2 hours before:
Average: 80.32
%Load: 80.32
❖ 24 hours:
Average: 60.05
%Load: 60.05

➢ Use the 70% curve initial load


➢ Permissible overload in percent: 150
➢ Max overload for transformer 150
➢ Higher than max overload 109.18
CONDUCTOR SIZING, VOLTAGE
DROP CALCULATION, AND
RATING OF DISCONNECTS
(FOR THE PURPOSE OF CALCULATION, THE “HAWK CONDUCTOR
R = 0.2120 Ω/mi, GMR = 0.0289 Ω/mi all throughout the report
CONDUCTOR SIZING, VOLTAGE DROP CALCULATION,
AND RATING OF DISCONNECTS

PHASE A

Vo = 7620 V
N1 56.17 m N0

10A
Vo = 7620 V
10A, RATED 15 KV 41.25 m N2
N0
VHTR4= 7442.3163 V
Tr4= 50 KVA 15A
VLOWTR4= 234.4037 V 15A, RATED 15 KV

N5 91.67m VHTR29= 7469.7687 V


15A, RATED 15 KV Tr29=75 KVA
VHTR8= 7419.2314 V 10A
Vo = 7620 V VLOWTR29= 235.2683 V
Tr8=75 KVA
N4 56.94 m N3 35 m N0

20 A 20A
20A, RATED 15 KV 20A, RATED 15 KV

VLOWTR8= 233.6766 V VHTR6= 7468.2688 V VHTR5= 7468.2688 V


Tr6= 50 KVA Tr5= 50 KVA
VLOWTR6= 235.2211 V VLOWTR5=235.2211 V

N0 25.10 m N6
10A, RATED 15 KV
VHTR35= 7451.818 V
10 A
Tr35= 50 KVA
N7 48.14 m N0 VLOWTR35=234.7029 V
10A, RATED 15 KV
VHTR13= 7455.3011 V 10A
Tr13= 50 KVA
VLOWTR13= 234.8126 V

21.05 N0
N8
10A, RATED 15 KV
VHTR27= 7449.9369V 58.22 m N9 59.80 m N10 64.23 m N11
10A
Tr27= 50 KVA

VLOWTR27= 234.6437 V

10A 10A 10A


10A, RATED 15 KV
10A, RATED 15 KV 10A, RATED 15 KV VHTR25= 7461.873 V

VHTR23= 7457.3587 V VHTR24= 7457.3587 V


Tr25= 50 KVA
Tr23= 50 KVA Tr24= 50 KVA
VLOWTR25= 235.0196 V
VLOWTR23= 234.8774 V VLOWTR24= 234.8268 V
PHASE A

ASSUME THAT THE POWER FACTOR OF THE LOADS IS 0.9 LAGGING.


Z = 0.2120 + j0.6041 Ω/mi (ACSR ‘Hawk’: R = 0.2120 Ω/mi, GMR = 0.0289 ft. 4.2’
spacing) REFERENCE:

RATING OF THE TRANSFORMERS ARE:


TR4 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR29 = 75 KVA, 7620-240 V, Z = 17.3115∠59.0362°
TR5 = 50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR6 = 75 KVA, 7620-240 V, Z = 17.3115∠59.0362°
TR8 = 37.5 KVA, 7620-240 V, Z = 45.9586∠64.359°
TR35 = 50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR13 = 50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR27 = 50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR23 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR24 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR25 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°

CURRENT THROUGH N₀ - N₁ :TR4


LINE VOLTAGE, V₀ = 7620
P₀₁ = 60KVA
S₀₁ = KW + j KVAR = 54+26.1534i
I₀₁ = [S₀₁/V₀] *= 7.874∠-25.8419°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₀ - N₁)
Z₀₁ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0075+0.0213i
Vn₁ = V₀ - I₀₁*Z₀₁ = 7619.874∠-0.0009°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr1 = [Str1/Vn₁]* = 7.8741∠-25.8429°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr1 = Zbase*Zpu = 27.0857∠59.0362°
7442.3163∠-
Vtr1 (high side) = Vn₁ - Itr1 * Ztr1 =
0.8999°
Vtr1 (low side) = Vtr1(high side) / Turns ratio = 234.4037∠-0.8999°
VOLTAGE DROP THROUGH N₀ - N₁ :
%Vdrop = [(V₀ - Vtr1)/ V₀ ] *100 = 2.8012%
CURRENT THROUGH N1 - N2 :TR29
LINE VOLTAGE, V₀ = 7620
P₀₂ = 79.3KVA
S₀2 = KW + j KVAR = 71.37+34.5661i
I₀₂ = [S₀₂/V₀]* = 10.4068∠-25.8419°
VOLTAGE AT N₂ :
LINE IMPREDANCE (N₀ - N₂)
Z₀₂ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0054+0.0155i
7619.8789∠-
Vn₂ = V₀ - I₀₂*Z₀₂ =
0.0009°
VOLTAGE AT Tr29 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr29 = [Str29/Vn₂]* = 10.407∠-25.8428°
Zbase = (1000*KV^2)/KVA = 774.192Ω
Zpu = 0.0224∠63.4349°
Ztr29 = Zbase*Zpu = 17.3115∠59.0362°
7469.7687∠-
Vtr29 (high side) = Vn₂ - Itr29 * Ztr29 =
0.7575°
Vtr29 (low side) = Vtr29(high side) / Turns ratio = 235.2683∠-0.7575°
VOLTAGE DROP THROUGH N₀ - N₂ :
%Vdrop = [(V₀ - Vtr29)/ V₀ ] *100 = 2.3665%

CURRENT THROUGH N₀ - N₃ :TR5


LINE VOLTAGE, V₀ =
P₀₃ = 180.18KVA
S₀2 = KW + j KVAR = 162.162+78.5386i
I₀₃ = [S₀₃/V₀]* = 23.6457∠-25.8419°
VOLTAGE AT N₃ :
LINE IMPREDANCE (N₀ - N₃)
Z₀₃ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0046+0.0131i
7619.7665∠-
Vn₃ = V₀ - I₀₃*Z₀₃ =
0.0017°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr1 = [Str1/Vn₃]* = 7.5462∠-25.8437°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr5 = Zbase*Zpu = 27.0857∠59.0362°
7449.5672∠-
Vtr51(high side) = Vn₃ - Itr5 * Ztr5 =
0.8624°
Vtr1 (low side) = Vtr1(high side) / Turns ratio = 234.632∠-0.8624°
VOLTAGE DROP THROUGH N₀ - N₃ :
%Vdrop = [(V₀ - Vtr1)/ V₀ ] *100 = 2.6866%
CURRENT THROUGH N3 - N₄ :TR6
LINE VOLTAGE, V₀ = 7620
P₀₄ = 122.68KVA
S₀₄ = KW + j KVAR = 110.412+53.475i
16.1002∠-
I₀₄ = [S₀₄/V₀]* =
25.8437°
VOLTAGE AT N₄ :
LINE IMPREDANCE (N₀ - N₄)
Z₀₄ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] =
7619.5078∠-
Vn₄ = V₀ - I₀₄*Z₀₄ =
0.0019°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
10.4862∠-
Itr6 = [Str6/Vn₄]* =
25.8439°
Zbase = (1000*KV^2)/KVA = Ω
Zpu = 0.0224∠63.4349°
Ztr6 = Zbase*Zpu = 17.3104∠59.0362°
7468.2688∠-
Vtr6 (high side) = Vn₄ - Itr6 * Ztr6 =
0.7644°
235.2211∠-
Vtr6 (low side) = Vtr6(high side) / Turns ratio =
0.7644°
VOLTAGE DROP THROUGH N₀ - N₄ :
%Vdrop = [(V₀ - Vtr6)/ V₀ ] *100 = 2.3853%

CURRENT THROUGH N4 - N₅ :TR8


LINE VOLTAGE, V₀ = 7619.507767
P₀₅ = 42.78KVA
S₀₅ = KW + j KVAR = 38.502+18.6474i
I₀₅ = [S₀₅/V₀]* = 5.6145∠-25.8439°
VOLTAGE AT N₅ :
LINE IMPREDANCE (N₀ - N₅)
Z₀₅ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] =
7619.3625∠-
Vn₅ = V₀ - I₀₅*Z₀₅ =
0.0011°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr1 = [Str1/Vn₅] = 5.6146∠-25.843°
Zbase = (1000*KV^2)/KVA = Ω
Zpu = 0.0297∠57.3808°
Ztr1 = Zbase*Zpu = 45.9526∠64.359°
7419.2314∠-
Vtr1 (high side) = Vn₅ - Itr1 * Ztr1 =
1.242°
Vtr1 (low side) = Vtr1(high side) / Turns ratio = 233.6766∠-1.242°
VOLTAGE DROP THROUGH N₀ - N₅ :
%Vdrop = [(V₀ - Vtr1)/ V₀ ] *100 = 3.3867%
CURRENT THROUGH N₀ - N₆ :TR35
LINE VOLTAGE, V₀ = 7620
P₀₆ = 56.75KVA
S₀₆ = KW + j KVAR = 51.075+24.7368i
I₀₆ = [S₀₆/V₀]* = 7.4475∠-25.8419°
VOLTAGE AT N₆ :
LINE IMPREDANCE (N₀ - N₆)
Z₀₆ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0121+0.0344i
7619.8073∠-
Vn₆ = V₀ - I₀₆*Z₀₆ =
0.0014°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr1 = [Str1/Vn₆] = 7.4477∠-25.8434°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr1 = Zbase*Zpu = 27.0857∠59.0362°
Vtr1 (high side) = Vn₆ - Itr1 * Ztr1 = 7451.818∠-0.8506°
Vtr1 (low side) = Vtr1(high side) / Turns ratio = 234.7029∠-0.8506°
VOLTAGE DROP THROUGH N₀ - N₆ :
%Vdrop = [(V₀ - Vtr1)/ V₀ ] *100 = 2.6508%

