You are on page 1of 2

BLOCK 433a & 416b, TOUGGOURT REGION, ALGERIA

COMPLEX DEVELOPMENT

BIR SEBA FIELD DEVELOPMENT

Document Number: BRS1-DS-E-BRS-0005

Document Title: LOW VOLTAGE MOTOR DATA SHEET (TYPICAL)


BRS1-DS-E-BRS-0005.RD1 Low Voltage Motor Data Sheet
Document File Name: (Typical).xls

D1 25-Aug-09 Issued Approved for Design AM BH SS

0 04-Aug-09 Issued for Client Comment AM BH GS

A 17-Jul-09 Issued for IDC AM BH GS


Approved by
Rev Date Reason For Issue Issued by Checked by Approved by
Client
LOW VOLTAGE MOTOR DATA SHEET
PROJECT: BIR SEBA (BRS) TAG No.: See Load List, BRS1-SH-E-BRS-0001
LOCATION: ALGERIA No. REQ'D: See Load List, BRS1-SH-E-BRS-0001
PLANT: BRS FACILITY DATE: 25-Aug-09
SERVICE: LOW VOLTAGE MOTOR COMPANY: GROUPEMENT BIR SEBA
A. BASIC REQUIREMENTS: B. SUPPLIER'S INFORMATION:
DRIVEN EQUIPMENT: Various SUPPLIER:
DRIVE TYPE: Induction Motor SUPPLIER REFERENCE:
MOTOR SPEC. No.: BRS1-SP-E-BRS-0007 FRAME REF:
COOLING METHOD: TEFC (IC411) FRAME MATERIAL:
Ingress Prot. Mounting SERIAL NUMBER:
ENCLOSURE: IP 55 / IP 56 Horizontal / Vertical RATING: kW
CLIMATE: Dry, sandy desert environment (Sahara) LOAD: kW
PROTECTION: MCCB / Contactor FULL-LOAD CURRENT: A
STARTING METHOD: Direct On Line / Variable Speed Drive
RATED VOLTAGE: 400V, 3-phase, 50 Hz LOCKED ROTOR CURRENT: % FLC
RATED SHORT TIME WITHSTAND: 100kA for 1 second 100% 75% 50%
SYSTEM NEUTRAL EARTHING: Solid EFFICIENCY:
AREA CLASSIFICATION: Zone 2, Gas Group IIB, Temp. Class T3 POWER FACTOR:
TYPE OF PROTECTION: Ex nA (<100kW) / Ex de (>100kW) LR POWER FACTOR:
RATING: See note 1 SYNCHRONOUS SPEED: rpm
NUMBER OF POLES: See note 1 FULL-LOAD SPEED: rpm
ROTATION (from drive end): EPC 80% 100% VOLTAGE
DUTY: Continuous RUN-UP TIME: s
MAX. STARTING CURRENT: CENELEC HD 53.12 STALL TIME HOT: s
STALL TIME COLD: s
STARTING CHARACTERISTIC: EPC te Time (Ex e) N/A s
Min. Max. Net Shipping
DESIGN AMBIENT: -5˚C 55˚C MASS: kg
Min. Max. ROTOR INERTIA: kgm2
HUMIDITY: 9% 97%
ALTITUDE: 132 m PURGE AIR REQUIREMENT: L/hour
LOCATION: Outdoors CERTIFICATION AUTHORITY:
DESIGN LIFE: 25 years CERTIFICATION STANDARD:
Main Auxiliary CERTIFICATION NUMBER:
TERMINAL BOX (from NDE): Left Left OUTLINE DRG. No:
CABLE ENTRY: Bottom Bottom NEUTRAL BOX SIZED FOR CT:
MAIN CABLE DETAILS: EPC Type Reference
AUX. CABLE DETAILS: EPC BEARING DE:
MAIN TERM BOX TYPE: Air insulated BEARING NDE:
LUBRICATION:
WINDING TEMPERATURE: No INTERVAL:
BEARING TEMPERATURE: No Hot Cold
VIBRATION DETECTION: No No. OF CONSECUTIVE STARTS:
COOL DOWN TIME: s (after 3 starts)
EARTH BOSS: Two
PAINT COLOUR: See note 5 FULL LOAD TORQUE: Nm
SURGE WITHSTAND EQUIPMENT: See note 4 LOCKED ROTOR TORQUE: % FLT
PULL OUT TORQUE: % FLT
DIFFERENTIAL PROTECTION: No STATOR CONNECTION:
CT DIMENSIONS: N/A
ACOUSTIC HOOD:
NOISE LEVEL MAX: 82 dB(A) @ 1m (no load) NOISE LEVEL (guaranteed): dB(A) @ 1m (no load)

SPACE HEATER: Yes / No SPACE HEATER RATING: W


SPACE HEATER VOLTAGE:: 230V, 1 phase + Neutral, 50 Hz SPACE HEATER VOLTAGE: V
SPACE HEATER RATING: EPC W
INSULATION CLASS:
INSULATION CLASS: F TEMPERATURE RISE: ˚C (by resistance) ATEX app.
TEMPERATURE RISE: B
NOTES:
1. See document BRS1-SH-E-BRS-0001 for preliminary ratings 6. Vertically mounted motors shall be protected to IP 56
2. Motor rating shall be verified during detailed design and to be confirmed by Supplier 7. EPC - Information to be completed during detailed design
3. Motor shall be ATEX certified 8. Where LV motors are controlled via VSD, motors shall be suitabely rated for
4. Refer to Low Voltage Induction Motors Specification BRS1-SP-E-BRS-0008 duty required. In addition the motor shall be certified as Ex de.
5. Refer to Specification for Painting, BRS1-SP-M-BRS-0033

LOW VOLTAGE MOTOR DATA SHEET (TYPICAL)

PROJECT DOCUMENT NUMBER Sht No. REV


BRS1-DS-E-BRS-0005 2 of 2 D1

You might also like