MCset 17.5 kV
Air insulated switchboard
Withdrawable switchgear SF6 or vacuum technology
Catalogue
2009
A new path for achieving your electrical installations
A comprehensive offer
The MCset range is part of a comprehensive offer of products that are perfectly coordinated
to meet all medium and low voltage electrical distribution requirements.
All of these products have been designed to work together: electrical, mechanical
and communication compatibility.
The electrical installation is thus both optimised and has improved performance:
@ better service continuity,
@ increased personnel and equipment safety,
@ guaranteed upgradeability,
@ efficient monitoring and control.
You therefore have all the advantages at hand in terms of know-how and creativity
for achieving optimised, safe, upgradeable and compliant installations.
With Schneider Electric, you have a complete range of tools to help you get to know and
install the products whilst complying with current standards and good working practices.
These tools, technical sheets and guides, design software, training courses, etc are
regularly updated.
Presentation 5
General 13
Cubicle description 25
Switchgear 43
Installation 73
Appendices 79
DEAI02EN.indd 3
4 DEAI02EN.indd
MCset 17.5 kV Presentation
DEAI02EN.indd 5
Presentation MCset, the strength of experience
Energy
b Electric power stations (thermal, nuclear),
b Auxiliary substations,
b Source substations.
Industry
b Oil & gas,
b Chemical industry,
b Paper mills,
b Metallurgy,
b Car industry,
b Mining,
PE57462
b Cement plants,
b …
Infrastructure
b Airports,
b Ports,
b Hospitals,
b Water treatment,
b …
b Tankers,
b Offshore platforms, fixed and mobile,
b LNG (Liquid Natural Gas),
b Navy,
b …
6 DEAI02EN.indd
Presentation The range’s advantages
Safety
b Operations are all performed from the front, including access to
connections and busbars.
b Racking in and out is only possible with the door closed.
b The power-on indicator is situated on the front of the functional unit.
b A earthing switch with making capacity.
b One single ‘‘anti-reflex” handle is used for all MCset operations.
b Internal arc withstand developed for all functional units.
PE56582
Reliability
b Type testing was carried out for each performance level in the MCset
range.
b The design, manufacturing and testing of MCset was carried out
according to ISO 9001quality standard.
PE90006
Simplicity
b A user interface which is easily understood by everybody.
b Interlocks and padlocks preventing operator errors.
PE56386
DEAI02EN.indd 7
Presentation MCset, continuity of service
and complete safety
MCset provides the most efficient means to control and protect a wide
range of applications.
Due to the devices it comprises, MCset can be easily integrated into
a monitoring and control system.
Sepam series 20, series 40 and series 80 digital protection relays take full
advantage of Merlin Gerin experience in electrical network protection.
Sepam series 20, series 40 and series 80 provides all the necessary
functions:
b effective protection of people and property,
b accurate measurements and detailed diagnosis,
b integral equipment control,
b local or remote indication and operation.
Easy evolution
Addition of communication, digital I/O’s, analog output, or temperature
acquisition are possible due to its modular design.
8 DEAI02EN.indd
Presentation MCset, a comprehensive solution
PE55137
Sepam
Easy commissioning
Transparent Ready™ equipment is delivered ready to connect and
Sepam
commission. A Quick Start guide, packaged with your switchboard,
provides three easy-to-follow steps.
CM/PM
MCset switchboard
Functionalities provided
TRe-1 TRe-2
Instantaneous readings b b
PE57471
Power summary b b
Displays the present demand (kW), the peak demand (kW)
and the times and dates of the records
Energy summary b b
Displays the energy (kWh) the reactive energy (kvarh),
and the times and dates of the records
Instantaneous readings, all devices b
Basic historical data logging, energy and trending
Displays automatically updated meter values
for all the communicating devices in the equipment
PE57473
Log displays b
Displays data as time curves, or tables
Export of data tables b
Allows data tables to be exported in a standard
Windows format
DEAI02EN.indd 9
Presentation MCset, a comprehensive solution
(cont.)
MT20064
Specifying
We help you to define your solutions: selection guide,
technical assistance, advice…
Implementing
We oversee the completion and commissioning of your installation:
design, cost optimization, guaranteed performances and dependability,
Modernizing Operating commissioning tests, etc.
Operating
We help run your daily operations in real time: maintenance contract,
technical assistance, supply of replacement parts, corrective and
preventive maintenance, operation and maintenance training, etc.
Modernizing
We can bring the performance of your installation up to date:
installation audit, switchgear diagnosis, adaptation and modification,
end of life recycling, etc.
MT20065EN
End-of-life recycling
Schneider Electric Services has an operational subsidiary allowing you
to recycle your medium voltage switchgear.
10 DEAI02EN.indd
Presentation Quality - Environment -
Maintenance
MT55055
whose main role is to check quality and monitor compliance with standards.
This procedure is:
b uniform throughout all departments,
b recognized by many customers and approved organizations.
But above all, it is its strict application that has allowed us to obtain
the recognition of an independent organization:
The French Quality Assurance Association (AFAQ).
The quality system for the design and manufacture of MCset
is certified to be in conformity with the requirements of
ISO 9001 quality assurance standard.
b dielectric test,
10% b testing of safety systems and interlocks,
Aluminium
b testing of low voltage components,
25%
b conformity with drawings and diagrams.
62% The results obtained are recorded and approved by the quality control
3% department on each device’s test certificate.
Plastic This therefore guarantees product traceability.
b Checking SF6 switchgear
Steel
v sealing test,
v filling pressure test.
b Checking vacuum switchgear
Each vacuum interrupter, sealed and airtight, is checked for the quality of
the vacuum obtained. This pressure measurement is based on the proven
“magnetron discharge” method.
Using this sophisticated procedure, measurement is very precise and
does not require access to the inside of the bulb, thus not affecting the
airtight seal.
Protected environment
PE56733
DEAI02EN.indd 11
Presentation A few references
MCset, a product for all your electrical
distribution applications
PE56586
Qatar Petroleum Qatar
ONAL Gabon
Syrian Gas Company Syria
Yemen LNG Company Yemen
Turkmengaz Turkmenistan
MT20072
CPOC Malaya
Norvegian Cruise Lines USA
Conti Rederei Germany
Petropod Norway
TMT Taiwan
British gas United Kingdom
MSC Italy
Jan de Nul Belgium
Nikki Shipping Greece
b Power generation
Moranbah Generation Facility Australia
PE57460
Sonelgaz Algeria
Enertherm France
Ergon Energy Australia
China Nuclear Power programmes China
Mount Isa – Clark Energy Australia
La Termica Italy
Al Fanar Electrical System KSA
Industry
b Mining, Minerals & Mining
Croesus Mining Australia
PE57463
Buildings
b Hotels
Hamilton Island Australia
Al Bustan Palace Hotel Oman
b Industrial buildings - Offices
Central Park Mall of Jeddah KSA
Emta Adana Irak
12 DEAI02EN.indd
MCset 17.5 kV General
Description 14
Technical characteristics 16
Operating conditions 17
Protection of people 18
Specific applications 19
Marine applications 20
A range for all functions 22
Choice of functional units
DEAI02EN.indd 13
General Description
PE57467
Busbars
LV control
cabinet
Sepam
Withdrawable part
Current
transformers
Cables
connection
Voltage
transformers
compartment
14 DEAI02EN.indd
General Description (cont.)
The cubicle
LSC2B The cubicle is of LSC2B (Loss of Service Continuity Category) type as defined by
(Loss of Service Continuity IEC 62271-200): IEC standard 62271-200, in other words the medium voltage parts are compartmented
using metal partitions (PM class) which are connected to earth and which separate:
this category defines the possibility b the busbars,
of keeping other compartments energised b the withdrawable part (circuit-breaker, fuse-contactor, disconnector truck or
(in service) when opening a main circuit earthing truck),
compartment. b MV connections, earthing switch, current sensors and voltage transformers
as required.
