FAS02-2016/17A
Contents
Page 1
Product Nomenclature
Standard Air Handling Unit
FFD 030 E C L R 6 N 04 B D
R Return air
F Fresh air
L Left type
R Right type
E Product generation
030 Size
Page 2
Air Handling Unit
FAD 030 D H1 L R 4 1 12 B G
FBD
B Front Bottom
T Front Top
F Upper Front
R Upper Rear
R Return air
F Fresh air
L Left type
R Right type
H1 Horizontal type 1
H2 Horizontal type 2
H3 Horizontal type 3
V1 Vertical type
D Product generation
030 Size
Page 3
Method to determine the side of unit
Left side
configuration
Direction of
air flow
Direction of
air flow
Page 4
Features
Special Panel Structure FFD’s and FAD’s panel is made of powder coated steel (outer) and
Design galvanized steel (inner) with high pressure PU foam sandwiched in
between, thus producing a rigid and robust panel (25mm) for FFD &
FAD model & panel (50mm) for FBD model is available upon request.
Structure of FFD and FAD is reinforced with specially designed hidden
aluminum alloy frame that are being fastened to the panels with bolts
and nuts. As a result, the structure is strong and lightweight, at the
same time possesses superior thermal insulation and anti-rust
property.
Low Air Leakage Patented “Labyrinth” panel design featuring integrated frame and panel
structure, proprietary aluminum profile fastened with bolts and nuts
and ingeniously designed insulation method, reduces the connecting
edges which produces a leading edge low air leakage panel structure.
No Cold Bridge High pressure PU foam sandwiched between panels and specially
designed insulation method is isolating all metal surfaces inside the air
handling unit from outside air which eliminate the possibility of cold
bridge. Thus, no condensation will happen and at the same time
minimize loss of energy.
Wide Product Range FFD’s and FAD’s design is adopting modular concept in both the
length and width, making it flexible and robust to suite different site
conditions. FFD is offering product range with air flow ranging from
1000–15,000 m3/h and FAD is offering product range from
3,000-50,000 m3/h with 3 different ESP to choose from, making it
versatile and able to fulfill various application requirements.
Computer Aided Coil All cooling is designed using professional computer selection software
Design which is carefully formulated, designed and being fine tuned through
laboratory testing and real life application.
Low Noise Rigidly bolted panels, dynamically and statically balanced fan assembly
with spring isolator and closely integrated sections reduces the
vibrations and noise generated, thus, providing a quiet operation air
handling unit.
ARI Performance All cooling is designed using professional computer selection software
Certified™ Coil * which is ARI Performance Certified™. The software is carefully
formulated, designed and being fine tuned through laboratory testing
and real life application to meet the highest standard of the HVAC
industry.
ARI Performance Certified™ is the trusted mark of performance
assurance for heating, ventilation, air conditioning and commercial
refrigeration equipment. Products earning the mark undergo rigorous,
independent annual evaluation to ensure that they perform according
to the manufacturers’ published claims. Certifying HVACR equipment
and component performance allows consumers to compare products
based on independently verified performance ratings. To find ARI
Performance Certified™ products, go to www.aridirectory.org.
Page 5
Unit Type Configuration (FAD)
Vertical Type, V1
Pre-filter [Nylon filter (slide rail)] + Cooling coil + Fan section
Horizontal Type 1, H1
Pre-filter [Nylon filter (slide rail)] + Cooling coil + Fan section
Horizontal Type 2, H2
Mixing box + Pre-filter [G3/G4 (slide rail)] + Cooling coil + Fan section
Horizontal Type 3, H3
Mixing box + Pre-filter [G3/G4 (slide rail)] + Medium efficiency bag
filter (F5/F6) + Cooling coil + Fan Section
Page 6
Engineering Specifications
General Data (3 Speeds Cooling Coil - 4 Rows) Return Air
Model FFD 010CC 015CC 020CC 025CC 030CC 040CC 050CC 060CC 070CC
CMH 1000 1500 2000 2500 3000 4000 5000 6000 7000
High
CFM 590 880 1180 1470 1770 2350 2940 3530 4120
CMH 830 1240 1650 2070 2450 3840 4790 5760 6720
Air Flow Medium
CFM 490 730 970 1220 1470 2260 2820 3390 3950
CMH 560 770 1120 1410 1700 2260 2820 3380 3940
Low
CFM 330 450 660 830 1000 1330 1660 1990 2320
High kW 5.10 8.30 11.50 14.40 17.50 23.40 28.30 34.50 40.30
Total Cooling Capacity Medium kW 4.20 6.80 9.50 12.00 14.40 19.40 23.20 28.60 33.40
Low kW 3.50 5.60 7.80 9.80 11.90 15.90 19.20 23.50 27.40
High l/s 0.24 0.40 0.55 0.69 0.83 1.13 1.37 1.64 1.92
Water Flow Rate Medium l/s 0.20 0.32 0.45 0.57 0.68 0.92 1.11 1.36 1.59
Low l/s 0.17 0.26 0.37 0.47 0.57 0.76 0.92 1.12 1.30
High kPa 3.00 9.00 11.00 18.00 31.00 60.00 40.00 43.80 58.00
Water Pressure Drop Medium kPa 2.30 6.90 8.50 13.90 23.90 46.20 30.80 33.70 75.30
Low kPa 1.80 5.30 6.50 10.60 18.30 35.40 23.60 25.80 34.20
High Pa 140 140 140 190 190 160 160 220 260
External Static Pressure Medium Pa 110 110 110 150 150 130 130 175 210
Length mm 950 950 950 950 1000 1000 1000 1000 1000
Dimension Width mm 787 912 992 1058 1207 1405 1657 1734 1859
Height mm 545 545 620 620 620 620 630 690 690
Power Input kW 0.35 0.45 0.50 0.70 0.70 1.00 1.40 2.30 2.70
Current Input A 1.40 1.70 3.20 3.50 3.50 5.00 7.00 9.00 12.00
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 27.0°C DB / 19.5°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
Page 7
General Data (3 Speeds Cooling Coil - 6 Rows) Return Air
Model FFD 010CC 015CC 020CC 025CC 030CC 040CC 050CC 060CC 070CC
CMH 1000 1500 2000 2500 3000 4000 5000 6000 7000
High
CFM 590 880 1180 1470 1770 2350 2940 3530 4120
CMH 830 1240 1650 2070 2450 3840 4790 5760 6720
Air Flow Medium
CFM 490 730 970 1220 1470 2260 2820 3390 3950
CMH 560 770 1120 1410 1700 2260 2820 3380 3940
Low
CFM 330 450 660 830 1000 1330 1660 1990 2320
High kW 7.20 11.00 14.90 18.20 22.00 30.10 35.20 43.70 49.40
Total Cooling Capacity Medium kW 6.00 9.10 12.20 15.10 18.30 25.00 29.20 36.30 40.50
Low kW 4.90 7.50 10.10 12.40 15.00 20.50 23.90 29.70 33.60
High l/s 0.34 0.52 0.71 0.87 1.05 1.43 1.68 2.08 2.35
Water Flow Rate Medium l/s 0.28 0.43 0.58 0.72 0.87 1.19 1.39 1.73 1.93
Low l/s 0.23 0.36 0.48 0.59 0.71 0.97 1.14 1.42 1.60
High kPa 8.80 19.50 26.00 38.00 24.00 49.50 32.00 44.00 59.00
Water Pressure Drop Medium kPa 6.80 15.00 20.00 29.30 18.50 38.10 24.60 33.90 45.40
Low kPa 5.20 11.50 15.30 22.40 14.20 29.20 18.90 26.00 34.80
Length mm 950 950 950 950 1000 1000 1000 1000 1000
Dimension Width mm 787 912 992 1058 1207 1405 1657 1734 1859
Height mm 545 545 620 620 620 620 630 690 690
Chilled Water Pipe Diameter mm(in) DN32 (1 1/4") DN40 (1 1/2") DN50 (2")
