You are on page 1of 1

PROJECT NAME : TN SUNRISE ONE (21.

75MWp DC 15MW AC SOLAR PV PLANT)


PROJECT DEVELOPER : RADIANCE RENEWABLES PVT LTD.
OWNERS ENGINEER : SGURR ENERGY PVT LTD.
EPC CONTRACTOR : SOLON INDIA PVT LTD.

DATA SHEET FOR LT XLPE ARMOURED CABLES

S.No. Description 3.5 Core x 50 Sq.mm


1 GENERAL
i) Name of Manufacture KEI INDUSTRIES LIMITED
ii) No. of Cores 3.5
iii) Area Sq.mm 50
iv) Cable Type / Code A2XFY - FR-LSH
v) Voltage Grade 1100 Volts
vi) Standards Applicable IS: 7098 (Part I) 1988, IS:5831-1984, IS:8130-2013 ,IS 3975-1999
2 CONDUCTOR
i) Material Stranded (Class 2) H2/H4 Grade Aluminium conductor as per IS : 8130-2013
ii) Shape Compacted Sector Shaped
iii) Cross Sectional Area (Main) sq.mm. 50
iv) Cross Sectional Area (Reduced Neutral) sq.mm. 25
3 INSULATION
i) Material Extruded Cross linked polyethylene (XLPE) as per IS 7098 Part-1 : 1988
ii) Thickness (Nom.) (Main) mm 1
iii) Thickness (Nom.) (Reduced Neutral) 0.9
iv) Core identification Red,Yellow,Blue & Black
v) Tensile Strength (Min.) - XLPE 12.5 N/sq.mm
vi) Elongation at break (Min.) - XLPE 200%
vii) Dielectric Strength 20-30 kV/mm
4 INNER SHEATH
i) Material Extruded PVC Type ST-2 as per IS: 5831-1984
ii) Thickness (Min.) mm 0.3
iii) Colour Black
5 ARMOUR
i) Material Galvanized Steel as per IS : 3975-1999
ii) Type Flat Strip
iii) Size - Nominal mm ( Width x Thickness) 4.0 x 0.8
iv) Tape over armour Suitable Water Swellable tape shall be provided over armour
6 OUTER SHEATH
Extruded PVC Type ST-2 as per IS: 5831-1984 with FR-LSH, Anti Rodent & termite, UV
i) Material
Resistant Properties
ii) Thickness(Min.) mm 1.40
iii) Colour Black
iv) Approx. Overall dia of cable mm 27.7
v) Tolerance on overall dia ± 3 mm
6A FR-LSH Properties
i)
Oxygen Index at room Temp °C. 29% Min. as per ASTM-D-2863
ii)
Temperature Index. Min. 250 deg.C. as per ASTM-D-2863
iii)
Smoke density Rating 60% max. as per ASTM-D-2843
iv)Acid Gas Generation 20% max. as per IEC 60754-1
v)Flammability test As per IEC 60332-1
7 ELECTRICAL DATA
i) Max DC resistance at 20 deg C (Main) Ω/Km 0.641
ii) Max DC resistance at 20 deg C (Neutral) Ω/Km 1.20
iii) Max. AC Resistance at 90 deg C (Main) Ω/Km 0.820
iv) Capacitance µf/Km 0.50
v) Reactance at 50Hz Ω/Km 0.078
vi) Current Ratings
a)In ground at 30 deg C Amps 134
b)In air at 40 deg C Amps 138
vii) Short circuit rating of conductor KA for 1 second 4.7
viii) Volume Resistivity Ω. cm
a) at 27 deg.c. 1 x 10^14
b) at 90 deg.c. 1x 10^12
ix) Conductor Temperature
a) under normal operating conditions 90 0C.
b) at the termination of short circuit 250 0C.
x) HV Test Voltage (AC, for 5 min. as per IS) 3 kV (rms)
8 CABLE DATA
i) Standard Drum Length Meters with ± 5% tolerance 1000
ii) Drum Material Non returnable Wooden
iii) Pulling Force
a)for Cables pulled with stocking 9 x D² Newtons, D is the cable OD in mm
b) Cables pulled with pulling eyes 5250 Newtons
iv) Printing/Embossing Manufacturer's Name , Voltage Grade, Cable Size & Type ,Year Of Manufacturing, FR-LSH
v) Min. Bending radius 12 x D ( where D is overall diameter )
vi) Sequential Marking Shall be provided at every one meter

NOTE :- Suitable Binder/Wrapping tapes shall be provided wherever necessary. The values given above are subject to tolerances as per the relevant standards