MCset guarantees a high level of protection of people; when a compartment
containing a main circuit is open, the other compartments and/or functional units
may remain energised.
The low voltage auxiliaries and monitoring unit are in a control cabinet separated
from the medium voltage section.
Five basic cubicle layouts are offered:
b incomer or feeder AD
b line up bussection CL - GL
b busbar metering and earthing TT
b switch-fuse feeder DI
AD and CL cubicles have withdrawable vacuum type circuit-breaker and
contactor switchgear.
DEAI02EN.indd 15
General Technical characteristics
The values below are given for normal operating conditions as defined in
PE57468
16 DEAI02EN.indd
General Operating conditions
Operating conditions
PE57464
Standards
The MCset range meets the following international standards:
b 62271-1 : clauses common to high voltage switchgear
b 62271-200 : metal-enclosed switchgear for alternating current at rated voltages
of between 1 and 52 kV
b IEC 62271-100 : high voltage alternating current circuit breakers
b IEC 60470 : high voltage alternating current contactors
b IEC 60265-1 : high voltage switches
b IEC 60282-2 : high voltage fuses
b IEC 60271-102 : alternating current disconnectors and earthing switches
b IEC 60255 : measurement relay and protection unit for the applicable parts
b IEC 60044-1 : current transformers
b IEC 60044-2 : voltage transformers
b IEC 60044-8 : electronic current transformers (for LPCT).
DEAI02EN.indd 17
General Protection of people
All operations are carried out from the front face, including access to connections
and busbars.
The user is guided through icon-diagrams on each front panel making it easy
to understand the operating sequence and device status.
Interlocks and padlocks prevent operator errors.
Several additional levels of security also protect operators:
b racking in and out is only possible with the door closed.
b locking of the MV door open if the LV plug of the circuit breaker is not plug-in.
b the very extensive set of mechanical and electrical interlocks do not allow operator
error. These can be added to by key locks or padlocks according to specific
operating procedures. Each selector can be fitted with one to three padlocks.
b all operations are carried out from the front face including access to connections
and busbars.
b the voltage present indicator is located on the front face of the functional unit,
in the immediate vicinity of the earthing switch control.
b disarming of circuit breaker when racking out. This function enables the circuit
breaker control springs to be disarmed during the extraction operation.
b locking of withdrawable part/cable compartment. This function disables the
possibility of racking the withdrawable part in if the front panel (cable compartment)
is not installed.
18 DEAI02EN.indd
General Specific applications
Nuclear
PE56575
Seismic areas
MCset meets international seismic specifications.
Test procedures follow IEC 60068-3-3 standard.
MCset is qualified following the standards:
b UBC 97,
b IBC 2000,
b MSK 64,
b ENDESA
b EDF HN.20.E53.
DEP Shell
MCset switchboards are certified by Shell n compliance with DEP 33.67.51.31 Gen
(July 1998 - updated November 2006) for MV equipments.
DEAI02EN.indd 19
General Marine applications
Derived from standard MCset, a Marine version has been developed to meet specific
PE57452
Environmental conditions
PE90007
20 DEAI02EN.indd
General Marine applications (cont.)
PE57453
arcing gases b Internal arcing withstand is ensured by the use of a tunnel specifically designed
Auxiliary cable duct
for marine applications. Located above the cubicle, it can evacuate gases due to
arcing effects.
Higher low voltage b A low voltage control cabinet has also been designed to meet the need for using
control cabinet numerous control and monitoring systems and LV components.
(640 mm) b The cubicles are provided with switchgear employing SF6 or vacuum technology
(please consult us).
b The incoming/outgoing feeder cubicles are connected by cables through the bottom.
b Skids are available on option to group together several cubicles on a platform
2530
for improved rigidity and to absorb vibrations by means of dampers.
“Anti-rolling” handle They also facilitate handling and installation of the switchboard.
b Motor starter applications: see Motorpact catalogue.
MCset is the solution to the specific needs and requirements of a Naval
environment:
1200 b Performances
v from 25 to 50 kA (consult us)
v Internal arc withstand 1 s
b Compactness: to meet space constraints (clearance under ceiling) that are
sometimes indispensable, a specific version is proposed.
85 Skid (option)
Rated voltage (kV)
7.2 12 17.5
Rated insulation level
Power frequency withstand voltage 50 Hz - 1 min (r ms kV) 20 28 38
Lightning impulse withstand voltage 1.2/50 µs (kV peak) 60 75 95
PE57458
the breaking capacity is equal to the short time withstand current. In all cases, the device peak
making capacity is equal to 2.5 times the short time withstand current.
(2) Lightning impulse dielectric withstand voltage = 60 kV peak.
(3) Limited by fuses.
DEAI02EN.indd 21
General A range for all functions
Choice of functional units
Device Circuit breaker Circuit breaker Circuit breaker Circuit breaker Circuit breaker Fuse-switch
MT20081
MT20082
Sepam Sepam
(1) The direct incomer (functional unit without circuit breaker, equipped with a fixed busbar bridge)
is produced using cubicles AD1-2-3.
(2) Transition cubicle for MCC application (Motorpact).
22 DEAI02EN.indd
General A range for all functions
Choice of functional units (cont.)
MT20083
MT20081
MT20083
MT20084
DE55076
MT20078
DE60167
Sepam Sepam Sepam
Sepam
DEAI02EN.indd 23
24 DEAI02EN.indd
MCset 17.5 kV Cubicle description
AD type cubicles 26
Incomer and feeder
CL - GL type cubicles 27
Line-up bussectioning
TT type cubicles 28
Metering
Busbar earthing
DI type cubicles 29
Fuse switch feeder
Motorpact 30
Motorpact transition cubicle (MTP)
Motor protection and control
DEAI02EN.indd 25
Cubicle description AD type cubicles
Incomer and feeder
DE56775
1
2
H
5
4
6
3
W D
MV compartments
MT20080
Characteristics (for more details, see the pages on the switchgear in question)
AD1 AD2 AD3
Rated voltage (kV) 7.2 12 7.2 12 17.5 7.2 12 17.5
Breaking capacity (kA) 25 31.5 50 25 31.5 50 40 50 40 25 31.5 25 31.5 40 50 25 31.5 40 50 25 31.5 40 50
(1) (1)
26 DEAI02EN.indd
Cubicle description CL - GL type cubicles
Line-up bussectioning
DE56776
DE56777
1 1
5 5
3
2
H
W W D D
CL1-2-3 or GL1-2-3
MV compartments
MT20084
Characteristics (for more details, see the pages on the switchgear in question)
CL1-GL1 CL2-GL2 CL3-GL3
Rated voltage (kV) 7.2 12 7.2 12 17.5 7.2 12 17.5
Breaking capacity (kA) 25 31.5 25 31.5 40 50 40 25 31.5 25 31.5 40 50 25 31.5 40 50 25 31.5 40 50
Rated current (A)
Evolis 630 b b b b b b b b
circuit breaker 1250 b b b b b b b b b
2500 b b b b b b b b b
Evolis HP 1250 b b (5)
circuit breaker 2500 b b b (5)
3150 b b b b b b b b b (5) b (5) b (5) b (5)
4000 (3) b b b (5)
LF circuit breaker 630 b b b b b b b b b
1250 b b b b b b b b b b b
2500 b b b b b b b b b b b
3150 b b b b b b b b b
4000 (6) b b b
Short-circuit making 50 Hz 63 79 63 79 100 125 100 63 79 63 79 100 125 63 79 100 125 63 79 100 125
current Ip (kA peak) 60 Hz 65 82 65 82 104 130 104 65 82 65 82 104 130 65 82 104 130 65 82 104 130
Dimensions (mm) H 2300 2300 2300
W 570 (x 2) 700 (x 2) 900 (x 2)
D (2) 1550 1550 1550
Weight (kg) (4) 1300 (CL1 + GL1) 1500 (CL2 + GL2) 1700 (CL3 + GL3)
(2) Overall + 175 mm for 4-sided internal arcing protected switchboards, for 3150 A, for 4000 A or 2 sets of CT’s.
