Professional Documents
Culture Documents
not permitted without express written authority. Offenders will be lible for
The reproduction, transmission or use of this document of its contents is
1 Total no. of sheets, pertaining to a Drawing No. are mentioned only on Sheet No. 1 and on last sheet.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
2 (4)
Alphabate in the 1 st square, of the 4th Block of squares, indicates latest amendment or the status of the issue of the drawing.
3 In case of changes, the amendment to Drawing No. will be carried out only on those sheet, in which changes have taken place and on Sheet No. 1 for the purpose of summary of amendments. The same procedure will continue for
of a utility model or design, are reserved
subsequent changes but every additional change will be indicated by use of next alphabet.
e.g. Say amendment ‘A’ takes place in Sheet No. 3,4,7. Then alphabet ‘A’ will appear in 1st square of 4th Block of Drawing No. Written on Sheet No. 3,4,7 & 1. Further, say, next amendment takes place in Sheet No. 3,5,9. Then alphabet
‘B’ will appear in 1st square of the 4th Block of Drawing No. Written on Sheet No. 3,5,9 & 1. Even though Sheet No. 5 & 9 do not have amendment ‘A’ earlier, they directly will have amendment ‘B’.
4 Separate tabular form of amendment column does not appear on Sheet No. 1 but does appear on all remaining sheets.The brief description in these columns indicates the reference of Client’s/Sales Office’s/Work’s letter or actual changes
done in the drawing. The date-column indicates when the amendment has been carried out. The actual and latest changes are highlighted by drawing a circular shape around them and by writing amendment-alphabet in a triangle near this
circular form.
5 Reference Drawing Nos. wherever mentioned, show basic Drawing Nos. without any amendment. The information about the latest issue of any drawing can be obtained only from latest copy of ‘List of Documents’ which is sent along with set
of drawings for every drawing submission
Index Summary of Amendments Date Drawn Checked
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
Client :- RUSHIL ENTERPRISES Sales Ref No.: 3008171574
Project: SUPPLY OF 11KV RMU TO BESCOM W.O. : 3008171854
Item No : 100 Qty : 20x
Date: 06-12-22 Description : - 8DJH ST RMU
Prep: PS Type 8DJH ST -RRL+ME, O/D,
Ckd: LHS-Extensible, Motorized
Work : - 8DJH ST
Issue Remarks Date Name Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :- :
DRG NO. (4) G71570- R8706 -D002 -
Since irrelevant points are deleted, Sr No. may not be in sequence.
Page 1 of 6
Client :- RUSHIL ENTERPRISES Sales Ref No.: 3008171574
Project: SUPPLY OF 11KV RMU TO BESCOM W.O. : 3008171854
Item No : 100 Qty : 20x
Date: 06-12-22 Description : - 8DJH ST RMU
Prep: PS Type 8DJH ST -RRL+ME, O/D,
Ckd: LHS-Extensible, Motorized
Work : - 8DJH ST
Issue Remarks Date Name Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :- :
DRG NO. (4) G71570- R8706 -D002 -
Since irrelevant points are deleted, Sr No. may not be in sequence.
The reproduction, transmission or use of this document of its contents is not permitted without express written authority. Offenders will be lible for damages. All rights, including righs
2.00.00 Construction
2.01.00 Type of Product : 8DJH ST Ring Main Unit
2.02.00 Installation
2.02.01 Location : Outdoor
2.02.02 Mounting : Base frame mounting
2.02.02A Minimum Clerance from front : 1000 mm
2.02.03 Lifting arrangement : To be lifted along with packing/ lifting arrangement is also provided on the RMU shipping section
2.02.04 Front access : Hinged Front Cover on front facia and then Bolted Cover for Mechanism & LV control In Outdoor RMU
2.02.05 Rear access : Not Applicable
2.02.06 Future extension : ONLY LHS, since metering Panel on RHS provided
2.02.07 Alignment with existing RMU : Nil
2.02.08 Pressure Relief Device Loaction : At Rear Bootom on LHS side for each SF6 Gas Veseel
2.02.09 SF6 Pressure Relese direction : Rear Bottom, Inside Trench, away from operator
2.02.10 Partition Class PM
2.02.11 Loss of service continuity category for modules : LSC 2
2.02.12 Internal arc classification : IAC AFLR up to 21kA, 0.1s (IAC is not applicable for ME compartment)
2.02.13 CRCA sheet thickness for outer enclosure : 2 mm
2.02.15 Stainless Steel sheet thickness for SF6 gas tank : 2.5mm(3 sides), 1.6mm(3 sides); Grade: SS 304. meeting IEC reqd. of 20 kA/0.1 Sec IAC creteria.
