Professional Documents
Culture Documents
INVERTERS
(1) Single phase Bridge Inverter: Single-phase bridge inverters are two types:
(a) Single-phase half bridge inverter (b) Single-phase full bridge inverter
(a) Single-phase half bridge inverter
The voltage waveform of single-phase full-bridge inverter can be resolved into Fourier series as:
∞
4Vs
v o= ∑ nπ
sin nωt
n=1 ,3 , 5 ,…
Where n = order of harmonic
ω = frequency of output voltage in rad/sec
If n = 1:
√[ ( )]
2
2 1
Z n= R + nωL−
nωC
ϕ n=tan
−1
( nωL−
1
nωC )
R
If I o 1 = RMS value of fundamental component of load current
The fundamental output power is given by:
2
Po 1=I o 1 R=V o 1 I o 1 cos ϕ1
Forced Commutated Thyristor Inverters
(1) Modified McMurray Half-Bridge Inverter
i c =V s
√ C
L
sin ω o t=I cp sin ω o t
Where I cp=V s
√ C
L
1
ω o=
√ LC
Circuit turn-off time for main thyristor T1 is
t c=
1
ωo [
π −2 sin
−1 I o
I cp ( )]
The value of resistance that gives critical damping is
Rd =2
√ L
C
Modified McMurray Full-Bridge Inverter
The number of thyristors, diodes and other components are double that of half-bridge inverter.
Modified McMurray Bedford Half-bridge Inverter
It uses less number of thyristors and diodes compared to Modified McMurray half-bridge inverter.
This is a complementary-commutated inverter.
Circuit turn-off time
π
t c< √ LC
2
V s tq
L=2.35
I om
I om t q
C=2.35
Vs
t q = thyristor turn-off time
( )
∞
4Vs nπ π
v ab= ∑ nπ
cos sin n ωt +
6 6
n=1 ,3 ,5 , ..
( )
∞
4V s nπ π
v bc= ∑ nπ
cos
6
sin n ωt −
2
n =1 , 3 ,5 ,..
( )
∞
4V s nπ 5π
v ca= ∑ nπ
cos
6
sin n ωt +
6
n=1 ,3 , 5 ,..
3π
For n = 3, cos =0. Thus, all triplen harmonics are absent from the line voltages.
6
For linear delta connected load, phase and line currents are obtained from the above expressions.
The line voltage waveforms represent a balanced set of three-phase alternating voltages.
The line voltages are independent of the nature of the load circuit which may consist of any
combination of resistance, inductance and capacitance and the load may be balanced or
unbalanced, linear or nonlinear.
Line to neutral voltage using Fourier series can be expressed as:
∞
2V s
v ao= ∑ nπ
sin nωt
n=6 k ±1
∞
2V s
v bo= ∑ nπ
sin(nωt−120o )
n=6 k ±1
∞
2V s
v ao= ∑ nπ
sin(nωt−240o )
n=6 k ±1
Where k = 0, 1, 2, …..
V L ( rms )=
√ 2
V =0.8165 V s
3 s
RMS value of phase voltage
V L (rms) √ 2
V ph ( rms )= = Vs
√3 3
The phase voltages have one positive pulse and one negative pulse (each of 120° duration) for one
cycle of output alternating voltage.
The line voltages have six steps per cycle of output alternating voltage.
The Fourier analysis of phase voltage waveform gives:
( )
∞
2Vs nπ π
v ao= ∑ cos sin n ωt +
n=1 ,3 ,5 , .. nπ 6 6
( )
∞
2Vs nπ π
v bo= ∑ cos sin n ωt−
n=1 ,3 ,5 , .. nπ 6 2
( )
∞
2V s nπ 5π
v co= ∑ nπ
cos
6
sin n ωt +
6
n=1 ,3 , 5 ,..
( )
∞
3.V s π
v ab = ∑ nπ
sin n ωt +
3
n=6 k ±1
( )
∞
3. V s π
v bc= ∑ sin n ωt −
n =6 k± 1 nπ 3
∞
3. V s
v ca= ∑ sin n ( ωt−π )
n=6 k ± 1 nπ
Where k = 0, 1, 2, 3, ….
V ph ( rms )=
√ 2 Vs Vs
. = =0.4082V s
3 2 √6
Advantages:
Output voltage waveform and its harmonic content are not affected appreciably as the inverter
output voltage is controlled through the adjustment of dc input voltage to the inverter.
Disadvantages:
Increased number of power conversion stages result in more losses and reduced efficiency of the
entire scheme.
Reducing the ripple content of dc voltage input to the inverter, filter circuit is required in all types of
schemes. This increases the cost, weight and size and at the same time reduces efficiency and
makes the transient response sluggish.
