Execution date 30/11/2023 Reason of the job
Tested by Location
Approved by Asset Transformer
Report ID 1 Asset type Two-winding
Report
issue date 30/11/2023 Asset serial number 8130227
Others
Category Power
Status Repair
Tank type Free
breathing
Insulation Mineral oil
medium
Fluid 10000 kg
insulation
weight
Total 430000 kg
weight
Voltage ratings
Insul. level
Winding Voltage L-L Voltage L-N
L-L
Prim 66 kV 38 kV 72.5kV
Sec 6.3 kV 7.2kV
Power ratings
20 MVA ONAN/ONAF
Current ratings at rated power
Winding
75 A 1833 A 20 MVA
OLTC DETC
uk[%] Base power Base voltage Load losses Pk
position position
9.62% 20 MVA 66 kV W 10
Tap Voltage
1 75900 kV
2 74800 kV
3 73700 kV
4 72600 kV
5 71500 kV
6 70400 kV
7 69300 kV
8 68200 kV
9 67100 kV
10 66000 kV
11 64900 kV
12 63800 kV
13 62700 kV
14 61600 kV
15 60500 kV
16 59400 kV
17 58300 kV
18 57200 kV
19 56100 kV
Test set information
Model Serial number Calibration date
Temperature corr.
1.216
factor (K)
PASS
Insulation Resistance Test ( IR ) :
يفضل إجراء عملية تكرير زيت لتحسين قيم العازلية لورق العزل1.2≥ هوR60 /R15 الحد األدنى المقبول لـ
PASS
NO LOAD TEST
نسبة تيار الالحمل إلى التيار االسمي يجب أن تكون أقل من ≥0.5 %
Vac mA HZ nF %
4000 9.983 50 7.543 0.2254
6000 14.26 50 7.54 0.2263
8000 18.975 50 7.54 0.2262
PASS
المحولة المساعدة
Insulation Resistance Test ( IR ) :
DC Winding Resistance
HV: LV: