Professional Documents
Culture Documents
At the experimental setup described in this paper, the One major task of the compiler is to partition the model
DRTS reproduces the dyiximic behaviour of a synchro- automatically, to make use of multiple parallel pro-
nous generator (SG) with machine transformer. The cessors. This makes it possible to simulate complex
DRTS is coupled with the analogue real-time simulator power systems, even though the calculation speed of the
(ARTS), where a benchmark model for HVDC control single DSP is limited. In order to get efficient perfor-
studies is simulated (Fig. 61).
'AC and DC Power Transm,ission',29 April-3 May 1996. Conference Publication No. 423'0 IEE, 1996
370
1
the simulation run. Furthermore, the parameters of a
block can be edited on-line, without reloading the
execution code. The on-line access to the simulation
data is made possible by the specialized hardware
structure of the General Purpose Card (GPC) of the
DRTS, see below. The recording of the simulation
Analogue 110 Rack
results at the GPS can be stopped (without stopping the L - - - - i
simulation), so that these data can be stored to the hard
disk of the connected PC. Figure 3: Hardware overview
371
cy 1 I 1
Simulator:
assumed that the magnetizing current is a non-linear Two-Terminal
function of the air gap flux linkage (which is an Synchronous HVDC
auxiliary variable). In order to avoid arithmetic loops, Generator I 1 System
I Y I I I
the individual linear parts of the magnetizing current
are calculated by using the actual values of the main Figure 5: Interface coilfiguration DRTS/ARTS
372
The HVDC benchmark model from the former CIGRE The benchmark system with a high capacitance in the
WG 14.02, Control in HVDC Systems (7), was adopted d.c. circuit is representative of a ca. 100km cable
for testing the dynamic interaction between the system. The benchmark parameters had been chosen
analogue and digital simulator, the latter being such that resonance conditions are created both on the
represented by a synchronous generator with trans- a.c. side (second harmonic parallel resonance) and on
former, sec Figure 6 and Table 1. the d.c. side (fundamental frequency series resonance).
For this purpose, the parameters of the a.c. system equi- For the short-term tests, as presented in the next chap-
valent of the rectifier side were changed in such a way ter, the synchronous generator was operated with
that the total short circuit power resulting from the a s . constant torque. The generator terminal voltage (V,) is
system equivalent and the generator-transformer unit controlled using an IEEE model of a static excitation
based on the generator subtransient reactance was system (10) as shown in Figure 4. For the HVDC
maintained at the benchmark level of 2500 MVA (7), system, digital controls were used, the concept and the
EMF
e'L AC
System
- 745m
345kV, 50Hz
lOO0Mw
230kV, 50Hz
I SCR = 2.5184"
I--- EMF
SCR = 2.5184'1 c
Filters +
ISG- - - - G5L-l Cap. Bank, {I1
,
Digital Real-Time Simulator Analogue Real-Time Simulator
I_ _ _ _ _ _ _ _ _ _ _ I
Figure 6: Extended benchmark system
R = 2.5 R; L = 597 mH; C = 26 pF
Va.rec [p.u.J
-05
15
Va,inv 1p.u.J
U-IIL [p.u.I
1
......................
0 ..................... :.
7
<.........................
K
._.). ....
0 5 ............................................................................................................................
K 1
(................ ................ i...............................
i
r :................................. + ............................... l
1-d rec [p.u.]
1
0.5 .......... + ........... ................................................... + ...............................
I_dinv[pu.J
i
E-FDE-FDO
Is_r....;
4
04-
.............................. i
1
................................. : .................................
. . . . . . . . . . . . . ..............
2 ..............
. . . . .
~ !. .......
.....................
.
I
+
.................................
.......
.
.
.
.
.
4
.
.
.
.
..
.
.
.
..
.
.
.
..
.
.
.
..
.
.
.
..
.
.
.
.
.
_y__I
~
.................................
.........................
I
I-F X-FDO
‘&\
4
2
-0
.......................................................
........................... i..........................
I
........................
j_.
!
...............................
......
+ .............................. .................................. I .................................
I
Omega [ p . ~ . ]
1 0075
?-----4
0 9925
0 965
01 02 03 04 05 06 07 08
l o 1 ; E 7 time Is]
Figure 7: Simulation results for a 5-cycle 3-phase rectifier fault (Legend: see Fig. 8)
parameters being essentially the same as those de- The more difficult case is the fault in the a.c. system of
scribed by Joetten et al (1l). the inverter (Fig. S), since this causes a commutation
failure. After initializing the fault, the rectifier side
5. ]EXPERIMENTALRESULTS busbar voltage fluctuates only slightly, causing a
corresponding fluctuation of the field voltage and
Figwe 7 shows a three-phase solid fault near the recti- current. The generator speed increases faster than in
fier bus, in Figure 8 the fault was applied to the inverter the first case, since in the second case the ax. system
bur;. Due to the saturation of the converter transformers equivalent can temporarily feed active power into the
a voltage and current in the d.c. circuit with fundamen- synchronous generator. The peak d.c. current of the
tal frequency is created. Via the conversion function, a rectifier is limited to 2.0 p.u. by the fast current control.
second harmonic current on the a.c. side is produced. Since no VDCOL is activated at the rectifier side, the
d.c. current is not reduced below 1 p.u. by the control
As expected, the extended benchmark model behaves during the fault.
very similar to the original system without synchronous
generator (1 1). For all cases, system recovery is stable 6. CONCLUSIONS
and smooth, without large a.c. voltage fluctuations.
A new digital real-time simulator (DRTS) has been
During the fault at the rectifier side (Fig. 7), the field presented. The user-friendly graphical interface conse-
current IFDof the generalor has the typical course of a quently supports a hierarchical representation of the
thr1:e-phase short circuit condition. Due to the d.c. model. The simulation model is partitioned automati-
cornponent of the armature current (not shown in the cally, making it possible to calculate complex power
oscillograms), a large 50 Hz component is created in systems in real time. Sophisticated hard- and software
the field current. Since the generator runs with constant allow an on-line visualization and control of the
mechanical torque, the generator speed is increased. simulation process.
The minimal alpha order of the inverter is below 90°,
so the d.c. current is determined by the inverter A flexible high-resolution, high-speed analogue inter-
VCCOL (voltage depe tident current order limit) face connects the DRTl3 to the analogue parity simu-
chalracteristic to ca. 0.5 p.u. About one cycle after lator of FGH, resulting in a high simulation accuracy.
iniliating the fault, the maximum field voltage is This is shown for a co’mbined digital/analogue simu-
reached due to the high gain of the static excitation lation of a point-to-point HVDC transmission system.
system. The generator speed swings with a hunting
frequency of ca. 1.2 Hz.
____
37 4
Va.rrc [p U , ] 15..
4
-05
15
Va.inv [p.u ]
U L 1P.U I
. .A.. . . . . . . . . . . . ..:...................... c ....................
............... 2.. .......................... :.............................. .............................
I_d.rec [p u.]
.................... I ................................................................... i.................................
I_d.inv [p U 1
............ ..L ............................... ;.............................. I.................................
-t
" I
E-FUE-FDO
I-FDfl-FDU
Omega [p u.]
1015 --- i
1
0985 - / '
097 -
Figure 8:
Phase ,,a" voltage at the rectifier commutation bus
Phase ,,a" voltage at the inverter commutation bus
Mid-line d.c. voltage
D.C. current through the d.c. reactor at the recitifier
D.C. current through the d.c. reactor at the inverter
Generator field voltage
Generator field current
Omega Generator speed