Power Input kW 0.35 0.45 0.50 0.70 0.70 1.00 1.40 2.30 2.70
Current Input A 1.40 1.70 3.20 3.50 3.50 5.00 7.00 9.00 12.00
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 27.0°C DB / 19.5°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
Page 8
General Data (3 Speeds Cooling Coil - 4 Rows) Fresh Air
Model FFD 010CC 015CC 020CC 025CC 030CC 040CC 050CC 060CC 070CC
CMH 1000 1500 2000 2500 3000 4000 5000 6000 7000
High
CFM 590 880 1180 1470 1770 2350 2940 3530 4120
CMH 830 1240 1650 2070 2450 3840 4790 5760 6720
Air Flow Medium
CFM 490 730 970 1220 1470 2260 2820 3390 3950
CMH 560 770 1120 1410 1700 2260 2820 3380 3940
Low
CFM 330 450 660 830 1000 1330 1660 1990 2320
High kW 13.90 18.70 27.00 30.80 39.90 49.70 64.50 72.70 84.10
Total Cooling Capacity Medium kW 11.40 15.50 22.40 25.60 33.10 41.30 53.50 60.30 69.00
Low kW 9.50 12.70 18.40 20.90 27.10 33.80 43.90 49.40 57.20
High l/s 0.66 0.93 1.29 1.47 1.90 2.37 3.07 3.46 4.00
Water Flow Rate Medium l/s 0.54 0.77 1.07 1.22 1.58 1.96 2.55 2.87 3.28
Low l/s 0.45 0.63 0.87 1.00 1.29 1.61 2.09 2.35 2.72
High kPa 16.00 33.00 43.00 26.00 48.00 32.00 63.00 11.00 15.10
Water Pressure Drop Medium kPa 12.30 25.40 33.10 20.00 37.00 24.60 48.50 8.50 11.60
Low kPa 9.40 19.50 25.40 15.30 28.30 18.90 37.20 6.50 8.90
High Pa 140 140 140 190 190 160 160 220 260
External Static Pressure Medium Pa 110 110 110 150 150 130 130 175 210
Length mm 950 950 950 950 1000 1000 1000 1000 1000
Dimension Width mm 787 912 992 1058 1207 1405 1657 1734 1859
Height mm 545 545 620 620 620 620 630 690 690
Chilled Water Pipe Diameter mm(in) DN32 (1 1/4") DN40 (1 1/2") DN50 (2")
Power Input kW 0.35 0.45 0.50 0.70 0.70 1.00 1.40 2.30 2.70
Current Input A 1.40 1.70 3.20 3.50 3.50 5.00 7.00 9.00 12.00
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 35.0°C DB / 28.0°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
Page 9
General Data (3 Speeds Cooling Coil - 6 Rows) Fresh Air
Model FFD 010CC 015CC 020CC 025CC 030CC 040CC 050CC 060CC 070CC
CMH 1000 1500 2000 2500 3000 4000 5000 6000 7000
High
CFM 590 880 1180 1470 1770 2350 2940 3530 4120
CMH 830 1240 1650 2070 2450 3840 4790 5760 6720
Air Flow Medium
CFM 490 730 970 1220 1470 2260 2820 3390 3950
CMH 560 770 1120 1410 1700 2260 2820 3380 3940
Low
CFM 330 450 660 830 1000 1330 1660 1990 2320
High kW 15.80 24.50 31.20 40.30 45.80 63.80 75.40 92.60 105.60
Total Cooling Capacity Medium kW 13.10 20.30 25.90 33.40 38.00 53.00 62.60 76.90 87.60
High l/s 0.75 1.17 1.49 1.92 2.18 3.04 3.59 4.41 5.03
Water Flow Rate Medium l/s 0.62 0.97 1.23 1.59 1.18 2.52 2.98 3.66 4.17
Low l/s 0.51 0.79 1.01 1.30 1.48 2.04 2.44 3.00 3.42
High kPa 24.70 66.00 31.40 47.90 33.00 65.50 41.00 47.70 68.40
Water Pressure Drop Medium kPa 18.30 48.90 23.20 35.50 24.50 48.60 30.50 35.40 50.70
Low kPa 13.40 35.30 17.00 25.80 17.80 34.70 22.20 25.80 37.00
Length mm 950 950 950 950 1000 1000 1000 1000 1000
Dimension Width mm 787 912 992 1058 1207 1405 1657 1734 1859
Height mm 545 545 620 620 620 620 630 690 690
Chilled Water Pipe Diameter mm(in) DN32 (1 1/4") DN40 (1 1/2") DN50 (2") DN65 (2 1/2")
Power Input kW 0.35 0.45 0.50 0.70 0.70 1.00 1.40 2.30 2.70
Current Input A 1.40 1.70 3.20 3.50 3.50 5.00 7.00 9.00 12.00
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 35.0°C DB / 28.0°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
Page 10
General Data (Belt Driven - 4 Rows) Return Air
Model FFD 030EC 040EC 050EC 060EC 070EC 080EC
Water Flow Rate l/s 0.83 1.13 1.37 1.64 1.92 2.20
Water Pressure Drop kPa 31.00 60.00 40.00 43.80 58.00 26.00
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 27.0°C DB / 19.5°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
Page 11
General Data (Belt Driven - 6 Rows) Return Air
Model FFD 030EC 040EC 050EC 060EC 070EC 080EC
Water Flow Rate l/s 1.05 1.43 1.68 2.08 2.35 2.74
Water Pressure Drop kPa 24.00 49.50 32.00 44.00 59.00 56.00
Chilled Water Pipe mm(in) DN32 (1 1/4") DN40 (1 1/2") DN50 (2")
Diameter
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 27.0°C DB / 19.5°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
Page 12
General Data (Belt Driven - 4 Rows) Fresh Air
Model FFD 030EC 040EC 050EC 060EC 070EC 080EC
Water Flow Rate l/s 1.90 2.37 3.07 3.46 4.00 4.71
Water Pressure Drop kPa 48.00 32.00 63.00 11.00 15.10 14.40
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 35.0°C DB / 28.0°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
Page 13
General Data (Belt Driven - 6 Rows) Fresh Air
Model FFD 030EC 040EC 050EC 060EC 070EC 080EC
Water Flow Rate l/s 2.18 3.04 3.59 4.41 5.03 5.75
Water Pressure Drop kPa 33.00 65.50 41.00 4 7.70 68.40 63.30
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 35.0°C DB / 28.0°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
Page 14
General Data (Belt Driven - 4 Rows) Return Air
Model FAD 030D 040D 050D 060D 070D 080D 090D 105D 120D 135D 150D
CMH 3000 4000 5000 6000 7000 8000 9000 10500 12000 13500 15000
Air Flow
CFM 1770 2350 2940 3530 4120 4710 5290 6180 7060 7940 8820
Total Cooling Capacity kW 17.20 23.40 28.20 35.10 41.00 48.20 52.30 59.70 69.80 79.10 90.40
Water Flow Rate l/s 0.80 1.10 1.30 1.70 2.00 2.30 2.50 2.80 3.30 3.80 4.30
Water Pressure Drop kPa 13.80 20.70 19.90 27.00 31.90 46.90 42.40 60.00 46.00 20.80 61.50
H1/V1 Pa 220 220 220 220 270 270 270 270 270 270 270
External Static
H2 Pa 220 220 220 220 270 270 270 270 270 270 270
Pressure
H3 Pa 220 220 220 220 270 270 270 270 270 270 270
H1/V1 kW 0.75 1.10 1.10 1.50 2.20 2.20 2.20 3.00 3.00 4.00 4.00
Motor Power H2 kW 0.75 1.10 1.50 2.20 2.20 2.20 3.00 3.00 3.00 4.00 5.50
H3 kW 1.10 1.50 1.50 2.20 2.20 3.00 3.00 4.00 4.00 4.00 5.50
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H 1 Width mm 1160 1160 1160 1160 1260 1260 1410 1410 1460 1360 1360
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H 2 Width mm 1640 1640 1640 1640 1740 1740 1990 1990 2040 1940 1940
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Dimension
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H 3 Width mm 2040 2090 2090 2090 2190 2190 2440 2440 2490 2390 2390
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
V 1 Width mm 710 710 810 810 810 810 960 960 960 960 960
Height mm 1220 1420 1570 1620 1770 1770 2020 2020 2020 2020 2070
H1 kg 148 167 186 211 242 256 299 325 350 442 447
H2 kg 177 201 230 261 288 319 343 392 426 525 569
Net Weight
H3 kg 197 224 249 282 310 345 394 433 471 574 600
V1 kg 153 175 206 231 257 272 326 360 367 481 491
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 27.0°C DB / 19.5°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
3) All Dimension for Standard 25mm Panel Thickness.
4) 50mm Panel Thickness is available upon request.
