Professional Documents
Culture Documents
SPECIFICATION
MI-QI-2887
PREPARED BY
Y. N. Song
REVIEWED BY
APPROVED BY
B. K. Song
R&D & Q.C MANAGER
QP-8390-01(0) A4(210mm×297mm)
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 2/8
1. Scope
This specification covers 0.6/1kV grade, Ethylene propylene (EP) rubber insulated,
2. Reference Standard
IEC 60502-1 : Power cables with extruded insulation and their accessories for rated voltages from 1
kV(Um =1.2 kV) up to 30 kV(Um =36 kV)
Part 1 :Cables for rated voltages of 1 kV(Um =1.2 kV) and 3 kV(Um =3.6 kV)
IEC 60811-1-1 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 1 : Methods for general application.
Section 1 : Measurement of thickness and overall dimension.
IEC 60811-1-2 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 1 : Methods for general application.
Section 2 : Thermal ageing methods.
IEC 60811-1-3 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 1 : Methods for general application.
Section 3 : Methods for determining the density, Water absorption tests, Shrinkage test.
IEC 60811-2-1 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 2 : Methods specific to elastomeric compounds.
Section 1 : Ozone resistance, hot set and mineral oil immersion tests.
QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 3/8
3. Symbol of Cable
〈Table 1〉
Description Symbol
4.1. Conductor
The conductor shall be bunched or multi-stranded with tinned annealed copper wires
specified in IEC 60228, class 5.
A suitable tape shall be applied on the conductor.
4.2. Insulation
The insulation shall be applied concentrically to the conductor with Ethylene Propylene(EP) rubber
The average thickness of insulation shall be not less than the value given in the attached table
and the minimum thickness at any point shall be not less than 90% of the specified value minus
The core of cables shall be identified either by color or by numbers in accordance with the
following methods.
QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 4/8
The required number of cores shall be cabled with suitable lay length and if necessary
with fillers in round shape and suitable tape shall be applied over the cabled core.
4.5. Sheath
The sheath shall be applied concentrically to the cabled core with Black colored
table 3.
The average thickness of sheath shall be not less than the value given in the attached
table and the minimum thickness at any point shall be not less than 85% of the
QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 5/8
5. Test
The test shall be carried out on the finished cable at our works in accordance with the
Cable Length
2 10 4 20 1
10 20 20 40 2
20 30 40 60 3
The type tests required by KS C IEC 60502-1 standard for insulation and sheath.
QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 6/8
Kind of test
DESIGNATION PROPERTIES Test methods
Routine Sample Type
* Electrical test
Conductor resistance ○ - ○ 15.2
Insulation resistance constant Ki (90℃) Min. 3.67 ㏁ㆍkm - - ○ 17.2
Voltage test for 4hours (4Uo at 4 h) - - ○ 17.3
Voltage test for (Attached table of dimension at 5 min.) ○ - ○ 15.3
* Construction and dimension of Cables
Conductor examination - ○ - 16.4
Measurement of thickness of insulation - ○ ○ 18.1
Measurement of thickness of sheath - ○ ○ 18.2
* Mechanical properties
Insulation Ethylene propylene (EP)
Tensile strength Min. 4.2N/mm² - - ○
Without
ageing
Elongation at break Min. 200% - - ○
Tensile 18.3
strength Variation ±30% - - ○
After ageing
in air oven Elongation Variation
at break ±30% - - ○
Elongation under
IEC
Hot set load Max. 175% - ○ ○
test Permanent elongation after Max. 15%
16.9 60502-1
cooling - ○ ○
Water absorption Max. 5mg/cm² - - ○ 18.13
Sheath Polychloroprene (PCP)
QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 7/8
6. Marking
The cable shall be indelibly marked on its surface repeatedly by a suitable method with
following information ;
4) Year of manufacture
Note) Any other information marking may be applicable, when purchaser required.
The drum shall be marked on the side face and the coil shall be affixed with a tag
1) Type of cable
3) Length(m)
5) Year of manufacture
7. Packing
Customer and manufacturer will agree upon the lengths and packing by order.
QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 8/8
1. Specification
Size 240SQ X 3C
No. of core EA 3
Nominal sectional area ㎟ 240
Conductor Max. Dia. mm 0.51
Dia (App.) mm 23.1
Thickness of insulation mm 2.5
Thickness of sheath mm 5.1
Nominal dia. over sheath App. mm 38.8 x 95.6
Weight App. kg/km 9,960
Max. Conductor Resistance(20℃) Ω/km 0.0817
Test Voltage V 3500/5min
2. Construct
QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.