Applications:
in battery storage systems
in UPS systems
BA ERY
in e-mobility FUSE
E RY
E EV NTS
U S U
C A CO
BE ND
E CO
S
Operating current
Operating current depends on battery storage specification
Battery operation: voltage of DC link circuit decreases to the final
discharge voltage
Consider maximum current at final discharge voltage
for fuse link selection
10000
1000
tE
operation
In
100 wi acco
sta th IE rda
nd C S nc
ar C 3 e
Time/s
wo disa 2B
10
rk tio
1
. n
short-circuit
0,1
0,01
0,1 IB IK 10 100
Current I/In
Short circuit point (IK) When choosing fuse switch disconnector
Short circuit current depending on battery model and type consider fuse link power dissipation!
Manufacturer datasheets to include short circuit current
according to IEC896 Pd(IB) < Py
Operating point has to be in adequate distance below the curve
Short-circuit point has to be above the range of tolerance of the Power dissipation of fuse link at maximal operating current (IB):
curve Pd(IB)=(IB/In)2 x Pd(In)
IB- maximal operating current
Operating point (tE/IB) Pd(IB)-power dissipation of fuse link at maximal operating current
maximum operating curent IB has to be calculated from battery Pd(In)-power dissipation of fuse link at nominal current
storage true power and final discharge voltage UE: IB = PW/UE Py- maximal permissible fuse link power dissipation mounted in
tE is the back-up time of battery storage system fuse switch disconnector
2
Applications
3
CH 10x38 BATTERY Fuse link 550V d.c.
General characteristics
Rated voltage 550V d.c. (L/R=10ms)
Breaking capacity 30kA d.c.
Standard IEC 60269
Application Battery protection
Note:
CH Battery fuse links are used in combination
with fuse disconnector EFH 10 DC
4
CH 10x38 BATTERY Fuse link 800V d.c.
General characteristics
Rated voltage 800V d.c. (L/R=10ms)
Breaking capacity 30kA d.c.
Standard IEC 60269
Application Battery protection
Note:
CH Battery fuse links are used in combination
with fuse disconnector EFH 10 DC
5
Dimensions for CH 10x38 Battery fuses
59,0-60,8
49,2-51,0
6
CH 14x51 BATTERY Fuse link 800V d.c.
General characteristics
Rated voltage 800V d.c. (L/R=10ms)
Breaking capacity 30kA d.c.
Standard IEC 60269
Application Battery protection
Note:
CH Battery fuse links are used in combination
with fuse disconnector EFH 14 DC
7
Dimensions for CH 14x51 Battery fuses
8
CH fuse holder for DC applications
Technical data
EFH 10 DC EFH 14 DC
Fuse type CH 10x38 DC CH 14x51 DC
IEC UL IEC UL
Versions Without indicator, LED indicator
Number of poles 1p, 2p, 2p+N+S
Rated operational voltage Ue 1000V d.c.
Rated operational current Ie 25A 50A
Rated conditional short-circuit current 30kA 10kA 30kA 10kA
Rated insulation voltage Ui 1000V 1000V
Rated imp. withstand voltage Uimp 8kV 8kV
Required insulation temperature rating 60°C 60°C
Max power dissipation of the fuse-link 3W 5W
Derating factor of 200 1
current In for different 300 0,95
ambient temperatures 400 0,9
500 0,8
600 0,7
700 0,5
Derating factor of 1-4 1
current In for side by 5-6 0,8
side mounting fuse 7-9 0,7
holders (nr. of poles) ≥10 0,6
LED indicator operating range 80V - 1000V d.c.