2.03.00 Degree of protection for enclosure : O/D RMU : IP54 for Enclosure, IP3X with Front Cover opened & IP67 for SF6 Gas Vessel (HV Part)
2.04.00 Painting
2.04.01 Procedure : Pre-treatment & painting as per 7 tank process, Siemens standard practice
2.04.02 Material : Epoxy Polyster (Hybrid) Resin Based Powder.
2.04.03 Shade : RAL 7032
2.04.04 Paint layer thickness : 100 microns +/- 25 Micron Standard
2.04.05 Paint Finish : Structure finish like light orange peel.
damages. All rights, including righs created by patent grant or registration of a
The reproduction, transmission or use of this document of its contents is not
Page 2 of 6
Client :- RUSHIL ENTERPRISES Sales Ref No.: 3008171574
Project: SUPPLY OF 11KV RMU TO BESCOM W.O. : 3008171854
Item No : 100 Qty : 20x
Date: 06-12-22 Description : - 8DJH ST RMU
Prep: PS Type 8DJH ST -RRL+ME, O/D,
Ckd: LHS-Extensible, Motorized
Work : - 8DJH ST
Issue Remarks Date Name Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :- :
DRG NO. (4) G71570- R8706 -D002 -
Since irrelevant points are deleted, Sr No. may not be in sequence.
damages. All rights, including righs created by patent grant or registration of a
The reproduction, transmission or use of this document of its contents is not
2.06.04 Cable Termination Precaution Sticker : Yes, in any one cable compartment cover
2.06.05 Phase Identification Stickers at Bushing : Yes, Standard Phase Identifciation L1,L2,L3 Stickers
Page 3 of 6
Client :- RUSHIL ENTERPRISES Sales Ref No.: 3008171574
Project: SUPPLY OF 11KV RMU TO BESCOM W.O. : 3008171854
Item No : 100 Qty : 20x
Date: 06-12-22 Description : - 8DJH ST RMU
Prep: PS Type 8DJH ST -RRL+ME, O/D,
Ckd: LHS-Extensible, Motorized
Work : - 8DJH ST
Issue Remarks Date Name Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :- :
DRG NO. (4) G71570- R8706 -D002 -
Since irrelevant points are deleted, Sr No. may not be in sequence.
load/classification
Rated no. of operation at active Load Breaking current
4.00.10 : 100/E3 as per IEC
I1/classification
Rated no. of operation at short circuit making current
4.00.11 : 5/E3 as per IEC
Ima/classification
Rated no. of operation at short circuit making current Ima
4.00.12 : 5/E2 as per IEC 62271-102
for earthing switch/classification
Manual Operation of Load Break Switch, (LBS ON/OFF,
4.00.13 : Yes
E/SW ON/OFF)
4.00.14 Motor Operation of LBS (ON/OFF) : Yes
4.00.15 Motor Rating : ≤65W Approx
4.00.16 Rated Motor current : 2.7A Approx.
4.00.17 Motor Voltage : 24VDC (+10% & -15%)
4.00.19 Aux Switch details : Please refer wiring diagram
4.00.20 TNC Switch for LBS ON/OFF : Yes, Pl refer Equipment list for more details
4.00.21 Local Remote switch : Yes, Pl refer Equipment list for more details
5.00.27 TNC Switch for CB ON/OFF : Yes, Pl refer Equipment list for more details
5.00.28 Local Remote switch : Yes, Pl refer Equipment list for more details
5.00.29 Aux Switch details : Please refer wiring diagram
Page 4 of 6
Client :- RUSHIL ENTERPRISES Sales Ref No.: 3008171574
Project: SUPPLY OF 11KV RMU TO BESCOM W.O. : 3008171854
Item No : 100 Qty : 20x
Date: 06-12-22 Description : - 8DJH ST RMU
Prep: PS Type 8DJH ST -RRL+ME, O/D,
Ckd: LHS-Extensible, Motorized
Work : - 8DJH ST
Issue Remarks Date Name Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :- :
DRG NO. (4) G71570- R8706 -D002 -
Since irrelevant points are deleted, Sr No. may not be in sequence.
