You are on page 1of 1

DOMESTIC WATER PUMP SCHEDULE

ELECTRICAL DATA QUANTITY PUMP'S MATERIAL MAXIMUM AMBIENT


FLOW HEAD INSTALLATION AND IP MAXIMUM LIQUID
REF. DESCRIPTION LOCATION TYPE TEMPERATURE REMARKS
(L/s) (m) CONTROL MOTOR SPEED MOTOR POWER MOTOR MOTOR MOTOR PHASE FREQUENCY VOLT RATING TEMPERATURE (°C)
DUTY STAND BY TOTAL CASING / HOUSING IMPELLER SHAFT (°C)
METHOD (RPM) (kW) PROTECTION TYPE EFFICIENCY INSULATION CLASS (Ø) (Hz) (V)

-WITH PRESSURE VESSEL .CAPACITY IN ACCORDANCE WITH MANUFACTURER


RECOMMENDATION
CONSTANT SPEED
TRANSFER WATER PUMP TO BASEMENT 2 -PRESSURE -WITH PRESSURE SWITCH
TWP-01 8.20 40.0 2900 12.0+12.0+12.0 THERMAL SWITCH IE3 F 3 60 380 2 1 3 PACKAGED MULTISTAGE CAST IRON STAINLESS STEEL STAINLESS STEEL INDOOR (IP44) 40 40
FILL SOFT WATER RESERVOIR (PUMP ROOM) SWITCH -WITH CONTROL PANEL
CENTRIFUGAL PUMP
-WITH DRY RUN PROTECTION
-SELF PRIMING WITH FOOT CHECK VALVE

-WITH PRESSURE VESSEL .CAPACITY IN ACCORDANCE WITH MANUFACTURER


RECOMMENDATION
VARIABLE SPEED PACKAGED
BASEMENT 2 PRESSURE -CONTROL PANEL FROM THE SAME MANUFACTURER
DCWP-01 TO SERVE TOILETS 8.50 65.0 2900 9.0+9.0+9.0 THERMAL SWITCH IE3 F 3 60 380 2 1 3 MULTISTAGE CENTRIFUGAL CAST IRON STAINLESS STEEL STAINLESS STEEL INDOOR (IP44) 40 40
(PUMP ROOM) SWITCH -WITH BUILT-IN VARIABLE FREQUENCY DRIVE (VFD)
BOOSTER PUMP
-WITH DRY RUN PROTECTION
-SELF PRIMING WITH FOOT CHECK VALVE

-WITH PRESSURE VESSEL .CAPACITY IN ACCORDANCE WITH MANUFACTURER


VARIABLE SPEED PACKAGED RECOMMENDATION
IRRIGATION WATER PUMP & BASEMENT 2 VERTICAL MULTISTAGE -CONTROL PANEL FROM THE SAME MANUFACTURER
IRRP-01 2.50 50.0 CONTROL PANEL 2900 3.0+3.0 THERMAL SWITCH IE3 F 3 60 380 1 - 1 CAST IRON STAINLESS STEEL STAINLESS STEEL INDOOR (IP44) 40 40
PARKING CAR WASH (PUMP ROOM) CENTRIFUGAL BOOSTER -WITH BUILT-IN VARIABLE FREQUENCY DRIVE (VFD)
PUMP SET -WITH DRY RUN PROTECTION
-SELF PRIMING WITH FOOT CHECK VALVE

-WITH PRESSURE VESSEL .CAPACITY IN ACCORDANCE WITH MANUFACTURER


RECOMMENDATION
VARIABLE SPEED PACKAGED
BASEMENT 2 PRESSURE -CONTROL PANEL FROM THE SAME MANUFACTURER
SCWP-01 TO SERVE KITCHENS 7.7 55 2900 5.0+5.0+5.0 THERMAL SWITCH IE3 F 3 60 380 1 1 2 MULTISTAGE CENTRIFUGAL CAST IRON STAINLESS STEEL STAINLESS STEEL INDOOR (IP44) 40 40
(PUMP ROOM) SWITCH -WITH BUILT-IN VARIABLE FREQUENCY DRIVE (VFD)
BOOSTER PUMP
-WITH DRY RUN PROTECTION
-SELF PRIMING WITH FOOT CHECK VALVE

NOTES:
* PUMP HEAD IS AN ESTIMATED VALUE, THE CONTRACTOR SHALL UNDERTAKE SYSTEM ACTUAL PRESSURE DROP, REVALIDATE HEAD OF PUMP AND SIZE PUMP MOTOR ACCURATELY ACCORDING TO APPROVED SHOP DRAWINGS.
** THE POWER CONSUMPTION IN (kW) SHOWN IN THE DESIGN SCHEDULES IS BASED ON PRELIMINARY EQUIPMENT SELECTION, ACTUAL POWER CONSUMPTION AND NOMINAL RATING SHOULD BE VERIFIED BY THE CONTRACTOR BASED ON FINAL EQUIPMENT SELECTION. ANY VARIANT IN POWER CONSUMPTION RATE SHALL BE CONSIDERED AT NO ADDITIONAL COST.

DOMESTIC WATER PUMP SCHEDULE

ELECTRICAL DATA QUANTITY PUMP'S MATERIAL MAXIMUM MAXIMUM


FLOW HEAD AMBIENT LIQUID
REF. DESCRIPTION LOCATION TYPE INSTALLATION AND IP RATING REMARKS
(L/s) (m) TEMPERATURE TEMPERATURE
MOTOR SPEED MOTOR POWER MOTOR PROTECTION MOTOR MOTOR INSULATION PHASE VOLT
CONTROL METHOD FREQUENCY (Hz) DUTY STAND BY TOTAL CASING / HOUSING IMPELLER SHAFT (°C) (°C)
(RPM) (kW) TYPE EFFICIENCY CLASS (Ø) (V)

-WITH DRY RUN PROTECTION


FIRE TANK CIRCULATING PUMP BASEMENT 2 -WITH TIMER SWITCH
CP-01 20.43 6.0 CONTACTOR 1450 3.0 - IE3 F 1 60 220 3 0 5 IN-LINE CENTRIFUGAL CIRCULATOR CAST IRON COMPOSITE MATERIAL STAINLESS STEEL INDOOR (IP44) 45 110
CHANGING RATE= 8 (PUMP ROOM) -CONTINUOUS HIGH WATER STREAM TEMPERATURE (NOT LESS
THAN 110° C)

You might also like