Professional Documents
Culture Documents
Project
**************
ELECTRICAL
Training Module
LIGHTING AND
DOMESTIC
DISTRIBUTION
COURSE CONTENTS
5. EMERGENCY LIGHTING
6. LIGHTING GLOSSARY
INSTALLATION
1
1. GENERALITIES
1.1. Related standards
Most countries have national regulations and or standards governing the rules
to be strictly observed in the design and realisation of electrical installations
for domestic and similar premises. The relevant international standard is the
IEC publication 364.
2
permitted current consumption) an incoming-supply differential circuit breaker,
which includes an overcurrent trip.
This circuit breaker is freely accessible to the consumer. On installations
which are TN-earthed, the supply authorities usually protect the installation
simply by means of sealed fuse cut-outs immediately upstream of the
meter(s). See figure above. The consumer has no access to these fuses.
Where the keraunic level of a locality exceeds 25, and the supply is taken
from an overhead line or underground cable, the installation of a lightning
arrester at the service position of a LV installation is prescribed in many
national standards and is strongly recommended for installations which
include sensitive (e.g. electronic) equipment.
These devices must automatically disconnect themselves from the installation
in case of failure or be protected by a RCD of appropriate sensitivity,
according to the resistance of the earthing electrode for the installation. In the
3
case of domestic installations the use of a 500 mA general differential
incoming-supply circuit breaker type S (i.e. slightly time-delayed) will provide
effective earth-leakage protection, while, at the same time, will not trip
unnecessarily each time a lightning arrester discharges the current (of an
overvoltage-surge) to earth.
2. PROTECTION OF PERSONS
In this case:
4
Recommendation of suitable
components
- Incoming-supply circuit
breaker with 500 mA differential,
and
- RCD of type 30 mA
(for example, differential circuit
breaker 1 P + N type Déclic Vigi)
on the circuits supplying socket-
outlets,
- RCD of type 30 mA
(for example, differential load
switch type ID'clic) on circuits to
bathrooms, shower rooms,
laundry rooms, etc.) (lighting,
heating, socket-outlets).
Recommendation of suitable
components
- Incoming-supply circuit breaker
with 500 mA differential, type S,
and
- RCD of type 30 mA
(for example, differential circuit
breaker 1 P + N type Déclic Vigi)
on the circuits supplying socket-
outlets,
- RCD of type 30 mA
(for example, differential load
switch, type ID'clic) on circuits to
bathrooms, shower rooms, etc.
(lighting, heating, socket-outlets),
- RCD of type 30 mA (for example, differential circuit breaker 1 P +
N, type Déclic Vigi) on circuits supplying washing machines and dish-washing
machines.
5
2.3. Incoming-supply circuit breaker without differential protection
Recommendation of suitable
components
1. Incoming-supply circuit breaker
without differential protection.
6
DOMESTIC DISTRIBUTION
RULES
1
1. CIRCUITS DISTRIBUTION
1.1 Subdivision
2
1.2 protective conductors
IEC and most national standards require that each circuit includes a protective
conductor.
This practice is strongly recommended where class 1 insulated appliances
and equipment are installed, which is the general case.
The protective conductors must connect the earthing-pin contact in each
socket-outlet, and the earthing terminals in class 1 equipment, to the main
earthing terminal at the origin of the installation.
Furthermore, 10/16 A (or similarly sized) socket-outlets must be provided with
shuttered contact orifices.
The c.s.a. of conductors and the rated current of the associated protective
device depend on the current magnitude of the circuit, the ambient
temperature, the kind of installation, and the influence of neighbouring circuits
Moreover, the conductors for the phase wires, the neutral and the protective
conductors of a given circuit must all be of equal c.s.a. (assuming the same
material for the conductors concerned, i.e. all copper or all aluminium).
Table under indicates the c.s.a. required for commonly-used appliances.
3
Type of c.s.a. of Maximum Protective
circuit single the power device
phase 230V
1ph + N + E
conductors
Dish 4 mm² 4600W Circuit
washing breaker 20A
machine Fuse 20A
Clothes 4 mm²) 4600W Circuit
washing breaker 20A
machine Fuse 20A
Cooker or 6 mm² 4600W Circuit
hot plates breaker 32A
Fuse 32A
Electric 2.5 mm² 4600W Circuit
heater or (4 mm²) as breaker 20A
AC unit per power Fuse 20A
* Disturbances
Three types of disturbance often occur on electrical-power networks:
- Lightning and atmospheric electrical phenomena in general, with its direct
and indirect consequences.
The direct effects, which are fairly infrequent, concern its impact on overhead
transmission and distribution lines.
The indirect effects are more common and occur at lower energy levels. Such
indirect phenomena are characterised by a powerful induction effect on the
lines and/or by an increase of local earth potential,
- Operational overvoltages are transient, and are caused by abrupt changes
in the circuit, such as the opening / closing of circuit breakers, load-break
switches, contactors, etc.,
- Overvoltages at normal system frequency can occur in many ways, and
will do so, for example, if a neutral connection is broken on a 3-phase system,
if the load is unbalanced,
4
2.2 Choice of a lightning arrester
It depends on:
Bathrooms and shower rooms are areas of high risk, because of the very low
resistance of the human body when wet or immersed in water.
Precautions to be taken are therefore correspondingly rigorous, and the
regulations are more severe than those for most other locations.
The relevant 1EC standards are 364-7-701, 479 and 669-1.
Classification of zones:
5
Zone 1 is above the bath as shown in vertical cross
6
Zone 0, 1, 2, 3 in proximity of a shower without basin
(1) when the shower head is at the end of a flexible tube, the vertical central
axis of a zone passes through the fixed end of the flexible tube
7
Individual showers with dressing cubicles
8
- Volume 0: interior volume of bathtub or shower
- Volume 1: volume above volume 0
- Volume 2: volume outside volumes 0 and 1 and in a radius of 0.60m
- Volume 3: volume outside volume 2 in a radius of 2.40m maximum
Volumes 0 1 2 3
Conduits / ducts X (b) II (a) II (a) II
Separation
Fittings (switch, sockets,…) X X (b) X (b) (a) VLVS (d)
RCD's 30 mA
Separation
II + RCD 30
Electrical apparatus, devices X 'b) X (b) (c) VLVS (d)
(b) (c) (e)
RCD's 30 mA (c)
X : forbidden
II: accepted in class II
RCDD 30 mA, differential device associated with breaker (or switch)
(a) limited to supply devices in the volume
(b) except if device is in 12VAC or 30VDC
(c) Electrical heater accepted
(d) Very Low Voltage Safety within the range of 50VAC
(e) Also a socket if supplied by an individual transformer, low energy
Electrical devices
Devices of class I can never be in zones 0, 1, 2 (except water heater which is
"supposed" to be protected against water projection by construction;
IP level
Fittings and devices should have the minimum IP of
- volume 0: IPX7
- volume I: IPX4 and if cleaning by water jet, IPX5
- volume 2: IPX3 and if cleaning by water jet, IPX5
- volume 3: IPX1 and if cleaning by water jet, IPX5
Equipotential connections
Paragraph 701-413-1-6 of NFC 15-100:
All conductive elements of the bathroom and all metallic parts of electrical
devices must be interconnected in volumes 0, 1, 2 and 3.
9
4. RECOMMENDATIONS APPLICABLES FOR SPECIAL INSTALLATIONS
AND LOCATIONS
Following table summarises main prescribed requirements (many standards)
10
5. RULES FOR LAYOUT cables, conduits, apparatus,…
11
5.2 Layout of electrical canalisation's in construction voids
(false ceiling, false floor, separation void,…)
Embedded receptacles
Nature of partition outlets
With box Without box
Brickwork, stonework, masonry, concrete,
Accepted Forbidden
plaster…..
Metallic frame (door, widow,…) Accepted Forbidden
Partition wall with internals ignitable / dusty Accepted Forbidden
Partition walls with void space as internals or
Accepted Forbidden
without any suspicious material
12
5.4 Conditions of recess in non supporting partition walls
13
Socket-outlet 32A
Maximum 40
Waterproof ends
Connections within a
connection box
14
5.6 Channelling in partition walls of at least 100mm thickness
Layout of conduits
- Oblique embedded is
forbidden
- Above doors, windows, the
embedding is forbidden
- Conduits must not have any
junction when inside a wall,
except when changing plan.
- Length of embedding for rigid Horizontal channel on one face
conduits is limited to their
construction length
- Conduits can be embedded 2 channels
only in longitudinal void of the on
partition (hollows or cells)
- Conduits are layed before
the construction of wall Same axis
= forbidden
- By exception, on horizontal
route, conduits can be joined by
fitting specially provided for this
function
In horizontal routing
Channelling can be only on one face of the wall
Channelling can be done only for a length of 0.50m from each side of an
intersection of 2 walls
In vertical routing
Channelling cannot exceed 0.80m under the ceiling and 1.20m above the
finished floor. The length of 0.80m can be extended to 1 / 3 of the height of
the wall if only one channelling is done in the same wall.
In the same wall the horizontal distance between 2 channels must be at least
1.50m. It is forbidden to make on the same axis one embedding above the
floor and one under the ceiling.