6.00.00 Three Position Switch, Off Load (Connected in series with VCB)
6.00.01 Rated Current : 630 A
6.00.02 Rated short circuit making current Ima : 52.5 kA
Rated no. of operating cycles, mechanical at no
6.00.03 : 1000/M0
load/classification
Rated no. of operation at short circuit making current Ima
6.00.04 : 5/E2(IN CONJUGATION WITH VCB)
for earthing switch/classification
Manual Operation of Three Position Switch, (TPS
6.00.05 : Yes
ON/OFF, E/SW ON/OFF)
9.00.00 Wiring
All rights, including righs created by patent grant or registration of a utility model
permitted without express written authority. Offenders will be lible for damages.
The reproduction, transmission or use of this document of its contents is not
Page 5 of 6
Client :- RUSHIL ENTERPRISES Sales Ref No.: 3008171574
Project: SUPPLY OF 11KV RMU TO BESCOM W.O. : 3008171854
Item No : 100 Qty : 20x
Date: 06-12-22 Description : - 8DJH ST RMU
Prep: PS Type 8DJH ST -RRL+ME, O/D,
Ckd: LHS-Extensible, Motorized
Work : - 8DJH ST
Issue Remarks Date Name Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :- :
DRG NO. (4) G71570- R8706 -D002 -
Since irrelevant points are deleted, Sr No. may not be in sequence.
express written authority. Offenders will be lible for
document of its contents is not permitted without
Annexure-1
Make of Equipment
Equipment Make
CT Narayan Power Tech/ Reco/ Siemens Approved Make
PT Narayan Power Tech/ Reco/ Siemens Approved Make
AUX. TRAFO Narayan Power Tech/ Siemens Approved Make
Surge Arrestor Oblum/ Siemens Approved Make
VPIS Leelen/ Siemens Approved Make
MFM Elmeasure/ Rishabh/ Siemens Approved Make
Numerical Relays C&S/ Siemens/ Siemens Approved Make
FPI C&S/ Siemens/ Siemens Approved Make
Battery Leoch/Exide/ HBL/ Equivalent Siemens Approved make
Battery Charger Alan/ Gogate/ Siemens Approved make
Terminal Elmex/ Siemens Approved make
Switches Siemens/ Siemens Approved make
Contactor Siemens/ Siemens Approved make
Control Fuse/ Link/ Base Siemens/ Siemens Approved make
MCB Siemens/ Siemens Approved make
CFL / LED SYSKA/ PHILIPS/ Siemens Approved make
Space Heater Siemens Approved make
Thermostat Siemens Approved make
Connectors AMPHENOL/ Harting / Siemens Approved make
Control cable RR cable / Finolex/ Siemens Approved make
Resistor Siemens Approved make
Cable Boots KD JOSHI/ JASON POLYMER/ Siemens Approved make
Page 6 of 6
MADE IN INDIA
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A A
9
816
130
RELAY
1369 2
1280
C 1
VPIS VPIS
1188
1066
3
H1
VPIS
10
857
D
1620
95 95 95 95 95 95
DANGER DANGER DANGER
NAME NAME NAME
1306
PLATE PLATE PLATE
B B
75
F 75 75
5 597
1908 A 954 954
SHEET METAL BASE FRAME
737.5
CABLE CLAMP ASSEMBLY 811 B1
FRONT VIEW (CLOSED DOOR) FRONT VIEW (OPEN DOOR)
SECTION A-A
G
I
3 Ring-main feeder bushing acc. to EN50181/DIN EN50181
158.50 type C with bolted contact M16
4 Busbar Extensible/Non-extensible
250.00
5 Earthing busbar(earthing point(M8) on earthing busbar)
737.5
J 6 Floor opening
250.00
7 SIEMENS logo
140
79.00 8 CABLE ENTRY
0
6 9 Front door * DOOR OPENDED CONDITION
787
477
167
1908
8
937
17.5
954
FLOOR OPENING & FIXING POINTS 10 Pressure Relief Device H1 2031 mm -RRL- ME
SECTION B-B
Mass ; Masse Papersize Designation
Tolerance
Format 22-06-2020 ISO-Projection
L - Unit;Einheit
Scale
Massstab Datum Name
Department
Abteilung SI DS O GIS SG MF GAS INSULATED SWITCHGEAR
- mm NTS Location
Standort GOA Page
Blatt
Material No./Nr. 1 Material No./Nr. 2 Released
xx/xxxx 01 Itemnumber
-
Freigabe
Mod./Ref-No.
