COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)

Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-233 Report no. : OHDS-23-233-T3
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW 522 Date of Sampling : 23 Jan 2023
Sampling method : Not given Date Sample Received : 24 Jan 2023
Sampled by : Nauman NF (CTTA#0763) Date Test Started : 30 Jan 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 30 Jan 2023
RFI No. : PTJ-SGCP-CIV-39151 ; CST RFI Date Reported : 30 Jan 2023
REF:PTJ-SGCP-CIV-39387
Location : GROUT FOR SACRAPER HANDLING FACILITY PAD BEAMS (2NOS) AND PEDESTALS (2NOS) (SCRAPER
AREA 36"DIA) AND CAMERA POLE PEDESTALS (2NOS), PANEL RACK FOUNDATION PEDESTALS (2NOS),
AREA LIGHTING POLE PEDESTALS ALF2(10NOS) (LIVE AREA) AT TINAT GGM.
Source of Grout : Time Batched (Hrs.) : 1310
Method of Placement : MANUAL Time Sampled (Hrs.) : 1314
Temp. of Mix (°C) : 23.6 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) :7

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231365 5 5 5 25 286 2.288 86 351 4988 34.4
2 231366 5 5 5 25 283 2.264 89 363 5162 35.6
3 231367 5 5 5 25 285 2.280 90 367 5220 36.0

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-233 Report no. : OHDS-23-233-T4
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW 522 Date of Sampling : 23 Jan 2023
Sampling method : Not given Date Sample Received : 24 Jan 2023
Sampled by : Nauman NF (CTTA#0763) Date Test Started : 20 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 20 Feb 2023
RFI No. : PTJ-SGCP-CIV-39151 ; CST RFI Date Reported : 02 Feb 2023
REF:PTJ-SGCP-CIV-40217
Location : GROUT FOR SACRAPER HANDLING FACILITY PAD BEAMS (2NOS) AND PEDESTALS (2NOS) (SCRAPER
AREA 36"DIA) AND CAMERA POLE PEDESTALS (2NOS), PANEL RACK FOUNDATION PEDESTALS (2NOS),
AREA LIGHTING POLE PEDESTALS ALF2(10NOS) (LIVE AREA) AT TINAT GGM.
Source of Grout : Time Batched (Hrs.) : 1310
Method of Placement : MANUAL Time Sampled (Hrs.) : 1314
Temp. of Mix (°C) : 23.6 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) : 28

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231368 5 5 5 25 289 2.312 99 404 5742 39.6
2 231369 5 5 5 25 285 2.280 94 383 5452 37.6
3 231370 5 5 5 25 287 2.296 97 396 5625 38.8

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
SLUMP AND TEMPERATURE TEST
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-239 Report no. : OHDS-23-239-T1
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR (3)- 35INP-20 Date of Sampling : 24 Jan 2023
Sampling method : C172 Date Sample Received : N/A
Sampled by : M.Abrar A (CTTA#1218) Date Test Started : 25 Jan 2023
Tested by : M.Abrar A(CTTA#1218) Date Test Completed : 26 Jan 2023
RFI No. : PTJ-SGCP-CIV-39209-39169-39149-39062-39150 Date Reported : 27 Jan 2023
Location : Concrete for Fence Brace Posts (24nos) North, East Side at Tinat GGM..REF RFI No PTJ-SGCP-CIV-39062. for Fence Anchor Beams
(9nos) 27m long and Brace Posts (9nos) North, East Side at Tinat GGM..REF RFI No PTJ-SGCP-CIV-39149. for Fence Line Posts (26nos)
at Water Injection Manifold Tinat GCP-1..REF RFI No PTJ-SGCP-CIV-39156.for Flange pit, Manhole MH side walls (Live area) at
HARADH REMOTE HEADER K10..REF RFI No PTJ-SGCP-CIV-39169. for open cut trench of 8'' rtr from Catch Basin (CB-2218A) to
16'' rtr line and 4'' rtr line to 16'' rtr line near inlet area at inside HDGP..REF RFI No PTJ-SGCP-CIV-39209.
Method of Placement : PUMP

Time Time Mix Air Air Unit


Test Truck / Ticket Slump Volume
Sl.No. Batched Sampled Temp Content Temp Weight Remarks
# No. (mm) (M³)
(Hours) (Hours) (°C) (%) (°C) (kg/M²)
1 1 4866-21109 1110 1202 28 150 21 09 Sampled # 08
2 2 4814-21098 1155 1330 27 190 12

Test method : ASTM C 172,ASTM C143/C143M,ASTM C1064/C1064M,ASTM C31/C31M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, Mr. Muhammed Almas Khan, Lab Manager,
(CTTA#0278) (CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-01 07 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CONCRETE CYLINDERS
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-239 Report no. : OHDS-23-239-T2
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR (3)- 35INP-20 Date of Sampling : 24 Jan 2023
Sampling method : C172 Date Sample Received : 25 Jan 2023
Sampled by : M.Abrar A (CTTA#1218) Date Test Started : 31 Jan 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 31 Jan 2023
RFI No. : PTJ-SGCP-CIV-39431 Date Reported : 31 Jan 2023
Location : Concrete for Fence Brace Posts (24nos) North, East Side at Tinat GGM..REF RFI No PTJ-SGCP-CIV-39062. for Fence Anchor Beams
(9nos) 27m long and Brace Posts (9nos) North, East Side at Tinat GGM..REF RFI No PTJ-SGCP-CIV-39149. for Fence Line Posts (26nos)
at Water Injection Manifold Tinat GCP-1..REF RFI No PTJ-SGCP-CIV-39156.for Flange pit, Manhole MH side walls (Live area) at
HARADH REMOTE HEADER K10..REF RFI No PTJ-SGCP-CIV-39169. for open cut trench of 8'' rtr from Catch Basin (CB-2218A) to
16'' rtr line and 4'' rtr line to 16'' rtr line near inlet area at inside HDGP..REF RFI No PTJ-SGCP-CIV-39209.
Source of Concrete : HACO Time Batched (Hrs.) : 1110
Method of Placement : PUMP Truck or Batch No. : 4866-21109
Temp. of Mix (°C) : 28 Time Sampled (Hrs.) : 1202
Curing Temp. (°C) : 23±2 Structure Represented : See Location
Air Content : Slump : 150
Strength Value : 35 Mpa
Dial Compressive Strength
Sl.No. Specimen Dia. Height Area Weight Density Age
Reading Type of Fracture
No. (cm) (cm) (cm²) (g) (kg/m³) (Days) kg/cm² PSI MPa
(kN)
Lab curing
1 231389 15.0 30.0 176.7 12920 2437 7 643 371 5280 36.4 Type1 (Cone)
2 231390 15.0 29.9 176.7 12894 2441 7 605 349 4960 34.2 Type4 (Diagonal)

