Professional Documents
Culture Documents
B.E.
2Nos. 50X6 mm GI. Strip
B.E.
OUTGOING FEEDER FOR FOR CCS (30kW) MCCB
Gurugram, Haryana-122102
CCS CHARGER-1 (30KW) 4Cx25 Sq.mm CU.
4Cx35 Sq.mm AL.
XLPE CABLE
4P
4P
OUTGOING FEEDER FOR FOR CCS (30kW) MCCB UN.AR.XLPE CABLE
100A
100A
MCCB
MCCB
CCS CHARGER-1 (30KW) 4Cx25 Sq.mm CU.
4Cx35 Sq.mm AL.
XLPE CABLE
4P
4P
UN.AR.XLPE CABLE OUTGOING FEEDER FOR FOR CCS (30kW) MCCB
100A
100A
MCCB
MCCB
CCS CHARGER-2 (30KW) 4Cx25 Sq.mm CU.
4Cx35 Sq.mm AL.
XLPE CABLE
4P
4P
FOR CCS (30kW) MCCB UN.AR.XLPE CABLE
100A
100A
MCCB
MCCB
CCS CHARGER-2 (30KW) 4Cx25 Sq.mm CU.
4Cx35 Sq.mm AL.
XLPE CABLE
4P
4P
UN.AR.XLPE CABLE OUTGOING FEEDER FOR FOR CCS (30kW) MCCB
100A
100A
MCCB
MCCB
CCS CHARGER-3 (30KW) 4Cx25 Sq.mm CU.
4Cx35 Sq.mm AL.
4P
4P
FOR CCS (30kW) MCCB UN.AR.XLPE CABLE
100A
100A
MCCB
MCCB
CCS CHARGER-3 (30KW) 4Cx25 Sq.mm CU.
4Cx35 Sq.mm AL.
XLPE CABLE
4P
4P
UN.AR.XLPE CABLE OUTGOING FEEDER FOR FOR CCS (60kW) MCCB
100A
100A
MCCB
MCCB
CCS CHARGER-4 (60KW) 4Cx35 Sq.mm CU.
4Cx70 Sq.mm AL.
AR. XLPE CABLE
4P
4P
OUTGOING FEEDER FOR FOR CCS (30kW) MCCB UN.AR.XLPE CABLE
160A
160A
MCCB
MCCB
CCS CHARGER-4 (30KW) 4Cx25 Sq.mm CU.
4Cx35 Sq.mm AL.
XLPE CABLE
4P
4P
UN.AR.XLPE CABLE OUTGOING FEEDER FOR FOR CCS (60kW) MCCB
100A
100A
MCCB
MCCB
CCS CHARGER-5 (60KW) 4Cx35 Sq.mm CU.
4Cx70 Sq.mm AL.
AR. XLPE CABLE
4P
4P
OUTGOING FEEDER FOR FOR CCS (30kW) MCCB UN.AR.XLPE CABLE
160A
160A
MCCB
MCCB
CCS CHARGER-5 (30KW) 4Cx25 Sq.mm CU.
4Cx35 Sq.mm AL.
XLPE CABLE
4P
4P
UN.AR.XLPE CABLE SPARE FOR
100A
100A
MCCB
MCCB
FAST CHARGER
4P
OUTGOING FEEDER FOR FOR CCS (30kW) MCCB
160A
MCCB
CCS CHARGER-6 (30KW) 4Cx35 Sq.mm AL.
MFM
4Cx25 Sq.mm CU.
XLPE CABLE
4P
4P
UN.AR.XLPE CABLE
100A
100A
MCCB
MCCB
MCB
630/5A
OUTGOING FEEDER FOR FOR CCS (30kW) MCCB
CL-0.5,10VA
CCS CHARGER-7 (30KW) 4Cx35 Sq.mm AL.
CL-0.5
630/5A
4Cx25 Sq.mm CU.
XLPE CABLE
4P
4P
UN.AR.XLPE CABLE
100A
100A
MCCB
MCCB
MCB
OUTGOING FEEDER FOR FOR CCS (30kW) MCCB
MFM
MCCB
4Cx35 Sq.mm AL.
CL-0.5
CCS CHARGER-8 (30KW)
630A 4P
200/5A
4Cx25 Sq.mm CU.
O/C,S/C,EF
MP BASED
MCB
XLPE CABLE
4P
4P
UN.AR.XLPE CABLE
100A
100A
MFM
MCCB
MCCB
EM.
FOR CCS (30kW) MCCB
R Y B
OUTGOING FEEDER FOR
ON OFF TRIP
CCS CHARGER-9 (30KW) 4Cx25 Sq.mm CU.
