Professional Documents
Culture Documents
ECE-5521-Lecture4 - Symmetrical Components
ECE-5521-Lecture4 - Symmetrical Components
Protective Relaying
Class 4
Symmetrical Components and Fault Analysis
_______________________________________
1J. Lewis Blackburn and Thomas J. Domin, Protective Relaying Principles and Applications, 3rd Ed., CRC Press, 2007
.
2John, A Horak, Derivation of Symmetrical Component Theory and Symmetrical Component Networks, Georgia Tech
_______________________________________
3Fortescue’s paper is available at http://thunderbox.uwaterloo.ca/~ccanizar/papers/classical/Fortescue.pdf
from the University of Waterloo.
4Rowland,Todd and Weisstein, Eric W. "Linear Transformation." From MathWorld—A Wolfram Web
Resource http://mathworld.wolfram.com/LinearTransformation.html
• A balanced system is
easily analyzed because
only one phase needs to
be considered.
• Unbalanced systems
require a full circuit
analysis of all three
phases, neutral and
ground elements.
• Therefore transforming an
unbalanced system into
balanced systems
promises to simplify our
analysis
• Within each set, each of the phasors has the same magnitude and successive
phases have the same phase angle separation between them.
• Let α be the angle between phases in an N-phase system. Then let’s define a
useful operator dubbed the “a” operator. The “a” operator is a unit phasor
(magnitude = 1) with an angle equal to α. Multiplying a phasor by a simply rotates
that phasor by α degrees in the counterclockwise direction.
360
= a =1 Rotation operator
N
• Within each sequence network, the angular displacement of successive phasors is
-α∙n where n is the phase sequence network number and where n = 0, 1, 2, …N-1.
a0,
α a b0,
c0
N=3
Seq #1 System (Pos Seq)
n = 0, 1, 2, …N-1
α = 120 deg c1
a1
b1
Note: All system rotation,
even “negative-sequence”
Seq #2 System (Neg Seq)
phasors, is counterclockwise!
b2
a2
c2
a0,
b0,
c a c3 a3
α c0,
d0
b d3
N=4
Seq #1 System
n = 0, 1, 2, …N-1
α = 90 deg d1
c1 a1
b1
Seq #2 System
b2, a2,
d2 c2
N=5
Seq #1 System Seq #4 System
n = 0, 1, 2, …N-1
α = 72 deg e1 b4
d1 c4
a1 a4
c1 d4
b1 e4
Seq #2 System
c2
e2
a2
b2
d2
a0,
b0,
b3, a3,
c0,
d a d3, c3,
d0,
f3 e3
e0,
f0
c b
N=6
Seq #1 System Seq #4 System
n = 0, 1, 2, …N-1
α = 60 deg e1 f1 b4,
Trivia Factoid: e4
V0 = Va 0 Va = V0 + V1 + V2
V1 = Va1 Vb = V0 + a 2V1 + aV2
a2
V2 = Va 2 Vc = V0 + aV1 + a 2V2 c2
Expressing the transformation in matrix notation makes the transformation format easier
to remember.
Va = V0 + V1 + V2 Va 1 1 1 V0
V = 1 a 2 a V
Vb = V0 + a 2V1 + aV2 b 1 Vabc = A V012
Vc = V0 + aV1 + a 2V2 Vc 1 a a 2 V2
V0 1 1 1 Va
V012 = A−1 Vabc V = 1 1 a a 2 Vb
1 3
V2 1 a 2 a Vc
Naturally, current phasors will have the same transformation form as voltage phasors.
I a = I 0 + I1 + I 2 I a 1 1 1 I 0
I b = I 0 + a 2 I1 + aI 2 I = 1 a 2 a I
b 1 I abc = A I 012
I c = I 0 + aI1 + a I 22
I c 1 a a 2 I 2
I0 1 1 1 I a
I 012 = A I abc
−1
I = 1 1 a a 2 I b
1 3
I 2 1 a 2 a I c
6This example is from Washington State University’s March 2011 Hands-On Relay School
This example is from Washington State University’s March 2011 Hands-On Relay School
ECE-5521 Class 4 Symmetrical Components 14
Symmetrical Component Transformation
Worked Example (Continued)
This example is from Washington State University’s March 2011 Hands-On Relay School
This example is from Washington State University’s March 2011 Hands-On Relay School
• Short circuit kVA or MVA values are used to express the fault duty of
an equivalent source at a point in the power system and can be
converted to equivalent impedances.
