Operation Manual of BMS System for Stations Page 1 of 18

Operation Manual
of
BUILDING MANAGEMENT
SYSTEM
(BMS)
Operation Manual of BMS System for Stations Page 2 of 18

About Document
Objective of this user manual is giving details of BMS SCADA Package. It covers all user
interfaces developed in Station level SCADA system to operate major equipment to operate
day by day activities in Metro Station.
This document will also guide Station operator to monitor vital parameters in BMS which will
enable to take decisions regarding controlling operations. Major system/Equipment covered
in this document are as follows.

• Fire Alarm Control Panel (FACP) and fire Suppression system


• Air Conditioning and Ventilation system
• Water distribution system
• Fan Control system
• Fire Fighting System
• Lift and Escalator System
• Lighting System
• Power Distribution system
• Ventilation and Exhaust Fan system
Operation Manual of BMS System for Stations Page 3 of 18

1. HOME SCREEN

1.Fire Alarm and Detection – Operator can click on Fire Alarm and Detection for detail view
of system.
2.Lifts and Escalators – Operator can click on Lifts and Escalators for detail view and
emergency on and off.
3.Fire Fighting – Operator can click on Fire Fighting for detail status.
4.Power Supply – Operator can click on Power Supply for detail status.
5. Water distribution and Sump Pump– Operator can click on Drinking Water and Sump
Pump for detail status.
6.Air Conditioning and Ventilation – Operator can click on Air Conditioning and Ventilation
for detail status and control.
7.Lighting – Operator can click on Lighting for detail view of status and control.
8.Fans – Operator can click on Fans for detail status and control.
9.Home – If Operator want to come from any screen to directly home page then he needs to
click on Home Button.
10.Prev - If Operator wants to go in Previous page then he needs to click on Prev Button.
11.Next - If Operator wants to go in Next page then he needs to click on Next Button.
Operation Manual of BMS System for Stations Page 4 of 18

12.Alarm – If any Alarm appears in any system, then respective button will blink in Red Color
as shown in below image. Action to be taken as per SOP or inform Controller depending on
the situation
13. Event – All Event will be shown in Event page. Operator can see the events by clicking it
on Event Button.
14. Login

After Clicking on any section, Operator


login Screen will appear to enter User
name and Password.

15. Logoff
All status can be viewed wihtout Login. However for any control, LOG IN is compulsory.
Operation Manual of BMS System for Stations Page 5 of 18

2. FIRE ALARM AND DETECTION


Purpose of system
The Fire Detection system is designed to detect the fire and at designated locations at station.
The fire detectors, hooters and suppressor are integrated to FACP panel installed at SCR room
for automated operations.
In Fire Alarm Page, where we can select the desired area between
a). CONCOURSE LEVEL
b). PLATFORM LEVEL
c). GROUND LEVEL

ABBREVIATION –
• FDA- Fire Detection and Alarm
• MCP- Manual Call Point
Click here to open
• GRP- Gas Release Panel for Suppression System
Concourse Level
Operator can go to each level by clicking it on level shown in below -

Concourse Level
Room will animate with Red color in case of
Station
fire detected.
Control
Room
Operation Manual of BMS System for Stations Page 6 of 18

Station Room will animate with Green color in case of


no alarm.
Control
Room

Platform Level Screen

Ground Level Screen


Operation Manual of BMS System for Stations Page 7 of 18

Action: -
Flashing with beeping will indicate detection of fire. Station Master can identify the
area from 3 Screens and take necessary action as per SOP.

3. LIFT AND ESCALATORS


The Escalator system is installed at station to move passenger up and down. In event of emergency
condition all the escalator must operate to move the passengers to exit.

ON message will come above escalator


symbol when it is running along with
Green Colour arrow showing direction of
movement.

OFF message will come above escalator


symbol when it is stopped.
Click on Blue Button to open Escalator
Pop-up.
Operation Manual of BMS System for Stations Page 8 of 18

If communication of Escalator with BMS


fails, it will show “COMMUNICATION FAIL”
message.

Pop-up of Escalator will show (Up/Down)


direction. Escalator can be started or
stopped using Start/Stop Button.

Click on ALL ESCALATOR CONTROL to give


command to all escalators simultaneously.

Pop-up will open after clicking on


ALL ESCALATOR CONTROL . Start / Stop
command can be given to all Escalators by
pressing “All Escalators Start

Lift Status :-

Lift Position will be shown Level in Green colour as


shown in image.

If communication of Lift with BMS fails, it will show


“COMMUNICATION FAIL” message.

Action : -
1. Operator can view lift position (Concourse, Ground or Platform.). Operator can
observe travel direction of lift.
Operation Manual of BMS System for Stations Page 9 of 18

2. Operator can check running direction of escalator on screen. Operator can give
command to escalator in direction which is selected by admin. If operator gives
command to Escalator, He need to wait for some seconds. “Please Wait” message
will be displayed.
3. For any faults or any emergency purpose, Operator shall contact Control room.

4. FIRE FIGHTING
After opening FIRE FIGHTING tab, we can view ON/OFF/Trip status for Diesel pump, Electric
main pump and Jockey pump, Water pressure, High level, low level Switch status as well as
water level of fire water tank.

Fire Diesel Pump Colour will change based on status


as follows.
- STOPPED
- RUNNING
- TRIPPED
Runtime since last reset will be displayed.

Duct Colour will change from blue to Red if pressure


drops below 5.8 Kg/Cm2 due to opening of Hydrant
valves.
Operation Manual of BMS System for Stations Page 10 of 18

Duct Colour will be blue in normal operation.


(Pressure above 5.8 Kg / Cm2)

Action: -
1. Operator can be monitor pipeline pressure, Pump status and Water level in Fire tank.
2. Alarms will be generated in case of low pressure in hydrant pipeline or water level.