Channels can be done only at a minimum distance of 20 cm from the
intersection of 2 walls.
15
5.7 Several circuits in the same conduit
Note:
- inside a 'canalisation' several circuits can
be mixed
- A circuit represents the complete loop
elements: wires, cables, apparatus,
protection,….
- The terminal circuit is the one protected
by the last protecting device
Nevertheless:
A cable, a conduit must host the conductors
of only one circuit if the hereafter 4 (four)
conditions are not met together:
1. All conductors must have the insulation for the highest voltage
2. All circuits should be issued from the same panel / protection panel without
intermediate device (transformer, converter,…)
3. Phases conductors must have same cross-section within the same circuit
and not be different than 2 consecutive section when different circuits
(ex: 1.5 + 2.5 + 4 is OK but not OK for 1.5 + 4 + 6)
4. Each circuit must be separately protected against overcurrent
16
5.8 Cross-section of conductors according to current (sockets)
The table under gives the minimum conductor section authorised within a
domestic installation when the length of cable or wires does not exceed an
average of 10m (between protection panel and socket-outlet).
If the cable has to run a "long" distance, drop voltage calculation should be
included to determine the cross-section of conductors.
A flexible cable can have a length exceeding 10m or have a section "smaller"
than the indication (only one consecutive section drop) as it is to connect
temporary devices.
Values hereunder are for metallic or ceramic lamp sockets. For other
materials lower values should be applied.
Values non valid for sockets included in lighting apparatus.
17
DOMECTIC DISTRIBUTION
GROUNDING
1
1. EARTH PROTECTION CONDUCTORS (PE)
Connection:
2
- In TT distribution, the PE conductor can run on a separate way than the active
conductors
- In TN-C distribution, Neutral and Earth are one unique conductor: PEN
(and become separated when going from TN-C to TN-S)
3
(5) They must the connection of other Protective Earth conductors,
Caution: each part of these electrical dusts must have individual tags
green/yellow colour, dimensions 15 to 100mm length, or have indications
'PE' green/yellow at 15cm from each end of each section.
(6) These parts could be removed only if continuity of PE has been anticipated
at design time, or if specific measures are taken to ensure this same
continuity.
(7) With formal approval of the "water company"
(8) For prefabricated electrical busbars trunkings, the metallic frame can be
connected in parallel with the existing PEN conductor inside the same
duct.
- PEN conductor assuming the neutral function cannot have its cross
section smaller than the one necessary for the neutral.
4
- nominal power of transformer HV/LV (in kVA)
- Time delay of switching off when in short circuit condition (response time
of HV breaker, in seconds*)
- Insulation type (PVC, PR) and nature (Cu, Alu, Steel) or conductor
* If general protection is done by fuses, response time to use is 0.2 s.
5
Individual earth electrode or Towards earth distribution
earth distribution network
Distribution
board
Cooking
device
Washing
Water
machine
heater
AC unit or
heater
bathroom
AC unit or heater
lighting
Metallic
bath
Equipotential loop of bathroom frame
6
2. NEUTRAL CONDUCTOR
7
Earthing system
TT TN-C TN-S IT
Protection By RCD's By breaker According to By breaker or
against indirect or fuse chosen fuses and
contacts protection RCD's at least
one by group of
interconnected
grounds
Circuit to
protect
Definitions:
Earth: conductive mass of the soil for which the electrical potential in each
point / part is considered equal to zero (theoretical reference)
Touch earthing / grounding: conductive parts of an apparatus / device
electrically connected which can be accidentally under voltage and touched by
human
8
(7) Isolating device (disconnecting earth electrodes(s)), allowing earth value
measurement.
Individual PE
derivation
towards different
users / devices
framework
Main
Protective
Earth
conductor
AC / heating
water
gas
9
3.2 Grounding of metallic frames
Metallic frame
Includes electrical Electrical No
Type of premise or location wires in conduits device electrical
Insulation Insulation base device
plastic metallic (support)
Dry and Within 2 metres range of
without conductive element or No Yes No (d) No
conductivity PE (b)
(a) Above 2m from
conductive element or No No No No
PE (b)
Bathroom Yes Forbidden Yes Yes
Other locations (c) no yes yes No
Yes: the metallic frame must be connected to the PE system
No: the metallic frame does not need to be connected to the PE system
(a) such as dining rooms, rest rooms, bedrooms, offices, corridors,….
(b) Referring to earth of permanently settled electrical apparatus
(c) Such as kitchens, drying rooms, cellars,….
(d) In condition that the electrical device is adapted to the metallic frame (with cover)
10
Measurement of earth soil resistance allows approximation of the resistivity as
average value for a given type of soil (such as in the following table
Distribution
board
Connecting
strip
Earth digging loop, done during construction and made either with:
- Copper wire bare of at least 25 mm² cross section
- Flat steel of at least 3 mm thickness and at least 100 mm² cross section
- Steel wire of at least 95 mm² cross section embedded in foundations
concrete.
11
Already built building / housing
Conductor in
trenches
Connecting strip
Earth electrode
Supplies
Water, gas, electricity
Purpose is to use the various (or common) trenches dug for the different
necessary supplies; Ground cable must be at least at 20 cm from any other
pipe / conduit.
Copper
plate (100Ω)
Tube Cable Flat steel Wire mesh
- Rods or tubes - flat steel wire or cable - plate - earth digging loop -
framework in foundations concrete - metallic water pipes (with respect of
conditions).
12
3.7 Minimum cross section of earth conductors
Are considered insulated floors: wooden floors, parquets, fabric carpet, plastic
carpet.
But concrete floors, tiled floors and (of course) metallic floors are not
considered as insulated floors.
(B) grounded or class II device. Sockets must include an earth pin / terminal,
corresponding circuit must include a PE conductor.
* Sockets without earth could be installed but only if they are supplied
individually by an isolation transformer or if they are individually protected by a
highly sensitive RCD's
13
3.9 Execution of earth electrodes
Resistance in Ω R=2ρ/L
Rods (tubes):
- Length ' 2 m
Rods/tube/frame connected in parallel
R=1/nxρ/L n: number of rods
Vertical plates
R = 0.8 ρ / L Thickness
2 mm (Cu)
14
(1) When no particular electrical fault risk exists, the human body can hold a
voltage of 50VAC permanently. Maximum value of earth resistance is
given by the formula:
R = 50 / I ∆n
(3) When several differential (RCD's) are existing, the highest set is to be
retained to determine the earth resistance value
Example: in an housing installation, with 2 RCD's 30 and 300 mA, the earth
resistance value must be ≤ 83 Ω
15
DOMESTIC DISTRIBUTION
DRAWINGS
(TYPICAL)
1
1. TYPICAL LIGHTING WIRING
2
Time delay relay (impulse
latched):
With additional by-pass switch
Fluorescent tubes:
With 'stabilisation' inductance L: inductance
S: starter
C: capacitance
With transformer
Luminescent tubes:
With grounded transformer
3
2. EXAMPLE OF HOUSING DISTRIBUTION
" The economical one" for well equipped house
2.2 Grounding
If already built house: by earth rod electrode copper bar 16mm² of at least 2m
length (if good resistivity of soil), vertically installed, wire in 16² up to the
connecting strip. Or with other type of electrodes, see the previous chapter.
4
2.4 Distribution board
NEUTRAL PHASE
BREAKER 300 mA
BREAKER 30 mA
16A
16A
16A
ISOLATION PROTECTION
1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 4 4 4 4 6 mm² 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 4 4 4 4 6 mm²
* In Total Indonésie, the minimum authorised cross section is 2.5 mm², the 1.5
'normally' used for lighting is then to be 'forgotten' in power distribution.
Reminder: no protection on the neutral, but nevertheless, isolation is required
when opening the corresponding phase circuit (with 2 poles -P+N- fuse carrier
device).
5
The above drawing is a part of the example.
This type of drawing is the most used when executing site works, the
electrician can read the lay-out of the different fittings / devices, see the
running lay-out of the cables / conduits and the number of wires with the
ground wire identified. As he is (supposed to be) a confirmed electrician, he
knows the cross section (and colours) of wires to use, and also the location of
wires / cables (distances, heights to respect)
Corridor Hall
Protection breaker
Counter
Distribution
board
Bedroom 3
Bathroom
16A Fridge
Shaving
Washing
machine
Dish
washer
Kitchen
Cooking
plate
6
2.6 One line distribution diagram
Energy
counter
16A 16A 16A 20A 20A 10A 10A 10A 20A 20A 32A 10A 10A Fuses
carriers
Spare
7
3.1 One line diagram - economical solution
Upstream
Protection inside general MCC panel protection
Cable link
General computer
circuits protection x Amp General utility x Amp General AC or x Amp
1+N or 2P or 3P or services circuits heating circuits
3P+N protection 1+N or protection 1+N or
2P or 3P or 3P+N 2P or 3P or 3P+N
and 300mA and 300mA
8
3.1 One line diagram - practical solution
Upstream
Protection inside general MCC panel protection
General computer
circuits breaker x Amp General utility x Amp General AC or x Amp
1+N or 2P or 3P or services circuits heating circuits
3P+N breaker 1+N or 2P breaker 1+N or 2P
or 3P or 3P+N or 3P or 3P+N
Other features:
……….
