You are on page 1of 11

Large Split Indoor Units

Four-way Cassette
1 Specifications ............................................................................................. 2

2 Dimensions ................................................................................................ 3

3 Unit Placement .......................................................................................... 4

4 Piping Diagram ........................................................................................... 5

5 Wiring Diagram .......................................................................................... 6

6 Capacity Tables........................................................................................... 8

7 Electrical Characteristics ........................................................................... 10

8 Sound Levels ............................................................................................ 11

202003 1
Large Split Indoor Units
1 Specifications
MQ4A-48CRDN1
Table 1.1: MQ4A-48(38)CRDN1 specifications
Model MQ4A-48CRDN1 MQ4A-38CRDN1
Power supply 1 phase, 220-240V, 50Hz
kW 14 11.75
Capacity
Cooling1 kBtu/h 47.8 40
Power input W 190
Rated current (Indoor unit) A 1.01
Type AC motor
Fan motor
Brand TD/Welling
Number of rows 2
Midea Large Split Indoor Units Engineering Data Book

Fin type Hydrophilic aluminum


Indoor coil
Dimensions (L×H ×W) mm 2007×252×38.8
Number of circuits 11
Air flow rate m3/h 1800
Sound pressure level2 dB(A) 41/39/37
Net dimensions3 (W×H×D) mm 840×300×840
Main body Packed dimensions (W×H×D) mm 955×330×955
Net/Gross weight kg 30.9/36.3
Net dimensions (W×H×D) mm 950×54.5×950
Panel Packed dimensions (W×H×D) mm 1035×90×1035
Net/Gross weight kg 5/8
Refrigerant type R410A
Type Electronic expansion valve
Throttle
Model BD24FKS(L)
Design pressure (H/L) MPa 4.4/2.6
Pipe Liquid/Gas pipe mm Ф9.53/Ф15.9
connections Drain pipe mm Φ32
Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Sound pressure level is from highest level to lowest level, total 3 levels for each model. Sound pressure level is measured 1.4m below the unit in a semi-
anechoic chamber.
3. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.

2 202003
Large Split Indoor Units
2 Dimensions
2.1 Unit Dimensions
Figure 2.1: Four-way Cassette dimensions (unit: mm)

Φ32Drain pipe outer diameter

Φ75New air
supply orifice

Main body of the unit


10-12mm

Ceiling

Table 2.1: Four-way Cassette dimensions


Dimensions (mm)
Model names
A B

MQ4A-48CRDN1 300 197

MQ4A-38CRDN1 300 197

202003 3
Large Split Indoor Units
3 Unit Placement
3.1 Placement Considerations
Unit placement should take account of the following considerations:
 Units should not be installed in the following locations:
 Where exposure to direct radiation from a high-temperature heat source or to interference from a source of
electromagnetic radiation may occur.
 Where dust or dirt may affect heat exchangers.
 Where exposure to oil or to corrosive or harmful gases, such as acidic or alkaline gases, may occur.
 Where exposure to salinity may occur, such as seaside locations.
 Where highly flammable materials are present.
 Where exposure to oily air may occur, such as a kitchen.
 Where exposure to very high humidity may occur, such as a laundry.
 Units should be installed in positions where:
Midea Large Split Indoor Units Engineering Data Book

 The ceiling is horizontal and is able to bear the unit’s weight.


 There are no obstructions that could impede the airflow into and out of the unit.
 The airflow out of the unit can reach throughout the room.
 There is sufficient space for access during installation, servicing and maintenance.
 The refrigerant piping and drain piping can be easily connected to the refrigerant piping and drain piping systems.
 Short-circuit ventilation (where outlet air returns quickly to a unit’s air inlet) will not occur.

3.2 Space Requirements


Figure 3.1: Four-way Cassette space requirements (unit: mm)
>1000mm

>1000mm
>1000mm

>1000mm

Table 3.1: Four-way Cassette dimensions and space requirements


Dimensions / Requirements (mm)
Model name
A H
MQ4A-48CRDN1 300 ≥330
MQ4A-38CRDN1 300 ≥330

4 202003
Large Split Indoor Units
4 Piping Diagram
Figure 4.1: Four-way Cassette piping diagram

motor

fan
T2B flare nut

gas side
T1
T2
EXV

heat exchanger flare nut

liquid side

Table 4.1: Four-way Cassette Temperature sensors in piping diagram


Legend
T1 Indoor ambient temperature sensor
T2 Indoor heat exchanger mid-point temperature sensor

T2B Indoor heat exchanger outlet temperature sensor

202003 5
Large Split Indoor Units
5 Wiring Diagram
Figure 5.1: MQ4A-48(38)CRDN1
Midea Large Split Indoor Units Engineering Data Book

6 202003
Large Split Indoor Units
Notes for installers and service engineers 

Caution
 All installation, servicing and maintenance must be carried out by competent and suitably qualified, certified and
accredited professionals and in accordance with all applicable legislation.
 Units should be grounded in accordance with all applicable legislation. Metal and other conductive components
should be insulated in accordance with all applicable legislation.
 Power supply wiring should be securely fastened at the power supply terminals – loose power supply wiring
would represent a fire risk.
 After installation, servicing or maintenance, the electric control box cover should be closed. Failing to close the
electric control box cover risks fire or electric shock.

