Professional Documents
Culture Documents
switches
for gas and air
GW…A6
GW…A6/1
5.01
Application
Pressure monitoring in combustion,
ventilation and air-conditioning tech-
nologies.
Suitable for gases of families 1,2,3 and
other neutral gaseous media.
1…6
Functional description GW…A6 pressure switch
Switching function
Single-acting pressure switch in over- The control unit responds to pressure. If
pressure range. the setpoint is exceeded or undershot,
If pressure increases:
The pressure switches operate without the circuit is switched on, off or over.
1 NC opens, 2 NO closes.
any power supply.
If pressure drops:
GW… / …A6 double pressure
1 NC closes, 2 NO opens.
Switching response switch
GW…A6 Combination of two flanged GW...
Short response time during pressure A6 single pressure switches. The two
fluctuations. setpoints are set separately and inde-
pendently. A combination of different 2 NO
GW…A6/1 setpoint ranges is therefore possible. COM
Slow response time during short-term The two control units are fed from the
pressure fluctuations by additional same medium at the medium’s pres- 3
damping nozzle. sure. 1 NC
p
2 NO
COM
Definition of ∆p switching differ-
ence 3 1 NC
The ∆p switching difference is the Pressure at
control unit
pressure difference between the up-
p
Setting tolerance
per and lower switching pressure. upper switching N
Adjustment when
∆p switching difference
pressure (ON)
pressure drops
2 NO
COM
falling
3 1 NC
lower switching
rising
pressure (OFF)
p N
3,5 27,5
25
3 22,5
20
2,5
17,5
2
[ mbar]
15
[ mbar ]
12,5
1,5
10
1 7,5
5
0,5 2,5
0
0
p↓ [mbar]
p ↓ [mbar]
2…6
Specifications
Pressure connection Standard (V0): centrally on housing bottom, G 1/4 inner thread
as per ISO 228
Special design (V3): additionally G 1/4 inner thread (side right)
Electrical connection Terminal connection for line sockets as per DIN EN 175 301-803, 3-pin,
protection-insulated without ground connection
Setting tolerance ± 15% switch point deviation referred to setpoint, adjusted for dropping pres-
sure, vertical diaphragm position
Deviation Permissible deviation of the set value ≤ ± 15 % in the service life test according
to EN 1854
1 no
2 no Pressure tap 3
Pressure tap 4
Pressure tap 1
3 pe (p1)
Pressure tap 2
4 pa (p2)
3…6
Dimensions [mm]
Pressure connection, optional
with damping nozzle in GW…A6/1
GW … A6, A6/1
Optional
ø 5,2
27,4
Pressure connection G 1/4
34
43
53,75
73
12,5
2
3
ø 4,2
1
58,4
39,2
10,3
18
Test nipple ø 9
Sealing screw
Oblong slot 1,0
72
42
Made in Germany
26
IP 54
Installation position
2
1
3
higher.
1
3
a pressure lower.
2 1
3
1
2
α
switch switches at pressure deviating from the set reference value.
4…6
Designation
Pressure connection
V0 Pressure connection G 1/4
position 0
V3 Pressure connection G 1/4
position 3
Sealing screw
VS0 Sealing screw at position 0
VS3 Sealing screw at position 3
Test nipple
MS9 Test nipple at position 9
GW 150 A6 [Ag-G3-MS9-V0-VS3]
Accessories for GW A6
pressure switch
5…6
Compact pressure switches
for gas and air
GW…A6
GW…A6/1
We reserve the right to make any changes in the interest of technical progress.