9
DOMESTIC DISTRIBUTION
LIGHTING
EMERGENCY LIGHTING
1
1.GENERAL RULES
The centralised source unit is a battery charger. The emergency light(s) can
be any type of devices (respecting at least standards of fire resistance)
Switching on and off is monitored generally by a centralised control system
The marked out light must allow anybody to be able to walk out any premise /
room with the sole help of the same marked out lights indicating any change
of direction and any obstacle in the way out.
The marking out lighting does not apply to premises allowing less than 20
persons and (in same time) having no risk of fire, explosion and having an
outward door at less than 30m from any point.
In corridor, each emergency light must not be spaced more than 15m from
each other. In indoor parking: 26m between a 'couple' of lights (2 emergency
blocks installed on the same spot).
When the lights are supplied by a common centralised autonomous unit, each
device should have a minimum power of 15W in incandescence and 5W in
fluorescence.
When the markings out lights are independent / autonomous blocks, the
minimum luminous flux (of one) must be 60 lumens.
EXIT
2
1.2 Ambient emergency lighting
With supply from a central autonomous source, each light should have a
power of at least 0.5W / m².
- Cables / wires housing (conduits, cable trays) are fire resistant (see § 1.6)
3
- Connection:
GENERAL GENERAL
PROTECTION PROTECTION
Each autonomous block to be connected (for its supply) after the normal
lighting protection and on this same protection, but before the normal switch
device
Fire monitoring as
Remote control complementary device
unit associated
with automatic
test accessory
4
1.5 Different type of Emergency Lighting
Sites / building are ranged / ranked by category. Safety rules (local standards)
give, for each application (category) the type of Emergency Lighting to use
with their different functions: permanent, non-permanent, centralised source,
autonomous blocks, marking out, ambience.
5
1.6 Choice of materials according to category of 'Public Area'
Conduits for
Cables electr. wires
Shock (IP)
Category
Metallic flexible
U 1000 RGPFV
Public Area
U 1000 RVFV
U 500/1000-X
Metallic rigid
U 500 VGPV
Plastic trunks
U 1000 R2V
A 05-VV-U
IP
H07 RNF
rigid/flex
Type of building / site
Plastic
L Theatres / Conferences - meeting (8)
buildings
Main spectators / attendants rooms 20 2/7 Y Y Y Y Y Y Y Y Y Y Y
Stage area (1 20 7 N N Y Y Y Y Y Y Y N N
Projection rooms / Stage set 20 2 N N Y Y Y Y Y Y Y N N
Annexes (dressing - stores …) 20 5 Y Y Y Y Y Y Y Y Y Y Y
M Commercial / Trade centres 20 7 N N Y Y Y Y Y Y Y N N
N Restaurants / Bars / Centralised
20 1 Y Y Y Y Y Y Y Y Y Y Y
kitchens (9)
0 Hotels 20 1 Y Y Y Y Y Y Y Y Y Y Y
P Dancing / Games 20 5 Y Y Y Y Y Y Y Y Y Y Y
R Education - holidays centres 20 1 Y Y Y Y Y Y Y Y Y Y Y
S Libraries (public) /
20 1 Y Y Y Y Y Y Y Y Y Y Y
Documentation centres
T Show centres
Halls and public areas / rooms 20 1 Y Y Y Y Y Y Y Y Y Y Y
Reception goods/storage's/garages 20 7 N N Y Y Y Y Y Y Y N N
U Sanitary centres - Hospitals
Bedrooms 20 1 Y Y Y Y Y Y Y Y Y Y Y
Incineration 20 5/7 (2) (2) Y Y Y Y Y Y Y (2) (2)
Operating theatre / surgical units 20 5 N N (3) (3) (3) (3) (3) N N N N
Sterilisation (centralised) 24 1/5 Y Y Y Y Y Y Y Y Y Y Y
Laboratories / pharmacy 21 1/5 N N Y Y Y Y Y Y Y Y Y
V Religion buildings 20 1 Y Y Y Y Y Y Y Y Y Y Y
W Administration centres / Banks 20 1 Y Y Y Y Y Y Y Y Y Y Y
X Indoor Sports (4)
Play grounds / Public areas 21 5/7 (5) (5) Y Y Y Y Y Y Y (5) (5)
Technical rooms 21 7 N N Y Y Y Y Y Y Y N N
Y Museums 20 1 Y Y Y Y Y Y Y Y Y Y Y
PA Open area theatres / playground 23
7 N N Y Y Y Y Y N N N N
25
CT Big tops / Tents (6) 44 7 N N N N N Y N N Y N N
SG Inflatable structures 44 7 N N N N N Y N N Y N N
PS Indoor parking's (7) 21 5/9 N N Y Y Y Y Y Y Y N N
EF Floating boats or structures - Subject to specific standards in the technical
GA Stations (railways - air -…) areas.
Factories / Plants / Mills / … - Common places such as administrative
Sites with Hazards (petroleum,..) buildings (receiving public) have to follow the
Electrical distribution rooms general rules
Centralised technical rooms
(HVAC rooms,…)
Staircases, corridors,… on "big"
storey housing buildings
Y: Authorised
N; Non authorised
(1) IP 20-7 can be required (increase of shock resistance)
6
(2) Can be accepted if mechanical risk is below IP XX5
(3) Authorised only in non exposed (visible) areas (NFC 15-100 art 522)
(4) Level IP 20-7 is the minimum required for Ball-games playground
(5) Authorised only if no mechanical risk
(6) For lighting fitting IP 24-7 is sufficient
(7) IP 20-9 is the minimum required when installed under 1.50m above the
ground level
(8) Can be authorised if manufacturer justify a sufficient IP level
(9) Subject to specific standards for centralised kitchens
Cables / conduits
- Installation type B: fire resistant (at least one hour) cables mandatory.(with
centralised source)
- Premises with fire risk should not be crossed with unnecessary electrical
circuits. Only cables for supply and control of the room equipment's and
lighting are allowed. Exception if the "unwanted" cables adequately
mechanically protected and have no connection point in the 'crossing"
section.
7
Weekly / Three-monthly
Blocks lights on
Diodes flashes in green
Pilot light stays on
8
3. MATERIAL CHOICE
Centralised source:
Battery charger and/or inverter output
in either AC or Dc 24 / 48 /110/ 220 V
Incandescence lights
Fluorescent
Glass + metal IP66-3 lamp 8W - G23
Can be in DC with adapted tube
9
Autonomous blocks incandescent
with remote control facility for public
areas
Marking out - 60 lumens - 1 hour
autonomy - pilot lamp E10 / 12V / 3W
3 batteries 4AH - 2 emergency lamps
E10 / 3?6V / 3.6W - IP 20-5 and
1P 44-9 - Supply 230V AC
Permanent or non permanent
Portable lamp
Incandescence: 5.5W - 3 hours max.
Fluorescence: 6W - 2 hours maximum
Halogen; 10W - 3 hours maximum
For technical rooms use.
10
3.1 Choice of products in centralised source mode
11
4. APPLICATION EXAMPLE
Advises:
General protection
Secondary
Protection protection
of remote
control unit
Remote
control Room Corridor
Detection presence
voltage (8)
Normal Normal
room corridor
lighting lighting
12
4.2 Example with lighting supplied from a centralised source
Type of premises
Supermarket 1500 m² - 50x30m - height 3.5m above 700 persons possible
Solution:
Type M (§ 2)
B type system on centralised source - permanent type (§ 2)
Solution:
By laying out units on architectural drawing
Unit for Exit : 7
Unit for obstacle 2
Unit in addition for L>15m: 6
Total 15
13
Solution:
In incandescence: power required 0.5 x 1500 = 750W (not chosen for ambient
lighting)
Solution
With a battery charger (DC): Incandescent marking out + DC fluo 18W
P = 450 + 150 = 600W x 1.05 = 630W
Source from catalogue can be 660W - 24V Dc (24V being safety voltage !)
With an inverter (230V AC): Fluorescent marking out (5W lamp) + compact
lamp (25W) for ambience
P (W) = 180 + 175 = 355W but VA power is necessary (see tables
before)
P (VA) = (15 x 42) + (8 x 47) = 1006 VA
Source from catalogue can be inverter v630W (1500 VA) 230V
14
Marking out Emergency Light unit
Ambient Emergency Light unit
15
LIGHTING
GLOSSARY
1
List of terms used in lighting, in alphabetical order (from 'Osram' catalogue)
Absorption
This is property of material to convert the radiation they receive (such as light)
into different forms of energy, mostly heat. A measure of this property is the
degree of absorption α = Φa / Φ0 .It is the ratio of the luminous flux
absorbed (Φa) to the luminous flux received. (Φ0) -
(Reflection, Transmittance)
Adaptation
This is the ability to adjust to changes in luminance by making the pupil larger
or smaller. It means we can see correctly across a wide range of illuminance
values. The time taken to adapt in this way is largely determined by the
luminance's at the start and end of the adaptation process. This adaptation
takes place very quickly from dark to light (brightness adaptation) but much
more slowly (30 minutes or more) from light to dark (darkness adaptation).