Aend.-Vorg.-Nr.
Revision
Revision
Sachnummer
502_9717_9 1-
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ISMC CHANNEL
D 200 200 100X50 150 159 250 250 79
100 100
50 50
300#
638
MIN TRENCH HT
1000MM
1000
* 400 200
954 954
H
17.5
L
Annexure - II
NOTE:
1. Fittings and Accessories shall be as per specifications.
Marketing Head
Page : 4 / 5
75
BSG : 00147
permitted without express written authority. Offenders will be lible for damages.
PROCEDURE FOR CARRYING OUT AMENDMENTS
Alphabate in the 1 st square, of the 4th Block of squares, indicates latest amendment or the status of the issue of the drawing.
3 In case of changes, the amendment to Drawing No. will be carried out only on those sheet, in which changes have taken place and on Sheet No. 1 for the purpose of summary of amendments. The same procedure will continue for subsequent
changes but every additional change will be indicated by use of next alphabet.
e.g. Say amendment ‘A’ takes place in Sheet No. 3,4,7. Then alphabet ‘A’ will appear in 1st square of 4th Block of Drawing No. Written on Sheet No. 3,4,7 & 1. Further, say, next amendment takes place in Sheet No. 3,5,9. Then alphabet ‘B’
model or design, are reserved
will appear in 1st square of the 4th Block of Drawing No. Written on Sheet No. 3,5,9 & 1. Even though Sheet No. 5 & 9 do not have amendment ‘A’ earlier, they directly will have amendment ‘B’.
4 Separate tabular form of amendment column does not appear on Sheet No. 1 but does appear on all remaining sheets.The brief description in these columns indicates the reference of Client’s/Sales Office’s/Work’s letter or actual changes done
in the drawing. The date-column indicates when the amendment has been carried out. The actual and latest changes are highlighted by drawing a circular shape around them and by writing amendment-alphabet in a triangle near this circular
form.
5 Reference Drawing Nos. wherever mentioned, show basic Drawing Nos. without any amendment. The information about the latest issue of any drawing can be obtained only from latest copy of ‘List of Documents’ which is sent along with set of
drawings for every drawing submission
Unrestricted Page 1 of 4
Client :- Rushil Enterprises Sales Ref No.:3008442918
Project : - Stock Order
W.O. : 3008443045
Item No : 600 Qty : 5x
Date: 09.06.23 Description : - 8DJH ST RMU
Prep: PS Type 8DJH ST LK
Ckd: Work : - O/D, Non-Ext, Manual OPTD.
Siemens Ltd.
Issue Remarks Date Name EM MS O GIS GOI Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :
DRG NO. (4) G71570- R8740-D002-
by
2.00.00 Construction
2.01.00 Type of Product : 8DJH ST Ring Main Unit
2.02.00 Installation
2.02.01 Location : Outdoor
2.02.02 Mounting : Floor Mounting with Cable Trench Beneath
2.02.03 Minimum Clearance from front : 1000 mm
2.02.04 Lifting arrangement : To be lifted along with packing/ lifting arrangement is also provided on the RMU shipping section
2.02.05 Front access : Hinged Front Cover on front facia and then Bolted Cover for Mechanism & LV control In Outdoor RMU
righs created by patent grant or registration of a utility model or design, are reserved
Unrestricted Page 2 of 4
Client :- Rushil Enterprises Sales Ref No.:3008442918
Project : - Stock Order
W.O. : 3008443045
Item No : 600 Qty : 5x
Date: 09.06.23 Description : - 8DJH ST RMU
Prep: PS Type 8DJH ST LK
Ckd: Work : - O/D, Non-Ext, Manual OPTD.