Site curing
3 231391 15.0 29.9 176.7 12883 2438 7 559 322 4590 31.6 Type4 (Diagonal)
4 231392 15.0 30.0 176.7 12911 2436 7 584 337 4790 33.0 Type2 (Cone & Vertical)

Test method : ASTM C39/C 39M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-02 09 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CONCRETE CYLINDERS
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-239 Report no. : OHDS-23-239-T3
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR (3)- 35INP-20 Date of Sampling : 24 Jan 2023
Sampling method : C172 Date Sample Received : 25 Jan 2023
Sampled by : M.Abrar A (CTTA#1218) Date Test Started : 21 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 21 Feb 2023
RFI No. : PTJ-SGCP-CIV-40268 Date Reported : 21 Feb 2023
Location : Concrete for Fence Brace Posts (24nos) North, East Side at Tinat GGM..REF RFI No PTJ-SGCP-CIV-39062. for
Fence Anchor Beams (9nos) 27m long and Brace Posts (9nos) North, East Side at Tinat GGM..REF RFI No
PTJ-SGCP-CIV-39149. for Fence Line Posts (26nos) at Water Injection Manifold Tinat GCP-1..REF RFI No
PTJ-SGCP-CIV-39156.for Flange pit, Manhole MH side walls (Live area) at HARADH REMOTE HEADER
K10..REF RFI No PTJ-SGCP-CIV-39169. for open cut trench of 8'' rtr from Catch Basin (CB-2218A) to 16'' rtr line and
4'' rtr line to 16'' rtr line near inlet area at inside HDGP..REF RFI No PTJ-SGCP-CIV-39209.
Source of Concrete : HACO Time Batched (Hrs.) : 1110
Method of Placement : PUMP Truck or Batch No. : 4866-21109
Temp. of Mix (°C) : 28 Time Sampled (Hrs.) : 1202
Curing Temp. (°C) : 23±2 Structure Represented : See Location
Air Content : Slump : 150
Strength Value : 35 Mpa
Dial Compressive Strength
Sl.No. Specimen Dia. Height Area Weight Density Age
Reading Type of Fracture Result
No. (cm) (cm) (cm²) (g) (kg/m³) (Days) kg/cm² PSI MPa
(kN)
Lab curing
1 231393 15.0 29.9 176.7 12899 2441 28 771 445 6330 43.6 Type1 (Cone) Passed
2 231394 15.0 30.0 176.7 12929 2439 28 785 453 6440 44.4 Type4 (Diagonal) Passed

Site curing
3 231395 15.0 30.0 176.7 12852 2424 28 747 431 6130 42.3 Type2 (Cone & Vertical) Passed
4 231396 15.0 29.9 176.7 12819 2426 28 760 438 6240 43.0 Type1 (Cone) Passed

Test method : ASTM C39/C 39M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-02 09 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
SLUMP AND TEMPERATURE TEST
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-269 Report no. : OHDS-23-269-T1
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR (3)- 35INP-20 Date of Sampling : 25 Jan 2023
Sampling method : C172 Date Sample Received : N/A
Sampled by : M.Abrar A (CTTA#1218) Date Test Started : 25 Jan 2023
Tested by : M.Abrar A(CTTA#1218) Date Test Completed : 26 Jan 2023
RFI No. : PTJ-SGCP-CIV-39228-39119-39174-39235-39070-39073 Date Reported : 27 Jan 2023
Location :
Method of Placement : PUMP

Time Time Mix Air Air Unit


Test Truck / Ticket Slump Volume
Sl.No. Batched Sampled Temp Content Temp Weight Remarks
# No. (mm) (M³)
(Hours) (Hours) (°C) (%) (°C) (kg/M²)
1 1 4814-21052 925 1000 26.5 120 19.5 12 Sampled # 08
2 2 4866-21043 1105 1200 26.5 165 07

Test method : ASTM C 172,ASTM C143/C143M,ASTM C1064/C1064M,ASTM C31/C31M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, Mr. Muhammed Almas Khan, Lab Manager,
(CTTA#0278) (CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-01 07 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CONCRETE CYLINDERS
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-269 Report no. : OHDS-23-269-T2
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR (3)- 35INP-20 Date of Sampling : 25 Jan 2023
Sampling method : C172 Date Sample Received : 26 Jan 2023
Sampled by : M.Abrar A (CTTA#1218) Date Test Started : 01 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 01 Feb 2023
RFI No. : PTJ-SGCP-CIV-39480 Date Reported : 01 Feb 2023
Location :
Source of Concrete : HACO Time Batched (Hrs.) : 925
Method of Placement : PUMP Truck or Batch No. : 4814-21052
Temp. of Mix (°C) : 26.5 Time Sampled (Hrs.) : 1000
Curing Temp. (°C) : 23±2 Structure Represented : See Location
Air Content : Slump : 120
Strength Value : 35 Mpa
Dial Compressive Strength
Sl.No. Specimen Dia. Height Area Weight Density Age
Reading Type of Fracture
No. (cm) (cm) (cm²) (g) (kg/m³) (Days) kg/cm² PSI MPa
(kN)
Lab curing
1 231467 15.1 29.9 179.1 13070 2441 7 686 390 5550 38.3 Type1 (Cone)
2 231468 15.1 29.9 179.1 13056 2438 7 583 332 4720 32.5 Type4 (Diagonal)

Site curing
3 231469 15.1 29.9 179.1 13042 2435 7 612 348 4950 34.2 Type2 (Cone & Vertical)
4 231470 15.1 29.8 179.1 13017 2439 7 616 351 4990 34.4 Type1 (Cone)

