You are on page 1of 3

PROJECT: TechCalc-Project 11.05.

2023

BOUNDARY CONDITIONS
Calculation Method Climate
Heat loss/gain and surface temperature Standard : ISO 12241 (2008)
Medium Ambient temperature : 37 °C
Medium Type : fluid
Cladding
Temperature inside : 343 °C
undefined , Emissivity: 0.1
hi-Value : infinity W/(m²K)
Economy
Currency : EUR
Energy Cost : 0 EUR/kWh
Energy Efficiency of the heating system : 1

Wall Component Nr.2


Length : 1 m
Height : 1 m
Orientation : Horizontal indoor

SUMMARY OF RESULTS
Version Name Compare versions
V. 0 Uninsulated Uninsulated : Version 1
V. 1 Version 1

Summary V. 0 V. 1 Saving
Heat loss 9693 62 -9631 W/m²
Heat loss (Area insulated) 9693 62 -9631 W/m²
Total heat loss 9693 62 -9631 W
T-surface 342.52 49.98 °C
he-Value 31.68 4.81 W/(m²K)

Page 1
PROJECT: TechCalc-Project 11.05.2023

INSULATION SYSTEM VERSION

Wall Component Nr.2


Insulation System : Version 1
Sum of insulation thickness : 279 mm

Layer Name Thickness Lambda m(*) Boundary T Fm Fa FC Fc Fd Fj F delta-Lambda


mm mW/(m.K) °C W/(m.K)
1 Mineral wool 1.2.2a Wired mat 200 59.46 343 1 1 1 1 1 1 1 0
80-120 kg/m³

* Note
Lambda m(*) = Thermal conductivity in mW/(m.K)
Fm = Moisture conversion factor
Fa = Aging conversion factor
FC = Compression conversion factor
Fc = Convection conversion factor in the vertical insulation
Fd = Thickness conversion factor
Fj = Joint-Factor
F = Overall conversion factor

DISCLAIMER
Calculation results are based exclusively on entered values and boundary conditions. These calculations are only an estimation
of the actual temperatures, and heat losses because it is impossible to accurately define real life conditions such as radiation,
wind speed, relative humidity...
BPB United Kingdom Limited trading as Saint-Gobain Isover (“Isover”) has provided the above guidance, based solely on the
attached documents or drawings / information as supplied by or on behalf of the recipient. This is not intended to form a
contractual relationship between Isover and the recipient. It is the responsibility of the recipient to approve and co-ordinate the
information provided by Isover before installation. The guidance is not intended for any third parties and or other circumstance
other than those noted in this enquiry. This guidance should also be read in conjunction with current literature which can be
found at either www.isover.co.uk. All materials, unless otherwise stated, shall be supplied by Isover and need to be installed in
accordance with current manufacturers recommendations and construction industry standards.

Page 2
PROJECT: TechCalc-Project 11.05.2023

INSULATION PRODUCTS SPECIFICATION

Mineral wool 1.2.2a Wired mat 80-120 kg/m³

T Lambda Term Coefficient Mue sd-Value

38 °C .039 W/(m.K) 1 0.03060000000 1 0

93 °C .049 W/(m.K) 2 0.00009603000000

149 °C .06 W/(m.K) 3 1.908000000e-7

204 °C 0.076 W/(m.K) 4 1.070000000e-10

Page 3