Amount of light Q
Unit of measurement: kilolumens per hour [klm / h]. The amount of light is the
luminous flux emitted by a light source overtime. This criterion plays an
important role, for example, in evaluating the light generated by flash bulbs.
Burning position
The burning position defines the position in which lamps may or may not be
operated. A combination of a letter and a number is used in which the letter
indicates the general alignment and the number the half-angle of t he
permitted range.
- h = vertical, base up
- s = vertical, base down
- p = horizontal
2
Characteristics of materials
When light hits material, such as a windowpane, there are three different
phenomena that come into play. Some of the light is reflected, some is
absorbed by the material and the rest is transmitted. The resultant luminous
flux components are known as Φp (reflected luminous flux), Φa (absorbed
luminous flux) and Φt. (transmitted luminous flux). For quantitative analysis
quotients from the three different components and the total amount of incident
light Φ0 are formed. These are known as
- Degree of reflectance p = Φp / Φ0
- Degree of absorption a = Φa / Φ0
- Degree of transmittance t = Φt / Φ0
Where p + a + t = 1 or Φp + Φa + Φt = Φ0
Colour rendering
Depending on the location and the purpose, artificial light should enable
colours to be perceived correctly as though being seen by natural daylight.
Such assessments are based on the colour rendering properties of a light
source, which are expressed in terms of categories of the "general colour
rendering index'" Ra. The colour rendering index is a measure of the
correspondence between the colour of an object under the light source being
measured and its colour under a reference light source.
The colour shifts of eight (or 14) test colours standardised in DIN 61 69 that
occur when they are illuminated by the light source being tested are compared
with the same test colour when illuminated by the reference light source. The
3
smaller the deviation the better the colour rendering properly of the lamp
being tested. A light source with an Ra value of 100 shows all the colours
perfectly, as in the case of the reference light source. The lower the Ra value,
the worse the colour rendering.
Test colour
R1 Old rose R5 Turquoise
R2 Mustard yellow R6 Sky blue
R3 Yellow-green R7 Violet
R4 Light green R8 Test lilac
Additional test colours with saturated colours
R9 Red R12 Blue
R10 Yellow R13 Skin tone
R11 Green R14 Leaf green
Computer workstations
Guidelines for lighting at computer workstations are given in DIN 5035, Part 2
and EU Directive 90/270/EWG, its appendix contains the following minimum
requirements:
Lighting
For further technical information see the DIN 5035-7 and DIN 66234-7
standards.
4
of appropriate 1 -1OV dimmer components depends to a large extent on the
application. The lighting system is controlled by light sensors according to the
amount of available daylight, so full use is made of free natural sunlight.
Energy savings of up to 60% are possible, rising to 70% if motion detectors,
time switches and sensors with automatic disconnection circuits are used.
- 1 Digital switching - The luminaires can be switched via the control line
independently of the power supply cabling.
- 2 Addressing - Control gear can be assigned 64 addresses so that they
can be controlled independently of one another via the same control line.
- 3 Simple control cabling -Switching and dimming circuits are independent
of line routing so that maximum flexibility and comfort can be achieved; ,"the
low-voltage cable can be laid anywhere and is polarity free to reduce
installation errors.
.- 4 Renovation - Since the circuits: are independent of the power supply
cabling existing cables in old buildings can be used; in new buildings a five-
core cable is used for the power supply and the control cabling.
- 5 Lighting scenes - Preset lighting scenes can be programmed in the
control gear for various tasks and moods.
- 6 Flexible room design - The cabling need not be changed if there is a
change in the way the room is divided
- 7 Upgrades - New sensors or interfaces: can be added without changing
the luminaire cabling; the luminaires to be controlled are simply selected and
reprogrammed.
- 8 No distortion - Digital signals offer greater freedom in laying cables.
- 9 Flexible - Any sensor can be configured for controlling any luminaire or
group of luminaires.
- 10 Overlapping groups - Luminaires can be assigned to more than one
sensor group (e.g. motion detection and infra-red)
- 11 Infra-red control zone 1 - Zones can be changed without having to
relay cables.
- 12 Infra-red control zone 2
- 13 PIR (passive infra-red) controlled zone
- 14 Daylight control zone - Control sing a photocell
Dimming
Dimmable lighting systems were developed originally to meet the need for
lighting that was easier on the eye. To an increasing extent, these systems
5
are now also being used for cost-saving reasons. Users can control the
lighting with remote controls and switches, or control circuits with daylight
sensors can be used.
Leading-edge phase dimming is used for low-voltage tungsten-halogen lamps
operated with magnetic transformers.
Trailing-edge phase dimming is used for the lamps which are operated with
electronic transformers.
Compact fluorescent lamps (dimming range 3 to 100%) and fluorescent lamps
(dimming range 1 to 100%) with electronic control gear are dimmed via a 1 to
10V interface.
Cables can either be laid separately (recommended for cable lengths > 100
m) or together, provided the requirements of VDE regulations are met.
DIN 5035
The table below lists the guidelines for illuminances to DIN 5035 Part 2,
Workplaces, Extract (September 1990), Workplaces regulations ASR 7/3 and
DIN 5035 Part 2 defines rated illuminances for workplaces lighting
The prescribed rated illuminances are minimum values.
6
Washrooms, firs-aid 300 1 1
room, medical
treatment rooms
Building installations
Machine rooms 100 3 3
Power supply and 100 3 3
distribution rooms
Telex rooms, post 500 2 1
rooms
Telephone exchange 300 2 1
rooms
Walkways in building
For people 50 3 3 Rated illuminance
For people and 100 3 3 matched to adjoining
vehicle rooms
Stairs, escalators ans 100 3 3 En1 = En of walkways
travellators En2 = En of
neighbouring rooms
Loading ramps 100 3 3
Automatic conveyor 100 3 3
near walkways
Offices and the like
Offices with daylight 300 2A 1 Workplace oriented
oriented workplaces general lighting at
exclusivrly directed least 0.8 En
near windows
Offices 500 2A 1
Open plan offices 750 2A 1 High reflectance
High reflectance ceiling at least 0.7
Open plan offices 1000 2A 1 Walls partitions at
Average reflectance least 0.5
Individual workplace,
lighting permitted
Technical drawing 750 2A 1 Angle of drawing
board 75° from the
horizontal at a height
of 1.2m at the mid
point
Rooms with sealing 300 2A 1
and meeting rooms
Reception rooms 100 2A 1
Rooms frequented by 200 2A 1
the public
Rooms for data 500 2A 1
processing
Wholesales and retails premises
Sales rooms 300 2A 1
POS workplaces 500 2A 3
7
Trade and commerce's (selection)
De-rusting and 200 3 2
painting steel
components
Pre-assembly of 200 3 2
heating and
ventilation systems
Locksmiths and 300 3 2
plumbers
Vehicle workshop 300 3 2
Machine repair 500 3 1
workshop
Opticians and watch 1500 2A -
makers
Jewellery workshops 1000 2A -
Working with 1500 1B -
precious stones
Radio and television 500 2A 1
workshop
Reception halls 200 2A 1
Kitchens 500 2A 2
Dining rooms 200 1B -
Living rooms 300 2A 1
Self-service 300 2B 1
restaurants
Hairdressers 500 1A 1
beauticians 750 1A 1
Laundries and dry cleaners
Washing 300 2A 2
Ironing by machine 300 2A 1
Ironong by hand 300 2A 1
Sorting 300 2A 1
Spot removal, 1000 2A 1
inspection
Hospitals
Wards, general 100 1B -
lighting
Wards, reading lights 200 1B -
Wards, examination 600 1B -
lighting
Wards, babies, 400 1B -
general
Examination rooms, 600 1B -
general
Examinations rooms 1000 1B -
point of examination
Dentists, general 500 1A -
Dentists, ambient 1000 1A -
Intensive care, gen. 100 1B -
8
Intensive care, 400 1B -
general bed area
Intensive care, 1000 1B -
examination, bed
area
Operating theatre 1000 1B -
Operating theatre, 600 1B -
side rooms, general
Operating theatre, 100 1B -
side rooms (wake-up
lighting)
Outdoor facilities of schools and colleges
Covered recreation 50 3 -
area
Covered bicycle 50 3 -
stand
Stairs, escalators 100 3 -
and inclined
walkways
General teaching rooms
Pre-school rooms 300 2 (1) For blackboard and/or
Teaching rooms 300 2 (1) demonstration table:
(1) additional lighting
Teaching rooms with 500 2 (1) (1) At least 0.8 En at
a daylight quotient (2) the desk
D<1% in the worst (2) The illuminance
location and Required for any other
predominantly for use can also be
evening use or achieved by switching
specifically for adult parts of the lighting
education system.