CURRENT THROUGH N₀ - N7 :
LINE VOLTAGE, V₀ = 7620
P₀7= 55.6KVA
S₀7 = KW + j KVAR = 50.04+24.2355i
I₀7 = [S₀7 V₀] = 7.2966∠-25.8419°
VOLTAGE AT N3 :
LINE IMPREDANCE (N₀ - N7)
Z₀7 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0063+0.0181i
7619.9009∠-
Vn7 = V₀ - I₀7*Z₀7 =
0.0007°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr13 = [Str7/Vn7] = 7.2967∠-25.8427°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr13= Zbase*Zpu = 27.0857∠59.0362°
7455.3011∠-
Vtr7 (high side) = Vn7 - Itr13 * Ztr13=
0.8323°
Vtr13 (low side) = Vtr7 (high side) / Turns ratio = 234.8126∠-0.8323°
VOLTAGE DROP THROUGH N₀ - N7 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.5954%
CURRENT THROUGH N₀ - N8 :
LINE VOLTAGE, V₀ = 7620
P₀8 = 57.44KVA
S₀8 = KW + j KVAR = 51.696+25.0375i
I₀8 = [S₀8/V₀] = 7.5381∠-25.8419°
VOLTAGE AT N8 :
LINE IMPREDANCE (N₀ - N8)
Z₀8 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0028+0.0079i
7619.9552∠-
Vn8 = V₀ - I₀8*Z₀8 =
0.0003°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr27= [Str27/Vn8] = 7.5381∠-25.8423°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr27 = Zbase*Zpu = 27.0857∠59.0362°
7449.9369∠-
Vtr27(high side) = Vn8 - Itr27 * Ztr27 =
0.8601°
Vtr8 (low side) = Vtr8(high side) / Turns ratio = 234.6437∠-0.8601°
VOLTAGE DROP THROUGH N₀ - N8 :
%Vdrop = [(V₀ - Vtr27)/ V₀ ] *100 = 2.6803%

CURRENT THROUGH N₀ - N9 :
LINE VOLTAGE, V₀ = 7620
P₀9 = 165KVA
S₀9 = KW + j KVAR = 148.5+71.9218i
I₀9 = [S₀9/V₀] = 21.6535∠-25.8419°
VOLTAGE AT N9 :
LINE IMPREDANCE (N₀ - N9)
Z₀9 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0077+0.0219i
Vn9 = V₀ - I₀9*Z₀9 = 7619.6443∠-0.0027°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr23 = [Str9/Vn9] = 7.3967∠-25.8446°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr23 = Zbase*Zpu = 27.0857∠59.0362°
Vtr23 (high side) = Vn23 - Itr9 * Ztr23 = 7452.8001∠-0.8459°
Vtr9 (low side) = Vtr9(high side) / Turns ratio = 234.7339∠-0.8459°
VOLTAGE DROP THROUGH N₀ - N9 :
%Vdrop = [(V₀ - Vtr23)/ V₀ ] *100 = 2.6356%
CURRENT THROUGH N9 – N10 :
LINE VOLTAGE, V₀ = 7619.644262
P₀10 = 108.64KVA
S₀10 = KW + j KVAR = 97.776+47.3551i
I₀10 = [S₀9/V₀] = 14.2579∠-25.8446°
VOLTAGE AT N10 :
LINE IMPREDANCE (N9 - N10)
Z₀10 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] =
Vn10= V₀ - I₀10*Z₀10 = 7619.4037∠-0.0018°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr24 = [Str24/Vn10] = 7.2552∠-25.8437°
Zbase = (1000*KV^2)/KVA = Ω
Zpu = 0.0233∠59.0362°
Ztr24 = Zbase*Zpu = 27.0831∠59.0362°
Vtr24 (high side) = Vn10 - Itr24 * Ztr24- = 7455.7512∠-0.8285°
Vtr24 (low side) = Vtr10(high side) / Turns ratio = 234.8268∠-0.8285°
VOLTAGE DROP THROUGH N9 - N10 :
%Vdrop = [(V₀ - Vtr24)/ V₀ ] *100 = 2.5806%

CURRENT THROUGH N10 – N11 :


LINE VOLTAGE, V₀ = 7619.403656
P₀11 = 53.36KVA
S₀11 = KW + j KVAR = 48.024+23.2591i
I₀11 = [S₀11/V₀] = 7.0032∠-25.8437°
VOLTAGE AT N11 :
LINE IMPREDANCE (N10 – N11)
Z₀11 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] =
Vn11= V₀ - I₀11*Z₀11 = 7619.2767∠-0.0009°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr25 = [Str25/Vn11] = 7.0033∠-25.8429°
Zbase = (1000*KV^2)/KVA = Ω
Zpu = 0.0233∠59.0362°
Ztr25= Zbase*Zpu = 27.0814∠59.0362°
Vtr25 (high side) = Vn11 - Itr15 * Ztr25- = 7461.2891∠-0.7983°
Vtr25 (low side) = Vtr11(high side) / Turns ratio = 235.0012∠-0.7983°
VOLTAGE DROP THROUGH N10 – N11 :
%Vdrop = [(V₀ - Vtr25)/ V₀ ] *100 = 2.4897%
CONDUCTOR SIZING, VOLTAGE DROP CALCULATION,
AND RATING OF DISCONNECTS

PHASE B

Vo = 7620 V
N14 84.31 m N13 78.30 m N12 46.38 m N0
15A, RATED 15 KV
VHTR3= 7469.7687 V 10A 10A 20A
Tr3=75 KVA 10A, RATED 15 KV 20A, RATED 15 KV
VLOWTR3= 235.2683 V VHTR2= 7457.3587 V VHT1= V
Tr2= 50 KVA Tr1= 50 KVA
VLOWTR2= 234.8774 V VLOWTR=235.0371 V

N15 N0
15A, RATED 15 KV
VHTR7= 7469.7687 V
34.90m N16
Tr7=75 KVA
15A, RATED 15 KV
VLOWTR7= 235.2683 V
15A VHTR34= 7469.7687 V

N17 Tr34=75 KVA


VLOWTR34= 235.2683 V
10A, RATED 15 KV
VHTR10= 7457.3587 V
Tr10= 50 KVA
VLOWTR5=234.632 V

74.56 m N18
10A, RATED 15 KV
VHTR38= 7442.3163 V
15A
Tr38= 50 KVA
N0 VLOWTR38= 234.4037 V
N19 52.26 m
10A, RATED 15 KV
VHTR40= 7442.3163 V 10A
Tr40= 50 KVA
VLOWTR40= 234.4037 V

92.74 m N0
N20
10A, RATED 15 KV
VHTR43= 7457.3587 V 10A
Tr43= 50 KVA
VLOWTR43= 234.8774 V
N0 32.15 m N21 53.07 m N22

10A 10A
10A, RATED 15 KV 10A, RATED 15 KV
VHTR30= 7457.3587 V VHTR28= 7457.3587 V
Tr30= 50 KVA Tr28= 50 KVA
VLOWTR30= 234.8774 V
VLOWTR28= 234.8774 V
PHASE B
ASSUME THAT THE POWER FACTOR OF THE LOADS IS 0.9 LAGGING.
Z = 0.2120 + j0.6041 Ω/mi (ACSR ‘Hawk’: R = 0.2120 Ω/mi, GMR = 0.0289 ft. 4.2’
spacing) REFERENCE:

RATING OF THE TRANSFORMERS ARE:


TR1 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR2 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR3 = 50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR7 = 75 KVA, 7620-240 V, Z = 17.3115∠59.0362°
TR34 = 37.5 KVA, 7620-240 V, Z = 45.9586∠64.359°
TR10 =75 KVA, 7620-240 V, Z = 17.3115∠59.0362°
TR38 =75 KVA, 7620-240 V, Z = 17.3115∠59.0362°
TR40 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR43 = 37.5 KVA, 7620-240 V, Z = 45.9586∠64.359°
TR30 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR28 =37.5 KVA, 7620-240 V, Z = 45.9586∠64.359°
REFERENCE: NEMA STANDARD

CURRENT THROUGH N₀ - N₁₂ :