Test method : ASTM C39/C 39M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-02 09 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CONCRETE CYLINDERS
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-269 Report no. : OHDS-23-269-T3
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR (3)- 35INP-20 Date of Sampling : 25 Jan 2023
Sampling method : C172 Date Sample Received : 26 Jan 2023
Sampled by : M.Abrar A (CTTA#1218) Date Test Started : 22 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 22 Feb 2023
RFI No. : PTJ-SGCP-CIV-40311 Date Reported : 22 Feb 2023
Location :
Source of Concrete : HACO Time Batched (Hrs.) : 925
Method of Placement : PUMP Truck or Batch No. : 4814-21052
Temp. of Mix (°C) : 26.5 Time Sampled (Hrs.) : 1000
Curing Temp. (°C) : 23±2 Structure Represented : See Location
Air Content : Slump : 120
Strength Value : 35 Mpa
Dial Compressive Strength
Sl.No. Specimen Dia. Height Area Weight Density Age
Reading Type of Fracture Result
No. (cm) (cm) (cm²) (g) (kg/m³) (Days) kg/cm² PSI MPa
(kN)
Lab curing
1 231471 15.1 29.9 179.1 13077 2442 28 853 485 6910 47.6 Type1 (Cone) Passed
2 231472 15.1 29.8 179.1 13039 2443 28 817 465 6610 45.6 Type2 (Cone & Vertical) Passed

Site curing
3 231473 15.1 29.8 179.1 12948 2426 28 732 417 5930 40.9 Type4 (Diagonal) Passed
4 231474 15.1 29.9 179.1 12981 2424 28 754 429 6100 42.1 Type2 (Cone & Vertical) Passed

Test method : ASTM C39/C 39M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-02 09 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-273 Report no. : OHDS-23-273-T3
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW 522 Date of Sampling : 25 Jan 2023
Sampling method : Not given Date Sample Received : 26 Jan 2023
Sampled by : Asim Ali M (CTTA#0894) Date Test Started : 01 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 01 Feb 2023
RFI No. : PTJ-SGCP-CIV-39166 ; CST RFI Date Reported : 01 Feb 2023
REF:PTJ-SGCP-CIV-39481
Location : GROUT FOR SACRAPER HANDLING FACILITY PAD BEAMS (2NOS) AND PEDESTALS (2NOS) (SCRAPER
AREA 36"DIA) AND CAMERA POLE PEDESTALS(2NOS),PANEL RACK FOUNDATION PEDESTALS (2NOS),
AREA LIGHTING POLE PEDESTALS ALF2 (10NOS) (LIVE AREA) AT TINAT GGM.
Source of Grout : Time Batched (Hrs.) : 1115
Method of Placement : MANUAL Time Sampled (Hrs.) : 1120
Temp. of Mix (°C) : 22.0 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) :7

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231499 5 5 5 25 283 2.264 87 355 5045 34.8
2 231500 5 5 5 25 286 2.288 92 375 5335 36.8
3 231501 5 5 5 25 284 2.272 82 334 4756 32.8

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-273 Report no. : OHDS-23-273-T4
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW 522 Date of Sampling : 25 Jan 2023
Sampling method : Not given Date Sample Received : 26 Jan 2023
Sampled by : Asim Ali M (CTTA#0894) Date Test Started : 22 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 22 Feb 2023
RFI No. : PTJ-SGCP-CIV-39166 ; CST RFI Date Reported : 23 Feb 2023
REF:PTJ-SGCP-CIV-40312
Location : GROUT FOR SACRAPER HANDLING FACILITY PAD BEAMS (2NOS) AND PEDESTALS (2NOS) (SCRAPER
AREA 36"DIA) AND CAMERA POLE PEDESTALS(2NOS),PANEL RACK FOUNDATION PEDESTALS (2NOS),
AREA LIGHTING POLE PEDESTALS ALF2 (10NOS) (LIVE AREA) AT TINAT GGM.
Source of Grout : Time Batched (Hrs.) : 1115
Method of Placement : MANUAL Time Sampled (Hrs.) : 1120
Temp. of Mix (°C) : 22.0 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) : 28

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231502 5 5 5 25 288 2.304 116 473 6728 46.4
2 231503 5 5 5 25 285 2.280 118 481 6843 47.2
3 231504 5 5 5 25 287 2.296 120 489 6959 48.0

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-274 Report no. : OHDS-23-274-T3
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW 522 Date of Sampling : 25 Jan 2023
Sampling method : Not given Date Sample Received : 26 Jan 2023
Sampled by : Iqbal H.M (CTTA#0904) Date Test Started : 01 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 01 Feb 2023
RFI No. : PTJ-SGCP-CIV-39266 ; CST RFI Date Reported : 01 Feb 2023
REF:PTJ-SGCP-CIV-39482
Location : GROUT FOR PIPE SUPPORT FOUNDATIONS PEDESTALS PS-01, P-01A, PS-02, H2S/LEL (4NOS), OPTF SKID
TYPE-1 FOUNDATIONS PEDESTALS F1(5NOS),F3(1NO) AT MDRK OPTF-19.
Source of Grout : Time Batched (Hrs.) : 1430
Method of Placement : MANUAL Time Sampled (Hrs.) : 1435
Temp. of Mix (°C) : 21.7 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) :7

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231505 5 5 5 25 290 2.320 100 408 5799 40.0
2 231506 5 5 5 25 287 2.296 106 432 6147 42.4
3 231507 5 5 5 25 289 2.312 106 432 6147 42.4

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-274 Report no. : OHDS-23-274-T4
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW 522 Date of Sampling : 25 Jan 2023
Sampling method : Not given Date Sample Received : 26 Jan 2023
Sampled by : Iqbal H.M (CTTA#0904) Date Test Started : 22 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 22 Feb 2023
RFI No. : PTJ-SGCP-CIV-39266 ; CST RFI Date Reported : 22 Feb 2023
REF:PTJ-SGCP-CIV-40313
Location : GROUT FOR PIPE SUPPORT FOUNDATIONS PEDESTALS PS-01, P-01A, PS-02, H2S/LEL (4NOS), OPTF SKID
TYPE-1 FOUNDATIONS PEDESTALS F1(5NOS),F3(1NO) AT MDRK OPTF-19.
Source of Grout : Time Batched (Hrs.) : 1430
Method of Placement : MANUAL Time Sampled (Hrs.) : 1435
Temp. of Mix (°C) : 21.7 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) : 28

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231508 5 5 5 25 289 2.312 129 526 7481 51.6
2 231509 5 5 5 25 293 2.344 133 542 7713 53.2
3 231510 5 5 5 25 291 2.328 134 546 7771 53.6