202003 7
Large Split Indoor Units
6 Capacity Tables
6.1 Cooling Capacity Table
Table 6.1: MQ4A-48CRDN1 Four-way Cassette cooling capacity
Indoor air temperature (°C WB/DB)
Outdoor air
Capacity 14/20 16/23 18/26 19/27 20/28 22/30 24/32
temperature
(kW) TC SC TC SC TC SC TC SC TC SC TC SC TC SC
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
12 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
14 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
16 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
18 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
20 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
Midea Large Split Indoor Units Engineering Data Book

21 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
23 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.3 11.0
25 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.2 10.9
27 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.4 10.7 16.0 10.8
29 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.3 10.6 15.9 10.7
14 31 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.2 10.5 15.7 10.6
33 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.1 10.3 15.6 10.5
35 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.0 10.1 15.4 10.2
37 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.5 9.6 14.9 9.9 15.2 10.1
39 9.5 8.0 11.5 8.6 13.4 9.0 13.7 9.1 14.3 9.4 14.7 9.7 14.9 9.9
42 9.5 8.0 11.5 8.6 13.0 8.9 13.3 9.0 13.9 9.3 14.4 9.5 14.6 9.7
44 9.5 8.0 11.5 8.6 12.7 8.8 13.0 8.9 13.5 9.1 14.0 9.4 14.3 9.5
46 9.5 8.0 11.5 8.6 12.4 8.7 12.6 8.8 13.1 9.0 13.6 9.2 13.8 9.3
48 9.5 8.0 11.2 8.5 11.9 8.6 12.2 8.7 12.6 8.8 12.9 9.0 13.2 9.1
50 9.5 8.0 10.8 8.3 11.4 8.4 11.7 8.5 12.0 8.7 12.2 8.8 12.5 8.9
52 9.5 8.0 10.2 8.1 10.7 8.2 11.0 8.2 11.2 8.4 11.4 8.5 11.7 8.7
55 9.2 6.9 9.4 7.2 9.9 7.4 9.9 7.5 10.0 8.0 10.1 8.2 10.2 8.3
Abbreviations:
TC: Total capacity
SC: Sensible capacity

Notes:
1. Shaded cells indicate rating condition.

8 202003
Large Split Indoor Units
Table 6.2: MQ4A-38CRDN1 Four-way Cassette cooling capacity
Indoor air temperature (°C WB/DB)
Outdoor air
Capacity 14/20 16/23 18/26 19/27 20/28 22/30 24/32
temperature
(kW) TC SC TC SC TC SC TC SC TC SC TC SC TC SC
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
12. 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
14 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
16 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
18 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
20 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
21 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
23 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.7 9.2
25 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.6 9.2
27 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 12.9 9.0 13.5 9.1
29 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 12.9 8.9 13.4 9.0
11.75 31 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 12.7 8.8 13.2 8.9
33 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 12.6 8.6 13.1 8.8
35 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.2 8.1 12.6 8.5 12.9 8.6
37 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.2 8.0 12.5 8.3 12.7 8.4
39 8.0 6.7 9.6 7.2 11.2 7.5 11.5 7.6 12.0 7.9 12.3 8.2 12.5 8.3
42 8.0 6.7 9.6 7.2 10.9 7.5 11.1 7.6 11.7 7.8 12.1 8.0 12.3 8.1
44 8.0 6.7 9.6 7.2 10.7 7.4 10.9 7.5 11.3 7.7 11.8 7.9 12.0 8.0
46 8.0 6.7 9.6 7.2 10.4 7.3 10.6 7.4 11.0 7.6 11.4 7.7 11.6 7.8
48 8.0 6.7 9.4 7.1 10.0 7.2 10.2 7.3 10.6 7.4 10.8 7.5 11.1 7.6
50 8.0 6.7 9.1 7.0 9.6 7.1 9.8 7.2 10.1 7.3 10.3 7.4 10.5 7.5
52 8.0 6.7 8.6 6.8 9.0 6.8 9.2 6.9 9.4 7.0 9.5 7.2 9.8 7.3
55 7.8 5.8 7.9 6.0 8.3 6.2 8.3 6.3 8.4 6.7 8.5 6.8 8.5 7.0
Abbreviations:
TC: Total capacity
SC: Sensible capacity

Notes:
1. Shaded cells indicate rating condition.

202003 9
Large Split Indoor Units
7 Electrical Characteristics
Table 7.1: Four-way Cassette electrical characteristics
Power supply Indoor fan motors
Model name Rated motor
Hz Volts Min. volts Max. volts MCA MFA FLA
output (kW)
MQ4A-48CRDN1 50 220-240 198 264 1.01 15 0.065 0.81
MQ4A-38CRDN1 50 220-240 198 264 1.01 15 0.065 0.81
Abbreviations:
MCA: Minimum Circuit Amps
MFA: Maximum Fuse Amps
FLA: Full Load Amps
Midea Large Split Indoor Units Engineering Data Book

10 202003
Large Split Indoor Units
8 Sound Levels
8.1 Overall
Table 8.1: Four-way Cassette sound pressure levels1
Sound pressure levels dB(A)
Model name
H M L
MQ4A-48CRDN1 41 39 37
MQ4A-38CRDN1 41 39 37
Notes:
1. Sound pressure levels are measured 1.4m below the unit in a semi-anechoic chamber. During in-situ operation, sound pressure levels may be higher as
a result of ambient noise.
Figure 8.1: Four-way Cassette sound pressure level measurement

202003 11