For a large variation of output voltage for a constant load current control of dc input voltage is not
conducive.
(C) Internal Control of Inverter
The most efficient method of controlling the output voltage of an inverter internally is Pulse Width
Modulation (PWM) control.
In this method, a fixed dc input voltage given to the inverter and a controlled ac output voltage is
obtained by adjusting ON and OFF periods of the inverter components.
Advantages of PWM:
No additional components are used
Lower order harmonic can be eliminated or minimized along with its output voltage control. As
higher order harmonics can be filtered easily, the filtering requirements are minimized.
SCRs used in this method are expensive as they must possess low turn-on and turn-off times.
PWM Inverters
PWM techniques are characterized by constant amplitude pulses. The width of these pulses
modulated to obtain inverter output voltage control and to reduce its harmonic content.
In PWM inverters, forced commutation is essential.
Different PWM techniques are:
(1) Single-Pulse Modulation
(2) Multiple-Pulse Modulation
(3) Sinusoidal-Pulse Modulation
∞
4Vs nπ
v o= ∑ nπ
sin
2
sin nd sin nωt
n=1 ,3 , 5 ,…
v o=
4V s
π [ 1 1
sin d sin ωt− sin 3 d sin 3 ωt + sin 5 d sin 5 ωt … ..
3 5 ]
When pulse width 2d = π, then the fundamental component of output voltage, has a peak value of
4V s
v o 1m =
π
For pulse width other than 2d = π, the peak value of fundamental component is
4V s
v o 1m = sin d
π
π 2π
If nd=π or d= or if pulse width is made equal to 2 d= , shows that nth harmonic is eliminated
n n
from the inverter output voltage.
o
2× 180
To eliminate 3rd harmonic, pulse width of 2d = = 120°.
3
o
2× 180
th
To eliminate 5 harmonic, pulse width of 2d = = 72°.
5
o
2× 180
To eliminate 7th harmonic, pulse width of 2d = = 51.42°.
7
The peak value of nth harmonic is
4Vs
v onm= sin nd
nπ
v onm sin nd
=
vo1 m n
In this method a great deal of harmonic content is introduced in the output voltage, particularly at
low voltage levels.
The rms value of output voltage
V ¿ =V s
√ 2d
π
(2) Multiple Pulse Modulation
It is an extension of single pulse modulation.
In MPM, several equidistant pulses per half cycle are used.
π−2 d
θ1=
N +1
d
θ2=¿ half of the pulse width =
N
π−2 d d
γ= +
N +1 N
Where N = number of pulses per half cycle.
Fundamental component of output voltage is lower for two-pulse modulation than it is for single-
pulse modulation.
For larger value of pulses per half cycle, the amplitudes of lower order harmonics are reduced but
those of some higher order harmonics are increased significantly which can be filtered out easily.
1
For traingular carrier wave, pulse width = f
c
1
For square reference wave, width of half-cycle =
2f
Number of pulses per half cycle = Number of hill tops for half cycle
1/2 f f c ωc
N= = =
1/f c 2 f 2 ω
Pulse width
2d
N [ ]
= 1−
Vr π
Vc N
V ¿ =V s
√ 2d
π
( N−1 ) or [ fc
2f ]
−1 pulses per half cycle.
Modulation Index controls the harmonic content of the output voltage waveform.
The magnitude of fundamental component of output voltage is proportional to MI.
MI can never be greater than unity.
Features of SPM:
For MI < 1, largest harmonics amplitudes in the output voltage are associated with harmonics of
fc
order ± 1 or 2N ± 1, where N is the number of pulses per half cycle. Thus by increasing the
f
number of pulses per half cycle, the order of dominant harmonic frequency can be raised, which
can then be filtered out easily. If N = 5, 9th and 11th harmonics are dominant in the output voltage.
With increase in N, order of significant harmonic increases, and the filtering requirements are
reduced.
Higher value of N requires higher switching frequency of thyristors. This increases switching losses
and reduces inverter efficiency. Thus a compromise between the filtering requirements and inverter
efficiency should be made.
For MI > 1, lower order harmonics appear. Also, pulse width is no longer a sinusoidal function of
the angular position of the pulse.
When there are several pulses per half cycle, lower-order harmonics are eliminated.
Output voltage waveform that can be obtained form an inverter is shown below.
This waveform needs ten commutations per cycle instead of two in an unmodulated wave.
The voltage waveform is symmetrical about π as well as π/2.
The amplitude of the fundamental voltage is 83.91% or 0.8391 times the amplitude of fundamental
component of unmodulated wave.
3rd and 5th harmonics are eliminated from the inverter output voltage wave.