Teaching rooms, 750 2 (1) (3) High reflectance
high reflectance (3) ceiling at least 0.5
Teaching rooms, 1000 2 (1)
average reflectance
Special teaching rooms
Teaching kitchen 500 2 2 If necessary additional
workshops 500 2 2 lighting
Handicraft, sewing 500 2 1
and typing rooms
Drawing painting 500 2 1
Physics, chemistry, 500 2 1
biology
Technical drawing 500 2 1
Teaching resource 200 2A -
rooms
Projection rooms 200 2A -
Meeting rooms 200 2A -
Corridors 100 2A -
9
Stairs 200 2A -
Entrance halls 200 2A -
Canteens 200 2A -
Exhibition rooms 200 2A -
Multipurpose rooms 200 2A -
Assembly halls 200 2A -
Library; media rooms 200 2A -
Reading rooms 200 2A -
Book stores 200 2A -
Auditorium
Auditorium with 500 2 1 Additional lighting
windows when necessary
Auditorium without 750 2 1
windows
Gymnasium and sports halls
Training Compe-- Training Compe- Comments
ting -ting
Gymnastics 200 400 1:2 1:1.5
Acrobatics 200 400 1:2 1:1.5 White ceiling with
Athletics 200 400 1:2 1:1.5 reflectance are
Ball games 200 400 1:2 1:1.5 needed
Hockey 200 400 1:2 1:1.5
Badminton 200 400 1:2 1:1.5
tennis 200 400 1:2 1:1.5
Table tennis 300 600 1:2 1:1.5
Boxing 200 1500 1:2 1:1.5 Additional lighting
only for the ring
Wrestling 200 400 1:2 1:1.5 White ceiling with
fencing 200 400 1:2 1:1.5 reflectance > 70
Cycling 200 400 1:2 1:1.5 are needed
Ice skating 80 400
Ice hockey - 400
Speed skating - 150
Show, jumping - 400
Swimming - 400
Diving - 500
Water polo - 400
bowling - 400
Incandescent lamps consist of glass and metal. They do not contain any
materials that will harm the environment so they can be simply thrown away
with the household refuse. They should not be placed in containers for
recycled glass, however, because the glass used for these lamps is not the
same as the glass used for bottles. Tungsten-halogen lamps contain very
10
small quantities of halogens and halogen- hydrogen compounds, but the
amounts are insignificant (only a few millionths of a gram). Even several
lamps together do not present any risk to people or the environment. The
lamps can therefore be thrown away with household waste.
ECG's do not contain any material that will harm the environment but they do
contain recyclable electronic components so they should be disposed of as
electronic waste.
Emergency lighting
Standby lighting takes over the functions of the normal lighting system if the
power supply to that system fails so that essential work can continue. In most
cases, standby power generators are used and these then supply power to
the normal luminaires. The generators must guarantee al least 10% of the
illuminance recommended for the activity. There are three types of safety
lighting:
! Safety lighting for escape routes; safe evacuation calls for a minimum
illuminance of >1 lux at a height of 0.2 m, with a uniformity ratio of 1:40.
Energy label
11
lamps and lamps without integrated control gear) must be printed with uniform
energy labelling indicating how much power and other resources they use.
Lamps with special properties (luminous flux >6500 lm, power consumption <
4 W, reflector lamps) or designed for specific applications (lamps for
generating non-visible light, battery powered lamps, and lamps for use in
equipment for which generating light is not the main purpose) are not covered
by this Directive.
The light sources are classified in energy efficiency classes A (very efficient)
to G (inefficient).
Exposure H
H=E * t
Eye
The eye is an optical system designed to create images on the retina. Its
various components, such as the comea, the aqueous humour, the iris, the
lens and the vitreous humour, combine to enable the eye to react quickly and
easily to different lighting levels that vary by factor 105. Its sensitivity threshold
is as low as 10-12 Ix (equivalent to the light from a faint star in the night sky).
12
Fluorescent lamps
! No preheating (cold start, used for example with slirriline lamps). This type
of starting reduces the lamp life more than any other type and is therefore not
recommended for systems with frequent on / off switching.
! Electronic control gear (ECG) converts the mains voltage into a high-
frequency oscillation of around 35 to 50 kHz. As a result, the 100 Hz flickering
that may appear as a stroboscopic effect in conjunction with rotating machine
parts, for example, is much less noticeable or virtually invisible.
13
Another advantage of ECG operation are the additional energy savings of
around 25% for the same luminous flux, comprising:
! 10% high luminous efficacy from the fluorescent lamp operating at a higher
frequency
! Much lower losses in the ECG (factor 2 or more) compared with
conventional control gear (CCG)
- Dimming
Dimmable ECG's operate with phase control on the leading edge and have
significantly improved the "dimmability" of fluorescent lamps. They make use
of the properly of a choke whereby its resistance increases as the frequency
increases. As the operating frequency increases, the choke connected in
series with the lamp supplies a lower and lower current via a 1-1OV interface
or a DALI interface, the must however be supplied separately to each ECG
and generated by an external actuator. The dimmable ECG's must also
ensure that in the dimmed state the electrode filaments are constantly heated
so that the electrodes continue to emit even when the lamp current is at a low
level.
If fluorescent lamps are operated with ECG's and conventional glow starters
their life is shortened considerably as the frequency of on / off switching
increases.
The same phenomenon can be observed with cold-start ECG's, which have
the advantage of starting fluorescent lamps instantly. However, the immediate
transition from glow discharge to emission temperature seriously damages the
electrodes, so frequent switching cycles reduce the life of fluorescent lamps.
Warm start control gear behave in a completely different way. In this case, the
electrodes are heated before ignition by an electric current, which virtually
eliminates switching damage to the electrodes. The associated delay in
ignition of around 1 second (varies according to the ECG) is acceptable.
- Thermal behaviour
14
Glare
Halogen cycle
15
Halogen cycle
HMI lamps
HMI lamps are metal halide lamps with an increased load on the bulb wall and
very short electrode gaps to improve luminous efficacy and colour rendering,
at the expense however of lamp life.
These lamps are ideal for applications such as theatre lighting, endoscopy.
and filming and TV recordings under daylight conditions (colour temperature =
60O0K). These lamps range in wattage from 200 W to 18 W
Short-arc halide lamps with extremely short electrode gaps were developed
for optical applications. They are characterised by high luminous efficacy and
extremely high luminance and are therefore used primarily for lighting effects,
as positional light sources and as light sources for endoscopy.
Illuminance E
16
intensity and solid angle Ω = A / r², we obtain the following formula for
illuminance:
The minimum illuminances at workplaces are defined in DIN 5035, Part 2 and
the relevant workplace guidelines. Compliance with these standards and
guidelines, however, is no guarantee for a good lighting system in every case.
Incandescent lamps
17
The main properties of an incandescent lamp, namely its luminous efficacy
and life, are influenced largely by the filament temperature.
The higher the filament temperature the higher the luminous efficacy but the
shorter the lamp life. A reduction in lamp life is a consequence of the rapid
increase in the rate of vaporisation of the tungsten atoms as the temperature
rises. this process not only produces a black coating on the bulb but also
ultimately causes the filament to break.
Blackening of the bulb can be effectively countered by having an inert gas as
heavy as possible (argon, krypton or xenon) and ensuring that this gas is at
high pressure. Inert gas is used to reduce the rate at which the tungsten
vaporises. The principal types of incandescent lamp are general-purpose
lamps, special-purpose lamps, decorative lamps and incandescent reflector
lamps. The luminous efficacy of incandescent lamps in the 25 to 1000 W
range is between (and about) 9 and 19 lm / W for lamps with an average life
of 1000 hours.
18
Interference
Labelling of luminaires
CE mark
Lens systems
Lens systems make use of the laws of refraction and reflection. They affect
the direction in which light travels and create an optical image. Lenses differ
according to their optical effect and geometrical design:
A convex lens reduces the divergence of a light beam. One or both of its
surfaces is spherical so that it is thicker in the middle than at the edges. Light
passing through a convex lens parallel to the optical axis converges at the
focal point F. The distance from the focal point to the lens is called the focal
distance f.
19
A concave lens increases the divergence of a light beam. One or both of its
surfaces is spherical so that it is thinner in the middle than at the edges. Light
passing through a concave lens parallel to the optical axis diverges as if it
came from a focal point in front of the tens F.. The distance between the lens
and this focal point is the focal length f. In this case, it has a negative value
(f < 0) and is also known as the diffusion length. The reciprocal of the focal
length f is called the refractive index D.
1
D =
f
Light is taken to mean the electromagnetic radiation that the human eye can
perceive. This is the radiation between the wavelengths of approximately 380
nm and 780 nm. There are no precise limits for the spectral range of visible
radiation as they depend on the amount of radiated power reaching the retina
and on the sensitivity of the eye of the observer. To perceive light, the human
eye contains two types of light-sensitive receptors:
! The highly sensitive rods that enable us to see in black and white ("night-
time vision"), with maximum sensitivity to light in the green range of the
spectrum at a wavelength of = 507 nm (night-time curve V' 0).
20
Description Wavelength range
Ultraviolet radiation - C (UV-C) 100 - 280 nm
Ultraviolet radiation - B (UV-B) 260 - 315 nm
Ultraviolet radiation - A (UV-A) 315 - 380 nm
Visible light 380 - 780 nm
Infra-red A (IR-A) 780 nm - 1.4 µm
Infra-red B (IR-B) 1.4 - 3 µm
Infra-red C (IR-C) 3µm - 1 mm
21
Light colour
The light colour of a lamp can be defined in terms of its colour temperature.
These are three main categories here:
- warm white < 3000K
- neutral white 3300-5000K
- daylight white > 5000K
Despite having the same light colour, lamps may have very different colour
rendering properties owing to the spectral composition of their light..