Page 15
General Data (Belt Driven - 4 Rows) Return Air
Model FAD 180D 2100D 240D 270D 300D 330D 350D 400D 450D 500D
CMH 18000 21000 24000 27000 30000 33000 35000 40000 45000 50000
Air Flow
CFM 10590 12350 14120 15880 17650 19410 20590 23530 26470 29410
Total Cooling Capacity kW 107.00 126.60 148.80 167.50 186.10 204.70 220.10 230.80 248.10 275.60
Water Flow Rate l/s 5.10 6.00 7.10 8.00 8.90 9.80 10.50 11.00 11.80 13.10
Water Pressure Drop kPa 31.80 36.30 53.40 55.10 56.80 72.30 85.60 69.20 71.50 79.10
H1/V1 Pa 320 320 320 420 420 420 470 470 470 470
External Static
H2 Pa 320 320 320 420 420 420 420 420 420 420
Pressure
H3 Pa 320 320 320 420 420 420 420 370 370 370
H1/V1 kW 5.50 7.50 7.50 11.00 11.00 15.00 15.00 15.00 18.50 22.00
Motor Power H2 kW 5.50 7.50 7.50 11.00 15.00 15.00 15.00 15.00 18.50 22.00
H3 kW 7.50 11.00 11.00 11.00 15.00 15.00 15.00 15.00 18.50 22.00
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H 1 Width mm 1510 1510 1510 1510 1560 1610 1710 1760 1760 1760
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H 2 Width mm 2090 2090 2090 2290 2340 2390 2490 2540 2540 2640
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Dimension
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H 3 Width mm 2540 2540 2540 2740 2790 2840 2940 2940 2940 3040
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
V 1 Width mm 960 960 960 960 960 1160 1160 1160 1160 1160
Height mm 2220 2270 2290 2440 2540 2640 2690 2940 3090 3240
H1 kg 539 584 644 728 761 882 953 986 1070 1097
H2 kg 652 707 780 912 958 1084 1170 1202 1285 1324
Net Weight
H3 kg 727 809 885 978 1033 1185 1246 1306 1421 1462
V1 kg 570 631 682 735 786 952 1020 1067 1112 1194
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 27.0°C DB / 19.5°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
3) All Dimension for Standard 25mm Panel Thickness.
4) 50mm Panel Thickness is available upon request.
Page 16
General Data (Belt Driven - 6 Rows) Return Air
Model FAD 030D 040D 050D 060D 070D 080D 090D 105D 120D 135D 150D
CMH 3000 4000 5000 6000 7000 8000 9000 10500 12000 13500 15000
Air Flow
CFM 1770 2350 2940 3530 4120 4710 5290 6180 7060 7940 8820
Total Cooling Capacity kW 22.70 29.60 34.50 42.40 48.80 57.20 65.10 74.20 89.90 104.10 115.00
Water Flow Rate l/s 1.10 1.40 1.60 2.00 2.30 2.70 3.10 3.50 4.30 5.00 5.50
Water Pressure Drop kPa 32.40 44.90 40.30 53.50 23.40 34.00 30.00 42.40 32.30 46.70 50.30
H1/V1 Pa 170 170 170 170 220 220 220 220 220 220 220
External Static
H2 Pa 170 170 170 170 220 220 220 220 220 220 220
Pressure
H3 Pa 170 170 170 170 220 220 220 220 220 220 220
H1/V1 kW 0.75 1.10 1.10 1.50 2.20 2.20 2.20 3.00 3.00 4.00 4.00
Motor Power H2 kW 0.75 1.10 1.50 2.20 2.20 2.20 3.00 3.00 3.00 4.00 5.50
H3 kW 1.10 1.50 1.50 2.20 2.20 3.00 3.00 4.00 4.00 4.00 5.50
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H 1 Width mm 1160 1160 1160 1160 1260 1260 1410 1410 1460 1360 1360
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H 2 Width mm 1640 1640 1640 1640 1740 1740 1990 1990 2040 1940 1940
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Dimension
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H 3 Width mm 2040 2090 2090 2090 2190 2190 2440 2440 2490 2390 2390
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
V 1 Width mm 710 710 810 810 810 810 960 960 960 960 960
Height mm 1220 1420 1570 1620 1770 1770 2020 2020 2020 2020 2070
H1 kg 155 175 197 223 257 272 318 342 376 459 470
H2 kg 184 208 240 274 303 335 362 408 452 554 597
Net Weight
H3 kg 201 232 259 295 324 362 412 450 494 598 645
V1 kg 160 183 216 244 272 289 344 376 394 518 520
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 27.0°C DB / 19.5°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
3) All Dimension for Standard 25mm Panel Thickness.
4) 50mm Panel Thickness is available upon request.
Page 17
General Data (Belt Driven - 6 Rows) Return Air
Model FAD 180D 2100D 240D 270D 300D 330D 350D 400D 450D 500D
CMH 18000 21000 24000 27000 30000 33000 35000 40000 45000 50000
Air Flow
CFM 10590 12350 14120 15880 17650 19410 20590 23530 26470 29410
Total Cooling Capacity kW 136.40 157.40 181.90 204.70 226.10 253.00 271.30 299.80 341.10 379.00
Water Flow Rate l/s 6.50 7.50 8.70 9.80 10.80 12.10 12.90 14.30 16.30 18.10
Water Pressure Drop kPa 21.00 26.40 37.70 39.00 39.80 52.20 61.60 52.50 59.80 65.90
H1/V1 Pa 270 270 270 370 370 370 420 420 420 420
External Static
H2 Pa 270 270 270 370 370 370 370 370 370 370
Pressure
H3 Pa 270 270 270 370 370 370 370 370 320 320
H1/V1 kW 5.50 7.50 7.50 11.00 11.00 15.00 15.00 15.00 18.50 22.00
Motor Power H2 kW 5.50 7.50 7.50 11.00 15.00 15.00 15.00 15.00 18.50 22.00
H3 kW 7.50 11.00 11.00 11.00 15.00 15.00 15.00 15.00 18.50 22.00
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H 1 Width mm 1510 1510 1510 1510 1560 1610 1710 1760 1760 1760
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H 2 Width mm 2090 2090 2090 2290 2340 2390 2490 2540 2540 2640
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Dimension
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H 3 Width mm 2540 2540 2540 2740 2790 2840 2940 2940 2940 3040
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
V 1 Width mm 960 960 960 960 960 1160 1160 1160 1160 1160
Height mm 2220 2270 2290 2440 2540 2640 2690 2940 3090 3240
H1 kg 580 626 692 781 813 947 1022 1099 1187 1231
H2 kg 693 750 829 965 1017 1149 1239 1315 1403 1459
Net Weight
H3 kg 759 842 922 1022 1092 1250 1236 1400 1539 1597
V1 kg 611 673 730 789 845 1018 1089 1181 1129 1330
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 27.0°C DB / 19.5°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
3) All Dimension for Standard 25mm Panel Thickness.
4) 50mm Panel Thickness is available upon request.
Page 18
General Data (Belt Driven - 4 Rows) Fresh Air
Model FAD 030D 040D 050D 060D 070D 080D 090D 105D 120D 135D 150D
CMH 3000 4000 5000 6000 7000 8000 9000 10500 12000 13500 15000
Air Flow
CFM 1770 2350 2940 3530 4120 4710 5290 6180 7060 7940 8820
Total Cooling Capacity kW 40.50 54.70 68.40 81.00 89.60 101.70 116.80 145.50 157.90 172.80 194.70
Water Flow Rate l/s 1.90 2.60 3.30 6.00 6.60 6.60 7.70 7.70 7.70 8.20 9.30
Water Pressure Drop kPa 31.90 49.80 49.40 46.20 49.40 63.40 5 7.30 62.60 66.70 13.80 15.60
H1/V1 Pa 220 220 220 220 270 270 270 270 270 270 270
External Static
H2 Pa 220 220 220 220 270 270 270 270 270 270 270
Pressure
H3 Pa 220 220 220 220 270 270 270 270 270 270 270
H1/V1 kW 0.75 1.10 1.10 1.50 2.20 2.20 2.20 3.00 3.00 4.00 4.00
Motor Power H2 kW 0.75 1.10 1.50 2.20 2.20 2.20 3.00 3.00 3.00 4.00 5.50
H3 kW 1.10 1.50 1.50 2.20 2.20 3.00 3.00 4.00 4.00 4.00 5.50
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H1/
Width mm 1160 1160 1160 1160 1260 1260 1410 1410 1460 1360 1360
V1
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H2 Width mm 1640 1640 1640 1640 1740 1740 1990 1990 2040 1940 1940
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Dimension
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H3 Width mm 2040 2090 2090 2090 2190 2190 2440 2440 2490 2390 2390
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
V1 Width mm 710 710 810 810 810 810 960 960 960 960 960
Height mm 1220 1420 1570 1620 1770 1770 2020 2020 2020 2020 2070
H1 kg 148 167 186 211 242 256 299 325 350 442 447
H2 kg 177 201 230 261 288 319 343 392 426 525 569
Net Weight
H3 kg 197 224 249 282 310 345 394 433 471 574 600
V1 kg 153 175 206 231 257 272 326 360 367 481 491
mm(in) DN40
Chilled Water Pipe Diameter DN50 (2") DN65 (2 1/2") DN80 (3")
(1 1/2")
Condensate Drain Size mm(in) DN25 (1") DN32 (1 1/4")
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 35.0°C DB / 28.0°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
3) All Dimension for Standard 25mm Panel Thickness.
