You are on page 1of 8

MYOUNG IN ELECTRIC WIRE CO., LTD.

SPECIFICATION
MI-QI-2887

0.6/1kV EP rubber insulated and PCP sheathed


flexible High tension Cable(flat type)
(0.6/1kV HT-PNCT-F)

ISSUED : Dec. 27. 2023 PAGE : 1 of 8 REV. : 0

PREPARED BY

Y. N. Song

REVIEWED BY

APPROVED BY

B. K. Song
R&D & Q.C MANAGER

QP-8390-01(0) A4(210mm×297mm)
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 2/8

1. Scope

This specification covers 0.6/1kV grade, Ethylene propylene (EP) rubber insulated,

Polychloroprene (PCP) sheathed flexible cables used for industrial purpose.

2. Reference Standard

IEC 60228 : Conductors of insulated cables.

IEC 60502-1 : Power cables with extruded insulation and their accessories for rated voltages from 1
kV(Um =1.2 kV) up to 30 kV(Um =36 kV)
Part 1 :Cables for rated voltages of 1 kV(Um =1.2 kV) and 3 kV(Um =3.6 kV)

IEC 60811-1-1 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 1 : Methods for general application.
Section 1 : Measurement of thickness and overall dimension.

IEC 60811-1-2 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 1 : Methods for general application.
Section 2 : Thermal ageing methods.

IEC 60811-1-3 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 1 : Methods for general application.
Section 3 : Methods for determining the density, Water absorption tests, Shrinkage test.

IEC 60811-2-1 : Insulating and sheathing materials of electric and optical cables
Common test methods for insulating and sheathing materials of electric cables.
Part 2 : Methods specific to elastomeric compounds.
Section 1 : Ozone resistance, hot set and mineral oil immersion tests.

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 3/8

3. Symbol of Cable

The symbol of cable are as shown in Table 1.

〈Table 1〉

Description Symbol

0.6/1kV EP rubber insulated and PCP sheathed flexible


0.6/1kV HT-PNCT-F
High tension Cable(flat type)

4. Construction and Material

4.1. Conductor
The conductor shall be bunched or multi-stranded with tinned annealed copper wires
specified in IEC 60228, class 5.
A suitable tape shall be applied on the conductor.

4.2. Insulation

The insulation shall be applied concentrically to the conductor with Ethylene Propylene(EP) rubber

complying with characteristics specified in the table 3.

The average thickness of insulation shall be not less than the value given in the attached table

and the minimum thickness at any point shall be not less than 90% of the specified value minus

0.1mm. A suitable tape may be applied on the braid at manufacture's option.

4.3. Identification of insulated cores

The core of cables shall be identified either by color or by numbers in accordance with the

following methods.

One core : Black


Two cores : Black, White
Three cores : Black, White, Red
Four cores : Black, White, Red, Green
Five cores and above : 1, 2, 3, ........., No. (No. : number of Cores)

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 4/8

4.4. Cabling of cores

The required number of cores shall be cabled with suitable lay length and if necessary
with fillers in round shape and suitable tape shall be applied over the cabled core.

4.5. Sheath

The sheath shall be applied concentrically to the cabled core with Black colored

Polychoroprene (PCP) compound complying with the characteristics specified in the

table 3.

The average thickness of sheath shall be not less than the value given in the attached

table and the minimum thickness at any point shall be not less than 85% of the

specified value minus 0.1mm.

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 5/8

5. Test

The test shall be carried out on the finished cable at our works in accordance with the

test method specified in the table 3.

5.1 Routine tests

5.1.1 Conductor resistance test

5.1.2 Voltage test

5.2 Sample tests

5.2.1 Construction test

5.2.2 Thickness of insulation and sheath

5.2.3 Hot set test of insulation and sheath

<Table 2 : Number of sample for sample test>

Cable Length

Multicore cables Single core cables No. of sample

Above Up to and including Above Up to and including


(km) (km) (km) (km)

2 10 4 20 1

10 20 20 40 2

20 30 40 60 3

etc etc etc

5.2 Type tests

The type tests required by KS C IEC 60502-1 standard for insulation and sheath.