Siemens Ltd.
Issue Remarks Date Name EM MS O GIS GOI Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :
DRG NO. (4) G71570- R8740-D002-
Since irrelevant points are deleted, Sr No. may not be in sequence.
without express written authority. Offenders will be lible for damages. All rights, including
not permitted
righs created by patent grant or registration of a utility model or design, are reserved
: Yes
its contents
All rights,ofincluding is created
righs
2.06.05 Phase Identification Stickers at Bushing : Yes, Standard Phase Identifciation L1,L2,L3 Stickers
nders
The reproduction,
6.00.00 Three Position Switch, Off Load (Connected in series with VCB, towards BUS side)
6.00.01 Rated Current : 630 A
6.00.02 Rated short circuit making current Ima : 52.5 kA
Rated no. of operating cycles, mechanical at no
6.00.03 : 1000/M0
load/classification
Rated no. of operation at short circuit making current Ima
6.00.04 : 5/E2(IN CONJUGATION WITH VCB)
for earthing switch/classification
Manual Operation of Three Position Switch, (TPS
6.00.05 : Yes
ON/OFF, E/SW ON/OFF)
Unrestricted Page 3 of 4
Client :- Rushil Enterprises Sales Ref No.:3008442918
Project : - Stock Order
W.O. : 3008443045
Item No : 600 Qty : 5x
Date: 09.06.23 Description : - 8DJH ST RMU
Prep: PS Type 8DJH ST LK
Ckd: Work : - O/D, Non-Ext, Manual OPTD.
Siemens Ltd.
Issue Remarks Date Name EM MS O GIS GOI Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :
DRG NO. (4) G71570- R8740-D002-
Since irrelevant points are deleted, Sr No. may not be in sequence.
nders will be lible for damages. All rights, including righs created by
9.00.00 Wiring
9.01.00 Auxiliary Circuits : PVC (Single Core Cu wire, Multistranded), Flexible
9.02.00 Insulation Grade : 1100 V
9.03.00 Size of wire (Control & auxiliary Circuits)
9.03.01 CT circuit If any : 2.5 mm.²/ Red, Yellow, Blue, Black
9.03.03 Control circuit DC If any : 1.0 mm.²/ Grey
9.03.04 Control circuit AC If any : 1.0 mm.²/ Grey
9.03.05 Auxiliary Buswire If any : 2.5 mm.² colour coding for AC/DC as per above
9.03.06 Circuit identification : Tubular Printed ferrules at termnations as per " Cross Dependent End Marking"
9.03.07 Earthing Wire colour : Yellow Green
Annexure-1
Make of Equipment
Equipment Make
CT Narayan Power Tech / Ashmor / ECS / Rishabh / Gilbert & Maxwell / Siemens Approved Make
Numerical Relays Ashida/ C&S / Siemens / Siemens Approved Make
Wires RR Kabel / Polycab / Finolex / Havells / Siemens Approved Make
Terminals Connectwell / Phoenix / Siemens Approved Make
Cable boots Siemens approved make
Vacuum interrupter Siemens / Siemens Approved Make
Manometer Wika / Siemens Approved Make
Unrestricted Page 4 of 4
MADE IN INDIA
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A A
9
816
7 126 125 125
H2
4
130
RELAY
1369 M
C
2
1280
1188 1
VPIS
H1
3
D
10
857
1620
DANGER DANGER
NAME NAME 95 95 95 95
PLATE PLATE
1306
Comunicado como segredo empresarial. Reservados todos os direitos.
Confiado como secreto industrial. Todos los derechos reservados.
E
Confiè a titre de secret d'enterprise. Tous droits reserves.
F
B B
597
G A 643
5 737.5
811 B1
Als Betriebsgeheimnis anvertraut. Alle Rechte vorbehalten.
Proprietary data, company confidential. All rights reserved.
