Professional Documents
Culture Documents
I Installation
outlet (usually at bottom) of the tank, the outlet MV01 of the purifier
and ground cable to the terminal block, Open circuit breaker QS1, QS2
and QS3. The power indicator on the control panel should be light on.
5.Turn on the “outlet pump” select switch and Turn off the “outlet
and exchange the wiring of any two terminals of the pump motor
rewired.
set correctly before leaving the factory. This operation is only needed
whether the oil level of vacuum pump and roots pump is within the
allowable range.
at the factory.
II Running
1.Open the oil inlet valve MV02 and the cycle valve MV03.
automatically opens the oil pump, the oil inlet solenoid and the oil
the center of the sight glass, the air valve MV07 should be partially
opened until the foam level is below the sight glass. Purifier with
become less, this time can be slightly closed valve MV07, but the foam
level is always lower than the center of the sight glass. Purifier with
MV03.
III Stop
1.Turn off the “heater 1” and the “heater 2” and wait for more
than 1 minute.
2.Turn off the “Auto/vacuum pump” select switch and close the
oil inlet valve MV02, and open the air valve MV07.
3.If you want to pump out the oil in the vacuum chamber, turn
on the "Outlet pump" select switch. Turn off the "Outlet pump" select
4.After the Vacuum gauge pointer return to 0Mpa, close the air
1.Purifier with oil inlet pump, can be used separately when the oil
does not need to be degassed (eg. transfer oil between tank or empty
oil of transformer).
2.Open oil inlet valve (MV02) and oil outlet valve (MV01).
After the machine starts running, observe the working pressure vale,
the operator can leave the machine and let it run automatically.
■ If the machine is mobile type, please make sure the casters are steady
■ The equipment does not have any abnormal vibration and noise.
■ Remember to check the vacuum pump oil and roots pump oil is on
Maintenance
a.Troubleshooting
displayed or undervoltage
3.The fuse F1 or F2 is
blown
prompt
motor is broken
is broken
broken
3.Condenser level
a.Check Filter
After the filter element has been working for a period of time, when
the pressure difference through the filter element increases to the limit
specified by the design due to the blockage of the dirt, the filter
Note: Among the filter elements used by DVTP plant, the Primary filter
filter element FL02, FL03 and the vacuum pump oil filter element
low, the liquid level control ball valve (MV12) is fully opened, and the
oil inlet speed is still slower than the oil pump oil discharge speed, you
should shut down and take the pr-filter out for maintenance . The filter
compressed air is used to blow away the dirt attached to the mesh
from the inside to the outside. Before installation, check whether the
a. Close the ball valve(MV02) of the inlet pipe, and open the outlet
b. Start the oil pump and drain off the oil from the filter as much as
c. Turn off the machine after confirming that there is no oil in it.
e. Take out the filter element, After unscrewing the filter element, pay
attention to check whether the "O"-ring under the fixed thread of the
Maintenance Schedule
Item Time Note
Check the fault indicator Everyday
Check every instruments Everyday
Check if the inlet and outlet pipes Every week
are damaged? The sealing is
good?
Replace pr-filter FL01 See R1
Replace filter filter FL02,FL03 See R2
After the vacuum pump Be sure to replace the
oil is emulsified or the vacuum pump oil and
Replace the vacuum pump oil vacuum pump runs for vacuum pump oil filter
and vacuum pump oil filter FL04 more than 100 hours element in time, otherwise
the vacuum pump will be
damaged.
When maintaining or
Clean the dirt or rust inside of the
replacing the filter
filter cartridge
element
Check the condition of the hose Every week
and each seal
Check the pressure switch Every 6 months
Check instrument’s accuracy Every 2 years