(3) With fan (consult us).
(4) Approximate weight fully equipped cubicle.
(5) Limited at 15 kV.
(6) With fan
DEAI02EN.indd 27
Cubicle description TT type cubicles
Metering
Busbar earthing
TT1-2
DE55093
DE56778
1
4
W D
MV compartments
MT20078
Characteristics
TT1 TT2
Rated voltage kV 7.2 12 7.2 12 17.5 (*)
Insulation voltage kV r ms 50 Hz - 1 min 20 28 20 28 38
kV impulse 1.2/50 µs 60 75 60 75 95
Rated current A 630 b b b b b b
(busbar intensity)) 1250 b b b b b b
2500 b b b b b b
3150 b b b b b b
4000 (2) b b b b b b
Short time withstand current kA r ms 3 s 31.5 31.5 50 50 31.5 40
Dimensions (mm) H 2300 2300
W 570 700
D (1) 1550 1550
Weight (kg) 500 550
(1) Overall + 175 mm for 4-sided internal arcing protected switchboards.
(2) With LF circuit breaker only.
(*) Note: rated voltage 15 kV available for the Evolis HP circuit breaker and for a short-time
withstand current of 50 kA rms 3 s.
28 DEAI02EN.indd
Cubicle description DI type cubicles
Fuse switch feeder
DI2
DE55098
DE56779
4
1
H 2
W D
MV compartments
MT20082
Characteristics
DI2
Rated voltage kV 7.2 12 17.5
Insulation voltage kV r ms 50 Hz - 1 min 20 28 38
kV impulse 1.2/50 µs 60 75 95
Rated current A 200 b b b
Short time withstand current kA r ms 1 s (2) 25 25 25
Dimensions (mm) H 2300
W 700
D (1) 1550
Weight (kg) 750
(1) Overall + 175 mm for switchboard internal arcing 4 sides.
(2) Limited by fuses.
DI cubicles including a fuse switch are used to supply power and protect low power
transformers.
E.g.: auxiliary service transformers in primary substations.
All operations are carried out from the front face, including access to connections
and busbars.
All functional interlocks meet recommendations in IEC 62271-200:
b the switch is only possible to close if the earthing switch is open and the connection
access panel is in place,
b closing of the earthing switch is only possible if the switch is open,
b opening of the access panel to medium voltage connections and fuses is only
possible of the earthing switches upstream and downstream of the fuses are closed,
b the switch is locked in the open position when the access panel is taken off.
The voltage presence indicator is situated on the front face of the functional unit,
integrated in the switch’s control panel.
DEAI02EN.indd 29
Cubicle description Motorpact
Motor protection and control (MTP)
DE56790
DE56791
H
W D
Composition
DE60167
Basic equipment
b 1 enclosure (standard IP3X),
b 1 set of busbars in separate compartment,
b 1 removable front panel.
Options
b Internal arc withstand,
b IP4X or IPX1 enclosure,
b Encapsulated busbars.
Characteristics
30 DEAI02EN.indd
Cubicle description Motorpact
Motor protection and control (cont.)
They are suitable for all MV motor applications in markets such as: oil & gas, mining,
water, pulp and paper, for starting:
b pumps,
b fans,
b compressors,
b crushers,
b conveyors, etc.
Compactness
b Compact dimensions thanks to a 375 mm width.
PE57469
Safety
b Full cubicle protection for internal arc withstand (AFLR 4 sides).
b Electrical and mechanical interlocking, closed door operation.
b Visible insulation by means of portholes.
Reliability
b Fewer components and fasteners.
Less maintenance
b Corrosive atmosphere withstand.
b Maintenance free disconnector (capacity: 5000 operations).
b Front access to compartments.
Characteristics
MCset lined up with Motorpact
Installation Indoor type
Maximum rated voltage 7.2 kV
Insulation voltage
Power frequency withstand (1 min) 20 kV
Impulse withstand voltage (1.2/50 µs, peak value) 60 kV
Maximum rated short time withstand current (busbars) 40 kA 3 s
50 kA 2 s*
Rated frequency 50/60 Hz
Maximum busbars rating 2500 A
3150 A*
Degree of protection
Enclosure IP3X, IP4X, IPX1, IPX2
Between compartments IP2XC
* for stand-alone applications or when lined up with LF circuit breaker MCset switchgear
DEAI02EN.indd 31
Cubicle description Motorpact
Motor protection and control (cont.)
DE56793
DE56794
1 Line disconnector
2 Busbars
7 3 Fuses
4 Contactor
Sepam 5 Earthing switch
M20
6 Current sensors LPCT,
LPCT
2 current transformer
1 and earth fault sensor
3
LV control cabinet
7 LV protection,
5 measurement and control
devices
4
6
M
RVAT
Auto-transformer asynchronous motor starter
1 Run and start vacuum
DE57088
DE56795
DE56796
contactor
2 Busbars
1 3 Auto-transformer
Sepam
M41
2
LPCT
RVSS
Softstart asynchronous motor starter
1 By-pass vacuum contactor
DE57090EN
DE56797
DE56798
2 Busbars
3 SoftStart power stack
1
Sepam SoftStart
protection
relay
2
LPCT
32 DEAI02EN.indd
MCset 17.5 kV Protection, monitoring
and control
Thermal diagnosis 34
Protection system Sepam range 35
Sepam series 20, series 40, series 80, Sepam 100 36
Sepam series 20, series 40, series 80 37
Selection guide
Instrument transformers 38
DEAI02EN.indd 33
Protection, monitoring Thermal diagnosis
and control
Probes CFO733
The optical fibre probes are factory-built assemblies comprising:
b 3 sensors attached to the power circuit,
b the optical connections,
b a connector linked to the module.
This connector incorporates the opto-electrical conversion unit thus eliminating
any optical connections when assembling.
MDT106 module
The MDT106 electronic module is mounted in the low voltage compartment
of the cubicle. It provides the following functions:
b monitoring of temperature rise in 2 zones,
b triggering of the pre-alarm,
b triggering of the alarm,
b self-monitoring of the module,
b self monitoring of the temperature probes.
Technical characteristics
Optical fibre probes CF0733
PE90039
34 DEAI02EN.indd
Protection, monitoring Protection system Sepam range
and control
DE56781
with a comprehensive protection,
monitoring and control system comprising:
b instrument transformers (*) to measure Protection relays
metering equipment
the necessary electrical values (phase
current, residual current, voltages, etc.)
b protection relays, providing functions Switchgear (circuit breaker and contactor)
adapted to the part of the network
to be protected
b metering equipment, to inform operators
b low voltage relaying, i.e. to provide control
of the breaking device (contactor and circuit
breaker) of the withdrawable part
b various auxiliaries: secondary circuit test
Instrument transformers
units, etc.
Like the MCset range, the Sepam range is a range of units defined to provide
an optimal solution for each application, and includes (eg):
b Sepam S, substation incomer and feeder,
b Sepam B, bussectioning,
b Sepam T, transformer feeder,
b Sepam M, motor feeder,
b Sepam G, generator feeder,
b Sepam C, capacitor feeder.
The Sepam range consists of Sepam series 20, series 40 and series 80,
a range of modular protection relays to adapt precisely to your need.
Sepam advantages
Reliability
b Over 20 years of experience in multi-function digital protection relays.
b Over 150,000 Sepam units in service in more than 90 countries.
Quality
b Quality design based on dependability studies and strict definition of
environmental constraints: temperature, pollution, EMC, dielectric strength…
b Quality manufacturing based on procurement agreements with suppliers
and inspection throughout all manufacturing phases.