LINE VOLTAGE, V₀ =
P₀₁₂ = 7620
S₁₂ = KW + j KVAR = 160.09KVA
I₀₁₂ = [S₀₁₂/V₀]* = 144.081+69.7816i
VOLTAGE AT N₁₂ : 21.0092∠-25.8419°
LINE IMPREDANCE (N₀ - N₁₂)
Z₀₁₂ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] =
Vn₁₂ = V₀ - I₀₁₂*Z₀₁₂ = 0.0061+0.0174i
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE): 7619.725∠-0.0021°
Itr1 = [Str1/Vn₁₂] =
Zbase = (1000*KV^2)/KVA = 6.9714∠-25.844°
Zpu = 1161.288Ω
Ztr1 = Zbase*Zpu = 0.0233∠59.0362°
Vtr1 (high side) = Vn₁₂ - Itr1 * Ztr1 = 27.0857∠59.0362°
Vtr1 (low side) = Vtr1(high side) / Turns ratio = 7462.4293∠-0.7958°
VOLTAGE DROP THROUGH N₀ - N₁₂ : 235.0371∠-0.7958°
%Vdrop = [(V₀ - Vtr1)/ V₀ ] *100 =
CURRENT THROUGH N₁₂ - N₁₃ :
LINE VOLTAGE, V₀ = 7619.725039
P₁₃= 106.97KVA
S₁₃= KW + j KVAR = 96.273+46.6271i
I₁₃= [S₁₂₁/V₀]* = 14.0386∠-25.844°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₁₂ - N₁)
Z₁₃= [(0.2120 + j0.6041)(DISTANCE/1609.34)] =
Vn₁ = V₁₂ - I₁₂₁*Z₁₃= 7619.4148∠-0.0023°
VOLTAGE AT Tr2 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr2 = [Str2/Vn₁] = 6.8969∠-25.8443°
Zbase = (1000*KV^2)/KVA = Ω
Zpu = 0.0233∠59.0362°
Ztr2 = Zbase*Zpu = 27.0837∠59.0362°
Vtr2 (high side) = Vn₁ - Itr2 * Ztr2 = 7463.8041∠-0.7874°
Vtr2 (low side) = Vtr2(high side) / Turns ratio = 235.0804∠-0.7874°
VOLTAGE DROP THROUGH N₁₂ - N₁ :
%Vdrop = [(V₁₂ - Vtr2)/ V₁₂ ] *100 = 2.4551%

CURRENT THROUGH N13 – N14:


LINE VOLTAGE, V₀ = 7619.309019
P₀11 = 54.42KVA
S₀11 = KW + j KVAR = 48.978+23.7211i
I₀11 = [S₀11/V₀]* = 7.1424∠-25.8443°
VOLTAGE AT N11 :
LINE IMPREDANCE (N10 – N11)
Z₀11 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] =
Vn11= V₀ - I₀11*Z₀11 = 7619.1391∠-0.0013°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr11 = [Str11/Vn11] = 7.1425∠-25.8432°
Zbase = (1000*KV^2)/KVA = Ω
Zpu = 0.0233∠59.0362°
Ztr4= Zbase*Zpu = 27.0807∠59.0362°
Vtr4 (high side) = Vn4 - Itr4 * Ztr4- = 7458.029∠-0.8148°
Vtr4 (low side) = Vtr4(high side) / Turns ratio = 234.8986∠-0.8148°
VOLTAGE DROP THROUGH N10 – N11 :
%Vdrop = [(V₀ - Vtr11)/ V₀ ] *100 = 2.5395%
CURRENT THROUGH N14 – N15:
LINE VOLTAGE, V₀ = 7620
P₀11 = 77.97KVA
S₀11 = KW + j KVAR = 70.173+33.9863i
I₀11 = [S₀11/V₀] = 10.2323∠-25.8419°
VOLTAGE AT N11 :
LINE IMPREDANCE (N10 – N11)
Z₀11 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.005+0.0142i
Vn11= V₀ - I₀11*Z₀11 = 7619.8905∠-0.0008°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr11 = [Str11/Vn11] = 10.2324∠-25.8428°
Zbase = (1000*KV^2)/KVA = 774.192Ω
Zpu = 0.0224∠63.4349°
Ztr4= Zbase*Zpu = 17.3115∠59.0362°
Vtr4 (high side) = Vn4 - Itr4 * Ztr4- = 7472.2872∠-0.7445°
Vtr4 (low side) = Vtr4(high side) / Turns ratio = 235.3476∠-0.7445°
VOLTAGE DROP THROUGH N10 – N11 :
%Vdrop = [(V₀ - Vtr11)/ V₀ ] *100 = 2.3266%
CURRENT THROUGH N15 – N16:
LINE VOLTAGE, V₀ = 7620
P₀11 = 48.14KVA
S₀11 = KW + j KVAR = 43.326+20.9837i
I₀11 = [S₀11/V₀] = 6.3176∠-25.8419°
VOLTAGE AT N11 :
LINE IMPREDANCE (N10 – N11)
Z₀11 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0046+0.0131i
Vn11= V₀ - I₀11*Z₀11 = 7619.9378∠-0.0005°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr11 = [Str11/Vn11] = 6.3176∠-25.8424°
Zbase = (1000*KV^2)/KVA = 1548.384Ω
Zpu = 0.0297∠57.3808°
Ztr4= Zbase*Zpu = 45.9586∠64.359°
Vtr4 (high side) = Vn4 - Itr4 * Ztr4- = 7394.9725∠-1.4015°
Vtr4 (low side) = Vtr4(high side) / Turns ratio = 232.9125∠-1.4015°
VOLTAGE DROP THROUGH N10 – N11 :
%Vdrop = [(V₀ - Vtr11)/ V₀ ] *100 = 3.8115%

CURRENT THROUGH N16 – N17:


LINE VOLTAGE, V₀ = 7620
P₀11 = 86.01KVA
S₀11 = KW + j KVAR = 77.409+37.4909i
I₀11 = [S₀11/V₀] = 11.2874∠-25.8419°
VOLTAGE AT N11 :
LINE IMPREDANCE (N10 – N11)
Z₀11 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0025+0.007i
Vn11= V₀ - I₀11*Z₀11 = 7619.9402∠-0.0004°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr11 = [Str11/Vn11] = 11.2875∠-25.8424°
Zbase = (1000*KV^2)/KVA = 774.192Ω
Zpu = 0.0224∠63.4349°
Ztr4= Zbase*Zpu = 17.3115∠59.0362°
Vtr4 (high side) = Vn4 - Itr4 * Ztr4- = 7457.1908∠-0.8224°
Vtr4 (low side) = Vtr4(high side) / Turns ratio = 234.8722∠-0.8224°
VOLTAGE DROP THROUGH N10 – N11 :
%Vdrop = [(V₀ - Vtr11)/ V₀ ] *100 = 2.5654%
CURRENT THROUGH N17 – N18:
LINE VOLTAGE, V₀ = 7620
P₀11 = 81.49KVA
S₀11 = KW + j KVAR = 73.341+35.5207i
I₀11 = [S₀11/V₀] = 10.6942∠-25.8419°
VOLTAGE AT N11 :
LINE IMPREDANCE (N10 – N11)
Z₀11 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0098+0.028i
Vn11= V₀ - I₀11*Z₀11 = 7619.775∠-0.0017°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr11 = [Str11/Vn11] = 10.6945∠-25.8436°
Zbase = (1000*KV^2)/KVA = 774.192Ω
Zpu = 0.0224∠63.4349°
Ztr4= Zbase*Zpu = 17.3115∠59.0362°
Vtr4 (high side) = Vn4 - Itr4 * Ztr4- = 7465.5361∠-0.7796°
Vtr4 (low side) = Vtr4(high side) / Turns ratio = 235.135∠-0.7796°
VOLTAGE DROP THROUGH N10 – N11 :
%Vdrop = [(V₀ - Vtr11)/ V₀ ] *100 = 2.4337%

CURRENT THROUGH N18 – N19:


LINE VOLTAGE, V₀ = 7620
P₀11 = 53.92KVA
S₀11 = KW + j KVAR = 48.528+23.5032i
I₀11 = [S₀11/V₀]* = 7.0761∠-25.8419°
VOLTAGE AT N11 :
LINE IMPREDANCE (N10 – N11)
Z₀11 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0069+0.0196i
Vn11= V₀ - I₀11*Z₀11 = 7619.8956∠-0.0008°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr11 = [Str11/Vn11] = 7.0762∠-25.8427°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr4= Zbase*Zpu = 27.0857∠59.0362°
Vtr4 (high side) = Vn4 - Itr4 * Ztr4- = 7460.2457∠-0.8067°
Vtr4 (low side) = Vtr4(high side) / Turns ratio = 234.9684∠-0.8067°
VOLTAGE DROP THROUGH N10 – N11 :
%Vdrop = [(V₀ - Vtr11)/ V₀ ] *100 = 2.5172%
CURRENT THROUGH N19 – N20:
LINE VOLTAGE, V₀ = 7620
P₀10 = 39.04KVA
S₀11 = KW + j KVAR = 35.136+17.0171i
I₀11 = [S₀11/V₀]* = 5.1234∠-25.8419°
VOLTAGE AT N12 :
LINE IMPREDANCE (N11 – N12)
Z₀12 = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0122+0.0348i
Vn10= V₀ - I₀10*Z₀10 = 7619.8659∠-0.001°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr11 = [Str10/Vn12] = 5.1234∠-25.8429°
Zbase = (1000*KV^2)/KVA = 1548.384Ω
Zpu = 0.0297∠57.3808°
Ztr10= Zbase*Zpu = 45.9586∠64.359°
Vtr10 (high side) = Vn4 - Itr10 * Ztr10- = 7437.0773∠-1.1308°
Vtr4 (low side) = Vtr4(high side) / Turns ratio = 234.2387∠-1.1308°
VOLTAGE DROP THROUGH N11– N12 :
%Vdrop = [(V₀ - Vtr10)/ V₀ ] *100 = 3.0926%

