Concrete retaining wall

dist to cg Rest M
Vert load on wall - kN/m m kN-m
soil density 19.00 kN/m3
Phi 30.00 deg
0.52 rad
Ka 0.33

retained height (HB-HF) 2.20 m


Depth OF BASE TOP below GL (HF) 0.80 m

wall ht above base (HB) 3.00 m


base width (L) 1.60 m
base height (BT) 0.20 m
Base projection front (L-LB-WTB) 0.60 m
wall thickness BOTTOM (WTB) 0.20 m L-.5(LB-.5(WB-WT))
WALL THIcknessTOP (WTT) 0.20 m

Vert load on wall - kN/m 0.70 -


Weight of wall 14.40 kN/m 0.80 11.52
Weight bas 7.68 kN/m 0.80 6.14
Weight of soil backside 45.60 kN/m 1.20 54.72
Weight of soil front 9.12 kN/m 0.30 2.74
76.80 kN/m 75.12
CG at toe
M due to vert loads restraing 75.12 kN-m/m
CG of Vertical load from toe 0.98 m
half base length 0.80 m
Eccentricty (0.18) m
Moment due to vertical loads abt center (13.68) kN-m/m
Earth pressure at bottom of base 20.27 kN/m2
Hor force on wall 28.50 kN/m2
Hor force on wall +base 32.43 kN/m width
Moment OT 34.59 kN-m/m V 32.43 serv
51.88 48.64 Ult
Moment onwall 28.50 28.50 serv
42.75 42.75 ult
FOS against OT 2.17
moment on base 20.91

base pressure due to vert loads 48.00 kN/m2 length of baSE behind wall
M due to base press line of wall back
base pressure due to net moment 49.00 kN/m2 Moment due to base concrete
base pressure front toe 97.00 kN/m2 M due to soil behind
base pressure back (1.00) kN/m2 2.02
Base pressur inline with back of wall 48.00 kN/m2 Net moment on base -back
Bottom of wall
V 42.75 V
Mu 42.75
As wall 785.00 mm2 LENGTH OF WALL FRONT
BASE PRESSURE TOE
T12 142.68 PRESSURE IN LINE WALL FRONT

T16 257.32 250 MOMENT ON BASE AT FRONT -EARTH PR

T20 400.00 V

T25 624.20 250

Dist 455.00 MM2/M

Dist - T10 171.43

T12 246.15 250 min steel 0.15


DEPTH 200
Ast 300

T12 373.33
T10 260.00
-.5(WB-WT))

vert load 76.80 kN/m


hor F 32.43 kN/m

Friction 0.4222222

Passive resist base 33.35


(0.40)
13.07

49.54667
ehind wall 0.80
ress line of wall back 10.13 distr
base concrete 0.77
hind 18.24
Serv Ult As T12 Say
base -back 8.88 kN-m 13.59 260 430.77 400

V (26.80) kN/m (40.20)

0.60 m
97.00 kN/m2
NE WALL FRONT 60.25 kN/m2

ASE AT FRONT -EARTH PR 21.87 kN-m serv


32.81 kN-m ult
47.18 kN serv
70.76 kN ult

As 592

T12 189.19 175

T16 341.22

% 0.15
200
300

350.00
250.00
Concrete retaining wall
dist to cg Rest M
Vert load on wall - kN/m m kN-m
soil density 19.00 kN/m3
Phi 30.00 deg
0.52 rad
Ka 0.33

retained height (HB-HF) 1.20 m


Depth OF BASE TOP below GL (HF) 0.90 m

wall ht above base (HB) 2.10 m


base width (L) 0.60 m
base height (BT) 0.200 m
Base projection front (L-LB-WTB) 0.20 m
wall thickness BOTTOM (WTB) 0.200 m
WALL THIcknessTOP (WTT) 0.20 m

Vert load on wall - kN/m 0.30 -


Weight of wall 10.08 kN/m 0.40 4.03
Weight bas 2.88 kN/m 0.30 0.86
Weight of soil backside 7.98 kN/m 0.50 3.99
Weight of soil front 3.42 kN/m 0.10 0.34
24.36 kN/m 9.23
CG from toe
M due to vert loads restraing 9.23 kN-m/m
CG of Vertical load from toe 0.38 m
half base length 0.30 m
Eccentricty (0.08) m
Moment due to vertical loads abt center (1.92) kN-m/m
Earth pressure at bottom of base 14.57 kN/m2
Hor force on wall 13.97 kN/m2
Hor force on wall +base 16.75 kN/m width
Moment OT 12.84 kN-m/m V 16.75 serv
19.26 25.13 Ult
Moment onwall 9.78 13.97 serv
14.66 20.95 ult
FOS against OT 0.72
moment on base 10.92

base pressure due to vert loads 40.60 kN/m2 length of wall behind wall
M due to base press line of wall back
base pressure due to net moment 182.05 kN/m2 Moment due to base concrete
base pressure front toe 222.65 kN/m2 41 M due to soil behind
base pressure back (141.45) kN/m2
Base pressur inline with back of wall (20.08) kN/m2 Net moment on base -back