Light generation
Basically, there are three ways in which electrical current can be used to
produce light thermal radiation, low-pressure discharge and high-pressure
discharge.
- Thermal radiation
- Gas discharge
A voltage is applied in a glass enclosure filled with inert gases, metal vapours
and rare earth's to produce an arc discharge. The direct radiation from the
gaseous filler substances combines to produce the desired light colour.
Examples: mercury vapour, metal halide and sodium vapour lamps.
22
- Luminescence
Luminaire efficiency
Luminaires
Luminance L:
23
Luminance L
Light source Average Light source Average
luminance luminance
Cd / m² Cd / m²
Xenon short-arc 200 000 - Candle 7 500
lamp 5 000 000 000
Sun 1 600 000 000 Blue sky 5 000
Metal halide lamp 10 000 000 - Specular louvre 100
60 000 000 luminaire
Incandescent 2 000 000 - Preferred values 50 - 500
lamp 26 000 000 for indoor lighting
Compact 20 000 - 70 000 White paper at 100
fluorescent lamp 500 lx
Fluorescent lamp 5 000 - 30 000 White paper at 1
5 lx
Sunlit clouds 10 000
Luminous efficacy
24
Luminous flux
The luminous flux [lm] indicates all the radiated power emitted by a light
source in all directions, evaluated with spectral eye sensitivity
A fluorescent tube, L36M21-840 Plus Eco, for example, emits 3350 Im.
Luminous intensity l
A light source generally emits its luminous flux in different directions and at
different intensities. The intensity of the light emitted in a certain direction is
called the luminous intensity l. The spatial distribution of the luminous intensity
of a light source produces a three-dimensional luminous intensity distribution
graph. A section through this graph produces the luminous intensity
distribution curve for the relevant plane. It is usual to use the polar coordinates
or the Cartesian coordinates and to normalise the values to a luminous flux of
1000 Im for luminaires so the figures can be more easily compared.
Metal halide lamps are high-pressure mercury lamps with added metal iodides
or iodides of the rare earth's (dysprosium (Dy), holmium (Ho) and thulium
(Tm)) and complex compounds of caesium (Cs) and tin halide (Sn).
They decompose in the core of the discharge arc and the metals can be
excited to emit light with an intensity and spectral distribution that depends on
the vapour pressure of the metal halides. The luminous efficacy and the
colour rendering properties of the mercury discharge are significantly
improved and the gaps in the mercury spectrum are closed.
Photometric formulas
25
Luminous intensity l ( cd ) Luminous flux in solid angle
candela
Solid angle
Luminous flux ( lm ) lumen Luminous intensity ( cd ) x solid
angle ( sr )
Illuminance E ( lx ) lux Luminous intensity ( cd )
Protection classes
Protection class 1:
All the exposed metal parts are connected to one another and
to the protective earth conductor
Protection class 2:
The luminaire is insulated in such a way that there is no metal
parts that can carry current. There is no protective earth conductor
Protection class 3:
The luminaire is separated on low voltage of 42V or less
supplied by a safety transformer or a battery.
Reflection
26
This is the properly of material s to return rays of light.
There are different types of reflection, such as mirroring, mixed, fully diffused
and irregularly diffused reflection. Indoor lighting uses diffused reflection
almost exclusively.
The reflective behaviour of a material is expressed as its degree of reflection.
This is the ratio of the luminous flux reflected by the material to the luminous
flux that strikes the material (= f ). The degree of reflection (reflectance) is
specified in most cases for diffused incidence of light (dif) or quasi-parallel
incidence of light. In lighting technology the value mostly used is "dif". In
theory, the maximum value for "dif" is 1 (100%).
This table shows the reflectance's of the commonest colours and materials
Colour p material p
White 0.9 Plaster 0.8
Light yellow 0.7 Tiles white 0.7
Light green, pink 0.4 Maple, birch 0.6
Sky blue 0.4 Light oak 0.4
Light grey 0.4. Concrete 0.3
Light brown 0.3 Dark walnut 0.2
mid-grey 0.2 Dark oak 0.2
Dark red 0.1 Red brick 0.2
black 0.1 Breeze block 0.1
Reflectors
Most divergent reflectors have a white coating. The efficiency and the way in
which light is distributed are primarily determined by the mounting depth of the
lamp and dimensions of the reflector. Their shape has only a small influence.
! Spherical reflectors return the fight to the focal point; they are often used
as additional reflectors for point-source lamps and spotlights
! Elliptical reflectors send the rays of light to a second focal point. These
reflectors enable a large quantity of light to be directed through small
openings, provided small lamps with high luminance's are used. The
disadvantages are high temperatures at the focal point due to the tight
bundling of the light
27
! Parabolic reflectors send the light from a light source out in parallel. The
maximum luminous intensity is determined by the luminance of the light
source and the opening of the reflector.
Parabolic reflectors are used predominantly in spotlights and narrow angle
luminaires.
Refraction
n0 = c0 / c
N = n0 / n a
The speed of propagation and therefore the refractive index depends on the
wavelength of the light (dispersion). Normally, the refractive index increases
as the wavelength decreases. UV light is therefore refracted more than IR
light, for example.
The refractive index for air is 1, for water = 1.33 and for glass = 1.44 ... 2.0.
When light arrives at the boundary between two optical media the direction of
the light changes according to the law of refraction, whereas the reflected light
is returned at the same angle. Law of reflection (angle of incidence = angle of
reflection)
Retina
28
The sensitivity of the receptors is not uniform of the entire range of visible
wavelengths. Perception begins at 38O nm (blue) and ends at 750 rim (red)
with maximum sensitivity at 555 rim (yellow. This is shown in the sensitivity
curve V 0.
Because of the different receptors the sensitivity curve is shifted slightly for
night vision and is known as the ' 0 curve.
Thermal radiation
The thermal radiation of a material which absorbs al the radiation failing on it,
depends exclusively on its temperature. The ideal is the black body radiator. It
has the highest emissivity of all thermal radiators and its spectral coefficient of
emission is 1 ( irrespective of temperature and wave1ength).
However, as there is no absolutely black material in reality a black body
radiator can only be generated in special laboratories. The radiation of the
black body radiator is defined by Planck's radiation law.
29
This shows how an increasing proportion of the radiation falls in the visible
and infra-red spectrums as the temperature increases.
Transmittance
Tungsten-halogen lamps
Types of protection
30
Uniformity of lighting
Uniformly of luminance
Local uniformity can be determined from lurninance values Lmin, Lmax and Lm,
where Lmin is the minimum luminance in the entire assessment field, Lmax is
the maximum luminance in the entire assessment field and Lm is the average
luminance in the entire assessment field.
The following two formulas have become established
Lmin Lmin
G= and
Lmax Lm
The following values are recommended according to DIN 5044 for longitudinal
uniformity glp and lateral uniformity gla:
A, D very good
B, E good
C, F satisfactory
Uniformity of luminance
Emin Emin
g1 = and g2 =
Em Emax
31
LIGHTING
CALCULATION PROJECT
CHOICES OF APPARATUS
1
1. LIGHTING PROJECT STUDY ELEMENTS
Criteria availability:
When starting a lighting project, elements, which are given, should be
Lighting requests:
What the final output should be:
- Satisfactory lighting
- Easy maintenance
- Easy replacement of bulbs / lamps
- Smooth control
- Advantageous energy consumption
- Aesthetics
- Respect of standards
- Investment returns
Choices of elements!
When going on into the project, should be gradually defined:
- Premises definition
- Dimensions, architectural characteristics
- Reflection factor
- Furniture's / lay-out of machines, tools,….
- Nature of ceiling
- Daylight ingress
- Premises activities
- Conditions of service and external influence
- Classification of the premises
- Electrical supply conditions
- Voltage
- Neutral protection type
- Conditions of utilisation
- Nuisance parameters
- Radio interference's
- Stroboscopic effects
- Noise of ballast's
- Heat dissipation
- Lighting level (lux) and material required
- Depreciation factors (lamps and installation)
- Ageing of lamps
2
- Dust on luminaires
- Dust and cleanness of the premises
- Cost involvement
- Watt/hour rate
- Total installed power
- Investment (complete installation)
- Manpower
- Lamp replacement cost
- Maintenance cost
- h: height of luminaires
above the work surface
- m and n distances between
axis of luminaires
- h': height of suspension for
the luminaires
- a and b: dimensions of
Work
room surface
Paints % Materials %
White 75 Plaster 85
Cream 70 Architectural stone 50
Yellow 60 Cement 40
Light green 45 Red brick 20
Grey (25% black) 35 Wood - maple 40
Red 25 Wood - oak 20
Dark green 20 Wood - mahogany 10
3
Index of one premises is also according to its dimensions
3ab
ab K=
K= 2(h + h') (a + b)
h (a + b)
See table in chapter 'DIN 5035' of "lighting glossary" paragraph; the minimum
prescribed illuminance being indicated, according to the type of premises.