CURRENT THROUGH N₀ - N₂₁ :


LINE VOLTAGE, V₀ = 7620
P₂₁ = 90.35KVA
S₀2 = KW + j KVAR = 81.315+39.3827i
I₂₁ = [S₂₁/V₀] = 11.857∠-25.8419°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₀ - N₁)
Z₂₁ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0042+0.0121i
Vn₁ = V₀ - I₂₁*Z₂₁ = 7619.8924∠-0.0008°
VOLTAGE AT Tr30 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr30 = [Str30/Vn₁] = 6.6261∠-25.8427°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr30 = Zbase*Zpu = 27.0857∠59.0362°
Vtr30 (high side) = Vn₁ - Itr30 * Ztr30 = 7470.3534∠-0.7544°
Vtr30 (low side) = Vtr30(high side) / Turns ratio = 235.2867∠-0.7544°
VOLTAGE DROP THROUGH N₀ - N₁ :
%Vdrop = [(V₀ - Vtr30)/ V₀ ] *100 = 2.3572%
CURRENT THROUGH N₂₁ - N₂₂ :
LINE VOLTAGE, V₀ = 7619.89243
P₂₂ = 39.86KVA
S₂₂ = KW + j KVAR = 35.874+17.3746i
I₂₂ = [S₂₂/V₀] = 5.231∠-25.8427°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₀ - N₁)
Z₂₂ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] =
Vn₁ = V₀ - I₂₂*Z₂₂ = 7619.8141∠-0.0006°
VOLTAGE AT Tr28 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr28 = [Str28/Vn₁] = 5.2311∠-25.8425°
Zbase = (1000*KV^2)/KVA = Ω
Zpu = 0.0297∠57.3808°
Ztr28 = Zbase*Zpu = 45.9573∠64.359°
Vtr28 (high side) = Vn₁ - Itr28 * Ztr28 = 7433.2219∠-1.1547°
Vtr28 (low side) = Vtr28(high side) / Turns ratio = 234.1172∠-1.1547°
VOLTAGE DROP THROUGH N₀ - N₁ :
%Vdrop = [(V₀ - Vtr28)/ V₀ ] *100 = 3.1556%
CONDUCTOR SIZING, VOLTAGE DROP CALCULATION,

AND RATING OF DISCONNECTS

PHASE C

Vo = 7620 V
N24 82.62 m N23 71.52 m N0

10A 20A
10A, RATED 15 KV 10A, RATED 15 KV
VHTR12= 7465.0772 V VHTR11= 7470.0991 V
Tr12= 50 KVA Tr11= 75 KVA N0 34.18 m N25 65.22 m N26
VLOWTR12= 235.1205 V VLOWTR11=235.2787 V
10A 10A
10A, RATED 15 KV 10A, RATED 15 KV
VHTR33= 7449.2172 V VHTR37= 7457.3587 V
Tr33= 50 KVA Tr37= 50 KVA
VLOWTR33=234.621 V VLOWTR37= 234.8774 V

N27 62.01 m N0 Vo = 7620 V

15A
10A, RATED 15 KV
VHTR32= 7463.2168 V
TR32= 37.5 KVA
VLOWTR32=235.0619 V

N28 29.34 m N0
10A, RATED 15 KV
N0 69.77 m N29 101.55 m N30
VHTR31= 7442.3163 V 10A
Tr31= 50 KVA
10A 10A
VLOWTR31= 234.4037 V
10A, RATED 15 KV 15A, RATED 15 KV
VHTR19= 7457.3587 V VHTR22= 7457.3587 V
Tr19= 50 KVA Tr22= 50 KVA
VLOWTR19= 234.8774 V VLOWTR22= 234.7679 V
PHASE C
ASSUME THAT THE POWER FACTOR OF THE
LOADS IS 0.9 LAGGING.
Z = 0.2120 + j0.6041 Ω/mi (ACSR ‘Hawk’: R = 0.2120 Ω/mi,
GMR = 0.0289 ft. 4.2’ spacing) REFERENCE:

RATING OF THE TRANSFORMERS ARE:


TR11 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR12 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR33 = 50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR37 = 75 KVA, 7620-240 V, Z = 17.3115∠59.0362°
TR32 = 37.5 KVA, 7620-240 V, Z = 45.9586∠64.359°
TR31 =75 KVA, 7620-240 V, Z = 17.3115∠59.0362°
TR19 =75 KVA, 7620-240 V, Z = 17.3115∠59.0362°
TR22 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°

REFERENCE: NEMA STANDARD

CURRENT THROUGH N0– N23:TR11


LINE VOLTAGE, V₀ = 7620
P23= 160.68KVA
S₀7= KW + j KVAR = 144.612+70.0388i
I₀7 = [S₀7/V₀] = 21.0866∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0094+0.0268i
Vn7= V₀ - I₀7*Z₀7 = 7619.5744∠-0.0032°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 10.3628∠-25.8451°
Zbase = (1000*KV^2)/KVA = 774.192Ω
Zpu = 0.0224∠63.4349°
Ztr7= Zbase*Zpu = 17.3115∠59.0362°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7470.0991∠-0.7565°
Vtr11 (low side) = Vtr8(high side) / Turns ratio = 235.2787∠-0.7565°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.362%
CURRENT THROUGH N₂₃ - N₂₄ :
LINE VOLTAGE, V₀ = 7619.57444
P₂₄ = 81.72KVA
S₂₄ = KW + j KVAR = 73.548+35.6209i
I₂₄ = [S₂₄/V₀] = 10.725∠-25.8451°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₀ - N₂₄)
Z₂₄ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] =
Vn₁ = V₀ - I₂₄*Z₂₄ = 7619.3244∠-0.0019°
VOLTAGE AT Tr12 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr12 = [Str12/Vn₁] = 10.7254∠-25.8438°
Zbase = (1000*KV^2)/KVA = Ω
Zpu = 0.0224∠63.4349°
Ztr12 = Zbase*Zpu = 17.3095∠59.0362°
Vtr12 (high side) = Vn₁ - Itr12 * Ztr12 = 7464.6602∠-0.782°
Vtr12 (low side) = Vtr12(high side) / Turns ratio = 235.1074∠-0.782°
VOLTAGE DROP THROUGH N₀ - N₁ :
%Vdrop = [(V₀ - Vtr12)/ V₀ ] *100 = 2.438%

CURRENT THROUGH N₀ - N₂₅ :


LINE VOLTAGE, V₀ = 7620
P₂₅ = 136.41KVA
S₂₅ = KW + j KVAR = 122.769+59.4597i
I₂₅ = [S₂₅/V₀] = 17.9016∠-25.8419°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₀ - N₁)
Z₂₅ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0045+0.0128i
Vn₁ = V₀ - I₂₅*Z₂₅ = 7619.8273∠-0.0013°
VOLTAGE AT Tr33 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr33 = [Str33/Vn₁] = 7.5645∠-25.8432°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr33 = Zbase*Zpu = 27.0857∠59.0362°
Vtr33 (high side) = Vn₁ - Itr33 * Ztr33 = 7449.2172∠-0.8641°
Vtr33 (low side) = Vtr33(high side) / Turns ratio = 234.621∠-0.8641°
VOLTAGE DROP THROUGH N₀ - N₁ :
%Vdrop = [(V₀ - Vtr33)/ V₀ ] *100 = 2.692%
CURRENT THROUGH N0 – N27 :T32
LINE VOLTAGE, V₀ = 7620
P₀7= 82.74KVA
S₀7= KW + j KVAR = 74.466+36.0655i
I₀7 = [S₀7/V₀] = 10.8583∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0082+0.0233i
Vn7= V₀ - I₀7*Z₀7 = 7619.81∠-0.0014°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 10.8585∠-25.8434°
Zbase = (1000*KV^2)/KVA = 774.192Ω
Zpu = 0.0224∠63.4349°
Ztr7= Zbase*Zpu = 17.3115∠59.0362°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7463.2168∠-0.7915°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 235.0619∠-0.7915°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.4703%

7620
CURRENT THROUGH N24 – N25 :T31
LINE VOLTAGE, V₀ = 54.4KVA
P₀7= 48.96+23.7124i
S₀7= KW + j KVAR = 7.1391∠-25.8419°
I₀7 = [S₀7/V₀] =
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14) 0.0039+0.011i
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 7619.9409∠-0.0004°
Vn7= V₀ - I₀7*Z₀7 =
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE): 7.1392∠-25.8424°
Itr7 = [Str7/Vn8] = 1161.288Ω
Zbase = (1000*KV^2)/KVA = 0.0233∠59.0362°
Zpu = 27.0857∠59.0362°
Ztr7= Zbase*Zpu = 7458.8775∠-0.8137°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 234.9253∠-0.8137°
Vtr7 (low side) = Vtr8(high side) / Turns ratio =
VOLTAGE DROP THROUGH N13– N14 : 2.5387%
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 7620

CURRENT THROUGH N₀ - N₂₉ :