54 529
711 B1 583 mm
1 Secondary wiring inlet (right,left) 2031 mm
H1
579
I 2 Vessel with three-postion switch H2 76 mm
3 Ring-main feeder bushing acc. to EN50181/DIN EN50181
type C with bolted contact M16
737.5
329 219
Ø
11
0
4 Busbar Extensible/Non-extensible
J 140
5 Earthing busbar(earthing point(M8) on earthing busbar)
79
0 6 Floor opening
167
477
626.5
644
17.5
6 7 SIEMENS logo
0
8
K
8 CABLE ENTRY
FLOOR OPENING & CLOSING POINTS
SECTION B-B
9 Front door - LK -
Indoor : Without Door Tolerance Mass ; Masse Papersize Designation
Note:- Dimension and Arrangements are for representation only. Toleranz Format
05-01-2021 RB Datum 05-01-2021 Benennung
ISO-Projection
± 2% of actual values
D/A1
Scale Date
Datum
Name
Name
Name
Name
Department
Abteilung
SHREYAS
SI-DS-OGIS GOI
8DJH ST -LK- MANO
GAS INSULATED SWITCHGEAR
L Unit;Einheit Massstab
Location OUTGOING FEEDER FRONT VIEW
- mm NTS GOA Page
-
Freigabe
Mod./Ref-No.
Aend.-Vorg.-Nr.
Revision
Revision
Sachnummer
502_9475_9 1-
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
D AN GER D AN GER
C N AME
PLATE
N AME
PLATE
150 50 50
D 200 200
100 100
638
300#
1000
* 400 200
644.00
H
L
G.T.P FOR 11 K.V METERING CUBICLE
( GUARANTEE TECHNICAL PARTICULARS )
03 MATERIAL & GAUGE USED FOR MAKING THE CRCA SHEET , 2mm
BODY OF THE M/C
I Armour
J Outer Sheath
1 Type & Material Extruded PVC Type ST-2, conforming to IS : 5831
2 Application BY-Extruded
3 Thickness Nominal (For unarmoured cables) MM 0.00
4 Thickness Minimum (For armoured/unarmoured cables) MM 2.68
5 Colour of outer sheath BLACK
K Special Properties of outer sheath
1 Oxygen index test -
2 Temperature Index Test -
3 Acid Gas Generation -
4 Smoke generation Test -
5 Flammability test -
L Electrical Characteristics
1 Max. Conductor DC Resistance at 20°C
a) Main OHM/KM 0.1250
b) Reduced Neutral OHM/KM 0.0000
2 Approx. Conductor AC Resistance at max. Operating Temp
a) Main OHM/KM 0.1620
b) Reduced Neutral OHM/KM 0.0000
3 Approx. Reactance at 50 Hz OHM/KM 0.0840
4 Approx. Capacitance of Cable MICROF/KM 0.4300
5 Min. volume resistivity of insulation OHM-CM 1 X 10^14 at 27 Deg. C & 1 X 10^12 at 90 Deg.C
6 Cont. Current Rating for Standard IS Condition when Laid
a) In Ground at 30°C AMPS 315.00
b) In Duct at 30°C AMPS 275.00
c) In Air. at 40°C AMPS 395.00
7 Allowable max. cond. Temp. When carrying Cont. rated DEG.C 90.00
current
8 Short Circuit Current Rating for 1 Sec. Duration KAMPS 22.56
9 Max. Conductor Temperature allowed for the short circuit DEG.C 250.00
condition
M General Information
1 Overall Diameter of cable(approx.) MM 73.00
2 Net weight of cable (approx.) KG/KM 8300.00
3 Standard drum length Meter 500 ± 5%
4 Non Standard drum length Max. 5 % of ordered quantity
5 Recommended min. Bending radius of cable MM 15 X D (WHERE D IS OVERALL DIAMETER OF CABLE IN MM)
6 Recommended Max. Safe pulling force
a) When cond. pulled by pulling eye N 30 x T ( where T is total cross sectional area of cond . In sqmm
b) When cable pulled by stocking N 9 X D^2 (where D is overall diameter of cable in mm)
7 Marking Detail ( by embossing / printing ) HAVELLS 6.35/11KV XLPE ELECTRIC CABLE (SIZE IN sq.mm)(YEAR
OF MFG.)
8 Sequential marking of length Shall be printed at every meter of length on outer sheath
9 Packing Material Non Returnable wooden/steel drums
* Values indicated as " Approx." are for guidelines only
* In case of any Typographical Error / Discrepancy , relevant standards shall be prevailed.