– Sometimes you may get driving point a.k.a. Thevenin impedances from
a short circuit program such as CAPE or Aspen. Generally they provide
Z0 and Z1. An equivalent source is nonrotating so Z2 = Z1.
S Base 3S Base
Z1 = Z 2 = Zg = = Z 0 + Z1 + Z 2
S3 ph S1 ph
Z 0 = Z g − Z1 − Z 2
3S Base S Base
= − 2
S
1 ph S3 ph
0.95 Xd 1.45
0.12 Xd’ 0.28 pu on generator base
0.07 Xd’’ 0.17
X2 = Xd’’
3Zn
E External neutral
Z2 impedance.
Z1 Z0
For solidly
REF REF REF grounded neutral
3Zn= 0.
POSITIVE NEGATIVE ZERO
SEQUENCE SEQUENCE SEQUENCE
For ungrounded
neutral 3Zn = ∞
ZS ZM + ZM − Z S + Z M + + Z M − 0 0
Z 012
= A−1 Z M − Z S Z M + A = 0 Z S + a 2 Z M + + aZ M − 0
Z M + Z M − Z S 0 0 Z S + aZ M + + a Z M −
2
• Zero sequence impedance of loads depends on the manner in which they are
connected and grounded as shown on the following page.
Rotating machines
sequence representation
Ia0 = I0
I0
Ib0 = I0 Z 3Zn
3I0
Z N
Zn Z0
Z
Ic0 = I0
Connection REF
Zero Sequence
Arrangement Equivalent Circuit
Z
Z N
Z Z0
REF
Z0
REF
ECE-5521 Class 4 Symmetrical Components 29
Circuit Element Sequence Representations
Series Load Impedances
• Positive and negative sequence impedances of lumped loads are generally
equal. These are shown on a reference phase basis in sequence networks.
ZS ZM ZM Z S + 2Z M 0 0
Z 012
= A−1 Z M ZS Z M A = 0 ZS − ZM 0
Z M ZM Z S 0 0 Z S − Z M
Ia Vaa a’
a
+ Zaa -
+ +
Vbb Va’n
Van b Ib b’
+
+ Zbb -
+
𝑍𝑎𝑎 = 𝑍𝑏𝑏 = 𝑍𝑐𝑐 = 𝑍𝑠
Vbn c Ic +
Vcc
c’ Vb’n 𝑍𝑎𝑏 = 𝑍𝑏𝑐 = 𝑍𝑐𝑎 = 𝑍𝑀
Zcc -
+ +
Vcn Vc’n
- - - - - - Series load sequence
n
representation
• Recall from earlier expressions that for lines and cables, ZL1 = ZL2
while ZL0 > ZL1.
ZS ZM ZM Z S + 2Z M 0 0
Z 012
= A−1 Z M Z S Z M A = 0 ZS − ZM 0
Z M Z M Z S 0 0 Z S − Z M
– The use of overhead shield wires and the type of tower grounding and
counterpoise.
– Ground resistivity.
Impedance matrix, in units of [ohms/mile ] for symmetrical components of the equivalent phase conductor
Rows proceed in the sequence (0, 1, 2), (0, 1, 2), etc.;
Columns proceed in the sequence (0, 2, 1), (0, 2, 1), etc. Z AA = (RA + RG ) + j ( X AA + X AG )
Z00
0 7.385127E-01 Z AB = RG + j ( X AB + X AG )
2.079613E+00
Z10 Z12
1 -2.156088E-02 -4.804473E-02 Z S + 2Z M 0 0
Z 012 = ZS − ZM
-4.577000E-03 2.854904E-02 0 0
Z20 Z22 Z21 0 0 Z S − Z M
2 1.471788E-02 5.428174E-02 4.869572E-02
-1.642828E-02 6.021421E-01 2.742369E-02
ECE-5521 Class 4 Symmetrical Components 33
Circuit Element Sequence Representations
ZL0 for Transmission Line Cables
• Most fault studies will choose a current level at which to study the
cable, usually a level corresponding with the available fault current.