As wall 743.00 mm2 LENGTH OF WALL FRONT


BASE PRESSURE TOE
T12 150.74 PRESSURE IN LINE WALL FRONT

T16 271.87 300 MOMENT ON BASE AT FRONT -EARTH PR

T20 422.61 V

T25 659.49 250

Dist 325.00 MM2/M

Dist - T10 240.00

T12 344.62 250


dead 3.75
fin 1.5

live 6.25
11.5

wall ht 4 m
Th 0.25

weight 22 kN/m

15.521774

vert load 24.36 kN/m


hor F 16.75 kN/m

Friction 0.687671

Passive resist base 37.05


wall behind wall 0.20
base press line of wall back (1.21) distr
ue to base concrete 0.05
oil behind 0.80
Serv Ult As T12 Say
nt on base -back 2.06 kN-m 3.09 260 430.77 400

V (24.13) kN/m (36.20)

F WALL FRONT 0.20 m


222.65 kN/m2
IN LINE WALL FRONT 101.28 kN/m2

ON BASE AT FRONT -EARTH PR 6.07 kN-m serv


9.11 kN-m ult
32.39 kN serv
48.59 kN ult

As 351

T12 319.09 300

T16 575.50
Concrete retaining wall
dist to cg Rest M
Vert load on wall 25.00 kN/m m kN-m
soil density 19.00 kN/m3
Phi 30.00 deg
0.52 rad
Ka 0.33

retained height (HB-HF) 2.70 m


Depth OF BASE TOP below GL (HF) 0.60 m
Dist Ext load from Front of wall 0.30 m
wall ht above base (HB) 3.30 m
base width (L) 2.00 m
base height (BT) 0.25 m
Base projection front (L-LB-WTB) 1.00 m
wall thickness BOTTOM (WTB) 0.25 m
WALL THIcknessTOP (WTT) 0.20 m

Vert load on wall 25.00 kN/m 1.10 27.50


Weight of wall 17.82 kN/m 1.23 21.83
Weight bas 12.00 kN/m 1.00 12.00
Weight of soil backside 48.59 kN/m 1.61 78.36
Weight of soil front 11.40 kN/m 0.50 5.70
Ext vert load 90.00 kN/m 0.70 63.00 (v load spread over 2m length)
204.81 kN/m 208.38
CG from toe
M due to vert loads restraing 208.38 kN-m/m
CG of Vertical load from toe 1.02 m
half base length 1.00 m
Eccentricty (0.02) m
Moment due to vertical loads abt center (3.57) kN-m/m
Earth pressure at bottom of base 22.48 kN/m2
Hor force on wall 34.49 kN/m2
Hor force on wall +base 39.91 kN/m width
Moment OT 47.22 kN-m/m V 39.91 serv
70.84 59.86 Ult
Moment onwall 37.93 34.49 serv
56.90 51.73 ult
FOS against OT about toe 4.41
moment on base 43.65

base pressure due to vert loads 102.41 kN/m2 length of wall behind wall
M due to base press line of wall back
base pressure due to net moment 65.48 kN/m2 Moment due to base concrete
base pressure front toe 167.88 kN/m2 32 M due to soil behind
base pressure back 36.93 kN/m2 175
Base pressur inline with back of wall 86.04 kN/m2 Net moment on base -back

As wall 764.00 mm2 LENGTH OF WALL FRONT


BASE PRESSURE TOE
T12 146.60 PRESSURE IN LINE WALL FRONT

T16 264.40 300 MOMENT ON BASE AT FRONT -EARTH PR

T20 410.99 V

T25 641.36 250

Dist 325.00 MM2/M

Dist - T10 240.00

T12 344.62 250


1.23 0.77

0.39
1.61

vert load 204.81 kN/m

hor F 39.91 kN/m

(v load spread over 2m length)

Friction 0.194851

Passive resist base 26.86


wall behind wall (0.20)
ase press line of wall back 1.39 distr
ue to base concrete 0.24
oil behind (1.14)
Serv Ult As T12 Say
nt on base -back (2.29) kN-m (3.44) 260 430.77 400

V (23.70) kN/m (35.54)

F WALL FRONT 0.25 m 1207.692


167.88 kN/m2
IN LINE WALL FRONT 36.93 kN/m2

ON BASE AT FRONT -EARTH PR 7.97 kN-m serv


11.96 kN-m ult
25.60 kN serv
38.40 kN ult

As 351

T12 319.09 300

T16 575.50

Dist 325.00 MM2/M

Dist - T10 240.00


Concrete retaining wall
dist to cg Rest M
Vert load on wall 25.00 kN/m m kN-m
soil density 19.00 kN/m3
Phi 30.00 deg
0.52 rad
Ka 0.33

retained height (HB-HF) 2.70 m


Depth OF BASE TOP below GL (HF) 0.85 m
Dist Ext load from Front of wall (0.40) m
wall ht above base (HB) 3.55 m
base width (L) 1.20 m
base height (BT) 0.20 m
Base projection front (L-LB-WTB) 0.70 m
wall thickness BOTTOM (WTB) 0.25 m
WALL THIcknessTOP (WTT) 0.20 m