4) 50mm Panel Thickness is available upon request.
Page 19
General Data (Belt Driven - 4 Rows) Fresh Air
Model FAD 180D 2100D 240D 270D 300D 330D 350D 400D 450D 500D
CMH 18000 21000 24000 27000 30000 33000 35000 40000 45000 50000
Air Flow
CFM 10590 12350 14120 15880 17650 19410 20590 23530 26470 29410
Total Cooling Capacity kW 230.50 276.30 319.90 359.90 384.10 445.70 454.30 477.10 536.70 605.10
Water Flow Rate l/s 11.00 13.20 15.20 17.10 18.30 21.20 21.60 22.70 25.60 28.80
Water Pressure Drop kPa 20.70 28.10 39.60 42.60 43.20 59.80 63.70 40.30 45.30 51.60
H1/V1 Pa 320 320 320 420 420 420 470 470 470 470
External Static
H2 Pa 320 320 320 420 420 420 420 420 420 420
Pressure
H3 Pa 320 320 320 420 420 420 420 370 370 370
H1/V1 kW 5.50 7.50 7.50 11.00 11.00 15.00 15.00 15.00 18.50 22.00
Motor Power H2 kW 5.50 7.50 7.50 11.00 15.00 15.00 15.00 15.00 18.50 22.00
H3 kW 7.50 11.00 11.00 11.00 15.00 15.00 15.00 15.00 18.50 22.00
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H1/
Width mm 1510 1510 1510 1510 1560 1610 1710 1760 1760 1760
V1
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H2 Width mm 2090 2090 2090 2290 2340 2390 2490 2540 2540 2640
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Dimension
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H3 Width mm 2540 2540 2540 2740 2790 2840 2940 2940 2940 3040
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
V1 Width mm 960 960 960 960 960 1160 1160 1160 1160 1160
Height mm 2220 2270 2290 2440 2540 2640 2690 2940 3090 3240
H1 kg 539 584 644 728 761 882 953 986 1070 1097
H2 kg 652 707 780 912 958 1084 1170 1202 1285 1324
Net Weight
H3 kg 727 809 885 978 1033 1185 1246 1306 1421 1462
V1 kg 570 631 682 735 786 952 1020 1067 1112 1194
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 35.0°C DB / 28.0°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
3) All Dimension for Standard 25mm Panel Thickness.
4) 50mm Panel Thickness is available upon request.
Page 20
General Data (Belt Driven - 6 Rows) Fresh Air
Model FAD 030D 040D 050D 060D 070D 080D 090D 105D 120D 135D 150D
CMH 3000 4000 5000 6000 7000 8000 9000 10500 12000 13500 15000
Air Flow
CFM 1770 2350 2940 3530 4120 4710 5290 6180 7060 7940 8820
Total Cooling Capacity kW 47.90 63.80 79.80 97.90 115.40 127.70 140.50 162.10 193.60 222.60 252.60
Water Flow Rate l/s 2.30 3.00 3.80 4.70 5.50 6.10 6.70 7.70 9.20 10.60 12.00
Water Pressure Drop kPa 45.90 32.40 29.60 39.40 48.00 21.60 20.50 29.30 43.00 61.10 69.30
H1/V1 Pa 170 170 170 170 220 220 220 220 220 220 220
External Static
H2 Pa 170 170 170 170 220 220 220 220 220 220 220
Pressure
H3 Pa 170 170 170 170 220 220 220 220 220 220 220
H1/V1 kW 0.75 1.10 1.10 1.50 2.20 2.20 2.20 3.00 3.00 4.00 4.00
Motor Power H2 kW 0.75 1.10 1.50 2.20 2.20 2.20 3.00 3.00 3.00 4.00 5.50
H3 kW 1.10 1.50 1.50 2.20 2.20 3.00 3.00 4.00 4.00 4.00 5.50
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H1/
Width mm 1160 1160 1160 1160 1260 1260 1410 1410 1460 1360 1360
V1
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H2 Width mm 1640 1640 1640 1640 1740 1740 1990 1990 2040 1940 1940
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Dimension
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
H3 Width mm 2040 2090 2090 2090 2190 2190 2440 2440 2490 2390 2390
Height mm 720 790 920 990 1070 1070 1170 1170 1170 1170 1270
Length mm 953 1053 1053 1153 1203 1353 1353 1553 1703 1953 1953
V1 Width mm 710 710 810 810 810 810 960 960 960 960 960
Height mm 1220 1420 1570 1620 1770 1770 2020 2020 2020 2020 2070
H1 kg 155 175 197 223 257 272 318 342 376 459 470
H2 kg 184 208 240 274 303 335 362 408 452 554 597
Net Weight
H3 kg 201 232 259 295 324 362 412 450 494 598 645
V1 kg 160 183 216 244 272 289 344 376 394 518 520
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 35.0°C DB / 28.0°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
3) All Dimension for Standard 25mm Panel Thickness.
4) 50mm Panel Thickness is available upon request.
5) *Indicates the water temperature difference is more than 5 C.
Page 21
General Data (Belt Driven - 6 Rows) Fresh Air
Model FAD 180D 2100D 240D 270D 300D 330D 350D 400D 450D 500D
CMH 18000 21000 24000 27000 30000 33000 35000 40000 45000 50000
Air Flow
CFM 10590 12350 14120 15880 17650 19410 20590 23530 26470 29410
Total Cooling Capacity kW 293.60 331.50 *366.20 *409.60 *455.20 *503.60 *552.50 *589.30 *647.20 *727.90
Water Flow Rate l/s 13.10 13.90 *12.50 *13.90 *15.50 *17.10 *15.50 *18.70 *19.30 *21.70
Water Pressure Drop kPa 71.80 78.30 *70.70 *72.40 *75.00 *96.30 *83.60 *83.50 *79.80 *89.90
H1/V1 Pa 270 270 270 370 370 370 420 420 420 420
External Static
H2 Pa 270 270 270 370 370 370 370 370 370 370
Pressure
H3 Pa 270 270 270 370 370 370 370 370 320 320
H1/V1 kW 5.50 7.50 7.50 11.00 11.00 15.00 15.00 15.00 18.50 22.00
Motor Power H2 kW 5.50 7.50 7.50 11.00 15.00 15.00 15.00 15.00 18.50 22.00
H3 kW 7.50 11.00 11.00 11.00 15.00 15.00 15.00 15.00 18.50 22.00
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H1/
Width mm 1510 1510 1510 1510 1560 1610 1710 1760 1760 1760
V1
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H2 Width mm 2090 2090 2090 2290 2340 2390 2490 2540 2540 2640
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Dimension
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
H3 Width mm 2540 2540 2540 2740 2790 2840 2940 2940 2940 3040
Height mm 1320 1370 1390 1520 1640 1640 1640 1893 2020 2150
Length mm 2153 2353 2653 2653 2653 2903 3053 3053 3053 3153
V1 Width mm 960 960 960 960 960 1160 1160 1160 1160 1160
Height mm 2220 2270 2290 2440 2540 2640 2690 2940 3090 3240
H1 kg 580 626 692 781 813 947 1022 1099 1187 1231
H2 kg 693 750 829 965 1017 1149 1239 1315 1403 1459
Net Weight
H3 kg 759 842 922 1022 1092 1250 1236 1400 1539 1597
V1 kg 611 673 730 789 845 1018 1089 1181 1129 1330
Note:
1) Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 35.0°C DB / 28.0°C WB
2) All the specifications are subjected to change by manufacturer without prior notice.
