FROM MAIN WATER SUPPLY

Ø100X65X65 FDC Ø100X65X65 FDC

FOR CONTINUATION REFER TO DWG No. 504415-00-DRG-FI-0012


17
NON-MODULATE FLOAT VALVE 22 ∅200 FIRE HEADER ∅200 FIRE HEADER ∅200 FIRE HEADER 22

∅20

18 14
∅200 ∅200 ∅50
FI
S
∅150 ∅150
18 18

S
5

S
S 5 S 5
19 Ø100x65x65 FDC
15 M
+4.00 NON-MODULATE FLOAT VALVE CLOSE Ø100x65x65 FDC

19 19 13
13 13 Ø100x65x65 FDC CLIENT

Ø150 F (FOR WET PIPE TO SERVE PRE ACTION SYSTEM)

Ø150 F (FOR WET PIPE TO SERVE PRE ACTION SYSTEM)


7
∅20 STT GDC (Thailand)
12
10
12
10
12
Company Limited
FIRE WATER TANK 2
FIRE WATER TANK 1

10
∅15 ∅15 ∅15 175 อาคารสาธรซิตี1 ทาวเวอร์ ชัน
1 13/1
+3.40 NON-MODULATE FLOAT VALVE OPEN 8 8 ห้องเลขที 1308 ถนนสาทรใต้

Ø150 F (FOR EXTERNAL FIRE HYDRANT)


01-01-FP-001 01-01-FP-002 01-01-JP-001
324 M3

335 M3

3 แขวงทุง่ มหาเมฆ เขตสาทร กรุงเทพมหานคร 10120

Ø150 F (FOR FIRE HOSE SYSTEM)

Ø150 F (FOR FIRE HOSE SYSTEM)

Ø150 F (FOR FIRE HOSE SYSTEM)

Ø150 F (FOR FIRE HOSE SYSTEM)


M 1 M 2 M ENGINEER
9
9 9

19 19 19
11 11 11
PS CONTROLLER PS CONTROLLER PS CONTROLLER
21 21 21
5 5 5

S
20 20 20 บริษทั ออเรคอน คอนซัลติง1 (ประเทศไทย) จํากัด
เลขที 9 อาคารภคินท์ ชัน
1 11 ห้อง 1101 ถ.รชั ดาภิเษก
21 ELECTRICAL ∅250 21 ELECTRICAL ∅250 21 ELECTRICAL ∅65
แขวงดินแดง เขตดินแดง กรุงเทพมหานคร 10400
POWER SUPPLIED POWER SUPPLIED POWER SUPPLIED
ผูต
้ รวจสอบรายการคํานวณโครงสร้าง
5 GROUP OF SIGNALS GROUP OF SIGNALS GROUP OF SIGNALS นิวตั กอสุราษฎร์ วย. 1297
TO BE REMOTED TO BE REMOTED TO BE REMOTED

Ø250 S
CONTROLLER IN POSITION CONTROLLER IN POSITION CONTROLLER IN POSITION 24 STRUCTURAL ENGINEER
Ø250 S
"AUTO" "AUTO" "AUTO" วีรพจน์ ปิ ตุปกรณ์ วุฒิ วย. 1488

S
PUMP OPERATING PUMP OPERATING PUMP OPERATING พิสฐิ ยิงมโนกิจ สย. 8086
FAIL TO START ∅250 FIRE HEADER FAIL TO START ∅250 FIRE HEADER FAIL TO START จิรภทั ร แย้มทิม สย. 12461
Ø200 F
17
+0.00 CIVIL ENGINEER
GROUND FLOOR 150 150
รสสุคนธ์ สรรพกิจกําจร สย. 9225
ชัยวุฒิ ชัยธินิกรรณ ภย. 21903
23 23
ฐาปกรณ์ สิทธิบรรณ์ ภย. 42639

FIRE PUMPS AND JOCKEY PUMP DIAGRAM


SANITARY ENGINEER
with control panel วิรชั จารุวงศ์วณิชย์ วส. 79
ท ัศนี ย์ ผาติเวทย์ สส. 183
PRE-ACTION VALVE DETAILS (BASE DESIGN) ศิรวิทธ์ เทพสุวรรณ สส. 438