Luminance
Cd / m²
Angle α L/H
4
Angle α
L/H
Due to
dust
5
Due to Luminous flux in %
lifetime
% of lifetime
General lighting
insufficient
6
2.8 Names of colours (appellation)
7
"comfort ambience" is in shaded area
Colour temperature in degree Kelvin
Illuminance in Lux
INTENSIVE EXTENSIVE
8
workshops
Fluorescent 40W 65W 80W 110W
Lux level 1.20m .1.50m 1.50m 2.40m
! 200 G G
! 400 F F
! 600 E E
! 800 D D
! 1000 D D C C
! 1200 C C C C
! 1500 C C C C
Offices
Fluorescent 40W 65W 110W
Lux level 1.20m .1.50m 2.40m
! 600 E E
! 800 D D
! 1000 D D C
! 1200 C C C
! 1500 C C C
9
2.15 Class - Efficiency - Protection Index of industrial reflector's
10
2.16 "Utilance" tables
J = 0
K = 0.80
Reflection Ceil. 70 70 70 70 50 50 50 30 30 30
factor wall 70 50 30 10 50 30 10 30 10 00
A 0.89 0.83 0.80 °.77 0.83 0.79 0.77 0.79 0.77 0.75
B 0.82 0.75 0.70 0.67 0.74 0.70 0.66 0.69 0.66 0.65
C 0.75 0.66 0.60 0.56 0.65 0.60 0.56 0.59 0.55 0.54
D 0.70 0.60 0.53 0.48 0.58 0.52 0.48 0.52 0.47 0.45
Class of E 0.65 0.53 0.46 0.49 0.52 0.45 0.40 0.44 0.40 0.37
luminaires F 0.63 0.51 0.43 0.37 0.50 0.43 0.37 0.42 0.37 0.35
G 0.61 0.49 0.41 0.35 0.48 0.40 0.35 0.40 0.34 0.32
H 0.59 0.47 0.38 0.32 0.45 0.38 0.32 0.37 0.32 0.29
I 0.56 0.43 0.34 0.27 0.41 0.33 0.27 0.32 0.27 0.24
J 0.54 0.40 0.31 0.24 0.39 0.30 0.24 0.30 0.23 0.21
Reflection Ceil. 70 70 70 70 50 50 50 30 30 30
factor wall 70 50 30 10 50 30 10 30 10 00
Class of
luminaires
0.14
11
J = 1/3
K = 0.60
Reflection Ceil. 70 70 70 70 50 50 50 30 30 30
factor wall 70 50 30 10 50 30 10 30 10 00
A 0.81 0.76 0.72 0.70 0.75 0.73 0.70 0.72 0.70 0.69
B 0.72 0.65 0.61 0.58 0.65 0.61 0.58 0.61 0.58 0.57
C 0.63 0.55 0.49 0.46 0.54 0.49 0.46 0.49 0.45 0.44
D 0.58 0.48 0.42 0.38 0.48 0.42 0.38 0.42 0.38 0.36
Class of E 0.52 0.42 0.35 0.30 0.41 0.35 0.30 0.35 0.30 0.28
luminaires F 0.48 0.35 0.29 0.24 0.36 0.29 0.24 0.29 0.24 0.22
G 0.50 0.38 0.31 0.26 0.38 0.31 0.28 0.31 0.26 0.24
H 0.46 0.37 0.30 0.25 0.36 0.29 0.25 0.29 0.24 0.23
I 0.43 0.30 0.23 0.17 0.30 0.22 0.17 9.22 0.17 0.15
J 0.42 0.30 0.22 0.16 0.29 0.22 0.16 0.22 0.15 0.14
J = 1/3
K = 0.80
Reflection Ceil. 70 70 70 70 50 50 50 30 30 30
factor wall 70 50 30 10 50 30 10 30 10 00
A 0.87 0.82 0.79 0.77 0.82 0.79 0.77 0.79 0.76 0.75
B 0.80 0.74 0.70 0.66 0.73 0.69 0.66 0.69 0.66 0.65
C 0.73 0.64 0.69 0.55 0.64 0.59 0.55 0.59 0.55 0.54
D 0.67 0.58 0.52 0.47 0.57 0.51 0.47 0.51 0.47 0.45
Class of E 0.62 0.51 0.44 0.40 0.51 0.44 0.40 0.44 0.39 0.37
luminaires F 0.60 0.49 0.42 0.37 0.48 0.42 0.37 0.41 0.37 0.35
G 0.58 0.47 0.40 0.34 0.46 0.39 0.34 0.39 0.34 0.32
H 0.56 0.45 0.37 0.31 0.44 0.37 0.31 0.36 0.31 0.29
I 0.53 0.41 0.32 0.27 0.40 0.32 0.27 0.32 0.27 0.24
J 0.51 0.38 0.29 0.23 0.37 0.29 0.23 0.29 0.23 0.21
K=
Reflection Ceil. 70 70 70 70 50 50 50 30 30 30
factor wall 70 50 30 10 50 30 10 30 10 00
A
B
C
D
Class of E
luminaires F
G
H
I
J 0.14
12
13
14
3. CHOICES OF LIGHTING DEVICES
Range of Luminous
General
Category Type power and efficiency Utilization
characteristics
flux Lifetime
General use: for decorative or
25 to 2000 localized lighting.
Standard Opalescent up to 300 9 to 20 lm / W
Watts 250 to Economical installation but for
lamps Watts clear above according to the
INCANDESCENT 40000lumens limited duration (intermittent
power
LAMPS occupancy)
Lifetime 1000
Mostly used in recess mode
Lamps with 40 to 300 hours
Directed light beam Extraction / fans to include if in
reflectors Watts
ceiling
High luminous Exterior lighting
Industrial efficiency Industrial lighting: stores /
white or Low color rendering shops / warehouses where
white 4500 Unpleasant ambient good color rendering is not
25 to 75 lm / W 50
coloring necessary
lm/W as an
Offices
Color rendering average
White Z or 20 to 120 Workshop where good color
acceptable Lifetime higher
FLUORESCENT white "de Watts rendering is necessary
Pleasant ambient than 4000 hours
TUBES Luxe" 75 to 8000 (care !: low rendering with
coloring (with a reasonable
lumens weak lighting)
frequency of
"Sun" white Exalt the warm colors
switching on and Offices
or slightly Pleasant lighting
off) Food industry
pink effects
High efficiency in color
Daylight Testing shop / laboratory
rendering at high level
"de Luxe" Paint-shop
(1000 lux)
15
Category Type Advantages Inconvenience's Luminaires choices
Standard Direct connection on supply Offices:
Low luminous efficiency
lamps (no intermediate "auxiliary") decorative diffusers and
Costly in use.
INCANDESCENT Low price reflectors
"Warm" colors (red, yellow).
LAMPS Lamps with Low dimensions Workshops:
Heat when strong lighting
reflectors Immediate lighting reflectors in aluminium or
required
metal sheet
Industrial Offices:
white or Ambient coloring displeasing - Diffusers
white 4500 Recessed
White Z or Semi recessed
white "de Suspended
Luxe" Economical use and Requires more space than - Luminous lines
"Sun" white maintenance incandescence for the tube and - Luminous ceilings
FLUORESCENT or slightly High luminous levels for the auxiliaries (ballast's)
TUBES pink Possibility to change or Installation to avoid in workshop Workshops:
choose the adapted with high height - Industrial reflector's
required colour Bad performances when Note dual tube device is
ambient temperature is either recommended to avoid
Daylight
too cold or too warm stroboscopic effect
"de Luxe"
Tube with integrated
reflectors are available
16
Range of Luminous
General
Category Type power and efficiency Utilization
characteristics
flux Lifetime
50 to 2000
DISCHARGE Open areas
Color rendering Watts 30 to 60 lm / W
LAMPS Store yards
acceptable in industrial 2000 to Lifetime: 6000
MERCURY WITH Workshops with heights
BALLASTS installation 125000 hours
Tall halls and warehouses
lumens
160 to 500 Big workshops, warehouses
COMBINED LAMP 20 lm / W
Color rendering not Watts Used to increase efficiency in
INCANDESCENT Lifetime: 6000
constant 3000 to 11000 "old" installation equipped with
AND MERCURY hours
lumens incandescence
40 to 200 Best efficiency
SODIUM LOW Open areas
Yellow (orange) color Watts 80 to 150 lm / W
PRESSURE Plants wit smokes, dusts,
rendering very poor 2500 to 30000 3000 to 5000
LAMPS vapors (mining, smelting,…)
lumens hours
250 to 400
SODIUM HIGH "Golden" color Exterior lighting
Watts
PRESSURE acceptable color 80 to 100 lm / W Road lighting
20000 to
LAMPS rendering Halls (with height)
40000 lumens
17
Category Type Advantages Inconvenience's Luminaires choices
DISCHARGE Workshops:
Good luminous efficiency
LAMPS Industrial reflectors
Small dimensions Ignition delay 5 minutes
MERCURY WITH Open areas:
BALLASTS High lifetime
Weatherproof devices
No auxiliary apparatus Available only in 220 Volts Workshops:
COMBINED LAMP
required Lower efficiency than Industrial reflectors
INCANDESCENT
AND MERCURY Can replace "immediately" fluorescent tube Open areas:
incandescent lamp Ignition delay 5 minutes Weatherproof devices
Workshops and outside:
Impossibility to distinguish
SODIUM LOW Industrial reflectors
Good visibility in smoggy / colors under the
PRESSURE Note: this type of lamp works
foggy / dusty surrounding 'monochromatic' yellow / orange
LAMPS in an horizontal position with
light of the lamp
little deviation.