3) All Dimension for Standard 25mm Panel Thickness.
4) 50mm Panel Thickness is available upon request.
5) *Indicates the water temperature difference is more than 5 C.
Page 22
Equipment Selection
External Static Pressure VS Motor Power Chart - Ceiling Hung
Air Flow ESP
FFD Rows
CMH CFM 80 120 160 200 240 280 320 360
4 0.18 0.18 0.25 0.25
010EC 1000 588
6 0.18 0.25 0.25 0.25
4 0.18 0.25 0.25 0.25 0.25
015EC 1500 882
6 0.25 0.25 0.25 0.25 0.32
4 0.32 0.32 0.32 0.32 0.32 0.32
020EC 2000 1176
6 0.32 0.32 0.32 0.32 0.37
4 0.32 0.37 0.45 0.45 0.45 0.55
025EC 2500 1471
6 0.37 0.45 0.45 0.45 0.55 0.55
4 0.55 0.75 0.75 0.75 0.75 1.10 1.10
030EC 3000 1765
6 0.75 0.75 0.75 0.75 1.10 1.10 1.10
4 1.10 1.10 1.10 1.10 1.10 1.10 1.50
040EC 4000 2353
6 1.10 1.10 1.10 1.10 1.10 1.50 1.50
4 1.10 1.50 1.50 1.50 1.50 2.20 2.20
050EC 5000 2941
6 1.50 1.50 1.50 1.50 2.20 2.20 2.20
4 1.50 1.50 1.50 1.50 2.20 2.20 2.20
060EC 6000 3529
6 1.50 1.50 1.50 2.20 2.20 2.20 2.20
4 1.50 1.50 2.20 2.20 2.20 2.20 2.20
070EC 7000 4118
6 1.50 2.20 2.20 2.20 2.20 2.20 3.00
4 2.20 2.20 2.20 2.20 2.20 3.00 3.00
080EC 8000 4706
6 2.20 2.20 2.20 2.20 3.00 3.00 3.00
4 2.20 2.20 2.20 2.20 2.20 3.00 3.00
090EC 9000 5294
6 2.20 2.20 2.20 2.20 3.00 3.00 3.00
4 3.00 3.00 3.00 3.00 3.00 3.00 4.00
105EC 10500 6176
6 3.00 3.00 3.00 3.00 3.00 4.00 4.00
4 3.00 3.00 3.00 4.00 4.00 4.00
120EC 12000 7059
6 3.00 4.00 4.00 4.00 4.00 4.00
4 3.00 3.00 4.00 4.00
135EC 13500 7941
6 3.00 4.00 4.00 4.00
4 4.00 4.00 4.00 5.50
150EC 15000 8824
6 4.00 4.00 5.50 5.50
Note:
1) The table presents the motor power for different models under different external static pressure.
2) Values with bold are values under nominal external static pressure
3) The unit is in kW
Page 23
External Static Pressure VS Motor Power Chart - H1 / V1 Series
Air Flow ESP
FAD DH1 / DV1 Rows
CMH CFM 120 170 220 270 320 370 420 470 520 570 620 670 360
4 0.55 0.75 0.75 1.10 1.10 1.10 1.10 1.10
030D 3000 1765
6 0.75 0.75 0.75 1.10 1.10 1.10 1.10 1.10
4 1.10 1.10 1.10 1.10 1.10 1.50 1.50 1.50
040D 4000 2353
6 1.10 1.10 1.10 1.10 1.50 1.50 1.50 1.50
4 1.10 1.10 1.10 1.50 1.50 1.50 1.50 2.20
050D 5000 2941
6 1.10 1.10 1.50 1.50 1.50 1.50 2.20 2.20
4 1.50 1.50 1.50 2.20 2.20 2.20 2.20 2.20
060D 6000 3529
6 1.50 1.50 2.20 2.20 2.20 2.20 2.20 3.00
4 1.50 1.50 1.50 2.20 2.20 2.20 2.20 2.20 3.00 3.00
070D 7000 4118
6 1.50 1.50 2.20 2.20 2.20 2.20 2.20 3.00 3.00 3.00
4 2.20 2.20 2.20 2.20 2.20 3.00 3.00 3.00 3.00 3.00
080D 8000 4706
6 2.20 2.20 2.20 2.20 3.00 3.00 3.00 3.00 3.00 4.00
4 2.20 2.20 2.20 2.20 3.00 3.00 3.00 3.00 4.00 4.00
090D 9000 5294
6 2.20 2.20 2.20 3.00 3.00 3.00 3.00 4.00 4.00 4.00
4 2.20 3.00 3.00 3.00 3.00 3.00 4.00 4.00 4.00 4.00
105D 10500 6176
6 3.00 3.00 3.00 3.00 3.00 4.00 4.00 4.00 4.00 5.50
4 2.20 3.00 3.00 3.00 3.00 4.00 4.00 4.00 4.00 5.50
120D 12000 7059
6 3.00 3.00 3.00 3.00 4.00 4.00 4.00 4.00 5.50 5.50
4 3.00 3.00 3.00 4.00 4.00 4.00 4.00 5.50 5.50 5.50
135D 13500 8824
6 3.00 3.00 4.00 4.00 4.00 4.00 5.50 5.50 5.50 5.50
4 3.00 4.00 4.00 4.00 5.50 5.50 5.50 5.50 5.50 7.50
150D 15000 8824
6 4.00 4.00 4.00 5.50 5.50 5.50 5.50 5.50 7.50 7.50
4 4.00 4.00 5.50 5.50 5.50 5.50 7.50 7.50 7.50 7.50
180D 18000 10588
6 4.00 5.50 5.50 5.50 5.50 7.50 7.50 7.50 7.50 7.50
4 5.50 5.50 5.50 7.50 7.50 7.50 7.50 11.00 11.00 11.00
210D 21000 12353
6 5.50 5.50 7.50 7.50 7.50 7.50 11.00 11.00 11.00 11.00
4 5.50 5.50 5.50 7.50 7.50 7.50 11.00 11.00 11.00 11.00
240D 24000 14118
6 5.50 5.50 7.50 7.50 7.50 11.00 11.00 11.00 11.00 11.00
4 7.50 7.50 7.50 7.50 11.00 11.00 11.00 11.00 11.00 11.00 15.00 15.00
270D 27000 15882
6 7.50 7.50 7.50 11.00 11.00 11.00 11.00 11.00 11.00 15.00 15.00
4 7.50 11.00 11.00 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00
300D 30000 17647
6 11.00 11.00 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00
4 7.50 11.00 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 15.00
330D 33000 19412
6 11.00 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 15.00 18.50
4 7.50 7.50 11.00 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00
350D 35000 20588
6 7.50 11.00 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 18.50
4 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 18.50 18.50 18.50
400D 40000 23529
6 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 18.50 18.50 18.50 18.50
4 15.00 15.00 15.00 15.00 15.00 15.00 18.50 18.50 18.50 18.50 22.00 22.00
450D 450000 264706
6 15.00 15.00 15.00 15.00 15.00 18.50 18.50 18.50 18.50 22.00 22.00
4 15.00 15.00 18.50 18.50 18.50 18.50 22.00 22.00 22.00
500D 50000 29412
6 15.00 18.50 18.50 18.50 18.50 22.00 22.00 22.00
Note:
1) The table presents the motor power for different models under different external static pressure.