Simplicity of use
b Local operation facilitated by the ergonomic User Machine Interface informing
the operator fully and clearly in his own language.
b Ease of setup thanks to the flexibility and user-friendliness of the parameters
setup software.
DEAI02EN.indd 35
Protection, monitoring Sepam series 20, series 40,
and control
series 80, Sepam 100
PE57125
PE57126
Sepam 100 units round off the Sepam range and can be installed either separately
or combined with either Sepam series 20, series 40 and series 80.
Sepam 100 has several variants:
b Sepam 100 MI, local breaking device control and signalling modules
(many different line diagram types are available):
b Sepam 100 LD, high impedance differential protection
b Sepam 100 LA, self-powering protection (back-up protection without auxiliary
power supply).
36 DEAI02EN.indd
Protection, monitoring Sepam series 20, series 40,
and control
series 80
Selection guide
Sepam series 20
b 10 logic inputs Current S20 T20 M20
DE57493
frequency
protection
Loss of mains B22
(ROCOF)
Sepam series 40
b 10 logic inputs Current, S40 T40 G40
DE57495
frequency
protection for
two sets of
busbars
Capacitor C86
DE57499
bank
unbalance
DEAI02EN.indd 37
Protection, monitoring Instrument transformers
and control
Transformer ARJP1/N2J
b Single primary current, double secondary current for measurement or protection
b Frequency 50-60 Hz
I1n (A) 10 20 30 50 75 100 150 200 250
Ith (kA) 1.2 2.4 3.6 6 10 10 10 10 10
t (s) 1 1 1 1 1 1 1 1 1
Measuring* cl.0.5 15 VA
Protection* 5P20 2.5 VA
ARJP1, 2 or 3
Transformer ARJA1/N2J
b Single primary current, double secondary current for measurement or protection
b Frequency 50-60 Hz
I1n (A) 1500 2000 2500
Ith (kA) 50 50 50
t (s) 1 1 1
measuring* cl.0.5 30 VA 30 VA 30 VA
protection* 5P20 15 VA 15 VA 15 VA
ARJA1
Transformer ARO1a/N3
b Single primary current, triple secondary current for measurement or protection
b Frequency 50-60 Hz
I1n (A) 3150
Ith (kA) 50
t (s) 1
Measuring* cl.0.5 30 VA
Protection* 5P20 7.5 VA
ARO1
38 DEAI02EN.indd
Protection, monitoring Instrument transformers (cont.)
and control
LPCT’s (Low Power Current Transformers) LCPT low power current transformers
meet IEC standard IEC 60044-8.These are LPCT’s are specific current sensors with a direct voltage output of the “Low Power
CT’s with a direct voltage output which has Current Transformers” type, in conformity with standard IEC 60044-8.LPCT’s
the advantage of having a very wide range provide metering and protection functions.
They are defined by:
of applications, simplifying selection. b the rated primary current
b the extended primary current
b the accuracy limit primary current or the accuracy limit factor.
These have a linear response over a large current range and do not start to saturate
until beyond the currents to be broken.
PE56564
PE56561
PE56563
CLP1 CLP3
AD1 - AD1C 630/1250 A b
AD2 630 A b
AD3 1250 A b
2500 A b
LPCT in cubicle
Type Primary current Secondary Accuracy Accuracy Thermal Rated insulation Frequency Secondary
rated extended voltage class limit factor resistance connector
FLP Ur Ud Up
(A) (A) (mV) (kA - 1 s) (kV) (kV - 1 min) (kV peak) (Hz)
CLP1 100 1250 22.5 0.5 - 5P 500 50 17.5 38 95 50/60 RJ45 - 8 pts
CLP3 2500 400 40
DEAI02EN.indd 39
Protection, monitoring Instrument transformers (cont.)
and control
(CSH type)
CSH 120 and CSH 200 core balance CT’s, provide more sensitive protection
by direct measurement of earth fault currents.
Specifically designed for the Sepam range, they can be directly connected to
the Sepam “residual current” input.
They are only different in terms of their diameter:
b CSH 120 - 120 mm internal diameter,
b CSH 200 - 200 mm internal diameter.
40 DEAI02EN.indd
Protection, monitoring Instrument transformers (cont.)
and control
Voltage transformers
These supply power to:
b measuring, metering and monitoring devices,
b relays or protective devices,
b auxiliary LV sources for various types of switchgear; all these devices are protected
and insulated from the MV section.
They are installed at the bottom of the functional unit. In the withdrawable fuse
version, the voltage transformers are attached to a side wall. The energized part
is entirely encapsulated in an epoxy resin, which provides both electrical insulation
and excellent mechanical strength.
They include the following models:
b with one insulated MV terminal, for connection between neutral and phase
conductors in three-phase systems with withdrawable MV fuses,
b with two insulated MV terminals, for connection between phase conductors.
Transformer VRQ3n/S2
b Phase-earth
b Frequency 50-60 Hz
Primary voltage 3/3 3.3/3 5.5/3 6/3 6.6/3 10/3 11/3 13.8/3 15/3
(kV)
1st secondary 100/3 110/3 110/3 100/3 110/3 100/3 110/3 110/3 100/3
voltage (V)
VRQ3
2nd secondary 100/3 110/3 110/3 100/3 110/3 100/3 110/3 110/3 100/3
voltage (V)
1st secondary 30-50 VA cl.0.5
accuracy class
(VA)
2nd secondary 50 VA cl.0.5
accuracy class
(VA)
Transformer VRC1/S1F
b Phase-phase
b Frequency 50-60 Hz
Primary voltage (kV) 3.3 5.5 6,6 11 13.8 15
Secondary voltage (V) 110 110 110 110 110 100
Accuracy class (VA) 75 VA cl.0.5
VRC1/S1F
This transformer provides power to the coil in order to keep the magnetic circuit
of the contactor closed.
Transformer VRCR/S1
b Phase-phase
b Frequency 50-60 Hz
Primary voltage (kV) 3.3 5.5 6.6
Secondary voltage (V) 110 110 110
Accuracy class (VA) 50 VA cl.0.5
VRCR
DEAI02EN.indd 41
42 DEAI02EN.indd
MCset 17.5 kV Switchgear
DEAI02EN.indd 43
Switchgear Safety and protection of persons
and property
PE57465
Withdrawable
part
Extraction
table
44 DEAI02EN.indd
Switchgear Safety and protection of persons
and property (cont.)
The devices used to equip the MCset range of functional units have
outstanding features:
b long service life,
b maintenance-free live parts,
b high electrical endurance,
b operating safety,
b insensitivity to the environment.
The withdrawable parts:
b the circuit breaker or contactor, the disconnector truck or the earthing truck,
b the lever-type propulsion mechanism for racking in-out,
b interlocks to fix the withdrawable parts onto the fixed part.
The live parts are housed in an insulating enclosure in the sealed pressure system
in compliance with IEC 62271-100.
Circuit breaker
61058N
Contactor
61011N
Earthing truck
DE56784
The earthing truck is a safety feature which allows the cubicle busbar to be earthed.
It is installed instead of the circuit breaker and has the same interlock possibilities.
Disconnector truck
DE56785
The disconnector truck enables the upper and lower part of the cubicle
to be short-circuited. It is installed instead of the circuit breaker and
has the same interlock possibilities.
DEAI02EN.indd 45
Vacuum type switchgear Evolis 17.5 kV circuit breaker
Presentation
Presentation
PE56565
The Evolis circuit breaker is used to equip AD1-2-3 and CL1-2-3 cubicles for rated
values of 7.2kV to 17.5kV.
46 DEAI02EN.indd
Vacuum type switchgear Evolis 17.5 kV circuit breaker
Characteristics
DEAI02EN.indd 47
Vacuum type switchgear Evolis 17.5 kV circuit breaker
P2 stored energy operating mechanism
Presentation
This mechanism guarantees the device an opening and closing speed unaffected
by the operator, for both electric and manual orders.