CONTROL CONTROL วิชณา เปี ยมปิ ติรตั น์ ภส. 3002


ITEM NO. DESCRIPTIONS ITEM NO. DESCRIPTIONS VALVE NAME VALVE SIZE LOCATION PROTECTION AREA REMARK VALVE NAME VALVE SIZE LOCATION PROTECTION AREA REMARK
PANEL PANEL เอกพันธุ์ วรวานิช ภส. 3287
ดลยา แสงจันทร์ศรี ภส. 3675
1 MOTOR DRIVEN FIRE PUMP 1 (01-01-FP-001) 17 HEADER 01-01-PACV-001 Ø150 FIRE PUMP ROOM AT GROUND FLOOR PARKING AREA AND FUEL PUMP ROOM SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-01-PACP-001 01-04-PACV-001 Ø150 FIRE SERVICE ROOM 1 AT 4th FLOOR COMMON AREA SHALL BE INSTALLED WITH
- QUICK OPENING DEVICE 01-04-PACP-001
ELECTRICAL ENGINEER
2 MOTOR DRIVEN FIRE PUMP 2 (01-01-FP-002) 18 BUTTERFLY VALVE. W/SUPERVISORY SWITCH 01-01-PACV-002 Ø100 FIRE PUMP ROOM AT GROUND FLOOR COMMON AREA 1 - 01-01-PACP-002 01-04-PACV-002 Ø150 FIRE SERVICE ROOM 1 AT 4th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-04-PACP-002 วีรยุทธ กิงแก้ว วฟก. 944
3 JOCKEY PUMP (01-01-JP-001) ∅15 CHECK VALVE WITH 3/32" ORIFICE IN CLAPPER. 01-01-PACV-003 Ø100 FIRE PUMP ROOM AT GROUND FLOOR COMMON AREA 2 SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-01-PACP-001 01-04-PACV-003 Ø150 FIRE SERVICE ROOM 1 AT 4th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-04-PACP-003
19 จิตวิ ฒ
ั น์ เชาว์ประมวลกุล สฟก. 4644
5 OS & Y GATE VALVE WITH SUPERVISORY SWITCH. 20 ∅15 TEE WITH CAP. 01-01-PACV-004 Ø100 FIRE PUMP ROOM AT GROUND FLOOR PUMP ROOM AND DOMESTIC PUMP ROOM - 01-01-PACP-004 01-05-PACV-001 Ø150 FIRE SERVICE ROOM 1 AT 5th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-05-PACP-001 ธํารงศักดิ ' จันทรักษ์ สฟก. 5491
6 ∅20 CASING RELIEF VALVE FOR MOTOR DRIVEN FIRE PUMP 21 ∅15 GLOBE VALVE WITH CAP. 01-02-PACV-001 Ø150 FIRE SERVICE ROOM AT 2nd FLOOR COMMON AREA - 01-02-PACP-001 01-05-PACV-002 Ø150 FIRE SERVICE ROOM 1 AT 5th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-05-PACP-002 อภิธาน ธาราจันทร์ ภฟก. 47567
7 ∅20 CASING RELIEF VALVE FOR JOCKEY PUMP. 22 AUTOMATIC AIR VENT WITH SEPARATED VALVE. 01-02-PACV-002 Ø80 FIRE SERVICE ROOM AT 2nd FLOOR GENSET AREA - 01-02-PACP-002 01-05-PACV-003 Ø150 FIRE SERVICE ROOM 1 AT 5th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-05-PACP-003 ยุวดี เอมอร่าม ภฟก. 42524
8 AUTOMATIC AIR RELEASE VALVE WITH SEPARATED VALVE. 23 SUCTION VORTEX PLATE 1200 mm. x 1200 mm. 01-02-PACV-003 Ø32 FIRE SERVICE ROOM AT 2nd FLOOR UPS/BATTERY ROOM A1 - 01-02-PACP-003 01-06-PACV-001 Ø150 FIRE SERVICE ROOM 1 AT 6th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-06-PACP-001 นลัทธวลั สุทธิพน
ั ธุ์ ภฟก. 40209
9 SUCTION PRESSURE GAUGE (DIAL RANGE-15 TO 50 PSI) 24 ALARM VALVE 01-02-PACV-004 Ø32 FIRE SERVICE ROOM AT 2nd FLOOR UPS/BATTERY ROOM A2 - 01-02-PACP-004 01-06-PACV-002 Ø150 FIRE SERVICE ROOM 1 AT 6th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-06-PACP-002 MECHANICAL ENGINEER
10 DISCHARGE PRESSURE GAUGE (DIAL RANGE 0 TO 500 PSI) 01-02-PACV-005 Ø32 FIRE SERVICE ROOM AT 2nd FLOOR UPS/BATTERY ROOM B1 - 01-02-PACP-005 01-06-PACV-003 Ø150 FIRE SERVICE ROOM 1 AT 6th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-06-PACP-003 สุชาติ ศิรท
ิ าวรจันทร์ วก. 848
25 PRE-ACTION VALVE
ECCENTRIC SUCTION REDUCER. 01-02-PACV-006 Ø40 FIRE SERVICE ROOM AT 2nd FLOOR UPS/BATTERY ROOM B2 - 01-02-PACP-006 01-07-PACV-001 Ø150 FIRE SERVICE ROOM 1 AT 7th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-07-PACP-001 ชลิต ทวีสน
ิ ฟู สก. 4142
11 PRE-ACTION VALVE WITH QUICK OPENING DEVICE
25
CONCENTRIC DISCHARGE INCREASER. 01-02-PACV-007 Ø80 FIRE SERVICE ROOM AT 2nd FLOOR CHILLER PLANT - 01-02-PACP-007 01-07-PACV-002 Ø150 FIRE SERVICE ROOM 1 AT 7th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-07-PACP-002 พณฉัตร เชียววุฒก
ิ ุล ภก. 31802
12