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 6/8

<table 3 Properties of cable >

Kind of test
DESIGNATION PROPERTIES Test methods
Routine Sample Type
* Electrical test
Conductor resistance ○ - ○ 15.2
Insulation resistance constant Ki (90℃) Min. 3.67 ㏁ㆍkm - - ○ 17.2
Voltage test for 4hours (4Uo at 4 h) - - ○ 17.3
Voltage test for (Attached table of dimension at 5 min.) ○ - ○ 15.3
* Construction and dimension of Cables
Conductor examination - ○ - 16.4
Measurement of thickness of insulation - ○ ○ 18.1
Measurement of thickness of sheath - ○ ○ 18.2
* Mechanical properties
Insulation Ethylene propylene (EP)
Tensile strength Min. 4.2N/mm² - - ○
Without
ageing
Elongation at break Min. 200% - - ○
Tensile 18.3
strength Variation ±30% - - ○
After ageing
in air oven Elongation Variation
at break ±30% - - ○
Elongation under
IEC
Hot set load Max. 175% - ○ ○
test Permanent elongation after Max. 15%
16.9 60502-1
cooling - ○ ○
Water absorption Max. 5mg/cm² - - ○ 18.13
Sheath Polychloroprene (PCP)

Tensile strength Min. 10.0N/mm² - - ○


Without
ageing
Elongation at break Min. 300% 이상 - - ○
18.4
Minimum - - - ○
Tensile
strength
After ageing Variation ±30% - - ○
in air oven
Elongation Minimum 250% - - ○
at break 18.12
Variation ±40% - - ○
Tensile Variation
After strength ±40% - - ○
immersion in
hot oil Elongation Variation
at break ±40% - - ○
16.9
Elongation under load Max. 175% - ○ ○
Hot set
test
Permanent elongation after
cooling Max. 15% - ○ ○

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 7/8

6. Marking

6.1. Marking on the Cable

The cable shall be indelibly marked on its surface repeatedly by a suitable method with

following information ;

1) Type of cable (as 0.6/1kV HT-PNCT-F)

2) Nominal sectional area & number of cores (as 3C x 240SQMM)

3) Manufacturer's name (as MYOUNG IN)

4) Year of manufacture

Note) Any other information marking may be applicable, when purchaser required.

6.2. Marking on the Package

The drum shall be marked on the side face and the coil shall be affixed with a tag

marked with following particulars ;

1) Type of cable

2) Nominal sectional area & number of cores

3) Length(m)

4) Manufacturer's name or trade mark

5) Year of manufacture

6) Net & gross weight in case of drum (kg)

7. Packing

Customer and manufacturer will agree upon the lengths and packing by order.

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.
ISSUED : Dec. 27. 2023.
MYOUNG IN Standard of Cables SPEC NO. : MI-QI-2887
Myoung In PAGE : 8/8

Attached table . 0.6/1kV HT-PNCT-F

1. Specification

Symbol 0.6/1KV HT-PNCT-F

Size 240SQ X 3C
No. of core EA 3
Nominal sectional area ㎟ 240
Conductor Max. Dia. mm 0.51
Dia (App.) mm 23.1
Thickness of insulation mm 2.5
Thickness of sheath mm 5.1
Nominal dia. over sheath App. mm 38.8 x 95.6
Weight App. kg/km 9,960
Max. Conductor Resistance(20℃) Ω/km 0.0817
Test Voltage V 3500/5min

2. Construct

1. Conductor : Tinned annealed copper wires

2. Insulation : Ethylene propylene rubber (EPR)

3. Sheath : Polychloroprene rubber (PCP)

< NOT TO SCALE >

QP-8390-01(0) A4(210×297mm)
MYOUNG IN ELECTRIC WIRE CO., LTD.