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
SLUMP AND TEMPERATURE TEST
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-276 Report no. : OHDS-23-276-T1
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR(3)-35INP-20 Date of Sampling : 26 Jan 2023
Sampling method : C172 Date Sample Received : N/A
Sampled by : Asim Ali M (CTTA#0894) Date Test Started : 27 Jan 2023
Tested by : Asim Ali M(CTTA#0894) Date Test Completed : 28 Jan 2023
RFI No. : PTJ-SGCP-CIV-39217-39237-39257-39250-39222-39212 Date Reported : 29 Jan 2023
Location : Concrete for Fence Brace Posts (23nos) and Fence Anchor Beams (4nos) at BURN PIT Tinat Remote Header-C.REF RFI No
PTJ-SGCP-CIV-39212. for Fence Anchor Beams(3nos) West Side Near Walk Gate at Tinat Remote Header-A.REF RFI No
PTJ-SGCP-CIV-39222.for Fence Line Posts (33nos) and Corner Posts (4nos) at Water Injection Manifold Tinat GCP-1.REF RFI No
PTJ-SGCP-CIV-39250. for Burnpit Control Rack Foundation(1no) and Burnpit Propane Bottle Rack Foundation TYPE-2(1no) at BURN
PIT Tinat Remote Header-C.REF RFI No PTJ-SGCP-CIV-39257. for Stair Foundations SF(03nos) and Ladder Foundations LF(1nos) at
MDRK Remote Header-D.REF RFI No PTJ-SGCP-CIV-39217. .for scraper handling facility foundation (SHF) Pad beams (02nos) and curb
wall and pedestals (02nos) scraper handling facility foundation (SHF) for 20" to 36" scraper-1 at MDRK RH-B.REF RFI No
PTJ-SGCP-CIV-39237.
Method of Placement : PUMP

Time Time Mix Air Air Unit


Test Truck / Ticket Slump Volume
Sl.No. Batched Sampled Temp Content Temp Weight Remarks
# No. (mm) (M³)
(Hours) (Hours) (°C) (%) (°C) (kg/M²)
1 1 4866-21177 1135 1300 28.5 170 23 07 Sampled # 08
2 2 4810-21179 1220 1320 27 175 12

Test method : ASTM C 172,ASTM C143/C143M,ASTM C1064/C1064M,ASTM C31/C31M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, Mr. Muhammed Almas Khan, Lab Manager,
(CTTA#0278) (CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-01 07 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CONCRETE CYLINDERS
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-276 Report no. : OHDS-23-276-T2
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR(3)-35INP-20 Date of Sampling : 26 Jan 2023
Sampling method : C172 Date Sample Received : 27 Jan 2023
Sampled by : Asim Ali M (CTTA#0894) Date Test Started : 02 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 02 Feb 2023
RFI No. : PTJ-SGCP-CIV-39514 Date Reported : 02 Feb 2023
Location : Concrete for Fence Brace Posts (23nos) and Fence Anchor Beams (4nos) at BURN PIT Tinat Remote Header-C.REF RFI No
PTJ-SGCP-CIV-39212. for Fence Anchor Beams(3nos) West Side Near Walk Gate at Tinat Remote Header-A.REF RFI No
PTJ-SGCP-CIV-39222.for Fence Line Posts (33nos) and Corner Posts (4nos) at Water Injection Manifold Tinat GCP-1.REF RFI No
PTJ-SGCP-CIV-39250. for Burnpit Control Rack Foundation(1no) and Burnpit Propane Bottle Rack Foundation TYPE-2(1no) at BURN
PIT Tinat Remote Header-C.REF RFI No PTJ-SGCP-CIV-39257. for Stair Foundations SF(03nos) and Ladder Foundations LF(1nos) at
MDRK Remote Header-D.REF RFI No PTJ-SGCP-CIV-39217. .for scraper handling facility foundation (SHF) Pad beams (02nos) and curb
wall and pedestals (02nos) scraper handling facility foundation (SHF) for 20" to 36" scraper-1 at MDRK RH-B.REF RFI No
PTJ-SGCP-CIV-39237.
Source of Concrete : HACO Time Batched (Hrs.) : 1135
Method of Placement : PUMP Truck or Batch No. : 4866-21177
Temp. of Mix (°C) : 28.5 Time Sampled (Hrs.) : 1300
Curing Temp. (°C) : 23±2 Structure Represented : See Location
Air Content : Slump : 170
Strength Value : 35 Mpa
Dial Compressive Strength
Sl.No. Specimen Dia. Height Area Weight Density Age
Reading Type of Fracture
No. (cm) (cm) (cm²) (g) (kg/m³) (Days) kg/cm² PSI MPa
(kN)
Lab curing
1 231517 15.0 29.9 176.7 12910 2444 7 693 400 5690 39.2 Type4 (Diagonal)
2 231518 15.0 30.0 176.7 12969 2447 7 675 389 5540 38.2 Type1 (Cone)

Site curing
3 231519 15.0 30.0 176.7 12940 2441 7 690 398 5660 39.0 Type2 (Cone & Vertical)
4 231520 15.0 29.9 176.7 12913 2444 7 686 396 5630 38.8 Type4 (Diagonal)

Test method : ASTM C39/C 39M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-02 09 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CONCRETE CYLINDERS
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-276 Report no. : OHDS-23-276-T3
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR(3)-35INP-20 Date of Sampling : 26 Jan 2023
Sampling method : C172 Date Sample Received : 27 Jan 2023
Sampled by : Asim Ali M (CTTA#0894) Date Test Started : 23 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 23 Feb 2023
RFI No. : PTJ-SGCP-CIV-40315 Date Reported : 23 Feb 2023
Location : Concrete for Fence Brace Posts (23nos) and Fence Anchor Beams (4nos) at BURN PIT Tinat Remote
Header-C.REF RFI No PTJ-SGCP-CIV-39212. for Fence Anchor Beams(3nos) West Side Near Walk Gate at Tinat
Remote Header-A.REF RFI No PTJ-SGCP-CIV-39222.for Fence Line Posts (33nos) and Corner Posts (4nos) at
Water Injection Manifold Tinat GCP-1.REF RFI No PTJ-SGCP-CIV-39250. for Burnpit Control Rack
Foundation(1no) and Burnpit Propane Bottle Rack Foundation TYPE-2(1no) at BURN PIT Tinat Remote
Header-C.REF RFI No PTJ-SGCP-CIV-39257. for Stair Foundations SF(03nos) and Ladder Foundations LF(1nos) at
MDRK Remote Header-D.REF RFI No PTJ-SGCP-CIV-39217. .for scraper handling facility foundation (SHF) Pad
beams (02nos) and curb wall and pedestals (02nos) scraper handling facility foundation (SHF) for 20" to 36"
scraper-1 at MDRK RH-B.REF RFI No PTJ-SGCP-CIV-39237.
Source of Concrete : HACO Time Batched (Hrs.) : 1135
Method of Placement : PUMP Truck or Batch No. : 4866-21177
Temp. of Mix (°C) : 28.5 Time Sampled (Hrs.) : 1300
Curing Temp. (°C) : 23±2 Structure Represented : See Location
Air Content : Slump : 170
Strength Value : 35 Mpa
Dial Compressive Strength
Sl.No. Specimen Dia. Height Area Weight Density Age
Reading Type of Fracture Result
No. (cm) (cm) (cm²) (g) (kg/m³) (Days) kg/cm² PSI MPa
(kN)
Lab curing
1 231521 15.0 30.0 176.7 12974 2447 28 844 487 6930 47.7 Type4 (Diagonal) Passed
2 231522 15.0 30.0 176.7 12959 2445 28 842 486 6910 47.6 Type1 (Cone) Passed