It carries out the O and CO cycles and is automatically recharged
by a gear motor after closing.
It consists of:
b the stored energy operating mechanism which stores in springs the energy
required to open and close the device
b a gear motor electrical charging device with manual charging by lever
(useful on loss of auxiliary supply)
b manual order devices by push buttons on the front panel of the device
b an electrical remote closing device containing a release with an antipumping relay
b an electrical opening device containing one or more releases, for example:
v shunt opening
v Undervoltage
v Mitop, a low consumption release, used only with the Sepam 100 LA
protection relay.
b an operation counter
b a position indication device by mechanical indicator
and 3 modules of 4 auxiliary contacts whose availability varies according
to the diagram used
b a device for indicating “charged” operating mechanism status by mechanical
indicator and electrical contact.
MCH
OF1 OF2 OF3 OF4 OF11 OF12 OF13 OF14 OF21 OF22 OF23 OF24
XF
MX1
MX2
or
MN
Mitop Reset
SDE
PF
48 DEAI02EN.indd
Vacuum type switchgear Evolis 17.5 kV circuit breaker
P2 stored energy operating mechanism
Opening circuit
Composition
DE57526
DEAI02EN.indd 49
Vacuum type switchgear Evolis 17.5 kV circuit breaker
P2 stored energy operating mechanism
Opening circuit (cont.)
This release unit causes the systematic opening of the circuit breaker when its
supply voltage drops below a value less than 35% of the rated voltage, even if this
drop is slow and gradual. It can open the circuit breaker between 35% and 70% of
its rated voltage. If the release unit is not supplied power, manual or electrical closing
of the circuit breaker is impossible. Closing of the circuit breaker is possible when
the supply voltage of the release unit reaches 85% of its rated voltage.
Undervoltage release (MN)
Characteristics
Power supply V AC 24, 48, 100…130, 200…250
V DC 24…30, 48 …60, 100…130, 200…250
DE57528
This function is achieved by adding a time delay unit outside of the undervoltage
release (MN) circuit (adjustable time delay).
This unit is placed outside the circuit breaker and can be inhibited by an emergency
stop button to obtain instant circuit breaker opening.
Characteristics
Power supply V AC 48…60, 100…130, 200…250
V DC 100…130, 200…250
Threshold Opening 0.35 to 0.7 Ur
Closing 0.85 Ur
Consumption (VA or W) Triggering 200 (for 200 ms)
Latched 4.5
Temporisation 0.5 s - 0.9 s - 1.5 s - 3 s
50 DEAI02EN.indd
Vacuum type switchgear Evolis 17.5 kV circuit breaker
P2 stored energy operating mechanism
Remote control
Function
DE57530
Remote control enables the remote opening and closing of the circuit breaker.
The opening order always takes priority over the closing order.
In the event of simultaneous opening and closing orders, the mechanism discharges
under no load, without moving the main contacts. The circuit breaker remains in the
“open” position.
In the event of latched opening and closing orders, the mechanism carries out anti-
pumping function as standard, by blocking the circuit breaker in the “open” position.
Anti-pumping function: after opening on a fault or deliberate opening via the manual or
electrical mechanism, the closing order must be interrupted then reactivated to enable
reclosing of the circuit breaker.
Composition
The remote control comprises:
b an electrical motor (MCH) equipped with a “spring armed” CH limit switch
Circuit breaker equipped with remote control
b a shunt closing release (XF).
The electrical motor carries out the automatic rearming of the storage energy springs
as soon as the circuit breaker closes. This allows instant reclosing of the device
after opening. The arming lever is only used as a backup control in the case of
the absence of the auxiliary power supply.
An electrical motor (MCH) equipped with a “spring armed” CH limit switch.
This contact indicates the “armed” position of the mechanism (springs armed).
Characteristics
Power supply V AC 48…60, 100…130, 200…240
V DC 24, 24…30, 48, 48…60 , 100…130, 200…250
Threshold 0.85 to 1.1 Ur
Electrical motor MCH Consumption (VA or W) 180
Motor overcurrent 2 ot 3 In for 0.1 s
Arming time 6 s maximum
Operating rate 3 cycles maximum per minute
CH contact 10 A/240 V
This release allows remote closing of the circuit breaker when the control
mechanism is armed. It can be permanently or briefly supplied power.
Characteristics XF
Power supply V AC 100…130, 200…250
V DC 24…30, 48…60, 100…130, 200…250
Threshold XF 0.85 to 1.1 Ur
Shunt closing release (XF)
Consumption (VA or W) Triggering 200 (for 200 ms)
Latched 4.5
DEAI02EN.indd 51
Vacuum type switchgear Evolis 17.5 kV circuit breaker
P2 stored energy operating mechanism
Indication
These auxiliary contacts indicate the “open” or “closed” position of the circuit breaker.
b Rotary type changeover contacts directly controlled by the circuit breaker
mechanism.
b Indicator contacts are proposed:
Rotary type contacts (OC)
v for standard relaying applications
v for low level control applications with plc’s or electronic circuits.
This version is compatible with Sepam series 20-40-80 units.
Characteristics
Standard delivery 4
Maximum quantity 12
Breaking capacity (A) Standard Min. load: 100 mA/24 V
Cos ϕ: 0.3 V AC 240/380 10/6 *
CA12/DC12 480 10/6 *
690 6
V DC 24/48 10/6 *
125 10/6 *
250 3
Low level Min. load: 2 mA/15 V DC
V AC 24/48 6
240 6
380 3
V DC 24/48 6
125 6
250 3
* Standard contacts: 10 A; optional contacts: 6 A (temperature derating)
52 DEAI02EN.indd
Vacuum type switchgear Evolis HP circuit breaker
Presentation
DEAI02EN.indd 53
Vacuum type switchgear Evolis HP circuit breaker
Characteristics
54 DEAI02EN.indd
Vacuum type switchgear Evolis HP circuit breaker
RI stored energy operating mechanism
Presentation
This gives the device an opening and closing speed that is independent of the
operator whether the order is electrical or manual.
The electrical control mechanism carries out reclosing cycles and is automatically
recharged by a geared motor each time after closing.
It consists of:
b the stored energy operating mechanism which stores in springs the energy
required to open and close the device
b a manual lever-operated spring arming device
b a geared electrical arming device which automatically re-arms the control
mechanism as soon as the circuit breaker is closed (optional)
b manual order devices by push buttons on the front panel of the device
b an electrical remote closing device containing a release with an antipumping relay
b an electrical opening order device comprising one or several release units which
can be of the following type:
v shunt opening
v undervoltage
v Mitop, a low consumption release, used only with the Sepam 100 LA
protection relay.
b an operation counter
b an “open/closed” position indicator device with a mechanical indicator
b a device for indicating “charged” operating mechanism status by mechanical
indicator and electrical contact (optional)
b a module of 14 auxiliary contacts whose availability varies according
to the diagram used.
Close CB
Open CB
M3
YF + Mitop
anti-pumping YO1 YO2 YM
Remote control
DEAI02EN.indd 55
Vacuum type switchgear Evolis HP circuit breaker
RI stored energy operating mechanism
Opening circuit
Composition
DE57612EN
Characteristics
Power supply V AC (50 Hz) 110, 220
V AC (60 Hz) 120
V DC 24, 48, 110, 125, 220
Threshold Opening 0.35 to 0.7 Ur
Undervoltage release (2) Closing 0.85 Ur
Consumption Triggering V AC 400 VA
V DC 100 W
DE53122
Latched V AC 100 VA
V DC 10 W
56 DEAI02EN.indd
Vacuum type switchgear Evolis HP circuit breaker
RI stored energy operating mechanism
Remote control
Function
DE57604
Remote control enables the remote opening and closing of the circuit breaker.
