21305

Date of test: 19.11.2020


Type Test Report Date of Issue: 2.2.2024

Tests have been carried out for motor no. 3G1F2043709296,


which is identical in electrical design with motor type(s) Type: M3JM / M3JP / M3KP 90LD 4
stated in this report. Product Code: 3GJM / 3GJP / 3GKP 092540-_SK
Protection type: Ex d I Mb / Ex db I Mb
Ex d IIB T4 Gb / Ex db IIB T4 Gb
Ex de IIB T4 Gb / Ex db eb IIB T4 Gb

Rating:
V Hz kW r/min A cos φ Duty
3~Motor 400 Y 50 1.5 1439 3.1 0.78 S1
Ins. Class F 230 D 50 1.5 1439 5.5 0.78 S1
380 Y 50 1.5 1432 3.3 0.80 S1
220 D 50 1.5 1432 5.7 0.80 S1
415 Y 50 1.5 1443 3.1 0.76 S1
460 Y 60 1.5 1750 2.8 0.76 S1
Eff class IE3 50Hz: IE3 - 85.3(100%) - 86.4(75%) - 85.9(50%)
60Hz: IE3 - 86.5(100%)
Winding resistance* Measured at Calculated at Insulation resistance after heat run at 42 °C Overload tests
20 °C 20 °C 40000 MΩ , tested at 1000 V Torque 160 % 15 s
U1 - V1 5.6660 Ω 5.6660 Ω
U1 - W 1 5.6700 Ω 5.6700 Ω
V1 - W 1 5.6650 Ω 5.6650 Ω

Withstand voltage test for winding 2410 V 1s

Performance tests* Torque Line Input Output


[Nm] U[V] f[Hz] I[A] P1 [kW] P2 [kW] n[r/min] cos φ h [%] s [%]
No-load test 400.0 Y 50 1.83 0.10 0.08
Short circuit test 68.4 Y 50 3.10 0.23 0.62

Temp. rise test S1 10.0 400.0 Y 50 3.23 1.75 1.50 1435 0.78 85.7 4.35

Partial load points:


~75% load 7.5 399.9 Y 50 2.70 1.32 1.14 1452 0.71 86.3 3.18
~50% load 5.0 399.9 Y 50 2.26 0.91 0.77 1468 0.58 85.0 2.09
~25% load 2.5 399.9 Y 50 1.95 0.50 0.39 1484 0.37 78.2 1.06
Temperature rise at performance tests* [°C] [K] Method Measurement method
Stator winding : 28 1 1 Resistance
Frame : 18 2 2 Thermocouples
Bearing N-end : 12 2 3 Thermometer

Ambient Temperature : 20 2

Starting current (IS / IN) : 7.62


Locked rotor torque (T L / TN) : 3.89

Current unbalance at full load: 0.74 %

On behalf of manufacturer
Tested by ABB Oy, IEC LV Motors, Strömbergin puistotie 5, 65320 Vaasa, Finland
The results stated in this report relate only to the item tested.
Tommi Pantti
Manufactured and tested acc. to IEC/EN 60034-1:2017 and IEC/EN 60034-2-1:2014 Method 2-1-1B. Test Floor Manager
Test laboratory is accredited acc. to SFS-EN ISO/IEC 17025:2017 by FINAS. Ref. T345.
*) Accredited test method

ABB Oy, IEC LV Motors Telephone +358 10 2211


Telefax
www.abb.com/motors&generators +358 10 22 47372