Site curing
3 231523 15.0 29.9 176.7 12844 2431 28 759 438 6230 42.9 Type2 (Cone & Vertical) Passed
4 231524 15.0 30.0 176.7 12876 2429 28 816 471 6690 46.2 Type4 (Diagonal) Passed

Test method : ASTM C39/C 39M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-02 09 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-287 Report no. : OHDS-23-287-T3
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW Date of Sampling : 26 Jan 2023
Sampling method : Not given Date Sample Received : 27 Jan 2023
Sampled by : Asim Ali M (CTTA#0894) Date Test Started : 02 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 02 Feb 2023
RFI No. : PTJ-SGCP-CIV-39241 ; CST RFI Date Reported : 02 Feb 2023
REF:PTJ-SGCP-CIV-39515
Location : GROUT FOR PANEL RACK FOUNDATIONS (03NOS) AT MDRK REMOTE HEADER-B.
Source of Grout : Time Batched (Hrs.) : 1310
Method of Placement : MANUAL Time Sampled (Hrs.) : 1315
Temp. of Mix (°C) : 23.0 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) :7

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231605 5 5 5 25 281 2.248 86 351 4988 34.4
2 231606 5 5 5 25 284 2.272 90 367 5220 36.0
3 231607 5 5 5 25 283 2.264 94 383 5452 37.6

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-287 Report no. : OHDS-23-287-T4
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW Date of Sampling : 26 Jan 2023
Sampling method : Not given Date Sample Received : 27 Jan 2023
Sampled by : Asim Ali M (CTTA#0894) Date Test Started : 23 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 23 Feb 2023
RFI No. : PTJ-SGCP-CIV-39241 ; CST RFI Date Reported : 23 Feb 2023
REF:PTJ-SGCP-CIV-40316
Location : GROUT FOR PANEL RACK FOUNDATIONS (03NOS) AT MDRK REMOTE HEADER-B.
Source of Grout : Time Batched (Hrs.) : 1310
Method of Placement : MANUAL Time Sampled (Hrs.) : 1315
Temp. of Mix (°C) : 23.0 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) : 28

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231608 5 5 5 25 286 2.288 128 522 7423 51.2
2 231609 5 5 5 25 283 2.264 119 485 6901 47.6
3 231610 5 5 5 25 285 2.280 132 538 7655 52.8

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
SLUMP AND TEMPERATURE TEST
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-309 Report no. : OHDS-23-309-T1
Source of sample : HACO Lab Project No. : PH22-007
Sample description : 35MPa Date of Sampling : 28 Jan 2023
Sampling method : C172 Date Sample Received : N/A
Sampled by : M.Almas K (CTTA#0709) Date Test Started : 28 Jan 2023
Tested by : M.Almas K(CTTA#0709) Date Test Completed : 29 Jan 2023
RFI No. : PTJ-SGCP-CIV-39350-39347-39253-39300 Date Reported : 30 Jan 2023
Location : Concrete for Fence Brace Posts (42nos) at MLV-5(HRDH-462) Main Line Valve Station..REF RFI No PTJ-SGCP-CIV-39253. for Fence
Brace Posts (40nos) North, East, South Side at Tinat GGM..REF RFI No PTJ-SGCP-CIV-39300.For Base Slab of Flange pit, Manhole
MH-1(Live area) at HARADH REMOTE HEADER K8..REF RFI No PTJ-SGCP-CIV-39347. for Brace post foundations (19nos) at west,
East & North side(live area) and Fence Anchor Beam (5nos) beside 5Mtr Sliding Gate(West side , Live area) at Remote Header RH-K8..REF
RFI No PTJ-SGCP-CIV-39350.
Method of Placement : CHUTE

Time Time Mix Air Air Unit


Test Truck / Ticket Slump Volume
Sl.No. Batched Sampled Temp Content Temp Weight Remarks
# No. (mm) (M³)
(Hours) (Hours) (°C) (%) (°C) (kg/M²)
1 1 4814-21335 1145 1235 26.7 140 25.8 8 Sampled # 08
2 2 4866-21338 1215 1315 28 170 12

Test method : ASTM C 172,ASTM C143/C143M,ASTM C1064/C1064M,ASTM C31/C31M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, Mr. Muhammed Almas Khan, Lab Manager,
(CTTA#0278) (CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-01 07 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CONCRETE CYLINDERS
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-309 Report no. : OHDS-23-309-T2
Source of sample : HACO Lab Project No. : PH22-007
Sample description : 35MPa Date of Sampling : 28 Jan 2023
Sampling method : C172 Date Sample Received : 29 Jan 2023
Sampled by : M.Almas K (CTTA#0709) Date Test Started : 04 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 04 Feb 2023
RFI No. : PTJ-SGCP-CIV-39567 Date Reported : 02 Feb 2023
Location : Concrete for Fence Brace Posts (42nos) at MLV-5(HRDH-462) Main Line Valve Station..REF RFI No PTJ-SGCP-CIV-39253. for Fence
Brace Posts (40nos) North, East, South Side at Tinat GGM..REF RFI No PTJ-SGCP-CIV-39300.For Base Slab of Flange pit, Manhole
MH-1(Live area) at HARADH REMOTE HEADER K8..REF RFI No PTJ-SGCP-CIV-39347. for Brace post foundations (19nos) at west,
East & North side(live area) and Fence Anchor Beam (5nos) beside 5Mtr Sliding Gate(West side , Live area) at Remote Header RH-K8..REF
RFI No PTJ-SGCP-CIV-39350.
Source of Concrete : HACO Time Batched (Hrs.) : 1145
Method of Placement : CHUTE Truck or Batch No. : 4814-21335
Temp. of Mix (°C) : 26.7 Time Sampled (Hrs.) : 1235
Curing Temp. (°C) : 23±2 Structure Represented : See Location
Air Content : Slump : 140
Strength Value : 35 Mpa
Dial Compressive Strength
Sl.No. Specimen Dia. Height Area Weight Density Age
Reading Type of Fracture
No. (cm) (cm) (cm²) (g) (kg/m³) (Days) kg/cm² PSI MPa
(kN)
Lab curing
1 231677 15.1 29.8 179.1 13007 2437 7 692 394 5600 38.6 Type1 (Cone)
2 231678 15.1 29.9 179.1 13034 2434 7 707 402 5720 39.5 Type2 (Cone & Vertical)

