Parameters

12/11/2023 2:25:36 PM

Config bits
High alarm
Enabled
Inv. prop.
Channel Name Value Timer Outputs Fail class Auto ack.

8001 Ld. start limit P 100 kW N/A A: N/A ¨ N/A ¨


B: N/A

8002 Ld. start limit S 100 kVA N/A A: N/A ¨ N/A ¨


B: N/A

8003 Ld. start limit % 55 % N/A A: N/A ¨ N/A ¨


B: N/A

8004 Ld. start timer N/A 5 A: N/A ¨ N/A ¨


B: N/A

8005 Ld. Minimum Load 20 kW N/A A: N/A ¨ N/A ¨


B: N/A

8006 Load dep. scale 0 N/A A: N/A ¨ N/A ¨


B: N/A

8011 Ld. stop limit P 200 kW N/A A: N/A ¨ N/A þ


B: N/A

8012 Ld. stop limit S 200 kVA N/A A: N/A ¨ N/A ¨


B: N/A

8013 Ld. stop limit % 35 % N/A A: N/A ¨ N/A ¨


B: N/A

8014 Ld. stop timer N/A 30 A: N/A ¨ N/A þ


B: N/A

8015 Ld. stop on HC req 1 N/A A: N/A ¨ N/A ¨


B: N/A

8021 Start/stop 0 N/A A: N/A ¨ N/A ¨


B: N/A

8022 Mode update 0 N/A A: N/A ¨ N/A ¨


B: N/A

8031 Priority select 0 N/A A: N/A ¨ N/A ¨


B: N/A

8081 Priority 1 1 N/A A: N/A ¨ N/A ¨


B: N/A

8082 Priority 2 2 N/A A: N/A ¨ N/A ¨


B: N/A

8083 Priority 3 3 N/A A: N/A ¨ N/A ¨


B: N/A

8084 Priority 4 4 N/A A: N/A ¨ N/A ¨


B: N/A

8085 Priority 5 5 N/A A: N/A ¨ N/A ¨


B: N/A

8086 Transmit 0 N/A A: N/A ¨ N/A ¨


B: N/A

Device: AGC 242 (4.59.1)


Page 1
Utility software (3.58.0.2752)
F:\MIGRASI DOKUMEN ASUS TUF\FOLDER DOCUMENT\FINAL TEST UNIT 2.usw
Parameters
12/11/2023 2:25:36 PM

Config bits
High alarm
Enabled
Inv. prop.
Channel Name Value Timer Outputs Fail class Auto ack.

8091 Priority 6 6 N/A A: N/A ¨ N/A ¨


B: N/A

8092 Priority 7 7 N/A A: N/A ¨ N/A ¨


B: N/A

8093 Priority 8 8 N/A A: N/A ¨ N/A ¨


B: N/A

8094 Priority 9 9 N/A A: N/A ¨ N/A ¨


B: N/A

8095 Priority 10 10 N/A A: N/A ¨ N/A ¨


B: N/A

8096 Priority 11 11 N/A A: N/A ¨ N/A ¨


B: N/A

8101 Priority 12 12 N/A A: N/A ¨ N/A ¨


B: N/A

8102 Priority 13 13 N/A A: N/A ¨ N/A ¨


B: N/A

8103 Priority 14 14 N/A A: N/A ¨ N/A ¨


B: N/A

8104 Priority 15 15 N/A A: N/A ¨ N/A ¨


B: N/A

8105 Priority 16 16 N/A A: N/A ¨ N/A ¨


B: N/A

8111 Priority update hour 175 Hours N/A A: N/A ¨ N/A þ


B: N/A

8112 Run. hours type 0 N/A A: N/A ¨ N/A þ


B: N/A

8113 Rel. counter N/A N/A A: N/A ¨ N/A þ


B: N/A

8120 Ground relay N/A N/A A: Not used ¨ N/A þ


B: Not used

8124 Ground failure N/A 1 A: N/A þ Trip GB þ


B: N/A

8131 Gnd Open fail N/A 1 A: N/A þ Trip GB þ


B: N/A

8133 Gnd Close fail N/A 1 A: N/A þ Block þ


B: N/A

8135 Gnd Pos fail N/A 1 A: N/A þ Trip GB þ


B: N/A

8140 Stop noncon. DG N/A s 60 A: N/A ¨ N/A þ


B: N/A

Device: AGC 242 (4.59.1)


Page 2
Utility software (3.58.0.2752)
F:\MIGRASI DOKUMEN ASUS TUF\FOLDER DOCUMENT\FINAL TEST UNIT 2.usw
Parameters
12/11/2023 2:25:36 PM

Config bits
High alarm
Enabled
Inv. prop.
Channel Name Value Timer Outputs Fail class Auto ack.