7th, 9th and 11th harmonics are 24.78%, 40.86% and 30.37% of the fundamental component of the
unmodulated wave.
Disadvantages:
Inverter is derated by 16.09%.
Additional 8 commutation per cycle leads to more switching losses.
Harmonic reduction by transformer connections
Output voltage from two or more inverters can be combined by means of transformers to get a net
output voltage with reduced harmonic content.
The essential condition is that output voltage waveforms from the inverters mus be similar but
phase-shifted from each other.
With this type of connection, 3rd and triplen harmonics are eliminated from net output voltage
wave.
The amplitude of fundamental component of v o
4Vs
V o 1 m= √3
π
When there is no phase shift between the voltages v o 1 and v o 2, the amplitude of fundamental
component would be
8Vs
V o 1 m=
π
With phase shift between voltages v o 1 and v o 2, the amplitude of fundamental voltage =
√3 times
2
the amplitude of fundamental voltage with no phase shift.
With this type of method, the derating of inverter is 13.4%.
The main disadvantage of this method is the requirement of a greater number of inverters and
transformers of similar ratings.
Harmonic reduction by stepped wave inverters
In this method, pulses of different widths and heights are superimposed to produce a resultant
stepped wave with reduced harmonic content.
The two transformers used have different turns ratio from primary to secondary.
Inverter-1 output is two level modulated and inverter-2 output is three level modulated.
Series Inverters
Inverters in which commutating components are permanently connected in series with the load are
called ‘series inverters’. The series circuit so formed must be underdamped.
Series inverters are also classified as ‘self-commutated inverters’.
These inverters operate at high frequencies (200Hz to 100kHz), the size of commutating
components is therefore, small.
These inverters are used in induction heating and fluorescent lighting.
Basic series inverter
DC CHOPPERS
¿ D .V s
T on
D= = Duty cycle
T
Vo
Average thyristor current, V o , Th=
R
RMS load voltage, V orms =√ D .V s
Disadvantage:
T on cannot be reduced to near zero. Low range of D control is not possible in PWM. Increasing or
decreasing chopping period is possible.
(ii) Variable frequency system
F or T is varied and either (a) T on is kept constant (b) off-time is kept constant.
This is called ‘frequency modulation scheme’.
Step-up choppers
For a basic dc to dc converter, the critical inductance of the filter circuit is,
( V s −V o ) T on V o2 ( V s −V o )
L= =
2 Io 2 f V s Po
V o =¿ Load voltage, V s =¿ Source voltage, Po =¿ Load power, f = Chopping frequency
If type-A chopper is feeding an RLE load, the average input (or thyristor) current is
D ( V s −E ) L
I T , av=
R
− ( I −I )
RT max min
If type-A chopper is feeding an RLE load, the maximum value of average thyristor current is
2
E
I T , max=
4 VsR
If type-A chopper is feeding an RLE load, the average value of freewheeling diode current is
I max −I min E
I fd , av= − ( 1−D )
TR R
If type-A chopper is feeding an RLE load, the average load current is
DV s−E
I o ,av =
R
( V s−E ) . T on=L. ∆ I
In type-A chopper, under continuous mode of operation, the peak to peak (p.u) ripple in load
current is maximum when D = 0.5.
Vs
The maximum value of ripple current, ∆ I max =
4 fL
Maximum value of ripple current is inversely proportional to chopping frequency and the
inductance.
In type-A chopper, for discontinuous current mode, the average voltage is given by,
V o =DV s + 1− [ ] tx
T
E
t x =¿ Extinction time
T on
D=
T
sin 2 πnD
θn =
1−cos 2 πnD
Maximum value of nth harmonic occurs when sin nπD=1 and its value is
2V s 0.6366 V s
=
πn n
RMS value of nth harmonic is
2V s 0.45V s
=
πn √ 2 n
Z n=√ R + ( nωL )
2 2
V r =√ V rms2−V o2
V r =V s √ D−D2
AC ripple voltage V r
Ripple voltage= =
Average voltage V o
R . F=
√ 1−D
D
=
√1
D
−1
Disadvantages:
π
(iii) Turn-off time for TA, t c1 = √ LC
2
( )
2
Vs
(v) Commutating inductor, L ≥ C
Io
[
(ii) Circuit turn-off time for main SCR T1, t c = π−2 sin
−1
( )]
Io
I cp
[
(iii) Turn-off time for main SCR ¿ π−2sin
−1
( )] √
Io
I cp
LC
T
(vi) The value of charging resistor, Rc ≤
3C
Design considerations:
2Vs
(i) I o=C
T on
2
2. V s .C . f
(ii) V o =
Io
1
(iv) Maximum chopping frequency, f max=
T on
Io
(v) C=
2.V s . f max
C .V s
(vi) Circuit turn-off time for each thyristor, t c =
Io
2. C . V s
(vii) Total commutation interval ¿ T on=
Io
Advantages:
(ii) No commutating inductor is required that is normally costly, bulky and noisy.
