Part1 Installation
Before installing the chiller, please choose a place with flat base and broad-view surrounding.
The place should provide protection from corrosion, wind and water. Select matching water tower
according to the volume to be cooled (Forced air cooled type does not need water tower).
Configure pipelines and tubing of the chiller according to the magnitude of the machine. To avoid
bringing up high-pressure overloaded and affecting the effect of cooling and add usage of
electricity volume, please do not dwindle in size. (Notice: the chilled water pipe for the new
installed machine must contain thermocline ) The chiller of the forced air cooled type should be
installed 1 meters away from walls to avoid dispersing heat badly and bringing up high-pressure
overloaded and affecting the effect of cooling and add using of electricity volume, please do not
NOTICE: When choosing of the power supply load and the earth wire, please closely follow local
1. Please refer to the nameplate to check whether the voltage of power supply and phases match
the model and standard of the machine. (NOTICE: Power supply of 3HP and the above should
use 3 phases and 4 wires power supply. The phases and wires of 380~415V,50HZ are R,S,T
and N(Neutral conductor),the earth conductor is double colored wire labeled E; Power
supply below 3HP uses single phase for power supply. The single phase and wires of 220~240V,
50HZ are L(Phase line of power supply),N (Neutral conductor ) and E (Earth wire).
2 .Check whether the mouth of cooling water and circulating water are connected to the pipe and
keep the valve open (Please refer to the installation drawing)
3. Run the water pump only after you have filled the cooling water tank up with water or other
cooling medium. (Notice: Select the cooling medium according to the instructions)
4. Check whether the direction of the water pump and water tower fan are running adversely. (We
assume the phase of power supply of the water pump is three) Change any two phase lines to run
adversely, and close the switch after the phase lines having correctly been connected.
-2-
1. Be sure that the machine is correctly connected to power supply;
2. Close cooling switch, please make sure that the inlet and outlet valve of cooling water are
3. Close cooling switch again. Please make sure that the inlet and outlet valve of cooling water are
ON. The compressor will function automatically after time delay switch closed. Check and adjust
Part4 Attention
1. Do not run the cooling water pump without any water;
3. It is normal when the compressor stops working automatically because of the cooling
4. To avoid the evaporator freezing, the temperature switch should not be set under 5℃ except
5. To guarantee the cooling effect and keep the best operating state, please clear the condenser and
APPENDIX 1:
When the condenser disperses heat badly, the compressor works inefficiently and running
current will increase. When the pressure of the compressor of forced air cooled type increases to
24 kg/cm2, and that of water-cooled type is more than 20kg/cm2, the compressor will stop working
for high pressure protection. In this occasion, check whether the circulating cooling water is
normal, the temperature of the cooling water is too high, or water tower, fan and the pump runs
APPENDIX 2:
1. When the water temperature is over 5℃ and low pressure gauge indicates less than 2kg/ cm2m,
that is to say medium is insufficient. First, make up the place where cooling medium leaks and
then change the evaporation filter to evacuate water and fill in some cooling medium
2. When you find part of the cooling medium draw in some water, please instantly stop running
-3-
the machine and phone the service department of us to prevent further worse damage.
APPENDIX 3:
The best value of high pressure is 12.5~16 kg/cm2 when water-cooled compressor runs normally
and it should keep under 20kg/cm2 ( the compressor of forced air cooled type 14 ~ 18 kg/cm2
best).If water-cooled pressure is more than 20 kg/cm2 and the compressor of forced air cooled type
24 kg/cm2, the high pressure switch will be broken up. The best value of low pressure is 3.1~4.5
kg/cm2,but never under 2 kg/cm2.If the pressure is less than 2 kg/cm2, the low pressure switch will
If the pressure difference between high pressure and low pressure is small, it indicates that valve
elements of the compressor have been broken or damaged, please stop running the machine and
NOTICE: The precondition of all mentioned above is that the compressor is in operation, if the
APPENDIX 4:
The compressor does not work even if the indicator lights and all protection switches reveal there
1. Whether the temperature switch is adjusted too high or the switch is damaged;
7. Whether the level of water inner the water tank is too low
8. If the machine is without water tank, please check whether the freezing-water switch is
damaged.
Part5 Maintenance
1. Clear the condenser and the evaporator regularly to keep the machine running smoothly;
-4-
2. Keep the cooling tower clean, and clear it regularly. Make sure that there are no sundries and
3. If the machine is forced air-cooled type, please regularly clear the radiator and keep the face of
-5-
Error Causes Fault Clearance
Power supply normal , the whole 1 Fuse broken up ①Use standby fuse
machine cannot run ②Adverse relay error ②Change the adverse relay
Power supply switch broken up ① The load line of power supply ①Change a new one
earthing or short circuit ②Error for sure,change or repair
2 Compressor, Pump, motor the
earth wire error
Adverse phase ①Pump, Compressor and Fan run ① Exchange any two phase lines
adversely ②Checking the power supply line
②Phases not complete
Indicator light of dispersing heat ①High pressure switch broken up ① Clear the machine, keep
badly is on ②Low pressure switch broken up temperature below 40 ℃ ,follow
APPENDIX 1
②Change pressure switch
1.Operating Procedure
Connect the machine to the power supply, the system starts 6 seconds countdown. The zone PV
displays the version number, and the zone SV displays time. If the key “SET” is not pressed, the
(1)When main procedure will start working, the zone PV displays the acuter temperature, and the
zone SV displays the setting time. At this time, you can press the key “SET” to modify the
parameters by the key “UP” or “DOWN” and press the key “SET” again to exit.