LINE VOLTAGE, V₀ = 7620
P₂₉ = 108.24KVA
S₂₉ = KW + j KVAR = 97.416+47.1807i
I₂₉ = [S₂₉/V₀] *= 14.2047∠-25.8419°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₀ - N₂₉)
Z₂₉ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0091+0.026i
Vn₁ = V₀ - I₂₉*Z₂₉ = 7619.7223∠-0.0021°
VOLTAGE AT Tr19 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr19 = [Str19/Vn₁]* = 7.352∠-25.844°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr19 = Zbase*Zpu = 27.0857∠59.0362°
Vtr19 (high side) = Vn₁ - Itr19 * Ztr19 = 7453.8814∠-0.8401°
Vtr19 (low side) = Vtr19(high side) / Turns ratio = 234.7679∠-0.8401°
VOLTAGE DROP THROUGH N₀ - N₁ :
%Vdrop = [(V₀ - Vtr19)/ V₀ ] *100 = 2.6183%

CURRENT THROUGH N₂₉ - N₃₀ :


LINE VOLTAGE, V₀ = 7619.722343
P₃₀ = 52.22KVA
S₃₀ = KW + j KVAR = 46.998+22.7622i
I₃₀ = [S₃₀/V₀]* = 6.8533∠-25.844°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₂₉ - N₃₀)
Z₃₀ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] =
Vn₁ = V₀ - I₃₀*Z₃₀ = 7619.5259∠-0.0015°
VOLTAGE AT Tr22 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr22 = [Str22/Vn₁*] = 6.8534∠-25.8434°
Zbase = (1000*KV^2)/KVA = Ω
Zpu = 0.0233∠59.0362°
Ztr22 = Zbase*Zpu = 27.0837∠59.0362°
Vtr22 (high side) = Vn₁ - Itr22 * Ztr22 = 7464.8903∠-0.7815°
Vtr22 (low side) = Vtr22(high side) / Turns ratio = 235.1147∠-0.7815°
VOLTAGE DROP THROUGH N₀ - N₁ :
%Vdrop = [(V₀ - Vtr22)/ V₀ ] *100 = 2.4376%
CONDUCTOR SIZING, VOLTAGE DROP CALCULATION,

AND RATING OF DISCONNECTS

3PHASE

Vo = 13200 V
N12 3m N0

10A, RATED 15 KV 10A


VHT1= 7457.3587 V
Tr14= 75 KVA
VLOWTR1=234.632 V

10A, RATED 15 KV
VHTR10= 7457.3587 V
Tr10= 50 KVA
VLOWTR5=234.632 V

N19 3m
10A, RATED 15 KV
VHTR9= 7457.3587 V 10A
Tr9= 15 KVA
VLOWTR43= 234.8774 V

N12 3m

10A, RATED 15 KV 10A


VHT1= 7457.3587 V
Tr15= 100 KVA
VLOWTR1=234.632 V

3m

10A, RATED 15 KV
VHTR17= 7457.3587 V
Tr17= 37.5 KVA
VLOWTR5=234.632 V
Vo = 7620 V
N12 3m N0

10A, RATED 15 KV 10A


VHT1= 7457.3587 V
Tr36= 100 KVA
VLOWTR1=234.632 V
3m
10A, RATED 15 KV
VHTR10= 7457.3587 V
Tr10= 50 KVA
VLOWTR5=234.632 V

N19 3m
10A, RATED 15 KV
VHTR43= 7457.3587 V 10A
Tr41=37.5 KVA
VLOWTR43= 234.8774 V

3m

10A, RATED 15 KV
VHTR10= 7457.3587 V
Tr42= 37.5 KVA
VLOWTR5=234.632 V

10A, RATED 15 KV
VHTR10= 7457.3587 V
Tr10= 50 KVA
VLOWTR5=234.632 V

10A, RATED 15 KV
VHTR10= 7457.3587 V
Tr26= 50 KVA
VLOWTR5=234.632 V

N19 3m
10A, RATED 15 KV
VHTR43= 7457.3587 V 10A
Tr21= 37.5 KVA
VLOWTR43= 234.8774 V

3m

10A, RATED 15 KV
VHTR10= 7457.3587 V
Tr20= 50 KVA
VLOWTR5=234.632 V

3m
10A, RATED 15 KV
VHTR10= 7457.3587 V
Tr18= 50 KVA
VLOWTR5=234.632 V
3PHASE
ASSUME THAT THE POWER FACTOR OF THE LOADS IS 0.9 LAGGING.
Z = 0.2120 + j0.6041 Ω/mi (ACSR ‘Hawk’: R = 0.2120 Ω/mi, GMR = 0.0289 ft. 4.2’
spacing) REFERENCE:

RATING OF THE TRANSFORMERS ARE:


TR14 =75 KVA, 7620-240 V, Z = 17.3115∠59.0362°
TR16=50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR9 = 3-15 KVA, 7620-240 V, Z= 102.1963∠53.1301°
TR15 = 3-100KVA, 7620-240 V, Z= 13.5925∠61.3895°
TR17 = 37.5 KVA, 7620-240 V, Z = 45.9586∠64.359°
TR36 =3-100KVA, 7620-240 V, Z= 13.5925∠61.3895°
TR39 = 50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR41 = 37.5 KVA, 7620-240 V, Z = 45.9586∠64.359°
TR42= 37.5 KVA, 7620-240 V, Z = 45.9586∠64.359°
TR44 = 50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR45 = 3-100KVA, 7620-240 V, Z= 13.5925∠61.3895°
TR26 =50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR21 = 37.5 KVA, 7620-240 V, Z = 45.9586∠64.359°
TR20 = 50 KVA, 7620-240 V, Z = 27.0857∠59.0362°
TR18 = 50 KVA, 7620-240 V, Z = 27.0857∠59.0362°

REFERENCE: NEMA STANDARD


CURRENT THROUGH N₀ - N31 :
LINE VOLTAGE, V₀ = 13200
P₃₁ = 80.9KVA
S₃₁ = KW + j KVAR = 72.81+35.2635i
I₃₁ = [S₃₁/V₀]* = 6.1288∠-25.8419°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₀ - N₁)
Z₃₁ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn₁ = V₀ - I₃₁*Z₃₁ = 13199.9948∠0°
VOLTAGE AT Tr14 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr14 = [Str14/Vn₁] = 6.1288∠-25.842°
Zbase = (1000*KV^2)/KVA = 2323.2Ω
Zpu = 0.0224∠63.4349°
Ztr14 = Zbase*Zpu = 51.9483∠59.0362°
Vtr14 (high side) = Vn₁ - Itr14 * Ztr14 = 12934.7426∠-0.7722°
Vtr14 (low side) = Vtr14(high side) / Turns ratio = 407.3935∠-0.7722°
VOLTAGE DROP THROUGH N₀ - N₁ :
%Vdrop = [(V₀ - Vtr14)/ V₀ ] *100 = 2.412%

CURRENT THROUGH N₀ - N32:


LINE VOLTAGE, V₀ = 13200
P₃₂ = 52.22KVA
S₃₂ = KW + j KVAR = 46.998+22.7622i
I₃₂ = [S₃₂/V₀]* = 3.9561∠-25.8419°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₀ - N₁)
Z₃₂ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn₁ = V₀ - I₃₂*Z₃₂ = 13199.9967∠0°
VOLTAGE AT Tr16 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr16 = [Str16/Vn₁] = 3.9561∠-25.8419°
Zbase = (1000*KV^2)/KVA = 3484.8Ω
Zpu = 0.0233∠59.0362°
Ztr16 = Zbase*Zpu = 81.2788∠59.0362°
Vtr16 (high side) = Vn₁ - Itr16 * Ztr16 = 12932.1209∠-0.78°
Vtr16 (low side) = Vtr16(high side) / Turns ratio = 407.3109∠-0.78°
VOLTAGE DROP THROUGH N₀ - N₁ :
%Vdrop = [(V₀ - Vtr16)/ V₀ ] *100 = 2.436%
CURRENT THROUGH N₀ - N33:
LINE VOLTAGE, V₀ = 13200
P₃₃ = 16.57KVA
S₃₃ = KW + j KVAR = 14.913+7.2227i
I₃₃ = [S₃₃/V₀]* = 1.2553∠-25.8419°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₀ - N₁)
Z₃₃ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn₁ = V₀ - I₃₃*Z₃₃ = 13199.9989∠0°
VOLTAGE AT Tr9 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr9 = [Str9/Vn₁] = 1.2553∠-25.8419°
Zbase = (1000*KV^2)/KVA = 11616Ω
Zpu = 0.0264∠37.3039°
Ztr9 = Zbase*Zpu = 306.6712∠53.1301°
Vtr9 (high side) = Vn₁ - Itr9 * Ztr9 = 12859.0869∠-0.7864°
Vtr9 (low side) = Vtr9(high side) / Turns ratio = 405.0106∠-0.7864°
VOLTAGE DROP THROUGH N₀ - N₁ :
%Vdrop = [(V₀ - Vtr9)/ V₀ ] *100 = 2.9164%

CURRENT THROUGH N₀ - N34 :