13 CHECK VALVE 01-02-PACV-008 Ø150 FIRE SERVICE ROOM AT 2nd FLOOR OFFICE AREA AND NOC ROOM - 01-02-PACP-008 01-07-PACV-003 Ø150 FIRE SERVICE ROOM 1 AT 7th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-07-PACP-003
- ARCHITECTS
14 FLOW INDICATED SENSOR (50-200% OF 1250 GPM) 01-03-PACV-001 Ø80 FIRE SERVICE ROOM 1 AT 3rd FLOOR GENSET AREA - 01-03-PACP-001 01-08-PACV-001 Ø80 AT ROOF FLOOR COMMON AREA AND GENERATOR 01-08-PACP-001
FLOW METER (50-200% OF 1250 GPM) -
15 01-03-PACV-002 Ø100 FIRE SERVICE ROOM 1 AT 3rd FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-03-PACP-002 01-08-PACV-002 Ø100 AT ROOF FLOOR COMMON AREA AND GENERATOR 01-08-PACP-002
01-03-PACV-003 Ø150 FIRE SERVICE ROOM 1 AT 3rd FLOOR DATA HALL B (EAST SIDE) SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-03-PACP-003

01-03-PACV-004 Ø65 FIRE SERVICE ROOM 2 AT 3rd FLOOR BATTERY ROOM A1 - 01-03-PACP-004 บริษทั สตีเฟน เจ. ลีช อาร์คเิ ทคส์ จํากัด
01-03-PACV-005 Ø65 FIRE SERVICE ROOM 2 AT 3rd FLOOR BATTERY ROOM B1 - 01-03-PACP-005 62 อาคารมิลเลเนี ย ชัน
1 10 ซอยหลังสวน ถนนเพลินจิต
แขวงลุมพินี เขตปทุมวน ั กรุงเทพมหานคร 10330
01-03-PACV-006 Ø65 FIRE SERVICE ROOM 2 AT 3rd FLOOR BATTERY ROOM A2 - 01-03-PACP-006
ARCHITECT
01-03-PACV-007 Ø65 FIRE SERVICE ROOM 2 AT 3rd FLOOR BATTERY ROOM B2 - 01-03-PACP-007
NOTE : ฐากูร สุวรรณสุขุม ว-สถ 603
1. ALL FIRE PUMP FITTINGS ITEM 5 THRU 16 SHALL BE FURNISHED WITH FIRE PUMP MANUFACTURER.
เฉลิมชัย ประยูรโต ส-สถ 3222
2. THE INSTALLATION OF CENTRIFUGAL FIRE PUMPS SYSTEM SHALL BE FABRICATED, INSTALLED, TESTED AND PLACED
INTO AUTOMATIC SERVICE IN ACCORDANCE WITH NFPA 20 & THE SPECIFICATION.
3. THE PRESSURE SENSING PIPE AND FITTING SHALL BE MADE OF STAINLESS STEEL PIPE SCHEDULE 80 AND CLASS 300. PRE-ACTION VALVE DETAILS TABLE (OPTION 1 AT LEVEL 4 ONLY)
4. FIRE PIPE AND FITTING IN FIRE PUMP ROOM SHALL BE HOT DIPPED GALVANIZED STEEL, SCHEDULE 40 SEAMLESS.