Utilization category Do not operate under load
Operational performance (cycles 0 0
with current)
Operational performance (cycles 2000 2000
without current)
Inclined Plane Tracking (IPT) 60min / 1kV 60min / 1kV
Humidity 90% / 20°C 90% / 20°C
Operating ambient temperature -5°C ... +40°C -5°C ... +40°C
Store ambient temperature -25°C ... +55°C -25°C ... +55°C
Degree of protection (IEC 60529) IP 20 IP 20
Terminal capacity 1-25mm2 AWG 18-8, 1,5-35mm2 AWG 16-6,
solid&stranded, Cu only solid&stranded, Cu only
Screw PZ M5 PZ M5 PZ M5 PZ M5
Torque 2Nm 2Nm,17,7 lb-in 2,5-3Nm 2Nm,17,7 lb-in
Mounting on EN 60715 rail 35mm rail
Sealing posibility ON and OFF
Standards - fuse links IEC/EN 60269-2, IEC/ IEC/EN 60269-2, IEC/ IEC/EN 60269-2, IEC/EN UL 248-4, IEC/EN
EN 60269-6, UL 284-4 EN 60269-6, UL 284-4 60269-6, UL 284-4 60269-2
Standards - fuse holders IEC 60947-1, IEC UL 4248-1*, UL 4248- IEC 60947-1, IEC UL 4248-1*, UL
60947-3 18*, UL 486E*, 60947-3 4248-18*,
CSA C22.2 No.65* UL 486E*
Test reports Int UL Int UL
Certificates UL Listed UL Listed
*Not for 2p+N+S
9
EFH 10 DC - Fuse holder
EFH 10 DC
Number Ue/Ui Imax. Code No. Indicator Adapter Weight Pack.
of poles [V] [A] [g] [pcs]
002540201 - - 63
002540211 LED - 64
1p 12/108
002540501 - 68
002540511 LED 69
1000V
25 002540203 - - 124
d.c.
002540213 LED - 125
2p 6/54
002540503 - 134
002540513 LED 135
2p+N+S* 002540204 - - 257 3/27
*Only IEC certified
B
1p 17,5
2p 35
2p+N+S 70
Version with adapter
10
EFH 14 DC - Fuse holder
EFH 14 DC
Number Ue/Ui Imax. Code No. Indicator Weight Pack.
of poles [V] [A] [g] [pcs]
002560201 - 102
1p 12/96
002560211 LED 103
1000V
50 002560203 - 206
2p d.c. 6/48
002560213 LED 208
2p+N+S* 002560205 - 452 3/24
*Only IEC certified
B
1p 27
2p 54
2p+N+S 108
11
for efficient gas recombination of up to Nominal Voltage 12V
99% and freedom from electrolyte Number of cell 6
maintenance or water adding. Design Life 10 years
Not restricted for air transport-complies Nominal Capacity 77oF(25oC)
with IATA/ICAO Special Provision A67.
UL-recognized component. 10 hour rate (18.7A, 10.8V) 187Ah
Can be mounted in any orientation. 5 hour rate (35.8A, 10.5V) 179Ah
Long service life, float or cyclic Fully Charged battery 77oF(25oC) 3.5mOhms
applications. Self-Discharge
Low power dissipation and fast characteristic in time range of 5s!
Maintenance-free operation.
Low self discharge.
3% of capacity declined per month at 20oC(average)
104 Operating Temperature Range
6
4 20A
25A 40A
32A 50A
63A
80A
100A
125A
160A
Discharge -20~60oC
Dimensions
2 and Weight Charge -10~60oC
Pre-arcing time (s) tv/s
103
Storage -20~60oC
Length(mm
6
/ inch) 522 / 20.55
4
Max. Discharge Current 77oF(25oC) 1000A(5s)
Width(mm
2 / inch) 238 / 9.37
Height(mm
10 / inch) 2
218 / 8.58 Short Circuit Current 3300A
Total Height(mm / inch) 223 / 8.78
6
4 Charge Methods: Constant Voltage Charge 77oF(25oC)
Approx.
