Annexure to Document Transmittal No.

COMN/33/--- dated --/02/2007

Point wise response to DEWA’s Comments Vide Letter no. P-TR/TN/VC/1262/2007 Dated 11/02/2007

S.No DEWA Comments AMBC’s reply to DEWA Comments

CE/248/COMN/E/12/232 –132KV LINE PROTECTION BLOCK DIAGRAM

Please check and confirm the complete ordering code of Main-1


1. Protection relay MICOM P543 in JAFZA South, where the last Complied. please find enclosed the drawing.
alphabetic “J” is not shown in the ordering code reference in P543
catalogue. Please clarify and attach the reference document.

Please check and confirm the complete ordering code of Main-2


2. Protection relay 7SD610 in JAFZA South, type of communication Complied. please find enclosed the drawing.
card (M2G,M2D of M2H” shall be shown in the drawing.

3. Complete ordering code for NSD570 shall be shown on the Drawing.

4. Sheet No. 40, Under Device VA Burden, the type of Main-2 device Complied. please find enclosed the drawing.
shall be 7SD610, F87.2 & Siemens make instead of P543, F871 &
Areva.

5. Sheet No. 42, Under current transformer calculation CT Complied. please find enclosed the drawing.
characteristics shall be the same as mentioned under particulars.

6. Sheet No. 42, Under Device VA Burden, the type of Main-2 device Complied. please find enclosed the drawing.
shall be 7SD610, F87.2 & Siemens make instead of P543, F871 &
Areva.