Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
The "SETUP" memory is used to store constant parameters necessary for proper operation
of the controller. In order to switch to the "SET UP" programming mode, press the buttons listed
below in correct sequence:
-3– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
For some program steps, the MIKSTER MCC 050 FUTURE Microprocessor Controller allows
defining, whether the bar condition is met for:
Read out Temp. (bar) > Preset Temp (bar)
or
Read Out Temp. (bar) < Preset Temp. (bar)
In order to define method of the bar condition interpretation do the following: ( while
remaining
in the SET-UP mode )
-4– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
-5– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
Then, by pressing the key, you may switch to calibration of another sensor.
The calibration is carried out analogically as for the first sensor.
-6– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
F02 3[s] 0..255 Duration of acoustic When switching over from one step
signal when switching to another during automatic
over to the next step execution of the program, the
(MCC 050 FUTURE, MCC device generates an acoustic signal,
100)* and its duration is determined by
F02.
-7– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
F06 45[s] 0..255 Frequencies of saving This function determines how often
recordings in the technological process parameters
controller memory will be saved in the controller
memory
(MCC 050 FUTURE,
MCC 100)*,**
F07 011 0..999 First 3 digits of security
code for the SET-UP
F08 011 0..999 Next 3 digits of security
code for the SET-UP
F09 022 0..999 First 3 digits of security
code for the
PROGRAMMING
F10 022 0..999 Next 3 digits of security
code for the
PROGRAMMING
F11 40 [min] 0..255 Duration of continued The F11 function permits to
program operation after determine time, after which
power supply decay. execution of program interrupted
due to power supply decay will be
discontinued.
-8– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
-9– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
F23 5[°C] 0..10 Range of operation for the Detailed description in section:
"lifting" algorithm. "Description of algorithms for on-off
controller".
F24 3[s] 0..5 Temperature controller as before
action delay.
-10– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
F29 15[°C] 0..30 Permissible level of This function determines how far the
exceeding the BOILER / chamber preset temperature may be
exceeded without signalling ERROR-
CHAMBER preset 21, e.g.:
temperature value.
Chamber preset temperature=
70 [ºC], F29 = 15 [ºC] – then
ERROR-21 signalling will take place
after exceeding the read out
temperature value = 85 [ºC].
F30 150 [°C] 0..500 Maximum “jacket”
(casing) temperature. If
it is exceeded, the result
will be signalling of
ERROR-22
(MCC 051)*
F31 20[°C] 0..250 Difference (“distance”) Example:
between “jacket”
Preset boiler temperature = 80 [°C]
temperature control and
preset boiler temperature and F31 = 20 [°C], then
(MCC 051)* Preset jacket temperature =
100[°C]
F32 2.0[°C] “Jacket” temperature
controller lower
hysteresis.
(MCC 051)*
F33 2.0[°C] “Jacket” temperature
controller upper
hysteresis.
(MCC 051)*
F34 0 NU***
-11– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
F35 10[min] 0..30 "SMOKE GENERATOR" This function determines time, after
output switching off time. which the "SMOKE GENERATOR"
(MCC 050, MCC 100)* output will be switched off, counting
from starting time of the step, in
which the above-mentioned output
was switched on.
F36 0 0..1 The "SHOWER" output Definition:
status.
0 – The “SHOWER" output operation
(MCC 100)* is consistent with its program, that
is it may be switched on or off
throughout the step.
1 – The “SHOWER" output is an
output of the smoke generator
extinguishing system and it is
dependent on smoke temperature
readout. If acceptable smoke
temperature determined in the F39
function is exceeded, then an
impulse signal appropriate for
particular values of the F37 and F38
functions will appear at this output.
F37 0.5[s] 0..25,5 Duration of water supply
to the shower of smoke
generator extinguishing
system.
(MCC 100)*
F38 1.0 [s] 0..25,5 Duration of break in
supplying water to the
shower of smoke
generator extinguishing
system.
(MCC 100)*
F39 250 [°C] 0..300 Preset temperature for
switching on the smoke
generator extinguishing
system. (MCC 100)*
F40 0 0..1 Humidity control SWITCH-
OFF / SWITCH-ON,
through the use of air
damper.
F41 0 [s] 0..999 Air damper opening time
during execution of
humidity control.
F42 0 [s] 0..999 Air damper closing time
during execution of
humidity control
-12– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
F43 NU
F44 2 0..5 Frequency of recording 0 – printout off
printout on a thermal 1 – printout every 1minute
printer. 2 – printout every 30 sec.
3 – printout every 15 sec.
4 – printout every 10 sec.
F45 NU
F46 NU
F47 NU
F48 0 0..1 Transmission speed 0- 9600
1 - 19200
F49 0 0..1 Transmission speed 0- Mikster-bus
1- MODBUS RTU
F50 NU
F51 NU
F52 0 0..1 Product identification 0- ID off
input on / off.
1- ID on
F53 0 0..1 Control from PC This parameter determines, whether
computer. it will be possible to start
technological process execution
using the controller keyboard. If this
parameter is set at 1, then the
process may be started only from
master computer level.
0- Control on
1- Control off
F54 NU
F55 NU
F56 0 0..1 Recording accuracy 0- 1 degree
(scale)
1- 0.2 degree
F57 NU
F58 NU
F59 NU
* - numbers in brackets indicate, in which types of controllers certain function is used. In case if
function description does not list types of controllers, the function applies to these controllers:
(MCC 050 FUTURE, MCC 051, MCC 100)
** - functions apply to the MCC 050, MCC 051 controllers equipped with technological process
recording system, used in controllers manufactured since January 1, 1996.
***- NU - unused
-13– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
Hg
Tz
Hd
Zd
Tz inst
ON
OFF
SYMBOL DEFINITIONS:
ON – Controller output on
Tz inst – "Instantaneous" preset temperature – temperature control is carried out in relation to this
value.
-14– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
EXPLANATION OF PRINCIPLES
IF Tod>=Zd and Tod<(Tz-Hd) then the preset temperature "lifting" algorithm is executed, the
algorithm is based on the fact that the controller output (Rout=OFF) is switched off at the moment the
value of instantaneous preset temperature (Tz inst) is exceeded. The output will be switched on again
(Rout=ON) when temperature drop is confirmed; simultaneously new value of instantaneous preset
temperature Tz inst=(Tz-Tod)/2 will be established. In case of establishing preset temperature value
Tz inst>=(Tz-Hd) then Tz inst=Tz.
Case 3
If (Tz+Hg)>=Tod>(Tz-Hd) then the controller output (Rout=OFF) is switched off when temperature
increase is observed. The output will be switched on (Rout=ON) when temperature drop is confirmed
(Rout state change is delayed by time value determined in the F24).
Case 4
If Tod>(Tz+Hg) then the controller output is off (Rout=OFF).
TYPE-2
Hg1
Hd1
Tz
ZAŁ
WYŁ
-15– 24.02.2006
Specification for the "MIKSTER MCC 050 FUTURE" Microprocessor Controller
ANNEX for SERVICE
TYPE-3
Hg1
Hd1
Tz
ZAŁ
WYŁ
NOTES