2 Weight(Kg / lbs) 65 / 143.3 Cycle use 14.4-14.7V
101
Maximum charging current 60A
5s 5s 6
4
2
Ik Temperature compensation -30mV/oC
100
Standby use 13.6-13.8V
6
4
Temperature compensation -20mV/oC
2
10-1
6
4
Discharge Constant Current (Amperes at 77oF25oC)
2
End Point
10-2 5min 10min 15min 30min 45min 1h 3h 5h 10h
2 4 6 102 2 4 6 103 2 Volts/Cell
Prospective current (A) Ip/A
Time-current characteristics NH00C and NH00 1.60V 537 423 350 215 156 126 57.0 38.0 19.1
1.65V 489 403 340 207 150 122 55.0 37.0 19.0
Better protection of battery cells on overheating in case1.70V
of short459
circuit385comparable
327 201to 146 118 54.5 36.4 18.9
standard gG characteristic1.75V 439 367 310 195 142 115 52.9 35.8 18.8
4 15oF25
Discharge Constant Power (Watts at 77 s oC)
2 End Point
5min 10min 15min 30min 45min 1h 2h 3h 5h
Volts/Cell
Pre-arcing time (s) tv/s
10 4 1.60V
1.65V
876
856
727
701
607
586
392
380
288
280
227
222
137
135
+ 108
106
72.6
71.6
–
6
1.70V 816 677 569 373 274 218 132 104 70.8
4
1.75V 774 653 561 363 269 214 128 100 69.9
2 1.80V 737 619 538 355 265 212 125 97.0 69.0
tE 103 (Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
6
4
page1 of 2 www.vision-batt.com
2
102
6
4
2
gG 160A/400Va.c.
101 Battery
6 fuse
5s
4 0,6 s
2
+ –
100
6 Battery fuse
4 80V d.c./160A
2
10-1
6
4
6 102 2 4 6 103 2 4 6 104 2
Prospective current (A) Ip/A
IB Ik
12
General characteristics
Rated voltage 80V d.c., L/R=10ms
Breaking capacity 30kA d.c..
Standard IEC 60269
Application Battery protection
104
6 160A
4
2
Pre-arcing time (s) tv/s
103
6
4
102
6
4
101
6
4
100
6
4
10-1
6
4
10-2 2
10 2 4 6 103 2
Prospective current (A) Ip/A
14
Dimensions
C 9,8
G
E
H
B K
A F
A B C D E F G H K
00 C 79 53 47 35 15 21 52 7,5 6
00 79 53 47 35 15 28 56 12 6
1C 135 68 65 40 15 28 61 12 6
1 135 72 65 40 20 46 65 14 6
104 104
6 25A 40A 63A 100A 160A 6
4 20A 32A 50A 80A 125A 4
25A 40A 63A 100A 160A 250A
20A 32A 50A 80A 125A 200A
2 2
Pre-arcing time (s) tv/s
103 103
6 6
4 4
2 2
2
10 102
6 6
4 4
2 2
1
10 101
6 6
4 4
2 2
0
10 100
6 6
4 4
2 2
10-1 10-1
6 6
4 4
2 2
10-2 10-2
2 4 6 102 2 4 6 103 2 2 4 6 102 2 4 6 103 2
Prospective current (A) Ip/A Prospective current (A) Ip/A
Time-current characteristics NH00C and NH00 Time-current characteristics NH1C and NH1
15
NH BATTERY fuse link 440V d.c.
General characteristics
Rated voltage 440V d.c., L/R=10ms
Breaking capacity 30kA d.c.
Standard IEC 60269
Application Battery protection
C 9,8
D
G
E
H
B K
A F
A B C D E F G H K
00 79 53 47 35 15 28 56 12 6
1C 135 68 65 40 15 28 61 12 6
16
I/t characteristics
104
6
4
25A 40A 63A 100A 160A
20A 32A 50A 80A 125A
2
Pre-arcing time (s) tv/s
103
6
4
102
6
4
101
6
4
100
6
4
10-1
6
4
-2
10
6 101 2 4 6 102 2 4 6 103 2
Prospective current (A) Ip/A
Application
17
NH BATTERY fuse link 550V d.c.