4Cx35 Sq.mm AL.
OUTGOING FEEDER-1 FOR SLOW CHARGER
XLPE CABLE
4P
4P
UN.AR.XLPE CABLE
100A
100A
MCCB
FOR SLOW CHARGER
MCCB
CLIENT:
4Cx6 Sq.mm CU. 4Cx16 Sq.mm AL.AR
4P
(9.9 KW)
4P
63A
UN.AR.XLPE CABLE XLPE FRLS CABLE
63A
MCB
MCB
OUTGOING FEEDER FOR FOR CCS (30kW) MCCB
CCS CHARGER-10 (30KW) 4Cx25 Sq.mm CU. 4Cx35 Sq.mm AL.
OUTGOING FEEDER-2 FOR SLOW CHARGER
XLPE CABLE
PROJECT :
4P
4P
UN.AR.XLPE CABLE
100A
100A
MCCB
FOR SLOW CHARGER
MCCB
4Cx6 Sq.mm CU. 4Cx16 Sq.mm AL.AR
4P
(9.9 KW)
4P
63A
UN.AR.XLPE CABLE XLPE FRLS CABLE
63A
MCB
MCB
OUTGOING FEEDER FOR FOR CCS (30kW) MCCB
CCS CHARGER-11 (30KW) 4Cx25 Sq.mm CU. 4Cx35 Sq.mm AL.
OUTGOING FEEDER-3 FOR SLOW CHARGER
XLPE CABLE
4P
4P
UN.AR.XLPE CABLE
100A
100A
MCCB
FOR SLOW CHARGER
MCCB
4Cx6 Sq.mm CU. 4Cx16 Sq.mm AL.AR 4P
(9.9 KW)
4P
63A
63A
MCB
MCB
SPARE FOR
FAST CHARGER
OUTGOING FEEDER-4 FOR SLOW CHARGER
4P
160A
MCCB
FOR SLOW CHARGER 4Cx6 Sq.mm CU. 4Cx16 Sq.mm AL.AR
4P
(9.9 KW)
4P
63A
63A
MCB
MCB
GURGAON
OUTGOING FEEDER-5 FOR SLOW CHARGER
FOR SLOW CHARGER 4Cx6 Sq.mm CU. 4Cx16 Sq.mm AL.AR
4P
(9.9 KW)
4P
63A
63A
MCB
MCB
OUTGOING FEEDER-6 FOR SLOW CHARGER
FOR SLOW CHARGER 4Cx6 Sq.mm CU. 4Cx16 Sq.mm AL.AR
MFM
4P
(9.9 KW) 4P
63A
MCB
MCB
FOR SLOW CHARGER
1000/5A
OUTGOING FEEDER-7
FOR SLOW CHARGER
CL-0.5,10VA
4Cx6 Sq.mm CU. 4Cx16 Sq.mm AL.AR
CL-0.5
800/5A
4P
(9.9 KW)
4P
63A
MCB
S P A R E FOR
MCB
SLOW CHARGER
MFM
MCCB
CL-0.5
400/5A
1000A 4P
4P
MCB
O/C,S/C,EF
MP BASED
63A
MCB
MFM
EM.
S P A R E FOR
R Y B
ON OFF TRIP
SLOW CHARGER
4P
63A
OUTGOING FEEDER-1
FOR SLOW CHARGER 4Cx6 Sq.mm CU. 4Cx16 Sq.mm AL.AR
4P
(9.9 KW)
63A
4P
UN.AR.XLPE CABLE XLPE FRLS CABLE
MCB
63A
S P A R E FOR
MCB
SLOW CHARGER
4P
63A
OUTGOING FEEDER-2
FOR SLOW CHARGER 4Cx6 Sq.mm CU. 4Cx16 Sq.mm AL.AR
4P
(9.9 KW)
63A
4P
UN.AR.XLPE CABLE XLPE FRLS CABLE
MCB
63A
MCB
OUTGOING FEEDER-3 FOR SLOW CHARGER
FOR SLOW CHARGER 4Cx6 Sq.mm CU. 4Cx16 Sq.mm AL.AR
4P
(9.9 KW)
63A
MCB
63A
MCB
OUTGOING FEEDER-4 FOR SLOW CHARGER
4P
(9.9 KW)
63A
4P
UN.AR.XLPE CABLE XLPE FRLS CABLE
MCB
63A
MCB
Strip
4P
(9.9 KW)
63A
4P
UN.AR.XLPE CABLE XLPE FRLS CABLE
MCB
63A
MCB
OUTGOING FEEDER-6 FOR SLOW CHARGER
R
4P
CKD.
DRN.
