Professional Documents
Culture Documents
95
1. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS
EXISTING GROUND LEVEL
100
B - LIFTING SOCKET(1.2 TON ARE IN METERS UNLESS OTHERWISE SPECIFIED.
LIFTING SOCKET(1.2 TON ROAD SURFACE/INTERLOCK PAVING
CAPACITY PER SOCKET) HEAD FRAME
220 140
CAPACITY PER SOCKET) SEE DETAIL-Z (4 Nos.) 2. DO NOT SCALE FROM THE DRAWING.
(4 Nos.) PULL BOX COVER
ROAD SURFACE/ FRAME WITH INLETS
60 3 60 3 60 REF. BELOW COVER & FRAME DETAILS 3. END DUCT MUST BE IN LINE.
16mm MORTAR INTERLOCK PAVING WORKING PIT
C EXISTING GROUND LEVEL EXISTING GROUND LEVEL 4. PULL BOX COVER AND FRAME CLASS D400 FOR ALL
90
90
90
970
- NATURAL SOIL FILLING TO THE HEIGHT: 95mm AREAS, AND PROVIDED WITH UNIQUE LOCK.
90
220
75mm HOLE FOR NORMAL GROUND LEVEL STEEL FRAME
PIPE FIXING Ø75mm HOLE
FOR COMPACTION SEE NOTE 14 700345480
EXTERNAL PROTECTION 375 375 FOR PIPE FIXING
AS PER SPECIFICATION 300 154 154 300 100131 131100
220
EXTERNAL PROTECTION FRAME WITH INLETS
AS PER SPECIFICATION NOTES FOR CONCRETE PULL BOX:
BASE PLATE HEIGHT: 140mm
825
825
75 75
1065
1065
75 75 HEAD FRAME 5. CONCRETE STRENGTH AT LEAST 40 N/mm².
70
150
5
75 75 GEOTEXTILE 063780082 6. CONCRETE COVER FOR REINFORCEMENT
75 2"Ø DRAIN PIPE 75 SOAKAGE LAYER OF 150mm MINIMUM OF 50mm AT THE EDGES AND 30mm AT
75 SEE NOTE 10 75 Min.(STONE SIZES 8-24mm)
75 75 50mmØ THE FACES.
50mmØ 75mmØ FRAME HEIGHT: 220mm
7. ALL EXPOSED CONCRETE EDGES SHALL HAVE A
150
150
150 150 75mmØ WIDTH 6X Ø110
110mmØ
LENGTH 10XØ110 25mmx25mm CHAMFER.
E SECTION
100mm THK BLINDING
T10@150C/C 300X300 GEOTEXTILE +GRAVEL 100mm THK BLINDING
ONE COAT PRIMER
T10@150C/C
VERTICAL & HORIZONTAL
- 063780052 8.
9.
SPACERS IN ROBUST PROPRIETARY PLASTIC.
EXTRA OPENINGS CLOSED WITH STYROFOAM
VERTICAL & HORIZONTAL
1000 550 FRAME HEIGHT: 220mm OR EQUIVALENT EXTRUDED POLYSTERENE FOAM
25mm CEMENT RENDERING WITH FALL TO THE END. 200 75 400 75 200 WIDTH 6X Ø110 SEALED WITH SILICON MASTIC.
DIRECTION DETERMINED BY SITE CONDITIONS. LENGTH 10XØ110
063780052 10. DRAIN PIPE INSTALLED ONLY IF WATER TABLE IS
95
EXISTING GROUND LEVEL BELOW THE CONCRETE PULL BOX BOTTOM LEVEL.
100
A SECTION B SECTION
- - FRAME HEIGHT: 220mm
LENGTH 10XØ110
NOTES FOR PROTECTION OF UNDERGROUND
25
WORKING PIT 063780052
970
NATURAL SOIL FILLING TO THE HEIGHT: 70mm CONCRETE:-
25 NORMAL GROUND LEVEL FOR FRAME
IT IS MANDATORY TO PROTECT ALL UNDERGROUND
COMPACTION SEE NOTE 14 063780058
CHAMFER CONCRETE STRUCTURES AS PER THE
--
HEIGHT: 5mm
FRAME WITH INLETS BASE PLATE
DETAIL-Z BASE PLATE 063780054
SPECIFICATION WHICH INCLUDES THE FOLLOWING.
NTS 1215
11. OUTER SURFACE OF WALLS OF ALL PULL BOXES
OVERALL HEIGHT: 970mm
70
150
GEOTEXTILE
5
607 607 AND CABINETS.
Ø75mm HOLE 150 150 308 308 150 150 Ø75mm HOLE ISOMETRIC VIEW 12. BOTTOM SURFACE OF BASES OF ALL PULL BOXES /
FOR PIPE FIXING (3+3 Nos.) 110mmØ SOAKAGE LAYER OF 150mm Min. CABINETS.
FOR PIPE FIXING 50mmØ 75mmØ (STONE SIZES 8-24mm)
1215 (5 Nos.) 13. OUTER SURROUNDING SURFACE OF ALL CABINET/
D SECTION
-
150 915 150 KOISK BASES INCLUDING BOTTOM.
150
55
+GRAVEL
380
75 550
150
55
2"Ø DRAIN PIPE 212 DENSITY OF 95%.
150
SEE NOTE 10
960 -FOR NON-LOAD BEARING AREAS (UNPAVED AREAS):
Ø75mm HOLE 2"Ø DRAIN PIPE 800 BACKFILL LAYERS SHALL NOT EXCEED 15cm
150
400
550
COMPACTION SEE NOTE 14
C SECTION -
- PLAN NUMBER OF PULL BOXES/CABINETS, AS RANDOMLY
ELECTED BY THE ENGINEER.
15. THE POLYCARBONATE PULL BOX SHALL NOT BE
PRECAST CONCRETE PULL BOX GEOTEXTILE
INSTALLED ON UNPAVED AREAS WHERE VEHICLE
ACCESS IS EXPECTED; THE PRECAST CONCRETE
SOAKAGE LAYER OF 150mm Min.
(STONE SIZES 8-24mm) PLAN PULL BOX INSTALLED INSTEAD IN SUCH
D SECTION
- FOR ASPHALT ROAD / PAVEMENT
SITUATIONS.
155
M.C.C
40
ممت
155
40
M.C.C
تمم
460
570
EPDM
RUBBER SEAL 915X460 DUCTILE M10 SS ANTI THEFT D-BOLT -6 NOS
100
EN 124-2 D400
SECTION-F-F
915
1025
PLAN COVER & FRAME