-7-
(2)During the time of countdown, press the key “SET” to the interface of factory parameters
setting. Enter password “4561” and you can change input sequence by pressing the key “UP” and
press the key “DOWN” to modify the numbers you have just inputted. After entering password,
press the key “SET” to go into the interface of parameters setting. The zone PV displays “Pr00”, it
means the project 0.You can modify the parameters by pressing the key “UP” or “DOWN”. Press
the key “Comp1” to save and exit and press the key “SET” to exit the interface of parameters
(3)If there is any error, the zone PV will display “ERR” and the zone SV displays the error code.
You can refer to the table of error code to know about the error. Press the key “RESET” to cancel
the alarming sound. Press the key “RESET” to reset after the fault has been settled.
(4)The key “Comp1” and “Comp2” respectively stand for the running key of the compressor 1 and
the compressor 2.If either of the two keys is pressed, the indicator light led will be on. Only when
(5)Indicator Light:
(6)In main interface, press the key “SET” and hold on for a long time to enter the interface of
whether setting lock or not. Enter password “0021”(refer to②) and you can modify parameters by
pressing the key “UP” or “DOWN”. Lock the machine by pressing the key “LOCK” and Cancel
the state of being locked by pressing the key “OFF”. Press the key “SET” again to exit.
2.Parameters Setting
Name of the item Default Setup (Min.-Max.) Explanation of parameter setting
Pr-00 OFF(OFF-LOCK) Set the factory parameters
(LOCK: lock; OFF: cancel locking
Pr-01 OFF(OFF-ON) Check the phases(ON: closed; OFF: open)
-8-
Pr-03 OFF(OFF-ON) Compressor low pressure
(ON: closed; OFF: open)
Pr-04 OFF(OFF-ON) Compressor overloaded
(ON: closed; OFF: open)
Pr-05 OFF(OFF-ON) Too low pressure of freezing pump
(ON: closed; OFF: open)
Pr-06 OFF(OFF-ON) Freezing pump overloaded
(ON: closed; OFF: open)
Pr-07 OFF(OFF-ON) Too low pressure of cooling water/too hot
of cooling fan/line control switch
(ON: closed; OFF: open)
Pr-08 OFF(OFF-ON) Freezing pump/cooling fan overloaded(ON:
closed; OFF: open)
Pr-09 OFF(OFF-ON) Anti-frozen switch(ON: closed; OFF: open)
Pr-10 OFF(OFF-ON) Too low pressure of cooling water/line
control switch shifting setting
(NO: Too low pressure of cooling water;
ON: line control switch)
Pr-11 OFF(OFF-ON) Set temperature control
(OFF: unlock; LOCK: lock)
Pr-12 OFF(OFF-ON) Type of line control switch
(OFF: Plucking; ON:pulsation)
(Function only when Pr-10 is ON)
Pr-13 Backup
Pr-14 30℃(0℃~100℃) Control the max. temperature
(Only in Main interface)
Pr-15 5.0℃(-20℃~100℃) Control the min. temperature
(Only in Main interface)
Pr-16 0.0℃(-100℃~100℃) Temperature compensation
Pr-17 4.0℃(-20℃~100℃) Protection setting for too low temperature
of water outlet (Set the point of alarming)
Pr-18 12.0℃(-20℃~100℃) Set control temperature
Pr-19 1.0℃(0℃~100℃) Control the difference of temperature (used
in adjusting energy)
Pr-20 0(0~1) Selecting the type of machine(0:air-colled
type;1.water-cooled type)
Pr-21 2(1~2) Number of compressor
Pr-22 NO(NO ~US) Selecting ways of alarming output
(sound alarming when error happens; US:
NO: stop alarming output)
Pr-23 NO(NO ~US) Set auto running when the power is on(NO:
do not use .US: use)
Pr-24 Backup
Pr-25 10 seconds(0-255 seconds) Cooling pump running delay
Pr-26 10 seconds(0-255 seconds) Cooling pump/cooling fan running delay
Pr-27 180 seconds(0-255 seconds) Compressor anti-frequent-running time
delay
Pr-28 10 seconds(0-255 seconds) Water insufficient checking delay
-9-
Pr-29 20 seconds(0-255 seconds) Normal error checking delay
Pr-30 2 seconds(0-255 seconds) Phase error checking delay
Pr-31 5 seconds(0-255 seconds) Energy adjusting cycle
Pr-32 20 seconds(0-255 seconds) Set time for water insufficient checking
delay(Only after this period of time can
checking work start)
Pr-33~Pr40 Backup
4. Energy adjuster
(1)Run the machine: Press the key “PUMP” to run the machine --> Run the cooling pump -->
Time delay (It can be set) --> Run cooling fan -->Time delay (It can be set) -->Run the compressor
(2)Stop the machine: Press the key “STOP” to stop the machine -->Stop all the compressors-->
Time delay (It can be set) --> Stop the fan -->Time delay (It can be set) -->Stop the cooling pump.
(3)Energy adjusting
In the course of temperature increasing, when T>=Ts+△T , it will run the compressor; when
- 10 -
T<=Ts-△T,it will stop the compressor;
In the course of temperature increasing, when T>=Ts , it will run one compressor; when
T>=Ts+△T,it will run all the two compressors; when T<=Ts,it will stop one compressor; when
(4)When time delay finishes after all compressors stop, the machine has been shut down.
- 11 -
Sketch Map of Electrical Continuity
- 12 -
Functional Diagram of Water-cooled Type
(Capillary)
7.Evaporator
- 13 -
Functional Diagram of Forced Air-cooled Type
1.Compressor 8.Evaporator
(Capillary)
- 14 -