Professional Documents
Culture Documents
Ttree VTA28 1
Ttree VTA28 1
Possible Causes:
1. Fault simulation is enabled.
2. The High AC Voltage Trip parameter is incorrectly set for the application.
3. The High AC Voltage threshold is set too low for the application.
4. Faulty PTs, incorrect PT ratio, PTs, PT connections.
5. Faulty AVR.
6. Faulty PMG.
7. Governor preload offset percentage too high.
8. The Generator Is Faulty.
9. Refer to Generator troubleshooting.
Possible Causes:
1. Fault simulation is enabled.
2. The Low AC Voltage threshold is set too high.
3. Faulty PTs, incorrect PT ratio, PTs, PT connections.
4. Faulty AVR.
5. Faulty PMG.
6. Faulty rotating rectifier assembly.
7. The Generator is Faulty.
8. Refer to Generator troubleshooting.
4. The diodes on the main rectifier assembly can be checked with a multimeter.
The flexible leads connected to each diode should be disconnected at the terminal
end, and the forward and reverse resistance checked. A healthy diode will indicate
a very high resistance (infinity) in the reverse direction, and a low resistance in the
forward direction. A faulty diode will give a full deflection reading in both directions
with the test meter on the 10,000 Ohms scale, or an infinity reading in both
directions. On an electronic digital meter a healthy diode will give a low reading in
one direction, and a high reading in the other. Replace diode(s) if faulty.
7. The Generator is faulty.
a. If the previous steps did not identify a faulty component, replace the Generator unit..
Possible Causes:
1. Fault simulation is enabled.
2. Underfrequency threshold is set too high.
3. There are fuel or air delivery problems.
4. Overload.
5. Fuel system issue(s).
6. Refer to Generator troubleshooting.
Possible Causes:
1. The genset and bus voltages are not properly setup or calibrated.
2. Refer to Generator troubleshooting.
Possible Causes:
1. Incorrectly wired.
2. Faulty Genset Circuit Breaker (CB).
3. The base board is faulty.
4. Refer to Generator troubleshooting.
NOTICE
This fault remains active and cannot be reset until the Alternator Overheat Integral
time has expired (which takes up to five minutes). The Alternator Overheat Integral
time allows the alternator to cool down before allowing a restart.
Possible Causes:
1. Short or overload.
2. Incorrect CT Ratio, CTs, or CT connections.
3. The base board is faulty.
4. Refer to Generator troubleshooting.
Possible Causes:
1. Wiring issue at the First Start Arbitration input.
2. The base board is faulty.