You are on page 1of 9

TECHNICAL DATA PANEL ELEKTRIK FIRE PUMPS

AXIA

Technical Data
INPUT-POWER 380V - 415V
P motor KW 37 45 55 75 110 160 200 280
P motor HP 49.6 60.5 73,8 100.6 147.5 214.6 268.2 375.5
Ampere 70.3 85.5 104.5 142.4 208.9 303.9 379.8 531.8
Main Kontaktor 41 50 61 83 121 176 220 308
Star Kontaktor 24 29 35 48 70 102 127 178
DeltaKontaktor 41 50 61 83 121 176 220 308
Breaker 88 107 131 179 262 380 475 665

FEATURE
VISUAL ALARM
1.Power Lamp 1.Motor Overload
2.Alarm Lamp 2.Phase Failure
3.Motor run Lamp
3.Phase Revesal
4.Motor Off Lamp
5.A.V Digital Meter 4.Under Voltage
6.Selektor switch MOA 5.Over Voltage
7.Tombol Start
8.Tombol Silent
9.Buzzer
10.Remote Start
11.Emergency to Run
TIMERS OPERATOR
1.Minimum run period timer 1. MANUAL-OFF-AUTO Switch
2.Sequential start timer 2. Start and stop push button

RELAY
INPUT
I1 Relay PFR OUTPUT
I2 Selector Switch Manual Q1 Coil K1 (A1 A2
I3 Selector Switch Auto Q2 Coil K2 (A1 A2)
I4 Push Bottom Start Q3 Coil K3 (A1 A2)
I5 Push Bottom Stop Q4 Alarm Lamp
I6 Alarm Silent Q5 Motor Run Lamp
I7 Remote Start Q6 Motor Stop Lamp
I8 Emergency to Run Q7 Buzzer
I9 Presure switch cut in
MODE STARTING
1.Manual
2.Auto
3.Remot Start
4.Handle Emergency to Start
AXIA
FLOW CHART ELEKTRIK PUMPS
AXIA

FLOW CHART PENGOPERASIAN


PANEL ELEKTRIK
“ MODE MANUAL “

Breaker “ on ”
MCB Control “ on “

Lampu Power “ on ”
Lampu Stop “on “
Digital Ampere Meter “on ”
PFR “ on “
Smart Relay “ Aktif “

KONDISI “ Stand by “

Pilih
Mode Selector Switch
“ Manual “

Tekan
“ PB. Start “

Lampu Stop “ off “


Lampu Run “ on “
Koil K1 “ on “
Koil K3 “ on “
POMPA RUN STAR
Timer 1 (5s)
Koil K3 ” off ”
Koil K2 “ on “
POMPA RUN DELTA
Koil K3 “ on “
Timer 2 (3s) “ aktif “
Lampu Stop “ on “
Tekan
Lampu Run “ off “
“ PB. Stop “
Koil K1, K2, K3 “ off “
POMPA STOP
FLOW CHART ELEKTRIK PUMPS
AXIA

FLOW CHART PENGOPERASIAN


PANEL ELEKTRIK
“ MODE AUTO “

Breaker “ on ”
MCB Control “ on “

Lampu Power “ on ”
Lampu Stop “on “
Digital Ampere Meter “on ”
PFR “ on “
Smart Relay “ Aktif “

KONDISI “ Stand by “

Pilih
Mode Selector Switch
“ Auto “

“ < CUT IN “ Kondisi “ > CUT IN “


“ Presure “

Lampu Stop “ off “


“ PRESURE DROP “
Lampu Run “ on “
PS. Cut in “ close “
Koil K1 “ on “
Lampu Stop “ off “
Koil K3 “ on “
Lampu Run “ on “
POMPA RUN STAR
Koil K1 “ on “
Timer 1 (5s)
Koil K3 “ on “
Koil K3 ” off ”
POMPA RUN STAR
Koil K2 “ on “
Timer 1 (5s)
POMPA RUN DELTA
Koil K3 ” off ”
Koil K2 “ on “
POMPA RUN DELTA
Tekan
“ PB. Stop “

Timer 2 (3s) “ aktif “


Lampu Stop “ on “
Lampu Run “ off “
Koil K1, K2, K3 “ off “
POMPA STOP
FLOW CHART ELEKTRIK PUMPS
AXIA