LINE VOLTAGE, V₀ =
P₀₁ = 13200
S₀₁ = KW + j KVAR = 110.05KVA
I₀₁ = [S₀₁/V₀] = 99.045+47.9697i
VOLTAGE AT N₁ : 8.3371∠-25.8419°
LINE IMPREDANCE (N₀ - N₁)
Z₀₁ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] =
Vn₁ = V₀ - I₀₁*Z₀₁ = 0.0004+0.0011i
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE): 13199.9929∠0°
Itr1 = [Str1/Vn₁] =
Zbase = (1000*KV^2)/KVA = 8.3371∠-25.842°
Zpu = 1742.4Ω
Ztr1 = Zbase*Zpu = 0.0234∠70.0169°
Vtr1 (high side) = Vn₁ - Itr1 * Ztr1 = 40.7885∠61.3895°
Vtr1 (low side) = Vtr1(high side) / Turns ratio = 12924.8218∠-0.8765°
VOLTAGE DROP THROUGH N₀ - N₁ : 407.081∠-0.8765°
%Vdrop = [(V₀ - Vtr1)/ V₀ ] *100 =
CURRENT THROUGH N28 – N29 :TR17
LINE VOLTAGE, V₀ = 7620
P₀7= 46.32KVA
S₀7= KW + j KVAR = 41.688+20.1904i
I₀7 = [S₀7/V₀] = 6.0787∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9949∠0°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 6.0787∠-25.842°
Zbase = (1000*KV^2)/KVA = 1548.384Ω
Zpu = 0.0297∠57.3808°
Ztr7= Zbase*Zpu = 45.9586∠64.359°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7403.4535∠-1.3466°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 233.1796∠-1.3466°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 3.6664%

CURRENT THROUGH N28 – N29 :TR36


LINE VOLTAGE, V₀ = 7620
P₀7= 109.18KVA
S₀7= KW + j KVAR = 98.262+47.5905i
I₀7 = [S₀7/V₀] = 14.3281∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9879∠-0.0001°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 14.3281∠-25.842°
Zbase = (1000*KV^2)/KVA = 580.644Ω
Zpu = 0.0234∠70.0169°
Ztr7= Zbase*Zpu = 13.5925∠61.3895°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7462.3877∠-0.8695°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 235.0358∠-0.8695°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.5561%
CURRENT THROUGH N28 – N29 :TR9
LINE VOLTAGE, V₀ = 7620
P₀7= 52.22KVA
S₀7= KW + j KVAR = 46.998+22.7622i
I₀7 = [S₀7/V₀] = 6.853∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9942∠0°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 6.853∠-25.842°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr7= Zbase*Zpu = 27.0857∠59.0362°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7465.3567∠-0.78°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 235.1293∠-0.78°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.436%

CURRENT THROUGH N0 – N29 :TR15


LINE VOLTAGE, V₀ = 7620
P₀7= 110.05KVA
S₀7= KW + j KVAR = 99.045+47.9697i
I₀7 = [S₀7/V₀] = 14.4423∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9878∠-0.0001°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 14.4423∠-25.842°
Zbase = (1000*KV^2)/KVA = 580.644Ω
Zpu = 0.0234∠70.0169°
Ztr7= Zbase*Zpu = 13.5925∠61.3895°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7461.1388∠-0.8765°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 234.9965∠-0.8765°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.5764%
CURRENT THROUGH N28 – N29 :TR17
LINE VOLTAGE, V₀ = 7620
P₀7= 46.32KVA
S₀7= KW + j KVAR = 41.688+20.1904i
I₀7 = [S₀7/V₀] = 6.0787∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9949∠0°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 6.0787∠-25.842°
Zbase = (1000*KV^2)/KVA = 1548.384Ω
Zpu = 0.0297∠57.3808°
Ztr7= Zbase*Zpu = 45.9586∠64.359°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7403.4535∠-1.3466°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 233.1796∠-1.3466°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 3.6664%

CURRENT THROUGH N28 – N29 :TR36


LINE VOLTAGE, V₀ = 7620
P₀7= 109.18KVA
S₀7= KW + j KVAR = 98.262+47.5905i
I₀7 = [S₀7/V₀] = 14.3281∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9879∠-0.0001°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 14.3281∠-25.842°
Zbase = (1000*KV^2)/KVA = 580.644Ω
Zpu = 0.0234∠70.0169°
Ztr7= Zbase*Zpu = 13.5925∠61.3895°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7462.3877∠-0.8695°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 235.0358∠-0.8695°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.5561%
CURRENT THROUGH N28 – N29 :TR39
LINE VOLTAGE, V₀ = 7620
P₀7= 109.18KVA
S₀7= KW + j KVAR = 98.262+47.5905i
I₀7 = [S₀7/V₀] = 14.3281∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9879∠-0.0001°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 14.3281∠-25.842°
Zbase = (1000*KV^2)/KVA = 580.644Ω
Zpu = 0.0234∠70.0169°
Ztr7= Zbase*Zpu = 13.5925∠61.3895°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7462.3877∠-0.8695°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 235.0358∠-0.8695°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.5561%

CURRENT THROUGH N28 – N29 TR41


LINE VOLTAGE, V₀ = 7620
P₀7= 39.3KVA
S₀7= KW + j KVAR = 35.37+17.1305i
I₀7 = [S₀7/V₀] = 5.1575∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9956∠0°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 5.1575∠-25.842°
Zbase = (1000*KV^2)/KVA = 1548.384Ω
Zpu = 0.0297∠57.3808°
Ztr7= Zbase*Zpu = 45.9586∠64.359°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7436.0027∠-1.1375°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 234.2048∠-1.1375°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 3.1107%
CURRENT THROUGH N28 – N29 TR42
LINE VOLTAGE, V₀ = 7620
P₀7= 39.56KVA
S₀7= KW + j KVAR = 35.604+17.2438i
I₀7 = [S₀7/V₀] = 5.1916∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9956∠0°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 5.1916∠-25.842°
Zbase = (1000*KV^2)/KVA = 1548.384Ω
Zpu = 0.0297∠57.3808°
Ztr7= Zbase*Zpu = 45.9586∠64.359°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7434.7954∠-1.1452°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 234.1668∠-1.1452°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 3.1313%

CURRENT THROUGH N28 – N29 TR44


LINE VOLTAGE, V₀ = 7620
P₀7= 61.54KVA
S₀7= KW + j KVAR = 55.386+26.8247i
I₀7 = [S₀7/V₀] = 8.0761∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9932∠-0.0001°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 8.0761∠-25.842°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr7= Zbase*Zpu = 27.0857∠59.0362°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7437.9057∠-0.9226°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 234.2647∠-0.9226°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.8708%
CURRENT THROUGH N28 – N29 TR45
LINE VOLTAGE, V₀ = 7620
P₀7= 111.25KVA
S₀7= KW + j KVAR = 100.125+48.4928i
I₀7 = [S₀7/V₀] = 14.5997∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9876∠-0.0001°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 14.5998∠-25.842°
Zbase = (1000*KV^2)/KVA = 580.644Ω
Zpu = 0.0234∠70.0169°
Ztr7= Zbase*Zpu = 13.5925∠61.3895°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7459.4164∠-0.8863°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 234.9422∠-0.8863°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.6045%

CURRENT THROUGH N28 – N29 TR26


LINE VOLTAGE, V₀ = 7620
P₀7= 54.41KVA
S₀7= KW + j KVAR = 48.969+23.7168i
I₀7 = [S₀7/V₀] = 7.1404∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.994∠0°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 7.1404∠-25.842°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr7= Zbase*Zpu = 27.0857∠59.0362°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7458.9022∠-0.8134°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 234.9261∠-0.8134°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.5382%
CURRENT THROUGH N28 – N29 TR21
LINE VOLTAGE, V₀ = 7620
P₀7= 39.56KVA
S₀7= KW + j KVAR = 35.604+17.2438i
I₀7 = [S₀7/V₀] = 5.1916∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.9956∠0°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 5.1916∠-25.842°
Zbase = (1000*KV^2)/KVA = 1548.384Ω
Zpu = 0.0297∠57.3808°
Ztr7= Zbase*Zpu = 45.9586∠64.359°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7434.7954∠-1.1452°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 234.1668∠-1.1452°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 3.1313%