2) Values with bold are values under nominal external static pressure
3) The unit is in kW
Page 24
External Static Pressure VS Motor Power Chart - H2 Series
Air Flow ESP
FAD DH2 Rows
CMH CFM 120 170 220 270 320 370 420 470 520 570 620 670
4 0.75 0.75 0.75 1.10 1.10 1.10 1.10 1.10
030D 3000 1765
6 0.75 0.75 1.10 1.10 1.10 1.10 1.10 1.50
4 1.10 1.10 1.10 1.10 1.50 1.50 1.50 2.20
040D 4000 2353
6 1.10 1.10 1.10 1.50 1.50 1.50 2.20 2.20
4 1.10 1.10 1.50 1.50 1.50 1.50 2.20 2.20
050D 5000 2941
6 1.10 1.50 1.50 1.50 1.50 2.20 2.20 2.20
4 1.50 1.50 2.20 2.20 2.20 2.20 2.20 3.00
060D 6000 3529
6 1.50 2.20 2.20 2.20 2.20 2.20 3.00 3.00
4 1.50 1.50 2.20 2.20 2.20 2.20 2.20 3.00 3.00 3.00
070D 7000 4118
6 1.50 2.20 2.20 2.20 2.20 2.20 3.00 3.00 3.00 3.00
4 2.20 2.20 2.20 2.20 3.00 3.00 3.00 3.00 3.00 4.00
080D 8000 4706
6 2.20 2.20 2.20 3.00 3.00 3.00 3.00 3.00 4.00 4.00
4 2.20 2.20 2.20 3.00 3.00 3.00 3.00 4.00 4.00 4.00
090D 9000 5294
6 2.20 2.20 3.00 3.00 3.00 3.00 4.00 4.00 4.00 4.00
4 3.00 3.00 3.00 3.00 4.00 4.00 4.00 4.00 4.00 5.50
105D 10500 6176
6 3.00 3.00 3.00 4.00 4.00 4.00 4.00 4.00 5.50 5.50
4 3.00 3.00 3.00 3.00 4.00 4.00 4.00 5.50 5.50 5.50
120D 12000 7059
6 3.00 3.00 3.00 4.00 4.00 4.00 5.50 5.50 5.50 5.50
4 3.00 3.00 4.00 4.00 4.00 4.00 5.50 5.50 5.50 5.50
135D 15000 8824
6 3.00 4.00 4.00 4.00 4.00 5.50 5.50 5.50 5.50 7.50
4 4.00 4.00 4.00 5.50 5.50 5.50 5.50 5.50 7.50 7.50
150D 15000 8824
6 4.00 4.00 5.50 5.50 5.50 5.50 5.50 7.50 7.50 7.50
4 4.00 5.50 5.50 5.50 5.50 7.50 7.50 7.50 7.50 7.50
180D 18000 10588
6 5.50 5.50 5.50 5.50 7.50 7.50 7.50 7.50 7.50 11.00
4 5.50 5.50 7.50 7.50 7.50 7.50 11.00 11.00 11.00 11.00
210D 21000 12353
6 5.50 7.50 7.50 7.50 7.50 11.00 11.00 11.00 11.00 11.00
4 5.50 5.50 7.50 7.50 7.50 11.00 11.00 11.00 11.00 11.00
240D 24000 14118
6 5.50 7.50 7.50 7.50 11.00 11.00 11.00 11.00 11.00
4 7.50 7.50 7.50 11.00 11.00 11.00 11.00 11.00 11.00 15.00 15.00
270D 27000 15882
6 7.50 7.50 11.00 11.00 11.00 11.00 11.00 11.00 15.00 15.00
4 11.00 11.00 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00
300D 30000 17647
6 11.00 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00
4 11.00 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 15.00
330D 33000 19412
6 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 15.00 18.50
4 7.50 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 15.00
350D 35000 20588
6 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 15.00 18.50
4 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 18.50 18.50 18.50
400D 40000 23529
6 11.00 11.00 15.00 15.00 15.00 15.00 15.00 18.50 18.50 18.50 18.50
4 15.00 15.00 15.00 15.00 15.00 18.50 18.50 18.50 18.50 22.00 22.00
450D 450000 264706
6 15.00 15.00 15.00 15.00 18.50 18.50 18.50 18.50 22.00 22.00
4 15.00 18.50 18.50 18.50 18.50 22.00 22.00 22.00
500D 50000 29412
6 18.50 18.50 18.50 18.50 22.00 22.00 22.00
Note:
1) The table presents the motor power for different models under different external static pressure.
2) Values with bold are values under nominal external static pressure
3) The unit is in kW
Page 25
External Static Pressure VS Motor Power Chart - H3 Series
Air Flow ESP
FAD DH3 Rows
CMH CFM 120 170 220 270 320 370 420 470 520 570 620 670
4 0.75 1.10 1.10 1.10 1.10 1.10 1.50 1.50
030D 3000 1765
6 1.10 1.10 1.10 1.10 1.10 1.50 1.50
4 1.10 1.10 1.50 1.50 1.50 2.20 2.20 2.20
040D 4000 2353
6 1.10 1.50 1.50 1.50 2.20 2.20 2.20 2.20
4 1.50 1.50 1.50 1.50 2.20 2.20 2.20 2.20
050D 5000 2941
6 1.50 1.50 1.50 2.20 2.20 2.20 2.20 2.20
4 2.20 2.20 2.20 2.20 2.20 3.00 3.00 3.00
060D 6000 3529
6 2.20 2.20 2.20 2.20 3.00 3.00 3.00
4 2.20 2.20 2.20 2.20 2.20 3.00 3.00 3.00 3.00 3.00
070D 7000 4118
6 2.20 2.20 2.20 2.20 3.00 3.00 3.00 3.00 3.00 4.00
4 2.20 2.20 3.00 3.00 3.00 3.00 3.00 3.00 4.00 4.00
080D 8000 4706
6 2.20 3.00 3.00 3.00 3.00 3.00 3.00 4.00 4.00 4.00
4 2.20 3.00 3.00 3.00 3.00 4.00 4.00 4.00 4.00 4.00
090D 9000 5294
6 3.00 3.00 3.00 3.00 4.00 4.00 4.00 4.00 4.00 5.50
4 3.00 3.00 4.00 4.00 4.00 4.00 4.00 5.50 5.50 5.50
105D 10500 6176
6 3.00 4.00 4.00 4.00 4.00 4.00 5.50 5.50 5.50 5.50
4 3.00 3.00 4.00 4.00 4.00 5.50 5.50 5.50 5.50
120D 12000 7059
6 3.00 4.00 4.00 4.00 5.50 5.50 5.50 5.50
4 4.00 4.00 4.00 4.00 5.50 5.50 5.50 5.50 7.50
135D 15000 8824
6 4.00 4.00 4.00 5.50 5.50 5.50 5.50 7.50
4 4.00 5.50 5.50 5.50 5.50 5.50 7.50 7.50 7.50 7.50
150D 15000 8824
6 5.50 5.50 5.50 5.50 5.50 7.50 7.50 7.50 7.50
4 5.50 5.50 5.50 7.50 7.50 7.50 7.50 7.50 11.00 11.00
180D 18000 10588
6 5.50 5.50 7.50 7.50 7.50 7.50 7.50 11.00 11.00 11.00
4 7.50 7.50 7.50 7.50 11.00 11.00 11.00 11.00 11.00 11.00
210D 21000 12353
6 7.50 7.50 7.50 11.00 11.00 11.00 11.00 11.00 11.00 11.00
4 7.50 7.50 7.50 11.00 11.00 11.00 11.00 11.00
240D 24000 14118
6 7.50 7.50 11.00 11.00 11.00 11.00 11.00
4 7.50 11.00 11.00 11.00 11.00 11.00 11.00 15.00 15.00
270D 27000 15882
6 11.00 11.00 11.00 11.00 11.00 11.00 15.00 15.00
4 11.00 11.00 11.00 11.00 15.00 15.00 15.00 15.00
300D 30000 17647
6 11.00 11.00 11.00 15.00 15.00 15.00 15.00
4 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 15.00 18.50
330D 33000 19412
6 11.00 11.00 15.00 15.00 15.00 15.00 15.00 15.00 18.50 18.50
4 11.00 11.00 11.00 15.00 15.00 15.00 15.00 15.00 15.00
350D 35000 20588
6 11.00 11.00 15.00 15.00 15.00 15.00 15.00 15.00 18.50
4 11.00 15.00 15.00 15.00 15.00 15.00 18.50 18.50 18.50 18.50
400D 40000 23529
6 15.00 15.00 15.00 15.00 15.00 18.50 18.50 18.50 18.50
4 15.00 15.00 15.00 18.50 18.50 18.50 18.50 22.00 22.00
450D 450000 264706
6 15.00 15.00 18.50 18.50 18.50 18.50 22.00 22.00
4 18.50 18.50 18.50 22.00 22.00 22.00
500D 50000 29412
6 18.50 18.50 22.00 22.00 22.00
Note:
1) The table presents the motor power for different models under different external static pressure.