(9.9 KW)
63A
4P
UN.AR.XLPE CABLE XLPE FRLS CABLE
MCB
63A
MCB
SIGN.
Y
PACK
B
2Nos. 50X6 mm GI.
110Vdc
SCALE
OUTGOING FEEDER-7
POWER
APFC PANEL
4P
(9.9 KW)
63A
4P
B.E.
63A
MCB
MCB
3 Ph. AC SPD TYPE
11kV HT XLPE AL.CABLE
1R, 3C x300 sqmm
WTI
800 KVA
6A,SP
FP
OUTGOING FEEDER-8
1000A
AN COOLING
(50KA)
MCCB,
IMPEDANCE-5%,
SF6
4P
(9.9 KW)
63A
3 WAY
4P
UN.AR.XLPE CABLE
3CT.3PT
63A
HV-DELTA,LV STAR
MCB
MFM
MFM
CORE-1
PROTECTION.
6A,SP
CL-0.5s,10VA
H.T METERING
CUBICAL WITH
3, 80-100/5-5A
4P
(9.9 KW)
63A
630A,TP
4P
UN.AR.XLPE CABLE XLPE FRLS CABLE
MCB
63A
MCB
CT
BSES
PUNEET
OUTGOING FEEDER-10
1:250
3Rx4Cx300 Sq.mm AL. AR.
1250/5A
SF6
VCB
(9.9 KW)
IDMT
63A
N.E.
SUPPLY FROM
4P
63A
MCB
Electrical panel -2
CL-0.5S,15VA
TTB
11000/110V
PLC
A
OUTGOING FEEDER-11
630A,TP
N.E.
KWH
(9.9 KW)
63A
4P
63A
MCB
EDO,25ka for 3sec.
ANIL SHARKI
PACK
8 WINDOW
220 Vac
POWER
PT 100VA,CL-05 PTR
11KV/1.732,110/1.732
R
ANNUNCIATOR
4R, 4Cx300 SQ.MM AL.
OUTGOING FEEDER-12
230V,5A SOCKET 1NOS.
230V,15A SOCKET 1NOS.
32
46
TAPPING FROM MAIN MCCB
H
4P
ARM. LT XLPE FRLS CABLE
(9.9 KW)
Strip
63A
Y B
4P
UN.AR.XLPE CABLE
IP 55
63A
HOOTER
MCB
IP 65
64R
PLC
ANNUNCIATOR
PHASE IND.
ON OFF TRIP
SWITCH
1R, 3C x300 sqmm
EMERGENCY
4P
(9.9 KW)
63A
4P
63A
MCB
BODY EARTHING
1R, 3C x300 sqmm
REV.
FOR SLOW CHARGER
IP 55
OUTGOING FEEDER-14
DGN.
DATE
FOR SLOW CHARGER 4Cx6 Sq.mm CU. 4Cx16 Sq.mm AL.AR
4P
APPD.
(9.9 KW)
63A
11kV HT XLPE Al.CABLE
4P
63A
MCB
2Nos. 50X6 mm CU.
(9.9 KW)
63A
4P
63A
MCB
R0
(9.9 KW)
63A
HT
4P
63A
MCB
(9.9 KW)
63A
4P
63A
MCB
(9.9 KW)
63A
GAURAV
4P
63A
MCB
MCB
SPARE FOR
SLOW CHARGER
4P
63A
MCB
SPARE FOR
SLOW CHARGER
4P
63A
MCB
SHT. No.
DWG. NO:
No. OF SHT.
07
7 OF 10
GFC DRAWING
EL-SLD-8
R0
KEY PLAN:-
REV. NO.
VARY.
LAT.-28.53757115617268,
LONG.-77.28756993859945
BASEMENT-2.
BASEMENT-3.
PER ACTUAL .
46
32
H3
H2
H1
MFM
DETAIL ENGINEERING.
(MCB)
(MCCB)
REMARK
11 KV SF6
AMMETER
CAPACITOR
HRC FUSES
VOLTMETER
W
GFC DRAWING
11KV HT METER
INDICATING LAMP
GENERAL NOTES
S
(SULFUR HEXAFLUORIDE)
POTENTIAL TRANSFORMER
ACB (AIR CIRCUIT BREAKER)
N
6. WE ARE CONSIDER TWO WHEELER PARKING AT
DATE
E
4. THE NUMBER OF CHARGERS AND THE LOCATION MAY
05.02.2024
5. ELECTRICAL PANELS / EQUIPMENTS SIZE MAY VARY AS
2. DIMENSIONS ARE TO BE READ AND NOT TO BE SCALED.
3. THIS IS TENTATIVE LAYOUT, IT CAN BE CHANGE DURING