General characteristics
Rated voltage 550V d.c. (L/R=10ms)
Breaking capacity 30kA d.c.
Standard IEC 60269
Application Battery protection
18
NH BATTERY fuse link 700V d.c.
General characteristics
Rated voltage 700V d.c. (L/R=10ms)
Breaking capacity 30kA d.c.
Standard IEC 60269
Application Battery protection
19
NH BATTERY fuse link 800V d.c.
General characteristics
Rated voltage 800V d.c. (L/R=10ms)
Breaking capacity 30kA d.c.
Standard IEC 60269
Application Battery protection
20
Dimensions
pic. 1
A B C E G S L N P R T
1 135 24 40 46 52 6 65 73 20,5 13,7 27,5
2 150 30 48 54 61 6 65 73 27,3 16,2 27,5
3 150 37 60 64 74 6 65 73 35,6 17 27,5
pic. 2
G
B
11
11
A 6
C E
A B C D E G
1 72 24 110 140 46 51
2 72 30 110 140 54 59
3 72 37 110 140 64 70
21
I/t characteristics for NH Battery fuses sizes 1, 2, 3
2 250A 400A
125A 224A 350A 500A
4 35A 40A 50A 63A 80A100A 160A200A 315A 425A 630A
10
6
t v /s
2
3
10
6
4
2
2
10
6
4
2
1
10
6
4
2
0
10
6
4
2
-1
10
6
4
2
-2
10
6
4 2 3 4
4 6 10 2 4 6 10 2 4 6 10 2
I p /A
22
pic. 3
A B C D E F G H J
3L 208 130 37 73 73 60 126 11 13
2
Pre-arcing time (s) tv/s
500A
103
6
4
102
6
4
101
6
4
100
6
4
10-1
6
4
10-2
6
4
6 102 2 4 6 103 2 4 6 104 2
Prospective current (A) Ip/A
23
Battery fuse NH1,2,3 550V, 700V, 800V d.c.-current loading derating factor in disconnector
0,98
0,96
0,94
0,92
0,9
0,88
Current (I/In)
0,86
0,82
0,8
0,78
0,76
0,74
0,72
0,7
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600
Time (s)
0,98
0,96
0,94
0,92
0,9
0,88
Current (I/In)
0,86
0,82
0,8
0,78
0,76
0,74
0,72
0,7
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200
Time (s)
0,98
0,96
0,94
0,92
0,9
0,88
Current (I/In)
0,86
0,82
0,8
0,78
0,76
0,74
0,72
0,7
1100 1250 1400 1550 1700 1850 2000 2150 2300 2450 2600 2750 2900 3050 3200 3350 3500 3650 3800 3950 4100 4250 4400 4550 4700 4850 5000 5150 5300 5450 5600 5750 5900 6050 6200 6350 6500 6650 6800 6950 7100 7250 7400 7550
Time (s)
24
Horizontal fuse-switch disconnector type KVL
for DC applications
Technical data (in accordance with IEC/EN 60947-3)
Technical specifications Size 00 Size 1 Size 3
Technical caracteristics
Rated operational voltage Ue V DC250 DC440 DC1000 DC250 DC440 DC1000 DC220 DC440 DC1000
Rated operational current Ie A 160 160 160 250 250 250 630 630 630
Rated insulation voltage Ui V AC1000 AC1000 AC1000
Total power loss (without fuse) Pv W 1P-3W, 3P-9W 1P-5W, 3P-15W 1P-17W, 3P-51W