4. POWER SUPPLY

1. After login click on Power Supply tab at home screen.

POWER SUPPLY SCREEN

DG Status will be shown as


- STOPPED
- RUNNING
Operation Manual of BMS System for Stations Page 11 of 18

UPS Status will be shown as


- STOPPED
- RUNNING

6 WATER DISTRIBUTION AND SUMP PUMP

The Domestic water system is designed to circulate water in station for washing, flush, etc.
To automate the water supply and maintain the water across all tanks the system is
interfaced with BMS.
1. After clicking on DRINKING WATER AND SUMP PUMP tab, Water level status of
water tanks will be available. Running status of Distribution pumps, Sump pumps,
and Borewell pumps also can be viewed.
2. Refer to legend provided at the screen for status as per colour codes.
Operation Manual of BMS System for Stations Page 12 of 18

Pump Colour will change based on status as follows.


- STOPPED
- RUNNING
- FAULT
Runtime since last reset will be displayed.

“L “in Grey indicates Water pump in Local mode and “R “ in Green


L R
indicates Water Pump in Remote mode.
M
“A” in Green box indicates Pump is in BMS mode (From OCC) and
M
A M “M” in Grey colour in manual mode.

Action: -

1. For remote operation, selector switch will be in Remote mode. Indication of Remote mode will
be available on Pump Symbol as “R”. If it is in Local mode, It will show “L”.
2. Operator should observe water level on Screen. Pumps will run in Auto mode.
3. If any water level is low and still pump is not running (abnormal condition) then Operator need
to inform to controller for corrective action.
Operation Manual of BMS System for Stations Page 13 of 18

7. AIR CONDITIONING AND VENTILATION


Process Description
The AC system is installed at different rooms of station to maintain the required set
temperature.

1. For Air Conditioning control, click on blue button provided in each area with air conditioning.
Controls provided are: -

ON/OFF control
MODE control (Cool mode, Dry mode, Heat and Auto mode).
FAN SPEED control
Operation Manual of BMS System for Stations Page 14 of 18

Colour of Area will change as per following.

- AC ON
M
M - AC OFF

- Room Temperature

Click on Blue button as shown in image to open mode selection


popup.

Mode Selection of Air Conditioning can be done from Popup.


• Auto Mode
• Manual Mode

AC Function Mode Can be selected for pop-up.

• Cool Mode
• Dry mode
• Fan mode
• Heat mode
• Auto mode.

Fan speed can be regulated using FAN SPEED


• LOW
• Medium
• High2
• Auto
• High

Required Temperature can be set by Clicking on TEMP SET.


Starting time and Stopping time can be Set on START HR and
STOP HR

Action: -

1. Operator can Make AC On/ Off individually in Manual mode. Fan Speed, Temperature
setpoint and operation mode can be changed from screen.
2. In Auto mode, ACs will operate as per schedule time. Operator intervention is not required in
Auto mode
Operation Manual of BMS System for Stations Page 15 of 18

8 LIGHTING

Operator can view status and control Normal/Emergency lights at


- CONCOURSE LEVEL
- PLATFORM LEVEL.

CONCOURSE LEVEL

For manual Control click on Manual ON tab provided and select MANUAL OVERRIDE and will be able
to ON/OFF lights as per requirement.
Operation Manual of BMS System for Stations Page 16 of 18

Click on “MANUAL ULDB ON” Pushbutton to


open Pop-UP for operating Emergency Light.
M
M
Rectangle with RED M shows that lights are
M
A in Manual mode. Rectangle with GREEN A is
for Auto mode.

This pop-up is for Emergency Lights.


• Selected Mode will be in Green
colour.
• For Manual operation click on
“MANUAL OVERRIDE” to operate
light in manual mode. Press “LIGHT
ON” and “LIGHT OFF” button.
• Starting Hour and Stopping Hour can
be set by clicking on Black textbox.
Keypad will open to enter data
• Three set of timings are available
1. Commercial Hour Timing
2. After Commercial Hour Timing
3. Night Timng

Click on “MANUAL LDB ON” Pushbutton to


open Pop-UP for operating Norma Lights.
M
M Red Rectangle with M shows that lights are in
M Manual mode. Green Rectangle with A shows
A
lights are in .Auto mode

Colour Animation of Lights is as per legends


shown in image.

Action:-

Operator can Switch On/Off Lighting in manual mode as per requirement. However manual mode
will be overridden by auto mode after 3 hours of operation. For any faults or any emergency,
Operator should contact control room.
Operation Manual of BMS System for Stations Page 17 of 18

9 FAN CONTROL
Fans are segregated in two groups for controlling.
• Platform-1
• Platform-2
In Fan Control Page, where we can select the desired area between
a). CONCOURSE LEVEL Click here to open
b). PLATFORM LEVEL Platform Level
PLATEFORM LEVEL

Platform Level Screen

Fan symbol colour will change based on status as follows.


STOPPED -
RUNNING - -

Click on Manual Override tab present below fan to control On/Off


manually.
• Pop-up will open as shown in image for Auto/Manual
operation.
Selected mode button will be having Green colour.
• Click on Manual Override button for manual operation.
Click on FAN ON and FAN OFF Button.
• Set Starting time and Stopping time using in START HR and
STOP HR Input block by clicking on the block.
Operation Manual of BMS System for Stations Page 18 of 18

Action: -
1. Normally fans will run in Auto mode with Set Timings for commercial hours and
season. (Can be modified by Administrator login.)
2. Operator can override Auto mode by selecting manual override and switch “ON”
or OFF. After 3 hours fans will again go in Auto Mode.
3. If FAN is stopped even after Manual On, Controller to be informed.