SODIUM HIGH
PRESSURE High efficiency Limited power range Reflectors or projectors
LAMPS
18
4. TECHNICS AND LIGHTING APPARATUS 4.1 Luminous sources
Characteristics Electrical Luminous Colour Colour Shape Luminous Comments and used
Type / method reference flux rendering Temperatur Aspect efficiency
e And
P Lumens Ra Lifetime
°K
Incandescence 50 to 350 to Good colour 2800 to Many 10 to 20 Soft lighting
2000W 37000 rendering 3000 shapes lm/W The most used in domestic lighting
Clear, 1000 to High energy lighting (halogen)
Frosted 2000 hours Heating (infra-red lamps)
Opalescent
Discharge 50 to 1700 to Average 3300 to Fluorescent 30 to 60 Open areas in plants / factories
Mercury vapour 2000W 125000 Acceptable 4300 coating lm/W Storage yards
in industrial 5000 hours Halls, warehouses, tall workshops
environment
Metal halide 400 to 30000 to Good 4000 to Tubular 75 to 100 Reach spectrum in white lighting
2000W 190000 5000 Ovoid satin lm/W Television shows
4000 to Sport grounds, tennis, parking
6000 hours Industrial plant, road lighting
Combined 160 to 3000 to Poor colour 4000 to Fluorescent 20 lm/W Big warehouses
Mercury and 500W 12500 rendering 4500 coating 6000 hours Increases number of lumens when
incandescence substituting incandescent lamps
Fluorescent 20 to 850 to 8000 Average or 3000 to Tubular 25 to 75 Possibility of choice for colour
tubes 105W acceptable 6000 Miniature lm/W temperature, specially if it is used in
according to tubular >4000 hours offices…
type of Circular
tubes
Sodium 35 to 4600 to Acceptable 2200 Tubular 65 to 185 Industrial plants
400W 40000 if colour Ovoid satin lm/W Motorways, parking
rendering is 8000 hours Working sites
not
important
19
4.2 Main types of tubes
dimensions °K
Type of tube power socket Ra
Dia mm L mm 1 2 3
Fluorescent lamp, 18 26 590 G13 85 2700 3000 4000
chromatic, high efficiency 30 26 894 G13 85 2700
with starter mode 36 26 1200 G13 85 2700 3000 4000
58 26 1500 G13 85 2700 3000 4000
Fluorescent lamp, 8 15 288 G5 85 2700
chromatic, high efficiency 13 15 517 G5 85 2700
with starter, miniature
Fluorescent tube, 20 38 590 G13 85-92 3000 4000 6500
chromatic standard, with 30 38 894 G13 86 3000 4000
starter 40 38 1200 G13 85-92 4000 6500
65 38 1500 G13 85-92 3000 4000 6500
Fluorescent tube, 32 305 85 4000
chromatic standard, with 40 410 85 4000
starter, circular
Fluorescent tube, 20 38 590 G13 85 4000
chromatic standard, 40 38 1200 G13 85 3000 4000
'rapid start' 65 38 1500 G13 85 3000 4000
Chromatic standard, 20 38 590 R 18 S 85 4000
'rapid start' 40 38 1200 R 18 S 85 4000
Chromatic, high 30 38 590 G13 86 4000
efficiency 40 38 1200 G13 86 4000
'rapid start' 65 38 1500 G13 86 4000
20
Luminous flux
Chroma Chroma White Chroma White
Type of tube Power Chroma White Daylight
comfort shining shining shining industrial
W sun 83 sun 32 55
82 84 34 34 33
Fluorescent lamp, 18 1300 1450 1450
chromatic, high efficiency 30 2300
with starter mode 36 3250 3450 3450
58 5350 5400 5400
Fluorescent lamp, 8 450
chromatic, high efficiency 13 1000
with starter, miniature
Fluorescent tube, 20 850 850 800
chromatic standard, with 30 2100 1400
starter 40 2100 2000
65 3250 3300 3300
Fluorescent tube, 32 1400
chromatic standard, with 40 1950
starter, circular
Fluorescent tube, 20 800
chromatic standard, 40 2100 2100
'rapid start' 65 3200 3200
Chromatic standard, 20 720
'rapid start' 40 1800
Chromatic, high 20 720
efficiency 40 2900
'rapid start' 65 4900
21
dimensions °K
Type of tube power socket Ra
Dia mm L mm 1 2 3
Industrial type 14 / 16 26 360 G13 66 4200
Starter mode 18 26 590 G13 66 4200
36 26 1200 G13 66 4200
58 26 1500 G13 66 4200
Industrial type 20 38 590 G13 66 4200
'rapid start' 40 38 1200 G13 66 4200
65 38 1500 G13 66 4200
Industrial type 20 38 590 R 18 S 66 4200
'rapid start' 40 38 1200 R 18 S 66 4200
Industrial type 6 15 212 G5 66 4200
Miniature lamp 8 15 288 G5 66 4200
Starter mode 13 15 517 G5 66 4200
Industrial type 20 38 590 Fa8 66 4200
'rapid start' 40 38 1200 Fa8 66 4200
Industrial type 32 305 66 4200
'rapid start' - circular 40 410 66 4200
22
Luminous flux
Chroma Chroma White Chroma White
Type of tube Power Chroma White Daylight
comfort shining shining shining industrial
W sun 83 sun 32 55
82 84 34 34 33
Industrial type 14 / 16 750
Starter mode 18 1200
36 3100
58 5000
Industrial type 20 1100
'rapid start' 40 2900
65 4900
Industrial type 20 1000
'rapid start' 40 2500
Industrial type 6 300
Miniature lamp 8 450
Starter mode 13 950
Industrial type 20 1000
'rapid start' 40 2525
Industrial type 32 2050
'rapid start' - circular 40 2900
23
5. LIGHTING PROJECT 5.1 example 1, office
Room dimensions
L (a) = 9m l (b) = 6m h = 2.85m.
Room colours
Ceiling, white - walls, light yellow -
floor, clear
Required illuminance
500 Lux (table in glossary section)
Ambience comfort
Kruithof curve 52.10) gives for 500
Lux, a colour temperature from
3000 to 5000 °K
Layout of luminaires
Modern office, in line luminaires is
to be adopted. Height of source: 2
metres
Table 2.13 (repartition of luminaires)
shows for a class H a distance of
1.50m maxi between axis of luminaires, with e = 1.50 x 2 = 3m
Will be installed 3 rows distant of 2m. Number of reflector by row being
N = 900 / 120 = 7 total number 7 x 3 = 21 luminaires
24
Index of premises
axb 6x9
K= = = 1.8
h (a + b) 2(6 + 9)
H-h 2.85 - 2
J= = = 0.29 = 1 / 3
H 2.85
S = room surface in m²
Fluorescent tubes catalogues show that for a luminaire with two 1.20m tubes
a required power of 60W per tube (with 2 tubes by reflector)
25
5.2 Example 2, workshop
Room dimensions
L (a) = 65m l (b) = 28m h=
7.50m.
Room colours
Ceiling, yellow - walls, cement
painted in yellow
Required illuminance
300 Lux (table in glossary section)
Layout of luminaires
According to table 2.13 (repartition
of luminaires), height of place,
class of reflectors
E = 1.20 x 7 = 8.4m.
There will be 4 rows distant each
other of 7m. and 65 / 8.4 8
luminaires by row for a total of
8 x 4 = 32 luminaires
Index of premises
axb 28 x 65
K= = = 2.8
h (a + b) 7(28 + 65)
26
Depreciation factor (d)
Curves in 2.6 give d= 1.3 (average value)
H-h 7.5 - 7
J= = =0
H 7.5
S = room surface in m²
Catalogues for discharge lamps show that the choice should be for a mercury
discharge lamp of 400W.
27
In fluorescence:
Choice of semi direct system
Choice of lamp: fluorescent tubes (40W - 1.20m) or (65W - 1.50m) sun white
Luminous flux of tubes
(40W - 1.20m) = 2100 lm
(65W - 1.50m) = 3200 lm
Number of tubes
In 40W : 50 000 / 2100 = 24
In 65W : 50 000 / 3200 = 15
Chosen: 16 tubes of 65W in 8 luminaires of 2x65W (more economical than 24
tubes in 12 luminaires
Layout: 2 rows of 4 luminaires
Verification that L < 1.5h = 1.5 x 1.7 = 2.65m
Fu 3200 x 16 x 0.46
E= = = 310 Lx
Sd 59 x 1.3
In incandescence
Luminous flux (same) 50 000 lm
Commonly used in classroom is 200W bulb, luminous flux 2950 lm
Number of sources 50 000 / 2950 = 17
Chosen 18 lamps of 200W IN 3 rows of 6 luminaires
Verification that : L < 1.5h = 1.5 x 1.7 = 2.55m
Comparison:
Incandescent apparatus and lamps
are cheaper. (in 'classic' design) at
installation time
Lifetime of a bulb is 1000 hours, and 4000 hours for a tube. Power
consumption is 3 times higher for incandescence (KWH involvement)
28