Utilisation category - - DC22B DC21B DC20B DC22B DC21B DC20B DC22B DC22B DC20B
Fuse links
Size-DIN43620 - - 00C/00 1 3
Max. rated current In A 160 160 160 250 250 250 630 630 630
Max. permissible power loss per fuse Pa W
12 23 48
link
Screw - - M8 M10 M10/M12
Torque Ma Nm 12-15 30-35 30-35
Clip terminal, Clamping cross-section - mm 2
Round conductor: 1,5-70 Round conductor: 2,5-150
Strip conductor: 11 x 21
Cu , Strip conductor: 6 x 9 Cu , Strip conductor: 6 x 16
x 1 Cu
x 0,8 Cu x 0,8 Cu
Tightening torque Ma Nm 2,6 9,5 23
Prism Clamp, Clamping cross-section mm2 (SP KVL00 P1); 10-70 Al/
(SP KVL1 P1); 10-150 Al/Cu (SP KVL3 P1); 120-300 Al/Cu
Cu , 35-95 Al/Cu
Tightening torque Ma Nm (SP KVL00 P1); 2,6 (SP KVL1 P1); 4,5 (SP KVL3 P1); 11
Prism Clamp, Clamping cross-section mm 2
(SP KVL1 P2); 2 x (10-150) (SP KVL3 P2); 2 x (120-
/
Al/Cu 240) Al/Cu
Tightening torque Ma Nm / (SP KVL1 P2); 4,5 (SP KVL3 P2); 11
Frame clamp, Clamping cross-section mm2 1,5-95 Al/Cu , (Al 95: max. 125A) 35-150 Al/Cu 95-300 Al/Cu
Torque Ma Nm 4,5 12 20
Protection
Front cover close - - IP20 IP20 IP20
Front cover open - - IP10 IP10 IP10
Operating condition
Ambient temperature Tu °C -25°C ... +55°C
Operating condition - - continous operation
Mounting - - vertical, horizontal
Altitude - m ≤ 2000
Pollution degree overvoltage category - - 3
25
1-pole horizontal fuse-switch disconnector for baseplate mounting
For size Code No. Type Weight Packaging
[kg] [pcs]
00 001690890 KVL-00 1p M8-M8 0,31 2
1 001690891 KVL-1 1p M10-M10 0,93 1
2-3 001690892 KVL-3 1p M10-M10 1,57 1
* see also table of accessories for KVL
26
e e
KVL-00 1p KVL-00 2p
i i
a a
q
p
l
l
b
b
c
c
f
f
r
r
g
g
s
i i
KVL-00 1p M8-M8
KVL-00 2p M8-M8
a i
p
q
l
b
c
r
g
i
u
s
KVL-1 1p M10-M10
KVL-3 1p M10-M10
27
e
a i
q
l
b
c
r
g
i
u
s
KVL-1 2p M10-M10
KVL-3 2p M10-M10
KVL-00 3p M8-M8
KVL-00 3p BC95-BC95
KVL-00 3p M8-M8 LED
KVL-00 3p BC95-BC95 LED
e
h1
KVL-00 3p M8-M8
h3
KVL-00 3p BC95-BC95
KVL-00 3p M8-M8 LED a h2
KVL-00 3p BC95-BC95 LED i
k k
p
q
l
t1
t2
b
c
r
g
u
s
i
h2
h3
KVL-1 3p M10-M10 (LED) h1
KVL-2 3p M10-M10 (LED)
KVL-3 3p M10-M10 (LED)
28
Accessories for KVL
Type Code No. Description Packaging
29
How to choose the correct Battery fuse -
example
Pw=67,5kW
tE= 20min (back-up time of storage system)
AC DC
DC AC
Battery fuse
700V d.c., 160A
Ik=580A
tE = 20min (1200s)
NH00 gG 160A 690V a.c.….problem DC rating at min. breaking capacity ~ 2xIn ???