Disadvantages:
(i) Peak load voltage is equal to twice the supply voltage. This peak can however be reduced by filtering.
(ii) For high-power applications, efficiency may become low because of higher switching losses at high
operating frequencies.
(iv) The commutating capacitor has to carry full load current at a frequency of half the chopping frequency.
(v) One pair of SCRs should be turned on only when the other pair is commutated. This can be done by
sensing the capacitor current that is alternating.
Multiphase Choppers
I max=
Vo Vo
+
R 2 fL [ ]
1−
Vo
Vs
I min =
Vo V o
−
R 2 fL
1−
[ ]
Vo
Vs
Vo
∆ I =I max −I min= T
L off
t on v control
D= =
Ts V^ st
Vd
k= =constant
V^ st
( V d −V o ) t on=V o ( T s−t on )
Io V d 1
= =
Id V o D
I d = Average input current
1 t on DTs
I LB = i L , peak =
2 2L
( V d −V o )=
2L
( V d −V o ) =I oB
If the average output current becomes less than I LB then i L will becomes discontinuous.
Discontinuous conduction mode:
The output current required for a continuous conduction mode is maximum at D = 0.5.
T sV d
I LB ,max =
2L
I LB =4 I LB, max D ( 1−D )
The average inductor current at the edge of the continuous conduction mode is
T sV o
I LB = ( 1−D )
2L
If V o is kept constant, maximum value of I LB occurs at D = 0.
T sV o
I LB ,max =
2L
I LB =( 1−D ) I LB ,max
D=
√
V o I o /I LB, max
V d 1−V o /V d
1 1 ∆ IL Ts
∆ V o=
2C 2 2
Ts Vo
∆ V o= (1−D ) T s
8C L
()
2 2
∆ V o 1 T s ( 1−D ) π 2 fc
= = ( 1−D )
Vo 8 LC 2 fs
1 1Vd T sV o
I LB = I L , peak = t on= D ( 1−D )
2 2 L 2L
Average output current at the edge of discontinuous conduction is
T sV o 2
I oB= D (1−D )
2L
I LB reaches maximum at D = 0.5.
T sV o
I LB ,max =
8L
I oB has its maximum at D = 1/3 = 0.333.
2 T sV o T sV o
I oB ,max = =0.074
27 L L
I LB =4 D (1−D ) I LB, max
27 2
I oB= D ( 1−D ) I oB ,max
4
With constant V o , if the average load current falls I oB, the current conduction will become
discontinuous.
V o ∆1 + D
=
Vd ∆1
Io ∆1
=
I d ∆1 + D
The average input current is equal to the inductor current, and is given by
Vd
I d= D T s ( D+ ∆1 )
2L
I o= ( )
TsVd
2L
D ∆1
D=
√[ 4 Vo Vo
(
27 V d V d
−1
)
Io
I oB , max
2
]
1 2 (V d D T s )
Li = w−s
2 L, peak 2L
Output voltage ripple:
∆ V o DT s D T s
= =
Vo RC τ
1 T sV d
I LB = i l , peak = D
2 2L
I o=I L −I d
Average output current and the output current at the border of continuous conduction in terms of V o
T sV o
I LB = ( 1−D )
2L
T sV o 2
I oB= ( 1−D )
2L
Both I LB and I oB result in their maximum values at D = 0.
T sV o
I LB ,max =
2L
T sV o
I oB ,max =
2L
I LB =I LB ,max ( 1−D )
2
I oB=I oB ,max (1−D )
D=
Vo
√ Io
V d I oB ,max
Vd
V o= v =k v control
V^ tri control
The waveform for the output voltage V o shows that the voltage jumps between +V d and −V d .
Hence this switching strategy is called “Bi-polar switching voltage PWM”.
The average output voltage can either be positive or negative.
(ii) PWM with unipolar voltage switching:
A triangular waveform is compared with the control voltage v control and −v control for determining the
switching signals for leg A and leg B, respectively.
A comparison of v control with v tri control leg A switches, whereas leg B switches are controlled by
comparing −v control with v tri in the following manner:
T A+ ¿on :if v control > v tri ¿
The average output voltage in this scheme is same as that in the bi-polar voltage switching scheme
and varies linearly with v control.
Fig (e) and fig (f) show the current waveforms and the devices conducting for I o >0 and I o <0, where
V o is positive in both cases.