FLOW CHART PENGOPERASIAN


PANEL ELEKTRIK
“ REMOTE START “

Breaker “ on ”
MCB Control “ on “

Lampu Power “ on ”
Lampu Stop “on “
Digital Ampere Meter “on ”
PFR “ on “
Smart Relay “ Aktif “

KONDISI “ Stand by “

KONDISI
Mode Selector Switch
“ Manual / Auto “

Tekan
PB. Remote Start “ on “

Lampu Stop “ off “


Lampu Run “ on “
Koil K1 “ on “
Koil K3 “ on “
POMPA RUN STAR
Timer 1 (5s)
Koil K3 ” off ”
Koil K2 “ on “
POMPA RUN DELTA

Timer 2 (3s) “ aktif )


Lampu Stop “ on “
Tekan Lampu Run “ off “
PB. Remote Start “ off “ Koil K1, K2, K3 “ off “
POMPA STOP
FLOW CHART ELEKTRIK PUMPS
AXIA

FLOW CHART PENGOPERASIAN


PANEL ELEKTRIK
“ EMERGENCY TO RUN “

Breaker “ on ”
MCB Control “ on “

Lampu Power “ on ”
Lampu Stop “on “
Digital Ampere Meter “on ”
PFR “ on “
Smart Relay “ Aktif “

KONDISI “ Stand by “

KONDISI
Mode Selector Switch
“ Manual / Auto “

Tarik
Handle Emergency to Run

Lampu Stop “ off “


Lampu Run “ on “
Koil K1 “ on “
Koil K3 “ on “
POMPA RUN STAR
Timer 1 (5s)
Koil K3 ” off ”
Koil K2 “ on “
POMPA RUN DELTA

Timer 2 (3s) “ aktif)


Lampu Stop “ on “
Tekan Lampu Run “ off “
Handle Emergency to Run Koil K1, K2, K3 “ off “
POMPA STOP
FLOW CHART ELEKTRIK PUMPS
AXIA

FLOW CHART PENGOPERASIAN


PANEL ELEKTRIK
“ FUNGSI ALARM “

Breaker “ on ”
MCB Control “ on “

Kondisi
“ Pompa Run “
Auto / Manual

“ ALARM AKTIF “
“ ALARM AKTIF “
1.Motor Overload
1.Motor Overload
2.Phase Failure
2.Phase Failure
3.Phase Revesal
3.Under Voltage
4.Under Voltage
4.Over Voltage
5.Over Voltage

Kondisi
TEKAN
“ Pompa Run “
PB Silent
Lampu Alarm “ on “
Buzzer “ off “
Buzzer “ on “

Tekan
“ PB. Stop “

PILIH
Breaker “ off ”
MCB Control “ off “

“ PERBAIKAN “
WIRING ELEKTRIK PUMPS
AXIA

INPUT OUTPUT
I1 Relay PFR TERMINAL CABLE
I2 Selector Switch Manual Q1 Coil K1 (A1 A2)
I3 Selector Switch Auto Q2 Coil K2 (A1 A2) 1 TO PUMP ( U1.V1.W1.U2.V2.W2 )
I4 Push Bottom Start Q3 Coil K3 (A1 A2) 2 POWER INPUT ( L1.L2.L3.N )
I5 Push Bottom Stop Q4 Alarm Lamp 3 REMOT START ( 1.2 )
I6 Alarm Silent Q5 Motor Run Lamp 4 PRESURE SWITCH ( NO.C )
I7 Remote Start Q6 Motor Stop Lamp
I8 Emergency to Run Q7 Buzzer
I9 Presure switch cut in
PANEL ELEKTRIK FIRE PUMPS
AXIA
POWER

PILOT LAMP
RUN ALARM ALARM

A.V METER

M O A

PUSH SELEKTOR
BOTTOM START SILENT STOP SWITCH

PFR
BUZZER

SMART
RELAY

MCB 3ph MAGNIT


CONTACTOR

MCB 1ph

TERMINAL
L1 L2 L3 N
INCOMING
POWER
U1 V1 W1
TO
U2 V2 W2

MOTOR/PUMP
12
REMOT
START
13 NO
PRESURE
SWITCH
C
BLOCK

You might also like