2) Values with bold are values under nominal external static pressure
3) The unit is in kW
Page 26
Dimensions
\
40 F 60 WATER O UT LET D
G
WATER INLET
E
B
J
CONNECTING BOX
H
CONDENSATION WATER OUTLET
20 20
C A
D
G H1 G
G AD G
B
E
J
A
H
20 20
A
FFD 030 - 040C
Return Fresh
FFD A B C D E F G H H1 J Air Flange Air Flange
010CC 787 545 950 623 505 850 300 88 - 262 563 x 445 300 x 260
015CC 912 545 950 748 505 850 300 88 - 262 688 x 445 300 x 260
020CC 992 620 950 828 580 850 300 88 - 262 768 x 520 300 x 260
025CC 1058 620 950 894 580 850 300 88 - 262 834 x 520 300 x 260
030CC 1207 620 1000 1043 580 900 232 88 275 262 983 x 520 740 x 262
040CC 1405 620 1000 1241 580 900 300 88 205 262 1181 x 520 805 x 262
*Dimension in mm
Page 27
Model: FFD 050 - 070EC-C (3 Speeds)
40 F 60 WATER OUTLET D
I G H1 G
WATER INLET
E
J
B
CONNECTING BOX
H
CONDENSATION WATER OUTLET
C 20 20
A
Return Fresh
FFD A B C D E F G H H1 J Air Flange Air Flange
050CC 1657 630 1000 1493 580 900 300 89 330 262 1433 x 520 930 x 262
060CC 1734 690 1000 1570 640 900 331 234 308 289 1510 x 580 970 x 291
070CC 1859 690 1000 1695 640 900 331 234 308 289 1635 x 580 970 x 291
*Dimension in mm
Page 28
Model: FFD 030 - 150 EC-D (Belt Driven, Ceiling Hung Type)
40 F 60 WATER OUTLET D
I G
WATER INLET
E
B
J
CONNECTING BOX
20 20
C A
FFD 030 - 040EC
D
G H G
E
J
B
20 20
A
FFD 050 - 150EC
Return Fresh
FFD A B C D E F G H J Air Flange Air Flange
030EC 1207 620 1000 1043 580 900 298 - 262 983 x 520 298 x 262
040EC 1405 620 1000 1241 580 900 331 - 289 1181 x 520 331 x 289
050EC 1657 630 1000 1493 580 900 232 184 262 1433 x 520 648 x 262
060EC 1734 690 1000 1570 640 900 265 214 289 1510 x 580 744 x 289
070EC 1859 690 1000 1695 640 900 331 264 289 1635 x 580 926 x 289
080EC 1859 780 1000 1695 730 900 331 264 289 1635 x 670 926 x 289
090EC 1988 780 1100 1824 730 1000 309 244 341 1764 x 670 862 x 341
105EC 2248 780 1100 2084 730 1000 309 244 341 2024 x 670 862 x 341
120EC 2298 820 1100 2134 770 1000 395 324 341 2074 x 710 1141 x 341
135EC 2241 1027 1300 2041 947 1200 373 294 404 1981 x 887 1040 x 404
150EC 2241 1155 1300 2041 1075 1200 373 294 404 1981 x 1015 1040 x 404
*Dimension in mm
Page 29
Model: FAD 030 - 500 DV1 (Belt Driven, Vertical Type)
E
KxL
FAD 030 - 120DV1 FAD 135 - 500DV1
A
GxH GxH
D
D
C
C
B B
FAD A B C D E G H K L
030DV1 710 953 1220 1100 650 298 262 893 490
040DV1 710 1053 1420 1300 650 331 289 993 590
050DV1 810 1053 1570 1450 750 309 341 993 720
060DV1 810 1153 1620 1500 750 395 341 1093 790
070DV1 810 1203 1770 1650 750 373 404 1143 840
080DV1 810 1353 1770 1650 750 373 404 1293 840
090DV1 960 1353 2020 1900 900 430 478 1293 970
105DV1 960 1553 2020 1900 900 430 478 1493 970
120DV1 960 1703 2020 1900 900 557 478 1643 970
135DV1 960 1953 2020 1900 900 1040 404 1893 990
150DV1 960 1953 2070 1950 900 1040 404 1893 1040
180DV1 960 2153 2220 2100 900 1203 478 2093 1140
210DV1 960 2353 2270 2150 900 1203 478 2293 1190
240DV1 960 2653 2290 2150 900 1572 478 2593 1190
270DV1 960 2653 2440 2300 900 1572 478 2593 1320
300DV1 960 2653 2540 2400 900 1572 478 2593 1440
330DV1 1160 2903 2640 2500 1100 1588 569 2843 1440
350DV1 1160 3053 2690 2550 1100 1776 638 2993 1440
400DV1 1160 3053 2940 2800 1100 1776 638 2993 1690
450DV1 1160 3053 3090 2950 1100 1776 638 2993 1840
500DV1 1160 3153 3240 3100 1100 1776 638 3093 1940
*Model FAD270DV1 and above adopt CKD method in sea freight shipping.
*All Dimension for Standard 25mm Panel Thickness.
* 50mm Panel Thickness is available upon request.
Page 30
Model: FAD 030 - 500 DH1 (Belt Driven, Horizontal Type 1)
KxL
D
C
C
B B
FAD A B C D E G H K L
030DH1 1160 953 720 600 1100 298 262 893 540
040DH1 1160 1053 790 670 1100 331 289 993 610
050DH1 1160 1053 920 800 1100 309 341 993 740
060DH1 1160 1153 990 870 1100 395 341 1093 810
070DH1 1260 1203 1070 950 1200 373 404 1143 890
080DH1 1260 1353 1070 950 1200 373 404 1293 890
090DH1 1410 1353 1170 1050 1350 430 478 1293 990
105DH1 1410 1553 1170 1050 1350 430 478 1493 990
120DH1 1460 1703 1170 1050 1400 557 478 1643 990
135DH1 1360 1953 1170 1050 1300 1040 404 1893 990
150DH1 1360 1953 1270 1150 1300 1040 404 1893 1090
180DH1 1510 2153 1320 1200 1450 1203 478 2093 1140
210DH1 1510 2353 1370 1250 1450 1203 478 2293 1190
240DH1 1510 2653 1390 1250 1450 1572 478 2593 1190
270DH1 1510 2653 1520 1380 1450 1572 478 2593 1320
300DH1 1560 2653 1640 1500 1500 1572 478 2593 1440
330DH1 1610 2903 1640 1500 1550 1588 569 2843 1440
350DH1 1710 3053 1640 1500 1650 1776 638 2993 1440
400DH1 1760 3053 1893 1753 1700 1776 638 2993 1693
450DH1 1760 3053 2020 1880 1700 1776 638 2993 1820
500DH1 1760 3153 2150 2010 1700 1776 638 3093 1950
Page 31
Model: FAD 030 - 500 DH2 (Belt Driven, Horizontal Type 2)
E
KxL
KxL
A’
FAD 030 - 120DH2 A FAD 135 - 500DH2
GxH GxH
D
D
C
C
B B
FAD A A' B C D E G H K L
030DH2 1 64 0 - 953 720 600 1 60 0 298 262 600 300
040DH2 1640 - 1053 790 670 1600 331 289 700 300
050DH2 1640 - 1053 920 800 1600 309 341 800 300
060DH2 1640 - 1153 990 870 1600 395 341 900 300
070DH2 1740 - 1203 1070 950 1700 373 404 1000 300
080 DH2 1740 - 1353 1070 950 1700 373 404 1100 300
090DH2 1990 - 1353 1170 1050 1950 430 478 1000 440
105DH2 1990 - 1553 1170 1050 1950 430 478 1100 440
120DH2 2040 - 1703 1170 1050 2000 557 478 1200 440
135DH2 1940 - 1953 11 7 0 1050 1900 1040 404 1300 440
150DH2 1940 - 1953 12 7 0 1150 1900 1040 404 1500 440
180DH2 2090 - 2153 13 2 0 1200 2050 1203 478 1700 440
210DH2 2090 - 2353 13 7 0 1250 2050 1203 478 1900 440
240DH2 2090 - 2653 1390 1250 2050 1572 478 2200 440
270DH2 2290 - 2653 1520 1380 2250 1572 478 2200 580
300DH2 2340 607 2653 1640 1500 2300 1572 478 2300 580
330DH2 2390 807 2903 1640 1500 2350 1588 569 2400 580
350DH2 2490 807 3053 1640 1500 2450 1776 638 2400 580
400DH2 2540 800 3053 1893 1753 2500 1776 638 2600 580
450DH2 2540 800 3053 2020 1880 2500 1776 638 2800 580
500DH2 2640 900 3153 2150 2010 2600 1776 638 2800 630
*All Dimension for Standard 25mm Panel Thickness.