NOTE: If the switching frequencies of the switches are the saame in these two PWM strategies, then
the unipolar voltage switching results in a better output voltage waveform and in a better frequency
response, since the ‘effective’ switching frequency of the output voltage waveformis doubled and the
ripple is reduced.
In step-down and step-up converters, if the input and the output voltages are of the same order of
magnitude, then the switch utilization is very good. Therefore, for nonisolated converters, it is
preferable to use either step-up or step-down converter from the switch utilization consideration.
In the buck-boost and the Cuk converter, the switch is poorly utilized. If both higher as well as lower
output voltages compared to the input are necessary or a negative polarity output compared to the
input is desired, then the buck-boost or the Cuk converter should be used.
The maximum switch utilization of 0.25 is realized at D = 0.5, which corresponds to V o =V d
In the nonisolated full-bridge converter, the overall switch utilization is also poor. It is maximum at
V o =−V d and V o =V d respectively. Hence it should only be used if four quadrant operation is
required.
Diode Circuits and Rectifiers
(I) Diode circuits with dc load:
(a) With R-load:
Vs
i=
R
(b) With RC-load:
V s −t
i (t )= . e RC
R
v ( t )=V (1−e )
−t
RC
c s
( )
−R
Vs t
i (t )= . 1−e L
R
−R
t
L
v L ( t )=V s . e
i (t )=V s .
√ C
L
sin ωo t
1
Where ω o= =¿ Resonant frequency
√ LC
v c ( t )=V s ( 1−cos ω o t )
v L ( t )=V s cos ωo t
π
Conduction time of diode, t o= =π √ LC
ωo
v c ( t )=−V o cos ωo t
π
Conduction time of diode, t o= ω =π √ LC
o
Roots are: S=
−R
2L
±
√( R 2 1
2L
−
LC )
¿−ξ ± √ ξ 2−ω o2
R
Where ξ= = Damping factor
2L
1
ω o= = Resonant frequency
√ LC
Ringing frequency, ω r=
1
−
LC 2 L√
R 2
( )
= √ ω o2−ξ 2
ω o=√ ω r2 +ξ 2
If ξ <ω o, the roots are complex and the circuit is said to be underdamped.
If ξ >ω o, the roots are real and the circuit is said to be overdamped.
If ξ=ωo, the roots are equal and the circuit is said to be critically damped.
π
Conduction time of diode t 1= ω
r
( )
−R
Vs t
When S is closed, i= 1−e L
R
Vs
Final current, i=
R
V s −LR t
When S is opened, i= .e
R
(h) Diode and L circuit:
Vs
When S is closed, i= t
L
Vs
When S is opened, i fd = t
L 1
2
1 Vs
Energy stored in the inductance, E= t
2 L 1
(2) Single-phase diode rectifiers
(i) Single-phase half wave rectifier (single-phase one-pulse rectifier)
(a) With R-load:
Vm
Average value of output (load) voltage, V o =
π
Vm
RMS value of output voltage, V ¿ =
2
Vo Vm
Average load current, I o= =
R πR
V¿ Vm
RMS value of load current, I ¿= =
R 2R
Vm
Peak value of load or diode current, I m=
R
Peak inverse voltage, PIV = V m =√ 2 V s
Power delivered to resistive load = (RMS load voltage) × (RMS load current)
= V ¿× I¿
Vm Vm
= ×
2 2R
2
V
= m
4R
2
Vs
=
2R
= I ¿2 R
¿ V × I V √ 2V s
Input power factor = Power delivered ¿ load = ¿ ¿= ¿= =0.707 lag
input VA V s × I ¿ V s 2V s
(b) With L – load:
Vm
i o= ( 1−cos ωt )
ωL
v o=V m sin ωt=v s
Average value of output voltage V o =0.