Site curing
3 231679 15.1 29.9 179.1 13022 2432 7 736 419 5960 41.1 Type4 (Diagonal)
4 231680 15.1 29.8 179.1 12996 2435 7 685 390 5550 38.2 Type1 (Cone)

Test method : ASTM C39/C 39M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-02 09 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CONCRETE CYLINDERS
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-309 Report no. : OHDS-23-309-T3
Source of sample : HACO Lab Project No. : PH22-007
Sample description : 35MPa Date of Sampling : 28 Jan 2023
Sampling method : C172 Date Sample Received : 29 Jan 2023
Sampled by : M.Almas K (CTTA#0709) Date Test Started : 25 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 25 Feb 2023
RFI No. : PTJ-SGCP-CIV-40401 Date Reported : 25 Feb 2023
Location : Concrete for Fence Brace Posts (42nos) at MLV-5(HRDH-462) Main Line Valve Station..REF RFI No
PTJ-SGCP-CIV-39253. for Fence Brace Posts (40nos) North, East, South Side at Tinat GGM..REF RFI No
PTJ-SGCP-CIV-39300.For Base Slab of Flange pit, Manhole MH-1(Live area) at HARADH REMOTE HEADER
K8..REF RFI No PTJ-SGCP-CIV-39347. for Brace post foundations (19nos) at west, East & North side(live area)
and Fence Anchor Beam (5nos) beside 5Mtr Sliding Gate(West side , Live area) at Remote Header RH-K8..REF RFI
No PTJ-SGCP-CIV-39350.
Source of Concrete : HACO Time Batched (Hrs.) : 1145
Method of Placement : CHUTE Truck or Batch No. : 4814-21335
Temp. of Mix (°C) : 26.7 Time Sampled (Hrs.) : 1235
Curing Temp. (°C) : 23±2 Structure Represented : See Location
Air Content : Slump : 140
Strength Value : 35 Mpa
Dial Compressive Strength
Sl.No. Specimen Dia. Height Area Weight Density Age
Reading Type of Fracture Result
No. (cm) (cm) (cm²) (g) (kg/m³) (Days) kg/cm² PSI MPa
(kN)
Lab curing
1 231681 15.1 29.9 179.1 13048 2437 28 829 472 6710 46.3 Type4 (Diagonal) Passed
2 231682 15.1 29.9 179.1 13062 2439 28 905 515 7330 50.5 Type1 (Cone) Passed

Site curing
3 231683 15.1 29.8 179.1 12938 2424 28 821 467 6650 45.8 Type2 (Cone & Vertical) Passed
4 231684 15.1 29.9 179.1 12969 2422 28 845 481 6840 47.2 Type1 (Cone) Passed

Test method : ASTM C39/C 39M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-02 09 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-312 Report no. : OHDS-23-312-T3
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW 522 Date of Sampling : 28 Jan 2023
Sampling method : Not given Date Sample Received : 29 Jan 2023
Sampled by : Nauman NF (CTTA#0763) Date Test Started : 04 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 04 Feb 2023
RFI No. : PJT-SGCP-CIV-39568 Date Reported : 04 Feb 2023
Location : GROUT FOR PIPERACK FOUNDATIONS PEDESTALS F2 (4NOS), F77 (2NO) GL A-B-C/1-2 (LIVE AREA) AT
TINAT GGM.
Source of Grout : Time Batched (Hrs.) : 1036
Method of Placement : MANUAL Time Sampled (Hrs.) : 1040
Temp. of Mix (°C) : 22.7 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) :7

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231705 5 5 5 25 281 2.248 68 277 3944 27.2
2 231706 5 5 5 25 285 2.280 69 281 4001 27.6
3 231707 5 5 5 25 284 2.272 72 294 4176 28.8

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-312 Report no. : OHDS-23-312-T4
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW 522 Date of Sampling : 28 Jan 2023
Sampling method : Not given Date Sample Received : 29 Jan 2023
Sampled by : Nauman NF (CTTA#0763) Date Test Started : 25 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 25 Feb 2023
RFI No. : PJT-SGCP-CIV-40402 Date Reported : 25 Feb 2023
Location : GROUT FOR PIPERACK FOUNDATIONS PEDESTALS F2 (4NOS), F77 (2NO) GL A-B-C/1-2 (LIVE AREA) AT
TINAT GGM.
Source of Grout : Time Batched (Hrs.) : 1036
Method of Placement : MANUAL Time Sampled (Hrs.) : 1040
Temp. of Mix (°C) : 22.7 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) : 28

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231708 5 5 5 25 286 2.288 156 636 9047 62.4
2 231709 5 5 5 25 284 2.272 141 575 8177 56.4
3 231710 5 5 5 25 283 2.264 140 571 8119 56.0

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
SLUMP AND TEMPERATURE TEST
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-331 Report no. : OHDS-23-331-T1
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR-(3)-35INP-20 Date of Sampling : 29 Jan 2023
Sampling method : C172 Date Sample Received : N/A
Sampled by : Asim Ali M (CTTA#0894) Date Test Started : 30 Jan 2023
Tested by : Asim Ali M(CTTA#0894) Date Test Completed : 31 Jan 2023
RFI No. : PTJ-SGCP-CIV-39309-39378-39358 Date Reported : 01 Feb 2023
Location : Concrete For Manhole MH-1(1no) at Inside Aramco Live Area Haradh Remote Header-K5.REF RFI No PTJ-SGCP-CIV-39309.for Fence
Line Posts (6nos) and Corner Posts (3nos) at Water Injection Manifold Tinat GCP-1. REF RFI No PTJ-SGCP-CIV-39358.for Line post
foundations(16nos) and Corner post foundation(1no) (East & North side) at Burn PIT Haradh Remote Header -K14.REF RFI No
PTJ-SGCP-CIV-39378.
Method of Placement : PUMP