8
40
7
35
30 6
25 5
X0/X1
R0/R1
20
4
15
3
10
5 2
0 1
10 100 1000 10000 100000 10 100 1000 10000 100000
Total Pipe Current - Amperes Total Pipe Current - Amperes
Recall that the impedances derived from measurements (i.e test reports) are those
between pairs of windings with the third winding being an open circuit. Thus we can
relate the values ZPS, ZPT and ZST to effective individual winding impedances ZP, ZS and
ZT as follows:
If the zero sequence is open as for a delta-delta transformer or ungrounded wye winding
clearly there is no neutral current. When there is only a series path there is zero
sequence current flow but not through the neutral.
I0
I0
I0
Consider a similar mapping for wye-wye windings. Notice that when there is only a series path there
is zero sequence current flow through the windings but the net zero sequence current through the
neutrals is zero.
GA
GA
b
At the fault point Vaf = Vbf = Vcf = 0 and Iaf + Ibf + Icf=0,
c
Iaf Ibf Icf
Since Va = Vb = Vc = 0
From the definitions: V0 = V1 = V2 = 0 ZF ZF ZF
REFERENCE EQUATIONS
V0 =
1
(Va + Vb + Vc ) I0 =
1
(I a + I b + I c )
3 3 Va = V0 + V1 + V2 I a = I 0 + I1 + I 2
V1 = (Va + aVb + a 2Vc ) I1 = (I a + aI b + a 2 I c )
1 1
3 Vb = V0 + a 2V1 + aV2 I b = I 0 + a 2 I1 + aI 2
3
V2 = (Va + a 2Vb + aVc ) Vc = V0 + aV1 + a 2V2 I c = I 0 + aI1 + a 2 I 2
I 2 = (I a + a 2 I b + aI c )
1 1
3 3
a Va = Vb = Vc = 0
I a + Ib + Ic = 0
b
c
V
I a1 =
Z1
I1
Z1
| I a |=| I b |=| I c |
Va = Vb = Vc = 0 V POS V1
I2
Z2
V1 0
V0 = V2 = 0 NEG V2
I0 = I2 = 0
I0
Z0
Notice there is a extra
component of V1 and I1
present because of load
current and source impedance. ZERO V0
The above fault record is from Washington State University’s March 2011 Hands-On Relay School
POS V V1 ZF
V
I a1 =
I2
Z2
Z1 + Z f
NEG V2
I0
Z0
ZERO V0
b
At the fault point Vaf = 0 and Ibf = Icf = 0
c
REFERENCE EQUATIONS
V0 =
1
(Va + Vb + Vc ) I0 =
1
(I a + I b + I c )
3 3 Va = V0 + V1 + V2 I a = I 0 + I1 + I 2
V1 = (Va + aVb + a 2Vc ) I1 = (I a + aI b + a 2 I c )
1 1
3 Vb = V0 + a 2V1 + aV2 I b = I 0 + a 2 I1 + aI 2
3
V2 = (Va + a 2Vb + aVc ) Vc = V0 + aV1 + a 2V2 I c = I 0 + aI1 + a 2 I 2
I 2 = (I a + a 2 I b + aI c )
1 1
3 3
Va = 0
Ib = Ic = 0
V
I a1 = I a 2 = I a 0 =
Z1 + Z 2 + Z 0
3V
I a = I a1 + I a 2 + I a 0 = 3I a 0 =
Z1 + Z 2 + Z 0
I1
Z1
POS
Va = 0 V V1
Ib = Ic = 0
I2
Z2
NEG
V0 + V1 + V2 0 V2
I 0 I1 I 2
I0
Z0
Notice there is a extra
component of V1 and I1 ZERO
present because of load
current and source V0
impedance.