CONTROL REV DATE DESCRIPTION APP
VALVE NAME VALVE SIZE LOCATION PROTECTION AREA REMARK
PANEL A 22-03-2019 60%DD SA
B 06-05-2019 ISSUE FOR TENDER SA
C 30-05-2019 REVISED SA
01-04-PACV-001 Ø80 FIRE SERVICE ROOM 1 AT 4th FLOOR GENSET AREA - 01-04-PACP-001 D 01-07-2019 ADDENDUM 4 SA
E 17-07-2019 ADDENDUM 5 SA
01-04-PACV-002 Ø150 FIRE SERVICE ROOM 1 AT 4th FLOOR COMMON AREA SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-04-PACP-002 F 03-09-2019 PTA2 - 100% TENDER DRAWINGS SA
G 08-10-2019 ISSUE FOR CONSTRUCTION SA
01-04-PACV-003 Ø150 FIRE SERVICE ROOM 1 AT 4th FLOOR DATA HALL A (WEST SIDE) SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-04-PACP-003

01-04-PACV-004 Ø150 FIRE SERVICE ROOM 1 AT 4th FLOOR DATA HALL A RAISED FLOOR (WEST SIDE) SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-04-PACP-004

01-04-PACV-005 Ø150 FIRE SERVICE ROOM 1 AT 4th FLOOR DATA HALL B (EAST SIDE) SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-04-PACP-005

01-04-PACV-006 Ø150 FIRE SERVICE ROOM 1 AT 4th FLOOR DATA HALL B RAISED FLOOR (EAST SIDE) SHALL BE INSTALLED WITH QUICK OPENING DEVICE 01-04-PACP-006
01-04-PACV-007 Ø65 FIRE SERVICE ROOM 2 AT 4th FLOOR BATTERY ROOM A1 - 01-04-PACP-007 SCALE SIZE FOR
01-04-PACV-008 Ø65 FIRE SERVICE ROOM 2 AT 4th FLOOR BATTERY ROOM B1 - 01-04-PACP-008 1 : 100 A0 CONSTRUCTION
Filename: BIM 360://504415 - Project - Terra/504415-FAC-CS-00-001.rvt

01-04-PACV-009 Ø65 FIRE SERVICE ROOM 2 AT 4th FLOOR BATTERY ROOM A2 - 01-04-PACP-009 DRAWN APPROVED
01-04-PACV-010 Ø65 FIRE SERVICE ROOM 2 AT 4th FLOOR BATTERY ROOM B2 - 01-04-PACP-010 SK DATE

DESIGNED
WP
CHECKED
ST MM
PROJECT
อาคารศูนย์เก็บข้อมูลอิเล็คทรอนิคส์
สูง 8 ชัน
1 จํานวน 1 หลัง
ซอยรามคําแหง 28 ถนนรามคําแหง แขวงหัวหมาก เขต
บางกะปิ กรุงเทพมหาคร 10240
TITLE
FIRE PUMP SCHEMATIC
Office:
Plot Date: 10/8/2019 6:15:16 PM

DRAWING NUMBER
PRINT IN COLOUR REV

504415-00-DRG-FI-0013 G