CURRENT THROUGH N28 – N29 TR20


LINE VOLTAGE, V₀ = 7620
P₀7= 54.12KVA
S₀7= KW + j KVAR = 48.708+23.5904i
I₀7 = [S₀7/V₀] *= 7.1024∠-25.8419°
VOLTAGE AT N13 :
LINE IMPREDANCE (N13 – N14)
Z₀7= [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn7= V₀ - I₀7*Z₀7 = 7619.994∠0°
VOLTAGE AT TR1 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr7 = [Str7/Vn8] = 7.1024∠-25.842°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr7= Zbase*Zpu = 27.0857∠59.0362°
Vtr7 (high side) = Vn7 - Itr7 * Ztr7- = 7459.7568∠-0.809°
Vtr7 (low side) = Vtr8(high side) / Turns ratio = 234.953∠-0.809°
VOLTAGE DROP THROUGH N13– N14 :
%Vdrop = [(V₀ - Vtr7)/ V₀ ] *100 = 2.5247%
CURRENT THROUGH N₀ - N₁ :
LINE VOLTAGE, V₀ = 7620
P₄₅ = 54.3KVA
S₄₅ = KW + j KVAR = 48.87+23.6688i
I₄₅ = [S₄₅/V₀]* = 7.126∠-25.8419°
VOLTAGE AT N₁ :
LINE IMPREDANCE (N₀ - N₁)
Z₄₅ = [(0.2120 + j0.6041)(DISTANCE/1609.34)] = 0.0004+0.0011i
Vn₁ = V₀ - I₄₅*Z₄₅ = 7619.994∠0°
VOLTAGE AT Tr18 (REFFERED TO THE HIGH VOLTAGE SIDE):
Itr18 = [Str18/Vn₁] = 7.126∠-25.842°
Zbase = (1000*KV^2)/KVA = 1161.288Ω
Zpu = 0.0233∠59.0362°
Ztr18 = Zbase*Zpu = 27.0857∠59.0362°
Vtr18 (high side) = Vn₁ - Itr18 * Ztr18 = 7459.2263∠-0.8117°
Vtr18 (low side) = Vtr18(high side) / Turns ratio = 234.9363∠-0.8117°
VOLTAGE DROP THROUGH N₀ - N₁ :
%Vdrop = [(V₀ - Vtr18)/ V₀ ] *100 = 2.5331%
BALANCING OF PHASES
BALANCING OF PHASES
TRANSFORMER PHASE A PHASE B PHASE C
1 53.1200
2 52.5500
3 54.4200
4 67.8800
5 57.5000
6 79.9000
7 77.9700
8 42.7800
9 16.5700 16.5700 16.5700
10 86.0100
11 78.9600
12 81.7200
13 55.6000
14 80.9000
15 110.0500 110.0500 110.0500
16 53.1200
17 46.3200
18 54.3000
19 56.0200
20 54.1200
21 39.5600
22 52.2200
23 56.3600
24 55.2800
25 53.3600
26 54.4100
27 57.4400
28 39.8600
29 79.3000
30 50.4900
31 54.4000
32 82.7400
33 57.6400
34 48.1400
35 56.7500
36 109.1800 109.1800 109.1800
37 78.7700
38 81.4900
39 51.1600
40 53.9200
41 39.3000
42 39.5600
43 39.0400
44 61.5400
45 111.25 111.25 111.25
TOTAL 1040.3900 1042.39000 1040.54000
AVERAGE 1041.106667
CONCLUSION AND RECOMMENDATIONS

The design and installation of the substations are essential steps in


creating a reliable and effective electrical infrastructure. The substation acts as a
hub for power transmission and distribution, and its design is crucial to making
sure that electricity is delivered to homes, companies, and industries in a safe and
effective manner.

To guarantee that all components are properly grounded, insulated, and


installed to prevent faults and interruptions, the installation of electrical
equipment in the substation should be done with the utmost care. This
necessitates the use of the proper tools and materials, such as transformers, switch
gear, safety equipment, and insulators, to guarantee that the substation can handle
the necessary power transmission and distribution.

Furthermore, safety should be a priority during the substation design


process. This entails using the proper safety tools and installation processes, as
well as regular maintenance and monitoring to guarantee the substation stays
secure and dependable throughout time. The danger of electrical hazards to
workers and the general public can be reduced by putting safety first.

In conclusion, the design and installation of substations are intricate


procedures that demand careful forethought, design, and execution. In order for
the substation to be able to supply the increasing demand for energy in the area,
it should be designed with safety, efficiency, and dependability as top priorities.
The substation design will help to ensure that local businesses and industries can
continue to flourish and grow while also providing crucial energy services to local
inhabitants by establishing a safe, dependable, and efficient system.
CALCULATION OF PERCENT UNBALANCED

AVERAGE LOADING = 1041.1067

DEVIATION @ PHASE A = 1040.3900 - 1041.1067 = -0.72 kVA


DEVIATION @ PHASE B = 1042.3900 - 1041.1067 = 1.28 kVA
DEVIATION @ PHASE C = 1040-.5400 - 1041.1067 = -0.57 kVA

HENCE, THE MAXIMUM


DEVIATION FROM THE = 1.28 kVA
AVERAGE IS

%UNBALANCED = 0.123 %
APPENDICES
R2
R1 R1 R6 R1 R5
R1 R6
R4
LEGENDS:
R2
R4 R1
R3
R4 R2
R3
R3
R1
R8
R2
R1
R1
RESIDENTIALS
R1
R1 R1
R2
R1 R1
R1 R1 RESIDENTIAL 1 R6 RESIDENTIAL 6
TR42
R1 R1
TR43 R5 R1
R1
R3 R2 RESIDENTIAL 2 R7 RESIDENTIAL 7
TR32 R3
R3 R2 R7
R1 R3
R2 R1
R3 RESIDENTIAL 3 R8 RESIDENTIAL 8
R1 R4
R1 TR44
R3 R4 TR25
R4 RESIDENTIAL 4
R5 R1
R2 R3
R2 R1 R4 R5 RESIDENTIAL 5
R3 R1 R4
R2 R1 R3 R1
R2
R2 R1 R4
R1
R6 R5
COMMERCIALS
N
R1 TR41 TR45 R1
R3
R1 R5
R3 R5
R2 R3 R3 R5 HIGH SCHOOL
R5 R3 R4
R2 TR31
ELEMENTERAY
R2 MUNICIPAL
CF R1 ES
R2 TR24 R2
SCHOOL HALL
R1 R1
TR39
R3 POLICE
BEER HOUSE

R2 CO.EST
P BEER
TR38
R2 R6 R3 STATION HOUSE
R2 TR33

W
R3 R3 R5 R6
R1

R1
TR40

R3
R1
BEER HOUSE

R6
R2
R6

R4
R8
GS
R5
E PM
F FIRE
STATION
PUBLIC
WESTERN
UNION
R2 TR37
R5 MARKET
R1 R5
R1 R4 R2
R4 FITNESS
DS R4 R5 R7
TR26 R4
R3 R PH BUS
R4 TR30 R6 CH CHURCH
R4 R6 R5 STATION
R5
R4 R4
S WS
CH PHARMACY
R4 R4

R4
R5 R4 R4
R4
R2
R2
S PH

GAS
BASKETBALL
COURT

ES COMP. S
R4 R6
R6 CF TR23
GS STATION
BARANGAY HALL

BARANGAY
TR36 R6 R3
R5 R3 HALL
TR27
TR35 TR28 R3 R3 R3 R2 B
R5 R5 R5 R1 BAKERY
TR34
R2 R
R4 R2
TR15 CO.EST
COMMERCIAL HOSPITAL
TR17 R5
XXXXXXXXXXX

R4 HOSPITAL R3 R5 HOSPITAL
R4 ESTABLISHMENT
DS XXXXXXXXXXX
WESTERN UNION

R5 R5
R2
R3 R5 R2 R1 DRUG
R5 R1 DS WATER
WS
COMP. S
PH R4 FITNESS
R2 STORE STATION
R1
R2 R3 R4
B
R3 S TR22
GS TR9 LAUNDRY
R1 R4
R4 S R4 R3
R1
CF CAFE LS SHOP
R4 CULTURAL PARK
TR21
TR10 R2 TR29
CO.EST
WS R3 R3
CF R4
CO.EST
R2 R1
R4 TR13
R
RESTAURANT GYM
R2 WS
R5 R1 R4 R4 FITNESS

R4 R1 GROCERY
R2 R4 R6
TR19 STORE S SALON
R6
R1
R4
R1
CO.EST DS
HS
R5 R4
CH R6
COMP. S
COMPUTER
R4 R5 TR20
SHOP
R1 B R4 R5 TR16
R6 R3 APARTMENT
PH R3
R5 R6 R5 R1
R1 R1 R6
R1 R4 R1 R6
R2 R4 B R4
R2
TR11
R4 TR7
COMP. S

P R4 R3
R3
R1 R1 R4 R5
R2 R1 R6 R5 R4 R4 R4 R5 R3

INDUSTRIALS
R8
R R6 R4
R4 R3
R5 R4 LS TR5 R3 R8 R4
R5 R2 R2 R7
R1 R2 R3 R2
TR12 TR8 LS R3
R5 R4 TR14
R1 TR18
R5 R2 R5
R4 R1 R2 TR6 R7
WS
R6 R R BARANGAY HALL

INDUSTRIAL 1 INDUSTRIAL 2
R6 R6 S
R1 R2 R4
R2 R4
R5
R2 R3
R2 TR4 R5
S
S
R3 B
PH
R4
SUBSTATION
R2
R4
R1
R5
R3 R5 B
R3 R4 main pole
R4
TR3
R5 F R5 R3
sub. pole
R6
R4 R3
R6
R1
TR1
R5
PM R1 R2

R2
R2 TR2
R4 PHASE A
R2 R4
R2 PHASE B
R5
R1 PHASE C
R3
R2 R1
R4 R5 R1 R2
R1
PROJECT: DISTRIBUTION SYSTEM AND SUBSTATION DESIGN
LOCATION : LUZON, CLAVERIA, CAGAYAN
BOQ
ITEM DESCRIPTION
QTY. UNIT PRICE AMOUNT
CARRIED TO COLLECTION

