Hull No. :-
Classification :-
Work order No. :-
Equipment type : Boiler control panel
Aux. boiler
Upgrade system
PLAN HISTORY
The atomizing steam pressure low alarm was configured to operate only in the
atomizing valve open state. However, it has been found that a valve fault may not
cause an atomizing steam pressure low alarm.
The upgraded system has been developed to make an alarm and boiler/burner trip
due to low atomizing valve steam pressure when open command to atomizing valve
or F.O. valve is active.
The upgraded system is eliminating the potential dangers and improving the safety of
the system. This can be verified by using many simulation test.
Atomizing steam
valve open limit is
On
Atomizing
steam press. Normal
switch on? operation
Yes
No
Boiler trip
Audible and visible
alarm
Common trip to AMS.
The atomizing
valve 's
solenoid is
powered
Atomizing
steam press. Normal
switch on? operation
Yes
No
Boiler trip
Audible and visible
alarm
Common trip to AMS.
Atomizing
Steam valve open
(Delay 30s)
OR
Atomizing
Oil supply steam press. Low
valve open AND Boiler trip
Common trip
Atomizing
steam press.
Switch off
(delay 2sec)
* After the program update, enter the information and results of the ship.
Please send this page by E-mail.
E-mail address: service department: service@kangrim.com
electric department: electric@kangrim.com
1) Before Update
The update will change the parameter values recorded within the PLC.
Therefore , you must record the parameter values or save them as a picture
prior to the update system. (Please refer the reference picture.)
6) Setting
MAIN->SETTING