Composition
The remote control mechanism comprises:
b an electrical motor with gearing
b a shunt closing release (YF) combined with an anti-pumping device
b an operation counter.
V DC 380 W
to be given to opening in the case of a permanent closing order. This thus avoids
the device being caught in an uncontrolled opening-closing cycle.
Operation counter
The operation counter is visible on the front panel.
It displays the number of switching cycles (CO) that the device has carried out.
DEAI02EN.indd 57
Vacuum type switchgear Evolis HP circuit breaker
RI stored energy operating mechanism
Indication
The number of contacts available depends on the options chosen on the operating
mechanism.
In the basic configuration, the circuit breaker’s operating mechanism comprises
a total of:
b 5 normally closed contacts (NC)
b 5 normally open contacts (NO)
b 1 changeover contact (CHG).
The usage procedure for auxiliary contacts is given in the following table:
Options
NC contact NO contact
Shunt opening release (each one) 0 1
Undervoltage release 0 0
Low energy release (Mitop) 0 0
In order to know the final number of available contacts, you must deduct the total
number of contacts included in the circuit breaker (5 NC + 5 NO + 1 CHG),
the number of contacts used given in the table above.
E.g.: a circuit breaker equipped with a remote control and a shunt trip unit has
Operating mechanism the following available contacts:
5 NC + 4 NO + 1 CHG.
With a undervoltage release instead of the shunt trip, this circuit breaker would have
DE53129
58 DEAI02EN.indd
Vacuum type switchgear CTV1 contactor
Presentation
Characteristics
Description
PE56567
Electrical characteristics
Rated voltage kV (50/60 Hz) 7.2
Insulation voltage kV r ms 50 Hz - 1 min 20
kV impulse 1.2/50 µs 60
Operating current A 250 (1)
Rated current A 400
Short time withstand kA r ms 2 s 8
current kA r ms 12 s 4
kA r ms 30 s 2.4
Mechanical endurance (number of operations) 2 500 000 250 000 (2)
Electrical endurance (number of operations) 250 000 250 000 (2)
(1) For greater values: please consult us.
(2) Version with mechanical latching.
Control unit
Supply voltage (3)
V DC: 110, 120 and 220 V
V AC: 100, 110, 120 and 220 V
Possible variations: +10% –15%
(3) Possibility of supplying power through an auxiliary transformer, optional (see page 41).
Consumption
Closing is achieved via the inrush coils.
The latching coils are inserted in the circuit at the end of travel.
Under 100-110 V Inrush Latched
With magnetic latching 5A 0.6 A
With mechanical latching 5.5 A —
Auxiliary contacts
The auxiliary contacts are of changeover type with a common point.
The following are available :
v 3 NO + 3 NC for the magnetic latching version,
v 2 NO + 2 NC for the mechanical latching version.
Contact characteristics
Operating voltage Max. 480 V, min. 48 V
Rated current 10 A
Breaking capacity: V DC: 60 W (L/R 150 ms)
V AC: 700 VA (cos ϕ 0.35)
DEAI02EN.indd 59
Vacuum type switchgear CTV1 contactor
Characteristics (cont.)
125 A
160 A
200 A
250 A
50 A
63 A
80 A
Fuses
The fuses used are of the Fusarc CF or Ferraz type (Standard IEC 60282.1
and DIN 43625) with high breaking capacity.
Substantial fault current limitation reduces the electrodynamic stresses on
the load-side components (contactor, cables, CT, etc).
Trip curves A “blown fuse” device is used to open the three poles of the contactor.
The trip curves for Fusarc CF (figure 1) and Ferraz (figure 2)
fuses are shown above. Rated voltage (kV) 7.2
These are the average curves with an rms current value Max. fuse rating (A) 315 (*)
tolerance I ± 10%. Breaking capacity (kA) 50
* Higher values, please consult us.
DE57472
100
2 Figure 3
Schematic diagrams
Ik
1.
8
Ik
2 Mechanical latching contactor
= =
DE57474
Ia Is 250 A +C +C
M1
200 A Sepam
160 A
125 A verrouillage
S4
enclenchement
80 A closing
XE
XE
63 A interlock
50 A
XU
X20 32 33 4 1 3 40 9 36 20
X61
4 1 3
FU1 K1 FU1
K1
FU1 5
S61 K1
S61
YF
21 K1
XU XE 6 YD
K1 DU P61 O 000
2 7
DE57473
2 10 21
M2
00
Figure 4 -C -C
+C +C
M1
Sepam
verrouillage
enclenchement
XE
closing
interlock
XE
XU
X20 32 33 4 1 3
X61
22 4 1 3
K1
21 FU1 5
22
YF
21 K1
XU XE 6 P61 O 000
DU
Limitation curves 2
Fusarc CF (figure 3) and Ferraz (figure 4) fuses have current
limiting capacity. M2
2
60 DEAI02EN.indd
SF6 type switchgear LF circuit breaker
Presentation
Specific applications
Protection of generators and power station auxiliaries
All circuit breakers in the LF range break short circuit currents with an asymmetry
of at least 30%.
In cases where the network constant X/R is greater than 45 ms, the asymmetry
to be broken is higher; this is often the case of circuit breakers protecting nuclear
or thermal power station auxiliaries or circuit breakers that are close to generator
sets or large transformers.
Specific tests have been carried out:
Circuit breakers kV kA Asymmetry
LF2 7.2 43.5 50%
LF3 7.2 43.5 50%
12 40 50%
17.5 25 100%
DEAI02EN.indd 61
SF6 type switchgear LF circuit breaker
Characteristics
LF3/MCset 3
Rated voltage Ur kV 50/60 Hz 7.2 12 17.5
Insulation voltage
- power frequency withstand Ud kV 50 Hz 1min (1) 20 28 38
- lightning impulse withstand Up kV peak 60 75 95
Rated current Ir A 1250 – – – – – – – b – – b
2500 b b b b b b b b b b b
3150 – b b b – b b b b b b
4000 (4) – – – b – – – b – – b
Short circuit current Isc kA peak 25 31.5 40 50 25 31.5 40 50 25 31.5 40
Short time withstand current Ik/tk kA/3 s 25 31.5 40 50 25 31.5 40 50 (2) 25 31.5 40
Short-circuit making current Ip kA 50 Hz 63 79 100 125 63 79 100 125 63 79 100
60 Hz 65 82 104 130 65 82 104 130 65 82 104
Rated switching sequence O-3 min-CO-3 min-CO b b b b b b b b b b b
O-0.3 s-CO-3 min-CO b b b b b b b b b b –
O-0.3 s-CO-15 s-CO b b b b b b b b b b –
62 DEAI02EN.indd
SF6 type switchgear LF circuit breaker
RI stored energy operating mechanism
Presentation
This gives the device an opening and closing speed that is independent of the
operator whether the order is electrical or manual.
The electrical control mechanism carries out reclosing cycles and is automatically
recharged by a geared motor each time after closing.