Vert load on wall 25.00 kN/m 0.80 20.00


Weight of wall 19.17 kN/m 0.92 17.73
Weight bas 5.76 kN/m 0.60 3.46
Weight of soil backside 18.55 kN/m 1.06 19.71
Weight of soil front 11.31 kN/m 0.35 3.96
Ext vert load 90.00 kN/m 1.10 99.00 (v load spread over 2m length)
169.78 kN/m 163.85
CG from toe
M due to vert loads restraing 163.85 kN-m/m
CG of Vertical load from toe 0.97 m
half base length 0.60 m
Eccentricty (0.37) m
Moment due to vertical loads abt center (61.98) kN-m/m
Earth pressure at bottom of base 23.75 kN/m2
Hor force on wall 39.91 kN/m2
Hor force on wall +base 44.53 kN/m width
Moment OT 55.66 kN-m/m V 44.53 serv
83.50 66.80 Ult
Moment onwall 47.22 39.91 serv
70.84 59.86 ult
FOS against OT about toe 2.94
moment on base (6.32)

base pressure due to vert loads 141.49 kN/m2 length of wall behind wall
M due to base press line of wall back
base pressure due to net moment (26.33) kN/m2 Moment due to base concrete
base pressure front toe 115.16 kN/m2 32 M due to soil behind
base pressure back 167.81 kN/m2 175
Base pressur inline with back of wall 156.84 kN/m2 Net moment on base -back

As wall 800.00 mm2 LENGTH OF WALL FRONT


BASE PRESSURE TOE
T12 140.00 PRESSURE IN LINE WALL FRONT

T16 252.50 300 MOMENT ON BASE AT FRONT -EARTH PR

T20 392.50 V

T25 612.50 250

Dist 325.00 MM2/M

Dist - T10 240.00

T12 344.62 250


0.92 0.28

0.14
1.06

vert load 169.78 kN/m

hor F 44.53 kN/m

(v load spread over 2m length)

Friction 0.2622822

Passive resist base 35.20


wall behind wall (0.25)
ase press line of wall back 5.02 distr
ue to base concrete 0.26
oil behind (1.41)
Serv Ult As T12 Say
nt on base -back (6.17) kN-m (9.25) 260 430.77 400 TOP

V (51.89) kN/m (77.83)

F WALL FRONT 0.25 m


115.16 kN/m2
IN LINE WALL FRONT 180.98 kN/m2

ON BASE AT FRONT -EARTH PR 2.23 kN-m serv


3.34 kN-m ult
37.02 kN serv
55.53 kN ult

As 351

T12 319.09 300

T16 575.50

Dist 260.00 MM2/M

Dist - T10 300.00


Density 2400 kg/cu.m
Ht wall 5m lifting
width top 0.20
width bot 0.35 dia 20
3300 kg /m area 314.16
wt wall single shear 47,123.89
Base 47.12
Len 2.70 4,712.39
Ht base 0.25
Load per bolt 4773.6
wt 1620
toe 384
Total 5304 kg/m lifting

wt 1.2 section 6364.8 kg dia 25


area 490.87
single shear 73,631.08
73.63
7,363.11

Load per bolt 4773.6


N
kN
kg

kg

N
kN Lifting BM on bolt
kg
BM 0.54 kN-m 0.6
kg
Z reqd 1963.636 mm3 2181.818

dia 25 mm 28

Z 1533.981 mm3 2155.133


Concrete retaining wall
dist to cg
Vert load on wall 20.00 kN/m m
soil density 19.00 kN/m3
Phi 30.00 deg
0.52 rad
Ka 0.33

retained height (HB-HF) 2.40 m


Depth OF BASE TOP below GL (HF) 0.75 m

wall ht above base (HB) 3.15 m


base width (L) 0.40 m
base height (BT) 0.15 m
Base projection front (L-LB-WTB) 0.10 m
wall thickness BOTTOM (WTB) 0.20 m

Vert load on wall 20.00 kN/m 0.20


Weight of wall 15.12 kN/m 0.20
Weight bas 1.44 kN/m 0.20
Weight of soil backside 5.99 kN/m 0.35
Weight of soil front 1.14 kN/m 0.05
43.69 kN/m
Dist CG from toe 0.22 m
Eccenticity 0.02 m
Vertical force on base 43.69 kN/m
Direct presuure under base 109.21 kN/m2
Moment on base 0.73 kN-m/m
Pressure due to BM 27.25 kN/m2
Pressure at toe 136.47 kN/m2
Pressure at back 81.96 kN/m2

Earth pressure at bottom of base 20.90 kN/m2


Earth pressure at bottom of wall 19.95 kN/m2
Hor force on wall +base 34.48 kN/m width
Horizantal Force at top 11.49 kN/m width
Horizantal Force at bottom 22.99 kN/m width

Passive resistance at bottom 23.09


base resistance to sliding

FOS sliding 1.00


Rest M
kN-m

L-.5(LB-.5(WB-WT))

4.00
3.02
0.29
2.09 0.4
0.06
9.46

42.7721765625
BM .1283 Wl
12.70 kN-m/m

h 200
cover 50
As 260

T10 300.00 B/W on both faces