Professional Documents
Culture Documents
Lab 2 Three Phase Induction Motor StartStop 10102023 014258pm
Lab 2 Three Phase Induction Motor StartStop 10102023 014258pm
LAB EXPERIMENT # 2
OBJECTIVES:
To install and operate the three-phase induction motor using thermal overload relay and
control lamp indicators.
EQUIPMENT:
THEORY:
Many kinds of lamp indicator are installed at the system to monitor incoming power, run,
overload, and emergency at a system. Power indicator is installed at real wiring to indicate the
incoming power in the power wiring. The lamp usually uses 250 VAC which is installed at Line
to Neutral. Control lamp indicators (such as run, overload, or emergency) are installed at control
wiring. Control wiring of a system can use high voltage (220 VAC) low voltage (120, 24 or 12
VAC or VDC) depending on the control planner. Electrical circuit fault trainer in our lab is
using high voltage level 220VAC to supply the control wiring.
6
Lab No. 2
run indicator lamp will light. Overload indicator is installed in series with contact NO of thermal
overload to neutral. When over current flow at the circuit, the thermal overload will trip and
change the contacts and overload indicator will light. Emergency lamp indicator is installed in
series with contact NO of emergency stop button. When emergency stop is pressed, the NO
contacts will close and emergency lamp will light. Normally emergency lamp is completed with
buzzer or shrine.
Safety Checklist
➢ Be careful, keep your hands or clothing caught in moving parts such as Motor.
➢ Observe all electrical safety precautions. High voltage is present in this experiment, do not
make any connections when the power is on! Ensure the polarity is correct!
Figure 2.2 Start/Stop of Three Phase Induction Motor Completed by Lamp Indicators
7
Lab No. 2
Table 2.1 Voltage and Resistance Measurement at Normal and Fault Condition of L1/R Lamp Indicator
No Observation Location Point Normal Faulty Unit
Power lamp L1 to N Ohm
1
indicator L1/R L1 to N V
Table 2.2 Voltage and Resistance Measurement at Normal and Fault Condition of L2/Y Lamp Indicator
No Observation Location Point Normal Faulty Unit
Power lamp L2 to N Ohm
1
indicator L2/Y L2 to N V
8
Lab No. 2
22. By using multimeter check voltage of L2/Y power lamp indicator and write the data in the
Table 2.2 column “Faulty”.
23. Switch OFF the ELCB and three phase MCB.
24. By using multimeter check resistance of L2/Y power lamp indicator and write the data in
the Table 2.2 column “Faulty”. Analyze the data to find trouble shoot.
25. Switch to “Normal” position.
26. By using multimeter check the resistance of the L3/B power lamp indicators. Write the
data in the Table 2.3 column “Normal”.
Table 2.3 Voltage and Resistance Measurement at Normal and Fault Condition of L3/B Lamp Indicator
No Observation Location Point Normal Faulty Unit
Power lamp L3 to N Ohm
1
indicator L3/B L3 to N V
Table 2.4 Voltage and Resistance Measurement at Normal and Fault Condition of Run Lamp Indicator
No Observation Location Point Normal Faulty Unit
L to N Ohm
1 Run lamp indicator
L to N V
35. Switch ON the single phase MCB, ELCB and three phase MCB.
36. Press Push button “A” to start the motor.
Does the motor run? Yes / No
Is lamp indicator ON? Yes / No
37. Select the fault simulator switch ______ to “Faulty” condition.
Does the motor run? Yes / No
Is lamp indicator ON? Yes / No
38. By using multimeter check the voltage of run lamp indicator and write the data in
the Table 2.4 column “Faulty”.
39. Switch OFF the single phase MCB.
40. By using multimeter check the resistance of run lamp indicator and write the data in the
Table 2.4 column “Faulty”. Analyze the data to find trouble shoot
41. Switch to “Normal” position.
9
Lab No. 2
42. Set the thermal overload at manual reset and maximal current rating at 1.6A
43. By using multimeter check the resistance of the overload lamp indicator. Read the data
in the Table 2.5 column “Normal”.
Table 2.5 Voltage and Resistance Measurement at Normal and Fault Condition of Overload Lamp Indicator
No Observation Location Point Normal Faulty Unit
Overload lamp L to N Ohm
1
indicator L to N V
47. By using multimeter check the voltage of overload lamp indicator and write the data
in the Table 2.5 column “Normal”.
48. Select the fault simulator switch ______ to “Faulty” condition.
Does the overload lamp indicator light? Yes / No.
54. By using multimeter check the resistance of overload lamp indicator and write the data in
the Table 2.5 column “Faulty”. Analyze the data to find trouble shoot.
55. Press “RESET” button at thermal overload. Select the fault simulator switch to
“normal” position.
56. Switch to “normal” position.
57. By using multimeter check the resistance of the emergency lamp indicator. Note the data
in the Table 2.6 column “Normal”.
Table 2.6 Voltage and Resistance Measurement at Normal and Fault Condition of Emergency Lamp Indicator
No Observation Location Point Normal Faulty Unit
Emergency lamp L to N Ohm
1
indicator L to N V
61. By using multimeter check the voltage of emergency lamp indicator and write the data in
the Table 2.6 column “Normal”.
62. Counter clockwise the emergency switch.
63. Select the fault simulator switch to “Faulty” condition.
64. Press Push button “A” to start the motor.
Does the motor run? Yes / No
CONCLUSION:
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
11