It consists of:
b the stored energy operating mechanism which stores in springs the energy
required to open and close the device
b a manual lever-operated spring arming device
b a geared electrical arming device which automatically re-arms the control
mechanism as soon as the circuit breaker is closed (optional)
b manual order devices by push buttons on the front panel of the device
b an electrical remote closing device containing a release with an antipumping relay
b an electrical opening order device comprising one or several release units which
can be of the following type:
v shunt opening
v undervoltage
v Mitop, a low consumption release, used only with the Sepam 100 LA
protection relay.
b an operation counter
b an “open/closed” position indicator device with a mechanical indicator
b a device for indicating “charged” operating mechanism status by mechanical
indicator and electrical contact (optional)
b a module of 14 auxiliary contacts whose availability varies according
to the diagram used
b a single contact pressure switch is activated when the gas pressure exceeds
0.1 MPa (relative pressure: 1 bar).
Close CB
Open CB
M3
YF + Mitop
anti-pumping YO1 YO2 YM
Motor Shunt closing “Control Shunt Under- Low energy Changeover NO NC Pressure
release mechanism opening voltage release contact contacts contacts switch
+ anti-pumping armed” release release (Mitop)
system indicator contact
Remote control
DEAI02EN.indd 63
SF6 type switchgear LF circuit breaker
RI stored energy operating mechanism
Opening circuit
Composition
DE57612EN
Characteristics
Power supply V AC (50 Hz) 48, 110, 220
V AC (60 Hz) 120, 240
V DC 24, 30, 48, 60, 110, 125, 220
Threshold Opening 0.35 to 0.7 Ur
Undervoltage release (2) Closing 0.85 Ur
Consumption Triggering V AC 400 VA
V DC 100 W
DE53122
Latched V AC 100 VA
V DC 10 W
64 DEAI02EN.indd
SF6 type switchgear LF circuit breaker
RI stored energy operating mechanism
Remote control
Function
DE57604
Remote control enables the remote opening and closing of the circuit breaker.
Composition
The remote control mechanism comprises:
b an electrical motor with gearing
b a shunt closing release (YF) combined with an anti-pumping device
b an operation counter.
V DC 380 W
to be given to opening in the case of a permanent closing order. This thus avoids
the device being caught in an uncontrolled opening-closing cycle.
Operation counter
The operation counter is visible on the front panel.
It displays the number of switching cycles (CO) that the device has carried out.
DEAI02EN.indd 65
SF6 type switchgear LF circuit breaker
RI stored energy operating mechanism
Indication and locking/interlocking
The number of contacts available depends on the options chosen on the operating
mechanism.
In the basic configuration, the circuit breaker’s operating mechanism comprises
a total of:
b 5 normally closed contacts (NC)
b 5 normally open contacts (NO)
b 1 changeover contact (CHG).
The usage procedure for auxiliary contacts is given in the following table:
Options
NC contact NO contact
Shunt opening release (each one) 0 1
Undervoltage release 0 0
Low energy release (Mitop) 0 0
In order to know the final number of available contacts, you must deduct the total
number of contacts included in the circuit breaker (5 NC + 5 NO + 1 CHG),
the number of contacts used given in the table above.
E.g.: a circuit breaker equipped with a remote control and a shunt trip unit has
Operating mechanism the following available contacts:
5 NC + 4 NO + 1 CHG.
With a undervoltage release instead of the shunt trip, this circuit breaker would have
DE53129
Shunt opening release 5NC + 3NO + 1CHG 5NC + 4NO+ 1CHG 5NC + 4NO + 1CHG
YO2
Undervoltage release 5NC + 4NO + 1CHG 5NC + 5NO + 1CHG
YM
Mitop 5NC + 4NO + 1CHG 5NC + 5NO + 1CHG
66 DEAI02EN.indd
SF6 type switchgear Rollarc contactor
Presentation
Description
PE56568
FUBT LV fuse
K1 R400 AC MV contactor
P61 Operation counter
S61 Locking contact activated
by the pretrip push button and during
racking in/out operations
SQ1 Contactor limit switch
X20 LV connecter, 42 pins + earth
X51 Control plate
X61 Contactor terminal block
XAP Instantaneous auxiliary relay
XE Instantaneous auxiliary control relay
XU 0.6 s time delay auxiliary relay
YD Shunt trip coil
YF Closing coils
YM Latching coil
S4 Trip button
DEAI02EN.indd 67
SF6 type switchgear Rollarc contactor
Characteristics
Operating schemes
Temporary service or periodic service
The two curve systems (Fig. 1 and 2) can be used to determine the maximum current
surges accepted by the Rollarc 400 contactor, in temporary or periodic service.
b Temporary service: knowing the steady state current Ip, we determine
the maximum duration Ts of a current surge Is from graph 1 (Fig. 2).
b Periodic service: knowing 3 of the following 4 parameters:
v overcurrent Is,
v overcurrent time Ts,
v cooling current Ir,
v cooling time Tr.
We determine the 4th parameter using graph 2 (Fig. 1 and 2).
Operating time
b Opening time 20 to 35 ms,
b Arcing time: < 20 ms,
b Closing time: 80 to 120 ms.
Fig. 2
68 DEAI02EN.indd
SF6 type switchgear Rollarc contactor
Characteristics (cont.)
Fuses
DE57470
125 A
160 A
200 A
250 A
50 A
63 A
80 A
Figure 1
The fuses used are of the FUSARC CF or FERRAZ type (Standard IEC 60282.1
and DIN 43625) with high breaking capacity.
Substantial fault current limitation reduces the electrodynamic stresses
on the load-side components (contactor, cables, CT, etc).
A “blown fuse” device is used to open the three poles of the contactor.
Rated voltage (kV) 7.2 12
Max. fuse rating (A) 315 250*
Breaking capacity (kA) 50 50
* please consult us
Trip curves
DE57471
The trip curves for FUSARC CF (Fig. 1) and FERRAZ (Fig. 2) fuses are shown
Figure 2 opposite.
These are the average curves with an rms current value tolerance ± 10%.
Limitation curves
FUSARC CF (Fig. 3) and FERRAZ (Fig. 4) fuses have current limiting capacity.
These curves give the maximum value of the limited breaking current Ic (in kA peak),
as a function of the value Ip (in kA rms) of the presumed current that would be created
if there were no protection. For further details ask for the fuse catalogues.
Operating mechanism
Trip curves
The trip curves for Fusarc CF (figure 1) and Ferraz (figure 2) Supply voltage (1)
fuses are shown above.
DC: 48, 110, 127 and 220 V
These are the average curves with an rms current value
tolerance I ± 10%. AC: 50, 100, 110, 127 and 220 V
Acceptable variations: +10% –15%
100
2 Figure 3 The latching coils are inserted in the circuit at the end of the stroke of the contactor.
Ik 2
8
1. Ik Consumption Pick-up Latched
= =
Ia Is 250 A
200 A DC 1050 W 30 W
160 A
125 A AC 900 VA 30 VA
80 A
63 A
50 A
b Rollarc 400D contactor
The contacts are mechanically latched in the closed position. They are opened
by a shunt trip release which releases the latching.
Consumption Pick-up coil (2) Shunt trip
DC 1050 W 80 W
AC 900 VA 100 VA
(1) Optional supply possible by auxiliary transformer (see page 41).
(2) Supply time < 0.12 s.
DE57473
Figure 4
Auxiliary contacts
Auxiliary contacts are of the common point changeover type.
The following are available:
b 9 contacts for the Rollarc 400,
b 8 contacts for the Rollarc 400D.
Contact characteristics:
Rated current: 10 A
Breaking capacity: DC (L/R ≤ 0.01 s): 2 A at 110 V
AC (cos.ϕ ≥ 0.3): 10 A at 220 V
Limitation curves
Fusarc CF (figure 3) and Ferraz (figure 4) fuses have current
limiting capacity.
These curves give the maximum value of the limited breaking
current Ic (in kA peak), as a function of the value Ip (in kA rms)
of the presumed current that would be created if there were no
protection. For further details, ask for the fuse catalogues.
DEAI02EN.indd 69
SF6 type switchgear DI switch cubicle
Presentation
Switch
E74222
The three rotating contacts are placed in an enclosure filled with gas to a relative
pressure of 0.04 MPa (0.4 bars).
The system offers maximum operating reliability.
Gas tightness
The SF6 filled enclosure is of the “sealed pressure system type”. Sealing tightness
is always checked in the factory.
Safety
b The switch may be in one of three positions: “closed”, “open” or “earthed”,
giving a natural interlocking system that prevents operator error.
b Moving contact rotation is driven by a fast acting mechanism that is independent
of the operator.
b The device combines the breaking and disconnecting functions.
b The SF6-enclosed earthing switch has a short-circuit making capacity
in compliance with standards.