8171 Fuel optimize load 80 % N/A A: N/A ¨ N/A ¨


B: N/A

8172 Fuel optimize swap 200 kW N/A A: N/A ¨ N/A ¨


B: N/A

8173 Fuel optimize timer N/A s 10 A: N/A ¨ N/A þ


B: N/A

8174 Fuel optimize hours 175 N/A A: N/A ¨ N/A ¨


B: N/A

8201 HC 1 req value 500 kVA N/A A: N/A ¨ N/A ¨


B: N/A

8202 HC 1 Nom. power 400 kW N/A A: N/A ¨ N/A ¨


B: N/A

8203 HC 1 load type 0 N/A A: N/A ¨ N/A ¨


B: N/A

8211 HC 2 req value 500 kVA N/A A: N/A ¨ N/A ¨


B: N/A

8212 HC 2 Nom. power 400 kW N/A A: N/A ¨ N/A ¨


B: N/A

8213 HC 2 load type 0 N/A A: N/A ¨ N/A ¨


B: N/A

8220 Available power 1 1000 kW 10 A: Not used ¨ Warning þ


B: Not used

8230 Available power 2 1000 kW 10 A: Not used ¨ Warning þ


B: Not used

8240 Available power 3 1000 kW 10 A: Not used ¨ Warning þ


B: Not used

8250 Available power 4 1000 kW 10 A: Not used ¨ Warning þ


B: Not used

8260 Available power 5 1000 kW 10 A: Not used ¨ Warning þ


B: Not used

8280 Asymm Load share 80 % N/A A: N/A ¨ N/A ¨


B: N/A

8301 Ld. start limit P 2 100 kW N/A A: N/A ¨ N/A ¨


B: N/A

8302 Ld. start limit S 2 100 kVA N/A A: N/A ¨ N/A ¨


B: N/A

8303 Ld. start limit % 2 90 % N/A A: N/A þ N/A ¨


B: N/A

8304 Ld. start timer 2 0 10 A: N/A ¨ N/A ¨


B: N/A

Device: AGC 242 (4.59.1)


Page 3
Utility software (3.58.0.2752)
F:\MIGRASI DOKUMEN ASUS TUF\FOLDER DOCUMENT\FINAL TEST UNIT 2.usw
Parameters
12/11/2023 2:25:36 PM

Config bits
High alarm
Enabled
Inv. prop.
Channel Name Value Timer Outputs Fail class Auto ack.

8311 Ld. stop limit P 2 200 kW N/A A: N/A ¨ N/A ¨


B: N/A

8312 Ld. stop limit S 2 200 kVA N/A A: N/A ¨ N/A ¨


B: N/A

8313 Ld. stop limit % 2 70 % N/A A: N/A ¨ N/A ¨


B: N/A

8314 Ld. stop timer 2 0 30 A: N/A ¨ N/A þ


B: N/A

8881 Ld. start/stop unit 0 N/A A: N/A ¨ N/A ¨


B: N/A

8882 Ld. start/stop type 1 N/A A: N/A ¨ N/A ¨


B: N/A

8921 Secured mode 0 N/A A: N/A ¨ N/A ¨


B: N/A

8922 Multistart set1 2 N/A A: N/A ¨ N/A ¨


B: N/A

8923 Min. run. set 1 1 N/A A: N/A ¨ N/A ¨


B: N/A

8924 Multistart conf 0 N/A A: N/A ¨ N/A ¨


B: N/A

8925 Multistart set2 16 N/A A: N/A ¨ N/A ¨


B: N/A

8926 Min. run. set 2 1 N/A A: N/A ¨ N/A ¨


B: N/A

8931 HC 1 variable load 4 N/A A: N/A ¨ N/A ¨


B: N/A

8932 HC 1 variable load 0 mA N/A A: N/A ¨ N/A ¨


B: N/A

8933 HC 1 variable load 20 mA N/A A: N/A ¨ N/A ¨


B: N/A

8941 HC 2 variable load 5 N/A A: N/A ¨ N/A ¨


B: N/A

8942 HC 2 variable load 0 mA N/A A: N/A ¨ N/A ¨


B: N/A

8943 HC 2 variable load 20 mA N/A A: N/A ¨ N/A ¨


B: N/A

Device: AGC 242 (4.59.1)


Page 4
Utility software (3.58.0.2752)
F:\MIGRASI DOKUMEN ASUS TUF\FOLDER DOCUMENT\FINAL TEST UNIT 2.usw