Large Split Indoor Units
1 Specifications
MQ4A-48CRDN1
Table 1.1: MQ4A-48(38)CRDN1 specifications
Model MQ4A-48CRDN1 MQ4A-38CRDN1
Power supply 1 phase, 220-240V, 50Hz
kW 14 11.75
Capacity
Cooling1 kBtu/h 47.8 40
Power input W 190
Rated current (Indoor unit) A 1.01
Type AC motor
Fan motor
Brand TD/Welling
Number of rows 2
Midea Large Split Indoor Units Engineering Data Book
2 202003
Large Split Indoor Units
2 Dimensions
2.1 Unit Dimensions
Figure 2.1: Four-way Cassette dimensions (unit: mm)
Φ75New air
supply orifice
Ceiling
202003 3
Large Split Indoor Units
3 Unit Placement
3.1 Placement Considerations
Unit placement should take account of the following considerations:
Units should not be installed in the following locations:
Where exposure to direct radiation from a high-temperature heat source or to interference from a source of
electromagnetic radiation may occur.
Where dust or dirt may affect heat exchangers.
Where exposure to oil or to corrosive or harmful gases, such as acidic or alkaline gases, may occur.
Where exposure to salinity may occur, such as seaside locations.
Where highly flammable materials are present.
Where exposure to oily air may occur, such as a kitchen.
Where exposure to very high humidity may occur, such as a laundry.
Units should be installed in positions where:
Midea Large Split Indoor Units Engineering Data Book
>1000mm
>1000mm
>1000mm
4 202003
Large Split Indoor Units
4 Piping Diagram
Figure 4.1: Four-way Cassette piping diagram
motor
fan
T2B flare nut
gas side
T1
T2
EXV
liquid side
202003 5
Large Split Indoor Units
5 Wiring Diagram
Figure 5.1: MQ4A-48(38)CRDN1
Midea Large Split Indoor Units Engineering Data Book
6 202003
Large Split Indoor Units
Notes for installers and service engineers
Caution
All installation, servicing and maintenance must be carried out by competent and suitably qualified, certified and
accredited professionals and in accordance with all applicable legislation.
Units should be grounded in accordance with all applicable legislation. Metal and other conductive components
should be insulated in accordance with all applicable legislation.
Power supply wiring should be securely fastened at the power supply terminals – loose power supply wiring
would represent a fire risk.
After installation, servicing or maintenance, the electric control box cover should be closed. Failing to close the
electric control box cover risks fire or electric shock.
202003 7
Large Split Indoor Units
6 Capacity Tables
6.1 Cooling Capacity Table
Table 6.1: MQ4A-48CRDN1 Four-way Cassette cooling capacity
Indoor air temperature (°C WB/DB)
Outdoor air
Capacity 14/20 16/23 18/26 19/27 20/28 22/30 24/32
temperature
(kW) TC SC TC SC TC SC TC SC TC SC TC SC TC SC
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
12 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
14 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
16 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
18 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
20 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
Midea Large Split Indoor Units Engineering Data Book
21 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.4 11.0
23 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.3 11.0
25 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.5 10.8 16.2 10.9
27 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.4 10.7 16.0 10.8
29 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.3 10.6 15.9 10.7
14 31 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.2 10.5 15.7 10.6
33 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.1 10.3 15.6 10.5
35 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.6 9.7 15.0 10.1 15.4 10.2
37 9.5 8.0 11.5 8.6 13.4 9.0 14.0 9.2 14.5 9.6 14.9 9.9 15.2 10.1
39 9.5 8.0 11.5 8.6 13.4 9.0 13.7 9.1 14.3 9.4 14.7 9.7 14.9 9.9
42 9.5 8.0 11.5 8.6 13.0 8.9 13.3 9.0 13.9 9.3 14.4 9.5 14.6 9.7
44 9.5 8.0 11.5 8.6 12.7 8.8 13.0 8.9 13.5 9.1 14.0 9.4 14.3 9.5
46 9.5 8.0 11.5 8.6 12.4 8.7 12.6 8.8 13.1 9.0 13.6 9.2 13.8 9.3
48 9.5 8.0 11.2 8.5 11.9 8.6 12.2 8.7 12.6 8.8 12.9 9.0 13.2 9.1
50 9.5 8.0 10.8 8.3 11.4 8.4 11.7 8.5 12.0 8.7 12.2 8.8 12.5 8.9
52 9.5 8.0 10.2 8.1 10.7 8.2 11.0 8.2 11.2 8.4 11.4 8.5 11.7 8.7
55 9.2 6.9 9.4 7.2 9.9 7.4 9.9 7.5 10.0 8.0 10.1 8.2 10.2 8.3
Abbreviations:
TC: Total capacity
SC: Sensible capacity
Notes:
1. Shaded cells indicate rating condition.
8 202003
Large Split Indoor Units
Table 6.2: MQ4A-38CRDN1 Four-way Cassette cooling capacity
Indoor air temperature (°C WB/DB)
Outdoor air
Capacity 14/20 16/23 18/26 19/27 20/28 22/30 24/32
temperature
(kW) TC SC TC SC TC SC TC SC TC SC TC SC TC SC
(°C DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
12. 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
14 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
16 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
18 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
20 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
21 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.8 9.2
23 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.7 9.2
25 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 13.0 9.1 13.6 9.2
27 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 12.9 9.0 13.5 9.1
29 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 12.9 8.9 13.4 9.0
11.75 31 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 12.7 8.8 13.2 8.9
33 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.3 8.1 12.6 8.6 13.1 8.8
35 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.2 8.1 12.6 8.5 12.9 8.6
37 8.0 6.7 9.6 7.2 11.2 7.5 11.7 7.7 12.2 8.0 12.5 8.3 12.7 8.4
39 8.0 6.7 9.6 7.2 11.2 7.5 11.5 7.6 12.0 7.9 12.3 8.2 12.5 8.3
42 8.0 6.7 9.6 7.2 10.9 7.5 11.1 7.6 11.7 7.8 12.1 8.0 12.3 8.1
44 8.0 6.7 9.6 7.2 10.7 7.4 10.9 7.5 11.3 7.7 11.8 7.9 12.0 8.0
46 8.0 6.7 9.6 7.2 10.4 7.3 10.6 7.4 11.0 7.6 11.4 7.7 11.6 7.8
48 8.0 6.7 9.4 7.1 10.0 7.2 10.2 7.3 10.6 7.4 10.8 7.5 11.1 7.6
50 8.0 6.7 9.1 7.0 9.6 7.1 9.8 7.2 10.1 7.3 10.3 7.4 10.5 7.5
52 8.0 6.7 8.6 6.8 9.0 6.8 9.2 6.9 9.4 7.0 9.5 7.2 9.8 7.3
55 7.8 5.8 7.9 6.0 8.3 6.2 8.3 6.3 8.4 6.7 8.5 6.8 8.5 7.0
Abbreviations:
TC: Total capacity
SC: Sensible capacity
Notes:
1. Shaded cells indicate rating condition.
202003 9
Large Split Indoor Units
7 Electrical Characteristics
Table 7.1: Four-way Cassette electrical characteristics
Power supply Indoor fan motors
Model name Rated motor
Hz Volts Min. volts Max. volts MCA MFA FLA
output (kW)
MQ4A-48CRDN1 50 220-240 198 264 1.01 15 0.065 0.81
MQ4A-38CRDN1 50 220-240 198 264 1.01 15 0.065 0.81
Abbreviations:
MCA: Minimum Circuit Amps
MFA: Maximum Fuse Amps
FLA: Full Load Amps
Midea Large Split Indoor Units Engineering Data Book
10 202003
Large Split Indoor Units
8 Sound Levels
8.1 Overall
Table 8.1: Four-way Cassette sound pressure levels1
Sound pressure levels dB(A)
Model name
H M L
MQ4A-48CRDN1 41 39 37
MQ4A-38CRDN1 41 39 37
Notes:
1. Sound pressure levels are measured 1.4m below the unit in a semi-anechoic chamber. During in-situ operation, sound pressure levels may be higher as
a result of ambient noise.
Figure 8.1: Four-way Cassette sound pressure level measurement
202003 11