Breaking principle
The outstanding qualities of SF6 gas are used to extinguish the electrical arc.
To increase cooling of the arc, a relative movement is created between the arc
and the gas. The arc strikes when the fixed and moving contacts separate.
The combination of the current and a magnetic field created by a permanent magnet
causes the arc to rotate around the fixed contact, extending and cooling it until
it is extinguished at current zero point. The distance between the fixed and moving
contacts is then sufficient to withstand the recovery voltage.
This system is both simple and dependable, and it provides improved electrical
endurance due to very low wear of contacts.
1 Enclosure
DE57486
2 6
2 Cover
3 Operating shaft
4 Fixed contact
5 Moving contact
6 Seal
1 3 4 5
DE55122
70 DEAI02EN.indd
SF6 type switchgear DI switch cubicle
Characteristics
v switch (2 O + 2 C),
v switch (2 O + 3 C) and earthing switch (1 O + 1 C),
v switch (1 C) and earthing switch (1 O + 1 C) if motor option.
b Motor option
b Opening release:
v shunt,
v undervoltage (option).
b Closing release: shunt trip.
b Fuse blown release: any fuse blown trips the opening of the switch.
DEAI02EN.indd 71
SF6 type switchgear DI switch cubicle
Fuses
Fuse ratings for MCset protection units depend, among other things,
on the following criteria:
b service voltage
b transformer rating
b fuse technology (manufacturer).
Different types of fuses with medium loaded striker maybe installed:
b Solefuse: fuses as per standard UTE NCF 64.210
b Fusarc CF: fuses as per IEC recommendation 60.282.1 and DIN dimensions 43.625.
For fuse-switch combination unit, refer only to the selection table and reference list of
fuses. For all other type of fuses, consult us.
Example: for the protection of a 400 kVA transformer at 10 kV, select either Solefuse
fuses rated 43 A or Fusarc CF fuses rated 50 A.
Fuses dimensions
Solefuse (UTE standards)
520 Ur Ir L Ø Weight
DE57461
Ø6
(kV) (A) (mm) (mm) (kg)
17.5 6.3 to 63 450 55 2
Ø55
35 450 23 max.
Fusarc CF
Ø Ur Ir L Ø Weight
DE57462
72 DEAI02EN.indd
MCset 17.5 kV Installation
DEAI02EN.indd 73
Installation Extraction withdrawable parts
Extraction table
DE57468
Racking handle
DE57582
Marine application
DE57485
74 DEAI02EN.indd
Installation Implementation examples
MCset 17.5 line up switchboard
Line up switchboard
(2 supplies cubicles and 1 bussection)
DE57487
200
500 570 570 900 900 900 900 570 570 570 500
2 feeders Incomer Bussection Incomer 3 feeders
cubicle AD1 cubicle AD3 cubicles CL3/GL3 cubicle AD3 cubicle AD1
Room
entrance
(1) (1)(5)
2500 2800
(3) (4)
200 1550 1520 - 1720
(1)
B 420 810 A
(2)
1100
(1) Minimum dimensions to be complied with when installing the MCset switchboard.
(2) Minimum dimensions to be defined according to the cable bending radius.
(3) Operating distance.
(4) Distance needed to extract a functional unit from the switchboard without moving
the other units.
(5) Provide an exhaust tunnel above the switchboard when the room height is less than 4 metres
(see page 18).
A anchor point
B adjustment point
Note: for further information, refer to the civil engineering, user and instruction manual.
DEAI02EN.indd 75
Installation Implementation examples
MCset/Motorpact transition switchboard
Transition switchboard
(2 supplies cubicles and 1 bussection)
DE57490
200
804
500 375 375 375 375 900 900 900 900 375 375 375 375 500
3 feeders Incomer Bussection Incomer 3 feeders
cubicle Motorpact cubicle AD3 cubicles CL3/GL3 cubicle AD3 cubicle Motorpact
Transition Transition
cubicle cubicle
(3) (4)
804 992 1520 - 1720
MCset Motorpact
(2) (2)(5)
2500 2800
Room
entrance
825 425
(1)
1425 208 1200
Note: for further information, refer to the civil engineering, user and instruction manual.
76 DEAI02EN.indd
Installation Connections
3 key factors
b The need for correctly made connections
New cold connecting technologies offer easy installation and favour durability
in time. Their design means they can be used in polluted environments with harsh
atmospheres.
b The impact of relative humidity
The installing of a heating element is essential in climates with high relative
humidities and significant temperature differentials.
b Ventilation control
The dimensions of air vents must be appropriate for the dissipated energy
in the substation. They must only sweep across the transformer environment.
Cold connected terminals
Schneider Electric’s experience has led it to favour this technology wherever
possible for optimum durability.
The maximum acceptable cable cross-section for standard assemblies are:
b 630 mm2 for incomer or feeder cubicles with single-pole cables,
b 400 mm2 for incomer or feeder cubicles with three-pole cables,
b 95 mm2 for transformer protection cubicles with fuses.
Access to the compartment is only possible when the earthing switch is closed.
Tightening torques for cables will be attained using a dynamo wrench set to 50 mN.
DEAI02EN.indd 77
Installation Connections (cont.)
(1) When installing with a LV core balance CT, use a LV core balance CT of type ARC3
when connecting with 2 cables (see page 40).
Figure 2 b The cubicles and cables requiring the maximum depth should be taken into
consideration when determining the depth P of a switchboard cable duct (figure 1).
b When using cables of length greater than 460 mm, install an additional
compartment as marked (A) under the cubicle (figure 2).
DE56774
78 DEAI02EN.indd
MCset 17.5 kV Appendices
Cubicle equipment 80
Current transformers 81
Selection guide
Notes 82
DEAI02EN.indd 79
Appendices Cubicle equipment
Key:
b: basic equipment
v: option
(1) Basic equipment with earthing switch option.
(2) According to the room in which the MCset switchboard is installed, you can choose option 3 or 4 sides,
and possibly an exhaust tunnel for hot gases (see page 18).
(3) Connection 1 or 2 cables per phase.
(4) 1 NO + 1 NC available.
(5) Compartment protection.
(6) For 4000 A/95 kV impulse: insulated busbar compulsory.
(7) Consult us.
80 DEAI02EN.indd
Appendices Current transformers
Selection guide
Type of cubicle Accuracy class AD1 AD1 fuse- AD2 AD2 AD3 CL1 CL2
and ratio contactor CL3
Isc kA 1 s 31.5 NA (1) 40 50 50 31.5 50
Ratio number 1
Accuracy class 40-80/1 or 5 v 10/1-1 or 5-5 v
and ratio 2.5-5 VA - 5P20 2.5 VA - 5P20
15 VA - cl 0.5
50-100/1-5 v 20/1-1 v v
2.5-5 VA - 5P20 2.5 VA - 5P20
15 VA - cl 0.5
2000/1-1 or 5-5 v
15 VA - 5P20
30 VA - cl 0.5
2500/1-1 or 5-5 v
15 VA - 5P20
30 VA - cl 0.5
(1) Short-circuit current withstand is co-ordinated with the current limited through the fuses.
Other characteristics are available, including the possibility of having 3 secondary windings.
Please consult us detailing the type of protection or measuring required as well as the impedance of the outside loads and the cabling.
DEAI02EN.indd 81
Appendices Notes
82 DEAI02EN.indd
ART.960195 © Schneider Electric Industries SAS - All rights reserved
Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35,rue Joseph Monier of the information given in this publication.
CS 30323
F - 92506 Rueil Malmaison Cedex This document has been printed
on ecological paper
RCS Nanterre 954 503 439
Capital social 896 313 776 € Publishing: Schneider Electric Industries SAS
www.schneider-electric.com Design: Graphème
Printing: Made in France
DEAI02EN 01-2009