Time Time Mix Air Air Unit


Test Truck / Ticket Slump Volume
Sl.No. Batched Sampled Temp Content Temp Weight Remarks
# No. (mm) (M³)
(Hours) (Hours) (°C) (%) (°C) (kg/M²)
1 1 4866-21197 1145 1235 27 150 22 8 Sampled # 08
2 2 4866-21198 1200 1310 27 180 6

Test method : ASTM C 172,ASTM C143/C143M,ASTM C1064/C1064M,ASTM C31/C31M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, Mr. Muhammed Almas Khan, Lab Manager,
(CTTA#0278) (CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-01 07 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CONCRETE CYLINDERS
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-331 Report no. : OHDS-23-331-T2
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR-(3)-35INP-20 Date of Sampling : 29 Jan 2023
Sampling method : C172 Date Sample Received : 30 Jan 2023
Sampled by : Asim Ali M (CTTA#0894) Date Test Started : 05 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 05 Feb 2023
RFI No. : PTJ-SGCP-CIV-39604 Date Reported : 05 Feb 2023
Location : Concrete For Manhole MH-1(1no) at Inside Aramco Live Area Haradh Remote Header-K5.REF RFI No PTJ-SGCP-CIV-39309.for Fence
Line Posts (6nos) and Corner Posts (3nos) at Water Injection Manifold Tinat GCP-1. REF RFI No PTJ-SGCP-CIV-39358.for Line post
foundations(16nos) and Corner post foundation(1no) (East & North side) at Burn PIT Haradh Remote Header -K14.REF RFI No
PTJ-SGCP-CIV-39378.
Source of Concrete : HACO Time Batched (Hrs.) : 1145
Method of Placement : PUMP Truck or Batch No. : 4866-21197
Temp. of Mix (°C) : 27 Time Sampled (Hrs.) : 1235
Curing Temp. (°C) : 23±2 Structure Represented : See Location
Air Content : Slump : 150
Strength Value : 35 Mpa
Dial Compressive Strength
Sl.No. Specimen Dia. Height Area Weight Density Age
Reading Type of Fracture
No. (cm) (cm) (cm²) (g) (kg/m³) (Days) kg/cm² PSI MPa
(kN)
Lab curing
1 231739 15.0 30.0 176.7 12958 2444 7 620 358 5090 35.1 Type2 (Cone & Vertical)
2 231740 15.0 30.0 176.7 12973 2447 7 607 350 4980 34.3 Type1 (Cone)

Site curing
3 231741 15.0 29.9 176.7 12920 2445 7 628 362 5150 35.5 Type1 (Cone)
4 231742 15.0 30.0 176.7 12948 2443 7 563 325 4620 31.9 Type4 (Diagonal)

Test method : ASTM C39/C 39M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-02 09 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CONCRETE CYLINDERS
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-331 Report no. : OHDS-23-331-T3
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-HAR-(3)-35INP-20 Date of Sampling : 29 Jan 2023
Sampling method : C172 Date Sample Received : 30 Jan 2023
Sampled by : Asim Ali M (CTTA#0894) Date Test Started : 26 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 26 Feb 2023
RFI No. : PTJ-SGCP-CIV-40455 Date Reported : 26 Feb 2023
Location : Concrete For Manhole MH-1(1no) at Inside Aramco Live Area Haradh Remote Header-K5.REF RFI No
PTJ-SGCP-CIV-39309.for Fence Line Posts (6nos) and Corner Posts (3nos) at Water Injection Manifold Tinat
GCP-1. REF RFI No PTJ-SGCP-CIV-39358.for Line post foundations(16nos) and Corner post foundation(1no) (East
& North side) at Burn PIT Haradh Remote Header -K14.REF RFI No PTJ-SGCP-CIV-39378.
Source of Concrete : HACO Time Batched (Hrs.) : 1145
Method of Placement : PUMP Truck or Batch No. : 4866-21197
Temp. of Mix (°C) : 27 Time Sampled (Hrs.) : 1235
Curing Temp. (°C) : 23±2 Structure Represented : See Location
Air Content : Slump : 150
Strength Value : 35 Mpa
Dial Compressive Strength
Sl.No. Specimen Dia. Height Area Weight Density Age
Reading Type of Fracture Result
No. (cm) (cm) (cm²) (g) (kg/m³) (Days) kg/cm² PSI MPa
(kN)
Lab curing
1 231743 15.0 29.9 176.7 12936 2448 28 819 472 6720 46.3 Type2 (Cone & Vertical) Passed
2 231744 15.0 30.0 176.7 12966 2446 28 797 460 6540 45.1 Type1 (Cone) Passed

Site curing
3 231745 15.0 30.0 176.7 12889 2431 28 829 478 6800 46.9 Type1 (Cone) Passed
4 231746 15.0 29.9 176.7 12855 2433 28 791 456 6490 44.7 Type4 (Diagonal) Passed

Test method : ASTM C39/C 39M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-02 09 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-335 Report no. : OHDS-23-335-T3
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW 522 Date of Sampling : 29 Jan 2023
Sampling method : Not given Date Sample Received : 30 Jan 2023
Sampled by : Iqbal H.M (CTTA#0904) Date Test Started : 05 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 05 Feb 2023
RFI No. : PTJ-SGCP-CIV-39355-39306 ; CST RFI Date Reported : 05 Feb 2023
REF:PTJ-SGCP-CIV-39605
Location : GROUT FOR OPTF SKID TYPE-1A FOUNDATIONS F1 (6NOS) AND PIPE SUPPORT FOUNDATIONS
PS-01,02,03,10/OPTF PS-06 (4NOS) AND H2S (01NO) AT MDRK OPTF-35. OF NON-SHRINK GROUT OPTF SKID
TYPE-1 FOUNDATIONS F1(5NOS),F3(1NO) AND PIPE SUPPORT FOUNDATIONS PS-01-01A-02-03/OPTF
PS-06(4NOS) AND H2S (01NO) AT MDRK OPTF-2.
Source of Grout : Time Batched (Hrs.) : 1305
Method of Placement : MANUAL Time Sampled (Hrs.) : 1309
Temp. of Mix (°C) : 20.1 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) :7

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231783 5 5 5 25 284 2.272 80 326 4640 32.0
2 231784 5 5 5 25 282 2.256 78 318 4523 31.2
3 231785 5 5 5 25 285 2.280 81 330 4698 32.4

