: 10669975-PIB
AC DRIVE DRILLING SYSTEM

Date: 6/21/ 2012

Subject: Availability of the Resistor Bank Temperature Protection Circuit.

Product: All VFD systems with a resistor bank and chopper.

Assemblies: Chopper cabinets.

Objective: To inform customers of engineering recommendation for use of additional


resistor bank temperature protection circuit into the chopper enable
circuit. This addition enhances resistor bank thermal protection.

Issue: During chopper’s normal operation if for any reason the fan inside resistor
bank stops running, the resistor bank protection circuit will disable the
chopper thereby protecting the resistor bank from thermal damage.

Solution: The resistor bank temperature switch is typically wired into the
respective chopper cabinets. The addition of this temperature switch
status shall be included into the chopper enable circuit. An open contact
of resistor bank 1 Temp O.K relay, resistor bank 2 Temp O.K relay (RL05,
RL08 or RL01, RL06 in some model) are to be wired up to the respective
chopper enable circuit per attached drawing. Exact wiring may differ per
installation. The following diagrams are added for guidance/reference
purpose.

Resistor bank Temperature status is currently also fed into the control
system. The control system is therefore aware of this status and the
reason for the chopper being disabled.

Customers should also refer to previous NOV Product Information Bulletins and
Safety Alerts at http://www.nov.com/drilling for additional information related to this
issue and information regarding safe operation, maintenance, and inspection criteria.
Failure to follow the recommendations and/or guidance in NOV Product
Bulletins may result in death, bodily injury or property damage.
Please contact your local National Oilwell Varco (NOV) Service Center if you have
any questions regarding this alert.
Drawings:

(1) Example of chopper boards before resistor bank temp. ok relay contact is
added:
Drawings:

(1) Example of chopper boards with resistor bank temp. ok relay contact: