Short-circuit Coordination Bypass

Starter

Starter Type: Soft-starter - Delta Connected Motors


Normal Duty Rating - AC53a
Distribution
Circuit Breaker + Line Contactors + SMC-50

R
Block
S.C. Protective Device: UL 489 MCCB BCPD K1M SCR SMC-50 K2M
CB Input Fuse Output
140G Thermal-Mag, Inverse-time
5
Line Contactor: 100-C, 100-E (100S-C, 100S-E) M
3
Soft-starter: SMC-50 Smart Motor Controller 1 3~
Rated Operational Voltage: 460V 60Hz (480V Line)
Test Voltage: 483V 60Hz
Rated Conditional S.C. Current (Iq): 65kA (rms sym.)
Level of S.C. Coordination: Type "1" or "2" per IEC 60947-4
UL 508 High Fault SCCR

Motor SMC-50 (Normal Duty) BCPD - Circuit Breaker Dist Block Line Contactor Bypass Starter 6) SCR Fuse (Optional) IEC Coordination 8)
3 ph 1800 rpm Thermal Setting Utilization Category App. Current Max. Current Input/Output Cat. Contactor Cat. No. OLR Max. SCCR Coordination
Cat. No. Cat. No. Cat. No. Class
Rating Rating No. Cat. No. Adj range Current Rating Type
[HP] [A] 1) 2) [A] IEC 60947-2 3) [A] [A] 9) 4) 4) 5) [A] 7) [A] kA Remark
40 52 150-SB1NBD 52 - 155 AC53a: 3.5-10: 99-2 140G-G6C3-C80 80 450 1492-BG 100-C60*… 100-C60*… 193-EEGE 18 - 90 A70QS 150 65 ---
50 62 150-SB1NBD 52 - 155 AC53a: 3.5-10: 99-2 140G-G6C3-C90 90 450 1492-BG 100-C72*… 100-C72*… 193-EEGE 18 - 90 A70QS 150 65 ---
60 77 150-SB1NBD 52 - 155 AC53a: 3.5-10: 99-2 140G-G6C3-D12 125 450 1492-BG 100-C85*… 100-C85*… 193-EEGE 18 - 90 A70QS 150 65 ---
75 96 150-SB1NBD 52 - 155 AC53a: 3.5-10: 99-2 140G-J6F3-D15 150 450 1492-BG 100-E116*… 100-E116*… 193-EEHJ 30 - 150 A70QS 150 65 ---
100 124 150-SB1NBD 52 - 155 AC53a: 3.5-10: 99-2 140G-J6F3-D20 200 450 1492-BG 100-E146*… 100-E146*… 193-EEHJ 30 - 150 A70QS 150 65 Type 1 ---
125 156 150-SB2NBD 65 - 190 AC53a: 3.5-10: 99-2 140G-J6F3-D22 225 500 1492-BG 100-E190*… 100-E190*… 193-EEJJ 40 - 200 A70QS 175 65 ---
150 180 150-SB2NBD 65 - 190 AC53a: 3.5-10: 99-2 140G-J6F3-D25 250 500 1492-BG 100-E205*… 100-E205*… 193-EEJJ 40 - 200 A70QS 175 65 ---
200 240 150-SB3NBD 82 - 242 AC53a: 3.5-10: 99-2 140G-K6F3-D35 350 700 1492-BG 100-E265*… 100-E265*… --- --- A70QS 200 65 ---
250 302 150-SB4NBD 104 - 311 AC53a: 3.5-10: 99-2 140G-K6F3-D40 400 700 1492-BG 100-E305*… 100-E305*… --- --- A70QS 250 65 ---
300 361 150-SC1NBD 122 - 363 AC53a: 3.5-10: 99-2 140G-M6F3-D60 600 1,000 1353703 9) 100-E370*… 100-E370*… --- --- A70QS 350 65 ---
350 414 150-SC2NBD 151 - 450 AC53a: 3.5-10: 99-2 140G-M6F3-D60 600 1,200 1353703 9) 100-E400*… 100-E400*… --- --- A70QS 400 65 ---
Type 1
400 477 150-SC3NBD 186 - 554 AC53a: 3.5-10: 99-2 140G-M6F3-D70 700 1,200 1353703 9) 100-E460*… 100-E460*… --- --- A70QS 450 65 ---
450 515 150-SC3NBD 186 - 554 AC53a: 3.5-10: 99-2 140G-M6F3-D80 800 1,200 1353703 9) 100-E580*… 100-E580*… --- --- A70QS 450 65 ---
500 590 150-SD1NBD 210 - 625 AC53a: 3.5-10: 99-2 140G-N6H3-E12 1,000 10) 1,200 1352702 9) 100-E580*… 100-E580*… --- --- A70QS 500 65 42kA
600 708 150-SD2NBD 243 - 727 AC53a: 3.5-10: 99-2 140G-N6H3-E12 1,000 10) 1,600 1352702 9) 100-E750*… 100-E750*… --- --- A70QS 600 65 Type 1 42kA
700 826 150-SD3NBD 302 - 900 AC53a: 3.5-10: 99-2 140G-N6H3-E12 1,200 10) 2,000 1352702 9) 100-E860*… 100-E860*… --- --- A70QS 700 65 42kA

Note: Normal Duty Ratings - AC53a: Typical applications include pumps, compressors, elevators & short conveyors.

Start NOT TO EXCEED: 350% of the motor FLA, 10 sec. start time, 99% on-load factor, 2 starts per hour, with 40°C surrounding air ambient temperature.

Refer to Estimation & Thermal Selection Wizards to ensure the SMC selection meets the application requirements. See http://ab.rockwellautomation.com/Motor-Control/Soft-Starters Note: Heavy Duty Starting may require upsizing of the fuse and/or line contactors and bypass starter.

1) Typical motor current per NEC Article 430, Table 430-150


2) Incomplete catalog number, add coil code and auxiliary contacts
3) 140G-G Frame can be replaced by 140G-H Frame
4) Incomplete catalog number, add coil code and auxiliary contacts
5) Data applies to 193-E1 Plus, E3, E3 Plus & E300
6) Bypass starter sized to cover motor FLA. Verify motor DOL starting characteristics to avoid nuisance trip of CB
7) A70QS are High Speed Semi-Conductor fuses that provide additional protection with no damage to the SMC power structure, Coordination Type 2
8) Short Circuit Coordination between branch circuit protection device, line contactors and by-pass starters
9) Distribution Block can be sourced from Marathon
10) Circuit Breaker ratings and protection characteristics determined by selection of rating plugs

Note: This data is subject to change by Rockwell Automation without notice. Go to www.rockwellautomation.com/go/globalsccr for latest information.

SCCR-226116E 080420 MM.xlsx 460V_Delta_ND_CB_SMC50_65kA