30
1. Short circuit point (Ik):
Time-current characteristics
4
2
Pre-arcing time (s) tv/s
104
6
4
103
6
4
102
6
4
2
short circuit
101
point
6
<5s
4
100
6
4
10-1
6
4
6 102 2 4 6 103 2 4 6 104 2
Prospective current (A) Ip/A
Ik
580A
31
2. Operating point (tE/IB):
Time-current characteristics
4
2
Pre-arcing time (s) tv/s
104
6
4
2 operating point
tE 103
1200s 6
4
102
6
4
2
short circuit
101
point
6
<5s
4
100
6
4
10-1
6
4
6 102 2 4 6 103 2 4 6 104 2
Prospective current (A) Ip/A
IB Ik
150A 580A
32
Battery fuse selection-I/t characteristic
Time-current characteristics
4
2
Pre-arcing time (s) tv/s
104
6
4
2 operating point
tE 103
6
4
2
Battery fuse
2 160A
10
6
4
100
6
4
10-1
6
4
6 102 2 4 6 103 2 4 6 104 2
Prospective current (A) Ip/A
IB Ik
33
Time-current characteristics
4
2
Pre-arcing time (s) tv/s
104
6
4
2
tE 103 operating point
6
4
102
6
4
2
Battery fuse gG 160A
1 160A
10
6
<5s
4
short circuit
2 point
100
6
4
10-1
6
4
6 102 2 4 6 103 2 4 6 104 2
Prospective current (A) Ip/A
IB Ik
Required
operating time
<5s
Battery fuse 700V d.c.
160A
MCB 160A
operating time gG fuse 160A operating time
2,5s operating time
~30s
15s
34
Battery array
+ + + +
Battery string 1 F1
+ + + +
Battery string 2 F2
+ + + +
Battery string n Fn
Battery array
+ + + +
Battery string 1
+ + + +
Battery string 2 F
+ + + +
Battery string n
For battery banks with parallel strings, a good practice is to include overcurrent protection for each battery
string. This minimizes the potential of the bank backfeeding a single shorted battery, which can lead to fires and
property damage.
Battery-string fusing is best accomplished with appropriately sized dc-rated fuses secured in bolt-in fuse holders
that are housed in a single enclosure. This arrangement makes it easy to isolate one battery string for testing
or maintenance while allowing the system to continue operation. Individual battery-string fuses can provide
protection against catastrophic failure in the event of major fault in the main disconnect breaker panel or
elsewhere in the battery bank. Series fuses on each battery string also reduce the available shortcircuit current
levels, allowing for the use of lower ampere interrupting current rated circuit breakers for the inverter/ charger
disconnects. Without the fuses, the amount of current that the circuit breaker has to interrupt during a fault
could potentially exceed it's rating.
35
Ratings for Li-ion batteries
The first set of C ratings on a Li-ion tells us how fast the battery can be discharged.
30C/60C
translates to
Burst can last for <5 seconds. To figure out how many amps this rate is, you need to know the capacity of
the battery pack. If the pack says that it has 2,3Ah, take that number before the Ah and multiply with 30
to get the number of amps. In this case, it would be 69A. That is rating of 30C for that pack.
The burst rate would then be 2,3 x 60=138A amps for less than 5 seconds.
36
Examples of maximum discharge current
for Lead-acid and Li-ion batteries:
A few reasons why protection of batteries with simple fuse link is not OK:
Flammable hydrogen gas is always present during battery recharging.
Hydrogen gas is potentially explosive if allowed to accumulate in a closed
area.
Prevent open flames, sparks, or electrical arcs in the battery charging area
to minimize the danger of explosion.
Breaking capacity of »fork lift fuse link« is less than 1kA at nominal
voltage!
37
Comparison characteristics
Battery fuse Semiconductor protection fuse
2
Pre-arcing time (s) tv/s
103
6
4
102
6
4
2
Battery fuse
101 fast in time range of
s 6
4
seconds!
2
100
6
4
10-1 Semiconductor
6 protection fuse
4
fast in time range of
2
miliseconds!
ms 10 -2
6
4
6 102 2 4 6 103 2 4 6 104 2
Prospective current (A) Ip/A
Battery fuse
DC
breaking
voltage
Semiconductor
protection fuse
2x In 10x In
38
Notes
39
www.etigroup.eu
June 2018