Professional Documents
Culture Documents
NOTE: METER LOCATION IS FOR REPRESENTATION PURPOSES ONLY. ACTUAL LOCATION WILL VARY PENDING ON SECTION AND BUCKET CONSTRUCTION.
OVERALL EQUIPMENT
RATING
SYSTEM VOLTAGE:
480V
PHASE - WIRE
3P3W 4.4
FREQUENCY
60 Hertz 90
65000
4" WIREWAY
4" WIREWAY
4" WIREWAY
MAIN BUS AMPS: C
72
3200
EPM
AAD
GROUND AMPS: D
Space
12
66
800A
BUS BRACING: E
60
65000
AAF ABF ACF
BUS MATERIAL / PLATING TYPE: F FDRCB 300A FDRCB 300A
Space
12 24 Stationary 24 Stationary
54
COPPER/TIN (STD)
OPEN
48
NEMA 1G PUSH-OFF
[2286]
AAH
PUSH-ON TU-Reset
90
MOUNTING TYPE: H
Space DISCHARGED
SPRING
12
42
Front Only
WIRE CLASS: I
36
I-BD
AAJ ABJ ACJ
CONTROL VOLTAGE: J FDRCB 300A FDRCB 300A
Space
12 24 Stationary 24 Stationary
30
120
CURRENT RATING:
850 AAL
L
Space
12
18
STANDARD:
UL Listed AAM ADM
M FDRCB 35A MAINCB 3200A
6 Stationary 66 Stationary
12
NUMBER OF SECTIONS
4 AAN ABN ACN
N FDRCB 35A FDRCB 300A SPD
6 Stationary 72 24 Stationary 72 24 Stationary 72
6
WIREWAY
O WIREWAY WIREWAY WIREWAY
6 6 6 12
0
WIREWAY
10.66
4.72
20
5.25
5.25
5.25
[762]
3.10
3.10
3.10
15.25
1.22 1.22 1.22
33.56
3.10
1.22
SIDE VIEW
TOP VIEW
EQUAL EQUAL
13[330.2], 20[508]
2.11
& 22[558.8]
SECTION
DEPTHS
2.09 20 20 20 36
[508] [508] [508] [914.4]
2.16
1 2 3 4
AA AB AC AD
ANCHOR
DETAIL
EQUAL EQUAL
2.16
[762]
3.50
3.50
3.50
30
3.10
3.10
25[635] & 30[762]
7.925
33.59
3.10
1.22
2.09
2.16
ANCHOR
DETAIL
20 20 20 36
[508] [508] [508] [914.4]
1 2 3 4
AA AB AC AD
BOTTOM VIEW
PROJECT NAME : DRAWING TITLE: Conduit View PRODUCT NAME: DRAWING NO:
holcim cargadores CREATED BY: Lora, Fernando ITEM NO: 1
ReliaGear LV MCC MARKS:
CUSTOMER:
SOPORTE A LA DATE: 02/22/2024 20:15:38 Motor Control Center QUOTE NO: UXG-00001601
INGENIERIA SAS, CALI REVISION NO. SHEET: 2 of 5
02/22/2024 20:36:31
UNIT CIRCUIT WIRE FUNCTION HEIGHT SIZE HP, KW, FULL RPM SERVICE OVERLOAD OVERLOAD CIRCUIT TRIP FUSES TOTAL CPT INDICATING SWITCH PUSH NOTES
LOC NAME DIAGRAM K=KW LOAD FACTOR HEATER RELAY BREAKER/ FUSE/ BY INTERLOCK VA LIGHTS BUTTON
AMPS SWITCH CLIP NO NC
110-127 V ac / 110-125 V dc Shunt Trip. 1Q + 1SY 250 V ac Auxiliary Contact. Thermal Magnetic Fixed trip unit with LI protection. The load of the unit will support cable range of #10 - 1/0 AWG and (1) cables per phase. Stationary Stab.
AAN BLANK NP FDRCB 6 XT2H125 35A
110-127 V ac / 110-125 V dc Shunt Trip. 1Q + 1SY 250 V ac Auxiliary Contact. Thermal Magnetic Fixed trip unit with LI protection. The load of the unit will support cable range of #10 - 1/0 AWG and (1) cables per phase. Stationary Stab.