2Vm
Peak value of current, I max=
ωL
2V m 1
Average value of current, I o= = I
ωL 2 max
V s Io
RMS value of fundamental current, I 1r = =
ωL √ 2
1
Average value of current, I o=
2 πR
[ 2 V m cos θ1−E ( π −2θ 1) ]
RMS value of the load current,
I ¿=
√ 1
2π R 2 {( s
V 2+ E 2 ) ( π −2 θ1 ) +V s2 sin 2θ 1−4 V m E cos θ1 }
2
Power delivered to load, P=E I o + I ¿ R
Supply power factor =
2
¿ E I o+ I ¿ R
Power delivered ¿ load =
( Source voltage ) ( RMS value of source current ) V s .I¿
PIV for diode = ( V m + E )
(e) With RL – Load:
Vm
Average value of output voltage, V o = ( 1−cos ωt )
2π
Vo
Average value of load or output current, I o=
R
(f) With RL – Load and Freewheeling diode:
Vm
Average output voltage, V o =
π
(3) Single-phase full-wave diode rectifiers:
2Vm
Average output voltage, V o =
π
Vo
Average output current, I o=
R
Vm
RMS value of output voltage, V ¿ = =V
√2 s
V¿
RMS value of load current, I ¿=
R
Power delivered to load, P=V ¿ . I ¿ =I ¿ 2 R
Input volt-amperes = V s . I ¿
V ¿.I¿
Input power factor = =1
V s .I¿
PIV = 2V m
(4) Single-phase full-wave diode bridge rectifier:
2Vm
Average output voltage, V o =
π
Vo
Average output current, I o=
R
Io
Average value of diode current, I D ,av =
2
Io
RMS value of diode current, I D ,rms =
√2
For constant load current,
I ¿=I o
I s=I o
Load power = V o I o
Input power = V s I s cos ϕ
V o Io
Supply power factor, cos ϕ=
V s Is
(5) Zener diode:
V s −V z
Source current, I s=
Rs
Vz
Load or output current, I o=
R
Current through Zener diode, I z =I s−I o
(6) Three-phase half-wave diode rectifier:
3 √3
V mp = √ V ph, rms
3 6
V o=
2π 2π
V mp=¿ Maximum value of phase voltage (line to phase voltage).
(7) Three-phase full bridge rectifier (or) 3-phase 6-pulse diode rectifier:
3 V mL 3 √ 2V Lrms
V o= =
π π
V mL is the maximum value of line or line to line voltage V L.
Phase-Controlled Rectifiers
(1) Single-phase half-wave controlled converter:
(i) With R-Load:
π
(a) Circuit turn-off time, t c =
ω
Vm
(b) Average load voltage, V o = ( 1+cos α )
2π
Vo
(c) Average load current, I o=
R
=
√ 2 V s2
2R√π √[ 1
( π−α ) + sin 2 α
2 ]
(h) Input power factor = Power delivered ¿ load ¿ V .I V
= ¿ ¿= ¿=
1
Input VA V s . I ¿ V s √ 2 π √[ ( 1
π −α )+ sin 2 α
2 ]
(ii) With RL – Load:
(a) Conduction angle = Extinction angle – Firing angle
γ =β−α
2 π−β
(b) Circuit turn-off time, t c =
ω
Vm
(c) Average load voltage, V o = ( cos α −cos β )
2π
Vo V m
(d) Average load current, I o= = ( cos α −cos β )
R 2 πR
√
Vm
(e) RMS load voltage, V ¿ = ( β−α )− 1 ( sin 2 β−sin 2 α )
2√ π 2
(iii) With RL – Load & FD:
π
(a) Circuit turn-off time, t c =
ω
Vm
(b) Average load voltage, V o = ( 1+cos α )
2π
Vo
(c) Average load current, I o=
R
(d) FD improves input pf, load current and load performance.
(iv) With RLE – load:
( ) } ]
¿
1
2 πR [ { γ γ
2V m sin α + sin −E . γ
2 2
¿
Vm
2
(
E
cos α +cos θ1 ) + 1+
2 π (
θ1 + α
)
If thyristor is fired continuously, θ1=α
1
I o=
2 πR
[ 2 V m cos θ1−E ( π −2θ 1) ]
1
V o =E+ I o R=E+
2π
[ 2V m cos θ1−E ( π−2θ1 ) ]
(c) RMS value of load current,
I ¿=
√ 1
2π R 2 {(
E 2+V s2 ) ( π −2 α ) } +V s2 sin 2 α −4 V m E cos α
[ ]
1 /2
1 V max
RMS value of load voltage, V orms = ( π −α )+ sin 2 α
√2 π 2
[ ]
1 /2
π −α sin 2 α
¿Vm +
2π 4π
[ ]
1/ 2
V V π −α sin 2 α
RMS value of load current, I orms = ¿ = m +
R R 2π 4π
(ii) With RL-Load:
π −α
Circuit turn-off time, t c =
ω
2Vm
Average value of output voltage, V o = cos α
π
PIV = 2V m
(iii) With RL-Load & FD
Vm
The average dc output voltage, V o = ( 1+ cos α )
π
Vo Vm
Average dc load current, I o= = ( 1+cos α )
R πR
α Vm
Current through the freewheeling diode, I FD =I o = α ( 1+cos α )
π πR
(3) Single-phase full-wave converters:
(i) Half-controlled converter or semiconverter
In symmetrical configuration, the voltage source and the load are connected in parallel across the
two semiconductor switches. In this configuration, the voltage across the load is always equal to the
voltage across the source.