A ELECTRICAL

1 LOW VOLTAGE TRANSFORMERS

37.5kVA, Primary Voltage 7620/13200V 5 taps 2x=2.5% / 2x-


1.2 9 PCS 130,000.00 910,000.00
2.5% Secondary Voltage 120/240V NEA
50kVA, Primary Voltage 7620/13200V 5 taps 2x=2.5% / 2x-
1.3 17 PCS 142,000.00 2,130,000.00
2.5% Secondary Voltage 120/240V NEA
75kVA, Primary Voltage 7620/13200V 5 taps 2x=2.5% / 2x-
1.4 12 PCS 200,000.00 1,000,000.00
2.5% Secondary Voltage 120/240V NEA
100kVA, Primary Voltage 7620/13200V 5 taps 2x=2.5% / 2x-
1.5 7 PCS 265,000.00 2,385,000.00
2.5% Secondary Voltage 120/240V NEA

2 CONDUCTOR

2.1 477 Hawk ACSR Aluminum Conductor Steekl Reinforced 31332.02 FT. 184.26 5,773,238.19

3 TRANSMISSION POLE 20
3.1 WOODENP OLE 92 PCS
3.2 GALVANIZED STEEL POLE PCS

4 MISCELLANEOUS 312,000.00 312,000.00

12,510,238.19
NOTE: THAT THIS PRICE MAY CHANGE
ALL STRUCTURAL SUPPORT AND CONSUMABLES
IN THE NEAR FUTURE. DUE TO
MATERIALS FOR THE INSTALLATIONS SHALL BE
MARKET FLUCTUATIONS AND OTHER
PROVIDED BY CONTRUCTOR
FACTORS
SOURCE 3-PHASE, 13.2KV, 4WIRE
FROM TRANSFORMER,5MVA,69/13.2 KV)

FEDER LOOP
BREAKER 1 MEDIUM VOLTAGE SWITCH GEAR(MVSG)

MAIN BREAKER

FEDER LOOP
BREAKER 2

N14 84.31 m N13 78.30 m N12 46.38 m N0


N0 69.77 m N29 101.55 m N30
15A, RATED 15 KV
VHTR3= 7469.7687 V 10A 10A 20A N28 29.34 m
Tr3=75 KVA 10A, RATED 15 KV 10A 10A
10A, RATED 15 KV 20A, RATED 15 KV
VLOWTR3= 235.2683 V VHTR2= 7457.3587 V VHT1= V VHTR31= 7442.3163 V 10A 10A, RATED 15 KV 10A, RATED 15 KV
Tr31= 50 KVA VHTR19= 7457.3587 V VHTR22= 7457.3587 V
Tr2= 50 KVA Tr1= 50 KVA
VLOWTR31= 234.4037 V Tr19= 50 KVA Tr22= 50 KVA
VLOWTR2= 234.8774 V VLOWTR=235.0371 V
N12 3m VLOWTR19= 234.8774 V VLOWTR22= 234.7679 V

41.25 m N2
10A, RATED 15 KV N0 N19 3m
10A
VHT1= 7457.3587 V 10A, RATED 15 KV
Tr14= 75 KVA 15A VHTR43= 7457.3587 V 10A
VLOWTR1=234.632 V 15A, RATED 15 KV Tr21= 37.5 KVA
VHTR29= 7469.7687 V VLOWTR43= 234.8774 V
Tr29=75 KVA N0 58.22 m N9 59.80 m N10 64.23 m N11
N5 91.67m N4 56.94 m N3 35 m VLOWTR29= 235.2683 V
15A, RATED 15 KV 10A 10A 10A
34.18 m N25 65.22 m N26
VHTR8= 7419.2314 V 10A 20 A 20A 10A, RATED 15 KV 10A, RATED 15 KV
N12 3m
Tr8=75 KVA 20A, RATED 15 KV 20A, RATED 15 KV 3m VHTR23= 7457.3587 V VHTR24= 7457.3587 V
10A 10A
VLOWTR8= 233.6766 V VHTR6= 7468.2688 V VHTR5= 7468.2688 V Tr23= 50 KVA Tr24= 50 KVA
10A, RATED 15 KV 10A, RATED 15 KV 10A 10A, RATED 15 KV 10A, RATED 15 KV
Tr6= 50 KVA Tr5= 50 KVA VHTR17= 7457.3587 V VHT1= 7457.3587 V VHTR33= 7449.2172 V VHTR37= 7457.3587 V VLOWTR23= 234.8774 V VLOWTR24= 234.8268 V
VLOWTR6= 235.2211 V VLOWTR5=235.2211 V Tr33= 50 KVA Tr37= 50 KVA 10A, RATED 15 KV
Tr17= 37.5 KVA Tr36= 100 KVA
N15 N0 VHTR25= 7461.873 V
VLOWTR5=234.632 V VLOWTR1=234.632 V VLOWTR33=234.621 V VLOWTR37= 234.8774 V 10A, RATED 15 KV
15A, RATED 15 KV Tr25= 50 KVA
52.26 m VHTR10= 7457.3587 V
N19
VHTR7= 7469.7687 V N28 29.34 m VLOWTR25= 235.0196 V
10A, RATED 15 KV Tr26= 50 KVA
Tr7=75 KVA 34.90m N16 10A, RATED 1515A
KV
VHTR40= 7442.3163 V 10A VLOWTR5=234.632 V
VHTR31= 7442.3163 V 10A
VLOWTR7= 235.2683 V 15A, RATED 15 KV Tr40= 50 KVA
N17 3m
15A VHTR34= 7469.7687 V Tr31= 50 KVA
N19 3m VLOWTR40= 234.4037 V
10A, RATED 15 KV Tr34=75 KVA VLOWTR31= 234.4037 V
10A, RATED 15 KV 10A, RATED 15 KV
VHTR10= 7457.3587 V VHTR10= 7457.3587 V
VHTR9= 7457.3587 V 10A VLOWTR34= 235.2683 V 32.15 m N21 53.07 m N22
Tr10= 50 KVA Tr42= 37.5 KVA
Tr9= 15 KVA
VLOWTR5=234.632 V VLOWTR5=234.632 V
VLOWTR43= 234.8774 V 10A 10A
10A, RATED 15 KV 10A, RATED 15 KV
N0 VHTR30= 7457.3587 V VHTR28= 7457.3587 V
N20 92.74 m
N12 3m
Tr30= 50 KVA Tr28= 50 KVA
TIE BRAKER 10A, RATED 15 KV
VLOWTR30= 234.8774 V
10A, RATED 15 KV 10A 10A VHTR43= 7457.3587 V VLOWTR28= 234.8774 V
VHT1= 7457.3587 V Tr43= 50 KVA N27 62.01 m
N24 82.62 m N23 71.52 m
Tr15= 100 KVA VLOWTR43= 234.8774 V
VLOWTR1=234.632 V 15A
10A 20A 3m
10A, RATED 15 KV
10A, RATED 15 KV 10A, RATED 15 KV 10A, RATED 15 KV VHTR32= 7463.2168 V
VHTR12= 7465.0772 V VHTR11= 7470.0991 V VHTR49= 7457.3587 V TR32= 37.5 KVA
Tr12= 50 KVA Tr11= 75 KVA Tr39= 50 KVA VLOWTR32=235.0619 V
VLOWTR12= 235.1205 V VLOWTR11=235.2787 V VLOWTR5=234.632 V

N19 3m
10A, RATED 15 KV
VHTR43= 7457.3587 V 10A
Tr41=37.5 KVA
VLOWTR43= 234.8774 V
PROJECT: DISTRIBUTION SYSTEM AND SUBSTATION DESIGN
LOCATION : LUZON, CLAVERIA, CAGAYAN
BOQ
ITEM DESCRIPTION
QTY. UNIT PRICE AMOUNT
CARRIED TO COLLECTION

A ELECTRICAL

1 LOW VOLTAGE TRANSFORMERS

37.5kVA, Primary Voltage 7620/13200V 5 taps 2x=2.5% / 2x-


1.2 7 PCS 130,000.00 910,000.00
2.5% Secondary Voltage 120/240V NEA
50kVA, Primary Voltage 7620/13200V 5 taps 2x=2.5% / 2x-
1.3 15 PCS 142,000.00 2,130,000.00
2.5% Secondary Voltage 120/240V NEA
75kVA, Primary Voltage 7620/13200V 5 taps 2x=2.5% / 2x-
1.4 5 PCS 200,000.00 1,000,000.00
2.5% Secondary Voltage 120/240V NEA
100kVA, Primary Voltage 7620/13200V 5 taps 2x=2.5% / 2x-
1.5 9 PCS 265,000.00 2,385,000.00
2.5% Secondary Voltage 120/240V NEA

2 CONDUCTOR

2.1 477 Hawk ACSR Aluminum Conductor Steekl Reinforced 31332.02 FT. 184.26 5,773,238.19

3 TRANSMISSION POLE 7
3.1 WOODENP OLE 99 PCS
3.2 GALVANIZED STEEL POLE PCS

4 MISCELLANEOUS 312,000.00 312,000.00

12,510,238.19
NOTE: THAT THIS PRICE MAY CHANGE
ALL STRUCTURAL SUPPORT AND CONSUMABLES
IN THE NEAR FUTURE. DUE TO
MATERIALS FOR THE INSTALLATIONS SHALL BE
MARKET FLUCTUATIONS AND OTHER
PROVIDED BY CONTRUCTOR
FACTORS