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-335 Report no. : OHDS-23-335-T4
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW 522 Date of Sampling : 29 Jan 2023
Sampling method : Not given Date Sample Received : 30 Jan 2023
Sampled by : Iqbal H.M (CTTA#0904) Date Test Started : 26 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 26 Feb 2023
RFI No. : PTJ-SGCP-CIV-39355-39306 ; CST RFI Date Reported : 26 Feb 2023
REF:PTJ-SGCP-CIV-40456
Location : GROUT FOR OPTF SKID TYPE-1A FOUNDATIONS F1 (6NOS) AND PIPE SUPPORT FOUNDATIONS
PS-01,02,03,10/OPTF PS-06 (4NOS) AND H2S (01NO) AT MDRK OPTF-35. OF NON-SHRINK GROUT OPTF SKID
TYPE-1 FOUNDATIONS F1(5NOS),F3(1NO) AND PIPE SUPPORT FOUNDATIONS PS-01-01A-02-03/OPTF
PS-06(4NOS) AND H2S (01NO) AT MDRK OPTF-2.
Source of Grout : Time Batched (Hrs.) : 1305
Method of Placement : MANUAL Time Sampled (Hrs.) : 1309
Temp. of Mix (°C) : 20.1 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) : 28

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231786 5 5 5 25 283 2.264 110 449 6379 44.0
2 231787 5 5 5 25 287 2.296 117 477 6786 46.8
3 231788 5 5 5 25 284 2.272 120 489 6959 48.0

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-370 Report no. : OHDS-23-370-T3
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW Date of Sampling : 30 Jan 2023
Sampling method : Not given Date Sample Received : 31 Jan 2023
Sampled by : Nauman NF (CTTA#0763) Date Test Started : 06 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 06 Feb 2023
RFI No. : PTJ-SGCP-CIV-39394 ; CST RFI Date Reported : 06 Feb 2023
REF:PTJ-SGCP-CIV-39650
Location : GROUT FOR TRANSFORMER FOUNDATIONS (2NOS) (LIVE AREA) AND AREA LIGHTING POLE
FOUNDATIONS PEDESTALS ALF2 (11NOS), ALF3 (11NOS) (NEW AREA) AT TINAT GGM.
Source of Grout : Time Batched (Hrs.) : 0840
Method of Placement : MANUAL Time Sampled (Hrs.) : 0844
Temp. of Mix (°C) : 20.4 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) :7

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231881 5 5 5 25 282 2.256 76 310 4408 30.4
2 231882 5 5 5 25 285 2.280 76 310 4408 30.4
3 231883 5 5 5 25 284 2.272 86 351 4988 34.4

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
COMPRESSIVE STRENGTH OF CEMENT GROUT/MORTAR MIX(CUBES)
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-370 Report no. : OHDS-23-370-T4
Source of sample : Not given Lab Project No. : PH22-007
Sample description : MASTERFLOW Date of Sampling : 30 Jan 2023
Sampling method : Not given Date Sample Received : 31 Jan 2023
Sampled by : Nauman NF (CTTA#0763) Date Test Started : 27 Feb 2023
Tested by : AbeLabanta(CTTA#0278) Date Test Completed : 27 Feb 2023
RFI No. : PTJ-SGCP-CIV-39394 ; CST RFI Date Reported : 27 Feb 2023
REF:PTJ-SGCP-CIV-40495
Location : GROUT FOR TRANSFORMER FOUNDATIONS (2NOS) (LIVE AREA) AND AREA LIGHTING POLE
FOUNDATIONS PEDESTALS ALF2 (11NOS), ALF3 (11NOS) (NEW AREA) AT TINAT GGM.
Source of Grout : Time Batched (Hrs.) : 0840
Method of Placement : MANUAL Time Sampled (Hrs.) : 0844
Temp. of Mix (°C) : 20.4 Curing Temp. (°C) : 23±2
Structure Represented : Age (Days) : 28

Dimensions Compressive Strength


Sl.No. Specimen Area Weight Density Load
Remarks
No. Length Width Height (cm²) (g) (g/cc) (kN) kg/cm² PSI MPa
(cm) (cm) (cm)
Lab curing
1 231884 5 5 5 25 287 2.296 103 420 5974 41.2
2 231885 5 5 5 25 283 2.264 109 444 6321 43.6
3 231886 5 5 5 25 285 2.280 101 412 5857 40.4

Test method : ASTM C109 / C109M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, (CTTA#0278) Mr. Muhammed Almas Khan, Lab Manager, ,
(CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-07 05 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025
SLUMP AND TEMPERATURE TEST
Client : Petrojet
Project name : South Gas Compression Plants (SGCP) Pipelines
Sample no. : OHDS-23-408 Report no. : OHDS-23-408-T1
Source of sample : HACO Lab Project No. : PH22-007
Sample description : AFAL-35MPa Date of Sampling : 31 Jan 2023
Sampling method : C172 Date Sample Received : N/A
Sampled by : Nauman NF (CTTA#0763) Date Test Started : 01 Feb 2023
Tested by : Nauman NF(CTTA#0763) Date Test Completed : 02 Feb 2023
RFI No. : PTJ-SGCP-CIV-39390, 39384 Date Reported : 03 Feb 2023
Location : Concrete for Pipe support foundations PS-01 (4nos), PS-02(6nos), PS-03(3nos) in Water injection manifold at MDRK GCP1.REF RFI No
PTJ-SGCP-CIV-39384. for Thrust Anchor block 8" for Blow Down Pipe line 8"BD-0019-1CS2P06 at Tinat Remote Header-C.REF RFI No
PTJ-SGCP-CIV-39390.
Method of Placement : PUMP

Time Time Mix Air Air Unit


Test Truck / Ticket Slump Volume
Sl.No. Batched Sampled Temp Content Temp Weight Remarks
# No. (mm) (M³)
(Hours) (Hours) (°C) (%) (°C) (kg/M²)
1 1 4866-30518 1230 1330 27 170 5 Sampled # 08

Test method : ASTM C 172,ASTM C143/C143M,ASTM C1064/C1064M,ASTM C31/C31M


Test method variations : NIL
Remarks : NIL

Mr. Abe C Labnta,Lab Supervisor, Mr. Muhammed Almas Khan, Lab Manager,
(CTTA#0278) (CTTA#0709)
Reviewed By Approved By

P.O Box 1736, Al-Khobar 31952,K.S.A Documents No. Revision No. Effective Date Page Sequence
Tel. 8573664/8573668/8573880, Fax. 8573144,
e-mail: info@osaimiengineering.com TF-C-01 07 30-01-2022 Page 1 of 1

An Independant Testing Laboratory This is digitally generated report does not require stamp/sign
Results related only to the items tested This test is accredited by ISO/IEC 17025

You might also like