The above fault record is from Washington State University’s March 2011 Hands-On Relay School
ECE-5521 Class 4 Symmetrical Components 54
Fault Analysis Using Symmetrical Components
Single-Line-to-Ground (SLG) Fault
Z1
POS V V1
𝑉
𝐼1 = 𝐼2 = 𝐼0 = Z2
I2 ZF
𝑍1 + 𝑍2 + 𝑍3 + 3𝑍𝑓
NEG V2
ZF
I0 ZF
Z0
ZERO V0
REFERENCE EQUATIONS
V0 =
1
(Va + Vb + Vc ) I0 =
1
(I a + I b + I c )
3 3 Va = V0 + V1 + V2 I a = I 0 + I1 + I 2
V1 = (Va + aVb + a 2Vc ) I1 = (I a + aI b + a 2 I c )
1 1
3 Vb = V0 + a 2V1 + aV2 I b = I 0 + a 2 I1 + aI 2
3
V2 = (Va + a 2Vb + aVc ) Vc = V0 + aV1 + a 2V2 I c = I 0 + aI1 + a 2 I 2
I 2 = (I a + a 2 I b + aI c )
1 1
3 3
V
I a1 = − I a 2 =
Z1 + Z 2
Va1 = Va 2
V1 V2 Z0
I0
I0 0
I1 − I 2 ZERO V0
The above fault record is from Washington State University’s March 2011 Hands-On Relay School
ECE-5521 Class 4 Symmetrical Components 58
Fault Analysis Using Symmetrical Components
Line-to-Line (LL) Fault
I1
Z1
POS V V1
ZF
I2
𝑉 Z2
𝐼1 = −𝐼2 =
𝑍1 + 𝑍2 + 𝑍𝑓
NEG V2
I0
Z0
ZERO V0
REFERENCE EQUATIONS
V0 =
1
(Va + Vb + Vc ) I0 =
1
(I a + I b + I c )
3 3 Va = V0 + V1 + V2 I a = I 0 + I1 + I 2
V1 = (Va + aVb + a 2Vc ) I1 = (I a + aI b + a 2 I c )
1 1
3 Vb = V0 + a 2V1 + aV2 I b = I 0 + a 2 I1 + aI 2
3
V2 = (Va + a 2Vb + aVc ) Vc = V0 + aV1 + a 2V2 I c = I 0 + aI1 + a 2 I 2
I 2 = (I a + a 2 I b + aI c )
1 1
3 3
Ia = 0
Vb = Vc = 0
Va1 = Va 2 = Va 0
V
I a1 =
Z Z
Z1 + 2 0
Z2 + Z0
I1
Z1
Ia = 0
V POS V1
Vb = Vc = 0
I2
Z2
V0 V1 V2 NEG V2
I1 − ( I 0 + I 2 )
I0
Z0
Notice there is a extra
component of V1 and
I1 present because of
load current and ZERO V0
source impedance.
The above fault record is from Washington State University’s March 2011 Hands-On Relay School
ECE-5521 Class 4 Symmetrical Components 62
Fault Analysis Using Symmetrical Components
Double Line-to-Ground (DLG) Fault
I1
Z1
POS V V1
I2
Z2
NEG V2
I0
Z0
3Zf
ZERO V0
I1
Z1 ZF
a POS V V1
I2
Z2 ZF
b
NEG V2
c
I0
Z0 ZF
ZF ZF
3ZG
ZERO V0
ZG
I1
Z1
a POS V V1
I2
Z2
b
NEG V2
c
I0
Z0
ZF
ZERO V0 ZF/3
I1
Z1 ZB
a POS V V1
I2
Z2 ZB
b
NEG V2
c
I0
Z0 ZB + 3ZG
ZA ZB ZB
ZERO V0
(ZA – ZB)/3
ZG
I1X I1Y
Z1X Z1Y
X Y
a POS V V1X V1Y V
I2X I2Y
Z2X Z2Y
b
NEG V2X V2Y
c
I0X I0Y
Z0X Z0Y