In asymmetrical configuration, the voltage source and the load are connected in series across the
two semiconductor switches. In this, the voltage across the load is not always equal to the voltage
across the voltage source. The voltage across the load depends on the conduction angle of the
semiconductor switch.
Symmetrical configuration has a lower harmonic content in the input current than the asymmetrical
configuration.
Supply RMS current and average output voltage are also same for both configurations.
The waveforms of diode current i D and thyristor current i T for the two configurations are different.
Let γ T = conduction angle of thyristor
γ D = conduction angle of diode in period of 2π radians.
√
Vm 1
RMS value of output voltage, V ¿ = ( π −α )+ sin 2 α
√2 π 2
(b) With RL – Load & with or without FD:
Vm
Average output voltage, V o = ( 1+ cos α )
π
√
Vm 1
RMS value of output voltage, V ¿ = ( π −α )+ sin 2 α
√2 π 2
(c) With RLE – Load:
π −α
Circuit turn-off time for semiconverter, t c =
ω
Continuous conduction mode:
Vm
Average output voltage, V o = ( 1+ cos α )
π
V o =R I o + E
In case load is a dc motor, E=K m ωm
Torque developed, T e =K m I a =K m I o
V o =I a r a + K m ω m
V o−I a r a
ω m=
Km
Vm
( 1+cos α ) r
π a
ω m= − 2 Te
Km Km
Discontinuous conduction mode:
(i) When π < β < ( π +α ):
Conduction period: α <ωt < π , v o=v s.
For ( π +α ) ¿ 2 π , v o=v s
Freewheeling period: π <ωt < β
FD conducts, i fd =i o and v o=0
For 2 π < ωt < ( π + β ), FD conducts, i fd =i o and v o=0
Idle period: β <ωt < ( π +α ), No circuit component conducts, i o = 0 and v o = E
(ii) When β < π and V m sin β< E:
Conduction period: α <ωt < β , v o=v s.
( π +α ) ¿ ( π + β), v o=v s
Freewheeling period: Absent and i fd =0
Idle period: β <ωt < ( π +α ) and ( π + β ) <ωt < ( 2 π + α ):
No circuit element conduct i o=0 and v o=E
For single-phase semiconverter for β < π :
( )
Vm γ
Average output voltage, V o = ( cos α −cos β )+ E 1−
π π
where γ = conduction angle = ( β−α )
Vm E
Average load current, I o= ( cos α −cos β )− ( β−α )
πR πR
For single-phase semiconverter with β > π :
( )
Vm γ
Average output voltage, V o = ( 1+ cos α ) + E 1−
π π
Vm E
Average load current, I o= ( cos α −cos β )− ( β−α )
πR πR
(ii) Single-phase Fully Controlled bridge converter
(a) With R-Load:
Vm
Average dc voltage across load, V o = ( 1+ cos α )
π
Vo Vm
Average load current, I o= = ( 1+cos α )
R πR
[ ]
1/ 2
Vm 1
RMS value of load voltage, V ¿ = ( π−α ) + sin 2 α
√2 π 2
[ ]
1 /2
π −α sin 2 α
¿Vm +
2π 4π
[ ]
1/ 2
V o V m π−α sin 2 α
RMS value of load current, I ¿= = +
R R 2π 4π
(b) With RL – Load:
2Vm
Average output dc voltage, V o = cos α
π
2V m
Average load current, I o= cos α
πR
For firing angle α <90 ° , circuit acts as rectifier.
o
For firing angle 90° < α <180 , circuit acts as inverter.
Full converter with α >90 o is called “line-commutated inverter”.
(c) With RLE – Load:
Power would flow from dc source to ac supply system, only when E ¿ V o .
π −α
Circuit turn-off time for both converter and inverter operations, t c =
ω
Continuous conduction mode:
2Vm
Average value of output voltage, V o = cos α
π
V o =Ri o + E
In case load is a dc motor, V o =r a I a + K m ω m
2Vm
cos α
π ra
ω m= − 2 Te
km Km
Discontinuous conduction mode:
For β > π , α to β , v o=v s
β to ( π +α ), no SCR conducts, v o=E
At (π+β), i o falls to zero, no SCR conducts, v o=E
For β < π :
α to β , v o=v s
β to ( π +α ),no circuit element conducts, v o=E
( π +α ) to ( π + β ), v o=v s
LINE FREQUENCY DIODE RECTIFIERS (NED MOHAN)
(1) Single-phase diode bridge rectifier:
2√ 2 2Vm
Average dc output voltage ¿ V s=0.9 V s =
π π
2 √2
RMS value of fundamental harmonic of supply current I s 1= I =0.9 I d
π d
I s1
RMS value of harmonic components of supply current I sh =
h
Total harmonic distortion = 48.43%
AC VOLTAGE CONTROLLERS
Integral cycle control:
Output voltage is controlled by connecting the load to source for an integral number of cycles and
then disconnecting the load for a further number of integral number of cycles.