*50mm Panel Thickness is available upon request.
Page 32
Model: FAD 030 - 500 DH3 (Belt Driven, Horizontal Type 3)
E
KxL
KxL
A’
A
FAD 030 - 120DH3 FAD 135 - 500DH3
GxH D GxH
D
C
C
B B
FAD A A' B C D E G H K L
030DH3 2040 - 953 720 600 2000 298 262 600 300
040DH3 2090 - 1053 790 670 2050 331 289 700 300
050DH3 2090 - 1053 920 800 2050 309 341 800 300
060DH3 2090 - 1153 990 870 2050 395 341 900 300
070DH3 2190 - 1203 1070 950 2150 373 404 1000 300
080DH3 2190 - 1353 1070 950 2150 373 404 1100 300
090DH3 2440 900 1353 1170 1050 2400 430 478 1000 440
105DH3 2440 900 1553 1170 1050 2400 430 478 1100 440
120DH3 2490 900 1703 1170 1050 2450 557 478 1200 440
135DH3 2390 900 1953 1170 1050 2350 1040 404 1300 440
150DH3 2390 900 1953 1270 1150 2350 1040 404 1500 440
180DH3 2540 900 2153 1320 1200 2500 1203 478 1700 440
210DH3 2540 900 2353 1370 1250 2500 1203 478 1900 440
240DH3 2540 900 2653 1390 1250 2500 1572 478 2200 440
270DH3 2740 900 2653 1520 1380 2700 1572 478 2200 580
300DH3 2790 900 2653 1640 1500 2750 1572 478 2300 580
330DH3 2840 1200 2903 1640 1500 2800 1588 569 2400 580
350DH3 2940 1200 3053 1640 1500 2900 1776 638 2400 580
400DH3 2940 1200 3053 1893 1753 2900 1776 638 2600 580
450DH3 2940 1200 3053 2020 1880 2900 1776 638 2800 580
500DH3 3040 1200 3153 2150 2010 3000 1776 638 2800 630
Page 33
Wiring Diagrams
Model : FFD 010C - 070C (3 Speeds)
Power Supply
220 ~ 240V/1Ph/50 ~60Hz
ON/OFF
3-Speeds
ON/OFF
H L
M
KM3
KM2
H M L
Yellow/Green
Yellow
Black
Blue
Black
Red
Blue
Red
White White
White White Yellow
Yellow
Yellow/Green
Yellow/Green
QF QF
RVR
A
B SB2
C FU SB1 KM
KM
KM
FR
Km
FR FR
KM
Legend : U1 V1 W1U2 V2 W2
U VW Fu - Fuse
QF - Main switch
FR - Overload protector
KMY
D O L S tarter Y- S tarter
Note :
For unit < 11kW - DOL Starter.
For unit ≥ 11kW - Star - Delta Starter.
Overload, fuse and thermal protection is to be installed at field.
Page 34
Model : FAD 030 - 500 (Belt Driven)
RST NE Power Supply RST E
380 ~ 415 /3/50 ~ 60Hz
QF QF
RVR
A
B SB2
C FU SB1 KM
KM
KM
FR
KM
FR FR
KM
U1 V1 W1 U2 V2 W2
U VW
KMY
DOL Starter Y- Starter
Note :
For unit < 11kW - DOL Starter.
For unit ≥ 11kW - Star - Delta Starter.
Overload, fuse and thermal protection is to be installed at field.
Page 35
Installation
●● For safety consideration, the hanging rod for ceiling hung type must be firmly fitted and the unit must be hoisted
according to the diagram as shown as following. The hoist must be strong enough to withstand the weight of the
unit and maintain level while hoisting.
●● Before connecting the wiring, make sure the electrical rating is correct and the fluctuation in voltage should not
exceed 10% of the rated voltage.
●● Before startup, the fan blower should be physically checked by rotating the blade manually to make sure there is
no excessive friction and no abnormal sound. During commissioning, make sure the direction of rotation of fan
blower is correct.
Water discharge pipe
Base steel
frame
100mm
150mm
●● Ensure water pipes are cleaned before connection. Chilled/hot water connection must be connected according to
the name plate on the unit and must install valve and filter on the water entering direction of pipes.
●● All pipes must be insulated to prevent heat loss/gain and condensation of water.
●● When connecting inlet/outlet water pipe, make sure they are free of torsional force during operation (under 250
Nm). The condensate water must be discharged through the U-trap as above.
●● Ensure there is no leaking after installation.
●● Ensure that the unit do not support the weight of the duct and the water pipes.
●● All the electrical connections must adhere to the LOCAL CODES AND REGULATION.
●● For unit with fresh air, it is recommended to install air vent at fresh air section to control the amount of fresh air
entering the unit.
Page 36
Servicing and Maintenance
Caution : Make sure the unit is OFF before any service and maintenance work being carried out!
Check unit operation regularly. Scheduled and efficient maintenance will greatly improve the unit reliability and
increase its lifespan.
1. When the unit is not in operation, make sure the heat exchanger is filled with water to avoid rust. During winter,
when the ambient temperature is under 0°C, the water inside the pipes need to be discharged to avoid freezing.
(The water discharge valve is located at the bottom of water entering pipes.)
2. To ensure the high efficiency of heat exchanger, the air filter should be cleaned once a month. If the environment
is dirty, the filter needs to be washed once a week.
3. The heat exchanger should be cleaned regularly. Clean the internal part of coil after 2~3 years. If it is permitted,
use soft water for heat exchanger.
4. The drain pan and elbow should be cleaned once a year.
5. Check the flexible connector of air duct regularly. If found any air leakage, repair immediately.
6. Adjust the tension of belt regularly. Proper belt tension is important for proper unit operation and reduce the
down time. If the belt is too tight, the belt and bearing may be overloaded, subsequently reduce the lifespan. If the
belt is too loose, the belt may slip and produce unnecessary friction, which will create excessive noise and reduce
belt lifespan.
Cent
e
r to
16mm center
/m
Page 37
Troubleshooting
Troubleshooting Guide
Abnormal Noise 1. Blower blade or blower shaft loose. 1. Tighten the shaft.
2. Blower or blower housing dirty. 2. Clean blower.
3. Duct or modulating valve loose. 3. Repair duct and modulating valve.
4. Fan belts not align or loose. 4. Align or tighten fan belt.
5. Flexible duct at intake/discharge too 5. Re-adjust the flexible duct. Change if
tight. necessary / Re-adjust.
6. Fan operating point is not optimum. 6. Re-select fan motor or pulleys.
7. Lubrication is bad or no lubrication. 7. Clean the bearing and apply lubrication
oil. Change to a suitable grade of oil if
needed.
8. Bolts and nuts for motor or fan loose. 8. Tighten the bolts and nuts.
9. Fan is too small. 9. Re-select fan.
Supply Air too Low 1. Dirty filter . 1. Clean or change filter.
2. Leakages in duct. 2. Check and seal the leakages.
3. Air duct is blocked or air vent is not 3. Clear the air duct or open the air vent.
opened.
4. Fan rotate in wrong direction. 4. Reverse the phase of power supply.
5. Fan or fan motor undersized. 5. Re-select fan or fan motor / Re-Select.
6. RPM too low. 6. Change fan motor or pulleys.
Supply Air too High 1. Oversized fan or fan motor. 1. Re-select fan or fan motor/ Re-Select.
2. RPM too high. 2. Change fan motor or pulleys.
Water Leaking 1. Air velocity too high, water carry over. 1. Reduce air velocity.
2. Condensate water not being discharged 2. Check the U-trap and clean any
properly. blockage of pipe.
3. Air leakage causing condensation. 3. Find out the seal the air leakage spots.
Not Enough Cooling 1. Chilled water temperature too high. 1. Adjust the temperature of incoming
Capacity chilled water.
2. Heat exchanger dirty. 2. Clean heat exchanger.
3. Unit undersized. 3. Re-select unit.
Air Speed too High 1. Air velocity too high at discharge. 1. Increase the air outlet area.
Page 38