ABF BLANK NP FDRCB 24 XT5H400 300A
110-240 V ac 110-250 V dc Shunt Trip. 1Q + 1SY 250 V ac Auxiliary Contact. Electronic Ekip Dip LSIG trip unit with LSIG protection. The load of the unit will support cable range of 2/0 - 500 MCM and (2) cables per phase. Device Trip Unit Long Time target
Fixed mounting. Ekip Dip trip unit and LSIG protection. 4 AUX (4Q) 400V Auxilary Contacts. Std 250V Bell Alarm. 110-120 Vac/dc Shunt Trip and 110-120 Vac/dc Redundant Shunt Trip. Ekip Supply 110-240 VAC/DC Ekip Supply Module.
PROJECT NAME : DRAWING TITLE: Unit Summary PRODUCT NAME: DRAWING NO:
holcim cargadores CREATED BY: Lora, Fernando ITEM NO: 1
ReliaGear LV MCC MARKS:
CUSTOMER:
SOPORTE A LA DATE: 02/22/2024 20:15:38 Motor Control Center QUOTE NO: UXG-00001601
INGENIERIA SAS, CALI REVISION NO. SHEET: 3 of 5
02/22/2024 20:36:31
GENERAL NOTES FOR ENTIRE JOB:
1. MCC Enclosure is furnished per Nema Type 1 Gasketed specifications.
2. MCC Lineup will be provide with 1.5" Main bus.
3. The minimum clearance required between the rear of the MCC enclosure and the nearest wall is 3 inches.
4. Tin-Plated Stabs are furnished with stab units.
5. Hi-Density Pull-Apart Control Terminal Boards will be supplied.
6. All unused stab holes in vertical bus will be plugged.
7. MTW VW1 wire required for all control wire.
8. MTW VW1 wire required for all power wire.
9. Standard Stripped wire connections on all power wire.
10. Standard stripped wire connections on all control wires.
11. Standard power terminal boards will be supplied.
12. Communication wiring will NOT be provided from the factory for any devices in the lineup.
13. Standard blank doors provided for starter units without any pilot lights, selector switches or push buttons selected.
14. MCC Furnished with Black with White Text Unit Nameplates.
15. Main, Vertical, Ground will be furnished with Double Bolt Joints.
16. MCC qualified for Seismic Ratings (non-OSHPD) per publication DET-463 and OSP-0093-10.
17. Each vertical section will be provided with Rear Covers.
18. MCC Furnished with Type 2 SPD ME 65kA per mode / 130kA per phase, 200KAIC. SPD Furnished with Indicating Lights, Alarm, Form C Contacts, Surge Counter & Disconnect Switch.
19. EPM 6010 (PL6010*5A-THD-HI) installed in MCC monitoring the Main incoming.
20. Customer will NOT provide Specifications or Drawings to the Factory.
PROJECT NAME : DRAWING TITLE: Notes Sheet PRODUCT NAME: DRAWING NO:
holcim cargadores CREATED BY: Lora, Fernando ITEM NO: 1
ReliaGear LV MCC MARKS:
CUSTOMER:
SOPORTE A LA DATE: 02/22/2024 20:15:38 Motor Control Center QUOTE NO: UXG-00001601
INGENIERIA SAS, CALI REVISION NO. SHEET: 4 of 5
02/22/2024 20:36:31
E4.2S32
3200A
ADM Location
3200A BUS
FEEDER FEEDER
300A 300A
XT5H400 XT5H400
FEEDER FEEDER
300A 300A
XT5H400 XT5H400
FEEDER
300A
XT5H400
SPD
FEEDER
35A ACN
XT2H125
FEEDER
35A
XT2H125
AA AB AC AD
Section 1 Section 2 Section 3 Section 4
PROJECT NAME : DRAWING TITLE: Line Diagram PRODUCT NAME: DRAWING NO:
holcim cargadores CREATED BY: Lora, Fernando ITEM NO: 1
ReliaGear LV MCC MARKS:
CUSTOMER:
SOPORTE A LA DATE: 02/22/2024 20:15:38 Motor Control Center QUOTE NO: UXG-00001601
INGENIERIA SAS, CALI REVISION NO. SHEET: 5 of 5
02/22/2024 20:36:31