Let n = number of cycles for supply connected to load (number of on cycles)
m = number of cycles for supply disconnected to load (number of off cycles)
In the above fig., n = 3 and m = 2.
Power is delivered to load for n cycles.
Integral cycle control is also known as ‘on-off control’ or ‘burst firing’ or ‘zero-voltage switching’ or
‘cycle selection’ or ‘cycle syncopation’.
[ ]
2 2 2
V¿ V s n Vs
Power delivered to load ¿ = =k .
R R n+m R
RMS value of input current, I s=¿ RMS value of load current, I ¿
V¿
Input VA ¿ V s . I s=V s . I ¿ =V s .
R
Im
Average thyristor current, I T , av=k .
π
Im
RMS value of thyristor current, I T , rms= √ k .
2
This method introduces less harmonics in to the supply system.
This method is used for heating loads and for motor control loads.
√
Vm
RMS thyristor current, I T , rms= ( π−α ) + 1 sin 2 α
2 R √π 2
Vm
Maximum RMS thyristor current, I RM =
2R
I RM π
=
I T , AVM 2
[ ]
2
Vm 1
P= ( π−α ) + sin 2 α
2 πR 2
[( ]
2
Vs 1
P= π −α ) + sin 2 α
πR 2
Maximum power is delivered when α =0 .
2
Vs
P m=
πR
Real power V s I 1 cos ϕ 1 I 1
Power factor ¿ = = cos ϕ 1
Apparent power V s . I rms I rms
I1m
I 1= = rms value of fundamental component of source current
√2
ϕ 1=¿ phase angle between V s and I 1
Power factor ¿
V¿
Vs
=
√
1
π { 1
( π−α ) + sin 2 α
2 }
Single-phase AC voltage controller with RL load:
π
Circuit turn-off time for each SCR, t c =
ω
Conduction angle, γ =β−α
As α is decreased, γ increases.
0 to ϕ – T2 conducts
ϕ to (π+ϕ) – T1 conducts
(π+ϕ) to (2π+ϕ) – T2 conducts and so on
When γ =π :
0 to α – T2 conducts
α to (π+α) – T1 conducts
(π+α) to (2π+α) – T2 conducts and so on
Load voltage is equal to the source voltage
When α =ϕ then γ =π .
The reduction of α below ϕ is not able to control the load voltage and load current.
−1 ωL
The minimum value of firing angle, α =¿ Load phase angle, ϕ ¿ tan
R
The ac output power can be controlled only for α >ϕ . For α ≤ ϕ , γ remains equal to π. Thus the
control range of firing angle is ϕ < α <180o .
The maximum value of rms load current occurs when α =ϕ.
Vs
Maximum value of rms load current, I RM =
√ R + ( ωL )2
2
[ ] d io
dt max
=
ω .V m
Z
CYCLOCONVERTERS
Cycloconverter will provide either a variable frequency power from a fixed input frequency power
(as in ac motor speed control) or a fixed frequency power from a variable input frequency power (as
in aircraft or shipboard power supplies).
Single-phase to single-phase step-up cycloconverter
A step-up cycloconverter requires forced commutation.
Mid-point type Cycloconverter
Bridge-type Cycloconverter
1
In fig., output frequency, f o= f s
8
For positive half cycle, α is varied from 90 o to zero and from zero to 90 o.
For negative half cycle, α is varied from 90 o to 180o and from 180o to 90 o.
Two 3-phase half-wave converters are connected in antiparallel.
Intergroup reactor is connected between two converters to limit the circulating current.
o
α p +α n=180
The magnitude of output voltage and total VA rating of bridge cycloconverter is double that of 18
thyristor cycloconverter.
Gives smooth variation of output voltage.
Control circuit is complex and expensive.
Output voltage equation for a cycloconverter
2π
In m-phase half-wave cycloconverter, each phase conducts for radians in one cycle of 2π
m
radians.
For α =0 o, V o =V m [ m
π
sin
π
m ]
m π
¿ √ 2V ph sin
π m
V ph =¿ RMS value of per phase supply voltage
[ ( ) ( )]
V ¿ =r V ph
m
π
sin
π
m
The above equation is used for 3-phase to 3-phase or 3-phase to single phase cycloconverter
employing m-phase half wave circuits.
The above equation is also applicable for 3-phase to 3-phase or 3-phase to 1-phase cycloconverter
employing 6-pulse bridge converter circuit, but then m is equal to the number of pulses and V ph is
replaced by line to line voltage.